Chapter 3. Generator and Transformer Models; The Per-Unit System 3.1 Introduction 1. Use of the "per phase" basis to represent a three-phase balanced system. 2. Use the π model to describe transmission lines (see Chapter 5). 3. Simple models for generators and transformers to study steady state balanced operation. 4. One-line diagrams to represent a three phase system. 5. The per-unit system and the impedance diagram on a common MVA base. 3.2 Synchronous Generators • Note the coils aa', bb', and cc' are 120o apart. Axis of a-coil is the x-axis as shown. • These are Fr "concentrated" full pitch windings. In δr real machines the a Fsr windings are n distributed among many slots, and often c' b' are not full pitch. ωt • We assume the ψ r r' windings produce a sinusoidal mmf ψ around the rotor periphery (angle F around the airgap s c b with respect to winding axis) . • Assume the rotor is m a' excited with DC current I f producing a flux φ which rotates with the rotor at speed ω . At time t the rotor would have moved an angle ωt . The flux linkage for an N-turn a-winding will be maximum ( Nφ ) at ω t = 0 . The flux linkage with the a-winding will go to 0 at ω t = π / 2 . The flux linkage will go to ( − Nφ ) at ω t = π , and back to 0 at ω t = 3π / 2 . When ω t = 2π the flux linkage will Rotor position shown at • w t = p /2 be back to ( Nφ ) . Thus a whole cycle… This repeats every revolution of the rotor. • • The flux linkage with winding "a" is thus given by: λa = Nφ cos ωt Using Faraday's law, the voltage induced in phase "a" is given by: dλ = ω N φ sin ω t dt = Emax sin ωt ea = − π = Emax cos ω t − 2 Where Emax = ω Nφ = 2π fNφ , since 2π / 2 ≈ 4.44 , the rms value of the generated voltage is given by: E = 4.44 fNφ Fr a δr Fsr n c' b' r ωt ψ r' The frequency is a function of speed and the number of poles, thus: P n f = where n is 2 60 the speed in rpm (the synchronous speed) and P is the number of poles (always an even number). ψ If the phase "a" is connected to a load, then Fs b c a current ia will flow. Depending on the load, this current will have a m a' phase angle, say ψ (see figure) lagging the generated voltage ea which is along the xRotor position shown at w t = p /2 axis. Again, this is shown in the figure as the line "mn". N.B. The line "mn" is attached to and rotates with the rotor. Be careful also that the "Flux" vectors are spatial while the voltage and current vectors are phasors (in time). The same is true for phases "b" and "c" but they will "lag" the voltage in phase "a" by 120 and 240 degrees respectively. 2 Since ea ∝ sin (ωt ) , then we have: ia = Imax sin ( ωt − ψ ) ib = I max sin ( ω t −ψ − 120o ) ic = I max sin ( ωt − ψ − 240o ) Since mmf is proportional to the current, we then have: Fa = Fm sin ( ωt − ψ ) Fb = Fm sin ( ω t −ψ − 120o ) Fc = Fm sin ( ωt − ψ − 240o ) We now take components of these phasors along the line "mn" and in quadrature with it. Along "mn" we have: F1 = Fm sin ( ω t −ψ ) cos ( ωt − ψ ) + Fm sin (ω t −ψ − 120o ) cos ( ω t −ψ − 120o ) + Fm sin (ω t − ψ − 240o ) cos (ω t −ψ − 240o ) 1 Using the identity sin α cos α = sin ( 2α ) the above equation becomes: 2 F1 = Fm sin 2 (ωt − ψ ) + sin 2 ( ω t −ψ − 120o ) + sin2 ( ωt − ψ − 240o ) 2 It is noted that this expression is the sum of three balanced phasors hence is equal to zero. Next we consider the components of the mmf perpendicular to "mn": F2 = Fm sin ( ω t −ψ ) sin ( ω t −ψ ) + Fm sin ( ωt − ψ − 120 o ) sin ( ωt − ψ − 120o ) + Fm sin (ω t − ψ − 240 o ) sin ( ωt − ψ − 240o ) Using the identity sin 2 α = F2 = 1 (1 − cos2α ) we have: 2 { } Fm 3 − cos2 (ωt −ψ ) + cos2 (ω t − ψ − 120o ) + cos2 (ω t − ψ − 240o ) 2 The three cosine terms add to zero (balanced phasors) thus we have: 3 FS = 3 Fm 2 Thus the result of having three pulsating single phase fluxes produce (when applied symmetrically) a constant flux perpendicular to line "mn" and rotates at the same speed n as the rotor. This flux is called the "armature reaction" to the field of the rotor Fr . the various fields are shown for one phase (say phase "a") in the diagram below: Note that Fs is perpendicular to line "mn" and rotates with it at the same speed. The fact that Fs (which is proportional to Ia) is perpendicular to line "mn" indicates that that we can theorize that the armature current Ia is producing a reactive voltage drop parallel to line "mn" due to inductance in the machine. Run the command "rotfield" in a Matlab window to see a demo of the rotating field. Fr Fsr n Ear Esr Fs jX ar Ia V R a Ia m E jX l Ia Ia Figure 3.2 Page 53 θ is the angle between V and I a it is the power factor angle δ is the angle between E and V it is the power angle First the rotor field Fr produces the no-load generated voltage E (at zero armature current). Note that E lags Fr by 90 degrees. E is called the "excitation" voltage. It is directly proportional to the field current. The voltage/current phasors for phase "a" are shown above lagging the flux diagram by 90 deg. Note the above diagram is a "hybrid" combining spatial and temporal vectors. 4 Second, assume the armature carries a current to a load, now the armature reaction flux Fs is produced. This is perpendicular to line "mn". The two fluxes (due to rotor and armature) combine together to form the "resultant" flux Fsr. The resultant flux induces the generated on-load emf Esr. The armature mmf Fs induces the voltage Ear known as the armature reaction voltage. In all cases, each mmf produces a voltage lagging the mmf by 90 degrees. Note that the voltage Ea r leads Fs (hence Ia) by 90 degrees. Thus we can theorize an inductor model for this relationship with reactance Xar i.e. Ear = jX ar I a . Xar is known as the reactance of armature reaction. Thus we now have the circuit equation: E = Esr + jX ar I a The terminal voltage V is found by considering the armature resistance and leakage reactance thus: E = V + Ra + j ( X l + X ar ) I a Which can be simplified to: E = V + [ Ra + jX s ] I a where X s = X l + X ar is known as the synchronous reactance. The angle between V and Ia is θ the power factor angle. The power angle is the angle between E and V called δ. The circuit model of the machine is as shown below: The resistance Ra is much smaller than the synchronous reactance Xs and is often neglected. This is shown in the simplified one line diagram below where the machine is shown connected to an infinite E jX s Ia V Ra Ia jX s + + E V - - Load bus. An infinite bus has a voltage V (usually assumed at an angle zero) which does not change no matter how the generator is controlled or excited. A figure of merit of a generator is the percent voltage regulation VR defined as: VR = Vnl − Vrated E − Vrated ×100 = ×100 Vrated Vrated 5 The smaller the VR the better. In a real generator, the regulation is a few percent. 3.3 Steady-State Characteristics, Cylindrical Rotor Power factor control. Most generators are connected to a large power grid. This is an infinite bus (its voltage, angle and frequency are constant). Assuming the generator has small leakage reactance and small armature resistance, then its model is shown below: We have two ways of calculating the power (per phase): E jX s V Ia 1. P1φ = V I a cosθ 2. P1φ = E V sin δ Xs Equating these two equations we have E sin δ = X s I a cos θ . Assuming the power is constant, then from equation 1 we have: I a cos θ = const. This locus is shown as the vertical dashed line in the figure below. From equation 2, assuming the power is a constant we have: E sin δ = const . This locus is the horizontal dashed line shown. I a3 E3 E2 E1 Note that for this load, the minimum armature δ I V current is I a 2 when the power factor of the q generator is unity. Note that E2 is directly above I the voltage V . Thus I a 2 and V are in phase, producing unity power factor. If the excitation is increased, the emf of the generator is increased to some value say E1 as shown. Clearly the voltage of the generator leads the current hence it is like an inductor consuming vars (lagging power factor). On the other hand, if the excitation is reduced below that for unity power factor, the emf of the generator is smaller, say E3 which lags I a 3 . Now the power factor of the generator is "leading", i.e. it is like a capacitor (current leading voltage). A plot of the variation of I a as a function of field current is known as a V-curve. A family of such curves, one at each load is known as the V-curves of the generator. The minimum point on each curve corresponds to unity power factor. To the right (higher excitation) is the lagging power factor area and to the left is the leading power factor zone. 1 a2 1 a1 6 Power angle characteristics. Consider the machine connected to an infinite bus and neglecting armature resistance, the machine model is shown below: E S 3φ = 3VI a* But we have Ia = jX s Ia V E ∠δ − V ∠0 thus for complex power: Z s ∠γ 2 E V V S 3φ = 3 ∠γ − δ − 3 ∠γ thus the real and imaginary powers are given by: Zs Zs 2 EV V P3φ = 3 cos (γ − δ ) − 3 cos γ Zs Zs 2 E V V Q3φ = 3 sin (γ − δ ) − 3 sin γ Zs Zs and if we neglect the armature resistance we have: (Note that γ = 90o and Z s → X s ) EV V sin δ and Q3φ = 3 ( E cos δ − V ) . Thus the real power is a function of Xs Xs the power angle δ and varies as sin δ . The maximum power is given by: E V Pmax(3φ ) = 3 . Xs The angle δ starts at zero when the machine does not deliver any power. As the machine is loaded, the power delivered increases and the angle δ increases. As the angle δ reaches 90 o , maximum power is reached. If prime mover power is increased beyond this point, the machine will speed up and loose synchronism. This means the tie between the machine and the power grid can handle only the maximum power shown above. In real operation, the power angle is very small of the order of 10 degrees and less. The power angle δ can "swing" by larger amounts under transient conditions. P3φ = 3 The equation for Q shows that Q3φ ; 3 V Xs ( E − V ). Thus if E > V the generator delivers reactive power and the generator is said to be overexcited. If E < V , the generator is underexcited and the reactive power delivered to the bus is negative, thus the generator is receiving reactive power from the bus. Generators are usually operated in the overexcited mode since they need to supply the system with reactive power: most our domestic loads are reactive. Example 3.1 7 A 50-MVA, 30-kV, three phase, 60 Hz synchronous generator has Xs = 9 Ω per phase and a negligible resistance. The generator is delivering rated power at 0.8 power factor lagging at the rated terminal voltage to an infinite bus. (a) Determine the excitation voltage per phase E and the power angle δ. (b) With the excitation held constant at the value found in (a), the driving torque is reduced until the generator is delivering 25 MW. Determine the current and the power factor. (c) If the generator is operating at the excitation voltage of part (a), what is the steadystate maximum power the machine can deliver before losing synchronism? Also, find the armature current corresponding to this maximum power. The Matlab program follows: Ra=0; Xs = 9; Zs = Ra + j*Xs; S = 40 + j*30; V = 30/sqrt(3); % MW and kV Ia1 = conj(S)*1000/(3*conj(V)); % Amp Ia1M = abs(Ia1), Ia1ang=angle(Ia1)*180/pi E1 = V + Zs*Ia1*0.001; % kV E1M = abs(E1), delta1 = angle(E1)*180/pi % kV, deg disp('(b)') P = 25; % MW delta2 = asin(P*Xs/(3*abs(E1)*V)); delta2d = delta2*180/pi E2 = E1M*(cos(delta2) +j*sin(delta2)); % kV Ia2 = (E2 - V)*1000/Zs; Ia2M = abs(Ia2), Ia2ang=angle(Ia2)*180/pi PF = cos(angle(Ia2)) disp('(c)') Pmax = 3 *E1M*V/Xs % kW E3 = E1M*(cos(pi/2) +j*sin(pi/2)); % kV Ia3 = (E3 -V)*1000/Zs; % A Ia3M = abs(Ia3), Ia3ang=angle(Ia3)*180/pi PF = cos(angle(Ia3)) Ia1M = 962.2504 Ia1ang = -36.8699 E1M = 23.5584 delta1 = 17.1027 (b) delta2d = 10.5914 Ia2M = 807.4918 Ia2ang = -53.4284 PF = 0.5958 (c) Pmax = 136.0147 8 Ia3M = 3.2489e+003 Ia3ang = 36.3239 PF = 0.8057 Example 3.2 The generator of example 3.1 is delivering 40 MW at a terminal voltage of 30 kV. Compute the power angle, armature current, and power factor when the field current is adjusted for the following excitations: (a) The excitation voltage is decreased to 79.2 percent of the value found in example 3.1. (b) The excitation voltage is decreased to 59.27 percent of the value found in example 3.1. (c) Find the minimum excitation below which the generator will lose synchronism. The Matlab program follows: Ra=0; Xs = 9; Zs = Ra + j*Xs; V = 30/sqrt(3); P = 40; E1M = 0.792*23.558; delta1 = asin(P*Xs/(3*abs(E1M)*V)); delta1d = delta1*180/pi E1 = E1M*(cos(delta1) +j*sin(delta1)); Ia1 = (E1 - V)*1000/Zs; Ia1M = abs(Ia1), Ia1ang=angle(Ia1)*180/pi PF = cos(angle(V/Ia1)) disp('(b)') E2M = 0.5925*23.558; delta2 = asin(P*Xs/(3*E2M*V)); delta2d = delta2*180/pi E2 = E2M*(cos(delta2) +j*sin(delta2)); Ia2 = (E2 - V)*1000/Zs; Ia2M = abs(Ia2), Ia2ang=angle(Ia2)*180/pi PF = cos(angle(Ia2)) disp('(c)') E3M = P *Xs/(3*V*1) E3=E3M*(cos(pi/2)+j*sin(pi/2)); Ia3 = (E3 -V)*1000/Zs; Ia3M = abs(Ia3), Ia3ang=angle(Ia3)*180/pi PF = cos(angle(Ia3)) delta1d = 21.7975 Ia1M = 769.8005 Ia1ang = -0.0283 PF = 1.0000 (b) delta2d = 29.7592 Ia2M = 962.7210 9 Ia2ang = 36.9072 PF = 0.7996 (c) E3M = 6.9282 Ia3M = 2.0728e+003 Ia3ang = 68.1986 PF = 0.3714 Notes: in (a) the generator is operating at unity power factor. In both (b) and (c) the generator is under-erexcited and is receiving reactive power (power factor of load is leading, i.e. capacitive load and the generator is inductive.) In the real world the load is usually inductive (lagging power factor) and the generator is over-excited, delivering reactive power. Example 3.3 For the generator of example 3.1, construct the v-curve for the rated power of 40 MW with varying field excitation from 0.4 power factor leading to 0.4 powr factor lagging. Assume the open-circuit characteristic in the operating reagion is given by E = 2000If. The Matlab program follows: P = 40; % real power, MW V = 30/sqrt(3)+ j*0; % phase voltage, kV Zs = j*9; % synchronous impedance ang = acos(0.4); theta=ang:-0.01:-ang; % Angle from 0.4 leading to 0.4 lagging pf P= P*ones(1,length(theta)); % generates P array of same size Iam = P./(3*abs(V)*cos(theta)); % current magnitude kA Ia = Iam.*(cos(theta) + j*sin(theta)); % current phasor E = V + Zs.*Ia; % excitation voltage phasor Em = abs(E); % excitation voltage magnitude, kV If = Em*1000/2000; % field current, A plot(If, Iam), grid xlabel('If, A'), ylabel('Ia, kA') text(3.4, 1, 'Leading pf'), text(13, 1, 'Lagging pf') text(9, .71, 'Upf') 10 2 1.8 1.6 Ia, kA 1.4 1.2 1 Leading pf Lagging pf 0.8 Upf 0.6 2 4 6 8 10 If, A 12 14 16 18 Note that the over-excited generator (load is inductive, generator is capacitive) is the normal way to operate the generator since most loads are inductive. If the load becomes capacitive, then the generator is operated in the under-excited mode. 11