Wallmount 2 Way Interrupter

advertisement
Wallmount 2 Way Interrupter
S201066-003
Voltage: Continuous Current: Load-­‐Break Current: Basic Insulation Level (BIL): Interrupting Current (Sym.): Interrupting Current (Asym.): Peak Current: Mechanical Operations: 25 kV 600 A 600 A 125 kV 12,500 A 20,000 A 32,500 A 7500 15.5 kV 600 A 600 A 95 kV 12,500 A 20,000 A 32,500 A 7500 17.5 kV * 600 A 600 A 125 kV 16,000 A 25,600 A 41,600 A 2000 Certifiedto toIEEE IEEECC37.74-2003
Certified 37.74-­‐2003 and
and C37.60-2012.
C37.60-­‐2012. kAkA Fault
Interruption
capabilities.
* *17.5
17.5 kkV
V ddesigns
esigns aare
re available
available with
with 16
16 Fault Interruption capabilities. Office: (720) 440-9404
• 5073 Silver Peaks Avenue, #101 • Dacono, Colorado 80514 • www.innovative-switchgear.com
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF ISSI.
ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION
OF ISSI IS PROHIBITED
30"
36"
8"
LIFTING
EYE (2)
33-1/2"
8"
VIEWING WINDOWS
(2)
19-3/4"
22"
LOAD BREAK
PARKING STAND
(6)
600 AMP
BUSHING
(6)
APPROX. 420 LBS
WEIGHT
NATURAL
FINISH
304 STAINLESS STEEL
MATERIAL
GROUNDING
NUTS (2)
OPERATING
HANDLE
OPEN-CLOSED
SEMAPHORE
RELAY
CONNECTOR
600
WAY 2
UNLESS OTHERWISE SPECIFIED
TOLERANCE ARE: 1/16
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
600
WAY 1
23-1/2"
DATE
DATE
B
11 OCT 2013
DATE
17 JUN 2014
ALL DIMENSIONS PER
ASME Y14.5 1994
ENG APPR
CWALLACE
DRAWN
RLS
ENG
30-1/4"
32"
S201066-003
S201066-003-OL
CAD FILE
S201066-003-OL
DO NOT SCALE DRAWING
DRAWING NUMBER
1 OF 1
WALLMOUNT, 25KV, 12.5KA, 2 WAY WALL MOUNTED,
VCB WITH VISIBLE OPEN ISOLATION POINT
DESCRIPTION
PART NUMBER
5073 Silver Peaks Ave.
#101, Dacono CO.
80514