SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM
GUJARAT ENERGY TRANSMISSION CORPORATION
LTD.
SARADAR PATEL VIDYUT BHAVAN,
RACE COURSE, BARODA – 390 007.
FOR
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
Page 1 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM
(A) SPECIAL INSTRUCTIONS TO BIDDER
Please read following instructions carefully before submitting your bid.
1. All the drawings, i.e. elevation, side view, plan, cross sectional view etc., in AutoCAD format and manuals in PDF format, for offered item shall be submitted. Also the hard copies as per specification shall be submitted.
2. The bidder shall submit Quality Assurance Plan for manufacturing process and Field Quality Plan with the technical bid.
3. The bidder shall have to submit all the required type test reports for the offered item. In case of non-submission of the type test reports with the offer, the bid shall be liable to be rejected.
4. The bidder must fill up all the point of GTP for offered item/s.
Instead of indicating “refer drawing, or as per IS/IEC”, the exact value/s must be filled in.
5. All the points other than GTP, which are asked to confirm in technical specifications must be submitted separately with the bid.
6. The bidder is required to impart training in view of manufacture, assembly, erection, operation and maintenance for offered item, at his works, to the person/s identified by GETCO, in the event of an order, free of cost. The cost of logistics will be bear by GETCO.
7. Please note that the evaluation will be carried out on the strength of content of bid only. No further correspondence will be made.
8. The bidder shall bring out all the technical deviation/s only at the specified annexure.
9. The bidder should indicate manufacturing capacity by submitting latest updated certificate of a Chartered Engineer (CE).
Page 2 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM
(B) QUALIFYING REQUIREMENT DATA
(For Supply)
Bidder to satisfy all the following requirements.
1) The bidder shall be Original Equipment Manufacturer
(OEM). The offered equipment have to be designed, manufactured and tested as per relevant IS/IEC with latest amendments.
2) The minimum requirement of manufacturing capacity of offered type, size and rating of equipment shall be 7 times
tender / bid quantity. The bidder should indicate manufacturing capacity by submitting latest updated certificate of a Chartered Engineer (CE).
3) Equipment proposed shall be of similar or higher rating and in service for a minimum period of THREE (3) years and satisfactory performance certificate in respect of this is to be available and submitted.
Sr.
No
4) The bidder should clearly indicate the quantity and Single
Value Contract executed during last FIVE (5) years, for the offered equipment. Bidder should have executed one single contract during last five years for the quantity equivalent to tender / bid.
The details are to be submitted in following format,
ITEMS
SUPPLIED
TO
ORDER
REFERENCE
No. & DATE
ITEMS
QUANTITY
ORDER FULLY
EXECUTED
YES/NO
STATUS, IF
ORDER UNDER
EXECUTION
5) Equipment offered shall have Type Test Certificates from accredited laboratory (accredited based on ISO/IEC Guide
25 / 17025 or EN 45001 by the National accredition body of the country where laboratory is located), as per IEC / IS / technical specifications not older than FIVE (5) years and shall have validity till expiry of validity of technical bid.
REMARK
Page 3 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM
(I) GENERAL :
Indoor PLCC Equipments are required for important 400KV,
220KV and 132KV Sub/station for Speech, Data Transmission,
Protection and Teleprinter Links.
(II) GENERAL REQUIREMENT :
The equipments shall be of latest components, technology and highly reliable. The equipments offered must have been type tested.
(III) SCOPE OF SUPPLY :
PLCC TERMINAL WITH Single or DUAL 19” RACK OF
ETL-41 SYSTEM as per schedule of requirement , 4 Wire
Telephone, Dummy Load Print for testing of ETL-41 SYSTEM on
Loop, 75 Ohm Cylindrical Balance Load, 4 Nos. of UHF
Connector (UHF Gland), Emergency test tone calling jack handset, industrial good quality single phase A.C exhaust fan for cooling of carrier terminal under operation, Operating instruction manual,
Programming & tuning procedure manual etc., all are included in scope of supply. The Carrier equipment shall be supplied with fully wired complete in all respect with all interconnections between equipments wherever necessary and terminal blocks required for termination of external wiring or to provide interconnection between equipments to be integrated along with steel channels with fixing nut/screws. The internal co-axial loop with UHF gland of sufficient length for HF signal connectivity between two racks of ETL-41 system in case of panel with dual rack shall also be provided.
The equipment shall be of latest design with motherboard construction.
You will have to impart free training of ETL version carrier equipments to at least 3 to 4 telecom engineers of G.E.T.C.O to get acquainted with the technology for our new incumbents.
(IV) SPECIFICATION :
The equipments to be supplied under this specification shall function satisfactorily under tropical, hot, humid, salty and chemically polluted climatic condition with adverse temperature
Page 4 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM condition. The equipment shall be manufactured and tested as per latest national or international standard (IS, IEC, CCITT, CIGRE, etc.) whichever is better. This will be clearly brought out by the bidder. The equipments offered shall confirm to, but not limited to following standards.
(1) IEC 495 - Single sideband Power Line Carrier Terminals.
(2) IEC 834-1/1988 - Performance & Testing of teleprotection
(Part-I) equipments of Power system - Narrow band
Command system.
(3) IEC 68-2-3/1969 - Environmental Testing Part-2 Tests section-3
Test Ca: Damp heat steady state.
In addition to the above, the carrier terminal shall be manufactured and supplied detailed as under:
(IV)(A) CARRIER TERMINAL EQUIPMENT :
It will be multipurpose equipment to transmit and receive speech, data, protection, tele-operation, telemetry, and facsimile signals. It will be manufactured and supplied as per following details.
The "Carrier Cabinet" shall be multipurpose cubicle suitable to accommodate carrier equipment, electronic group selector, protection coupler, modems for data transmission, DC to DC convertor and band pass filters etc.
All the equipments details as above shall fit into different tiers of the "Swinging Frame" fitted inside the above cubicle, swinging frame shall be of 14 SWG sheet steel.
All the equipments fitted in above swinging frame shall be fully wired. It should be possible to test the equipment from front side and erect the cubicle side-by-side or back-to-back.
The cubicle shall be made from 16 SWG sheet steel. It will have rounded corners with front door and lock. It will be designed for efficient cooling with an exhaust fan at the top inside the cabinet, to take away the heat generated within the terminal. Normally the cable entry shall be from the bottom, however, suitable provision
Page 5 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM shall be made for cable entry from top, which shall be covered by blanking plate at the time of supply. Visual indication shall be provided in front of the terminal at the top for indication of failure of carrier terminal i.e. Transmitter, Receiver or Power supply.
There shall be provision for audio indication also. Suitable labels for identification of indication shall be provided.
The cubicle shall be provided with foundation holes for fixing the same on foundation. Air inlet shall be provided at bottom and Air
Outlet with exhaust fan at the top. Any opening shall be provided with wire mesh for vermin proofing. The cubicle shall be completely dust proof and vermin proof.
The cubicle shall go through seven-tank phosphating process and shall be coated with two coats of red oxide primer followed by synthetic enamel.
2 Nos. vertical C-Channels with slotted angles and sufficient no. of horizontal channels with holes shall be provided inside the cubicle at backside for wiring purpose suitable for system capacity of twin 19” rack of ETL-41.
The cubicle size shall generally match with existing cubicle and shall be of size 1960mm X 670 mm X 420 mm (Height x Width x
Depth). It shall be provided with standard 19" tiers to house the modules.
Three ways HF co-axial clamp with terminal shall be provided inside the cubicle at rear side.
One 8 way electrical connector, a three-pin plug with fuse shall be provided for 250 V AC 3 Phase 50 C/S supply. The cubicle shall be fully wired. Arrangement for internal lighting shall be provided using 15-Watt fluorescent tube of Philips make.
The equipment shall be supplied with arrangement suitable to operate either on 48V DC or 220V DC supply as per requirement provided in “SCHEDULE OF REQUIREMENT
OF respective tender” with voltage variation from - 15% to +
20% and ripple of
<
2 % maximum.
Page 6 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM
The carrier power supply module shall be provided with a circuit breaker, which shall automatically trip due to over voltage to carrier equipment and/or over modulation. The circuit breaker shall be provided in front of power supply module so that it is easily accessible. This circuit breaker shall be provided with a facility to switch on and to switch off the same mechanically by hand, by pressing and releasing a push button switch. A fuse shall also be provided in series of this circuit breaker, which shall operate in case of failure of the circuit breaker.
Amplitude Modulation, single side band, 40W (which can be programmed for 20w/10w/5w, if required) peak envelope power at co-axial output including pilot and if any other carrier signal shall be provided. HF range shall be 40 kHz to 500 kHz. The equipments are meant for multipurpose application like speech, data, teleprinter and control command facility. The requirement of
IS 9528 and IEC 663 shall be fulfilled for accurate transmission of control command, data and TP signals.
A central frequency synthesizer, whose basic frequency is obtained from a crystal-controlled oscillator with very high frequency stability, shall generate the necessary frequencies required in carrier terminal. Thus a synthesized version carrier set shall be preferable.
Carrier terminal shall be multipurpose, fully transistorized IC version with modular construction and mother board technique, fully programmable i.e. pilot frequency, audio freq. & carrier freq. with synchronizer and highly efficient for adjacent channel working to overcome frequency congestion problem.
It will be suitable for 2-Wire services and Hand set/Emergency call telephone, which can be used for "Audio Test", shall be provided with necessary circuitry etc., together with handset.
The transmitter shall be provided with 3 teleoperational input minimum (in addition to speech and protection input), which shall be fully decoupled and adjustable for level setting. Preferably inputs shall be through disconnectible links to avoid use of soldering irons for soldering and desoldering of wires from terminal block. Minimum separate tunable teleoperational output
Page 7 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM shall be provided, for the normal 600-Ohm termination.
Suitable facility for transit connection of teleoperational channel shall be provided. Additional outputs may be provided for this purpose.
The "Signal Boosting" facility shall be provided for important signals like "Protection of Tele-operational signals". The speech is disconnected and entire output is available for protection signals.
The bidder shall describe the arrangement provided.
A built in "PLC EQUALIZER" shall be provided to overcome effect of amplitude distortion due to mismatch etc. Equalization facility for auxiliary carrier shall be described in details.
A supervision module with necessary circuitry shall be provided to monitor Transmitter, Receiver and Power supply. Both the collective alarm and individual alarm shall be provided. Audio and
Visual indication shall be preferable. The indication for squelch operation is necessary. Suitable potential free contact shall be provided for external alarms. The bidder shall describe in detail indications, internal alarm and external alarms provided.
A module with built-in meter and oscillator with selector switch shall be provided with necessary circuitry to test and commission the PLC link without the help of an external signal for ease of inspection and testing. A cylindrical dummy load, dummy load print for testing shall be in the scope of supply. It shall be possible to test the equipment locally by a dummy load. It is preferable that equipment is provided with facility to test transmitter and receiver locally by connecting them back-to-back. Any extra optional print required for such type of test shall be in the scope of supply. Builtin AGC test for HF level variation of + 14 dB/-26 dB may be necessary. The local testing facility provided shall be described in detail by all bidders. The 4 Wire express telephone instruments shall also be in the scope of supply. The bidder shall have to provide training to four personals of GETCO on all the equipments covered under this specification free of cost at their works.
All the test points with standard values, indications etc. shall be provided in front of the cabinet and shall be easily accessible.
Page 8 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM
All the bidders should furnish full technical particulars of their equipment as indicated in Schedule-"A" attached.
The carrier terminal shall have a 4 kHz bandwidth so that it is compatible with UHF/Microwave equipment. Speech shall use bandwidth up to 2 kHz. The rest of the band shall be utilized for teleoperational channels. The bidder shall indicate possible number of teleoperational channels with speed. The pilot frequency shall be above 3600 Hz and should be programmable.
The bidder shall indicate Frequency Spacing required between
Transmit and Receive bands for parallel working of a number of
Carrier Terminals on a Common Line. This will be indicated in
Schedule-A attached.
Low Power consumption shall be desired feature to maintain healthy communication during system disturbance.
The equipment shall be suitable for co-axial cable having impedance of 75/125-Ohm unbalanced or 150-Ohm balance. This should be programmable.
Carrier Terminal shall be provided with 4-wire jack; dummy load module, and 75/125-Ohm load in loose.
Carrier Terminal shall have in built Digital Transit Filter with programmable frequency and also in built Compressor and
Expander for improving the S/N ratio.
The equipment must have gone through all environmental and field tests and shall work satisfactorily under hot, humid and polluted climate. It should have worked for at least five years successfully in Electricity Boards. It shall work satisfactorily up to 55
°
C. It shall satisfy a storage temperature of 70
°
C. The Temperature criteria shall be shown by laboratory test by using hot chamber during inspection.
The equipment shall be provided with a nameplate in front of cabinet indicating make, serial no., Transmit and Receive
Page 9 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM frequency and station Direction. The module layout and station direction and Transmit-Receive Frequency shall be indicated behind the door.
Bidder shall indicate guaranteed values for carrier terminal offered by him. This shall be indicated in Schedule-A attached.
The bidder may quote different models being manufactured by them, which are equivalent to or better than the specified.
(IV)(B)
(1) Any deviation shall only be indicated in Schedule-A/1 attached with this specification.
(2) The GETCO reserves right to increase or decrease the quantity at the time of placing the order.
(3) The GETCO reserve right either to accept or reject any of the offers without assigning the reason.
(V) CONFIGURATION:
The Configuration of 40 Watt Single Channels, Fully
Programmable Carrier Equipment Type ETL-41 shall have following different cards/prints.
•
B5LA : Power Supply Unit
•
N3NL : Test Meter
•
E5LA or E5LB: Tx-Filter (Detail of model will be decided later on & based on Tx/Rx frequencies).
•
P3LA : RF Hybrid
•
B4LA : 48V DC/DC Converter
•
O4LA + E1LA : Tele Control Interface
•
O4LC : 2/4 Wire PAX Interface
•
P4LA : Pilot and Supervision
•
P4LB : AF Converter
•
P4LC : IF Converter
•
P4LD : Rx RF Converter
•
P4LF : Tx RF Converter
•
P4LG : Carrier Generator
•
P1LA : RF Amplifier
Page 10 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM
•
P3LK : Dummy Load Print
•
Any other card/print required for proper working of carrier terminal.
(VI) TYPE TESTS:
Valid type test reports not older than 5 Years and shall be valid up to expiry of validity of offer for following tests along with all test results sheets & reference documents shall be submitted with the offer with ‘List of Type Tests’ in Performa- X given here under.
Performa – X:
Sr.
No.
Test
Equipment
Description of Applicable test conducted Standard/
Clause
Test of report
No. & Name test
Remarks
1. 2 3 4 laboratory
5 6
1.
Voltage variation test
2.
Carrier frequency range & band
3.
Frequency Accuracy
4.
Transmit/receive frequency Difference
5.
Automatic gain control
6.
Harmonic Distortion
7.
Selectivity
8.
Nominal impedance, return loss and tapping loss
9.
Balance to Ground
10.
Limiter action
11.
Spurious emission
12.
Carrier frequency levels
13.
Attenuation Distortion
14.
Noise Generated within Terminals
15.
Near end/Far end Cross Talk
16.
Group Delay Distortion
17.
Conducted noise
18.
Telephone Signaling Channel Distortion
19.
Speech Levels
Page 11 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM
20.
Voltage withstand test and Insulation test
21.
Teleprotection interface
22.
Input and Output level
23.
Speech band
24.
Frequency band above speech band
25.
EMI/EMC tests
26.
Conducted emission
27.
Radiated emission
28.
Radiated Susceptibility Amplitude modulated
29.
Electrostatic Discharge
30.
Electrical Fast Transient (EFT)
31.
High Frequency Disturbance test
32.
Storage test
33.
Dry Heat test
34.
Cold test
35.
Damp heat test
36.
Impulse withstand
37.
Power Supply variations
(VII) DRAWINGS:
Following Drawings shall be submitted with the offer.
1.
Module Layout For ETL 41 : Unit Arrangement
2.
Cabinet Layout For ETL 41
3.
Wiring Diagram For ETL 41 (DC Supply & Alarm)
The list of drawings that require to be submitted for approval on receipt of A/T from GETCO is as under.
1. Module Layout for ETL-41
2. Cabinet Layout for ETL-41 (Single or Dual 19” rack)
3. Cabinet wiring diagram (Single or Dual 19” rack)
4. Cabinet General Dimensional Drawing
5. External termination for ETL-41 (Single or Dual rack)
6. List of accessories
Page 12 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM
Sr.
No.
S C H E D U L E "A"
SCHEDULE OF GENERAL TECHNICAL DATA AND
GUARANTEED TECHNICAL PERTICULARS
(
TO BE FURNISHED BY THE BIDDER FOR CARRIER TERMINAL)
SYSTEM PARTICULAR TECHNICAL
PARTICULAR OF
BIDDER'S EQUIPMENT
1. Name of OEM
2. Type/Model
3. Operating Mode
4. HF Band
5. Nominal Bandwidth
6. Send / Receive Band
7. Permissible line attenuation
8. Frequency spacing for parallel
Working on a common line
9. HF System Impedance
10. Carrier Frequency Stability
11. Useful AF Bandwidth
12. Frequency Response
13. Linearity
14. Non - Linear Distortion
15. Near and Far End Crosstalk
16. Crosstalk Attenuation (Double channel)
17. Group delay
18. Basic Noise
19. Audio Frequency difference
Transmit to receive
20. Supervision alarms
21. Alarm Outputs
22. Ambient Conditions:
(a) For guaranteed data
(b) For reliable operation
(c) Storage
Page 13 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM
S C H E D U L E "A"
SCHEDULE OF GENERAL TECHNICAL DATA AND
GUARANTEED TECHNICAL PERTICULARS
Sr.
No.
23.
(
TO BE FURNISHED BY THE BIDDER FOR CARRIER TERMINAL)
SYSTEM PARTICULAR
Transmitter Data
TECHNICAL
PARTICULAR OF
BIDDER'S EQUIPMENT
(a) HF Output Power
(b) Harmonic and Spurious Signal
Attenuation
(c) Pilot channel with Programmable
range of Frequency
(d) Speech Input: 2 Wire
4 Wire
(e) Limiter Characteristics
(f) Suppression of unwanted Side bands.
24. Telephone Criteria
(a) Signaling
(b) Transit / Terminal Switching (V)
(c) Hybrid Switching (GA)
(d) 4 - Wire remote / emergency Call
telephone
25. Teleoperation Signals:
(A) Teleoperation I/P's
(a) Number & type of I/P
(b) Number of I/P with
Boosting Facility.
(c) Nominal I/P level.
(d) I/P level range
(e) Balance referred to
ground
(f) Return loss
(g) Minimum level for
maximum RF output
power.
(h) Boosting criteria.
Page 14 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM
Sr.
No.
S C H E D U L E "A"
SCHEDULE OF GENERAL TECHNICAL DATA AND
GUARANTEED TECHNICAL PERTICULARS
(
TO BE FURNISHED BY THE BIDDER FOR CARRIER TERMINAL)
SYSTEM PARTICULAR TECHNICAL
PARTICULAR OF
BIDDER'S EQUIPMENT
(B) Teleoperation O/P's
(a) Number & type of O/P's
(b) Nominal O/P level
(c) O/P level range
(d) Maximum O/P level (PEP)
(e) Balance referred to ground
(f) Return loss
Whether teleoperation I/P's & O/P's
expandable by inserting additional interface
module.
Whether provision is made for Programmable
Digital transit Filter, which allow to pass
required Band & frequencies of Teleoperation
Signal .
26. Receiver Data
(a) HF Sensitivity at coax input and at
Relative system impedance (speech) :
Carrier Frequency
(b) Selectivity :
From 4 kHz Carrier Band
(c) Image rejection
(d) IF rejection
(e) Automatic gain control:
AF Output Level
Time constant for 10 dB level
variation
(f) Hunting characteristics :
Synchronizing channel bandwidth
With loss of synch. signal
(auxiliary carrier)
Synchronization time with
loss of signal for 1 second:
Describe the method of
synchronization
Page 15 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM
Sr.
No.
S C H E D U L E "A"
SCHEDULE OF GENERAL TECHNICAL DATA AND
GUARANTEED TECHNICAL PERTICULARS
(
TO BE FURNISHED BY THE BIDDER FOR CARRIER TERMINAL)
SYSTEM PARTICULAR
(g) Frequency response equalization
TECHNICAL
PARTICULAR OF
BIDDER'S EQUIPMENT
(h) Describe the method of Equalization
(i) Speech outputs:
•
2 wire
•
4 wire
•
Symmetry against ground
• return loss
•
DC source resistance
(j) Signaling criteria :
(k) Pulse distortion :
(l) Squelch :
27. POWER SUPPLIES
(a) Mains
(b) Consumption
(c) Battery
(d) Consumption
(e) Reflected noise
28. TEST EQUIPMENT
(A) Test Tone generator : Test Tone
(B) Audio Tests :
(a) Band width
(b) Level range
(c) Input impedance
(d) Dummy load / test loop
(Whether print required for loop test is
provided)
(C) Any other test equipments required.
29. Insulation test and EMC:
(A) Unbalanced Carrier I/O
(a) impulse voltage test
(b) HF interference test
(c) Fast electrical transients/bursts
Page 16 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM
Sr.
No.
S C H E D U L E "A"
SCHEDULE OF GENERAL TECHNICAL DATA AND
GUARANTEED TECHNICAL PERTICULARS
(
TO BE FURNISHED BY THE BIDDER FOR CARRIER TERMINAL)
SYSTEM PARTICULAR TECHNICAL
PARTICULAR OF
BIDDER'S EQUIPMENT
(B) Balanced Carrier I/O
(a) Voltage withstand
(b) Insulation resistance
(c) Impulse voltage test
(d) HF interference test
(e) Fast electrical transients/burst
FREQUENCY SPACING required for operation of carrier Terminal on a common line:
(a) Transmitting Band to Own
Receiving Band :
(b) Transmitting Band to neighboring
Transmitting Band :
(c) Transmitting Band to neighboring
Receiving Band :
(d) Receiving Band to neighboring
Receiving Band :
Page 17 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM
S C H E D U L E ' A/1
(To be filled in and signed by the Tenderer)
Schedule of deviations from Technical Specifications for ____________.
We / I have carefully gone through the Technical Specification and we / I have satisfied ourselves / myself and hereby confirm that our / my offer strictly confirm to the requirements of the Technical Specification except for the deviations given below :
Sr.No. Description Stipulations in specification
Deviation
Offered
Remarks
___________________________________________________________
Signature :
Name of Authorized signatory of the company :
Name of the tendering Company
Date :
Place:
Page 18 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM
Description Sr.No.
1. 40Watt Single Channel, Fully Programmable
Carrier Equipment Type ETL-41 of ABB Make suitable to operate on 48V DC and with 4-
Wire table telephone for ETL, Dummy Load Print
P3LK, 75 Ohm Cylindrical Load and 4 Nos. of
UHF Gland , Emergency jack handset as per technical Specification.
2. 40Watt Single Channel, Fully
Programmable Carrier Equipment Type
ETL-41 of ABB Make suitable to operate on 220V DC and with 4-Wire table telephone for ETL, Dummy Load Print
P3LK, 75 Ohm Cylindrical Load and 4 Nos. of UHF Gland , Emergency jack handset as per technical Specification.
3. Carrier Terminal Equipment with Dual 19” rack of 40Watt Single Channel, Fully
Programmable Carrier Equipment Type
ETL-41 of ABB Make suitable to operate on 48V DC and with 4-Wire table telephone for ETL, Dummy Load Print
P3LK, 75 Ohm Cylindrical Load and 4 Nos. of UHF Gland , Emergency jack handset as per technical Specification.
4. Carrier Terminal Equipment with Dual 19” rack of 40Watt Single Channel, Fully
Programmable Carrier Equipment Type
ETL-41 of ABB Make suitable to operate on 220V DC and with 4-Wire table telephone for ETL, Dummy Load Print
P3LK, 75 Ohm Cylindrical Load and 4 Nos. of UHF Gland , Emergency jack handset as per technical Specification.
Unit Quantity
No.
No.
No.
No.
Page 19 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012