Form10/00 UK ABWR Document ID Document Number Revision Number : : : GA91-9901-0009-00001 XE-GD-0105 C UK ABWR Generic Design Assessment Fault Studies to Discuss Deterministic Analysis, PSA and Fault Schedule Development Hitachi-GE Nuclear Energy, Ltd. Form10/00 UK ABWR DISCLAIMERS Proprietary Information This document contains proprietary information of Hitachi-GE Nuclear Energy, Ltd. (Hitachi-GE), its suppliers and subcontractors. This document and the information it contains shall not, in whole or in part, be used for any purpose other than for the Generic Design Assessment (GDA) of Hitachi-GE’s UK ABWR. This notice shall be included on any complete or partial reproduction of this document or the information it contains. Copyright No part of this document may be reproduced in any form, without the prior written permission of Hitachi-GE Nuclear Energy Ltd. Copyright (C) 2014 Hitachi-GE Nuclear Energy, Ltd. Reserved. Hitachi-GE Nuclear Energy, Ltd. All Rights Form05/00 UK ABWR NOT PROTECTIVELY MARKED GDA Preliminary Safety Report Revision C Table of Contents 1. Introduction ............................................................................................................................. 1 2. Fault Assessment ..................................................................................................................... 2 2.1 Approach ............................................................................................................................ 2 2.2 Fault Schedule .................................................................................................................... 2 3. Deterministic Safety Analysis ............................................................................................... 27 3.1 Scope of Assessment ........................................................................................................ 27 3.2 Criteria ............................................................................................................................. 27 3.3 Analysis Code .................................................................................................................. 33 3.4 Frequent Design Basis Faults ........................................................................................... 39 3.5 Infrequent Design Basis Faults ........................................................................................ 56 3.6 Beyond Design Basis Faults ............................................................................................ 95 3.7 Conclusions .................................................................................................................... 100 4. Probabilistic Safety Assessment ......................................................................................... 101 4.1 Requirements and Assumptions ..................................................................................... 102 4.2 Internal Event Level 1 PSA ........................................................................................... 105 4.3 Internal Event Level 2 PSA ........................................................................................... 134 4.4 Internal Event Level 3 PSA ........................................................................................... 150 4.5 External Event PSA ....................................................................................................... 151 4.6 Conclusions .................................................................................................................... 153 5. Conclusions .......................................................................................................................... 154 6. Reference .............................................................................................................................. 155 Table of Contents Ver. 0 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C Acronyms Abbreviations and Acronyms ABWR ACWA AESJ AM AOOs ARI APTA ASEP ATWS BSL BSO BT BWR CCI CCF CCFL CCFP CDF CFF CFP COPS CPR CR CRD DB DBA DCD DCH DG DGFO DSA EA ECCS EDG FCI FLSS FP FPC GDA GEXL Description Advanced Boiling Water Reactor AC-Independent Water Addition system Atomic Energy Society of Japan Accident Management Anticipated Operational Occurrences Alternative Rod Insertion system Trip of all Reactor Internal Pumps Accident Accident Sequence Evaluation Program Anticipated Transient Without Scram Basic Safety Level Basic Safety Objective Boiling Transition Boiling Water Reactor Commercially Confidential Information Common Cause Failure Countercurrent Flow Limitation Conditional Containment Failure Probability Core Damage Frequency Containment Failure Frequency Containment Failure Probability Containment Over pressure Protections System Critical Power Ratio Control Rod / Control Room Control Rod Drive Design Basis Design Basis Accident Design Control Document Direct Containment Heating Diesel Generator Diesel Generator Fuel Oil Deterministic Safety Analysis Environment Agency Emergency Core Cooling System Emergency Diesel Generator Fuel Coolant Interaction Flooding system of Specific Safety system Fire Protection system Fuel Pool Cooling and filtering(Clean-up) system Generic Design Assessment GE Critical Quality (Xc)-Boiling Length (LB) correlation Acronyms Ver. 0 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C Acronyms (Contd.) Abbreviations and Acronyms HSE HPCF HVAC IAEA IE IORV JANSI JNES LDF LOCA LPFL LPRM LRF LUHS MCCI MCPR MSIV MSLBA MUWC NISA NPP NRC OLMCPR ONR PCS PCSR PCT PCV PIE POS PSA RCIC RCW RHR RIP RPT RPS RPV RSW RW Description UK Health and Safety Executive High Pressure Core Flooder system Heating, Venting and Air conditioning and Cooling International Atomic Energy Agency Initiating Event Inadvertent Open Relief Valve Japan Nuclear Safety Institute Japan Nuclear Energy Safety Organization Lower Drywell Flooder system Loss Of Coolant Accident Low Pressure Flooder system Local Power Range Monitor Large Release Frequency Loss of Ultimate Heat Sink Molten Core Concrete Interaction Minimum Critical Power Ratio Main Steam Isolation Valve Main Steam Line Break Make-Up Water Condensate system Nuclear and Industrial Safety Agency Nuclear Power Plant Nuclear Regulatory Commission / National Radiation Council Operating Limit MCPR Office for Nuclear Regulation Power Conversion System Pre-Construction Safety Report Peak Cladding Temperature Primary Containment Vessel Postulated Initiating Event Plant Operating State Probabilistic Safety Assessment Reactor Core Isolation Cooling system Reactor Cooling Water system Residual Heat Removal system Reactor Internal Pump Recirculation Pump Trip Reactor Protection System Reactor Pressure Vessel Reactor Sea Water system Rad. Waste Acronyms Ver. 0 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C Acronyms (Contd.) Abbreviations and Acronyms SAP SBO SFP SGTS SLC SLMCPR SORV SPCU SRV SSC T&M TAF TBD URD Description Safety Assessment Principle Station Blackout Spent Fuel Pool Stand-by Gas Treatment System Standby Liquid Control system Safety Limit MCPR Spurious Open of Relief Valves Suppression Pool water Clean-Up system Safety Relief Valve Structures, Systems and Components Test and Maintenance Top of Active Fuel To Be Determined User Requirements Document Acronyms Ver. 0 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C 1. Introduction The safety systems and the safety related systems of UK ABWR plant will be designed such that environmental release of any radioactive material from the plant during all modes of operation is acceptably minimized. To demonstrate the adequacy of the safety design and the suitability and sufficiency of the safety measures, fault assessment will be performed for UK ABWR. This document describes the approach taken in developing the fault assessment which consists of fault schedule, the Deterministic Safety Analysis (DSA) and the Probabilistic Safety Assessment (PSA). Draft initiating events for DSA and draft fault schedule have been developed on the basis of Hitachi-GE practice as the start line of our discussion for Step 1 and 2. The further discussion about draft initiating events and draft fault schedule will be presented in Section 2. The list of initiating events will be developed using a systematic exercise, such as FMEA exercise, and fault schedule will be developed based on Hitachi-GE practice for Japanese ABWR in Step 2. They will be reassessed based on UK ABWR design and involve faults associated with spent fuel and so on in Step 2 and 3, and be completed in Step 3. In Section 3, scope of events assessed, acceptance criteria and analysis code for DSA are described. In addition, examples of DSA performed based on Hitachi-GE practice are presented to explain that the basic design policies of safety systems are adequate and acceptance criteria in Japan are met. DSA for UK ABWR will be performed in Step 2-4. As the first step, DSA results for UK ABWR will be provided in PCSR published in the end of Step 2. Also, a submittal plan of the documents regarding DSA during Step 2 will be discussed. In Section 4, requirement and assumption as high level information on method, some examples and indicative results by PSA are described. Also, development plan of PSAs during GDA is discussed. 1. Introduction Ver. 0 1 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C 2. Fault Assessment 2.1 Approach A systematic approach to plant safety is applied to UK ABWR for fault assessment. Initiating events which lead to abnormal states will be identified systematically, auditably, and comprehensively under all operating modes and configurations including partial power operation and shutdown state, and impact of internal and external hazard. Initiating event that have an initiating frequency higher than about 1×10-3pa is categorized as design basis frequent fault. Also, initiating event that have an initiating frequency lower than about 1×10-3 pa and higher than about 1×10-5 pa is categorized as design basis infrequent fault. For design basis fault, the fault schedule will be developed in order to provide a clear and auditable linking of initiating events, fault sequences and safety measures. DSA will be carried out for design basis faults to confirm the adequacy of the safety design and the suitability and sufficiency of the safety measures against target 4 in HSE SAPs. Also, DSA will be carried out for beyond design basis faults to demonstrate that the safety measures can control severe plant condition such as frequent faults with common mode failure of engineered safety system or additional failures beyond the single failure criterion applied to design basis faults against target 4 in HSE SAPs. Fault sequences of beyond design basis faults will be analysed using realistic and best estimate assumptions. PSA will be carried out to evaluate the overall risk in order to confirm compliance with target 7, 8 and 9 in HSE SAPs and to understand the strengths and weakness of a safety design. 2.2 Fault Schedule 2.2.1 Identification of Initiating Events (1) Initiating Events on Hitachi-GE practice In this subsection, Initiating Events based on Japanese DSA practice by Hitachi-GE are provided for an informational purpose only and final faults studies will consider all potential initiating events consistent with HSE SAPs. In Japanese practice, DSA of events shown below are performed to confirm the adequacy of the safety design. - Anticipated operational occurrences (AOOs), which are chosen, considering initiating event frequency : 10-1 ~ 10-2~3 pa • The events during reactor operation may lead to such conditions as deviate from normal operation. • The events are expected to occur once or several times during the operating life of the nuclear reactor facility by single component failures, single component 2. Fault Assessment Ver. 0 2 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C malfunctions or single misoperations or by disturbances with a similar probability of occurrence. - Design basis accidents (DBAs) , which are chosen, considering initiating event frequency : 10-3 ~ 10-5 pa • The events beyond AOOs. • The events have quite small probabilities of occurrence. • The events may potentially lead to the release of radioactive materials from the nuclear reactor facility. For AOOs, logic tree analysis is performed to identify PIEs which lead to the following abnormal states as shown in Fig.2.2-1 ~ 2.2- 11. The representative initiating events to be analyzed in DSA are selected in terms of qualitative severity. 1) Abnormal change in the reactivity or power distribution in the core 2) Abnormal change in heat generation or removal in the core 3) Abnormal change in reactor coolant pressure or reactor coolant inventory On Hitachi-GE practice, shown below initiating events are identified as representative events of AOOs for ABWR based on the logic tree analysis. 1) Abnormal change in reactivity or power distribution in the core a. Control rod withdrawal error at reactor start-up b. Control rod withdrawal error at power 2) Abnormal change in heat generation or removal in the core a. Partial loss of reactor coolant flow (Trip of three reactor internal pumps) b. Loss of off-site power c. Loss of feedwater heating d. Recirculation flow control failure (Runout of all reactor internal pumps) 3) Abnormal change in reactor coolant pressure or reactor coolant inventory a. Generator load rejection with bypass / with failure of all bypass valves b. Inadvertent MSIV(Main Steam Isolation Valve) closure c. Feedwater controller failure – Maximum demand d. Reactor pressure regulator in the open direction e. Loss of all feedwater flow For DBAs, logic tree analysis is performed to identify PIEs which lead to the following abnormal states as shown in Fig.2.2-12 ~ 2.2-15. The representative initiating events to be analyzed in DSA are selected in terms of qualitative severity. 2. Fault Assessment Ver. 0 3 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C 1) Loss of reactor coolant or considerable change in core cooling 2) Abnormal reactivity insertion or rapid change in reactor power 3) Abnormal release of radioactive materials to the environment 4) Abnormal change in pressure and atmosphere etc. in the primary containment On Hitachi-GE practice, initiating events shown below are identified as representative events of DBAs for ABWR based on the logic tree analysis. 1) Loss of reactor coolant or considerable change in core cooling a. Loss of coolant (LOCA) b. Loss of reactor coolant flow (Trip of all reactor internal pumps) 2) Abnormal reactivity insertion or rapid change in reactor power a. Control rod drop 3) Abnormal release of radioactive materials to the environment a. Offgas treatment system failure b. Main steam line break (MSLBA) c. Fuel assembly drop (Fuel Handling Accident) d. Loss of coolant (LOCA) e. Control rod drop 4) Abnormal change in pressure and atmosphere etc. in the primary containment a. Loss of coolant (LOCA) b. Generation of flammable gas c. Generation of dynamic load 2. Fault Assessment Ver. 0 4 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR [Abnormal State] Abnormal change in the reactivity or power distribution in the core Revision C [Cause of Abnormal State] Change in reactivity Change in power distribution Change in coolant temperature Abnormal change in heat generation or removal in the core Change in coolant flow rate Loss of power Abnormal change in reactor coolant pressure or reactor coolant inventory Change in reactor coolant pressure Change in reactor coolant inventory [Postulated Disturbance] Increase in reactivity Decrease in reactivity Distribution anomaly Decrease in coolant temperature Increase in coolant temperature Decrease in coolant flow rate Increase in coolant flow rate Failure of Power supply system Increase in reactor pressure Decrease in reactor pressure Decrease in reactor coolant inventory Increase in reactor coolant inventory Fig. 2.2-1 Logic Tree Analysis for Identification of Postulated Disturbance for AOOs on Hitachi-GE Practice 2. Fault Assessment Ver. 0 5 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR [Postulated Disturbance] Increase in reactivity in the core Revision C [Event] [Initiating Event] [Evaluation] Increase in reactor recirculation flow Evaluated in abnormal heat generation or removal in the core Decrease in reactor coolant temperature Evaluated in abnormal heat generation or removal in the core Increase in reactor pressure Evaluated in Abnormal change in reactor coolant pressure or inventory Control rod withdraw Control rod withdrawal error at reactor start-up Control rod withdrawal error at reactor start-up (Representative event) Control rod withdrawal error at power Evaluated in abnormal change in power distribution Control rod drop Control rod drop DBA : Reason why not select as a representative event Fig. 2.2-2 Logic Tree Analysis for Identification of Initiating Event for AOOs on Hitachi-GE Practice (1/10) [Postulated Disturbance] [Event] [Initiating Event] Control rod withdrawal Power distribution anomaly [Evaluation] Control rod withdrawal error at reactor start-up Evaluated in increase in reactivity in the core Control rod withdrawal error at power Control rod withdrawal error at power (Representative event) Control rod drop Control rod drop Partial trip of reactor internal pumps DBA Core inlet flow distribution is uniform in case of partial RIPs operation : Reason why not select as a representative event Fig. 2.2-3 Logic Tree Analysis for Identification of Initiating Event for AOOs on Hitachi-GE Practice (2/10) 2. Fault Assessment Ver. 0 6 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR [Postulated Disturbance] Revision C [Event] Decrease in feedwater temperature Decrease in coolant temperature [Initiating Event] [Evaluation] Failure of High pressure drain pump Enveloped in Failure of feedwater heater because of less decreasing in feedwater temperature Failure of feedwater heater Loss of feedwater heating (Representative event ) Increase in feedwater flow Evaluated in Abnormal change in reactor coolant inventory Decrease in reactor pressure Evaluated in Abnormal change in reactor coolant pressure Inadvertent ECCS pump start Inadvertent RCIC pump start Enveloped in Loss of feedwater heating because of less injection flow than that of feed water Inadvertent HPCF pump start Enveloped in Loss of feedwater heating because of less injection flow than that of feed water : Reason why not select as a representative event Fig. 2.2-4 Logic Tree Analysis for Identification of Initiating Event for AOOs on Hitachi-GE Practice (3/10) 2. Fault Assessment Ver. 0 7 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR [Postulated Disturbance] Revision C [Event] Failure of power supply for reactor internal pump Decrease in coolant flow rate Failure of recirculation flow control system Failure of reactor internal pump Failure of reactor internal pump motor Inadvertentstart of recirculation pump trip function [Initiating Event] [Evaluation] Failure of a normal mediumvoltage bus Trip of 3 RIPs Partial loss of reactor coolant flow (Trip of 3 RIPs) (Representative event) Failure of all normal mediumvoltage buses Trip of 10 RIPs Loss of reactor coolant flow (Trip of All RIPs) DBAs Enveloped in loss of all normal medium-voltage buses Failure of several inverters Failure of a MG set Trip of 3 RIPs Same as failure of a normal medium-voltage bus Failure of 2 MG sets Trip of 6 RIPs Enveloped in failure of all normal medium-voltage buses Failure of main controller 10 RIPs decrease with 5%/sec Enveloped in failure of a normal medium-voltage bus Failure of speed controller 1 RIP decrease with 10%/sec Enveloped in failure of a normal medium-voltage bus 1 RIP seizure or shaft break Enveloped in failure of all normal medium-voltage buses Trip of several motors Enveloped in failure of all normal medium-voltage buses DBA DBAs Enveloped in failure of all normal medium-voltage buses Fig.2.2-5 Logic Tree Analysis for Identification of Initiating Event for AOOs on Hitachi-GE Practice (4/10) 2. Fault Assessment Ver. 0 8 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR [Postulated Disturbance] Increase in coolant flow rate Revision C [Event] [Initiating Event] Inadvertent operation of recirculation flow control system [Evaluation] 10 RIPs increase with 5%/sec Recirculation flow control failure (Runout of all reactor internal pumps) (Representative event) Failure of speed 1 RIP increase controller with 10%/sec Enveloped in main controller failure Failure of main controller : Reason why not select as a representative event Fig.2.2-6 Logic Tree Analysis for Identification of Initiating Event for AOOs on Hitachi-GE Practice (5/10) [Postulated Disturbance] [Event] Loss of off-site power Failure of power supply system [Initiating Event] Failure of external grid [Evaluation] Loss of off-site power (Representative event) Failure of a generator main circuit Loss of auxiliary power Failure of a normal medium-voltage bus Success of buses switching Enveloped in loss of off-site power Failure of a bus switching Enveloped in loss of reactor coolant flow in decrease in coolant flow rate DBA Evaluated in decrease in coolant flow rate : Reason why not select as a representative event Fig.2.2-7 Logic Tree Analysis for Identification of Initiating Event for AOOs on Hitachi-GE Practice (6/10) 2. Fault Assessment Ver. 0 9 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR [Postulated Disturbance] Revision C [Event] [Initiating Event] Turbine stop valve closure Enveloped in Generator load rejection Turbine control valve fast closure Generator load rejection (Representative Event) MSIV closure Inadvertent MSIV closure (Representative Event) Reactor pressure regulator failure Turbine control valve closure Enveloped in G enerator load rejection because the valve closure speed is slower t han t hat in case of generator load r ejection and increase in pressure is mitigated by opening bypass valve etc. Decrease in reactor free volume Feedwater controller failure Evaluated in abnormal change in reactor coolant inventory Valve closure Increase in reactor pressure [Evaluation] : Reason why not select as a representative event Fig.2.2-8 Logic Tree Analysis for Identification of Initiating Event for AOOs on Hitachi-GE Practice (7/10) [Postulated Disturbance] [Event] Valve opening Decrease in reactor pressure Reactor pressure regulator failure Break of reactor coolant pressure boundary [Initiating Event] [Evaluation] Inadvertent opening of a safety relief valve Enveloped in reactor pressure regulator failure because turbine control valves are controlled to maintain reactor pressure Inadvertent opening of a turbine control valve Enveloped in reactor pressure regulator failure because other turbine control valves are controlled to maintain reactor pressure Inadvertent opening of a turbine bypass valve Enveloped in reactor pressure regulator failure because turbine control valves are controlled to maintain reactor pressure Maximum demand signal generated Reactor pressure regulator failure in the open direction (Representative event) DBA : Reason why not select as a representative event Fig.2.2-9 Logic Tree Analysis for Identification of Initiating Event for AOOs on Hitachi-GE Practice (8/10) 2. Fault Assessment Ver. 0 10 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR [Postulated Disturbance] Revision C [Event] Decrease in feedwater flow rate Decrease in reactor coolant inventory Valve opening [Initiating Event] [Evaluation] Failure of heater drain pump Enveloped in loss of all feedwater flow All feedwater pumps trip Loss of all feedwater flow (Representative event) Feedwater controller failure Enveloped in loss of all feedwater flow Failure of condensate pumps Enveloped in loss of all feedwater flow Inadvertent opening of a safety relief valve Enveloped in loss of all feedwater flow Break of reactor coolant pressure boundary DBA : Reason why not select as a representative event Fig.2.2-10 Logic Tree Analysis for Identification of Initiating Event for AOOs on Hitachi-GE Practice (9/10) [Postulated Disturbance] [Event] [Initiating Event] Increase in feedwater flow Feedwater controller failure Feedwater controller failure – Maximum demand (Representative event) Inadvertent start of RCIC Enveloped in Feedwater controller failure because of less injection flow rate Inadvertent start of HPFC Enveloped in Feedwater controller failure because of less injection flow rate Increase in reactor coolant inventory Inadvertent start of ECCS [Evaluation] : Reason why not select as a representative event Fig.2.2-11 Logic Tree Analysis for Identification of Initiating Event for AOOs on Hitachi-GE Practice (10/10) 2. Fault Assessment Ver. 0 11 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C [Abnormal State] [Cause of Abnormal State] Change in coolant inventory Loss of reactor coolant or considerable change in core cooling Change in coolant flow rate [Postulated Disturbance] Decrease in Reactor coolant inventory Increase in Reactor coolant inventory Decrease in coolant flow rate Increase in coolant flow rate Increase in reactivity Change in reactivity Abnormal reactivity insertion or rapid change in reactor power Decrease in reactivity Change in power distribution Distribution anomaly Fig.2.2-12 Logic Tree Analysis for Identification of Postulated Disturbance for DBAs on Hitachi-GE Practice 2. Fault Assessment Ver. 0 12 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR [Postulated Disturbance] Revision C [Event] [Initiating Event] Failure of heater drain pump Decrease in feedwater flow Trip of all feedwater pumps Feedwater controller failure Failure of condensate pump Decrease in reactor coolant inventory Valve open Break of reactor coolant pressure boundary Inadvertent opening of a SRV [Evaluation] Enveloped in Loss of all feedwater flow Loss of all feedwater flow (Representative Event) Enveloped in Loss of all feedwater flow Enveloped in Loss of all feedwater flow Enveloped in Loss of all feedwater flow Inadvertent opening of SRVs Enveloped in MSLBA RPV break Very low frequency (IoF) CRD housing break Enveloped in LOCA Vapor phase line break Main steam line break AOOs LOCA -Feedwater line LOCA -HPCF line Liquid phase line break LOCA -LPFL line LOCA -RHR line : Reason why not select as a representative event LOCA -RPV bottom drain line Fig.2.2-13 Logic Tree Analysis for Identification of Initiating Event for DBAs on Hitachi-GE Practice (1/3) 2. Fault Assessment Ver. 0 13 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR [Abnormal State] Revision C [Event] [Initiating Event] Break of reactor coolant pressure boundary Break of Pipe etc. outside primary containment Release from the core MSLBA Fuel cladding not damaged except LOCA Change in coolant flow rate Fuel cladding not damaged Change in reactivity Control rod drop Change in power distribution Control rod drop Fuel damage in fuel handling Fuel assembly drop Gaseous radwaste system failure Pipe or Storage tank etc. failure Offgas treatment system failure Liquid radwaste system failure Pipe or Storage tank etc. failure Enveloped in Offgas treatment system failure because liquid and solid radwaste are harder to release than gaseous one. Abnormal release of radioactive materials to the environment Spent fuel damage : Reason why not select as a representative event LOCA Change in coolant inventory Fuel cladding damage Failure of Radwaste system [Evaluation] Solid radwaste system failure Fig.2.2-14 Logic Tree Analysis for Identification of Initiating Event for DBAs on Hitachi-GE Practice (2/3) [Abnormal State] Abnormal change in pressure and atmosphere etc, in the primary containment [Initiating Event] Break of reactor coolant pressure boundary [Evaluation] Increase in reactor pressure and temperature LOCA Generation of Hydrogen and Oxygen Generation of flammable gas Load in an accident Generation of dynamic load Fig.2.2-15 Logic Tree Analysis for Identification of Initiating Event for DBAs on Hitachi-GE Practice (3/3) 2. Fault Assessment Ver. 0 14 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C (2) Comparison with Initiating Events (IEs) in IAEA Safety Guide Table 2.2-1 and Table 2.2-2 show comparison result between IEs in Hitachi-GE practice and IEs in IAEA Safety Guide (NS-G-1.2). As shown in Table 2.2-1, IEs of AOOs in Hitachi-GE practice are almost same as that in IAEA Safety Guide. And not evaluated IEs are not severe, or low probability, or almost same as other event, or could not to be occurred by actual operating procedure. As shown in Table 2.2-2, IEs of DBAs in Hitachi-GE practice are almost same as that in IAEA Safety Guide. And not evaluated IEs are enveloped in other events. 2. Fault Assessment Ver. 0 15 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C Table 2.2-1 Comparison with Initiating Events (IEs) of AOOs in IAEA Safety Guide Group Increase in reactor heat removal Typical examples of IEs leading to AOOs in IAEA Safety Guide (NS-G-1.2*) Inadvertent opening of steam relief valves IEs in Hitachi-GE practice Not included [ ] Feedwater system malfunctions leading to an increase in the heat removal rate Included Feedwater pump trips Included Not included in AOOs [ Reduction in the steam flow rate for control malfunctions Decrease in reactor heat removal Reduction in the steam flow rate for main steam valve closure Reduction in the steam flow rate for turbine trip/loss of external load Reduction in the steam flow rate for loss of power Reduction in the steam flow rate for loss of condenser vacuum Decrease in reactor coolant system flow rate Reactivity and power distribution anomalies ] Included Included Included Not included [ ] Trip of one main coolant pump Included Inadvertent control rod withdrawal Included Not included [ Wrong positioning of a fuel assembly ] *: NS-G-1.2 is replaced to SSG-2 now, but typical examples of IEs in NS-G-1.2 are more detailed than those in SSG-2. So NS-G-1.2 is used in order to benchmark IEs in Hitachi-GE practice. 2. Fault Assessment Ver. 0 16 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C Table 2.2-2 Comparison with Initiating Events (IEs) of DBAs in IAEA Safety Guide Group Typical examples of PIEs leading to DBAs in IAEA Safety Guide (NS-G-1.2*) PIEs in Hitachi-GE practice Increase in reactor heat removal Steam line break Included Decrease in reactor heat removal Feedwater line break Included Trip of all main coolant pumps Included Decrease in reactor coolant system flow rate Reactivity and power distribution anomalies Increase in reactor coolant inventory Main coolant pump seizure or shaft break Not included [ ] Uncontrolled control rod withdrawal Included Control rod drop Included inadvertent operation of emergency core cooling Not included [ ] *: NS-G-1.2 is replaced to SSG-2 now, but typical examples of IEs in NS-G-1.2 are more detailed than those in SSG-2. So NS-G-1.2 is used in order to benchmark IEs in Hitachi-GE practice. 2. Fault Assessment Ver. 0 17 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C (3) List of Initiating Events (IEs) for UK ABWR As described above, IEs for DSA in Hitachi-GE practice are selected in terms of severity among IEs identified by logic tree analysis. And IEs in Hitachi-GE IE practice are almost same as those in IAEA Safety Guide. As the first step in developing fault schedule for UK ABWR, the list of IEs in Hitachi-GE practice is re-categorized into group of faults in PSA shown in Fig.2.2-8 to keep the consistency of DSA and PSA. Also, as shown in Table 2.2-4, IEs of AOOs in Hitachi-GE practice are translated into frequent faults and IEs of DBAs in Hitachi-GE practice are translated into infrequent faults for UK ABWR, and IEs included in PSA are presented for reference. Draft description of identification of IEs for UK ABWR will be provided early in Step 2. Also, the list of IEs for UK ABWR DSA will be completed in Step 2 based on SAP principles shown in Table 2.2-3 below according to the initiating event frequency and the corresponding potential consequences, that is, offsite/onsite radioactive dose. Table 2.2-3 Faults and Events Category [ This information is removed intentionally ] 2. Fault Assessment Ver. 0 18 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C < Design Basis Faults> Corresponding to grouping of PSA Transient Reactor Core (Internal initiating event) LOCA Others Non-isolation event <Beyond Design Basis Faults> (IE with Multiple Failures) Isolation event RPV Water level decreasing event Malfunction of control rod system or RPS ATWS Loss of off-site power Inadvertent opening of a SRV Loss of all DGs Small Medium Large Other type of LOCA Loss of ECCS Loss of all RHRs Loss of ECCS Radwaste system leak or failure Misplaced fuel bundle accident Fuel handling or cask drop accident SFP accident Fig. 2.2-8 Group of faults in PSA 2. Fault Assessment Ver. 0 19 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C [ Table 2.2-4 List of Initiating Events for UK ABWR DSA and PSA (1/5) No. Section Group 1.1 DSA Frequent Faults Infrequent Faults PSA Generator load rejection with bypass Partial loss of reactor coolant flow 1.2 (Trip of three reactor internal pumps) Loss of reactor coolant flow 1.3 (Trip of all reactor internal pumps) 1.4 Feedwater controller failure – Maximum demand Recirculation flow control failure 1.5 1.6 Initiating Events ] Transient Non-isolation event (Runout of all reactor internal pumps) Loss of feedwater heating 1.7 Turbine trip with bypass 1.8 Reactor pressure regulator failure in the closed direction 1.9 Inadvertent control valve closure 1.10 One reactor internal pump seizure or shaft break 1.11 Inadvertent HPCF pump start 1.12 Inadvertent one MSIV closure 2. Fault Assessment Ver. 0 [ This information is removed intentionally ] 20 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C Table 2.2-4 List of Initiating Events for UK ABWR DSA and PSA (2/5) No. Section Group Initiating Events 2.1 Inadvertent MSIV closure 2.2 Reactor pressure regulator failure in the open direction 2.3 Generator load rejection with failure of all bypass valves Isolation event 2.4 2.5 [ DSA Frequent Faults Infrequent Faults ] PSA Inadvertent partial MSIV closure Inadvertent turbine bypass valve opening Transient [ This information is removed intentionally ] 2.6 Turbine trip with failure of all bypass valves 2.7 Loss of main condenser vacuum 3.1 3.2 3.3 RPV Water level decreasing event Loss of all feedwater flow Trip of one feedwater or condensate pump Feedwater controller failure – Decreasing flow 2. Fault Assessment Ver. 0 21 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C Table 2.2-4 List of Initiating Events for UK ABWR DSA and PSA (3/5) [ ] No. Section Group Initiating Events 4.1 Control rod withdrawal error at reactor start-up 4.2 Control rod withdrawal error at power Malfunction of 4.3 DSA Frequent Faults Infrequent Faults PSA Control rod drop control rod 4.4 4.5 system or RPS Scram due to plant occurrences Transient 4.6 5.1 5.2 Scram due to reactor protection system failure [ This information is removed intentionally ] Scram due to sensor failure of reactor protection system Loss of off-site power Loss of off-site power Loss of auxiliary power Inadvertent 6.1 opening of a Inadvertent opening of a SRV SRV 2. Fault Assessment Ver. 0 22 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C Table 2.2-4 List of Initiating Events for UK ABWR DSA and PSA (4/5) No. Section Group Initiating Events [ DSA Frequent Faults Infrequent Faults ] PSA Small LOCA 7.1 inside primary LOCA –RPV bottom drain line break– containment Medium LOCA 8.1 LOCA –HPCF line break– inside primary 8.2 containment LOCA –LPFL line break– 8.3 Large LOCA LOCA –Feedwater line break– 8.4 inside primary LOCA –Main steam line break– containment LOCA –RHR Outlet line break– 8.5 LOCA LOCA outside primary containment 9.1 9.2 9.3 9.4 [ This information is removed intentionally ] –Main steam line break– Other type of LOCA Interface system LOCA –RHR suction line– Interface system LOCA –HPCF injection line– Interface system LOCA –LPFL injection line– 2. Fault Assessment Ver. 0 23 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C Table 2.2-4 List of Initiating Events for UK ABWR DSA and PSA (5/5) No. Section Group Initiating Events [ DSA Frequent Faults Infrequent Faults ] PSA Offgas treatment system failure 10.1 Radwaste system leak or 10.2 (Gaseous radwaste system leak or failure) Liquid radwaste system leak or failure failure 10.3 11.1 Solid radwaste system leak or failure Others Misplaced fuel Mislocated fuel bundle accident 11.2 bundle accident Misoriented fuel bundle accident 12.1 Fuel handling Fuel assembly drop [ This information is removed intentionally ] or cask drop 12.2 13 accident Cask drop SFP accident TBD 2. Fault Assessment Ver. 0 24 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C 2.2.2 Description of Fault Schedule Fault schedule identifies the protection systems and/or operator actions for each of the initiating events listed as design basis frequent and infrequent faults. For Step1 and 2, fault schedule have been developed based on data of Hitachi-GE practice for Japanese ABWR. Table 2.2-5 shows examples of fault schedule based on Hitachi-GE practice for Japanese ABWR. It is recognized that the fault schedule described here is based on fault groups used in Japan and elsewhere and does not include all contributing initiating events. A systematic exercise, such as FMEA exercise will be undertaken in Step 2 to identify all the contributing initiating events for each fault group. The fault schedule will be reassessed as detail of UK ABWR design is determined and be extended in consideration of all operating modes and configurations including partial power operation and shutdown state, and impact of internal and external hazard in Step 2 and 3, and be completed in Step 3. Draft description of fault schedule and fault sequence will be provided early in Step 2. The fault schedule will also be extended in Steps 2 and 3 to include faults associated with spent fuel handling and storage and with radwaste handling and storage. 2. Fault Assessment Ver. 0 25 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C Table2.2-5 Example of Fault Schedule based on Hitachi-GE practice [ Draft ] Item Freq (pry) Initiating Event 1 Non-isolation event 1.1 Generator load rejection with bypass [ Key Plant Impact (including consequential loss) ] Pressure boundary: Intact Off-site power: Supplied MS line: Not isolated Feedwater & Condensate system: Available Turbine Control Valve Rapid Closure → Reactor Scram → Reduced Pressure & Decrease Temp →Cold shutdown 2 Isolation event 2.1 Inadvertent MSIV closure [ ] [ This information is removed intentionally ] Pressure boundary: Intact Off-site power: Supplied MS line: Isolated Feedwater & Condensate system: Unavailable [ This information is removed intentionally ] [ This information is removed intentionally ] All MSIV closure → Reactor Scram → Reduced Pressure & Decrease Temp → Cold shutdown 3 RPV Water Level Decreasing Event 3.1 Loss of all feedwater flow [ ] Pressure boundary: Intact Off-site power: Supplied MS line: Not isolated Feedwater & Condensate system: Limited (Condensate system only available) Loss of all feedwater flow → Water level decrease → Low water level 3 → Reactor Scram → Reduced Pressure & Decrease Temp →Cold shutdown 5 Loss of off-site power 5.1 Loss of off-site power [ ] Pressure boundary: Intact Off-site power: Not supplied MS line: Not isolated Feedwater & Condensate system: Unavailable Turbine Control Valve Rapid Closure -> Reactor Scram -> Reduced Pressure & Decrease Temp -> Cold shutdown 8 Medium LOCA inside containment 8.1 LOCA –HPCF line break– [ ] [ This information is removed intentionally ] Pressure boundary: Loss of coolant accident Off-site power:Not supplied MS line: Isolated Feedwater & Condensate system: Unavailable [ This information is removed intentionally ] [ This information is removed intentionally ] 2. Fault Assessment Ver. 0 26 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C 3. Deterministic Safety Analysis DSA (Deterministic Safety Analysis) is carried out for design basis faults to confirm the adequacy of the safety design and the suitability and sufficiency of the safety measures against target 4 in HSE SAPs. Also, DSA is carried out for beyond design basis faults to demonstrate that the safety measures can control severe plant condition such as frequent faults with common mode failure of engineered safety systems or additional failures beyond the single failure criterion. In this document, examples of DSA performed based on Hitachi-GE practice are described. DSA for UK ABWR will be performed in Step2-4. It is recognized that it may be necessary to perform transient analyses in response to comments or queries from ONR. 3.1 Scope of Assessment The scope of IEs (Initiating Events) assessed in DSA includes frequent and infrequent design basis faults and beyond design basis faults. As described in Section 2.2.1 (3), IEs assessed in DSA are categorized as frequent and infrequent design basis faults and beyond design basis faults according to SAP principle shown in Table 2.2-3. As the first Step, Table 2.2-4 lists the IEs assessed for UK ABWR and their fault category according to Hitachi-GE practice. Table 2.2-4 will be completed in Step 2 based on SAP principle above. 3.2 Criteria 3.2.1 Acceptance Criteria for DSA in Japan The following acceptance criteria are used for AOOs (anticipated operational occurrences) and DBAs (Design Basis Accidents). These acceptance criteria are determined from “Regulatory Guide for Reviewing Safety Assessment of Light Water Nuclear Power Reactor Facilities (NSCRG: L-SE-I.0)”[1] published by The Nuclear Safety Commission of Japan. 3.2.1.1 Anticipated Operational Occurrences Acceptance criteria for AOOs are used to confirm that the reactor facility is designed such that initiating event of AOOs does not lead damage of the core and that the plant condition after the event allows return to the normal operation in Japan. Acceptance criteria for AOOs are listed below. 1) The minimum critical power ratio (hereinafter called "MCPR") shall be larger than the permissible limit value (safety limit MCPR). 2) Fuel cladding shall not be mechanically damaged. That is, the average plastic strain in the circumferential direction of the fuel cladding shall not exceed 1%. 3) Fuel enthalpy shall not exceed the design limit (defined in “Regulatory guidelines in Reactivity 3. Deterministic Safety Analysis Ver. 0 27 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C Insertion Event Evaluation”[2] published by The Nuclear Safety Commission of Japan) in case of reactivity insertion event. 4) Pressure on the reactor coolant pressure boundary shall be maintained below 110% of the maximum allowable working pressure. Regarding fuel safety limit, an objective for normal operation and AOOs of BWRs is to maintain nucleate boiling and thus avoid a transition to film boiling for preventing the damage of fuel cladding caused by overheating at boiling transition. The critical power ratio (CPR) is the figure of merit used to express a thermal margin to the onset of boiling transition. This is defined as the ratio of the critical power (bundle power at which some point within the bundle experiences onset of boiling transition) to the operating bundle power. The thermal margin is stated in terms of the minimum CPR (MCPR), which corresponds to the most limiting fuel assembly in the core. To assure that safety limit MCPR is not exceeded during the most limiting AOOs, the MCPR should be maintained above the operating limit MCPR which is evaluated by AOOs analysis and prescribed in a technical specification for MCPR monitoring during a steady state plant operation as shown in Fig.3.2-1. MCPR through operating cycle MCPR Expected MCPR 1.0 Operating Margin Operating limit MCPR(OLMCPR) (OLMCPR=SLMCPR + ΔMCPRMAX) Decrease of MCPR during the most limiting AOOs (ΔMCPRMAX) Uncertainties in manufacturing and monitoring the core operating state Safety limit MCPR(SLMCPR) Bundle power = Critical power Fig. 3.2-1 MCPR Limits 3.2.1.2 Design Basis Accidents Acceptance criteria for accidents are used to confirm that the nuclear reactor facility is designed such that initiating event of DBAs does not lead to melting or considerable damage of the core, that any secondary damage which may cause any other abnormal situations will not arise, that the protective barrier against release of radioactive material is adequate to be able to limit the release of radioactive materials to the environment as low as acceptable in Japan. 3. Deterministic Safety Analysis Ver. 0 28 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C Acceptance criteria for DBAs are listed below. 1) The core shall not be damaged considerably, and adequate coolable state of the core shall be maintained. The requirement in criterion (1) saying that adequate coolable state of the core shall be maintained implies that the core shall keep such geometry as allows quantitative, or at least semi-quantitative, assessment of the heat removal from the core, i.e. "coolable geometry". The practical determination of conformance to this criterion shall in general be subject to the following requirements specified in "Regulatory Guide for Evaluating Emergency Core Cooling System Performance of Light Water Power Reactors"[3] published by The Nuclear Safety Commission of Japan. (a) The calculated maximum fuel cladding temperature shall not exceed l200°C. (b) The calculated total oxidation of the fuel cladding shall not exceed 15% of the total cladding thickness before oxidation. 2) Fuel enthalpy shall not exceed the limit value to prevent the generation of mechanical energy (defined in “Regulatory guidelines in Reactivity Insertion Event Evaluation” published by The Nuclear Safety Commission of Japan) in case of reactivity insertion event. 3) Pressure on the reactor coolant pressure boundary shall be maintained below 120% of the maximum allowable working pressure. 4) Pressure on the reactor containment boundary shall be maintained below the maximum allowable working pressure. 5) The radiological risk to the off-site public shall be acceptably low. That is, effective dose for the public shall not exceed 5mSv. 3. Deterministic Safety Analysis Ver. 0 29 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C 3.2.2 Acceptance Criteria for UK ABWR UK ABWR design should comply with target 4 in relation to DSA. HSE SAP (Safety Assessment Principle) defines two types of safety level with different numerical targets. These are BSLs (Basic Safety Levels) and BSOs (Basic Safety Objectives). The BSL must be met as a minimum. The BSOs form benchmarks that reflect modern nuclear safety standards and expectations. • Target To confirm compliance with Target 4 of HSE SAPs, the effective dose received by any person arising from a design basis fault sequence shall not exceed below target. On-site BSL: 20mSv for initiating fault frequencies exceeding 1 × 10-3 pa 200mSv for initiating fault frequencies between 1 × 10-3 and 1 × 10-3 pa 500mSv for initiating fault frequencies less than 1 × 10-4 pa BSO: 0.1mSv Off-site BSL: 1mSv for initiating fault frequencies exceeding 1 × 10-3 pa 10mSv for initiating fault frequencies between 1 × 10-3 and 1 × 10-3 pa 100mSv for initiating fault frequencies less than 1 × 10-4 pa BSO: 0.01mSv 3.2.2.1 Frequent Design Basis Faults For frequent design basis faults in combination with principal safety measure success, basically, the following intermediate targets will be applied. These intermediate targets mean that the integrity of fuel cladding and the reactor coolant pressure boundary are maintained and radioactivity is not released to environment. • Intermediate Targets for frequent design basis faults with principal safety measure success 1) MCPR shall be greater than the safety limit MCPR. 2) Fuel cladding shall not be mechanically damaged. That is, the average plastic strain in the circumferential direction of the fuel cladding shall not exceed 1%. 3) Fuel enthalpy shall not exceed the design limit (defined in “Regulatory guidelines in Reactivity Insertion Event Evaluation” published by The Nuclear Safety Commission of Japan) in case of reactivity insertion event. 3. Deterministic Safety Analysis Ver. 0 30 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C 4) Pressure on the reactor coolant pressure boundary shall be maintained below 110% of the maximum allowable working pressure. However, for some frequent design basis faults with principal safety measure success that MCPR leads to be less than the safety limit MCPR, the following intermediate targets will be applied. These intermediate targets mean that the excess embrittlement of fuel cladding is prevented and the reactor coolant pressure boundary and reactor containment boundary are maintained. [ ] 3.2.2.2 Infrequent Design Basis Faults For infrequent design basis faults, the following intermediate targets will be applied. These intermediate targets mean that excess embrittlement of fuel cladding is prevented and the reactor coolant pressure boundary and reactor containment boundary are maintained. • Intermediate Targets for infrequent design basis faults 1) The calculated maximum fuel cladding temperature shall not exceed l200°C. 2) The calculated total oxidation of the fuel cladding shall not exceed 15% of the total cladding thickness before oxidation. 3) Fuel enthalpy shall not exceed the limit value to prevent the generation of mechanical energy (defined in “Regulatory guidelines in Reactivity Insertion Event Evaluation” published by The Nuclear Safety Commission of Japan) in case of reactivity insertion event. 4) Pressure on the reactor coolant pressure boundary shall be maintained below 120% of the maximum allowable working pressure. 5) Pressure on the reactor containment boundary shall be maintained below the maximum allowable working pressure. 3. Deterministic Safety Analysis Ver. 0 31 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR 3.2.2.3 Revision C Beyond Design Basis Faults For frequent design basis faults in combination with principal safety measure failure, the following intermediate targets will be applied. These intermediate targets indicate that the excess embrittlement of fuel cladding is prevented, and the reactor coolant pressure boundary and reactor containment boundary are maintained. • Intermediate Targets for frequent design basis faults with principal safety measure failure 1) The calculated maximum fuel cladding temperature shall not exceed l200°C. 2) Pressure on the reactor coolant pressure boundary shall be maintained below 120% of the maximum allowable working pressure. 3) Pressure on the reactor containment boundary shall be maintained below the limiting pressure. 4) Temperature on the reactor containment boundary shall be maintained below the limiting temperature. 3.2.2.4 All faults For all faults in UK ABWR, currently there are two acceptance criteria additional to the above under consideration: 1) Once the reactor is shut down, the available SSCs (Structures, Systems, and Components) shall prevent it returning to power. In the case of frequent faults, this means that, if the reactor is shut down by the diverse provision of the reactivity control safety function, that same diverse provision shall maintain sub-criticality as long as required. 2) Once the reactor is brought to a stable state, it shall be possible to bring the reactor to cold shutdown conditions using the available SSCs. In the case of frequent faults, this means that, if the reactor is cooled by the diverse provision of the ECCS function, that same diverse provision or another provision that can be made available on the required timescale shall be able to achieve cold shutdown conditions. 3. Deterministic Safety Analysis Ver. 0 32 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C 3.3 Analysis Code This subsection shows the list of the computer codes to be used for DSA. Table 3.3-1 lists the computer codes used for DSA in Japanese ABWR and the computer codes planned to be used for DSA in UK ABWR. Brief description of the codes used in Japanese ABWR is presented below for reference. Detailed description of the computer codes planned to be used in UK ABWR will be provided in Step 2, including their validation. Table 3.3-1 Computer Codes for DSA NO. 1 2 3 4 5 Computer Code Analysis Item Japanese ABWR Transient LOCA PCV Dose Evaluation Severe Accident UK ABWR REDY ODYN SCAT TASC Three dimensional boiling water Three dimensional boiling water reactor simulation calculation code reactor simulation calculation code ISCOR ISCOR APEX TRACG LAMB LAMB SCAT SCAT SAFER SAFER Containment Pressure Response Pressure Suppression Containment Analysis Code Analytical Code Flammable Gas Density Analysis Flammable Gas Density Analysis Code Code Dose Assessment Calculation Code RADTRAD MAAP MAAP JASMINE JASMINE AUTODYN AUTODYN Note: The codes in item 1~3 are proprietary to GE-Hitachi and the codes in item 4 and 5 are generally used in BWR analysis. Item 5 in the table above relates to Section 3.6.2 of this document. 3.3.1 REDY REDY, the plant dynamic characteristics analysis code, is for analysing the plant stability, “anticipated operational occurrences” and the loss of reactor coolant flow. This code simulates the 3. Deterministic Safety Analysis Ver. 0 33 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C entire plant including the reactor core, reactor pressure vessel (hereinafter referred to as the “pressure vessel”), pressure vessel internals, reactor coolant recirculation system, main steam pipe, turbine system, etc., and models one-point kinetic dynamics including 6 groups of delayed neutrons and reactivity feedbacks, thermal dynamics of the fuel rods, and the thermal hydraulic behaviour of coolant. Once the initial conditions including the reactor outputs, reactor core inlet flow (hereinafter referred to as the “core flow”), reactor, main steam pipe and other data, nuclear data, fuel rod data, various control system data, etc. as major inputs are set, the changes in time of the reactor outputs, reactor pressure, core flow, reactor water level, etc. are obtained as outputs. 3.3.2 SCAT SCAT, the single-channel thermal hydraulic analysis code, is for analysing the thermal margin of fuel in the cases of the “anticipated operational occurrences” and “accidents.” This code models a single channel, which consists of multi nodes in axial one-dimension. With regard to each node, the heat transfer to coolant is calculated by applying the heat equation for the fuel rods, and the thermal hydraulic behaviour of coolant is calculated by applying the law of conservation of mass, momentum and energy for coolant in the channel. Once the core data including the geometrical form of the fuel assemblies, axial power distribution, etc., initial conditions of the fuel assembly outputs, flow at the channel inlet, etc., transient data of the fuel assembly outputs, flow at the channel inlet, etc. as major inputs are set, the changes in time of the critical power ratio (CPR) based on the GEXL correlation formula, coolant flow at each node, quality, etc. are obtained as outputs. 3.3.3 Three dimensional boiling water reactor simulation calculation code The three-dimensional boiling water reactor simulation calculation code is for analysing the reactor core nuclear thermal hydraulic characteristics of a boiling water reactor, and calculates the power distribution and effective multiplication of the entire reactor with a three-dimensional diffusion equation. In addition, based on such power distribution, the thermal evaluation calculation and combustion calculation will be made. This code is used for a wide range of purposes such as calculations for control rod operation plans, burn-up control, reactor shutdown margin, etc. For calculation at the time of output operation, convergence calculation is made so as to produce power distribution with void distribution taken into consideration, due to the generation of void. Once the data representing the reactor core conditions including the geometrical form of reactor core, nuclear constants obtained from the nuclear calculation of unit fuel assemblies, data necessary for the thermal hydraulic calculation, control rod patterns, reactor core heat output, etc. as major inputs are set, reactor core power distribution, void distribution, burn-up distribution, effective 3. Deterministic Safety Analysis Ver. 0 34 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C multiplication ratio, etc. are obtained as outputs. 3.3.4 ISCOR ISCOR, the reactor core thermal hydraulic analysis code, is for analysing the thermal hydraulic characteristics in the reactor core at steady state, and calculates the thermal hydraulic characteristics for each type of fuel assembly in the reactor core and for the entire reactor core. In concrete terms, the distributions of fuel flow to each of fuel assemblies are obtained by iterative calculations by using the designed power distributions, so that the differences between pressures at the inlet and outlet of the fuel assembly will become equal for all the fuel assemblies, and the thermal hydraulic characteristics including the thermal margin, reactor core pressure loss, etc. are calculated. Once the data representing the reactor core conditions including the reactor core heat output, core flow, etc., data related to the power distribution, geometrical form of the fuel assemblies and other data required for the thermal hydraulic calculations as major inputs are set, the critical power ratio, pressure losses, void distributions, etc. are obtained as outputs. 3.3.5 APEX APEX, the reactivity insertion event analysis code, is for analysing the abnormal withdrawal of control rod and falling of control rod(s) at the time of reactor startup. This code assumes a thermal phenomenon of heat insulation, expresses the transients in average reactor core power in a dynamic characteristic equation by one-point kinetics, and expresses the special distribution of power at the core in a two-dimension (R-Z) diffusion equation. It is assumed that the rise of enthalpy at each part of the reactor core is in proportion to the power distribution, and that during the time when the average enthalpy at the core rises to a certain extent (the enthalpy step), the power distribution remains at a constant level. For inserted reactivity, the control rod value, scram reactivity and Doppler reactivity are considered, and this Doppler reactivity is obtained in consideration of the power distribution obtained by the two-dimensional diffusion calculation. Once nuclear data including the geometrical form of the reactor core, various neutrons’ cross sectional areas, diffusion coefficient, Doppler coefficient, reactor core dynamic characteristic parameter, etc. as major inputs are set, the changes in time of the neutron flux distribution, enthalpy distribution and average reactor core power are obtained as outputs. 3.3.6 LAMB LAMB, the short-term thermal hydraulic transient analysis code, is for analysing the short-term thermal hydraulic transients in the reactor, and can treat rupture accidents of various primary-system piping connected to the pressure vessel. By dividing the pressure vessel and reactor coolant 3. Deterministic Safety Analysis Ver. 0 35 NOT PROTECTIVELY MARKED Form05/00 UK ABWR NOT PROTECTIVELY MARKED GDA Preliminary Safety Report Revision C recirculation system into seven nodes and solving an equation based on the law of conservation of mass, momentum and energy, this code calculates changes in time in the mass, pressure and enthalpy of coolant in each node, coolant flows between the nodes during the time span from the steady state to several tens of seconds after the occurrence of the accident. For change in the reactor core flow, responses in the flow caused by a coast down of the reactor coolant recirculation pump (hereinafter referred to as the “recirculation pump”) from immediately after the rupture can be calculated. Once the initial conditions including the reactor power, reactor core flow, etc., geometrical form and various hydraulic quantities of the reactor, fuel assembly- and reactor core-related data, plant transient characteristic parameters, recirculation pump characteristics, position and area of the assumed rupture, etc. as major inputs are set, reactor pressure used for analysing the critical power transient of the fuel rod under a blow-down state, change in time in reactor core flow and reactor core inlet enthalpy, flow of bleed from rupture opening, etc. are obtained as outputs. 3.3.7 SAFER SAFER, the long-term thermal hydraulic transient analysis code, is for analysing the long-term thermal hydraulic transient in the reactor, and can treat rupture accidents of various primary-system piping connected to the pressure vessel and loss of reactor coolant flow. This code, with the interior of the reactor divided into nine nodes, calculates changes in the reactor pressure and water level of each node. In addition, by inputting the performance characteristics of various emergency core cooling systems (hereinafter referred to as the “ECCS”), this Code can evaluate the performance of the systems. In evaluating the in-core coolant quantity, the phenomenon that coolant falls to the plenum at the bottom of the core caused by the gas-liquid countercurrent flow limitation phenomenon (hereinafter referred to as the “CCFL”) at the upper tie plate, core inlet orifice, etc. and the localization of subcool area at the upper part of the core (CCFL breakdown) can be considered. In addition, this code performs temperature calculations for fuel pellets, fuel cladding and channel box etc. with regard to the average-power fuel assemblies and high-power fuel assemblies. In performing the temperature calculation for fuel cladding, the heat transfer coefficient reflecting the cooling state of the tube, radiation between the fuel rods, and radiation of the fuel rods and channel box can be considered. Also, the chemical reaction of the fuel cladding and cooling water or steam (hereinafter referred to as the “zirconium-water reaction”) is calculated by using the Baker-Just’s formula to obtain the oxidized quantity of the surface. Further, by calculating the pressure inside the fuel rods, the existence of any bulge and/or rupture in the fuel cladding is evaluated. In case that rupture has occurred, zirconium-water reaction occurring inside the fuel cladding is also considered. Once the initial conditions including the reactor power, reactor pressure, etc., the geometrical form and various hydraulic quantities of the reactor, data related to the fuel assemblies and reactor core, 3. Deterministic Safety Analysis Ver. 0 36 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C plant transient characteristic parameters, characteristics of ECCS, position and size of area of the assumed rupture, etc. as major inputs are set, the reactor pressure, reactor water level, the highest fuel cladding temperature, oxidized quantity of fuel cladding, etc. are obtained as outputs. 3.3.8 Short-term containment pressure response analysis code The short-term containment pressure response analysis code is for analysing changes in the pressure and temperature inside the containment during the period of a coolant blowdown immediately after an LOCA. By dividing the containment into two nodes of drywell and suppression chamber and resolving an equation based on the law of conservation of mass and energy, dynamic equation and state equation, this code calculates the pressure and temperature inside the containment. Conservatively, the exchange of heat with the instrumentation inside the containment is not considered. Once the initial conditions including the pressure, temperature, humidity at each part inside the containment, free space area, flow-path area and flow-path resistance, and mass flow and energy discharge quantity from the primary cooling system as major inputs are set, changes in time in the pressure and temperature inside the containment are obtained as outputs. 3.3.9 Long-term containment pressure response analysis code The long-term containment pressure response analysis code is for analysing changes in the pressure and temperature inside the containment during a long period when the reactor containment spray cooling system is in operation after the period of a coolant blowdown after an LOCA. By dividing the containment into two nodes of drywell and suppression chamber and resolving an equation based on the law of conservation of mass and energy, dynamic equation and state equation, this code calculates the pressure and temperature inside the containment. Also, the ECCS model, containment spray model and heat exchanger model are incorporated in this code. Once the ECCS flow, containment spray flow, heat exchanger model capacity, seawater temperature, etc. in addition to the initial conditions including the pressure, temperature, humidity at each part inside the containment, free space area, flow-path area and flow-path resistance, and mass flow and energy discharge quantity from the primary cooling system as major inputs are set, changes in time in the pressure and temperature inside the containment are obtained as outputs. 3.3.10 Flammable gas concentration analysis code The flammable gas concentration analysis code is for analysing the density of flammable gases at each part inside the containment after an LOCA. By dividing the containment into two nodes of drywell and suppression chamber, this code calculates changes in concentration of oxygen and hydrogen for each node by the mass balance formula. The code determines gas movement between 3. Deterministic Safety Analysis Ver. 0 37 NOT PROTECTIVELY MARKED Form05/00 UK ABWR NOT PROTECTIVELY MARKED GDA Preliminary Safety Report Revision C nodes from the pressure balance formula. As the source of hydrogen and oxygen, zirconium-water reaction (for hydrogen) and radiolysis of water (for oxygen) are considered. Also, a model of flammable gas concentration controlling system is incorporated in this code. Once the zirconium-water reaction rate, water radiolysis rate, flammable gas concentration control system capacity, the initial conditions including the pressure, temperature, humidity, etc. at each part inside the containment, free space cubage, flow-path area and flow-path resistance as major inputs are set, the change in time in the hydrogen and oxygen density are obtained as outputs. 3.3.11 MAAP MAAP, “Modular Accident Analysis Program” developed by EPRI, is a severe accident code that simulates both thermal-hydraulic characteristics and radioactive-material behaviour in a nuclear plant such as core damage, pressure vessel failure, containment failure, and environmental release of radioactive material. After core damage occurs in the simulation, the pressure vessel and containment are divided into three segments: primary, drywell, and wetwell, and the events to sequentially occur during a sever accident are modelled such as reactor heat-up, oxidation of cladding tube, core damage, behaviour of molten core (transfer, cooling, hydrogen and vapour generation, interaction with concrete), containment overpressure and over-temperature, and behaviour of radioactive material (release, transfer, and deposition). Because the water injection, cooling, and control systems are modelled, the MAAP is capable of plant analysis during a severe accident, such as automatic reactor trip and system response to personnel operation. Once the initial conditions including the reactor power, reactor pressure, containment pressure and temperature, etc., the geometrical form and various hydraulic quantities of the reactor, data related to the fuel assemblies and reactor core, containment free-volume, flow-path area and flow-path resistance, performance of water-injection and cooling systems, position and size of area of the assumed rupture, etc. as major inputs are set, the reactor pressure, reactor water level, fuel temperature, molten core temperature, containment pressure/temperature, quantity of eroded concrete, radioactive-material distribution in the containment etc. are obtained as outputs. 3. Deterministic Safety Analysis Ver. 0 38 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C 3.4 Frequent Design Basis Faults DSA for UK ABWR will be performed in Steps 2 and 3. Therefore, this section shows example of analysis results for frequent design basis faults which have been performed base on Hitachi-GE practice. These examples explain the sequence and progress of each fault based on the analysis results. It will explain that the basic design policies of safety systems and safety related systems on ABWR are adequate in order to meet acceptance criteria in Japan. 3.4.1 Evaluated Events Regarding abnormal events, if these events occur and if nuclear facilities are left uncontrolled, they may possibly cause excessive damages of the fuel and of the reactor coolant pressure boundary, the typical events are selected from the viewpoint of confirming the design validity of components, systems and equipments of safety protection systems, reactor shut down systems and so on. In analysing abnormal operational transients, we will study them by dividing them into the following main items: In cases where two or more similar abnormal transients are present, the analysis results will be given for the severest event selected as a typical example. (1) Abnormal changes of reactivity or power distribution inside the core a. Control-rod withdrawal during startup b. Control-rod withdrawal during power operation (2) Abnormal changes of heat generation or removal inside the core a. Loss of partial recirculation flow b. Loss of offsite power c. Loss of feedwater heating d. Malfunctioning of Recirculation Flow Control System (3) Abnormal changes of reactor coolant pressure or of inventory of coolant kept in the reactor a. Loss of load b. Inadvertent MSIV closure c. Failure of Feedwater Control System d. Failure of pressure control devices e. Loss of all feedwater flow 3.4.2 Analysis conditions The main conditions used in analysis are given below. (1) Unless explicitly stated otherwise, a reactor thermal power of 4,005 MW (approx. 102 % of the rated power), a core inlet flow of 47.0 x 103 t/h (90% of the rated flow), a turbine main steam flow of 7.82 x 103 t/h, a reactor pressure of 7.17 MPa[gage], and a reactor feedwater 3. Deterministic Safety Analysis Ver. 0 39 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C temperature of 217 ℃ are assumed as the reactor initial conditions. The MCPR is assumed as follows. 9×9 fuel (type A): 1.22 The maximum linear heat generation rate is assumed to be 44.0 kW/m throughout all the core states. (2) Unless explicitly stated otherwise, the recirculation flow control system is assumed to be in the automatic operation mode. However, the manual operation mode is assumed if the results for the manual operation mode are significantly severer. (3) Unless explicitly stated otherwise, any single failure of safety systems which are required to be actuated are assumed as single failure of the safety protection systems. 3.4.3 Analysis results In this section, the analysis results of some transients chosen from the listed events in Section 3.4.1 are given below. (1) Loss of partial recirculation flow (2) Loss of feedwater heating (3) Loss of load (generator load rejection) (4) Inadvertent MSIV closure (5) Loss of all feedwater flow The analysis results of ‘Loss of partial recirculation flow’ and ‘Loss of feedwater heating’ chosen from the ‘Abnormal changes of heat generation or removal inside the core’ are given below. (1) Loss of partial recirculation flow ‘Loss of partial recirculation flow’ is chosen from Fig.2.2-5 in the Section 2.2.1(1), the plant phenomenon is analyzed based on the event sequence shown in Fig.3.4-1. The analytical result is shown in Fig.3.4-2. When three recirculation pumps are tripped, the core flow will decrease rapidly, and the voids will increase quickly. Because of the increased voids, the reactor water level will rise, but will not result in turbine trip by high reactor water level (Level 8), therefore, not leading to reactor scram. If three recirculation pumps are tripped, the flow path resistance of the pumps on the normal side will decrease, and the flow will increase to approx. 141 %. The flow of the tripped pumps will reverse in approx. 0.8s, and the core flow will become approx. 85 % of the rating. Although the neutron flux will increase to approx. 106% of the rated value with an increased value in the normal side pump flow, the surface heat flux will not exceed the initial value. Against initial MCPR 1.22, the maximum value of ΔMCPR will be 0.05 and MCPR during the transient is 3. Deterministic Safety Analysis Ver. 0 40 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C maintained to a value of 1.17 or more. The dome pressure rises to approx. 7.18MPa[gage] slightly beyond the initial value. The event is converged as shown in analysis results. After the transient, the reactor can be operated by 7 recirculation pumps. If necessary, reactor condition can be transferred to cold shutdown by decreasing pressure and temperature of reactor following the normal shut down operation. The acceptance criteria for this phenomenon are as shown in 1), 2) and 4) in “3.2.1.1". Above-mentioned, the minimum/maximum values of MCPR and surface heat flux are satisfied the each acceptance criteria. The maximum reactor dome pressure value is smaller than that one gotten from ‘Loss of load’, so the maximum value of the pressure at reactor coolant pressure boundary is satisfied the acceptance criteria. (2) Loss of feedwater heating ‘Loss of feedwater heating’ is chosen from Fig.2.2-4 in Section 2.2.1(1), the plant phenomenon is analyzed based on the event sequence shown in Fig.3.4-3. It is supposed that the operating control mode of the Recirculation flow control system is manual for the severe analysis result. The analysis result is shown in Fig.3.4-4. It is supposed that the feedwater temperature will drop by 55 °C, because the one feedwater heater loses its heating ability. As a result of loss of feedwater heating, the core inlet subcooling increases, and the reactor power rises. The neutron flux increases to approx. 119 % of the rated value because of the increase of the inlet subcooling. The surface heat flux also increases to approx. 118 % of the rated value, the high neutron flux (corresponding to heat flux) scram signal is output, and reactor scram occurs in approx. 91 seconds. Against initial MCPR 1.22, for the 9×9 fuel (type A), the maximum value of the ΔMCPR is 0.15 and MCPR during the transient is maintained to a value of 1.07 or more. The event is converged as shown in analysis results. Afterwards, reactor condition can be transferred to cold shutdown by decreasing pressure and temperature of reactor following the scram (when MSIVs are opened) shut down operation. The acceptance criteria for this phenomenon are as shown in 1), 2) and 4) in “3.2.1.1". Above-mentioned, the minimum/maximum values of MCPR and surface heat flux are satisfied the each acceptance criteria. The maximum reactor dome pressure value is smaller than that one gotten from ‘Loss of load’, so the maximum value of the pressure at reactor coolant pressure boundary is satisfied the acceptance criteria. The analysis results of ‘Loss of load’, ’Inadvertent MSIV closure’ and ‘Loss of all feedwater flow’ chosen from the ‘Abnormal changes of reactor coolant pressure or of inventory of coolant kept in the reactor’ are given below. 3. Deterministic Safety Analysis Ver. 0 41 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C (3) Loss of load ‘Loss of load (specifically ‘Generator load rejection’)’ is chosen from Fig.2.2-8 in Section 2.2.1(1), the plant phenomenon is analyzed based on the event sequence shown in Fig.3.4-5. There is very small probability that turbine bypass valves are not activated when generator load rejection occurs. However, it is assumed here that the turbine bypass valves are not activated in order to have severer transients. So, the analysis result without turbine bypass is shown in Fig.3.4-6. When generator load rejection occurs, rapid closure of the steam control valves causes reactor scram and tripping of 4 of 10 recirculation pumps. The reactor pressure rises because of interruption of the main steam, and a positive reactivity is injected into the core because of the decrease of the voids. However, the decreased speed of voids is mitigated by tripping of the recirculation pumps, and a negative reactivity is injected by the scram. Since it is assumed that the turbine bypass valves are not activated, the transient will be severer than in cases where the turbine bypass valves are activated. However, the increase of the neutron flux will be suppressed to approx. 138 % of the rated value. The surface heat flux will not exceed its initial value. Against initial MCPR 1.22, the maximum value of ΔMCPR is 0.15 and MCPR during the transient is maintained to a value of 1.07 or more for the 9x9 fuel (type A). Since the turbine bypass valves are not activated, the reactor pressure will rise, but it will be suppressed to approx. 8.32MPa[gage] (pressure at reactor coolant pressure boundary is approx. 8.46MPa[gage]) by the activation of the safety/relief valves. The reactor pressure is controlled by safety/relief valves. The event is converged as shown in analysis results. Afterwards, reactor condition can be transferred to cold shutdown by decreasing pressure and temperature of reactor following the scram (when MSIVs are closed) shut down operation. The acceptance criteria for this phenomenon are as shown in 1), 2) and 4) in “3.2.1.1". Above-mentioned, the minimum/maximum values of MCPR, surface heat flux and pressure at reactor coolant pressure boundary are satisfied the each acceptance criteria. (4) Inadvertent MSIV closure ‘Inadvertent MSIV closure’ is chosen from Fig.2.2-8 in Section 2.2.1(1), the plant phenomenon is analyzed based on the event sequence shown in Fig.3.4-7. The analysis result is shown in Fig.3.4-8. If the main steam isolation valves close 10 % from the fully open position in approx. 0.3 second, reactor scrams by the main steam isolation valve closure scram signal from the position detection switches of the main steam isolation valves. When the main steam is interrupted, the reactor pressure will rise, the voids will be decreased, and a positive reactivity will be inserted into the core. However, the neutron flux and the surface heat flux will not exceed their initial values because of the effects of the negative reactivity due to the main 3. Deterministic Safety Analysis Ver. 0 42 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C steam isolation valve closure scram. The MCPR also will not drop below its initial value. The reactor pressure will rise as the main steam isolation valves are closed. However, the safety/relief valves will be activated approx. 2.4 seconds later, and the reactor pressure will be suppressed to approx. 8.08MPa[gage]. When the main steam isolation valves are closed, the speeds of the turbine driven feedwater pumps will drop, and the reactor water level will drop along with this. Since steam will still be generated by the decay heat after the reactor scram, the reactor pressure will rise, and the safety/relief valves will be opened intermittently. The reactor water level will drop gradually. Actually, the reactor core isolation cooling system will start up at a low reactor water level (Level 2) to prevent excessive dropping of the water level. The reactor pressure is controlled by safety/relief valves. The event is converged as shown in analysis results. Afterwards, reactor condition can be transferred to cold shutdown condition by decreasing pressure and temperature of reactor following the scram (when MSIVs are closed) shut down operation. The acceptance criteria for this phenomenon are as shown in 1), 2) and 4) in “3.2.1.1". Above-mentioned, the minimum/maximum values of MCPR and surface heat flux are satisfied the each acceptance criteria. The maximum reactor dome pressure value is smaller than that one gotten from ‘Loss of load’, so the maximum value of the pressure at reactor coolant pressure boundary is satisfied the acceptance criteria. (5) Loss of all feedwater flow ‘Loss of all feedwater flow’ is chosen from Fig.2.2-10 in Section 2.2.1(1), the plant phenomenon is analyzed based on the event sequence shown in Fig.3.4-9. The analysis result is shown in Fig.3.4-10. The reactor water level drops rapidly because of the discrepancy between the incoming flow of feedwater into the pressure vessel and the outgoing flow of steam due to the loss of feedwater flow. Therefore, reactor scram occurs in approx. 7.0 seconds in accordance with low reactor water level scram (Level 3), and 4 of 10 recirculation pumps are tripped. Approx. 15 seconds later, the remaining 6 recirculation pumps are tripped on account of low reactor water level (Level 2). The transient will be a leisurely one because the reactor is already scrammed by this time, and the power has decreased sufficiently. The neutron flux is kept down to approx. 105 % of the rated value, and the surface heat flux and reactor pressure also does not exceed its initial value. The MCPR will not drop below its initial value. This transient has the severest water level drop of all the transients analyzed in this section. However, even in this case, it is actually quite possible to recover the reactor water level with an adequate margin with respect to Level 1.5, since the reactor core isolation cooling system starts up at a low reactor water level (Level 2) to prevent the reactor water level from dropping. The event is 3. Deterministic Safety Analysis Ver. 0 43 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C converged as shown in the analysis result. Afterwards, reactor condition can be transferred to cold shutdown condition by decreasing pressure and temperature of reactor following the scram (when MSIVs are opened) shut down operation. The acceptance criteria for this phenomenon are as shown in 1), 2) and 4) in “3.2.1.1". Above-mentioned, the minimum/maximum values of MCPR and surface heat flux are satisfied the each acceptance criteria. The maximum reactor dome pressure value is smaller than that one gotten from ‘Loss of load’, so the maximum value of the pressure at reactor coolant pressure boundary is satisfied the acceptance criteria. 3.4.4 Review of conformance to acceptance criteria In this section, some examples of frequent design basis faults are presented. According to these analysis results, acceptance criteria for AOOs in Japan in Section 3.2.1 are met by safety systems on Japanese ABWR. The adjustments for each criterion are shown below. That is, the reactors are operated with the MCPR maintained at 1.22 or higher for the 9×9 fuel (type A). Thus, the MCPR will not drop below the permissible limit value of 1.07 (safety limit MCPR) even in the event of loss of feedwater heating, which is the severest transient. Even in the event of abnormal control rod withdrawal during power operation, when there is the severest surface heat flux of the fuel, the surface heat flux is approx. 120 % of the rated value, which is below the surface heat flux 170 % corresponding to a 1% plastic strain of the fuel cladding. In the event of abnormal control rod withdrawal at startup, the reactivity injected does not exceed approx. $0.72, and the rise of the reactor power is also slow. Therefore, a reactivity insertion event does not result, and there is no occurrence of fuel failure involving rapid adiabatic increases of the fuel enthalpy. The reactor pressure reaches its maximum in the event of loss of load (generator load rejection with turbine bypass valves not activated). Even in this case, the maximum pressure is suppressed to approx. 8.32MPa[gage] (pressure at reactor coolant pressure boundary is approx. 8.46MPa[gage]). These values are considerably lower than the maximum operating pressure at reactor coolant pressure boundary × 1.1 (9.48MPa[gage]). 3.4.5 Conclusion As indicated in some examples of analysis results for frequent design basis faults based on Hitachi-GE practice in Japan, ABWR can control its infrequent faults stably and ensure the integrity of the fuel, the reactor coolant pressure boundary with the self regulation capability of the boiling water reactor and the initiation of safety systems. Also, they meet acceptance criteria for AOOs in Japan. DSA for frequent design basis faults on UK ABWR will be performed to confirm the adequacy of 3. Deterministic Safety Analysis Ver. 0 44 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C the safety design and the suitability and sufficiency of the safety measures against target 4 in HSE SAPs in Step2. 3.4.6 Effect for Analysis Results by Deviations on Major Plant Specifications Table 3.4-1 shows deviations on major plant specifications between Japanese, US, and UK ABWR related to frequent design basis fault analysis. 3. Deterministic Safety Analysis Ver. 0 45 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C Sequence of Loss of partial recirculation flow Fig.3.4-1 Sequence of Loss of partial recirculation flow Fig.3.4-2 Analysis Result of Loss of partial recirculation flow [2] 3. Deterministic Safety Analysis Ver. 0 46 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C Sequence of Loss of feedwater heating Feedwater heater loss ↓ Feedwater temperature decrease (by less than 55℃) ↓ Core inlet subcooling increase ↓ Core void decrease ↓ Neutron flux increase ↓ Feedwater Heater Loss Scram Fig.3.4-3 Sequence of Loss of feedwater heating Neutron flux increase due to core inlet subcooling increase Scram Core inlet subcooling increase Time(sec) 1. 2. 3. 4. 6. Neutron flux (%) Fuel average surface heat flux (%) Core inlet flow rate (%) Feedwater flow rate (%) ⊿MCPR Time(sec) 1. 2. 3. 4. Reactor water level change from initial (x5cm) Reactor pressure change from initial (x0.01MPa) Core inlet subcooling (x5kJ/kg) Turbine steam flow rate (%) Fig.3.4-4 Analysis Result of Loss of feedwater heating [2] 3. Deterministic Safety Analysis Ver. 0 47 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C Sequence of Generator Load Rejection without Bypass (*)Assume the turbine bypass valve are not activated Load Rejection (*) Relief valve Neutron Flux close Decrease Fig.3.4-5 Sequence of Generator Load Rejection without Bypass Pressure increase due to closure of control valve Neutron flux spike due to void feedback Scram Relief valve open due to pressure increasing Main steam flow decrease due to closure of control valve and recover due to relief valve Recirculation flow decrease due to 4 of 10 RIPs trip MCPR decrease due to flux spike 1. 2. 3. 4. 6. Time(sec) Time(sec) Neutron flux (%) Fuel average surface heat flux (%) Core inlet flow rate (%) Main steam flow rate (%) ⊿MCPR 1. 2. 3. 4. Reactor water level change from initial (x5cm) Reactor pressure change from initial (x0.01MPa) Turbine bypass valve flow rate (%) Safety relief valve flow rate (%) Fig.3.4-6 Analysis Result of Generator Load Rejection without Bypass [2] 3. Deterministic Safety Analysis Ver. 0 48 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C Fig.3.4-7 Sequence of Inadvertent MSIV closure Fig.3.4-8 Analysis Result of Inadvertent MSIV closure [2] 3. Deterministic Safety Analysis Ver. 0 49 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C Fig.3.4-9 Sequence of Loss of all feedwater flow Fig.3.4-10 Analysis Result of Loss of all feedwater flow [2] 3. Deterministic Safety Analysis Ver. 0 50 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C Table 3.4-1 Deviation on Major Plant Specifications related to frequent design basis fault analysis (1/5) Item 1. Basic Operating Condition (1)Thermal output(Rated) (2)Core flow rate(Rated) Japanese Reference Plant UK ABWR US ABWR (DCD Rev.4) 3926MW 3926MW 3926MW 52200t/h 52200t/h 52200t/h (3)Feedwater temperature(Rated) 217 C 217 C 217 oC (4)Reactor Pressure(at RPV dome) 7.07MPa[gage] 7.07MPa[gage] 7.07MPa[gage] 9×9 Fuel 10×10 Fuel (GE14) 8×8 Fuel 2. Fuel Type 3. Nuclear Boiler System (1)Main steam line volume (2)Characteristic of Safety Valves ·Valve number ·Capacity (3)Characteristic of Relief Valves ·Valve number ·Capacity (4)Capacity of Bypass Valves (5)MSIV Closure time o o 113.2m3* 7.92MPa×395t/h×2 7.99MPa×399t/h×4 8.06MPa×402t/h×4 8.13MPa×406t/h×4 8.20MPa×409t/h×4 7.51MPa×363t/h×1 7.58MPa×367t/h×1 7.65MPa×370t/h×4 7.72MPa×373t/h×4 7.79MPa×377t/h×4 7.86MPa×380t/h×4 113.2m3* 7.92MPa×460t/h×2 7.99MPa×464t/h×4 8.06MPa×468t/h×4 8.13MPa×472t/h×3 8.20MPa×476t/h×3 33% 33% 3−4.5seconds 3−4.5seconds 7.51MPa×422t/h×1 7.58MPa×426t/h×1 7.65MPa×431t/h×4 7.72MPa×434t/h×4 7.79MPa×438t/h×3 7.86MPa×442t/h×3 Note [ ] 113.2m3 7.92MPa×395t/h×2 7.99MPa×399t/h×4 8.06MPa×402t/h×4 8.13MPa×406t/h×4 8.20MPa×409t/h×4 7.51MPa×1 7.58MPa×1 7.65MPa×4 7.72MPa×4 7.79MPa×4 7.86MPa×4 *Minimum volume requirement. Flow rates of UK ABWR safety valves are larger than those of the others, which mitigates the pressure increase more. Flow rates of UK ABWR safety valves are larger than those of the others, which mitigates the pressure increase more. 33% 3−4.5seconds 3. Deterministic Safety Analysis Ver. 0 51 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C Table 3.4-1 Deviation on Major Plant Specifications related to frequent design basis fault analysis (2/5) Item 4. Recirculation System (1)Pump Characteristic (2) Power supply configuration 5. RPV volume 6. Setpoints of RPS(Reactor Protection System) (1) High reactor pressure scram (2) Low reactor water level scram (Level 3) (3) High neutron flux scram ·In terms of neutron flux ·In terms of heat flux (4) Short reactor period scram (5) Main steam isolation valve closure scram (6)Turbine main steam stop valve closure scram 7. Scram insertion time Japanese Reference Plant Same as reference plant ASD×10 (1/RIP) MGset×2 Same as reference plant US ABWR (DCD Rev.4) Same as reference plant ASD×10 (1/RIP) MGset×2 Same as reference plant 7.52MPa[gage] 7.52MPa[gage] 7.62MPaG* *Analysis condition +62 cm from the bottom of separator skirt +62 cm from the bottom of separator skirt +57cm above bottom of separator* *Analysis condition 120% 120% 125% Reactor period of 10 s 90 % stroke position 90 % stroke position 1.44 s at 60 % of full stroke 2.80 s at 100 % of full stroke Reactor period of 10 s 90 % stroke position 90 % stroke position 1.44 s at 60 % of full stroke 2.80 s at 100 % of full stroke − ASD×10 (1/RIP) MGset×2 − UK ABWR * 85 % stroke position* 85 % stroke position* 1.44 s at 60 % of full stroke 2.80 s at 100 % of full stroke 3. Deterministic Safety Analysis Ver. 0 Note *Unconfirmed *Analysis condition *Analysis condition 52 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C Table 3.4-1 Deviation on Major Plant Specifications related to frequent design basis fault analysis (3/5) Item 8. Reactor high water level (1) Level 8 ·Turbine trip 9. Low reactor water level (1)Level 3 ·Trip of four RIPs (2) Level 2 ·Trip of six RIPs (3) Level 1.5 ·Closure of MSIVs, ·Initiation of HPCF ·Initiation of RCIC ·Initiation of emergency diesel generators (Division II/III) (2) Level 1 ·Initiation of LPFL ·Initiation of emergency diesel generators (Division I) ·Initiation of ADS Japanese Reference Plant +166 cm from the bottom of separator skirt +62 cm from the bottom of separator skirt −58 cm from the bottom of separator skirt UK ABWR US ABWR (DCD Rev.4) +166 cm from the bottom of separator skirt +62 cm from the bottom of separator skirt −58 cm from the bottom of separator skirt −203 cm from the bottom of the separator skirt −203 cm from the bottom of the separator skirt +1023.0 cm from the bottom of RPV −287 cm from the bottom of the separator skirt −287 cm from the bottom of the separator skirt +939.6cm from the bottom of RPV Note +1389.3 cm from the bottom of RPV +1285.7 cm from the bottom of RPV +1168.1 cm from the bottom of RPV 3. Deterministic Safety Analysis Ver. 0 53 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C Table 3.4-1 Deviation on Major Plant Specifications related to frequent design basis fault analysis (4/5) Item 10. High Pressure Core Flooder System (HPCF) (1)Number of unit (2) Flow rate (Rated) 11. Reactor Core Isolation Cooling System (RCIC) (1)Number of units (2) Flow rate (Rated) (3)Duration of loss of AC power Supply Japanese Reference Plant UK ABWR US ABWR (DCD Rev.4) 2units 2units * *Unconfirmed 182 m3/h (per pump, at 8.115 MPa [dif]), 727 m3/h (per pump, at 0.689 MPa [dif]) 182 m3/h (per pump, at 8.115 MPa [dif]), 727 m3/h (per pump, at 0.689 MPa [dif]) * *Unconfirmed 1unit 1unit 1unit 182 m3/h (per pump, at 8.115~ 1.034 MPa [dif]) 182 m3/h (per pump, at 8.115~ 1.034 MPa [dif]) 182 m3/h (per pump, at 8.12~ 1.03 MPa [dif]) [ ]hr [ ]hr 3. Deterministic Safety Analysis Ver. 0 * Note *Unconfirmed 54 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C Table 3.4-1 Deviation on Major Plant Specifications related to frequent design basis fault analysis (5/5) Item 12. Low Pressure Flooder System (LPFL) (1)Number of units (2) Flow rate (Rated) 13. Automatic Depressurization System (ADS) (1)Number of valves (2) Flow rate (Rated) Japanese Reference Plant UK ABWR US ABWR (DCD Rev.4) 3units 3units 3units 0 m3/h (per pump, at 1.551 MPa [dif]), 954 m3/h (per pump, at 0.276 MPa [dif]) 8units 0 m3/h (per pump, at 1.551 MPa [dif]), 954 m3/h (per pump, at 0.276 MPa [dif]) 7units 2.903×106 kg/h (per all valves) 2.903×106 kg/h (per all valves) Note 954 m3/h (per pump, at 0.27 MPa [dif]) 3. Deterministic Safety Analysis Ver. 0 * *Unconfirmed * *Unconfirmed 55 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C 3.5 Infrequent Design Basis Faults DSA for UK ABWR will be performed in Steps 2 and 3. Therefore, this section shows examples of analysis results for infrequent design basis faults, which have been performed on the basis of Hitachi-GE practice. These examples explain the causes of the occurrence and the measures implemented for preventing them, and also the safety function for each infrequent design basis fault. In addition, they show the progress of the faults based on the analysis result. It will explain that the basic design policies of safety systems and safety related systems on ABWR are adequate in order to meet acceptance criteria in Japan. 3.5.1 Evaluated Events In analysing accidents, we will study them by dividing them into the following main items: 1) Loss of reactor coolant or considerable change in core cooling a. Loss of coolant (LOCA) b. Loss of reactor coolant flow (Trip of all reactor internal pumps) 2) Abnormal reactivity insertion or rapid change in reactor power a. Control rod drop 3) Abnormal release of radioactive materials to the environment a. Offgas treatment system failure b. Main steam line break (MSLBA) c. Fuel assembly drop (Fuel Handling Accident) d. Loss of coolant accident(LOCA) e. Control rod drop 4) Abnormal change in pressure and atmosphere etc. in the primary containment a. Loss of coolant (LOCA) b. Generation of flammable gas c. Generation of dynamic load As an example, the analysis results of the following events chosen from the listed above are shown in this section. (1) Loss of coolant accidents (LOCA) (2) Loss of reactor coolant flow accident (Trip of all Reactor Internal Pumps Accident) (APTA) (3) Main steam line break accident (MSLBA) (4) Abnormal Change in Pressure and Atmosphere etc. in the Primary Containment (Analysis of Pressure and Temperature Responses of Containment Vessel) 3. Deterministic Safety Analysis Ver. 0 56 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C 3.5.2 Loss of Coolant Accidents (LOCA) 3.5.2.1 Causes If one of the various pipes connected to the reactor coolant pressure boundary should break during reactor operation for some reason, the reactor coolant leaks out of the pressure boundary or is lost. In this case, if the coolant cannot be replenished, it becomes impossible to cool the core sufficiently, and in the worst case, the fuel temperature rises excessively due to the decay heat, and fission products may possibly be released from the fuel. 3.5.2.2 Measures to Prevent Accidents and to Mitigate Accidents (1) Measures to Prevent Accidents The following measures are adopted in design and in operation management for the purpose of preventing the occurrence of LOCAs: a. In designing the piping, etc., severe conditions are to be applied, taking fully into consideration the various types of stresses operating during the reactor life. b. The selection and working of materials as well as the designing and fabrication of pipes, etc. are to comply with the various codes and standards, and adequate quality controls are to be carried out. c. The main sites are to be inspected during the period when the rector is in service, and their integrity is to be checked. d. The pipes, etc. which make up the reactor coolant pressure boundary are to have a design which will prevent non-ductile break. e. In addition, monitoring by means of the leakage detection system is used to detect damages before they develop into breaks, and suitable measures are to be taken. These claims will be substantiated in the structural integrity subject area. (2) Measures to Mitigate Accidents If a LOCA should occur in spite of the above measures to prevent an accident, the following measures will be applied to mitigate the accident: a. The ECCS are provided for the purpose of preventing damages of the fuel cladding tubes large enough to interfere with core cooling (large damages), suppressing the zirconium-water reaction to a sufficiently low level, and removing the decay heat over a prolonged period. 3. Deterministic Safety Analysis Ver. 0 57 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C a) The High Pressure Core Flooder Systems (hereinafter called the "HPCF"), the Reactor Core Isolation Cooling System (hereinafter called the "RCIC"), the Automatic Depressurization Systems (hereinafter called the "ADS") and the Low Pressure Flooder Systems (hereinafter called the "LPFL") are provided in these reactors in order to achieve the purposes mentioned above. Even in cases where there will be the largest decrease of the amount of coolant retained, such as a complete break of the pipe of the HPCF, depressurization inside the reactor will not be accelerated to a degree corresponding to the decrease of the coolant. Therefore, the HPCF and RCIC, which are able to inject water even with the reactor in a high pressure state, will start at signals indicating a low reactor water level or a high drywell pressure and will cool the core. Moreover, independently of the HPCF and the RCIC, the ADS will be activated after a time delay of 30 seconds by simultaneous signals indicating a low reactor water level and a high drywell pressure. By releasing reactor steam into the pool water of the suppression chamber, they will lower the reactor pressure, making possible prompt injection of water by the LPFL. b) In the ECCS of these reactors, systems with different basic principles are provided redundantly and independently to perform core cooling to deal with breaks of any area of the pipes connected to the pressure vessel. This design aims at preventing the core-cooling function from failing in the event of any single failure. c) The ECCS power sources are designed with three diesel generators to supply power even if no offsite power is available. b. A containment installation is provided in order to hold in the coolant and radioactivity released from the pressure vessel during a LOCA. The containment installation consists of a pressure-suppression type containment vessel and the Reactor Area of the Reactor Building (hereinafter called the "Reactor Area") surrounding the containment vessel. a) The containment vessel has a design capable of withstanding the rise of the internal pressure during a LOCA. It is designed to have a leakage rate of 0.4%/d or less (at normal temperature, in air, at a pressure 0.9 times the maximum service pressure). The containment vessel is provided with a Containment-Vessel Spray-Cooling System for preventing the pressure and temperature inside the containment vessel from exceeding the 3. Deterministic Safety Analysis Ver. 0 58 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C maximum service pressure and the maximum service temperature. In addition, these reactors are provided with Flammability Control Systems for preventing the flammable gases produced by radiolysis of water inside the containment vessel and by the zirconium-water reaction from reaching their flammable limits. b) Provisions are made for maintaining a negative pressure in the Reactor Area even during an accident. Its ventilation rate is to be 50%/d. Standby Gas Treatment Systems are also provided. They remove the iodine with a high efficiency before it is released through the main stacks into the air. 3.5.2.3 Analysis of Accident Process The break of HPCF pipe ends causes a peak of fuel cladding temperature. Hence, this accident is analyzed in order to confirm the performance of an ECCS during the loss of reactor coolants. (1) Analysis conditions The analysis of the HPCF pipe ends rupture accident is carried out based on the following assumptions. a. The reactor is assumed to operate at about 102% of rated power (4,005MWt) and at 90% of a rated core flow rate immediately before the accident. b. The maximum liner heat generation rate of a fuel rod is assumed to be 102% of 44.0 kW/m (operating limit). For a gap heat transfer coefficient between a fuel clad and pellet, a value that will make the analysis result more conservative is used in consideration of variations in the heat transfer during the cycle exposure. c. For the decay heat after the shutdown of the reactor, a value determined from an equation that incorporates a safety margin into actual measurements, is used. For reference, this equation incorporates a decay heat of actinide. d. Off-site power is assumed to be lost concurrently with the occurrence of the accident. Consequently, a recirculation pump will instantly be tripped. The reactor scram is assumed to be initiated by a signal of core flow rapid coastdown. 3. Deterministic Safety Analysis Ver. 0 59 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C e. It is considered that a signal for high pressure of a drywell as a ECCS startup signal is given earlier than a signal for a low water level in the reactor (Level 2 or 1), but ECCS is assumed to conservatively start up at the signal for the low level. f. A single failure is assumed in safety protection systems (scrams resulting from core flow rapid coastdown) from the viewpoint of the capability of reactor shutdown. g. The most conservative single failure is assumed in the ECCS network from the viewpoint of the capability of reactor cooling. The most conservative single failure in the case of the HPCF pipe break accident is a failure of a diesel generator that supplies power to an otherwise functional high-pressure core injection system. h. The leakage of coolant from the broken area is calculated based on a uniform critical flow model. i. In a safety and relief valve, the relief valve works earlier than the safety valve, but the safety valve is assumed to work earlier. For more information, major calculation conditions used for the analysis are shown in Table 3.5.2.1-1. (2) Analysis results a. Variations of core flow, reactor pressure, reactor water level and fuel cladding-tube temperature If there is a double-ended break of the HPCF lines, critical flow will occur at the HPCF sparger nozzle part having the smallest area within the flow path from the HPCF sparger to the rupture orifice. If we suppose a loss of offsite power occurring simultaneously with the accident, the core flow will decrease rapidly because of the shutdown of the recirculation pumps. Due to the core flow rapid coastdown, the MCPR d rops below 1.07(Safety Limit MCPR) in about 1 second after the accident, and boiling transition will occur as far as the fifth spacer position from the top of the fuel assembly. Together with this, the heat-transfer rate from the fuel cladding tubes to the coolant drops, and the fuel cladding-tube temperature rises. However, 3. Deterministic Safety Analysis Ver. 0 60 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C the temperature rise of the fuel cladding tubes subsides within a short time because of the drop of power due to reactor scram. On the other hand, the water level inside the core shroud starts to drop after about 56 seconds. However, the Reactor Core Isolation Cooling System is activated by low level (level 1.5) signals of reactor water and starts water injection in about 120 seconds after the accident. The Automatic Depressurization Systems also is activated by high pressure signals of drywell and low level (level1) signals of reactor water in about 160 seconds after the accident to lower the reactor pressure, and two Low-Pressure Flooder Systems begin to inject water in about 345 seconds. The water level inside the core shroud does not drop below top of the active fuel, and the core is kept flooded. For this reason, rises of temperature of the fuel cladding tubes because of core uncovering does not occur. That is, the fuel cladding-tube temperature does not rise above the temperature rise accompanying the boiling transition immediately after the accident. Fig. 3.5.2-1 illustrates the changes in the core flow during these accidents, and Figs. 3.5.2-2 and 3.5.2-3 illustrate the changes in the reactor water level and the reactor pressure. Fig. 3.5.2-4 illustrates the time variations of the fuel cladding tube temperature. The highest fuel cladding temperature during these accidents is about 600 degree-C. b. Rupture and oxidation of fuel cladding tubes Rupture of the fuel rods occurs when the temperature of the fuel cladding tubes rises after an accident until the circumferential stress of the fuel cladding tubes due to internal pressure exceeds the tensile strength at that temperature. Fig. 3.5.2-5 shows that the fuel cladding-tube temperature is about 600 degree-C or less during a double-ended break of the HPCF lines. On the other hand, in the fuel rods of this reactor, the maximum calculated difference between the internal and the external pressures is about 5MPa. Since the circumferential stress at this time is approximately 3×101 N/mm2, rupture does not occur in the fuel rods, as is clear from Fig. 3.5.2-5. There is very little increase in the thickness of the oxide layer on the fuel cladding tubes because of the low temperature of the fuel cladding tubes. Moreover, the zirconium-water reaction fraction in all of the fuel cladding tubes is negligibly small. c. Summary of analysis results When the severest single failure during a LOCA is assumed, the fuel cladding temperature is highest in the case of a double-ended break of the HPCF lines, which is approx.600 degree-C. Since there is very little increase in the thickness of oxide layer on the fuel cladding tubes, the fuel cladding tubes will not lose their ductility. Moreover, rupture will not occur in any of the 3. Deterministic Safety Analysis Ver. 0 61 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C fuel rods, the zirconium-water reaction fraction of all the fuel cladding tubes will be negligibly small. Removal of the decay heat of the long half-life nuclides over a prolonged period assured if one of the ECCS pumps is activated. In the case of partial breaks of the HPCF lines or of breaks of various other lines, the temperature of fuel cladding tubes will be less than in the case of a double-ended break of the HPCF lines. Thus, they are included within the analysis results for double-ended breaks of the HPCF lines. In these analyses, it is assumed that offsite power is lost simultaneously with the accident. However, the results are included within these analysis results even if the offsite power is not lost during an accident. 3.5.2.4 Review of Conformance to Acceptance Criteria As indicated in “3.5.2.3 Analysis of accident process”, the highest value of the fuel cladding temperature is 1,200°C or lower, and therefore, there are no fuel rods that would be ruptured, and the increase in the thickness of oxidized layer of the fuel cladding is 15% or less of the thickness of the fuel cladding at time before the oxidization reaction becomes significant. In addition, since the rate of zirconium-water reaction of the entire fuel cladding is at a negligible level, the quantity of hydrogen generated by the reaction is low enough from the viewpoint of securing the integrity of the containment. The removal of decay heat over a long period of time will be secured if one of the pumps of the ECCS other than the reactor core isolation cooling system is actuated. Therefore, the criteria in Japan described in “3.2.1.2 Design Basis Accidents” are met. 3.5.2.5 Assessment of Emissions and Dose Equivalents of Fission Products 3.5.2.5.1 Emissions of Fission Products (1) Analysis conditions The migration and emission of fission products during the accident is calculated based on the following assumptions. a. The reactor is assumed to operate for a sufficiently long time (2,000 d) at about 102% of nominal power (4,005MWt) just before the accident. 3. Deterministic Safety Analysis Ver. 0 62 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C b. The concentrations of fission products in the coolant before the accident are assumed to be equivalent to 1.3 × 103Bq/g, or the operational allowable maximum concentration of I-131. The composition of the products is assumed to be a diffusion composition. c. As shown in "3.5.2.3 Analysis of Accident Process", there are no additional broken fuel rods after the accident. Consequently, additional emission of I-131 from the fuel rod that is caused by a decrease in reactor pressure after the accident is assumed to be 3.7 × 1013Bq/g, or an average of past actual measurements in the existing plants plus a proper margin. The composition of other fission products is assumed to be an equilibrium composition. An emission of noble gas is assumed to be twice larger than that of iodine. d. Organic iodine is assumed to be 4% of additional iodine from the fuel rod, while 96% of the iodine is assumed to be inorganic. e. 50% of inorganic iodine is assumed to be deposited on the inside of the containment, and is assumed not to contribute to the leakage. Furthermore, the iodine is removed by the water spray system in the containment, or dissolved into a pool in the suppression chamber. A rate of the removed or dissolved iodine is assumed to be 100 as a partition coefficient. Organic iodine and noble gas is assumed not be removed or dissolved. f. The natural decay of fission products in the containment is assumed to be allowed for. g. A rate of leakage from the containment is assumed to be a leakage percentage that corresponds to a pressure in the containment during the accident, plus a proper margin. Emissions of fission products that are caused by the leakage of pool water in the suppression chamber, and led by ECCS outside the containment, are much smaller than emissions of the products leaked from a gas phase in the containment, and are not a significant contributor to the leakage. Consequently, the assessment of these emissions is assumed to be omitted. h. A heating, ventilating and air conditioning system for reactor and turbine areas that works during normal operation is assumed to be switched to a standby gas treatment system at a signal of a low water level in the reactor, for high pressure in a drywell, or for high activity in the reactor area. The deposition of fission products on floors and walls in the reactor area is disregarded. Only the natural decay of the products is assumed to be allowed for. 3. Deterministic Safety Analysis Ver. 0 63 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR i. Revision C A design value of 99.99% is used for the efficiency of iodine removal by a filter in the standby gas treatment system. j. A value defined in the design (0.5 times/d) is used for the capacity of the standby gas treatment system. k. When effective dose equivalents by direct and skyshine from fission products in the reactor area are evaluated all of the fission products leaked from the containment to the reactor area is assumed to be uniformly distributed in the area. However, direct and skyshine γ rays from fission products in the containment are sufficiently shielded by primary shielding in the reactor, and are not a significant contributor to the assessment of effective dose equivalents. Consequently, they is assumed to be excluded from radioactive sources in the reactor area l. An assessment period after the accident is a period lasting (or an indefinitely longer period in terms of conservatism) until internal pressure in the containment is decreased to the extent where the leakage from the containment becomes negligible. m. Fission products leaked from the containment to the reactor area is treated by the standby gas treatment system, and then released from an exhaust opening in the system into the air. n. A single failure is assumed in dynamic equipment of the Stand-by Gas Treatment system from the standpoint of radioactivity confinement. (2) Analysis results Emissions of fission products into the atmosphere that are calculated based on the above analysis conditions are shown in Table 3.5.2-2. Also, the processes of release of noble gas and iodine into the atmosphere are shown in Fig. 3.5.2-6 and Fig. 3.5.2-7. 3.5.2.5.2 Assessment of dose equivalent (1) Analysis assumptions The fission products emitted into the atmosphere is assumed to be released from an exhaust opening in the standby gas treatment system. Off-site effective dose equivalent that is given by the fission products emitted, and those that is given by direct and skyshine rays from the fission products in the reactor area is calculated based on the following assumptions. 3. Deterministic Safety Analysis Ver. 0 64 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR a. Revision C The concentrations in the air on the ground surface outside the site boundary are determined by multiplying the relative concentration of such plant by the total released amount of nuclear fission products. b. The gamma-ray air absorption dose due to noble gas outside the site boundary is assumed to be determined by multiplying the relative dose of such plant by the total release of noble gas c. Effective dose equivalents by direct and skyshine γ rays from fission products are determined based on source intensities of accumulated γ rays that are provided by the fission products in the reactor and in consideration of the shielding of the reactor building. (2) Assessment results Off-site effective dose equivalent is assessed based on the above analysis assumption. The result is shown in Table 3.5.2-3. This dose is based on assumptions generally used in Japanese assessments and should only be taken as indicative. It is recognized that the calculated doses will differ when calculated using UK assumptions and practice Judging from the above values, a risk of s radiation exposure to the surrounding public by this accident is considered to be sufficiently small. 3. Deterministic Safety Analysis Ver. 0 65 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C 3.5.3 Loss of Reactor Coolant Flow Accident (Trip of all Reactor Internal Pumps Accident) (APTA) 3.5.3.1 Causes It is assumed that all reactor internal pumps trip simultaneously during reactor power operation due to failure of the power source buses or some other cause. 3.5.3.2 Measures to Prevent Accidents and to Mitigate Accidents (1) Measures to Prevent Accidents The following measures are adopted in design and in operation management for the purpose of preventing the occurrence of loss of reactor coolant flow accident: a. Two or three of the ten recirculation pumps are each connected to four different systems of medium voltage buses for normal use. This is done so as to prevent four or more pumps from shutting down simultaneously because of a single failure of a medium voltage bus for normal use. These buses are configured so that they are supplied from a generator-side power source during normal operation of the reactor, and they are still supplied from a starting transformer even if the generator-side power source is interrupted. b. Static power-source devices for the recirculation pumps supply power to the motors driving the recirculation pump. These devices are independently connected to each of the ten recirculation pumps. This configuration makes it impossible for two or more pumps to shut down simultaneously because of a single failure of the power-source devices. c. The main sites are inspected during the period when the reactor is in service, and their integrity is checked. (2) Measures to Mitigate Accidents Even should an all RIPs trip accident occur in spite of the above measures to prevent accidents, the reactor power will decrease on account of the large negative void reactivity coefficient, and it will be terminated by means of reactor scram and turbine trip. Thus, there is no concern that the accident will proceed after that. 3.5.3.3 Analysis of Accident process (1) Analysis conditions a. The reactor is assumed to operate at about 102% of rated power (4,005 MWt) and at a 90% core flow rate (47,000t/h) immediately before the accident. 3. Deterministic Safety Analysis Ver. 0 66 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C b. The maximum liner heat generation rate of a fuel rod is assumed to be 102% of 44.0 kW/m (operating limit). For a gap heat transfer coefficient between a fuel clad and pellet, a value that will make the analysis result more conservative is used in consideration of variations in the heat transfer during the cycle exposure. c. A design value for a half time of pump speed that corresponds to a rated core flow rate of a circulation pump and that of the motor driving the pump is about 0.7 seconds, but a value 10% smaller than this time (0.62 seconds) is used for this analysis so as to give more conservative results. d. The reactor scram is assumed to be initiated by a signal of core flow rapid coastdown. e. A single failure is assumed in safety protection systems (scrams resulting from core flow rapid coastdown) from the viewpoint of the capability of reactor shutdown. f. In a safety and relief valve, the relief valves work earlier than the safety valves, but the only safety valves are assumed to work. g. Non-operation of turbine bypass valves is assumed so as to give more conservative result. (2) Analysis results Fig.3.5.3-1 shows responses at the loss of a reactor coolant flow. When all recirculation pumps concurrently are tripped, the core flow rate is rapidly decreased. About 2 seconds later, a signal of the rapid coast down in the core flow rate is occurred and causes the scram of the reactor. Consequently, neutron and surface heat fluxes do not exceed their initial values. On the other hand, water level in the reactor rises, and turbine trip is occurred at 3 seconds later by a high water level in the reactor (Level 8). The turbine trip increases the reactor pressure, but the scram of the reactor and the operation of a safety valve controlled the pressure to about 8.23MPa[gage]. Due to the core flow rapid coastdown, the MCPR drops below 1.07 (safety limit MCPR) about 1 second after the accident, resulting in boiling transition (BT) from the upper fuel assembly to the forth spacer. However, the increase in temperature is stopped after a short time because the scram reduces the power. Fig.3.5.3-2 shows variations in the peak cladding temperature. The peak cladding temperature during this accident is about 563 degree-C. The external pressure is kept higher than the internal pressure in the fuel rods of this reactor during 3. Deterministic Safety Analysis Ver. 0 67 NOT PROTECTIVELY MARKED Form05/00 UK ABWR NOT PROTECTIVELY MARKED GDA Preliminary Safety Report Revision C the accident. Consequently, the circumferential stress does not rupture the fuel rods. Furthermore, the increase of an oxidized layer on the fuel clad is significantly small because the temperature of the cladding is low. As indicated in the analysis result, the event ends. Afterwards, the reactor can be transferred to cold shutdown by pressure reduction and temperature drop according to the procedures for reactor shutdown at a reactor scram (during closing of the main steam isolation valve). 3.5.3.4 Review of Conformance to Acceptance Criteria The criteria applying to this accidents are 1) and 3) in Section 3.2.1.2. As indicated in “Analysis results", the maximum value of the fuel cladding temperature 1,200 degree-C or less; and the zirconium-water reaction fraction is 15% or less of the cladding-tube thickness before the oxidation reaction becomes pronounced. Therefore, 1) is met. Reactor pressure (reactor vessel dome pressure) goes about 8.23MPa[gage]. So, pressure to reactor coolant pressure boundary stays below 120% of maximum allowable working pressure. Therefore, 3) is met. Therefore, the criteria in Japan described in “3.2.1.2 Design Basis Accidents” are met. 3. Deterministic Safety Analysis Ver. 0 68 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C 3.5.4 Main Steam Line Break Accident (MSLBA) 3.5.4.1 Causes If a main-steam line break outside the containment should occur due to some causes during reactor operation, the reactor coolant begins to flow out from the broken area, and fission products may be released to the environment. 3.5.4.2 Measures to Prevent Accidents and to Mitigate Accidents (1) Measures to Prevent Accidents The following measures are adopted in design in operation management for the purpose of preventing the occurrence of main steam line break accidents: a. In designing the piping, etc., conditions are to be applied taking fully into consideration the various types of stresses occurring during the reactor life. b. The selection and working of materials as well as the designing and fabrication of pipes, etc. are to comply with the various codes and standards, and adequate quality controls are to be carried out. c. Detection of the atmospheric temperature inside the main-steam pipe tunnels and other methods are to be used to detect damages before they develop into breaks, and suitable measures are to be taken. (2) Measures to Mitigate Accidents If an accident should occur in spite of the above measures to prevent accidents, the following measures will be applied to mitigate the accident: a. Flow limiters are provided on the steam outlet nozzles of the reactor pressure vessel. They limit the amount of coolant flowing out during an accident. b. By signals such as those indicating a large main steam line flow, a high temperature in the main-steam line tunnels, a high radioactivity in the main steam line or a low main steam line pressure, the main steam isolation valves (MSIVs) installed on both sides of the drywell penetrations of the main steam lines are closed automatically to stop release of coolant. 3.5.4.3 Analysis of Accident Process (1) Analysis conditions The analysis is carried out based on the following assumptions. 3. Deterministic Safety Analysis Ver. 0 69 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR a. Revision C The reactor is assumed to operate at about 102% of rated power (4,005 MWt) and at 111% of a rated core flow rate immediately before the accident. b. The maximum liner heat generation rate of a fuel rod is assumed to be 102% of 44.0 kW/m (operating limit). For a gap heat transfer coefficient between a fuel clad and pellet, a value that will make the analysis result more conservative is used in consideration of variations in the heat transfer during the cycle exposure. c. On the assumption that instantly double-ended break of one of four main steam lines is assumed outside the containment, friction loss to the broken area is not allowed for when a quantity of coolants released is assessed. d. A main steam isolation valve is assumed to be completely closed 5 seconds (including a 0.5 second operation delay time) after the accident at a signal of a maximum flow rate in a main steam line. e. The reactor scram is assumed to be initiated by a signal of main steam isolation valve closure. f. A rate of released flow is assumed to be controlled to 200% of a rated flow rate by a flow limiter until the flow rate is limited by the isolation valve. g. A critical flow is calculated based on the critical flow model of Moody. h. Off-site power is assumed to be lost concurrently with the occurrence of the accident. Consequently, reactor internal pumps are instantly tripped. i. A single failure is assumed in safety protection systems (scram for closing the main steam isolation valve at a signal of a high flow rate in the main steam pipe) from the viewpoint of the capability of reactor shutdown. (3) Analysis results When a double-ended break of one of four main steam lines occurs instantly, steam in the broken pipe is leaked directly from the upstream broken end of the pipe. On the other hand, steam moving through the other three undamaged pipes counterflowed through the broken pipe via an interconnector upstream from the turbine stop valve, and is discharged from the downstream broken 3. Deterministic Safety Analysis Ver. 0 70 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C end. The amount of steam discharged from the upstream broken area of the pipe increases from about 102% of a rated flow rate immediately before the accident to about 4244 kg/s, equivalent to a critical flow at a main steam pipe nozzle. Due to that this value exceeds the rate of steam generated at the core, reactor pressure is reduced. The reduced pressure increases a void in the reactor. As a result, water level in the reactor increases, and the water level reaches the main steam pipe nozzle in about 2 seconds. After that, a two phase flow is discharged into the main steam pipes. The main steam isolation valves are completely closed 5 seconds (including a 0.5 second operation delay) after the accident at a signal of a high flow rate in the main steam pipe, but a signal for the closing of the valve is generated about 1 second after 10% closing of the valve, resulting in the reactor scram. Time variations of amount of discharged coolant during the accident, average core pressure and core flow rate are shown in Fig. 3.5.4-1 and Fig. 3.5.4-2. Amounts of steam and water discharged from the broken area until full closing of the main steam isolation valves represent the following values. Steam : approximately 1.6 × 104 kg Water : 4 approximately 2.4 × 10 kg However, the coolant of approx. 8.6 × 104 kg needs to be discharged in order to start uncovering the core. Consequently, the core is not uncovered during the accident. On the assumption that a loss of off-site power occurs with the accident, a trip of all internal pumps decrease the core flow rate rapidly. Due to the core flow rapid coastdown,, MCPR drops below 1.07 (safety limit MCPR) about 1 second after the accident, resulting in the occurrence of boiling transition (BT) from the upper fuel assembly to the fifth spacer. With boiling transition, a coefficient of heat transfer from the fuel clad to the coolant became low, and the fuel cladding temperature increased. However, the increase in temperature was stopped after a short time because the scram reduced the power. Fig.3.5.4-3 shows variations in temperature at a position where peak cladding temperature is given. The peak cladding temperature during this accident is about 569 degree-C. The rupture of the fuel rods occurs when, after the accident, the fuel cladding heats up and the circumferential stress due to the internal pressure of the fuel cladding exceeds the tensile strength held at that temperature. The fuel cladding temperature in this accident is about 569 degree-C or less. On the other hand, the external pressure is kept higher than the internal pressure in the fuel rods during the accident. Consequently, the circumferential stress due to internal pressure in the fuel rods does not cause rupture of the fuel rods, as shown in Fig. 3.5.2-5. Furthermore, the increase of an oxidized layer on the fuel clad is significantly small because the fuel 3. Deterministic Safety Analysis Ver. 0 71 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C cladding temperature is low. 3.5.4.4 Review of Conformance to Acceptance Criteria As shown in "3.5.3.3 Analysis of Accident Process," no fuel rod will burst in this accident. Moreover, the maximum temperature of the fuel cladding is 1,200°C or less and the rise in the thickness of the oxidized layer of the fuel cladding is not more than 15% of the thickness of the fuel cladding before the oxidation reaction becomes considerable, so that it will retain a geometry that can be cooled and the cooling capability will not be lost. Therefore, no new damage will occur to the fuel rods due to this accident, and the criterion 1) described in “3.2.1.2 Design Basis Accidents” is met. Therefore, the criteria in Japan described in “3.2.1.2 Design Basis Accidents” are met. 3.5.4.5 Assessment of Emissions and Dose Equivalents of Fission Products 3.5.4.5.1 Emission of Fission Products (1) Analysis conditions The migration and emissions of fission products during the accident is used to be assessed based on the following assumptions. a. The concentrations of fission products in a coolant before the accident are assumed to be equivalent to 1.3 × 103Bq/g, or the operational allowable maximum concentration of I-131. Their compositions are assumed to be a diffusion composition. The concentration of halogen in gas phase is assumed to be 2% of that in liquid phase. b. Additional emission of I-131 from the fuel rod that is caused by a decrease in reactor pressure after the accident is assumed to be 3.7 × 1013Bq/g, or an average of past actual measurements in the existing plants plus a proper margin. The composition of other fission products is assumed to be an equilibrium composition. An emission of noble gas is assumed to be twice larger than that of iodine. c. Fission products that are additionally emitted from a fuel rod before closing the main steam isolation valves are assumed to be released in proportion to the rate of decrease in reactor pressure before closing the valves, but additional fission products are assumed not to be emitted from the broken area. 3. Deterministic Safety Analysis Ver. 0 72 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C d. Fission products that are additionally emitted from a fuel rod after the closing of the valves are assumed to be gradually emitted to the coolant with the reduction of reactor pressure. e. Organic iodine is assumed to be 4% of additional iodine from the fuel rod, while 96% of the iodine is assumed to be inorganic. f. Of fission products that are additionally emitted from the fuel rod, all of the noble gases are assumed to migrate instantly to a gas phase. 10% of the organic iodine is assumed to migrate instantly to the gas phase, and the rest is assumed to decompose. 2% of inorganic iodine and halogen other than iodine that are decomposed from inorganic and organic iodine are assumed to be carried over to the gas phase. g. On the assumption of a single failure in a main steam isolation valve from the viewpoint of radioactivity confinement, steam is leaked from seven closed main steam isolation valves on the assumption that one of eight main steam isolation valves is not closed. The total leakage rates of the valves are assumed to be 30%/d based on a design leakage rate of 10%/d (one valve to a gas phase volume in a pressure vessel at a minimum set pressure of safety and relief valve), in consideration of the closing of seven valves in the four main steam pipes. Subsequent leakage rates depend on reactor pressure and temperature. h. On the assumption that steam equivalent to decay heat migrates to pool water in a suppression chamber through the safety and relief valves after the closing of the main steam isolation valves, the quantity of the steam is assumed to be 320 times/d larger than the gas phase volume in the vessel. Fission products contained in this steam assumed not to contribute to radiation exposure. i. The reactor pressure after the closing of the valves is assumed to be linearly reduced to an atmospheric pressure in 24 hours by the safety and relief valves, a Reactor core isolation cooling system and a Residual heat removal system. As a result, the leakage from the main steam system is assumed to be stopped. j. 50% of inorganic iodine and halogen other than the iodine that is decomposed from the inorganic/organic iodine emitted into a turbine building is assumed to be deposited on floors and walls. Noble gas and organic iodine are assumed not to be deposited. 3. Deterministic Safety Analysis Ver. 0 73 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C k. The coolant discharged from the broken area before the closing of the main valves is assumed to be completely vaporized, and form a vapour cloud that uniformly contains fission products emitted at the same time. l. The fission products that are leaked from the main steam system after the closing of the valves are assumed to be dispersed aboveground into the atmosphere. (2) Analysis results Emissions of the fission products into the atmosphere that are calculated based on the above analysis conditions are shown in Table 3.5.4-1. Also, the processes of release of noble gas and halogen etc. into the atmosphere are shown in Fig. 3.5.4-4 and Fig. 3.5.4-5. 3.5.4.5.2 Assessment of Dose Equivalent (1) Analysis assumptions Fission products emitted into the atmosphere are assumed to be dispersed aboveground from a turbine building. Off-site effective dose equivalent that is given by the emissions is calculated based on the following assumptions. a. The coolant that contains fission products released before the closing of main steam isolation valves is assumed to be completely vaporized in high temperature and low humidity in the atmosphere, and to form a hemispherical vapour cloud. In this case, a smaller vapour cloud will increase an effective dose equivalent, while a vapour cloud will become smaller under an outside air condition of higher temperature and lower relative humidity. In order to determine the size of the vapour cloud, temperature 35 degree-C and relative humidity 47% are used. b. The hemispherical vapour cloud is assumed to move downwind at a rate of 1m/s in consideration of a short-time emission. c. The concentrations in the air on the ground surface outside the site boundary of fission products, which are emitted into the atmosphere through main steam isolation valves after the closing of the valves, are determined by multiplying the relative concentrations of such plant by the total released amount of nuclear fission products. 3. Deterministic Safety Analysis Ver. 0 74 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C d. The γ absorbed dose outside the site boundary by noble gas and halogen etc. is determined by multiplying the relative dose of such plant by the total released amount of noble gas and halogen etc.. (2) Assessment results Off-site effective dose equivalent is assessed based on the above analysis assumption. The result is shown in Table 3.5.4-2. This dose is based on assumptions generally used in Japanese assessments and should only be taken as indicative. It is recognized that the calculated doses will differ when calculated using UK assumptions and practice Judging from the above values, a risk of s radiation exposure to the surrounding public by this accident is considered to be sufficiently small. 3. Deterministic Safety Analysis Ver. 0 75 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C 3.5.5 Abnormal Change in Pressure and Atmosphere etc. in the Primary Containment (Analysis of Pressure and Temperature Responses of Containment Vessel) 3.5.5.1 Causes The cause of this accident is the same as that described in "3.5.2.1 Causes." 3.5.5.2 Measures to Prevent Accidents and to Mitigate Accidents The measures to prevent and to mitigate these accidents are same as those described in "3.5.2.2 Measures to Prevent Accidents and to Mitigate Accidents". 3.5.5.3 Analysis of Accident Process In order to confirm the integrity of the containment vessel during a LOCA, an analysis of a complete-break accident of the feedwater lines is carried out. This is the accident in which there is the highest containment-vessel pressure. (1) Analysis conditions The following assumptions are used in the analysis: a. It is assumed that the reactor has been operating at about 102% of the rated power (4,005 MWt) until immediately before the onset of the accident. b. It is assumed that offsite power is lost simultaneously with the onset of the accident. Consequently, the recirculation pumps are tripped immediately. c. Moody's critical-flow model is used to calculate the discharged flow of coolant from the broken area. d. Immediately before the onset of the accident the drywell temperature is assumed to be 57 degree-C, the pool water temperature of the suppression chamber is assumed to be 35 degree-C, and the pressure inside the containment vessel is assumed to be 5kPa[gage]. e. It is assumed that the Residual Heat Removal System is manually switched to the Containment Vessel Spray Cooling System 10 minutes after the accident, and this operation is completed in 15 minutes after the accident in consideration of the time required for the operation. f. A single failure is assumed in the dynamic equipment of the Containment Vessel Spray Cooling System. 3. Deterministic Safety Analysis Ver. 0 76 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C (2) Analysis results If there is a complete break of the feedwater lines, the coolant flows out rapidly from the reactor and turbine side into the drywell, and the drywell pressure increases. For this reason, most of the gases inside the drywell are driven out by the discharged flow of coolant into the suppression chamber, and the steam in the gases is condensed by the pool water of suppression chamber. On the other hand, the non-condensable gases migrate to the airspace of the suppression chamber, and the pressure in the suppression chamber increases. After the water level in the pressure vessel is restored up to the elevation of the feedwater lines (converted into terms of static head) due to the activation of the ECCS, the excess water flows out through the broken area to the drywell. It cools and condenses the steam in the drywell and causes the heat generated in the core to move into the suppression chamber. As a result of condensation of the steam in the drywell, the drywell pressure decreases, and the vacuum breakers are actuated passively to redistribute the non-condensable gases in the suppression chamber to the drywell and the suppression chamber. The Residual Heat Removal System is used at first as a Low Pressure Flooder System, but 15 minutes after accident it is switched manually so that one pump is used as a Containment Vessel Spray Cooling System to lower the pressure in the containment vessel. After the heat generation from the core becomes equal to the heat removal by cooling system, the temperature in the suppression chamber is gradually lowered. As a result of the heat removal, the temperature in the drywell and in the suppression chamber is lowered, and the pressure also decreases along with this. Figs.3.5.5-1 and 3.5.5-2 show the results of analysis of the pressure and temperature variations in the drywell and in the suppression chamber after the accident. It is clear from these figures that the pressure inside the containment vessel reaches its maximum pressure of about 250 kPa[gage] in about 28 seconds after the accident. This is lower than 310 kPa[gage], the maximum allowable working pressure of the containment vessel. Because of the activation of the Containment Vessel Spray Cooling System, the pressure in the containment vessel can be lowered to the atmospheric pressure. The temperature in the drywell and the pool water temperature of the suppression chamber reach about 138 degree-C and 97 degree-C, respectively. These are lower than the maximum allowable working temperatures of 171 degree-C and 104 degree-C, respectively. 3.5.5.4 Review of Conformance to Acceptance Criteria As shown in section 3.5.5.3 “Analysis of Accident Process”, the temperature in the containment (temperature of the drywell and pool water temperature in the suppression chamber) does not exceed the maximum operating temperature, and the pressure applied to the boundary of the reactor 3. Deterministic Safety Analysis Ver. 0 77 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C containment is lower than the maximum operating pressure. Accordingly, 2) and 3) in “3.2.1.2 Design Basis Accidents” are met. 3.5.6 Conclusions In this section, some examples of infrequent design basis faults based on Hitachi-GE practice in Japan are presented. As indicated in the sections of "Review of conformance to acceptance criteria" for each fault, they meet acceptance criteria in Japan for all assumed faults. DSA for infrequent design basis faults on UK ABWR will be performed to confirm the adequacy of the safety design and the suitability and sufficiency of the safety measures against target 4 in HSE SAPs in Step2. 3. Deterministic Safety Analysis Ver. 0 78 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C Table 3.5.2-1 Main analysis conditions for loss of coolant accidents [4] Item Value used Reactor thermal power Approx. 102% of the rated power (4,005MW) Maximum linear heat generation rate 44.0 kW/m × 1.02 Core flow rate 90% of the rated flow rate (47.0 × 103 t/h) Reactor dome pressure 7.17 MPa [gage] Core inlet enthalpy 1.23 MJ/kg High pressure core flooder system flow rate (rated value) 727 m3/h (At 0.69 MPa [dif] per pump)* Low pressure flooder system flow rate (rated value) 954 m3/h (At 0.27 MPa [dif] per pump)* Reactor core isolation cooling system flow rate (rated value) 182 m3/h (At 8.12 to 1.03 MPa [dif] per pump)* Setpoints for reactor water level low (main steam isolation valve closed), high pressure core flooder system, reactor core isolation cooling system (core cooling function), and emergency diesel power generator (divisions II and III) Level 1.5 Setpoints for reactor water level low (low pressure flooder system and emergency diesel power generator (division I) starting, automatic depressurization system) Level 1 *: MPa [dif] : differential pressure between reactor pressure vessel and water source Table 3.5.2-2 Amounts of Fission Products Released during Loss of Coolant Accidents [4] Fission products Amounts released (Bq) Noble gases (converted into γ ray energy of 0.5 MeV) Iodine (I-131 equivalent) 3. Deterministic Safety Analysis Ver. 0 Approx. 3.5 × 1011 Approx. 6.3 × l06 79 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C Table 3.5.2-3 Off-Site Effective Dose Equivalence during Loss of Coolant Accidents [4] Effective dose equivalence (mSv) Approx. 1.5 × 10-5 Kashiwazaki-Kariwa Unit 7 Table 3.5.4-1 Amounts of Fission Products Released during a Main Steam Line Break Accident [4] Amounts released (Bq) Fission products Before main steam isolation After main steam isolation valves are closed valves are closed Noble gas and Halogen, etc.* (converted into γ ray of 0.5 MeV) Iodine (I-131 equivalent amount) Approx. 3.1 × 1012 Approx. 6.1 × 1011 Approx. 3.9 × 1010 Approx. 1.8 × 109 * These products include iodine and are treated from the viewpoint of evaluation of effective dose equivalent due to external radiation exposure. Table 3.5.4-2 Off-Site Effective Dose Equivalent at a Main Steam Line Break Accident [4] Effective dose equivalence (mSv) Kashiwazaki-Kariwa Unit 7 Approx. 1.7 × 10-2 3. Deterministic Safety Analysis Ver. 0 80 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Core flow rate (ratio to the rated value) Revision C Time (s) Fig. 3.5.2-1 Variations of core flow rate during a double-ended break accident of HPCF piping [4] 3. Deterministic Safety Analysis Ver. 0 81 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Reactor water level (m) (water level inside core shroud) Revision C Top of active fuel Bottom of active fuel Time (s) Fig. 3.5.2-2 Variations of reactor water level during a double-ended break accident of HPCF piping (with actuation of Reactor Core Isolation Cooling System, two pumps of Low Pressure Flooder System) [4] 3. Deterministic Safety Analysis Ver. 0 82 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Reactor pressure Revision C Time (s) Fig. 3.5.2-3 Variations of core average pressure during complete break accident of Peak cladding temperature (˚C) HPCF piping (with actuation of Reactor core isolation cooling system and two units of Low pressure flooder system) [4] Time (s) Fig. 3.5.2-4 Temperature change at the position giving the maximum temperature of the fuel cladding at an accident of complete break of the HPCF lines (with actuation of Reactor core isolation cooling system and two units of Low pressure flooder system) [4] 3. Deterministic Safety Analysis Ver. 0 83 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C Circumferential stress 1. 2. 2. 3. 1. 4. 5. 6. 7. 8. 8. 8. 8. 8. 8. 8. 8. 8. 8. Cladding temperature (˚C) Key: 1. (not irradiated) 3. (TREAT tests) 2. 4. 5. 6. 7. 8. (irradiated) (in air, one fuel rod) (already oxidized, one fuel rod) (in air, nine fuel rods, test I) (in air, nine fuel rods, test II) (Vallecitos data) Fig. 3.5.2-5 Relationship between fuel cladding temperature and fuel cladding stress in the circumferential direction at time when rapture occurs in fuel rods 3. Deterministic Safety Analysis Ver. 0 84 NOT PROTECTIVELY MARKED Form05/00 UK ABWR NOT PROTECTIVELY MARKED GDA Preliminary Safety Report Revision C Fig. 3.5.2-6 Process of release of noble gases into the atmosphere during loss of coolant accidents (values converted into gamma rays of 0.5 MeV) [4] 3. Deterministic Safety Analysis Ver. 0 85 NOT PROTECTIVELY MARKED Form05/00 UK ABWR NOT PROTECTIVELY MARKED GDA Preliminary Safety Report Revision C Fig. 3.5.2-7 Process of release of iodine into air during loss of coolant accidents (I-131 equivalent) [4] 3. Deterministic Safety Analysis Ver. 0 86 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C Time (s) 1. 2. 3. 4. 1. 2. 3. 4. Neutron flux (%) Average surface thermal flux (%) Core inlet flow (%) Reactor steam flow (%) Time (s) Variations in reactor water level (× 5 cm) Variations in reactor pressure (× 0.02 MPa) Turbine steam flow (%) Flow of safety valves (%) Fig. 3.5.3-1 Variations during Loss of reactor coolant flow accident (Trip of all reactor internal pumps accident) [4] 3. Deterministic Safety Analysis Ver. 0 87 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Peak cladding temperature (˚C) Revision C Time (s) Fig. 3.5.3-2 Temperature variations at positions giving maximum temperature of fuel cladding during Loss of reactor coolant flow accident (Trip of all reactor internal pumps accident) [4] 3. Deterministic Safety Analysis Ver. 0 88 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report Amount of discharged coolant (kg/s) UK ABWR Revision C Steam Flow Two Phase Flow Time (s) Fig. 3.5.4-1 Variation of amount of discharged coolant at a main steam line break accident [4] 3. Deterministic Safety Analysis Ver. 0 89 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C Core flow Average core pressure Core flow rate (ratio to the rated value) Average core Time (s) Fig.3.5.4-2 Change of core flow and average core pressure at a main steam line break accident [4] 3. Deterministic Safety Analysis Ver. 0 90 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Peak cladding temperature (˚C) Revision C Time (s) Fig. 3.5.4-3 Temperature change at the position giving the maximum temperature of the fuel cladding at a main steam line break accident [4] 3. Deterministic Safety Analysis Ver. 0 91 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C 16% Fig. 3.5.4-4 Process of Noble gas release into atmosphere at a main steam line break accident (converted into γ ray energy of 0.5 MeV) [4] 3. Deterministic Safety Analysis Ver. 0 92 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C 16 40t 3.9 3.1 Fig. 3.5.4-5 Process of Halogen release into atmospheres at a main steam line break accident [4] 3. Deterministic Safety Analysis Ver. 0 93 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C Pressure in the containment vessel Drywell Suppression Chamber One High Pressure Core Flooder System and two Residual Heat Removal Systems actuated Time (s) Drywell temperature and suppression chamber pool water temperature (˚C) Fig. 3.5.5-1 Pressure variations in drywell and suppression chamber during complete break accident of feedwater piping [4] Drywell Suppression Chamber One High Pressure Core Flooder System and two Residual Heat Removal Systems actuated Time (s) Fig. 3.5.5-2 Variations of the temperature in the drywell and the pool water temperature in the suppression chamber during complete break accident of feedwater line [4] 3. Deterministic Safety Analysis Ver. 0 94 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C 3.6 Beyond Design Basis Faults 3.6.1 Frequent faults with common mode failure of engineered safety system DSA for UK ABWR will be performed in Steps 2 and 3. Therefore, this section shows example of analysis result for frequent design basis faults with common mode failure of engineered safety systems, which have been performed on the basis of Hitachi-GE practice, and UK provision will be discussed. This example explains the causes of the occurrence, the safety function and the fault sequence based on analysis results. 3.6.1.1 Evaluated Events Based on PSA, fault sequences that could result in significant core damage are selected as the events to be assessed. They are selected on the basis of following point of view. 1) The core is significantly damaged by multi-systems failures caused by common cause failures or functional dependency. 2) The time margin to implement countermeasure for core damage prevention is small. 3) The fault sequence is representative among the fault sequence group. The following fault sequence groups are identified to be assessed. However, these fault sequence groups will be re-assessed in Steps 2 and 3 based on UK practice and rules. (a) High and low pressure coolant injection failure (b) High pressure coolant injection failure and depressurization failure (c) Loss of off-site power and failure of coolant injection with limited system (Station blackout) (d) Decay heat removal failure (e) Maintaining sub-criticality failure (f) Coolant injection failure at LOCA (g) Containment bypass (Interface system LOCA) Fault sequences of beyond design basis faults will be analyzed using realistic and best estimate assumptions. As an example, the analysis result of the following event chosen from the listed above is shown in this section. (1) Loss of off-site power and failure of coolant injection with limited system (Station blackout) 3. Deterministic Safety Analysis Ver. 0 95 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C 3.6.1.2 Loss of off-site power and failure of coolant injection with limited system (Long Term Station blackout) (1) Event and its success scenario After station blackout occurs, the safety systems and components are all assumed to fail. Significant core-damage can be avoided by maintaining the reactor water level at the proper level by water injection using RCIC (Reactor Core Isolation Cooling system). Water injection is implemented by reactor depressurization and alternative low pressure coolant injection system when gas turbine generator and alternative low pressure coolant injection system are available. This success scenario is based on Hitachi-GE practice. This is an extreme case. The UK provision will be discussed. (2) Analysis condition [ This information is removed intentionally ] (3) Analysis Results [ This information is removed intentionally ] 3. Deterministic Safety Analysis Ver. 0 96 NOT PROTECTIVELY MARKED Form05/00 UK ABWR NOT PROTECTIVELY MARKED GDA Preliminary Safety Report Revision C [ This information is removed intentionally ] 3. Deterministic Safety Analysis Ver. 0 97 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C 3.6.2 Severe accident analysis DSA for UK ABWR will be performed in Steps 2 and 3. Therefore, this section shows example of analysis result for severe accident analysis, which have been performed on the basis of Hitachi-GE practice, and UK provision will be discussed. 3.6.2.1 Evaluated Events In the accident progression, loss of core cooling leads to core melt condition. There are following uncertain threats on containment integrity for core damage condition. (a) Containment overpressure/overtemperature failure (Static loading) (b) High pressure molten core ejection/Direct containment heating (c) Interaction between molten core and coolant outside the RPV (d) Hydrogen combustion (e) Direct containment contact (shell attack) (f) Molten core-concrete interaction In this analysis, representative accident sequences with core melt are analyzed to justify the capability of overpressure and overtemperature control. The other uncertain phenomena will be discussed in the PSA section. As an example, the analysis result of the following event chosen from the listed above is shown in this section. (1) Containment overpressure/overtemperature failure (Static loading) 3.6.2.2 Containment overpressure/overtemperature failure (Static loading) (1) Event and its success scenario The containment pressure and temperature are slowly increased by accumulation of steam generated by decay heat of the molten core and high temperature coolant in the containment and non-condensable gas generated by interaction between metal and water, and it could lead the containment failure. The molten core is cooled using reactor water injection and alternative containment spray cooling system, and the decay heat is removed from containment by containment venting so that containment failure and significant release of any radioactive material into the environment are avoided. This success scenario is based on Hitachi-GE practice and the UK provision will be discussed. 3. Deterministic Safety Analysis Ver. 0 98 NOT PROTECTIVELY MARKED Form05/00 UK ABWR NOT PROTECTIVELY MARKED GDA Preliminary Safety Report Revision C (2) Analysis condition [ This information is removed intentionally ] (3) Analysis Results [ This information is removed intentionally ] 3. Deterministic Safety Analysis Ver. 0 99 NOT PROTECTIVELY MARKED Form05/00 UK ABWR NOT PROTECTIVELY MARKED GDA Preliminary Safety Report Revision C 3.7 Conclusions In this section, examples of DSA performed based on Hitachi-GE practice are presented. According to these analysis results, acceptance criteria in Japan are met by safety systems on Japanese ABWR. DSA for UK ABWR will be performed to confirm the adequacy of the safety design and the suitability and sufficiency of the safety measures against target 4 in HSE SAPs in Step 2. 3. Deterministic Safety Analysis Ver. 0 100 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C 4. Probabilistic Safety Assessment PSA (Probabilistic Safety Assessment) provides an integrated and structured safety analysis that combines engineering and operational features in a consistent overall quantification framework. This provides a logical basis for identifying any relative weaknesses in the design and be reflected according by the quantitative outputs. Then, PSA is useful tool to estimate vulnerabilities in plant and effectiveness of countermeasures. In this section, requirement and assumption as high level information on method, and some examples and indicative results by PSA are described. 4. Probabilistic Safety Assessment Ver. 0 101 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C 4.1 Requirements and Assumptions This sub-section proposes and describes targets, main assumptions, scope of PSA, and success criteria to be adopted for the UK ABWR PSA. (1) Target UK ABWR design should be demonstrated to comply with Targets 7, 8, and 9 in relation to PSA. HSE SAPs defines two types of safety level with different numerical values. These are BSLs (Basic safety Levels) and BSOs (Basic Safety Objectives). The BSL must be met as a minimum. The BSOs form benchmarks that reflect modern nuclear safety standards and expectations. The results from the UK ABWR PSA study will be explained in relation to these numerical targets. a. Target 7 To confirm compliance with Target 7 of HSE SAPs, the individual risk of death to a person off the site, from on-site accidents that results in exposure to ionizing radiation, will be assessed and will be below 10-7 /year. The corresponding BSO and BSL for Target 7 are: BSL : 1 x 10-4 pa BSO : 1 x 10-7 pa b. Target 8 To confirm compliance with Target 8 of HSE SAPs, the summated frequency of accidents for the UK ABWR leading to individual doses of different magnitudes will be assessed against the limits given in Table 4.1-1. The UKABWR design will need to be shown that the total frequency of accidents in each of the different dose categories in the table is below the Maximum Tolerable Limit. The design objective will be to achieve an accident frequency in each dose category that is below the Broadly Acceptable Level. Table 4.1-1 Target 8 of HSE SAPs Effective Dose Total predicted frequency per year BSL BSO Maximum Tolerable Limit Broadly Acceptable Limit 0.1 - 1 1 1 x 10-2 1 - 10 1 x 10-1 1 x 10-3 10 -100 1 x 10-2 1 x 10-4 100 - 1000 1 x 10-3 1 x 10-5 >1000 1 x 10-4 1 x 10-6 (mSv) 4. Probabilistic Safety Assessment Ver. 0 102 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C c. Target 9 To confirm compliance with Target 9 of HSE SAPs, the total risk of 100 or more fatalities, either immediate or eventual, from on-site accidents that result in exposure to ionizing radiation, will be assessed and will be below 10-7 /year. The corresponding BSO and BSL for Target 9 are: BSL : 1 x 10-5 pa BSO : 1 x 10-7 pa (2) Main Assumptions For UK ABWR PSA, all of the design information in the GDA process will be applied at the beginning of the assessment. Lack of information will be covered by following assumptions as examples: - Generic data for component reliability is applicable. - Same procedure of maintenance and surveillance test is applied from existing plant. - For human error probability, screening value is applied. (3) Scope of PSA A full scope Level 3 PSA, i.e. a PSA which covers all sources of radioactivity at the facility, all types of initiating faults, and all operational modes, will be provided in the UK ABWR PCSR. With regard to sources of radioactivity, reactor and spent fuel pool will be assessed. Other sources, which may have significant impact on public dose, will also be assessed. For initiating faults and operational modes, all type of initiating faults and operational modes will be included and the use of screening and bounding arguments will be justified. (4) Success Criteria for Level 1 PSA Level 1 PSA estimates core damage frequency. Therefore, success of fundamental functions combination to prevent core damage will be defined by using necessary minimum function or systems. The success criteria for level 1 PSA consist of systems whose functions are; - Reactivity control, - Core cooling, and - Long-term heat removal. 4. Probabilistic Safety Assessment Ver. 0 103 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C A definition of success and failure for each function or system will be provided based on realistic analysis. (5) Success Criteria for Level 2 PSA Level 2 PSA estimates large release frequency. Therefore, success of functions to prevent large release in conjunction with core damage will be defined by using necessary functions or systems. The success criteria for level 2 PSA consist of systems whose functions are; - Damaged core cooling, and - Decay heat removal A definition of success and failure for each function or system will be provided based on realistic analysis. 4. Probabilistic Safety Assessment Ver. 0 104 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C 4.2 Internal Event Level 1 PSA This sub-section describes model description, data for risk analysis, and indicative results from experience and CDF estimate, regarding to internal event level 1 PSA at power and shutdown. 4.2.1 Internal Event Level 1 PSA (Reactor core during normal operation) 4.2.1.1 Procedure of Internal Event Level 1 PSA A standard for internal level 1 PSA during power operation established by Atomic Energy Society of Japan [5] provides the procedure of the PSA as follows. 1. Investigation of plant information 2. Selection of initiating faults and estimation of their frequencies 3. Establishment of success criteria 4. Analysis of accident sequences 5. System reliability analysis 6. Human reliability analysis 7. Preparation of necessary parameters 8. Quantification of accident sequences 9. Uncertainty analysis and sensitivity analysis 10. Documentation 4.2.1.2 Model and Data (1) Initiating Faults A range of faults sequences, including multiple failures is considered in the PSA. Transient, LOCA and manual shutdown are identified based on review of industry PSAs and guidance. Transient event is composed of several groups which are developed by the plant condition and features of the initiating events. LOCA is divided into 3 groups considering required mitigation system. Manual shutdown is composed of normal shutdown and other manual shutdowns with loss of emergency system or support system. Initiating faults frequencies for transient and manual shutdown are estimated based on the Utility Requirements Document (URD) [6], or operating practices in Japan, where applicable. Initiating faults frequencies for LOCA is developed by NUREG-1829[7] and NUREG-5750[8]. Followings are example of initiating events in a PSA of Japanese ABWR. Table 4.2.1.2-1 shows 4. Probabilistic Safety Assessment Ver. 0 105 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C example of detail transient event in the PSA. Transient: • Non-isolation events • Isolation events • Loss of all feedwater flow • Decrease in reactor water level events • Failure of Reactor Protection System (RPS), etc. • Loss of off-site power • Inadvertent open relief valve (IORV) Loss of coolant accident (LOCA): • Large LOCA • Medium LOCA • Small LOCA Manual shutdown: • Planned normal shutdown • Loss of emergency AC power supply • Loss of emergency DC power supply • Loss of emergency reactor cooling water system(RCW) • Failure of turbine support systems (2) Accident Sequence Analysis Accident sequence event tree structures and end states are defined for each initiating fault category based on the expected response of mitigating systems. Success criteria are established to determine the minimum set of trains or components that will successfully perform an intended function. The success criteria are incorporated into the fault trees to define the minimum set of faults that lead to functional failure. Followings are important functions and main success criteria for them. Reactivity Control: RPS (Reactor Protection system) ARI (Alternative Rod Insertion system) and RPT (Recirculation Pump Trip) SLC (Stand by Liquid Control system) and RPT (Recirculation Pump Trip) Core Cooling: 4. Probabilistic Safety Assessment Ver. 0 106 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C Feedwater system/Condensate system RCIC HPCF LPFL and RPV depressurization Alternative water injection system and RPV depressurization Long-term Cooling: RHR Containment Venting with water addition Indicative success criteria for UK ABWR based on previous studies for ABWR PSA are shown in Table 4.2.1.2-2. Example of event trees for non-isolation, which is the basis of other event trees, is shown in Fig.4.2.1.2-1. Adequacy of the success criteria is demonstrated by deterministic analyses with following analysis codes. Initiating time of each mitigation system with which core damage is prevented is calculated. Reactivity control: ODYN, or REDY and SCAT Core cooling: SAFER or MAAP Long-term Cooling: MAAP Core damage occurs directly from failure of the core cooling key safety function, and indirectly from the failure of reactivity control, RPV overpressure protection, or containment heat removal. Acceptance criteria used as the PSA success criteria are realistic ones, which are described below. Reactivity Control To achieve sub-criticality and maintain the reactor in a sub-critical state RPV Overpressure Protection To maintain the reactor coolant pressure boundary below 120 percents of the maximum design pressure Core Cooling To maintain a peak cladding temperature (PCT) below 1200 degree-C for establishing adequacy of coolant inventory (This criterion defines the onset of core damage.) 4. Probabilistic Safety Assessment Ver. 0 107 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C Long-term Heat Removal (Containment Heat Removal) To maintain the containment pressure below the ultimate containment strength End state of the accident sequences is safe shutdown state defined for general ABWR. Mission time is 24 hour for Hitachi-GE practice. For UK ABWR analysis, mission time is determined considering the time for achieving the end state. (3) System Analysis System fault trees are developed based on the standard industry techniques and will reflect the UK ABWR system design. The systems which correspond to the functional headings described in the event trees have their system fault trees. A PSA support document [9] contains the following items: functional description, assumptions, system description, automatic and manual control, system interfaces, system testing, system maintenance, CCF (Common Cause Failures) and fault tree analysis results. Component failure probabilities are estimated from the generic industry data such as URD [6], JANSI [10] and so on. Appropriate data base will be used for UK ABWR. Data and the methodology for maintenance and test unavailability are based on the generic data or experiences of Japanese ABWR. Common cause failure rate will be developed from a generic data. (4) Human Reliability Analysis Task analyses and human error probability assessments are performed where operator actions are shown to have a significant effect on risk. The PSA operator actions are used to develop specific operator actions in the emergency response procedures. The methodology used in the existing study is in accordance with the THERP (NUREG/CR-1278) [10] and considers omission error and commission error. For human reliability analysis of UK ABWR PSA, THERP [10] or Accident Sequence Evaluation Program HRA Procedure (ASEP) [10] is used. Pre-accident Human Error considers recovery in the end of test/maintenance (ex. valve operation error). Post-accident Human Error considers manual operations, and recoveries. (5) Quantification The purpose of the core damage frequency quantification is to obtain the Boolean equation corresponding to the final event: “core damage”. The equation is developed in terms of minimal cut-sets, which represent the minimal combinations of events that result in core damage. Quantification of the model results in overall core damage frequency, as well as core damage frequency as a function of initiating faults or plant damage states (PDSs). 4. Probabilistic Safety Assessment Ver. 0 108 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C The computational tool for quantification of PSA for Japanese ABWR is NUPRA. NUPRA, CAFTA, or other appropriate tool will be selected for PSA of UK ABWR GDA. (6) Plant Damage State (PDS) There are three essential functions for ABWR. Headings of event trees are generally lined up in a following order. First, the reactor reactivity control function; Second, core cooling functions, which are the high pressure coolant injection into the RPV, or the RPV depressurization and the low pressure coolant injection into the RPV; and Third, long-term heat removal function. For example, in the event tree shown in Fig.4.2.1.1-1, a heading “C” is for the reactor reactivity control function, headings from “Q” to “VD” are for the core cooling function, and headings from “WP” to “WD” are for the long-term heat removal function. A heading “M” is for the pressure relief function to avoid over-pressure of the RPV. First, the PDS in which the reactor reactivity control of the first stage fails is defined as a “TC”. Second, there are several PDSs defined for failure of core cooling. The PDS in which the high pressure core injection and the RPV depressurization fail is defined as a “TQUX”. The PDS with failure of the high pressure core injection followed by successful depressurization and failure of low pressure core injection is defined as a “TQUV”. The PDS with failure of water injection to the core at LOCA is defined as “LOCA”. The PDS LOCA is sometimes divided into AE, S1E, S2E which are large LOCA (A), medium LOCA (S1) and small LOCA (S2) followed by failure of coolant injection to the core (E), respectively. Third, the PDS in which long-term heat removal fails is defined as a “TW”. Separately from the above ones, the PDS in which loss of electrical power necessary for above functions occurs is defined as a “TB”. The short definitions of PDSs are summarized again below. TQUX : High pressure coolant injection failure, and depressurization failure TQUV : High/low pressure injection failures 4. Probabilistic Safety Assessment Ver. 0 109 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C TB : Loss of off-site power and failure of coolant injection with limited system TW : Decay heat removal failure TC : Maintaining sub-criticality failure LOCA : Coolant injection failure at LOCA Detail definitions of the PDSs as the interface between Level 1 PSA process and Level 2 PSA process are described in section 4.3.1.2. 4. Probabilistic Safety Assessment Ver. 0 110 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C Table 4.2.1.2-1 Initiating events Broad category Manual Shutdowns Initiating event Planned normal shutdown Non-isolation event Anticipated Transients Isolation event Loss of all feedwater flow Decrease in reactor water level Failure of RPS, etc. Loss of offsite power LOCAs Special Initiators Inadvertent opening of relief valve Large LOCA Medium LOCA Small LOCA Loss of emergency AC power supply Loss of emergency DC power supply Loss of emergency reactor cooling water system (RCW) Failure of turbine support systems Postulated disturbances Planned normal shutdowns 1. Electric load rejection (w/ bypass) 2. Turbine trip (w/ bypass) 3. Pressure regulator fails closed 4. Turbine bypass or control valves cause increased pressure 5. Trip of all recirculation pumps 6. Recirculation pump seizure 7. Feed water -increasing flow at power 8. High feedwater flow during startup or shutdown 9. Inadvertent startup of HPCF 10. One MSIV closure 11. Recirculation control failure - increasing flow 12. Loss of feedwater heater 1. MSIV closure (all) 2. Partial MSIV closure 3. Pressure regulator fails open (leading to MSIV closure) 4. Turbine bypass fails open 5. Electric load rejection with bypass valve failure 6. Turbine trip with turbine bypass valve failure 7. Loss of normal condenser vacuum 1. Loss of all feedwater flow 1. Trip of one feedwater pump (or condensate pump) 2. Feedwater - low flow 3. Low feedwater flow during startup or shutdown 1. Rod withdrawal at power 2. High flux due to rod withdrawal at startup 3. Detected fault in rector protection system 4. Scram due to plant occurrences 5. Spurious trip via instrumentation, RPS fault 1. Loss of offsite power 2. Loss of auxiliary power 1. Inadvertent opening of a safety/relief valve (stuck) 4. Probabilistic Safety Assessment Ver. 0 111 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C Table 4.2.1.2-2 Success criteria to prevent core damage for ABWR [ This information is removed intentionally 4. Probabilistic Safety Assessment Ver. 0 ] 112 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C Nonisolation events Scram S/R valve open S/R valve close Feed water system HPCF Reactor decompression LPFL Alternative pouring water PCS RHR TT C M P Q U X V VD WP WR RHR Alternative recovery cooling WRR Sequance group WD - - - - - TW - - - - TW - - - - TW TQUV TQUX - - - TW - - - TW - - - TW - - - TW TQUV TQUX - - Fig. 4.2.1.2-1 Example of event tree 4. Probabilistic Safety Assessment Ver. 0 113 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR 4.2.1.3 Revision C Indicative results (1) Results from Japanese ABWR PSA Fig.4.2.1.3-1 shows plant configurations for PSA. There are mainly 4 plant configurations with history of adding AM (Accident Management) strategies. For each plant configuration, following PSA results are defined. Some AM strategies are considered from an initial stage of design, which are manual actuation of ECCS, manual depressurization of RPV, alternative coolant injection, and so on. PSA for this plant configuration is called as “PSA before the AM preparation”. In 1992, circular notice for preparations of accident management in a nuclear power plant is issued by Ministry of International Trade and Industry in Japan. Corresponding to this, new AM strategies are added, which are hardened containment venting, multi-unit cross tie, coolant injection with a pump of Fire Protection system (diesel-driven), and so on. PSA for this plant configuration is called as “PSA after AM preparation”. In this section, the result of “PSA after AM preparation” is shown as an example. Existing internal level 1 PSA results for Japanese ABWR are introduced here. Reference documents are shown below. • “The evaluation on accident management review report on Chugoku Electric Power Co. INC. Shimane 3rd NPP. (in Japanese)”, Nuclear and Industrial Safety Agency (NISA), Aug. 2010 [13] • “The report of accident management review for Shimane 3rd NPP (in Japanese)”, Chugoku Electric Power Co. INC, Apr. 2010 [14] • “The report of Probabilistic Safety Assessment for Shimane 3rd NPP (in Japanese)”, Chugoku Electric Power Co. INC, Apr. 2010 [15] Table 4.2.1.3-1 shows PSA results calculated by utility and JNES as a cross-check on utility report. CDF of the both PSAs are on the order of 10-9. Mitigation features credited for the PSA are described in Table 4.2.1.3-2. Fig. 4.2.1.3-2 shows CDF for each plant damage state. Risk contributors for each plant damage states in ABWR used to be following characteristic. TB is the largest contributor for total CDF in the calculation results of the utility and the JNES. [ This information is removed intentionally calculation results of the utility. [ ] TQUX is the second largest contributor in the This information is removed intentionally sequence is the third largest contributor in the calculation results of the utility. 4. Probabilistic Safety Assessment Ver. 0 ] LOCA [ This 114 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C information is removed intentionally ] 4. Probabilistic Safety Assessment Ver. 0 115 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C The result discussed in this section “PSA before the AM preparation” Mitigation systems AM strategies Plant only for design before a circular configuration basis accident notice [*1] “PSA after the AM preparation” AM strategies added after a circular notice [*1] AM strategies after Fukushima accident [*1] Circular notice of Ministry of International Trade and Industry, “Preparation of accident management in a nuclear power plant” (July 1992) [*1] Circular notice of Ministry of International Trade and Industry, “Preparations of accident management in a nuclear power plant” (July 1992) Fig. 4.2.1.3-1 Plant configurations for PSA Table 4.2.1.3-1 PSA results for Japanese ABWR Core damage frequency (/reactor year) Utility analysis 1.2×10-9 Cross check analysis of 2.4×10-9 JNES 4. Probabilistic Safety Assessment Ver. 0 116 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C Table 4.2.1.3-2 Mitigation features credited in Japanese ABWR PSA [ This information is removed intentionally 4. Probabilistic Safety Assessment Ver. 0 ] 117 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C Core Damage Frequency(/y) 1.00E-08 Utility JNES 1.00E-09 1.00E-10 1.00E-11 1.00E-12 TQUX TQUV TB TW TC LOCA Fig. 4.2.1.3-2 CDF for each plant damage state (This figure is developed from the data in ref. [15]) 4. Probabilistic Safety Assessment Ver. 0 118 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C (2)Results from USABWR DCD PSA This section is discussed based on Hitachi-GE experience and estimates. Other existing PSA result is that for US ABWR conducted by GE-Hitachi, which is referred in US ABWR DCD (Design Certification Document) [16] and NUREG-1503 [17]. Basic configurations of USA BWR and Japanese ABWR are the same. Therefore, PSA results of US ABWR are useful output for discussing sensitivity of modelling and database to the CDF and its break-down. GE-Hitachi estimated the total CDF from internal events for US ABWR to be 1.6E-7 per year, which is about two orders higher than that of Japanese ABWR. The initiating events that significantly contribute to the CDF are loss of offsite power and loss of feedwater/isolation events. Among them, SBO is the largest contributor. Table 4.2.1.3-2 shows the comparison of database and modelling between US ABWR DCD PSA and Japanese ABWR PSA. Based on Hitachi-GE experience, Hitachi-GE estimates that followings seem to be the main differences; In terms of database of initiating event frequency and component failure rate, Japanese ABWR PSA uses national records in Japan [10], which are generally less conservative than those for US ABWR DCD PSA. In terms of CCF (Common Cause Failure), US ABWR DCD PSA considers dependency among whole systems of ECCS (RCIC, 2 HPCFs, 3 LPFLs, and ADS) as CCF of transmission network, while Japanese ABWR PSA considers dependency among whole systems of ECCS as CCF of transmitters of reactor water level and digital systems. Only Japanese ABWR PSA considers CCF of valves/pumps/fans among intra-system redundant parts and also among inter-systems. In terms of human factors, both PSA considers following human actions and errors. Manual actuation of coolant injection with ECCS, depressurization of RPV, and RHR Pre-accident human errors (Leaving valves closed after maintenance, miscalibration of sensors (Japanese ABWR PSA include it in CCF of sensors.) US ABWR DCD PSA considers only human errors for the failure of coolant injection into the RPV with feedwater and condensate system, while Japanese ABWR PSA has fault trees for them, which include human errors (considering both component error and human error) In terms of recovery, both PSA considers recovery of off-site power, EDG and RHR. In 4. Probabilistic Safety Assessment Ver. 0 119 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C addition, recovery of feed water system for initiating event of loss of partial or all feed water flow, and support system during unplanned manual shutdown events (or called special initiators) due to loss of support system are considered. For US ABWR DCD PSA, unavailability values due to T&M (Test and Maintenance) for RCIC, HPCF-B, HPCF-C, RHR-A, RHR-B, and RHR-C are set to 2%, while Japanese ABWR PSA calculates unavailability of each system considering the maintenance rule of safety regulations. The resulting unavailability of each system in Japanese ABWR PSA is much smaller than that in US ABWR. In terms of self-diagnosis function of digital systems, only Japanese ABWR PSA considers this function. In terms of mitigation features, major differences between US ABWR and Japanese ABWR are summarized in Table 4.2.1.2-2. For alternative AC power supply, combustion turbine generator is applied for US ABWR, while multi-unit cross tie is applied for conventional Japanese ABWRs. After the Fukushima accident, alternative power source is planned to be added. Air-cooled EDG is considered as one of the options in UK ABWR. For RPV depressurization during transient events, transient ADS, which initiates ADS with low reactor water level and a timer, is applied for US ABWR, while manual depressurization is applied for conventional Japanese ABWR because ADS is designed for LOCA, which initiates with both signal of high D/W pressure and low reactor water level. For SLC injection, automatic initiation is applied for US ABWR, while manual initiation is applied for Japanese ABWR. For alternative water injection system, ACIWA (AC-Independent Water Addition system) to inject coolant into the RPV and D/W, which utilize fire protection system and a fire truck is applied for US ABWR, while alternative water injection with fire protection system (including diesel-driven pump) or Make-Up Water Condensate system (MUWC) to inject coolant into the RPV and D/W is applied for Japanese ABWR. 4. Probabilistic Safety Assessment Ver. 0 120 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C Table 4.2.1.3-3 Comparison of database and modelling between US ABWR DCD PSA and Japanese ABWR PSA USABWR Japanese ABWR Initiating event frequency Transients : URD LOCA: WASH-1400 Transients: National BWR record in Japan LOCA: NUREG-1829, and NUREG/CR-5750 Component failure rate Failure Rate Data Manual for GE BWR Components National record in Japan [10] Common Cause Failure Following dependent failures are considered: Following dependent failures are considered: Ex. transmission network, sensors and transmitters (including miscalibration), digital systems, EDGs, batteries, SRVs Ex. sensors and transmitters, digital systems, EDGs, batteries and some active component of HPCFs, LPFLs/RHRs, RCWs/RSWs, HVACs, DGFOs (Generic component CCF is additionally considered with MGL (Multiple Greek Method).) Beta factors taken from NUREG-1150, NUREG/CR-1205 (Rev.1), NUREG/CR-1363 (Rev.1), NUREG/CR-2771, SECY-83-293, P. A27 THERP Human factor THERP Recovery Recovery of off-site power, EDG and RHR are considered. Recovery of off-site power, EDG, and RHR are considered. Recovery of feedwater system and support systems are considered depending on an initiating event. Test and Maintenance 0.02 unavailability for each RCIC, HPCF, RHR Unavailability by test and maintenance is calculated for RCIC, HPCF, RHR, RCW/RSW, EDG (Unavailability is lower than 10-3.) Self-diagnosis function of digital system Credited Credited (With some percentage, faults are found out by self-diagnosis) Major differences in mitigation features Combustion turbine generator Transient ADS Automatic SLC AC-independent water addition system Multi-unit cross tie Manual actuation of ADS Manual SLC Alternative coolant injection system 4. Probabilistic Safety Assessment Ver. 0 121 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C (3) Discussion on the order of CDF The total CDFs from existing PSA results are 1.2×10-9 per year and 1.6×10-7 per year for Japanese ABWR PSA and US ABWR DCD PSA, respectively. This difference is two orders of magnitude. The potential contributors to this difference are; - Level of initiating event frequency - Level of component failure probability including CCF probability - Credit of recoveries When CDF by PDSs for Japanese ABWR are compared with that of US ABWRs, the ratio of the CDFs from each PDS is of similar level for all the PDSs. Then, the difference of initiating event frequencies seems to be the most dominant factor to contribute this difference. The sensitivity analyses regarding the initiating event frequency and recoveries are presented in the PSA support document [9]. 4. Probabilistic Safety Assessment Ver. 0 122 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR 4.2.2 Revision C Shutdown PSA (Internal Level 1) Section 4.2.2 describes an overview of shutdown PSA (internal level 1) of ABWR reactor core. The description covers the procedure (4.2.2.1), the concept and model (4.2.2.2) and the insights from indicative results (4.2.2.3) based on the practice and experience of Japanese ABWR with emphasizing the characteristics of shutdown PSA against internal level 1 PSA during normal operation. It should be noted that the Fukushima countermeasures to be implemented into UK ABWR are not included here. 4.2.2.1 Procedure of shutdown PSA A standard for shutdown PSA established by Atomic Energy Society of Japan [18] provides the procedure of shutdown PSA as follows. 1. Investigation of plant information 2. Classification of Plant Operating State (POS) 3. Selection of initiating faults and estimation of their frequencies 4. Establishment of success criteria 5. Analysis of accident sequences 6. System reliability analysis 7. Human reliability analysis 8. Preparation of necessary parameters 9. Quantification of accident sequences 10. Uncertainty analysis and sensitivity analysis 11. Documentation Those items except No.2 “Classification of POS” are basically the same as those of internal level 1 PSA during normal operation. 4.2.2.2 Model and Data (1) Plant Operating State (POS) In Japanese practice, partial power operation is enveloped by rated power operation in terms of PSA. For BWRs including ABWR, the period between two important operations, “vacuum break of main condensers” and “withdrawal of control rods”, is treated by shutdown PSA as illustrated in Fig. 4.2.2.2-1 because these operations significantly change the conditions of initiating events and mitigating systems. That is to say, the main condensers are not available for decay heat removal during such period. 4. Probabilistic Safety Assessment Ver. 0 123 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C In Japanese ABWR, the plant state treated by shutdown PSA is further divided into 5 sub-states (POSs) because 1) the mitigation systems to be considered change with the process of periodic inspection, 2) the decay heat changes with time, and 3) the water inventory in the RPV changes with the process of periodic inspection. The estimated time to core damage and thus the failure probability of some recovery actions may change among POSs. The example of the five POSs used in Japanese ABWR is describes below according to time series. POS “S”: Transition to reactor cold shutdown: This POS is defined as the period from “vacuum break of main condensers” to “starting the procedure of opening the PCV/RPV top heads”. The water level in RPV is the same as that of normal operation. The decay heat is being removed by one of the three RHRs in the shutdown cooling mode. The mitigation systems to be considered in PSA depend on the procedure of periodic inspection. POS “A”: Transition to opening PCV/RPV top heads: This POS is defined as the period from “starting the procedure of opening the PCV/RPV top heads” to “completing stretch of reactor well”. The decay heat is still large and the water level in RPV is higher than that in the normal operation. The decay heat is being removed by one of the three RHRs in the shutdown cooling mode, which is the same as the status S. The mitigation systems to be considered in PSA depend on the procedure of periodic inspection. POS “B”: Full water level in reactor well: This POS is defined as the period from “completing stretch of reactor well” to “starting drain off of reactor well”. The water inventory in RPV is large, so the heat up of reactor coolant is considerably slow even if the decay heat removal is lost. Usually this status is subdivided according to the available set of mitigation systems. POS “C”: Transition to closing PCV/RPV top heads: This POS is defined as the period from “starting drain off of reactor well” to “completing the closing procedure of the PCV/RPV top heads”. Inspection and maintenance of equipments are still continued in this period. The water level in RPV is higher than that at normal operation and the decay heat is about 1/10 of that just after the reactor shutdown. POS “D”: Preparation of plant startup: 4. Probabilistic Safety Assessment Ver. 0 124 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C This POS is defined as the period from “completing the closing procedure of the PCV/RPV top heads” to “starting CR withdrawal for startup”. During this period, inspection and maintenance of equipments are already completed, so many mitigation systems except the turbine driven RCIC are stand-by status. After the classification, the duration of each POS is established based on a representative case, a particular case, or statistics of periodic inspection according to the purpose of shutdown PSA. For operating plants, the duration of each POS may vary among past periodic inspections. When shutdown PSA is carried out based on statistical application of past inspections, “time window analysis” is an effective method for reflecting the variation of success criteria or time allowance among POSs of the same category (ex. “B”) at different inspections that is caused by the variation the decay heat level. The procedure of the time window analysis for particular POS (ex. “B”) is as follows. 1) The influence of decay heat level on the success criteria or time allowance is analyzed. 2) A POS (ex. “B”) is subdivided into several “time windows” so that identical success criteria or time allowance can be practically applied to the same category of the “time window” among different inspections. 3) CDF per unit time is quantified for each time window. 4) Representative CDF for a POS is estimated by summing up “(CDF per unit time) x (duration of time window)” for all the time windows and all the past inspections of interest. The time window analysis enables us to include the types of shutdown other than periodic inspection, such as unplanned shutdown, refuelling shutdown etc. Reactor Power Time Reactor Power Decreasing PSA at Power Insertion of all CRs Vacuum Breaking of Main Condenser Withdrawing of CRs PSA at Shutdown Rated Power Operation PSA at Power Fig. 4.2.2.2-1 Division of plant state in practice of Japanese ABWR 4. Probabilistic Safety Assessment Ver. 0 125 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C (2) Initiating Faults Generally, initiating faults for shutdown PSA are selected using master logic diagram. An example of master logic diagram for Japanese ABWR is illustrated in fig. 4.2.2.1-2. The potential faults leading to core damage can be mechanical failure of thermal failure of the fuel. The mechanical failure is mainly caused by drop of a fuel bundle itself, so that the fuel failure is localized and it would not lead to excessive core damage. In Japanese practice, the mechanical failure of fuel is not included in the scope of shutdown PSA. The applicability of such treatment to UK ABWR will be carefully discussed after STEP 1. Thermal failure of fuel is caused by a mismatch of heat production and heat removal, which is overpower or insufficient cooling of fuel. Overpower of fuel is potentially caused by CR withdrawal error or miss-loading of fuel bundles. However, reactivity insertion and thus overpower are localized, so that excessive core damage would not occur. In Japanese practice, the thermal failure of fuel by overpower is not included in the scope of shutdown PSA. The applicability of such treatment to UK ABWR will be carefully discussed after step 1. After all, only the thermal failure of fuel due to insufficient cooling is treated in shutdown PSA like level 1 PSA at power in Japanese practice. The insufficient cooling is caused by leakage or boil-off of primary coolant. In conventional BWR plants, the drain line of RHR is connected to the recirculation loop below the reactor core at the shutdown cooling mode. In case of multiple human errors during switchover of RHR shutdown cooling mode, leakage of primary coolant into the suppression pool through that drain line and the inadvertently opened mini flow valve may lead to core uncovery. On the other hand, the position of RHR drain line is above the reactor core region, so that leakage from that line would not directly lead to core uncovery. In shutdown PSA of Japanese ABWR, such leakage is not considered. Break of pipes connected to primary coolant boundary is also not considered in shutdown PSA because the low pressure and temperature of coolant during most of shutdown would make the probability of any pipe break extremely low. The leakage during shutdown period is assumed to occur during inspection of CRD (Control Rod Drive), replacement of LPRM (Local Power Range Monitor), inspection of RIP (Reactor Internal Pump), or inadvertent mainly due to human errors unique to shutdown state. Boil-off of primary coolant is attributed to loss of RHR or loss of offsite power according to a Hitachi-GE experience. Loss of RHR is caused by failure of either the front line or the support line 4. Probabilistic Safety Assessment Ver. 0 126 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C (RCW/RSW). In the case of support line failure, HPCF and LPFL in the same division are also lost. Potential fault leading to core damage Mechanical failure of fuel Thermal failure of fuel Insufficient cooling of fuel Overpower of fuel Leakage of coolant Boil-off of coolant Loss of RHR Loss of offsite power Loss of primary coolant boundary *Reactivity insertion *Drop of heavy equipments *Not considered in shutdown PS A due to localized fuel failure Considered in shutdown PS A Fig. 4.2.2.2-2 Example of master logic diagram for selecting initiating faults in shutdown PSA 4. Probabilistic Safety Assessment Ver. 0 127 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C (3) Accident Sequence Analysis The set of mitigation (heat removal and water injection) systems credited and the relevant success criteria in shutdown PSA are essentially different from those in level 1 PSA during normal operation. The success of heat removal is that the coolant temperature is kept below 100°C when the RPV is closed (POSs “S”, “A”, “C”, “D”) or 66 degree-C when the water level is in the reactor well (POS “B”). The success of water injection is that the injection rate is larger than the evaporation rate and leakage rate. An example of concrete set of success criteria are listed below. Heat removal: [ This information is removed intentionally ] Water injection: [ This information is removed intentionally ] Reactor Core Isolation Cooling system (RCIC), Control Rod Drive (CRD) and Standby Liquid Control system (SLC) have not been credited in shutdown PSA. (4) System Analysis As illustrated in Fig.4.2.2.2-2, the initiating faults considered in shutdown PSA are “Loss of RHR (front line or support line)”, “Loss of offsite power” and “Loss of primary coolant boundary”. An example of event tree for “Loss of primary coolant boundary” is shown in Fig.4.2.2.2-3. 4. Probabilistic Safety Assessment Ver. 0 128 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C The failure probability of each heading in event trees is estimated by fault tree analyses, which is essentially the same, including the failure rate database, as level 1 PSA during normal operation. Leakage Cognition of decreasing Isolation of leakage path water level Mitigation system Sequance group OK OK Core damage Core damage Fig. 4.2.2.2-3 Example of event tree in shutdown PSA (5) Human Reliability Analysis The characteristics of shutdown PSA in terms of human errors are summarized below. All the mitigation systems are manually initiated because automatic initiation is not always available in shutdown period. Available times for recovery actions are long due to large ratio of water inventory to decay heat. Cognition errors are important. In the fault tree analysis, failure of manual startup is considered for all the mitigating systems. Human errors leading to inadvertent stop of the systems having continuously operated during periodic inspection are also considered. Since Fire Protection system is prepared as an AM measure, 4. Probabilistic Safety Assessment Ver. 0 129 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C an error of realizing necessity of Fire Protection system and selecting necessary valves to open at the job site are considered as the dominant ones. When loss of RHR or loss of offsite power occurs as an initiating fault, the timing of manual actuation on the mitigating system(s) is important. If it is before the primary coolant temperature reaches 100 degree-C (for all POSs except “B”) or 66 degree-C (for POS “B”), failure of the mitigation system(s) does not immediately lead to core damage but recovery of the heat removal system and the water injection system is further considered as the headings. On the other hand, failure of the mitigation systems(s) after the primary coolant temperature reaches the above limit is assumed to result in core damage. Therefore, cognition of the necessity of short-term diagnosis is set as the heading in the event trees of “loss of RHR” and “loss of offsite power” just before the heading of mitigating system. When loss of primary coolant occurs as an initiating fault, failure of recognizing a decrease in the water level by start of core uncovery is supposed to result in core damage, so cognition error of the decreasing water level is the first heading just after the initiating fault as exemplified in Fig. 4.2.2.1-3. However, the cognition error is supposed to be negligible in Japanese practice if the leakage is caused through inspection of CRD, replacement of LPRM, or inspection of RIP. That is because the time to start of core uncovery is estimated to be [ intentionally [ This information is removed ] hours. On the other hand, the leakage through the CUW blow valve allows This information is removed intentionally ] hour, so that cognition errors of decreasing water level in the central control room and excess flow to the Rad. Waste (RW) tank in the RW facility are considered. Once the decrease in the water level due to loss of primary coolant boundary is successfully recognized, following isolation of the leakage path is of interest. Failure probabilities of such isolation works are considered in the event tree. (6) Quantification The quantification process is basically the same as that of level 1 PSA during normal operation. The characteristics of shutdown PSA in terms of quantification are summarized below. IE is calculated by field data or generic data. CDF per day is calculated for all POSs (and time windows if necessary). The calculated CDFs per day are integrated to a CDF per periodic inspection. 4. Probabilistic Safety Assessment Ver. 0 130 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR 4.2.2.3 Revision C Insights from Indicative Results Here, the insights from a past study of a Japanese ABWR plant are summarized. The average CDF per periodic inspection is smaller than the average CDF per year during normal operation. That is basically owing to the larger ratio of water inventory to decay heat. Among the initiating faults, loss of offsite power has the biggest contribution followed by loss of primary coolant boundary, loss of RHR support line and loss of RHR front line. The biggest contribution of loss of offsite power is mainly because the available systems for mitigation are limited. For each initiating faults, POS “C” (transition to closing PCV/RPV top heads) has the biggest contribution among the POSs. Therefore, the most contributing POS is “C” followed by “D”. The other POSs are not dominant. That is mainly because [ intentionally [ This information is removed ] This information is removed intentionally ] Another important insights is that human factor may have big impact. [ removed intentionally This information is ] 4. Probabilistic Safety Assessment Ver. 0 131 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR 4.2.3 Revision C Internal Event Level 1 PSA (Spent Fuel Pool) As PSA for Spent Fuel Pool (SFP) has not been carried out for Japanese BWRs including ABWR, it will be newly developed for UK ABWR. In this section, scope of internal level 1 PSA for SFP, called “SFP PSA” here, is discussed referring to the STEP1b S9b “Initial Safety Case report on Spent Fuel Storage Pool”[19] and taking some analogy with shutdown PSA discussed in 4.2.2. 4.2.3.1 Initiating Faults In the STEP1b S9b “Initial Safety Case report on Spent Fuel Storage Pool” [19], the following Postulated Initiating Events (PIEs) caused by internal faults are proposed. Single failure: [ This information is removed intentionally ] Multiple failures: [ This information is removed intentionally ] Infrequent single failure: [ This information is removed intentionally ] The initiating faults for SFP PSA will be selected based on those PIEs and a master logic diagram like shutdown PSA (see 4.2.2.2). In the SFP design, there is no piping connected to the SFP below the top of fuel bundle, so that the leakage caused by a pipe break would not immediately lead to fuel bundle uncovery. By analogy with shutdown PSA, the direct damage of fuel by dropped load might not be included in the scope of SFP PSA. The applicability of such treatment in shutdown PSA and spent fuel PSA to UK ABWR will be carefully discussed after step 1. At this moment, the SFP risk (internal) is regarded to mainly come from SBO and LUHS. 4. Probabilistic Safety Assessment Ver. 0 132 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR 4.2.3.2 Revision C Accident Sequence Analysis and System Analysis The candidate countermeasures to mitigate the SFP PIEs are introduced in section 4.3 of the STEP1b S9b “Initial Safety Case report on Spent Fuel Storage Pool” [19]. The key phenomena which the success criteria of the countermeasures in SFP PSA are based on are; SFP water temperature reaching 66 degree-C (from analogy with shutdown PSA) SFP water temperature reaching 100 degree-C (from analogy with shutdown PSA) Start of fuel bundle uncovery Peak Clad Temperature (PCT) reaching 1200 degree-C (from analogy with level 1 PSA during normal operation) Event trees for selected initiating faults (perhaps for each POS) will be developed. The failure probability of each heading in event trees will be estimated by fault tree analyses. Those processes will be essentially the same, including the failure rate database, as level 1 PSAs during normal operation and shutdown PSA. 4.2.3.3 Human Reliability Analysis A HRA regarding SFP faults is also new item. That will be developed in strong collaboration with the activities on Fault Schedule, Human Factor, C&I, etc. Due to relatively long available time and if some mitigation systems are to be initiated manually, cognition errors might be important from analogy with shutdown PSA. 4.2.3.4 Expected Risk Insights Although SFP PSA has not been carried out yet, the expected risk insight is discussed here from analogy with shutdown PSA, especially the POS “B (Full water level in reactor well)” due to the similarity in water inventory, heat rate and available mitigation systems. In a past study of shutdown PSA for Japanese ABWR, the average CDF per periodic inspection is smaller than the average CDF per year during normal operation. The contribution of POS “B” is not dominant. From those two things, it can be reasonably expected that average CDF in SFP PSA will be probably well below those in internal level 1 PSA during normal operation and shutdown PSA. 4. Probabilistic Safety Assessment Ver. 0 133 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C 4.3 Internal Event Level 2 PSA This sub-section describes model description, severe accident analysis, and indicative results from experience and LRF estimate, regarding to internal event Level 2 PSA at power. 4.3.1 Internal Event Level 2 PSA (Reactor core during normal operation) 4.3.1.1 Procedure of Internal Event Level 2 PSA A standard for Internal Level 2 PSA during power operation established by Atomic Energy Society of Japan [20] provides the procedure of the PSA as follows. 1. Investigation of plant information 2. Classification of plant damage states and estimation of their frequencies 3. Establishment of containment failure mode 4. Analysis of accident sequences 5. Accident progression analysis 6. Quantification of accident sequences 7. Classification of release category and estimation of their frequencies 8. Source term analysis for each release category 9. Uncertainty analysis and sensitivity analysis 10. Documentation 4.3.1.2 Model (1) Interface: Definition of PDSs Considering interfaces between Level 1 PSA and Level 2 PSA, following plant damage states (PDS) explained in 4.2 are used. Definitions of PDSs are described below. These PDSs are categorized in the view point of initiating events, similarity of plant thermal hydraulic characteristics (pressure in reactor, timing of core damage, timing of containment failure, core debris coolability, heat removal, and etc.), and availability of mitigation systems. LOCA This PDS includes large LOCA with injection failure, medium LOCA with injection failure and small LOCA with injection failure. Core damage shortly occurs at low RPV pressure. Availability of debris cooling measures and heat removal measures are treated in probabilistic way in the containment event tree. TQUV The PDS “TQUV” is Transient including manual shutdown and special initiators, followed by 4. Probabilistic Safety Assessment Ver. 0 134 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C failures of feedwater system, high pressure ECCS and low pressure ECCS. Since reactor depressurization is succeeded or the RPV pressure decreases due to inadvertent opening of SRV, the RPV pressure at the moment of core damage is categorized as low. The timing of core damage is categorized as short. The PCV spray system might be available. In Level 2 PSA, the availability of this system as the debris cooling measure and heat removal measure is treated in probabilistic approach under the failure of low pressure ECCS, because the PCV spray system shares the pumps and valves with the low pressure ECCS. TQUX The PDS “TQUX” is Transient including manual shutdown and special initiators, followed by failures of feedwater system, high pressure ECCS and reactor depressurization. Since high pressure injection measures are lost and reactor depressurization fails, core damage occurs at high pressure in short term. The low pressure ECCS for debris cooling and heat removal is credited with the same unavailability as used in Level 1 PSA. Common TB group (station blackout) is further divided into 4 PDSs from the viewpoint of PCV response. Availability of the debris cooling measures and heat removal measures is treated in probabilistic way, since it depends on recovery of AC/DC powers. Note that the Fukushima countermeasures, e.g. AC independent water injection by fire trucks and diesel driven pumps, are not credited in the PSA of this document. Long-term TB Long term station blackout (long term TB), including failures to recover offsite power by 30 minutes and 8 hours, occurs but high pressure injection is maintained till DC power is exhausted. The timing of core damage is long term. Since the exhaustion of DC power disables manual depressurization by SRV as well as RCIC, the RPV pressure is high at the moment of core damage. TBU The PDS “TBU” is station blackout (TB), including failure to recover offsite power by 30 minutes, is followed by failure of RCIC. Due to the station blackout, no water injection measures including alternative water injection are available. Thus, reactor is not depressurized despite of DC power available. Resulting core damage occurs in short term at high pressure. 4. Probabilistic Safety Assessment Ver. 0 135 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C TBD In the PDS “TBD”, failure of RCIC is caused by failure of DC power while it is due to failure of RCIC itself in TBU. The structure of containment event tree for TBD is the same as that for TB because DC power is not available in both PDSs. TBP Station blackout (TB) is followed by failure to re-close SRV. Reactor depressurization results in disabled RCIC, thus core damage occurs shortly at low pressure. In the containment event tree analysis, TBP is reprehensive by TBU from the viewpoint of credited mitigation measures. TW In this PDS, water injection to the core is successful but heat removal from PCV fails. As a result, PCV fails due to overpressure and it results in core damage (long term) at high pressure due to due to loss of RCIC and HPCF. Since PCV is assumed to have always failed at the moment of core damage, containment event tree analysis is not conducted. However, sever accident analysis is conducted for a representative scenario. TC In this PDS, water injection to the core is successful but heat removal from PCV is not enough due to failure of keeping sub-criticality. PCV overpressure failure occurs earlier than TW. Then, core damage occurs shortly at high pressure due to loss of RCIC and HPCF like TW. Containment event tree analysis is not conducted. However, sever accident analysis is conducted for a representative scenario. In TC and TW, containment fails earlier than core damage. Therefore, no event tree is necessary for these sequences. Containment event tree analysis is carried out for other seven PDSs. The dependencies between the PDSs and subsequent sequences are carefully examined. (2) Failure mode of containment Failure modes of containment are described below. Hydrogen combustion is not included because of the combustion characteristics in inert containment. Justification of it is performed in a future work. 4. Probabilistic Safety Assessment Ver. 0 136 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C Overpressure by steam (decay heat) Pressure increases slowly by accumulation of steam generated by decay heat of the core when debris (molten core) is cooled. This event is prevented by cooling core debris and appropriate removal of decay heat from containment. Steam explosion The thermal energy of debris is converted to mechanical energy instantaneously when a lot of high temperature material drops into water. Probability of occurrence of steam explosion and its effect on structural integrity of containment is studied in Level 2 PSA. Overpressure in case of failure of maintaining sub-criticality Containment pressure rises due to a steam generated in the core at early stages of accidents. This event is prevented by reactivity control in Level 1 PSA. Penetration overtemperature Inside containment is heated slowly by overheated steam or high temperature gases if core debris is not covered by water. Non-metallic parts of penetrations lose its integrity in high temperature environment. This event is prevented by coolant injection to debris, and/or by containment cooling using D/W spray. Direct Containment Heating With a failure of RPV depressurization, the core debris ejects from the RPV, the molten core debris might fragment into small particles and Direct Containment Heating (hereafter called DCH) might occur. Therefore, atmosphere in containment is heated directly in case when RPV failure occurs at high pressure, which may lead to failure of containment. This event is prevented by RPV depressurization adequately. Molten core concrete interaction After RPV failure, if debris on the lower D/W is not cooled, concrete is eroded by molten core concrete interaction (hereafter MCCI). Then base-mat melt-through occurs and it might lead to containment failure finally. This event is prevented by cooling debris in the pedestal Failure of containment isolation Isolation of containment already fails at the time of core damage. Leakage of radioactive material from containment cannot be prevented. Therefore this mode is treated as threatening containment integrity. This event is prevented by isolating containment. 4. Probabilistic Safety Assessment Ver. 0 137 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C (3) Accident Sequence Analysis The accident sequence might be changed from existing model because of some design change for UK ABWR. However, accident sequence model of existing Level 1.5 PSA, which calculates the CFF (Containment Failure Frequency), can be also the basis of Level 2 PSA for UK ABWR. Accident sequence for each PDS is described below. a. TQUX In this condition, high pressure injection systems are assumed to be not available by some reasons. ADS is initiated by both signals low reactor water level (Level1.5) and high D/W pressure. During transient events, high D/W pressure is too late to prevent core damage considering heat sink capacity of containment. Therefore, in Level 1 PSA, manual actuation of SRVs is necessary. However, in Level 2 PSA, time margin for this signal is enough until RPV failure. With automatic actuation of ADS or manual actuation of SRVs followed by low pressure injection with LPFL or alternative water injection (as AM measure), RPV failure can be prevented. If the RPV failure is prevented, stable state can be achieved by long-term heat removal with RHR. If the RHR fails, the containment can fail by overpressure like “TW” sequence. If the RPV fails due to failure of water injection to damaged core, accident progression is similar to that of TQUV explained later. With a failure of RPV depressurization, early containment failure can occur by direct containment heating (DCH). If containment is intact even after low-pressure RPV failure or high-pressure RPV failure (without DCH), core debris on the lower D/W floor needs to be cooled to stop progression of MCCI. Containment failure by MCCI is prevented by coolant injection into lower D/W and D/W spray with RHR / alternative water injection system. Steam explosion during the debris cooling is also considered. Including above things, containment failure is avoided if core debris is cooled and long-term heat removal is maintained. Figs.4.3.1.2-1 through 4.3.1.2-3 show conceptual diagram of the containment event tree for TQUX. b. TQUV Deference of TQUV from TQUX sequences is that RPV pressure is considered low. Containment failure is avoided if core debris is cooled and long-term heat removal is maintained as is mentioned in TQUX. c. LOCA Accident sequence of LOCA in Level 2 PSA is almost the same as that of TQUV. Only the 4. Probabilistic Safety Assessment Ver. 0 138 NOT PROTECTIVELY MARKED Form05/00 UK ABWR NOT PROTECTIVELY MARKED GDA Preliminary Safety Report Revision C difference is that before RPV fails, pool is generated in the lower D/W because of steam is released to D/W by LOCA. If the RPV fails, steam explosion by core debris dropping into this pond is considered. d. TB group TB group (station blackout) is divided into 2 subgroups (TBU/TBP and long term TB/TBD) in terms of availability of DC power at the moment of core damage. In TBU, core damage occurs at high pressure in short term due to the failure of RCIC itself. In TBP, core damage occurs at low pressure in short term because failure to re-close SRV disables the RCIC. From the viewpoint of Level 2 PSA, those PDSs are similar since DC power itself is assumed to be intact. In Hitachi-GE generic PSA, TBU and TBD shares the same event tree. Since the RPV pressure is high at the moment of core damage in TBU, the event tree structure is basically the same as that of TQUX except that “AC power recovery” is added before/after the RPV failure. Automatic depressurization dependent on DC power is credited like TQUX. When quantifying the containment event tree for TBP, in which core damage occurs at low pressure, failure probability of automatic depressurization is set as negligibly small. Since the low pressure ECCS itself is intact in station blackout condition, recovery of AC power before RPV failure enables injection into RPV by the low pressure ECCS or alternative water injection. Similarly, recovery of AC power even after RPV failure but before PCV failure enables debris cooing, PCV spray by RHR or alternative water injection, and long term heat removal by the RHR. Although the alternative water injection includes motor-driven MUWC pumps and diesel-driven fire protection (FP) pumps, the failure to recover AC power is assumed to lead to containment failure, which means that alternative water injection is not credited under station blackout condition. In the PDS “long term TB”, core damage occurs after the RCIC has stopped due to exhausted DC power in the Level 1 analysis. In TBD, DC power is also lost before core damage. Both of TB and TBD need recovery of DC power for reactor depressurization and AC power recovery. The difference from TBU/TBP is that the “DC power recovery” is considered. The former recovery is essential for reactor depressurization and AC power recovery before RPV failure which may enable cooling of damaged core inside the RPV by low pressure ECCS or alternative water injection. The latter recovery is essential for AC power recovery which enables debris cooling and PCV spray by RHR or alternative water injection, and also long term heat removal by the RHR. Although the alternative water injection includes motor-driven MUWC pumps and diesel-driven fire protection (FP) pumps, the failure to recover AC power is assumed to lead to containment failure, which means that alternative water injection is not credited under station blackout 4. Probabilistic Safety Assessment Ver. 0 139 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C condition. (4) Accident progression analysis MAAP is used in the UK ABWR PSA. This analysis includes models for the important accident phenomena that might occur within primary system, in the containment, and in the reactor building. MAAP calculates the progression of the postulated accident sequence, including the deposition of the fission products, from a set of initiating events to either a safe, stable state or to an impaired containment condition (by over-pressure or over temperature) and the possible releases if fission products to the environment. To establish that the MAAP code is capable of addressing the above purpose and uses, numerous benchmarks have been performed, both with respect to individual models and for the integral response of reactor systems. These benchmarks provide insights into the code performance and confidence in the capabilities of MAAP to represent individual phenomena as well as the integral response of reactor systems, including the influences of operator actions. Accident analyses for accident progression are prepared for 6 representative sequences. Each sequence represents each PDS. Analysis conditions are described below. a. TQUV Accident analysis conditions for TQUV are described below - For initiating event, transient event with MSIV closure is assumed. - [ This information is removed intentionally ] - [ This information is removed intentionally ] - [ This information is removed intentionally ] In the view point of conservativeness, loss of all feedwater flow and without stuck open relief valve condition is chosen. b. TQUX Accident progression analysis conditions for TQUX are described below - For initiating event, transient event with MSIV closure is assumed. - [ This information is removed intentionally ] - [ This information is removed intentionally ] In the view point of conservativeness, loss of all feedwater flow and without stuck open relief valve 4. Probabilistic Safety Assessment Ver. 0 140 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C condition is chosen. c. Long term TB Accident progression analysis conditions for TB are described below - For initiating event, loss of off-site power is assumed. - [ This information is removed intentionally ] - [ This information is removed intentionally ] In this case, RCIC runs for 8 hours. d. TW Accident progression analysis conditions for TW are described below - For initiating event, transient event with loss of all feedwater flow is assumed. - [ This information is removed intentionally ] - [ This information is removed intentionally ] - [ This information is removed intentionally ] In the view point of conservativeness, loss of all feedwater flow and without stuck open relief valve condition is chosen. e. TC Accident progression analysis conditions for TC are described below - For initiating event, transient event with spurious closure of MSIV is assumed. - [ This information is removed intentionally ] - [ This information is removed intentionally ] In the view point of conservativeness, spurious closure of MSIV is chosen for initiating event. f. LOCA Accident analysis conditions for LOCA are described below - For initiating event, guillotine break of feedwater piping is assumed. - [ This information is removed intentionally ] For Japanese ABWR PSA, acceptance criteria of containment are [ intentionally intentionally ] times of design pressure and about [ This information is removed This information is removed ] degree-C. Acceptance criteria of containment condition will be reviewed by appropriate method. 4. Probabilistic Safety Assessment Ver. 0 141 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C For following physical phenomena, branch probabilities of a heading of event trees are calculated. Dominant parameters with large uncertainty are selected, and statistical distribution of criterion parameter is generated to decide branch probability. Steam Explosion Direct Containment Heating Debris Cooling(MCCI) (5) Fission Product release category Containment failure sequences are categorized into 16 groups as shown below, considering containment integrity, release timing, release path, duration, and scrubbing effect, and etc. Indicative analysis conditions are described in PSA support document [9]. [ This information is removed intentionally ] 4. Probabilistic Safety Assessment Ver. 0 142 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Plant Damage State Revision C T2 T1 Containment RPV Isolation Depressuriz ation Low Pressure ECCS Containment failure by FCI Containment Failure by DCH Containment Condition / Rink to Other Trees Containment failure by Shell Attack Intact RPV /Containment Pressurizing sequence(T3A) RPV Failure Sequence(T3B) Containment failure (Ex-vessel FCI) RPV Failure Sequence(T3B) Containment failure(Shell Attack) [*1] Containment failure(DCH) Containment failure(Ex-vessel FCI) Containment Isolation failure Fig. 4.3.1.2-1 Conceptual diagram of event tree for TQUX (1/3) Coolant Injection into Containment Following Event ECCS Spray Alternative Spray Long Term Cooing Contain ment Venting Containment Condition Stable state without containment venting Containment Venting Containment Failure (Overpressure) Stable state without containment venting Containment Venting Containment Failure (Overpressure) Stable state without containment venting Containment Venting Containment Failure (Overpressure) Fig.4.3.1.2-2 Conceptual diagram of event tree for TQUX (2/3) 4. Probabilistic Safety Assessment Ver. 0 143 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C T1/T2 Followi ng Event T3B Injection into containment With RHR Lower D/W injection With alternative coolant Injection Upper D/W spray Lower D/W injection Upper D/W spray FCI at Injectio n into contain ment Debris Cooling Long Term Cooing Contain ment Venting Contain ment failure by overpres sure Containment Condition Stable state without containment venting Containment Venting Containment Failure (Overpressure) Containment Failure (MCCI) Containment Failure (Over temperature) Containment Failure (Ex-vessel FCI) Stable state without containment venting Containment Venting Containment Failure (Overpressure) Containment Failure (MCCI) Containment Failure (Over temperature) Containment Failure (Ex-vessel FCI) Containment Failure (Over temperature) Containment Failure (MCCI continue) Containment Failure (Over temperature) Containment Failure (Ex-vessel FCI) Stable state without containment venting Containment Venting Containment Failure (Overpressure) Containment Failure (MCCI) Containment Failure (Over temperature) Containment Failure (Ex-vessel FCI) Stable state without containment venting Containment Venting Containment Failure (Overpressure) Containment Failure (MCCI) Containment Failure (Over temperature) Containment Failure (Ex-vessel FCI) Stable state without containment venting Containment Venting Containment Failure (Overpressure) Containment Failure (MCCI) Containment Failure (Over temperature) Containment Failure (Ex-vessel FCI) Containment Failure (Over temperature) Containment Failure (MCCI) Containment Failure (Over temperature) Containment Failure (Ex-vessel FCI) Stable state without containment venting Containment Venting Containment Failure (Overpressure) Containment Failure (MCCI) Containment Failure (Over temperature) Containment Failure (Ex-vessel FCI) Containment Failure (Over temperature) Fig. 4.3.1.2-3 Conceptual diagram of event tree for TQUX (3/3) 4. Probabilistic Safety Assessment Ver. 0 144 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR 4.3.1.3 Revision C Indicative results (1) Results from Japanese ABWR Existing internal Level 1 and Level 1.5 PSA results for Japanese ABWR are introduced here. Reference documents are same as those introduced in section 4.2.1 [13] [14] [15]. Table 4.3.1.3-1 shows the CDFs, CFFs and CCFPs (conditional containment failure probabilities) calculated by the utility and JNES. Mitigation features credited in the PSAs are shown in Table 4.3.1.3-2.CCFP estimated by both parties are within the range of 0.1~0.4. Fig.4.3.1.3-1 shows the containment failure frequency by the containment failure modes. The containment failure mode “penetration overtemperature” and “overpressure by steam” are first and second largest contributors to the total CCF in both the results by the utility and JNES. Penetration overtemperature occurs if coolant injection into RPV or containment remains fail. TB sequences in which AC power supply remains lost even after the RCIC terminates at 8 hours (in case of long term TB) largely leads to RPV failure with this failure mode. In this case, containment spray with RHR after recovery of AC power, or containment spray with alternative water injection can prevent “penetration overtemperature”. The dominant factor of overpressure by steam is TW sequence. Recovery of RHR or containment venting can prevent this failure mode. Table 4.3.1.3-1 PSA results (Containment failure frequency) [ This information is removed intentionally 4. Probabilistic Safety Assessment Ver. 0 ] 145 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C Table 4.3.1.3-2 Mitigation features credited in Japanese ABWR PSA [ This information is removed intentionally 4. Probabilistic Safety Assessment Ver. 0 ] 146 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C 1.0E-07 Utility Core Damage Frequency(/y) 1.0E-08 JNES 1.0E-09 1.0E-10 1.0E-11 1.0E-12 1.0E-13 1.0E-14 1.0E-15 1.0E-16 Fig.4.3.1.3-1 Containment failure frequency (This figure is developed from the data in ref. [15]) 4. Probabilistic Safety Assessment Ver. 0 147 NOT PROTECTIVELY MARKED NOT PROTECTIVELY MARKED Form05/00 GDA Preliminary Safety Report UK ABWR Revision C (2)Results from USABWR DCD PSA (NUREG-1503[17]) Major difference of mitigation features in Level 2 PSA between US ABWR and Japanese ABWR is passive mitigation used in US ABWR. It consists of LDF (Lower D/W Flooder system), which supply water to the lower D/W to cover the debris there from S/P after RPV failure, and COPS (Containment Over Pressure protections system), which is a passive containment venting system. The LDF consists of pipes that run from the vertical pedestal vents into the lower drywell. Each pipe contains a fusible plug valve connected to the end of the pipe that extends into the lower drywell by a flange. The fusible plug valves open when the drywell atmosphere (and subsequently the fusible plug valve) temperature reaches 260 degree-C. Table 4.3.1.3-3 shows the CFFs and CCFPs of US ABWR performed by GE and NRC. There are two criteria for defining containment failure, i.e., structural integrity and dose definition. The higher CCFP estimated by NRC than by GE based on the structural integrity is due to (1) contribution from unisolated LOCAs outside containment and (2) increased probability of containment failure by DCH. The higher CCFP estimated by NRC than by GE is because doses excess of 25 rem at 0.8 km occur only when structural integrity is breached in GE’s result while 60% of the frequency of sequences with COPS actuation is treated as containment failure in addition to breached structural integrity in NRC’s result. However, NRC concluded that CCFP of 0.1 met the Commission’s safety goal. Table 4.3.1.3-3 Containment failure probability of USABWR DCD PSA (NUREG-1503 [17]) GE Updated PRA Performance Measure Containment Failure Staff- Adjusted Result (U.S. NRC cross check result) Containment Conditional CFP Probability (CFP) Failure Conditional CFP Probability (CFP) Structural Integrity 7.7E-10 0.005 4.1E-9 0.026 3E-10 0.002 1.6E-8 0.10 Dose Definition (*) (*) 25rem at 0.8km 4. Probabilistic Safety Assessment Ver. 0 148 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR 4.3.2 Revision C Internal Event Level 2 PSA (Shutdown and Spent Fuel Pool) For the period during the RPV/PCV top heads closed, the primary coolant boundary and the PCV can be credited as the barriers of radioactive materials, so that level 2 PSA supported by severe accident analysis will be essentially the same as level 2 PSA for normal operation. Resulting source term is expected to be of similar level to the severe accidents initiated from normal operation. For the period during the RPV/PCV opened, on the other hand, only the secondary containment facility (reactor building) would be the barrier after radioactive materials are released from the fuel rods. Countermeasures for minimizing source term will be rather important. is removed intentionally [ This information ] Countermeasures against hydrogen issues will also contribute to source term reduction. Scribing of volatile Fission Products by flooding damaged fuel will be also important. Now, it should be emphasized that the CDF during the period with the RPV/PCV opened (mostly POS “B”) is not dominant based on a past study in Japan. The method of level 2 PRA for such period is to be discussed. The simplest way is to set the conditional large release frequency as 1.0 and to assume certain release fraction of Fission Products to the total inventory according to past experiments. Methodology of internal level 2 PSA for SFP will be basically applicable from that for shutdown PSA. Based on this assumption, currently expected CDF (internal) for SFP is small as discussed in 4.2.3.5. In addition, compliance to the targets 7, 8, 9 in SAP will be assessed for shutdown condition, SFP as well as the reactor at normal operation. 4. Probabilistic Safety Assessment Ver. 0 149 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C 4.4 Internal Event Level 3 PSA This sub-section describes approach of Level 3 PSA. In the early phase of GDA, evacuation plan, which is critical to risk reduction, is not defined. In this limited condition, Level 3 PSA will be conducted by using generic site condition. With regard to quantification of risk, source term will be analyzed by using MAAP code, and consequence analysis will be performed by adequate code. A fuel scope PSA is currently considered for UK ABWR GDA and this will enable comparison with Target 7, 8, and 9 to be made. An approach to a Level 3 PSA will be defined. The development plan will be discussed with ONR /EA. 4. Probabilistic Safety Assessment Ver. 0 150 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C 4.5 External Event PSA This sub-section describes approach of external event PSA. (1) General Based on assessment on internal hazards and external hazards, hazards that have important risk features are selected by simple qualitative screening process. PSA for selected hazard will be conducted in GDA. Basically, earthquake, internal flooding and internal fire are assumed to have important risk features and will be at least assessed with probabilistic approach. (2) Seismic PSA (Seismic Margin Analysis) Because seismic hazard assessment with site-specific data will not be performed in GDA, the risk of seismic events was evaluated by seismic margin analysis. Important sequence and important component in terms of seismic risk are extracted by this analysis. Earthquake resistance is not dealt with in GDA. Therefore, generic data is basically applied and plant-specific data is applied if available. From existing study, SBO caused by loss of component cooling systems, which has lots of components, is an important sequence. Against this type of sequence, improvement of seismic resistance for component cooling systems for safety systems or systems for core cooling and long-term cooling which do not need component cooling systems such as RCIC, FLSS after depressurization, and containment venting have important role on mitigation in this uncertain event. (3) Internal Flooding PSA Potential flooding source and its failure frequency for internal flooding PSA is based on the internal hazard study. Therefore, internal flooding PSA is preformed after deterministic study of it. Assessment of the reliability with components that survive after the flooding is performed in the same way as internal events. From existing study, important internal flooding sequences are as follows. Turbine building ・A large pipe breaks in the CWS ・The isolation valves in the CWS lines fail to close ・Water fills up and runs out of the condenser pit 4. Probabilistic Safety Assessment Ver. 0 151 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C ・The fire door between the turbine building and service building is either open or fails open allowing water into the service building ・The service building floods and a door between the service building and the control building fails open or is open. Reactor building ・A large pipe breaks in the RSW piping in the RSW/RCW room and the operator fails to isolate the flooding Internal flooding PSA for UK ABWR is performed considering its characteristics of layout. (4) Internal Fire PSA Potential fire source and its ignition frequency for internal fire PSA is based on the internal hazard study. Therefore, internal fire PSA is preformed after deterministic study of it. Assessment of the reliability with components which survive after the fire is performed in the same way as internal events. [ This information is removed intentionally ] Internal fire PSA for UK ABWR is performed considering its characteristics of layout. 4. Probabilistic Safety Assessment Ver. 0 152 NOT PROTECTIVELY MARKED Form05/00 UK ABWR NOT PROTECTIVELY MARKED GDA Preliminary Safety Report Revision C 4.6 Conclusions Risk reduction features of UK ABWR design in terms of redundancy, diversity and independency will be demonstrated by PSA. UK ABWR PSA results will be compared with SAP target 7 and target 9, and its validity will be evaluated. In addition, it is used to improve design and operational procedure. 4. Probabilistic Safety Assessment Ver. 0 153 NOT PROTECTIVELY MARKED Form05/00 UK ABWR NOT PROTECTIVELY MARKED GDA Preliminary Safety Report Revision C 5. Conclusions Draft initiating events for DSA as the start line of our discussion has been developed by qualitative analysis considering frequency, severity and representativeness as shown in Table 2.2-1. Also, Draft fault schedule has been developed on the basis of Hitachi-GE practice. The list of initiating events, fault schedule and fault sequence will be developed during all modes of operation in Step 2. In this document, examples of DSA performed based on Hitachi-GE practice are presented. According to these analysis results, acceptance criteria in Japan are met by safety systems on Japanese ABWR. DSA for UK ABWR will be performed to confirm the adequacy of the safety design and the suitability and sufficiency of the safety measures against target 4 in HSE SAPs in Step2. Risk reduction features of UK ABWR design in terms of redundancy, diversity and independency are demonstrated by PSAs. UK ABWR PSA results are compared with SAP target 7 and target 9, and its validity is evaluated. In addition, it is used to improve design and operational procedure. The following is a development plan of PSAs for UK ABWR during GDA: 5. Conclusions Ver. 0 154 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C 6. Reference [1] NSCRG:L-SE-I.0 Regulatory Guide: Evaluating Safety Assessment of Light Water Reactor Facilities, Revision on March 29, 2001 by the Nuclear Safety Commission http://www.nsr.go.jp/archive/nsc/NSCenglish/guides/nsc_rg_lwr.htm http://www.nsr.go.jp/archive/nsc/NSCenglish/guides/lwr/L-SE-I_0.pdf [2] NSCRG: L-SE-I.03 Regulatory Guide for Evaluating Reactivity Insertion Events of Light Water Nuclear Power Reactor Facilities, Revision on August 30, 1990 by the Nuclear Safety Commission http://www.nsr.go.jp/archive/nsc/NSCenglish/guides/lwr/L-SE-I_03.pdf [3] NSCRG: L-SE-I.02 Regulatory Guide for Evaluating Emergency Core Cooling System Performance of Light Water Power Reactors, Revision on July 11, 1992 by the Nuclear Safety Commission http://www.nsr.go.jp/archive/nsc/NSCenglish/guides/lwr/L-SE-I_02.pdf [4] Establishment permission application document of the nuclear power station (Kashiwazaki -Kariwa unit 6/7) (in Japanese), March 1998,by Tokyo Electric Power Company [5] SC-P008:2008: A Standard for Procedures of Probabilistic Safety Assessment of Nuclear Power Plants during Power Operation (Level 1PSA) (in Japanese), March 2009, by Atomic Energy Society of Japan (AESJ) [6] TR-016780-V2R8: Advanced Light Water Reactor Utility Requirements Document, Volume 2, Revision 8: ALWR Evolutionary Plant, March 1999, by EPRI http://www.epri.com/abstracts/Pages/ProductAbstract.aspx?ProductId=TR-016780-V2R8 [7] NUREG-1829: Estimating Loss-of-Coolant Accident (LOCA) Frequencies Through the Elicitation Process, April 2008, by U.S.NRC http://www.nrc.gov/reading-rm/doc-collections/nuregs/staff/sr1829/ [8] NUREG/CR-5750: Rates of Initiating Events at U.S. Nuclear Power Plants: 1987-1995, February 1999, by Idaho National Engineering and Environmental Laboratory http://pbadupws.nrc.gov/docs/ML0618/ML061860698.pdf [9] GA21-9910-0001-00001: PSA Support Document, December 2013, Hitachi-GE Nuclear Energy, ltd. [10] Estimation of national general component failure rate considering uncertainties about number of failure cases, May 2009, by The Japan Nuclear Technology Institute (JANTI) http://www.nucia.jp/jfiles/reliability/REPORT200905.pdf [11] NUREG/CR-1278: Handbook of Human Reliability Analysis with Emphasis on Nuclear Power Plant Applications, August 1983, by U.S.NRC http://pbadupws.nrc.gov/docs/ML0712/ML071210299.pdf 6. Reference Ver. 0 155 NOT PROTECTIVELY MARKED Form05/00 NOT PROTECTIVELY MARKED GDA Preliminary Safety Report UK ABWR Revision C [12] NUREG/CR-4772: Accident Sequence Evaluation Program (ASEP) HRA Procedure, February 1987, by Sandia National Laboratory http://www.osti.gov/scitech/biblio/6370593 [13] The report of accident management review for Shimane NPP Unit3 (in Japanese), April 2010, by Chugoku Electric Power Co. INC [14] The report of Probabilistic Safety Assessment for Shimane NPP Unit 3 (in Japanese), April 2010, by Chugoku Electric Power Co. INC [15] H22-C01 r1: The assessment report of the accident management review report on Shimane NPP Unit 3 prepared by Chugoku Electric Power Co. INC. (in Japanese), August 2010, by Japan Nuclear Energy Safety Organization (JNES) http://www.nsr.go.jp/archive/nisa/shingikai/800/18/001/sankou1-3.pdf [16] "ABWR Design Control Document." 1997 by GE Nuclear Energy [17] NUREG-1503: Final Safety Evaluation Report Related to the Certification of the Advanced Boiling Water Reactor Design, Vol.1, July 1994 by U.S.NRC http://pbadupws.nrc.gov/docs/ML0806/ML080670592.html [18] AESJ-SC-P001:2010: A Standard for Procedures of Probabilistic Safety Assessment of Nuclear Power Plants during shutdown state (Level 1PSA) (in Japanese), November 2011, by Atomic Energy Society of Japan (AESJ) [19] GA91-9901-0003-00001: Initial Safety Case report on Spent Fuel Storage Pool, UK ABWR GDA Step 1b s9b, December 2013, by Hitachi-GE Nuclear Energy, ltd. [20] AESJ-SC-P009:2008: A Standard for Procedures of Probabilistic Safety Assessment of Nuclear Power Plants during Power Operation (Level 2PSA), March 2009, by Atomic Energy Society of Japan (AESJ) 6. Reference Ver. 0 156 NOT PROTECTIVELY MARKED