Wallmount 2 Way Interrupter S201066-003 Voltage: Continuous Current: Load-­‐Break Current: Basic Insulation Level (BIL): Interrupting Current (Sym.): Interrupting Current (Asym.): Peak Current: Mechanical Operations: 25 kV 600 A 600 A 125 kV 12,500 A 20,000 A 32,500 A 7500 15.5 kV 600 A 600 A 95 kV 12,500 A 20,000 A 32,500 A 7500 17.5 kV * 600 A 600 A 125 kV 16,000 A 25,600 A 41,600 A 2000 Certifiedto toIEEE IEEECC37.74-2003 Certified 37.74-­‐2003 and and C37.60-2012. C37.60-­‐2012. kAkA Fault Interruption capabilities. * *17.5 17.5 kkV V ddesigns esigns aare re available available with with 16 16 Fault Interruption capabilities. Office: (720) 440-9404 • 5073 Silver Peaks Avenue, #101 • Dacono, Colorado 80514 • www.innovative-switchgear.com THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF ISSI. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF ISSI IS PROHIBITED 30" 36" 8" LIFTING EYE (2) 33-1/2" 8" VIEWING WINDOWS (2) 19-3/4" 22" LOAD BREAK PARKING STAND (6) 600 AMP BUSHING (6) APPROX. 420 LBS WEIGHT NATURAL FINISH 304 STAINLESS STEEL MATERIAL GROUNDING NUTS (2) OPERATING HANDLE OPEN-CLOSED SEMAPHORE RELAY CONNECTOR 600 WAY 2 UNLESS OTHERWISE SPECIFIED TOLERANCE ARE: 1/16 UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES 600 WAY 1 23-1/2" DATE DATE B 11 OCT 2013 DATE 17 JUN 2014 ALL DIMENSIONS PER ASME Y14.5 1994 ENG APPR CWALLACE DRAWN RLS ENG 30-1/4" 32" S201066-003 S201066-003-OL CAD FILE S201066-003-OL DO NOT SCALE DRAWING DRAWING NUMBER 1 OF 1 WALLMOUNT, 25KV, 12.5KA, 2 WAY WALL MOUNTED, VCB WITH VISIBLE OPEN ISOLATION POINT DESCRIPTION PART NUMBER 5073 Silver Peaks Ave. #101, Dacono CO. 80514