Mechanical Inspection Asset Data Priority Condition Inspection

advertisement
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Mechanical Inspection
Q797
PS 150 ANNEX - QUEENS, 41-12 44TH STREET, QUEENS, NY, 11104
School:
InspectionId
Inspection Type
1861 MECHANICAL
Time In
Last Edited
2015-01-29 08:09AM
2015-02-04 04:12PM
Asset Data
Question
Answer
Have any Systems/Major Building Components been upgraded?
Systems:
Years:
Systems:
Years:
Systems:
Are there fuel tanks?
Total # of above ground tanks
Total capacity of all above ground tanks in gal.
Total # of below ground tanks
Total capacity of all below ground tanks in gal.
Total # of water main service entries to the asset
Years:
Yes
0
0
1
7,500
1
MERs/Fan Rooms Locations
None
CO/Gas Leak Detection; Electric Domestic Water
Heater in Warming Pantry (1 of 2); Sewage Ejector
Pumps; Boiler Safety Valves; Boiler Make-up Water
Backflow Preventer; Exhaust Fans
2007
Fixtures - Student: Drinking Fountains; Climate
Control System
2009
Electric Domestic Water Heater in Boiler Room; MDF
Room - Dedicated A/C Equipment (window A/C)
2012
Priority Condition
Priority Condition
Exist Last Year?
Priority
Category
Condition
Description
Component
Affected
Location
Description
Person(s) Notified
Person(s) Title
PhotoImage
No condition recorded
Inspection
Question
Response
Mechanical
AIR CONDITIONING
Does not exist
CENTRAL ACID WASTE NEUTRALIZING TANK
Does not exist
CLIMATE CONTROL SYSTEM
Inspected
BMS
Does not exist
Electric System
Inspected
Instance
Throughout (2 zones)
1- Good
Instance Condition
Instance Quantity
1
EACH
Instance Quantity Uom
Building Area Covered by Operational System
81-100%
Deficiency
No deficiencies recorded
Hybrid System
Does not exist
Pneumatic System
Does not exist
COMPACTOR
Does not exist
CONVEYING
Does not exist
DOMESTIC WATER SYSTEM
Inspected
Domestic Cold Water System
Inspected
Gravity System
Does not exist
Pressure Booster System
Does not exist
Water Service
Inspected
Instance
Basement Room C
3- Fair
Instance Condition
Instance Quantity
1
EACH
Instance Quantity Uom
Deficiency
Mobile Validity Version 2.0 (P)
WATER MAIN:MISSING BACKFLOW PREVENTION
DEVICE
Page 1 of 5
Print Date: 6/16/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Mechanical Inspection
Q797
Question
Response
DOMESTIC WATER SYSTEM
Domestic Cold Water System
Water Service
Deficiency Location/Instance
Deficiency Quantity
Basement Room C
1
EACH
INSTALL
PRIORITY 3
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Inspected
Domestic Hot Water System
Domestic Hot Water Remote Storage Tank
Does not exist
Domestic Water Heat Exchanger
Does not exist
Electric Domestic Water Heater
Inspected
Condition
1- Good
Deficiency
No deficiencies recorded
Gas Fired Domestic Water Heater
Does not exist
Oil Fired Domestic Water Heater
Does not exist
Inspected
Domestic Water Distribution Piping
3- Fair
Condition
Deficiency
No deficiencies recorded
Inspected
DRAIN/WASTE/VENT AND STORM SYSTEM
Inspected
Interior Storm Piping
3- Fair
Condition
Deficiency
No deficiencies recorded
Inspected
Sewage Ejector Pump
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
Inspected
Sewage/Waste/Vent Piping
3- Fair
Condition
Deficiency
No deficiencies recorded
Does not exist
Sump Pump
DUAL TEMPERATURE SYSTEM (CHILLED AND HOT WATER)
Does not exist
Enclosed IDF Room
Does not exist
FIXTURES
Inspected
Staff And Other
Inspected
Janitor Sink
Inspected
Condition
3- Fair
Deficiency
No deficiencies recorded
Inspected
Lavatory/Sink
Condition
3- Fair
Deficiency
No deficiencies recorded
Inspected
Toilet
Condition
3- Fair
Deficiency
No deficiencies recorded
Does not exist
Urinal
Inspected
Student
Inspected
Drinking Fountain
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Inspected
Lavatory/Sink
Condition
3- Fair
Deficiency
No deficiencies recorded
Does not exist
Locker Room Shower
Mobile Validity Version 2.0 (P)
Page 2 of 5
Print Date: 6/16/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Mechanical Inspection
Q797
Question
Response
FIXTURES
Student
Sink And Fountain Combo Unit
Does not exist
Toilet
Inspected
Condition
3- Fair
Deficiency
No deficiencies recorded
Inspected
Urinal
Condition
3- Fair
Deficiency
No deficiencies recorded
GAS FIRED FURNACE
Does not exist
GAS SERVICE
Inspected
Inspected
CO/Gas Leak Detection
Instance
Boiler Room
2- Between Good and Fair
Instance Condition
Instance Quantity
Instance Quantity Uom
1
EACH
Installation Year
Source of Installation Year
2007
Documented
Deficiency
No deficiencies recorded
Gas Distribution Piping
Does not exist
Gas Meter Room Exhaust Fan
Does not exist
Gas Meter Room Vent
Does not exist
Gas Pressure Booster
Does not exist
Inspected
HEATING
Heating Coil In Ductwork
Does not exist
Hydronic Heating
Inspected
Backflow Preventer
Does not exist
Hot Water Heat Exchanger
Does not exist
Hydronic Hot Water Distribution: Piping, Pumps and Auxiliaries
Inspected
Condition
3- Fair
Deficiency
No deficiencies recorded
Inspected
Radiator/Convector/Fin Tube
3- Fair
Condition
Deficiency
No deficiencies recorded
Steam Heating
Does not exist
Steam supplied by External Sources
Does not exist
Unit Heater/Cabinet Heater
Does not exist
HEATING PLANT
Replacement Quantity
3,548
MBH Net
Replacement Uom
Inspected
Oil
2
Instance on Basement
Burner Type
Heating Plant Oil Number
Boiler Auxiliaries
Inspected
Instance on Basement
Boiler Auxiliary Piping
Instance on Basement
Inspected
Instance Condition
3- Fair
Deficiency
No deficiencies recorded
Boiler Emergency Stop Switch
Instance on Basement
Inspected
Instance Condition
3- Fair
Deficiency
No deficiencies recorded
Boiler Feedwater System
Mobile Validity Version 2.0 (P)
Page 3 of 5
Print Date: 6/16/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Mechanical Inspection
Q797
Question
Response
HEATING PLANT
Boiler Auxiliaries
Boiler Feedwater System
Instance on Basement
Does not exist
Boiler Feedwater Treatment(Automatic)
Does not exist
Instance on Basement
Boiler Flue Exhaust
Instance on Basement
Inspected
Instance Condition
3- Fair
Deficiency
No deficiencies recorded
Boiler Make-up Water Backflow Preventer
Instance on Basement
Inspected
Instance Condition
1- Good
Deficiency
No deficiencies recorded
Boiler Room Steam And Condensate Piping
Does not exist
Instance on Basement
Boiler Safety Valve
Instance on Basement
Inspected
Instance Condition
1- Good
Deficiency
No deficiencies recorded
Boiler System
Inspected
Instance on Basement
Coal-fired Boiler
Does not exist
Instance on Basement
Hot Water Boiler
Instance on Basement
Inspected
Instance
Boiler Room
3- Fair
Instance Condition
Instance Quantity
Instance Quantity Uom
1,774
MBH Net
Manufacturer
EquipmentId
Capacity/Size Quantity
Capacity/Size UOM
Source of Capacity/Size
Installation Year
Source of Installation Year
Kewanee Boiler Corporation
83258-01
2040
MBH Gross
Documented
1956
Documented
Deficiency
Deficiency Location/Instance
Deficiency Quantity
BEYOND USEFUL LIFE
Boiler Room
1
EACH
REPLACE
PRIORITY 1
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Instance
Boiler Room
3- Fair
Instance Condition
Instance Quantity
Instance Quantity Uom
1,774
MBH Net
Manufacturer
EquipmentId
Capacity/Size Quantity
Capacity/Size UOM
Source of Capacity/Size
Installation Year
Source of Installation Year
Kewanee Boiler Corporation
83258-02
2040
MBH Gross
Documented
1956
Documented
Mobile Validity Version 2.0 (P)
Page 4 of 5
Print Date: 6/16/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Mechanical Inspection
Q797
Question
Response
HEATING PLANT
Boiler System
Hot Water Boiler
Deficiency
Deficiency Location/Instance
Deficiency Quantity
BEYOND USEFUL LIFE
Boiler Room
1
EACH
REPLACE
PRIORITY 1
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Modular Boiler
Does not exist
Instance on Basement
Steam Boiler
Does not exist
Instance on Basement
Fuel System
Inspected
Instance on Basement
Boiler Fresh Air Louver/Damper
Instance on Basement
Inspected
Instance Condition
3- Fair
Deficiency
No deficiencies recorded
Burner/Burner Control Panel
Instance on Basement
Inspected
Instance Condition
3- Fair
Deficiency
No deficiencies recorded
Fuel Oil Storage/Supply System
Instance on Basement
Inspected
Instance Condition
3- Fair
Deficiency
No deficiencies recorded
Gas Trains And Vent At The Boiler
Does not exist
Instance on Basement
Does not exist
KITCHEN
MDF Room
Inspected
Instance on Room 2F
Dedicated A/C Equipment
Instance on Room 2F
Inspected
Instance Condition
1- Good
Deficiency
No deficiencies recorded
SCIENCE DEMO ROOM
Does not exist
SCIENCE LAB
Does not exist
SCIENCE PREP ROOM
Does not exist
SPRINKLERS, STANDPIPE, FIRE SYSTEM
Does not exist
SWIMMING POOL
Does not exist
VENTILATION
Inspected
Exhaust Fan
Inspected
2- Between Good and Fair
Condition
Approximate Total # of Fans
Deficiency
1-25
No deficiencies recorded
Heating And Ventilating Unit
Does not exist
Metal Ductwork
Inspected
3- Fair
Condition
Deficiency
No deficiencies recorded
Supply Fan
Does not exist
Unit Ventilator
Does not exist
Mobile Validity Version 2.0 (P)
Page 5 of 5
Print Date: 6/16/2015