NYC Department of Education Building Condition Assessment Survey 2014-2015 Mechanical Inspection Q797 PS 150 ANNEX - QUEENS, 41-12 44TH STREET, QUEENS, NY, 11104 School: InspectionId Inspection Type 1861 MECHANICAL Time In Last Edited 2015-01-29 08:09AM 2015-02-04 04:12PM Asset Data Question Answer Have any Systems/Major Building Components been upgraded? Systems: Years: Systems: Years: Systems: Are there fuel tanks? Total # of above ground tanks Total capacity of all above ground tanks in gal. Total # of below ground tanks Total capacity of all below ground tanks in gal. Total # of water main service entries to the asset Years: Yes 0 0 1 7,500 1 MERs/Fan Rooms Locations None CO/Gas Leak Detection; Electric Domestic Water Heater in Warming Pantry (1 of 2); Sewage Ejector Pumps; Boiler Safety Valves; Boiler Make-up Water Backflow Preventer; Exhaust Fans 2007 Fixtures - Student: Drinking Fountains; Climate Control System 2009 Electric Domestic Water Heater in Boiler Room; MDF Room - Dedicated A/C Equipment (window A/C) 2012 Priority Condition Priority Condition Exist Last Year? Priority Category Condition Description Component Affected Location Description Person(s) Notified Person(s) Title PhotoImage No condition recorded Inspection Question Response Mechanical AIR CONDITIONING Does not exist CENTRAL ACID WASTE NEUTRALIZING TANK Does not exist CLIMATE CONTROL SYSTEM Inspected BMS Does not exist Electric System Inspected Instance Throughout (2 zones) 1- Good Instance Condition Instance Quantity 1 EACH Instance Quantity Uom Building Area Covered by Operational System 81-100% Deficiency No deficiencies recorded Hybrid System Does not exist Pneumatic System Does not exist COMPACTOR Does not exist CONVEYING Does not exist DOMESTIC WATER SYSTEM Inspected Domestic Cold Water System Inspected Gravity System Does not exist Pressure Booster System Does not exist Water Service Inspected Instance Basement Room C 3- Fair Instance Condition Instance Quantity 1 EACH Instance Quantity Uom Deficiency Mobile Validity Version 2.0 (P) WATER MAIN:MISSING BACKFLOW PREVENTION DEVICE Page 1 of 5 Print Date: 6/16/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Mechanical Inspection Q797 Question Response DOMESTIC WATER SYSTEM Domestic Cold Water System Water Service Deficiency Location/Instance Deficiency Quantity Basement Room C 1 EACH INSTALL PRIORITY 3 LEVEL 2 No violations recorded Quantity Uom Potential Action Urgency of Action Purpose of Action Violations Inspected Domestic Hot Water System Domestic Hot Water Remote Storage Tank Does not exist Domestic Water Heat Exchanger Does not exist Electric Domestic Water Heater Inspected Condition 1- Good Deficiency No deficiencies recorded Gas Fired Domestic Water Heater Does not exist Oil Fired Domestic Water Heater Does not exist Inspected Domestic Water Distribution Piping 3- Fair Condition Deficiency No deficiencies recorded Inspected DRAIN/WASTE/VENT AND STORM SYSTEM Inspected Interior Storm Piping 3- Fair Condition Deficiency No deficiencies recorded Inspected Sewage Ejector Pump 2- Between Good and Fair Condition Deficiency No deficiencies recorded Inspected Sewage/Waste/Vent Piping 3- Fair Condition Deficiency No deficiencies recorded Does not exist Sump Pump DUAL TEMPERATURE SYSTEM (CHILLED AND HOT WATER) Does not exist Enclosed IDF Room Does not exist FIXTURES Inspected Staff And Other Inspected Janitor Sink Inspected Condition 3- Fair Deficiency No deficiencies recorded Inspected Lavatory/Sink Condition 3- Fair Deficiency No deficiencies recorded Inspected Toilet Condition 3- Fair Deficiency No deficiencies recorded Does not exist Urinal Inspected Student Inspected Drinking Fountain Condition 2- Between Good and Fair Deficiency No deficiencies recorded Inspected Lavatory/Sink Condition 3- Fair Deficiency No deficiencies recorded Does not exist Locker Room Shower Mobile Validity Version 2.0 (P) Page 2 of 5 Print Date: 6/16/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Mechanical Inspection Q797 Question Response FIXTURES Student Sink And Fountain Combo Unit Does not exist Toilet Inspected Condition 3- Fair Deficiency No deficiencies recorded Inspected Urinal Condition 3- Fair Deficiency No deficiencies recorded GAS FIRED FURNACE Does not exist GAS SERVICE Inspected Inspected CO/Gas Leak Detection Instance Boiler Room 2- Between Good and Fair Instance Condition Instance Quantity Instance Quantity Uom 1 EACH Installation Year Source of Installation Year 2007 Documented Deficiency No deficiencies recorded Gas Distribution Piping Does not exist Gas Meter Room Exhaust Fan Does not exist Gas Meter Room Vent Does not exist Gas Pressure Booster Does not exist Inspected HEATING Heating Coil In Ductwork Does not exist Hydronic Heating Inspected Backflow Preventer Does not exist Hot Water Heat Exchanger Does not exist Hydronic Hot Water Distribution: Piping, Pumps and Auxiliaries Inspected Condition 3- Fair Deficiency No deficiencies recorded Inspected Radiator/Convector/Fin Tube 3- Fair Condition Deficiency No deficiencies recorded Steam Heating Does not exist Steam supplied by External Sources Does not exist Unit Heater/Cabinet Heater Does not exist HEATING PLANT Replacement Quantity 3,548 MBH Net Replacement Uom Inspected Oil 2 Instance on Basement Burner Type Heating Plant Oil Number Boiler Auxiliaries Inspected Instance on Basement Boiler Auxiliary Piping Instance on Basement Inspected Instance Condition 3- Fair Deficiency No deficiencies recorded Boiler Emergency Stop Switch Instance on Basement Inspected Instance Condition 3- Fair Deficiency No deficiencies recorded Boiler Feedwater System Mobile Validity Version 2.0 (P) Page 3 of 5 Print Date: 6/16/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Mechanical Inspection Q797 Question Response HEATING PLANT Boiler Auxiliaries Boiler Feedwater System Instance on Basement Does not exist Boiler Feedwater Treatment(Automatic) Does not exist Instance on Basement Boiler Flue Exhaust Instance on Basement Inspected Instance Condition 3- Fair Deficiency No deficiencies recorded Boiler Make-up Water Backflow Preventer Instance on Basement Inspected Instance Condition 1- Good Deficiency No deficiencies recorded Boiler Room Steam And Condensate Piping Does not exist Instance on Basement Boiler Safety Valve Instance on Basement Inspected Instance Condition 1- Good Deficiency No deficiencies recorded Boiler System Inspected Instance on Basement Coal-fired Boiler Does not exist Instance on Basement Hot Water Boiler Instance on Basement Inspected Instance Boiler Room 3- Fair Instance Condition Instance Quantity Instance Quantity Uom 1,774 MBH Net Manufacturer EquipmentId Capacity/Size Quantity Capacity/Size UOM Source of Capacity/Size Installation Year Source of Installation Year Kewanee Boiler Corporation 83258-01 2040 MBH Gross Documented 1956 Documented Deficiency Deficiency Location/Instance Deficiency Quantity BEYOND USEFUL LIFE Boiler Room 1 EACH REPLACE PRIORITY 1 LEVEL 2 No violations recorded Quantity Uom Potential Action Urgency of Action Purpose of Action Violations Instance Boiler Room 3- Fair Instance Condition Instance Quantity Instance Quantity Uom 1,774 MBH Net Manufacturer EquipmentId Capacity/Size Quantity Capacity/Size UOM Source of Capacity/Size Installation Year Source of Installation Year Kewanee Boiler Corporation 83258-02 2040 MBH Gross Documented 1956 Documented Mobile Validity Version 2.0 (P) Page 4 of 5 Print Date: 6/16/2015 NYC Department of Education Building Condition Assessment Survey 2014-2015 Mechanical Inspection Q797 Question Response HEATING PLANT Boiler System Hot Water Boiler Deficiency Deficiency Location/Instance Deficiency Quantity BEYOND USEFUL LIFE Boiler Room 1 EACH REPLACE PRIORITY 1 LEVEL 2 No violations recorded Quantity Uom Potential Action Urgency of Action Purpose of Action Violations Modular Boiler Does not exist Instance on Basement Steam Boiler Does not exist Instance on Basement Fuel System Inspected Instance on Basement Boiler Fresh Air Louver/Damper Instance on Basement Inspected Instance Condition 3- Fair Deficiency No deficiencies recorded Burner/Burner Control Panel Instance on Basement Inspected Instance Condition 3- Fair Deficiency No deficiencies recorded Fuel Oil Storage/Supply System Instance on Basement Inspected Instance Condition 3- Fair Deficiency No deficiencies recorded Gas Trains And Vent At The Boiler Does not exist Instance on Basement Does not exist KITCHEN MDF Room Inspected Instance on Room 2F Dedicated A/C Equipment Instance on Room 2F Inspected Instance Condition 1- Good Deficiency No deficiencies recorded SCIENCE DEMO ROOM Does not exist SCIENCE LAB Does not exist SCIENCE PREP ROOM Does not exist SPRINKLERS, STANDPIPE, FIRE SYSTEM Does not exist SWIMMING POOL Does not exist VENTILATION Inspected Exhaust Fan Inspected 2- Between Good and Fair Condition Approximate Total # of Fans Deficiency 1-25 No deficiencies recorded Heating And Ventilating Unit Does not exist Metal Ductwork Inspected 3- Fair Condition Deficiency No deficiencies recorded Supply Fan Does not exist Unit Ventilator Does not exist Mobile Validity Version 2.0 (P) Page 5 of 5 Print Date: 6/16/2015