TECH T NICAL L SPAN TS T 1402::2016 SPEC S IFICAT TION SEWA S GE TR REATM MENT S SYSTEM Standa S rd Sew wage Tre eatmen nt Plantt Part P 1 - Extend ded Aeration ((150 - 5000 5 PE E) Sewera age Regula atory Depa artment SPAN TS 1402:2016 CONTENTS Page 1.0 Scope ....................................................................................................... 8 2.0 Normative Reference ............................................................................. 8 3.0 Terms and Definitions .............................................................................. 8 3.1 biochemical oxygen demand, BOD .................................................... 8 3.2 chemical oxygen demand, COD......................................................... 8 3.3 design capacity ...................................................................................... 8 3.4 effluent ..................................................................................................... 8 3.5 equipment ............................................................................................... 9 3.6 population equivalent (PE) .................................................................... 9 3.7 performance requirements ................................................................... 9 3.8 regulatory authority ................................................................................ 9 3.9 scum ......................................................................................................... 9 3.10 sewage..................................................................................................... 9 4.0 Sewage Treatment Plant (STP) Drawings ........................................... 10 4.1 General Requirements ......................................................................... 10 4.2 Layout ..................................................................................................... 10 5.0 Civil and Structural (C&S) Requirements ........................................... 11 5.1 Reference Standards ........................................................................... 11 5.2 Soil and Hydraulics ................................................................................ 12 5.3 Concrete................................................................................................ 13 5.4 Reinforcement....................................................................................... 14 5.5 Coating for Steel ................................................................................... 14 5.6 Water Supply ......................................................................................... 15 5.7 Roads and Access ................................................................................ 16 5.8 Perimeter Drain...................................................................................... 16 1 SPAN TS 1402:2016 5.9 Effluent Discharge ................................................................................. 17 5.10 Fibre Reinforced Plastic (FRP) .............................................................. 17 5.11 Aluminium .............................................................................................. 19 5.12 High Density Polyethylene (HDPE) ...................................................... 19 5.13 Marine Corrosive Environment ............................................................ 19 6.0 Mechanical and Electrical Requirements ......................................... 20 6.1 Mechanical Design Consideration ..................................................... 20 6.2 Mechanical Installation Considerations............................................. 20 6.3 Noise ....................................................................................................... 22 6.4 Odour Control ....................................................................................... 22 6.5 Motors, Controllers and Motor Starters ............................................... 23 6.5.1 Motors .......................................................................................... 23 6.5.2 Controllers ................................................................................... 23 6.5.3 Motor Starters.............................................................................. 23 6.6 Power Supply Systems .......................................................................... 23 6.7 Switchgear and Control Gear Assemblies......................................... 24 6.8 Control Room and Cabinets ............................................................... 25 6.9 Control Requirements........................................................................... 26 6.9.1 Manual Control .......................................................................... 26 6.9.2 Drive Systems .............................................................................. 26 6.10 Early Warning System (EWS)................................................................. 26 6.11 Instrumentation ..................................................................................... 26 6.12 Cables and Cabling Installation ......................................................... 27 6.12.1 General ....................................................................................... 27 6.12.2 Instrumentation .......................................................................... 27 6.12.3 Buried Cables ............................................................................. 27 6.12.4 Underground Ducts ................................................................... 27 2 SPAN TS 1402:2016 6.12.5 Conduits ...................................................................................... 28 6.12.6 Cable Support Systems ............................................................. 28 6.13 Earthing and Lightning Protection ...................................................... 28 6.13.1 General Purpose Power ............................................................ 29 6.13.2 Manuals and Labelling .............................................................. 29 7.0 Process Design Requirements ............................................................. 30 7.1 Design Influent and Effluent Values .................................................... 30 7.2 Inlet Chamber ....................................................................................... 31 7.3 Primary Screens ..................................................................................... 31 7.4 Pump Stations ........................................................................................ 32 7.5 Secondary Screen Chamber .............................................................. 33 7.6 Grit and Grease Chamber .................................................................. 33 7.7 Anoxic Tank ........................................................................................... 34 7.8 Aeration Tank ........................................................................................ 35 7.9 Blower Room.......................................................................................... 36 7.10 Secondary Clarifier ............................................................................... 37 7.10.1 General ....................................................................................... 37 The design requirements shall include: .............................................. 37 7.10.2 Weirs............................................................................................. 37 7.10.3 Square Clarifiers.......................................................................... 38 7.11 Disinfection Tank ................................................................................... 38 7.11.1 Disinfection with Hypochlorite .................................................. 39 7.12 Flow measurement ............................................................................... 40 7.13 Sludge Holding Tank ............................................................................. 40 7.14 Sludge Drying Bed (If Applicable) ...................................................... 41 7.15 Sludge Storage Hut (If applicable) ..................................................... 42 7.16 Control Room ........................................................................................ 42 3 SPAN TS 1402:2016 7.17 Ancillary Requirement .......................................................................... 43 7.18 Yard Lighting .......................................................................................... 44 7.19 Handrail, Safety Chain, Staircase, Grating and Chequered Plate 45 7.20 Toilet........................................................................................................ 46 7.21 Lifting Facility ......................................................................................... 46 7.22 Ventilation .............................................................................................. 47 7.23 Painting for Pipe Works ......................................................................... 49 7.24 Plumbing Works ..................................................................................... 49 7.25 General Mechanical and Electrical ................................................... 50 8.0 Reporting Format .................................................................................. 52 9.0 Construction and Installation .............................................................. 52 10.0 9.1 General .................................................................................................. 52 9.2 Quality control ....................................................................................... 52 9.3 Health and safety requirements ......................................................... 52 9.4 Inspection .............................................................................................. 54 Testing and Commissioning ................................................................. 54 4 SPAN TS 1402:2016 TABLES Table 1 Range of PE .............................................................................................................. 10 Table 2 Design Influent Values ............................................................................................. 30 Table 3 Design Effluent Values ............................................................................................. 30 Table 4 Inlet Chamber Requirements ................................................................................. 31 Table 5 Primary Screen Requirements ................................................................................ 31 Table 6 Pump Station Requirements ................................................................................... 32 Table 7 Secondary Screen Chamber Requirements ........................................................ 33 Table 8 Grit Chamber Requirements .................................................................................. 33 Table 9 Grease Chamber Requirements ........................................................................... 34 Table 10 Grit and Grease Sand Bed Requirements .......................................................... 34 Table 11 Anoxic Tank Requirements ................................................................................... 34 Table 12 Aeration Tank Requirements ................................................................................ 35 Table 13 Blower Room Requirements ................................................................................. 36 Table 14 Secondary Clarifier Requirements ....................................................................... 38 Table 15 Chlorination Chamber Requirements ................................................................. 39 Table 16 Flow Measurement Requirements ....................................................................... 40 Table 17 Sludge Holding Tank Requirements..................................................................... 40 Table 18 Sludge Drying Bed Requirements ........................................................................ 41 Table 19 Sludge Storage Hut Requirements ...................................................................... 42 Table 20 Control Room Requirements ................................................................................ 42 Table 21 Anti-Climb, Brick Wall Fencing Requirements .................................................... 43 Table 22 Sliding Gate Requirements ................................................................................... 43 Table 23 Yard Lighting Requirements ................................................................................. 44 5 SPAN TS 1402:2016 Table 24 Handrail, Staircase, Grating and Chequered Plate Requirements ................ 45 Table 25 Toilet Requirements ............................................................................................... 46 Table 26 Lifting Requirements .............................................................................................. 46 Table 27 Common Ventilation Rates .................................................................................. 48 Table 28 Plumbing Work Requirements .............................................................................. 50 Table 29 Bolt and Nut Requirements .................................................................................. 50 Table 30 Piping Works Requirements .................................................................................. 50 Table 31 Emergency Shutoff Switch, Junction Box & Electrical Services Requirements .................................................................................................................................................. 51 6 SPAN TS 1402:2016 ANNEXES ANNEX A: REFERENCES .......................................................................................................... 55 ANNEX B: STANDARD STP DRAWINGS ................................................................................. 62 ANNEX C: INSPECTION GUIDE & TYPICAL LIST OF DEFECTS............................................... 67 ANNEX D: MASS BALANCE AND HYDRAULIC PROFILE ...................................................... 89 ANNEX E: PROCESS DESIGN CALCULATION ......................................................................... 1 7 SPAN TS 1402:2016 1.0 Scope The Technical Specification of Sewage Treatment Systems: Standard Sewage Treatment Plant, Part 1 - Extended Aeration (150 PE - 5000 PE) covers the following requirements: a) Section 1: Layout and Design b) Section 2: Construction and Installation c) Section 3: Testing and Commissioning 2.0 Normative Reference The documents and publications that are requisite for application of this specification are listed in ANNEX A. For undated references, only the edition cited and the latest edition of the referenced document (including any amendments) applies. 3.0 Terms and Definitions For the purpose of this specification, the following terms and definitions apply: 3.1 biochemical oxygen demand, BOD The concentration of dissolved oxygen consumed under specified conditions (5 days at 20°C with or without nitrification inhibition) by the biological oxidation of organic and/or inorganic matter in water 3.2 chemical oxygen demand, COD The concentration of oxygen equivalent to the amount of dichromate consumed when a water sample is treated with that oxidant under defined conditions 3.3 design capacity Maximum flows and loads of the sewage the facilities are designed for, which conform to the specified consent effluent standard 3.4 effluent The liquid discharged from a sewage treatment process 8 SPAN TS 1402:2016 3.5 equipment Any component which is installed in, mounted on, attached to, or operated on structures in the performance of their intended function 3.6 population equivalent (PE) The equivalent, in terms of fixed population of a varying or transient population or other activity (e.g. industrial, commercial contributing flow to the sewerage system) 3.7 performance requirements The functions that a system has to perform in order to operate as required 3.8 regulatory authority The authority which is empowered by statute to be responsible for regulating sewerage industry 3.9 scum The floating mass of sewage solids buoyed up by entrained gas, grease or other substances which form an accumulating layer on the liquid surface inside the tank. 3.10 sewage Any liquid discharges containing human excreta, animal or vegetable matters in suspensions or solution derived from domestic activities and being generated from household, commercial, institutional and industrial premises including liquid discharges from water closets, basins, sinks, bathrooms and other sanitary appliances but excluding rain water and prohibited effluent. 9 SPAN TS 1402:2016 4.0 Sewage Treatment Plant (STP) Drawings 4.1 a) General Requirements This technical specification shall be read in conjunction with the typical drawings in Annex B; b) All dimensions shown in the drawings are in millimeters (minimum) unless otherwise stated and shall be checked on site before commencement of works; c) The drawings are scaled to suit A3 paper size; d) The drawing code is to be read as follows: AAA/BBB/CCC/1234 whereby; Example: SPAN TS 1402/Type A/LP/01 AAA - Technical Specification Title BBB - PE Range CCC - Drawing Title 1234 4.2 - Drawing No. Layout The typical layout of the system shall be in accordance with drawings as stipulated in Annex B that varies in PE ranges as listed below; Table 1 Range of PE PE range Drawing No. 150 ≤ PE ≤1000 SPAN TS 1402/Type A/LP/01 1000 < PE ≤ 3000 SPAN TS 1402/Type B/LP/01 3000 < PE ≤ 5000 SPAN TS 1402/Type C/LP/01 10 SPAN TS 1402:2016 5.0 Civil and Structural (C&S) Requirements 5.1 Reference Standards All elements are to be designed to the Competent Person’s requirements complying with the specified standards, other appropriate standards and current standards. The references are as listed below:a) Structural elements - BS EN 1990+A1, BS EN 1992+A1, BS EN 1992-3, MS 1195 Part 2; b) Composition, specifications and conformity criteria for common cement - BS EN 197-1 c) Cement to be used to resist sulphate attack - MS 1037, BS EN 15743+A1; d) Pulverized-fuel ash - MS 1226: Part 1; e) Ground granulated blast furnace slag - MS EN 15167 Part 1 and 2; f) Aggregates - MS EN 12620; g) Steel: i) Steel reinforcement - BS 4449+A2; ii) Cold reduced mild steel wire and steel fabric - MS 144, MS 145; iii) Hot rolled steel bars and sections - MS 146, EN 10210; iv) Welding of steel reinforcement - BS EN ISO 17660-1, BS EN ISO 17660-2; v) Structural steel sections - BS 4-1; vi) Cold rolled steel sections - EN 10162; vii) Weldable structural steel and minor structural steelwork - EN 10025; viii) Steel tube- EN 10296, EN 10297, EN 10305; ix) Structural steel in building and all other steelwork - MS 415; h) Admixtures - MS 822, MS EN 934, BS EN 934-2; i) Waterstops for sealing joints in concrete - MS 1292; j) Ultra high-build paint- AS/NZS 3750.2; k) Alkyd/micaceous iron oxide- AS/NZS 3750.12; l) Hot dip galvanized coating - MS 740; m) Sealed sprayed zinc coating - EN ISO 2063; n) Other coatings - Table 3 Part 8 of BS 5493; o) Steel substrates - BS 7079; p) Other corrosion protection coating for steelwork - BS 5493 or AS/NZS 2312.1; q) Nuts, bolts, screws and washers in contact with sewage shall be stainless steel of Grade 316S31 steel in accordance with BS EN 10088 Part 1and 3 or EN 10029 and EN ISO 9445; 11 SPAN TS 1402:2016 r) Bolts, nuts, screws, fasteners and washers other than stainless steel shall conform to MS 739 and BS 4921; s) FRP: i) All other FRP products - ASTM C582 for FRP laminates; ii) Fire rating - ASTM E84, BS 476; iii) Unsaturated polyester resins - Type B or C of BS 3532; iv) E glass and E-CR glass -BS EN 14118 Part 1, 2 and 3, BS 3396-1, BS 3749; v) Textile glass rovings - EN 14020; vi) FRP water tanks - MS 1241 where not constructed of FRP panels, MS 1390 where constructed of FRP panels; t) Anodic oxidation coating on aluminium-BS EN ISO 3210; u) Structural design, materials, workmanship and protection of aluminium BS EN 1999-1-4+A1; BS EN 1999-1-3+A1; BS EN 1999-1-1+A2; v) w) Wrought aluminium and aluminium alloys: i) BS 1161 for structural purposes; ii) BS EN 485 for sheet,strip and plate; iii) BS EN 754 for drawn tube; iv) BS EN 755 for extruded rod/bar, tube and profiles; v) BS EN 1676 for ingots and castings; vi) BS 4868 for profiled sheet; Marine corrosive environment: i) Concrete resistant to all chemical attacks - BS EN 1990; ii) Structural steelwork shall be thoroughly descaled to second quality - BS 7079. 5.2 Soil and Hydraulics a) Soil bearing capacity to be taken as minimum 100kN/m2; b) Soil bearing pressure for brickwork fencing is to be taken as more than 50kN/m2. c) Soil investigation is required to determine soil condition and requirement of piling; d) All sub-grade compaction shall be determined by geotechnical results; e) Hydraulically shall be 50mm drop from component to component; f) Actual levels shall be determined from hydraulic calculation of actual plant design and actual site survey; g) Minimum openings are as stated in the drawings but should be designed according to hydraulic needs; 12 SPAN TS 1402:2016 h) Freeboard shall be 500mm for process tank; i) The emergency overflow pipe shall be located at inlet chamber whereby the level shall be lower than the lowest manhole ground level; j) Competent Person is allowed to propose overflow pipe at lowest cast manhole ground level which shall not create public nuisance; k) Flap gate shall be provided to avoid back flow from the river/ main drain; l) Plant hydraulic must be designed properly to ensure the discharge head is adequate to open the flap valve at any circumstances. 5.3 Concrete a) Unless otherwise stated, the design working life of all concrete structures shall be 50 years; b) Concrete for structures retaining sewage shall be designed for buoyancy due to ground condition; c) Concrete for structures retaining sewage shall be of grade 35A; d) Concrete for all other structures (except for fencing) shall be of grade 35; e) Concrete for fencing shall be of grade 25/20; f) Mass concrete for benching shall be of grade 35A; g) Mass concrete and lean concrete for fencing shall be of grade C20; h) Concrete structures retaining sewage shall be lined with high alumina cement mortar of 20mm thickness; i) All concrete shall be sufficiently vibrated; j) Concrete and cement mortar exposed to soils or groundwater, cement suitably resistant to sulphate attack shall be used for the entire structure; k) Cement to be used to resist sulphate attack shall be: l) Sulphate-resisting Portland cement; m) Portland pulverized fuel ash cement; n) Ground granulated blast furnace slag; o) High silica content Portland cement; p) Super sulphated cement; q) Approval for admixtures shall be obtained prior to inclusion in the concrete mix; r) All bottom of tank shall be chamfered to avoid dead zones. s) The water used for mixing and curing shall be fresh, clean and not contain any organic matter, sulphate or other impurities in sufficient quantities to reduce the strength of the concrete or attack the concrete of the reinforcement; t) The building area / compound shall be of mass concrete; 13 SPAN TS 1402:2016 5.4 Reinforcement a) Minor structural steelwork shall be Grade 43A; b) Stirrups / links shall be of mild steel; c) Bar lap length shall be of 50 times the diameter of bar; d) Open type flooring: i) where cut outs are required in flooring around pipework or other obstruction, a continuous nosing bar shall be fully welded to all bearing bars around the cut out; ii) maximum weight is 40kg; iii) superimposed loading is 5kN/m2; iv) deflection shall not exceed span/200 or 10mm whichever is lesser when fully loaded; v) clearance around the obstruction shall not exceed 30mm. 5.5 Coating for Steel a) Steelwork that may be in contact with sewage through immersion, splash or spray, or that is over tanks containing sewage, shall be protected against corrosion using one of the following coating systems: i) high build tar epoxy system shall be applied in two or more coats to give a total dry film thickness of not less than 200µm; ii) high build micaceous iron oxide pigmented epoxy system shall be applied in two or more coats to give a total dry film thickness of not less 200µm; b) iii) hot dip galvanized coating of 140µm nominal thickness; iv) sealed sprayed zinc coating of 150µm nominal thickness; Other coatings providing 10 to 20 years’ service, before first maintenance shall be considered for approval by the Commission; c) Steelwork that is exposed to the external atmosphere, except severe marine atmospheres, shall be protected against corrosion using one of the following coating systems; d) Steelwork that is exposed to the external atmosphere, except severe marine atmospheres, shall be protected against corrosion using one of the following coating systems: i) a prime coat of a two pack polyamide cured epoxy zinc phosphate of dry film thickness 60 to 80µm with a finishing coat of a high build 14 SPAN TS 1402:2016 micaceous iron oxide chlorinated rubber paint, spray applied to a dry film thickness of 60 to no more than 80µm; ii) hot dip galvanized coating of 85µm nominal thickness; iii) sealed sprayed zinc coating of 150µm nominal thickness; e) Steel substrates shall be prepared before application of coatings; f) Other corrosion protection coating systems for steelwork (for tropical atmospheres), provide 20 or more years to first maintenance; g) Unprotected steelwork in contact with sewage shall be stainless steel grade 316L; h) Successive coatings of the one component shall be tinted a different colour to facilitate over coating and inspection; i) All coatings shall be applied strictly in accordance with the coating manufacturer’s printed instructions; j) Bolts, nuts, screws and other fasteners shall have either hot dip galvanized, sherardized zinc or electro plating coating; k) Washers and other small components shall have either hot dip galvanized, or sherardized zinc coating; l) Fasteners of incompatible material to the component being fastened shall have suitable isolating washers and sleeves. 5.6 Water Supply a) Water shall be connected to potable supply that provides a minimum pressure of 20m head across the site; b) Water tank of at least 445 liter storage capacities or one day water usage or whichever is higher shall be provided; c) Double backflow prevention shall be provided in all cases to prevent contamination of any potable water service, including the incoming supply line; d) The water supply system shall be sized to meet the following cases: i) firefighting demand as instructed by the local regulations and any essential plant water demands; ii) all potentially simultaneous process uses, equipment uses and a for plant cleansing; e) All water supplies and its installation (piping, tanks, air conditioning drainpipes, gutters and etc.) must be totally isolated from all potential contact of electrical system; 15 SPAN TS 1402:2016 f) Where required, wash water shall be equipped with booster pump and where possible, obtain from reclaimed water. 5.7 Roads and Access a) Earth formation to be compacted or reinforced concrete road and withstand a load of at least 15 tonnes; b) Construction shall comply with Public Works Department requirements; c) On-site road shall be able to provide safe and convenient access for trucks or other machinery equipment used for maintenance purposes; d) Minimum width of the road shall be 4m; e) Where vehicles need to pass frequently or parking is required along the road, the minimum width shall be 6m; f) Corner of junction for perimeter internal road for tankers or trucks access shall have a minimum inside radius of 6m; g) Inside radius for perimeter road not intended for tankers or trucks access shall be not less than 4m; h) Where roads for maintenance vehicles or machineries are not required, concrete or hard surfaced walkways of at least 900mm width shall be provided between each process unit; i) Concrete hardstanding area can be laid where storage bins are located; j) The use of steps shall be avoided, where possible; k) Where the ingress or egress of the treatment plant is near a junction of a public road, an adequate acceleration and deceleration lane must be made available between the access road and the junction for vehicles to safely enter and leave the treatment plant; l) Slope area within the treatment plant reserve shall be premixed. 5.8 Perimeter Drain a) Drainage shall conform to local authority standard requirements and shall be of 225mm half round salt glaze ware drain (HRSGW); b) Velocity shall be on range of 0.8 m/s to 4.0 m/s; c) Reinforced concrete cover shall be provided for drain depth >1000mm; d) Drainage sump of 300mm x 300mm to be provided when there is a change of flow direction; e) Heavy duty mild steel grating shall be used for drainage sump; 16 SPAN TS 1402:2016 f) Any cleaning or maintenance process wash water must be returned to the inlet works via a separate drainage system; g) External drainage facilities must be provided for treatment plant along the slope area; h) Cut off drainage at the entrance must also be provided; i) Drainage routing shall be adjusted to suit the site condition; j) Location of perimeter drainage discharge shall be determined by on site condition. 5.9 Effluent Discharge a) Flap gate shall be provided to avoid back flow from the river/ main drain; b) Plant hydraulic must be designed properly to ensure the discharge head is adequate to open the flap valve at any circumstances; c) Effluent discharge shall be directed to the main drain or river to avoid discharging effluent into a drain within the residential area; d) Discharge to a retention pond is not allowed unless prior approval has been granted; e) The receiving drain/watercourse shall have sufficient capacity to accept the run-off from the plant as well as the effluent discharge from the treatment plant. 5.10 Fibre Reinforced Plastic (FRP) Only FRP products approved by the Commission shall be used and FRP products shall not be used for access purposes. The thickness of the structural section of the FRP wall shall not be less than 10mm. Notwithstanding any other requirements in standards, all FRP products, including FRP tanks and vessels for sewage treatment processes, shall conform to the following material requirements: a) FRP properties shall be as determined by design but shall not be less than the following values: i) Tensile strength - 80 MPa ii) Tensile modulus - 7000 MPa iii) Flexural strength - 140 MPa iv) Flexural modulus - 6000 MPa v) Water absorption-≤ 0.75 % vi) Barcol hardness - 40 vii) Operating temperature is -40°C to +50°C 17 SPAN TS 1402:2016 viii) ix) b) Specific gravity - ≥ 1.5 Fire rating - < 25s or Class 1 Unsaturated polyester resins shall be used but shall only be isophthallic, bisphenol A fumurate or terephthalic polyester resins; c) All surfaces shall have a resin rich layer, gel coat; d) Surfaces in contact with sewage, water or any moisture shall comprise of a resin rich layer at least 1 mm thick; e) All other surfaces shall comprise of a resin rich layer at least 0.25 mm thick up to 10% by mass of corrosion resistant glass fibres, (that is, C-glass or E-CR glass), polyester fibres or acrylic fibres may be used in the surface layer; f) A barrier layer shall be provided behind the surface layer and shall be at least 1.5 mm thick; g) The barrier layer shall comprise of 70to 80% by weight resin with the remainder by weight being E glass or E-CR glass; h) The structural layer shall comprise resin impregnated layers of E glass or E-CR glass and shall comprise at least 25 % E glassor E-CR glass. Aggregate and filler may be included; i) E glass and E-CR glass shall be of glass rovings, chopped strand mat woven fabric or woven roving fabric; j) Glass fibres shall have a surface treatment compatible with the manufacturing process to ensure bonding to the resin; k) Aggregates shall only be used in FRP structural layers and external layers. Aggregates shall be clean, washed, high grade silica sand containing not less than 95% silica; l) Aggregates shall be of a size not greater than 20% of the thickness of the FRP structural layer with a particle size not less than 0.05 mm and not greater than 5mm; m) Fillers shall only be used as a resin extender and shall comprise of clean inert material, for example, silica, with particle size less than 0.05 mm; n) Surfaces exposed to sunlight shall incorporate provisions to minimize ultraviolet degradation, such as, ultraviolet inhibitors, screening agents or pigment in the outer resin rich layer; o) Pigments and dyes shall not normally be required, but where required by the Commission, shall be of a type and colour specified by the Commission. 18 SPAN TS 1402:2016 5.11 Aluminium a) Aluminium is found primarily as the ore bauxite and is remarkable for its resistance to corrosion (due to the phenomenon of passivation) and its light weight; b) Structural components made from aluminium and its alloys are very important in which light weight, durability, and strength are needed. 5.12 High Density Polyethylene (HDPE) a) High density polyethylene (HDPE) is the high density version of PE plastic; b) Its molecules have an extremely long carbon backbone with no side groups; c) As a result, these molecules align into more compact arrangements, accounting for the higher density of HDPE; d) HDPE is stiffer, stronger, and less translucent than low-density polyethylene; e) HDPE is lighter than water, and can be moulded, machined and joined together using welding; f) High density polyethylene shall comply to the following physical properties: i) Tensile Strength0.20 - 0.40 n/mm2; ii) Notched Impact Strength no break kJ/m2; iii) Thermal Coefficient of expansion100 - 220 x 10-6; iv) Max Cont use Temp650°C; v) Density0.944 - 0.965g/cm3; vi) Minimum required strength 8.0 MPa. 5.13 Marine Corrosive Environment a) All areas within 5 km from the coast line or salt water bodies shall be classified as marine environment; b) Sewerage facilities in marine and corrosive environment e.g. where the atmosphere or soil contains high levels of chloride, sulphates and corrosive chemical elements or compounds shall be adequately designed to withstand the corrosive actions of the chemicals prevalent in the environment; c) Necessary protections shall be provided against all corrosive actions of the environment; d) Design requirement for facilities in marine and corrosive environment shall include two coats of sodium silicate that shall be applied to all external surfaces of concrete structures; e) Exposed metal shall be of corrosion resistant and of marine grade; 19 SPAN TS 1402:2016 f) Proper smooth surface finishing shall be provided for the metal; g) Unprotected metals acceptable for SS316L, aluminium alloy or materials suitable for use in corrosive environment acceptable by the Commission; h) All structural steelwork shall be painted with 2 coats of two pack epoxy based red lead primer before leaving the manufacturer ’s works; i) In addition, all structural steelwork shall be provided with protective paint for chloride, sulphate or the prevailing chemicals in the site after installation; j) Cathodic protection shall be provided for all load bearing steel structures in marine environment for a minimum life of 50 years. 6.0 Mechanical and Electrical Requirements 6.1 Mechanical Design Consideration a) The design shall simplify the equipment required, control system, maintenance and operational procedures, while fulfilling the intended performance and standard of service; b) The brand and models of major drive equipment (e.g.: pumps, blowers, aerators, clarifier scrappers, etc.) shall be those approved by the Commission; c) The types and makes of equipment provided throughout the facility shall be standardized, whenever possible; d) Only new and genuine equipment shall be provided; e) Equipment sizing and selection shall minimize energy and other consumables / costs; f) The minimum economic life of equipment; g) Material selection shall be in accordance with the Commission specifications or/and other relevant international standards; h) Components shall be robust and suitable for use. Where thin metal sheeting is used, it shall be stiffened to minimize distortion; i) Water storage tanks shall not be placed on the roof top of any control room; all water supply system shall be homed with separate entrance. 6.2 Mechanical Installation Considerations a) The base frame of rotational equipment or any equipment that may induce vibration shall be provided with anti-vibration mount; b) All revolving parts shall be properly balanced both statically and dynamically so that there shall be no undue vibration anywhere in the machine or transmitted to the adjacent structure; 20 SPAN TS 1402:2016 c) The criteria adopted for vibration severity shall be the RMS value of the vibration velocity in millimeters per second; d) Where rotational equipment or equipment which may induce vibration is connected to piping, then vibration isolator shall be provided; e) All moving parts shall be designed and installed in a manner that is inherently safe to operate; f) Foundations shall be adequately designed to include all dynamic load and anchored to withstand all loads imposed by the equipment; g) Equipment shall be accurately located, levelled and secured by holding down bolts; h) Non-shrink grout shall then be used to complete the foundation. In some cases, a resilient connection to the foundation is required, in which case, the manufacturer’s instructions shall be followed; i) Puddle collar is required for all pipe passing through all walls; j) Appropriate joints shall be provided in all pipe works to facilitate the removal of equipment, meters, valves and other special items without dismantling the entire pipeline; k) Valves shall be provided for isolation purpose; l) Outdoor and dry installation pump shall be provided with housing; m) Competent Person must ensure that the unit processes are arranged in such a way to prevent/reduce criss-crossing of piping works, unnecessary bends, choking of interconnected pipe and excessive hydraulic losses through the system; n) The platform level of mechanical equipment and electrical control system of any process unit shall be located above design flood level; o) Silencers and acoustic enclosures shall be provided as required to achieve noise level reduction; p) Enclosures used to achieve these noise reductions shall permit ready access to the equipment for routine maintenance; q) Adequate air ventilation shall be provided to allow cooling of the enclosure to prevent overheating of the equipment/motors; r) The fixing and co-ordination by exact position of service to and from sanitary fitting shall be the responsibility of contractor. 21 SPAN TS 1402:2016 6.3 Noise a) Noise level measurement in dB (A) shall be made with a sound level meter which complies with BS EN 61672 Part 1, 2 and 3; b) Noise level for all electronically operated electrical device such as soft starters, variable speed drives and others shall conform to IEC and EN. Thus it shall fulfill all EMC Immunity requirements complying with BS EN 61000-6 Part 1 and 2; c) Noise level generated shall comply with the requirements stipulated in Factories and Machinery (Noise Exposure) Regulations 1989, The Planning Guidelines for Environmental Noise Limits and Control by Department of Environment. 6.4 Odour Control Odour control requirements shall be applied upon condition set during planning stage as follow: a) Isolate odorous gases from general ventilation by containing identified odour generating sources with a separate local exhaust system; b) Containment of the odour sources shall be by installing lightweight and corrosion resistant covers/enclosures designed for practical operation and maintenance works; c) Local exhaust rates for containment shall be designed to provide a negative pressure preventing buildup of toxic, corrosive or explosive gases and to include provision for process air or air displaced by changes in the level of liquid inside the covered space; d) The odorous air in the local exhaust system shall be conveyed through well designed and balanced ductworks by a centrifugal fan to an effective odour treatment system; e) Odour treatment equipment shall be selected such that odour is reduced to the lowest possible level and in compliance to the EQA; f) In situation where specific gases such as hydrogen sulphide and ammonia are significantly present, provide a pre-scrubber unit upstream of the main odour treatment equipment; g) Containment, exhaust and treatment shall be designed as an integrated package; h) Consideration must be given to the life span of the odour control system and associated costs in operating and maintaining such a system. 22 SPAN TS 1402:2016 6.5 Motors, Controllers and Motor Starters 6.5.1 Motors a) Provide readily replaceable anti-condensation heaters for motors that do not require frequent operation. b) At least three thermistors to be provided for motors which are >50 kW. c) Electrical motors should be rated as continuous run. d) Motors > 22kW shall be protected with soft starter or variable speed drive. e) Where water hammer prevails, frequency inverter shall be provided. f) The appropriate cooling system based on the requirements of the equipment shall be provided. 6.5.2 Controllers a) Start push buttons to be green and recessed b) Stop push buttons to be red and recessed c) Emergency stop push button to be red and mushroom head type d) ON signal lamps to be green e) OFF signal lamps to be red f) Trip signal lamps to be amber 6.5.3 Motor Starters a) Up to 3.7 kW - Direct-On-Line starters b) Above 3.7 and up to 7.5 kW - Star/Delta starters c) Above 7.5 and up to 22 kW - Auto-transformer starters d) More than 22 kW - Soft starter e) Above 50 kW - Variable speed drive is preferred Soft starting of motors above 30kW or greater in size is necessary to minimize power disturbances (e.g. power surge) and process disturbances (e.g. water hammer). Variable speed drive shall be considered at application where variable capacity maybe need to enhance the process flexibility, for example, aeration device and blowers. 6.6 Power Supply Systems a) All matters relating to electricity shall comply with Energy Commission Law and any other subsidiary regulations; 23 SPAN TS 1402:2016 b) The power supply provided shall be single incomer with properly design control overflow system during power failure (all electrical control system shall be located above design flood level); c) No direct tapping of power is allowed from distribution board (DB). Proper protection shall be provided for any direct connection from switchboard; d) Earth leakage current breaker (ELCB) shall be provided for DB; e) The power system distribution shall be designed to achieve a minimum power factor of 0.9; f) For phase development, the plant and power system distribution shall be designed for maximum load and installed in appropriate modular unit to ensure that the minimum power factor is achievable at all phases of operation; g) Equipment shall be protected by either moulded case circuit breaker (MCCB) or miniature circuit breaker (MCB) based on its suitability; h) Every control circuit shall be protected with separate MCB; i) TNB meter panels shall be installed close to the site entrance or adjacent to but physically separated from the main switchboard; j) Suitable flexible steel conduit with approved adaptors shall be supplied and fitted between the main switchboards; k) All metering panel shall be located flush with the fence and door opening from outside to enable TNB inspector to read the kWh and kVAhr reading; l) Provide earthing connected with Current Transformer (CT) for Large Power Consumer (LPC) (i.e. consumption with more than 100A or 10kW); m) To provide earthing connected to ELCB/RCCB/ELR or Over Current & Earth Fault relay to protect overcurrent and surge current to all wiring connected to TNB metering panel for Large Power Customer (LPC) or Ordinary Power Customer (OPC); 6.7 Switchgear and Control Gear Assemblies a) Supply Authority Metering separated from the main switchboard; b) Electro galvanized plates to be used to protect materials against corrosion due to high humidity; c) Panel isolators and door locks to be capable of padlocking open with 6 mm hasp padlock; d) Separate panel boards to be used for general purpose light and power; e) All motor starting equipment for an area to be grouped into multi-motor, starter control board; 24 SPAN TS 1402:2016 f) Cabinets are to be constructed to prevent the ingress of insects and vermin; g) For all incomer above 400A, over current and earth fault protection to be provided on all starter circuits in excess of 200A; h) Where a circuit has a main and standby supply, an isolator in each supply circuit to be provided; i) Junction boxes for submersible pumps and float controls shall be above the floor or any possibility of flood level and must not be located in the wet well. 6.8 Control Room and Cabinets a) Provide 900mm minimum clearance between an open door and any fixed object; b) Provide 900mm clearance between open cabinet doors of facing cabinets; c) Front access cubicles to have the electrical clearance distances between doors mounted equipment and gear tray mounted equipment as specified in the regulations; d) Main supply bus bars shall extend the full length of panels, and the panel casings shall be effectively earthed; e) Mount all equipment inside cabinets on gear trays; f) All control panels shall be provided with phase sequence relay; g) All cabinets to have a base frame, at least 50mm high; h) All control rooms shall be isolated from invasive environment of the sewerage system, where carbonization, corrosion or condensation may occurs that lead to short-circuiting; i) Height to be no greater than 1600mm internally; j) Mount cabinet on reinforced concrete plinth, 200mm minimum above floor; k) Provide reinforced concrete paved area for the full width of the cabinet and extending 1m in front of the cabinet doors, when they are opened; l) Natural ventilation is suitable for direct-on-line, star-delta and auto transformer starters; m) The minimum acceptable IP rating and tests required shall be clearly specified; n) Cable entry from the bottom only. 25 SPAN TS 1402:2016 6.9 Control Requirements 6.9.1 Manual Control a) Interlocks shall be provided to prevent damage to the equipment during equipment start up, for example, bearing overload, overheated, temperature, loss of cooling water, no flow when operating; b) Selector switches to be provided at one location so that equipment can be manually operated from that location. 6.9.2 Drive Systems a) Each drive must be independently provided with the following features: i) ON-starts and runs drive; ii) OFF-stops drive; iii) AUTO-operates the drive in accordance with automatic control system; b) Indicate operation by an ammeter; c) Record running hours with local indicator; d) Local annunciation on motor starter of each fault condition; e) Record kilo-Watt-hour (kWh) of major drive equipment. 6.10 Early Warning System (EWS) a) For sewage treatment plants designed to comply with Standard A/B effluent discharge and located upstream of the water intake point, EWS shall be provided and comes with computer (monitoring) or data logger; b) The EWS is used to monitor raw sewage pumps and blowers trip signals, high water level, incoming power supply failure and RTUs health status; c) EWS system shall be able to transmit digital and analog values via Short Messaging Service (SMS), e-mail or via other telecommunication mean in text mode to technical staff for the fast recovery of the treatment system; d) The modules shall be able to interpret SMS message from the operator to activate or deactivate long distance machine (remote control); e) For public system, the EWS shall be integrated into a centralized monitoring system. 6.11 Instrumentation Provision for instrumentation shall be as follows: a) Inlet Pump Station - Level; b) Blower - Pressure; 26 SPAN TS 1402:2016 c) Effluent - Flow Measurement; d) Electrical Drive - Amp/Volt/HR/kW/Power Factor meter; e) Disinfection - Outlet water level indicator; Instruments shall be installed in such a way that they can be removed for maintenance without interrupting the process. 6.12 Cables and Cabling Installation 6.12.1 General a) b) Segregate cables into the following categories: i) Power (less than 1000 V phase to phase); ii) Instrumentation / telemetry; iii) Control; Wherever possible, use a separate cable-support system for each cable category; c) Separate such cable support systems by minimum clear distances of 300mm; d) When one cable support system has to be used, separate cable categories by minimum clear distances of 150mm; e) Secure cable at 900mm intervals for horizontal runs and 300mm for vertical runs; f) Cable ties shall be made of non-corrosive material and if exposed to the environment, shall have UV protection; g) All cables shall be at least of double PVC protection, and if exposed to the environment then armoured cable shall be provided. 6.12.2 Instrumentation a) Use separate cables for digital and analog signals; b) Marshal cables in a process or geographical area into junction boxes; c) Use multi-pair cables between areas. 6.12.3 Buried Cables a) Install cables without trees or through joints, unless approved; b) All buried cables shall be laid in ducts. 6.12.4 Underground Ducts a) Construct road crossings from uPVC conduit of minimum 100mm diameter with 900mm cover and encased on all sides with 150mm concrete; 27 SPAN TS 1402:2016 b) All other ducts to be PVC conduit laid with a minimum cover of 600mm. Ducts to be bedded in 75mm sieved sand; c) Provide draw strings in all ducts; d) Provide cable pits to suit cabling layout and to allow drain-in of cables through the duct work; e) Cable pits shall be provided no greater than 100m apart. They shall be fitted with trafficable cast iron covers and equipped with drainage; f) Seal ducts into buildings with approved systems providing a fire rating of 30 minutes. 6.12.5 Conduits a) All cabling within buildings or structures where cable trays are not permitted, and in all external locations, shall be installed within conduits; b) Conduits installed externally shall be arranged to minimize their length and exposure; c) PVC heavy duty conduit is permissible, where it is protected from physical damage and UV, otherwise, metal or flexible conduits shall be used; d) Use flexible steel reinforced conduit for connections, where relative movement and removal for maintenance has to be considered. 6.12.6 Cable Support Systems a) Ensure cable support systems in electrical switch rooms, equipment (for example, pump) rooms and service galleries; b) When run in common service galleries, ensure cables are not adjacent to hot services. 6.13 Earthing and Lightning Protection a) 2W UTX for earthing system / manhole with sufficient diameter size and number of pipe(s) shall be allocated / separated for earthing conductor / tape and electrical cable/wiring services; b) Lightning arrestor material shall be of copper and embedded in the wall; c) Provide earthing and lightning protection to meet local regulations; d) Use a specialist inspector to verify the installation; e) Earthing test results shall be submitted and results shall be below or equal to 1 Ohm; 28 SPAN TS 1402:2016 f) Lightning arrestor test results shall be submitted and results shall not more than 5 Ohms; g) Earthing and lightning arrestor chamber shall be of pre-cast material. 6.13.1 General Purpose Power Provide general purpose power socket outlets as follows: a) Single phase outlet rated at 10A adjacent to, or inside each control cabinet and within 10 in of all equipment installations; b) Three phase outlet rated at 50A within 20 in of every screen, sludge scraper, clarifier rake, grit collector and conveyor; c) Three (3) phase (with neutral) outlet rated at 50 Amp shall be provided at an interval of at least 20 in; d) These outlets shall be water proofed industrial type switch socket outlets (SSO). 6.13.2 Manuals and Labelling These items below shall be prepared and submitted to the plant operator or owner: a) Provide plant function diagrams, electrical system, electrical circuit, Process and Instrumentation Diagram (P&ID), instrument loop diagrams and single line diagrams with endorsement by qualified person, before the plant is precommissioned; b) All plant and equipment are to be provided with inscriptions and labels to facilitate understanding and safe operation and to satisfy the requirements of any standards and regulations applying to the works. Labelling includes: i) Inscriptions on equipment, cubicles, instruments, process controllers and on small equipment such as relays, control switches, indicating lights, etc.; ii) Identification of cables at both ends and along their lengths; iii) Identification of terminations for cable cores and cubicle wiring in accordance with the circuit diagrams. 29 SPAN TS 1402:2016 7.0 Process Design Requirements The detailed process design calculation is as shown in Annex E. The minimum design requirements shall be as stated below. 7.1 Design Influent and Effluent Values Treated sewage effluent requirement is to achieve Environmental Quality (Sewage) Regulations 2009 and any other related subsidiary law prescribed by Department of Environment (DOE). The effluent E.Coli compliance is subject to the sensitivity of the receiving watercourse and as directed by the Department of Environment (DOE). Table 2 Design Influent Values Item 1 2 3 4 5 6 7 Process Biochemical Oxygen Demand (BOD5) Suspended Solids (SS) Chemical Oxygen Demand (COD) Total Nitrogen (TN) Ammoniacal nitrogen (AMN) Total Phosphorus (TP) Oil and Grease (O&G) Value (g/capita.day) 56 68 113 11 7 2 11 Value (mg/l) 250 300 500 50 30 10 50 Table 3 Design Effluent Values Parameter BOD5 SS COD AMN Nitrate Nitrogen Total Phosphoru s O&G Effluent Discharge to Rivers / Stream Effluent Discharge to Stagnant Water Bodies* Standard A Standard A Standard B Standard B Absolute Design Absolute Design Absolute Design Absolute Design 20 50 120 10 10 20 60 5 50 100 200 20 20 40 100 10 20 50 120 5 10 20 60 2 50 100 200 5 20 40 100 2 20 10 50 20 10 5 10 5 N/A N/A N/A N/A 5 2 10 5 5 2 10 5 2 2 10 5 * Stagnant Water Bodies refer to enclosed water bodies such as lakes, ponds and slow moving watercourses where dead zone occur. 30 SPAN TS 1402:2016 7.2 Inlet Chamber Table 4 Inlet Chamber Requirements Item 1 2 3 7.3 Description Penstock (Manual) - Size - Rising stem - Spindle Emergency overflow pipe Fixed Screen Requirement Water tight – 1 no. 225mm min. depending on the sewerline sizing Ductile iron Stainless steel Vitrified clay pipe; Equivalent to incoming sewer pipe Non-corrosive material; Spacing: 50mm clearance Primary Screens Screens must be designed to withstand flushing velocity. In the event of the manual bypass screen being blocked, sewage must be able to flow over the top of the screen without causing excessive backup flooding or overflows. Table 5 Primary Screen Requirements Item 1 2 3 4 5 6 7 8 Process Screen clear spacing Slope Approach velocity at feed channel Flow through velocity at the screen face Approach & flow through velocity at 50% blockage Estimate screenings per volume of sewage Screenings skip storage capacity Overflow opening between channel 9 Coarse screen 10 11 12 13 Opening to pump sump Spotlight Perforated Tray Screening Bin Overflow pipe within chamber Standpipe 14 15 Requirement Max. clearance, 25 mm 30° to vertical or 60° to horizontal Max. 1.0 m/s Max. 1.0 m/s Min. 150mm freeboard shall be provided to prevent the approached channel from overflowing 20m3/106 m3 at average flow 7 days Invert level shall be with 50% blockage and 150mm freeboard Static, Fibre reinforced plastic (FRP); 2 nos. (2 duty); Min. width: 500mm; Spacing: 25mm Min. 300mm x 300mm Adjustable weather proof Fibre reinforced plastic (FRP) High Density Polyethylene (HDPE) Min. 200mm uPVC pipe Located within 3m 31 SPAN TS 1402:2016 Item 17 7.4 Process Requirement Fibre reinforced plastic (FRP) Stop log Pump Stations Table 6 Pump Station Requirements Item 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Description Hydraulic Retention Time at Qavg Pumping Cycle Raw sewage pump Guide rail of RSP Cat ladder Check and gate valve Spot light Force main and filtrate return pipe Staircase Float switch Check valve Slope of benching Internal width of pump sump Difference between pump Stop Level and pump Start Level Difference between pump Low Level Alarm and pump Stop Level Difference between pump Start Level and pump High Level Alarm Requirement Max. of 30min detention at Qavg(min) 6 - 15 (start/hour) 2 nos. (1 duty, 1 standby) Double Stainless Steel, Fixed type Ductile iron Adjustable weather proof Ductile iron Head clearance at least 2.1m Heavy duty non-mercury type Swing check type with anti-slam 60º (surrounding internal of tank) Min. 2m Min. 450mm, Max. 900mm Min. 150mm Min. 150mm Additional criteria for pumps: a) Shall operate within their best efficiency range at normal operating condition; b) Equipped with an auto restart mechanism in the event of power failure; c) Equipped with cutting or macerating facilities are not acceptable. 32 SPAN TS 1402:2016 7.5 Secondary Screen Chamber Table 7 Secondary Screen Chamber Requirements Item 1 2 3 4 5 6 7 8 9 10 7.6 Description Filtrate return pipe Ramp By-pass overflow pipe Fine screen (static) Kerb Screen clear spacing Estimate screenings per volume of sewage Perforated Tray Stop Log Screening Bin Requirement Ductile Iron (Above ground); VCP (Buried) Reinforced concrete UPVC - 200mm dia. Fibre reinforced plastic – 2 units duty 500mm width; 12mm spacing 100mm (H) x 100mm (W) x 500mm (L) Max clearance, 12mm 37m3/106 m3 at average flow (minus the rubbish removed by primary screen) Fibre reinforced plastic (FRP) Fibre reinforced plastic High Density Polyethylene (HDPE) Grit and Grease Chamber Table 8 Grit Chamber Requirements Item 1 2 3 4 5 6 7 8 9 10 Process Chamber unit at Qpeak Chamber type Hydraulic Retention Time at Qpeak Maximum gravity flow through velocity at Qpeak Estimated grit quantity Check valve Gate valve with T plain end Grit removal pipe Channel ratio Side slope degree Requirement 1 units duty; 1 unit standy Rectangular 3 min 0.20m/s ~ 0.03m3 / 103 m3 of sewage Ductile iron Ductile iron Ductile iron - 100mm dia. Gradient 1 : 75 Depth : width 1 : 2 Length : width 2 : 1 30° 33 SPAN TS 1402:2016 Table 9 Grease Chamber Requirements Item 1 2 3 4 5 6 7 8 9 10 11 Process Chamber unit at Qpeak Chamber type Hydraulic Retention Time at Qpeak Estimated grease quantity Concentration of grease in the water Grease removal pipe Gate valve Stop Log Feeding to Anoxic Grease skimmer Gradient of grease buffer wall Requirement 1 units duty; 1 unit standy Horizontal flow 3 min ~0.03 m3/103m3 of sewage 0.1 kg/m3 Ductile iron - 100mm dia. Cast iron Fibre reinforced plastic (FRP) Free flow with opening Fixed & adjustable 5° Table 10 Grit and Grease Sand Bed Requirements Item 1 2 3 4 5 6 7 8 7.7 Process Retention Time Screed to fall Depth of grit and grease feed Perforated& overflow pipe Filtrate return sump Filtrate return pipe Splash pad Sand layer Requirement 30 days 1:200 350mm uPVC /VCP Min. 450mm depth Ductile Iron (above ground); VCP (buried) 500mm x 500mm x 100mm thk. 200mm coarse sand; 300mm aggregate (Grade 28mm to 40mm) Anoxic Tank Table 11 Anoxic Tank Requirements Item 1 2 3 4 5 6 7 Process Number of tanks Mixed Liquor Suspended Solids (MLSS) Internal Recycle Location Mixing power No. of mixer Feeding to aeration Requirement 1 (Type A); 2 (Type B and C) 2000 -4000 mg/l 2 to 6 (MLSS recirculation ratio) Head of aeration tank 3 w/m3 - 8 w/m3 2 nos. (1 duty, 1 standby) Overflow design with opening 34 SPAN TS 1402:2016 The Competent Person shall take all necessary consideration in the design in relation to the specific requirements of the receiving water in determining the actual nutrient removal requirement on a case by case basis. The selection of mixer shall also referring to the thrust which refer to the geometry of the tank. The actual position of mixer shall refer to manufacturer recommendation. 7.8 Aeration Tank Table 12 Aeration Tank Requirements Item 1 4 5 6 Process Number of tanks Hydraulic Retention Time (HRT) Mixed Liquor Suspended Solids (MLSS) F/M Ratio Organic loading Sludge age 7 Sludge yield 2 3 11 Dissolved oxygen (DO) in the tank Total air provided for organic removal Total air required for mixing Type of diffuser 12 Diffuser installation 8 9 10 13 14 15 16 17 18 19 20 Material at air and purge line pipe Air required for blower selection MLSS recycle ratio Return activated sludge (RAS) flow, QRAS IR pump Guide rail of IR pump Tank dimension length to width ratio Water depth Requirement 2 18 - 24 hrs (typical 20 hrs) 2000 - 4000 mg/l 0.05 ~ 0.1d-1 0.1 - 0.4 kg BOD5/m3.day > 20 days 0.4 (at 24 hrs HRT) sludge produced / kg BOD5 consumed 0.6 kg (at 18 hrs HRT) sludge produced / kg BOD5 consumed ≥ 2.0 mg/l Safety factor 20% for blower selection at suction Diffuser grid arrangement, 10-15 m3/103m3.min complete with purge line Fine bubble disc type Top of diffuser to be installed at max. of 0.3m from tank floor Hot dipped galvanized iron Highest among total air required for organic removal and mixing requirement 4 - 6 times of Qavg Equal to Qave (if MLSS = 4000 mg/L and underflow concentration, Cu = 8000 mg/L) 2 nos. (1 duty, 1 standby) Double Type A ( > 2.5:1 ) / Type B ( 3:1 ) / Type C ( 2:1 ) Min. 3m (Type A); Min. 3.5m (Type B and Type C) 35 SPAN TS 1402:2016 7.9 Blower Room Table 13 Blower Room Requirements Item 1 2 Description Distance Main door Requirement 1000mm (between blower and wall) Acoustic door with engineering design soundproof (Sound Transmission Class 40) 2400mm (W) x 2700mm (H) Monolithic structures; Heavy duty 12mm deep groove at ramp 200mm dia. pipe header Horizontal Min. 2 times the blower discharge pipe dia. Hot dipped galvanized iron Cast iron To aeration tank; Individual air pipe tapping To sludge holding tank; from air header in blower To scum skimmer; house Min. 3 nos. air flow female tapping Mineral wool Plastering to HDGI air pipe To be provided with the blower 3 Ramp & floor slab 4 5 Outlet silencer Pipe header 6 7 Gate & check valve HDGI Air pipe 8 9 Sampling point HRC acoustic plastering Safety valve External compound Beacon light lighting Roof RC flat slab (screed to fall with water proofing) Throating size - 10mm wide Mortar for brickwork 1:1:5 Cement-Lime-Sand mortar; Plastering and 20mm thk. with 1:3 cement-sand mortar rendering Concrete Plinth Min. 100mm Blower selection Discharge temp.: 25°C-120°C; Ambient temp.: 40°C; Relative humidity: 85% blower capable of operating at partial load condition of at least 60% of the rate speed at continuous operation Dampener of Spring type blower Lifting device Mobile A-Frame Exhaust fan Shall be provided inlet and out c/w acoustic treatment 10 11 12 13 15 16 17 18 19 20 The Competent Person shall take all necessary consideration in the design where vibration from blower and piping shall be dampened adequately to avoid transmitting to the floor and wall of control room. Shall provide signage for mobile A-Frame not to bring out from the blower room. 36 SPAN TS 1402:2016 The design of roof shall be considered from the following: i) Suitable material for roof (flat or slope) including colour; ii) Adequate air for ventilations; iii) Enough height for lifting facilities, access and headroom; iv) Type of insulation; v) Acoustic treatment where applicable; 7.10 Secondary Clarifier 7.10.1 General The design requirements shall include: a) Minimum retention time for settlement; b) Maximum settling velocity for settlement; c) Sludge hopper to collect settled sludge; d) For square clarifiers with 60º slope (from horizontal), minimum 1m side water depth shall be provided; e) The 60º slope (from horizontal) shall be cast in reinforced concrete structure; f) All clarifiers must be equipped with scum skimmer to remove scum from the surface. The scum collected must be drained (where necessary) and disposed to sludge holding tank. Returning the scum to the preliminary system or the biological system is not permitted; g) Multiple hopper are not permitted; h) Stilling basin to prevent hydraulic shock circuiting; i) Facilities to dispose scum and sludge; j) Appropriate feed and outlet pipe with hydraulic consideration; k) Proper maintenance access to all components. 7.10.2 Weirs a) If insufficient length is available, then considerations shall be given for the use of double weir; b) Cascading V-notch is preferred over rectangular weirs; c) Broad crested weirs are not encouraged; d) Slots in the weir shall be provided to allow for level adjustment during the installation stage; e) All parts of the weirs must be visible and accessible for regular cleaning. 37 SPAN TS 1402:2016 7.10.3 Square Clarifiers Table 14 Secondary Clarifier Requirements Item 1 2 4 Process Number of tanks Type of configuration Hydraulic Retention Time (HRT) at Qpeak Surface overflow rate 5 Solids loading rate 6 7 8 Weir loading rate Feeding Stilling box 9 10 11 12 13 14 15 Return sludge rate, Scum skimmer Scum pipe Maintenance platform Air pipe Weir plate Effluent channel surrounding Effluent channel finishing RAS/WAS pump 3 16 17 18 19 20 Requirement 1 nos. (Type A) / 2nos. (Type B) / 4 nos. (Type C) Square with 60° slope, min. 1.0 side water depth ≥ 2 hrs ≤ 30 m3/d/m2 (Qpeak) < 150 kg/d/m2 (Qpeak) < 50 kg/d/m2 (Qave) < 180 m3/day/m (Qpeak) Centre Non-corrosive Metal or FRP 10mm thickness; Length to be extended top at max. 1.5m from bottom level Diameter min. 1.0m 0.5 - 1.0 (QRAS/ Qinflow) Adjustable air lift Ductile iron or 3 layer mPVC Reinforced concrete - 1000mm width Hot dipped galvanized with ball valve Fibre reinforced plastic 4 sides White glazed tile entirely (all internal surfaces) 2 nos. (1 duty, 1 standby) for Type A ; 4 nos. (2 duty, 2 standby) For Type B; 5 nos. (4 duty, 1 spare pump) for Type C Guide rail of RAS/WAS Double pump RAS/WAS pipe Ductile iron or 3 layer mPVC – min. 80mm dia. Check and gate valve Ductile iron 7.11 Disinfection Tank Continuous disinfection is required for those areas where the discharge from the sewage works will cause detrimental effect onto the receiving water course, such as bathing beaches, lakes, etc. The Commission reserves the right to determine the need for the provision of a continuous disinfection facility. Only liquid or solid hypochlorite (sodium or calcium) shall be used. 38 SPAN TS 1402:2016 7.11.1 Disinfection with Hypochlorite a) The dosage rate is affected by the suspended solids and ammonia present in the effluent, mixing employed, contact time and the control strategies used for dosing; b) Proper mixing is important for effective disinfection; c) Circular chambers for disinfection are not acceptable; d) For continuous disinfection, liquid or solid hypochlorite (sodium or calcium) shall be used; e) For intermittent disinfection, only liquid hypochlorite (sodium or calcium) shall be used; f) A bypass around the chlorine contact chamber shall also be provided to enable flows to be bypassed during maintenance or servicing. There shall be penstocks upstream and downstream of the chlorine contact chamber for isolation purposes; g) By pass channel to be constructed at higher level to avoid sludge settlement in the channel; h) Adequate access with sufficient turning radius for the vehicle to carry in the chemicals to the disinfection system shall be provided; i) Benching shall be provided for all corners to enable smooth flow and minimize solids deposition. Table 15 Chlorination Chamber Requirements Item 1 Process Dosage 2 Chlorination tube 3 4 Contact period Maximum water depth Ratio 5 6 7 8 Requirement 6 - 10 mg/l Portable type Non-corrosive material 15 minutes at Qpeak 3m depth: width (2 : 1); length to width at each pass (6 : 1); wetted depth: width (< 2 : 1) Minimum no. of passes 4 Stop Log Washing bay Fibre reinforced plastic One stand pipe complete with concrete kerb 39 SPAN TS 1402:2016 7.12 Flow measurement Table 16 Flow Measurement Requirements Item 1 2 3 4 5 Process Location of flow meter Type of flow measurement Type of flow meter Method of measurement Measurement times Requirement Outlet Open Channel V- notch Manual measurement using staff gauge to measure height of crest with calibration curves / tables Intermittent 7.13 Sludge Holding Tank Table 17 Sludge Holding Tank Requirements Item 1 2 3 4 5 6 7 8 9 10 11 12 Process Retention Time Required Mixing requirement Slanted floor Safety ramp (top of tank) Air and purge line pipe Looping pipe Air diffuser Sludge drawn out / Sludge Transfer Pipe Female coupling (without SDB) Sludge Transfer Pump Guide rail of sludge transfer pump Splash pad Requirement 30 days 20m3 air / min./1000m3 tank 1:50 Hot dipped galvanized mild steel Min. 600mm Hot dipped galvanized iron Hot dipped galvanized iron - 50mm dia. Coarse bubble disc type Ductile iron or 3 layer mPVC Ductile iron 1 Duty, Submersible Type Double 500mm x 500mm x 100mm (located below sludge drawn out pipe for tanker) 40 SPAN TS 1402:2016 7.14 Sludge Drying Bed (If Applicable) Table 18 Sludge Drying Bed Requirements Item 1 2 3 4 5 9 10 11 12 13 Description Retention Time Free board Roofing Column, Truss Min. clearance between roof truss & top of ramp Min. eave length Max. allowable depth of sludge feed. Screed to fall (floor) Concrete Perforated pipe Gate valve Sludge transfer pipe 14 15 16 Filtrate return sump Splash pad Ramp 17 Sand layer 6 8 Requirement 28 days 100mm from top of sludge feed 1:15 gradient metal roofing sheet Structural Steel 2.1m 300mm 450mm 1:200 Min. grade 25 uPVC / VCP Ductile Iron Ductile Iron Min. 80mm – Type A & Type B Min. 100 – Type C Brickwall c/w 150mm dia. interconnected pipe 500mm x 500mm x 100mm Reinforced concrete; 600mm width; 1:10 slope with min. length of 1m 200mm coarse sand (from 2mm-4.7mm); 300mm aggregate (Grade 28mm to 40mm) The actual quantity of sludge from the upstream unit processes needs to be computed before sizing the bed. Each bed may be designed to handle a maximum of 7 days continuous feed. The next feed to the same bed shall only be after a minimum of 21 days from the last feed. A one-third (1/3) reduction in actual land area requirement will be acceptable if fully covered drying beds are provided. Reduction shall only apply to the total surface area of drying bed. 41 SPAN TS 1402:2016 7.15 Sludge Storage Hut (If applicable) Table 19 Sludge Storage Hut Requirements Item 1 2 3 4 5 6 Description Roofing Column, Truss Min. clearance between roof truss & top of ramp Min. eave length Concrete Ramp Requirement 1:15 gradient metal roofing sheet Structural Steel 2.1m 300mm Min. grade 25 Reinforced concrete; 600mm width; 1:10 slope with min. length of 1m 7.16 Control Room Table 20 Control Room Requirements Item 1 Description Main door 2 3 Window Control panel box 4 5 6 7 8 9 Mounting Fire extinguisher First aid box, emergency sign & equipment labeling Rubber mat Exhaust fan Notice board 10 Roof Requirement Single leaf metal door with 2 layers anti rust epoxy coating 900mm (W) x 2100mm (H) Louvered window Front 2.0mm thk. mild steel sheet; Rear/Side/Top 2.0 mm thk. mild steel sheet ; Light grey powder coated paint ≤ 100A : Wall mounted; ≥ 100A : Floor mounted CO2 type To be provided 12mm thk. (min.) To meet the room air exchange requirement Single line diagram; Artificial respiration chart, process flow diagram RC flat slab (screed to fall with water proofing); Throating size - 10mm wide The design of roof shall be considered from the following: i) Suitable material for roof (flat or slope) including colour; ii) Adequate air for ventilations; iii) Enough height for lifting facilities, access and headroom; iv) Type of insulation; v) Acoustic treatment where applicable. 42 SPAN TS 1402:2016 7.17 Ancillary Requirement Table 21 Anti-Climb, Brick Wall Fencing Requirements Item 1 2 3 4 5 Description Gate wire mesh Cover to reinforcement Mortar Plastering and rendering Weld thickeners Requirement 10SWG / 13SWG (for anti-climb fencing only) 25mm 1:1:5 Cement-Lime-Sand mortar 20mm thk. with 1:3 cement-sand mortar 6mm fillet Table 22 Sliding Gate Requirements Item 1 2 Description Type Weld thickeners Requirement 6m wide double rail 6mm fillet Brick walls shall be anchored to concrete faces using galvanized fishtail anchors to lap in with the brick reinforcement at every fourth course commencing two courses above ground beam level. All exposed wall shall be painted with (1) one undercoat of approved resisting primer sealer and (2) two coats of approved weather resistant emulsion paint. All bricks used shall be first quality cement / sand bricks. Brickwork shall be reinforced with expanded metal or “exempt” at every fourth course commencing two courses above ground beam level. 43 SPAN TS 1402:2016 7.18 Yard Lighting Table 23 Yard Lighting Requirements Item 1 2 Description Type A Type B Type C 4 5 6 7 Type Supplier/manufacturer & galvanizer of the column Column design Steel column material Steel accessories Column seam building 8 Column material 9 10 11 12 13 Panel Material Thickness Painting Finish Colour 3 Requirement Min. 1 no at inlet works or entrance Min. 2 nos. at inlet works and treatment process unit Min. 4 nos. at every internal corner of STP boundary and nearby to inlet works and treatment process unit LED ISO 9001:2000 BS 5649 Steel BS-EN10025 fe 430C or fe 510C Fe 360 BS 5135 Hot dipped galvanized BS 729 (average coating weight 460gm/m) Outdoor type (floor standing) Electro galvanized sheet 2.3mm Epoxy powder paint Light grey Sufficient lighting shall be provided at strategic location such as entrance gate, inlet works and necessary areas. All lightings shall be installed above emergency overflow level. 44 SPAN TS 1402:2016 7.19 Handrail, Safety Chain, Staircase, Grating and Chequered Plate Table 24 Handrail, Staircase, Grating and Chequered Plate Requirements Item Handrail Description 1 Material 2 Size 3 4 At platform, walkways and landing Above pitch pitch line on stairs 5 Joint 6 Finishing 7 Kicker plate Staircase 1 Type 2 Thread and riser 3 Landing length Grating 1 Material 2 Weight Chequered plate 1 Material 2 Weight Guide rail 1 Material Requirement Hot dipped galvanized mild steel (above ground level and dry well area); Stainless steel 304 (wet well area and area that come in contact with sewage) 38mm dia. tubular rails; Top and intermediate rails at 550mm center 1100mm (H) 900mm to 1000mm Handrail joint to be located on center line of handrail standards All rough edges and burrs to be removed; Welds to be 6mm thk. fillet weld (neat and ground smooth) Hot dipped galvanized mild steel (above ground level and dry well area); Reinforced concrete- anti skid Thread : 250 Riser : 200 1000mm Fibre reinforced plastic or Hot dipped galvanized steel; ≤ 16kg / piece Hot dipped galvanized steel ≤ 16kg / piece Stainless steel filled with cement Safe access and walkways shall be provided at all process units and equipment (valves, penstocks, aeration tanks, etc.) that require service and maintenance. Safety handrails shall also be installed at walkways and other working areas with a fall greater than 2 m. 45 SPAN TS 1402:2016 Provision for fire detection, alarm and firefighting equipment shall be complying with the latest requirements in the Uniform Building Bylaws, the Institute of Electrical Engineers (IEE) guidelines and other statutory requirements. All tanks shall not exceed 1.2 m above ground. Staircase and ladder exceeding 1.2 m shall be provided with handrail. All plants located adjacent to earth slopes shall be provided with proper slope protection structures. The slope protection design must be certified by Competent Person. 7.20 Toilet Table 25 Toilet Requirements Item 1 2 3 4 5 6 Description Floor and Wall Window Washing bay Door Water closet Water tank Requirement Ceramic tiles Hollow ventilation block One stand pipe complete with concrete kerb PVC ; 900mm (W) x 2100mm (H) Squatting type 100 gallon 7.21 Lifting Facility Table 26 Lifting Requirements Item 1 Description Weight < 16kg 16 kg ≤ Weight ≤ 250 kg 2 Weight > 250 kg 3 4 Safety chain Requirement Manual lifting A davit or ‘A’ frame shall be arranged to allow items lifted by using manual chain hoist to be projected on a 1.2m truck tray and positioned at 2m above road level. In the pump station, motorized hoist is required for lifting weight exceeding 100 kg A gantry with motorized hoist shall be arranged to allow items to be projected on a 1.2 m truck tray and positioned at 2m above road level truck tray Min. 6mm dia. long link smooth welded complete with fixings including ‘S’ hooks and ‘D’ shackles stainless steel Lifting equipment shall be subjected to DOSH approval standards and guidelines. Safe Working Load with approved method of installation shall be rated, indicated and printed for all lifting facilities. Height and lifting method must be considered in the design for Safe Working Load of lifting facilities. All portable motorized hoist shall 46 SPAN TS 1402:2016 be of 230 V operating voltage and fixed electrical hoist shall be of 415 V operating voltage. All fixed 3 axis type gantry shall come with additional safety features such as travel stop limit switch, hoist over run limit switch, slow & fast speed mode and emergency stop (for all type of hoist). All fixed type outdoor lifting facility futures shall comprise of hoist parking bay with shade. All fixed type lifting facility shall come with working platform and excess ladder. 7.22 Ventilation Ventilation can be achieved naturally or mechanically: i) Natural ventilation uses the force of nature such as air currents, breezes, thermal gradients and pressure differences to move airing and out of the space; ii) Mechanical ventilation uses fans and blowers to force air through space. It is also sometimes called forced ventilation. Particular requirements are: i) Ventilation shall be intrinsically safe with respect to explosive gases (such as methane) where such gases may be present; ii) Ventilation shall be designed to deal with the different densities of the various gases; iii) Ventilation fans shall be located outside the enclosed space to induce forced air into the plant. Intake locations shall be such that only fresh air is drawn into the system and not air recirculated from the exhaust; iv) Mechanical ventilation shall be used if the system is required to remove contaminants; v) Ventilation exhaust shall be directed to a suitable location for discharge and it shall not be adjacent to the intake point; vi) Ventilation at rooms where heat generation may take place must be adequate to dissipate the heat generated to ensure a comfortable making ambient for the equipment and the operator; vii) Noise levels associated with operating fans and blowers, particularly in a confined space, shall conform to the requirements in Section5.7 and other stationary requirements; viii) ix) Optimize recurring cost for operation, maintenance and replacement; Regular testing and inspection of the equipment; 47 SPAN TS 1402:2016 x) Visible warning shall be provided at all entry points. This shall automatically operate if the fan fails; xi) Where natural or forced ventilation is provided, it shall be installed in such a manner so as to avoid any ingress of water due to rain or other sources; xii) In areas with routine entry by personnel, the ventilation strategy shall emphasize adequate control of contaminants and the ventilation system shall be continuously operated. Table 27 Common Ventilation Rates Item Wet-Well Dry-Well Grit Removal/Screen Area Digester Gas Control Room Sludge Gas Compressor Room Enclosed Grit Loading Areas Enclosed Primary Sedimentation Tanks Scum Concentration Tank Description 30 intermittent 12 continuous 30 intermittent 12 continuous 30 intermittent 12 continuous 30 intermittent 12 continuous 30 intermittent 12 continuous 30 intermittent 12 continuous 30 intermittent 12 continuous 30 intermittent 12 continuous Chlorine and Sulphur Dioxide Rooms 60 intermittent 12 continuous Filter/Dewatering Area 12 continuous All other enclosed unit processes not mentioned elsewhere 30 intermittent 12 continuous Requirement Use 100% outside air. Step up to 24 ac/hr if hazardous gases are detected. Consider odour control, where warranted Same as wet well Same as wet well Same as wet well Same as wet well Same as wet well Same as wet well Hazardous areas, toxic fumes, floor level exhaust required. Interlock fans with manual switches located at each entrance. Also interlock fans with chlorine and Sulphur dioxide detection. Use 100% outside air Consider odour control for exhaust air from dewatering area, where warranted In particular at blower room, high tension room, low voltage room, switchboard and control panel rooms, where there are tendency of heat generation 48 SPAN TS 1402:2016 7.23 Painting for Pipe Works Painting shall include all plant and machinery inside buildings, including pipework, grating, hand railing, internal walls below ground level and all metal work including machinery. The conduits and piping shall be appropriately named and labeled indicating flow directions and painted with the following colour codes for easy identification: i) Chlorine line - yellow with double green bands; ii) Compressed air line - green; iii) Fuel gas line - orange; iv) Potable water supply line - blue; v) Raw sewage line - black; vi) Final effluent line - grey; vii) Sludge line - brown; viii) Non-potable water line - blue with double black bands; ix) Other disinfectant lines - yellow with double red bands; x) Biogas line - yellow; The labels shall be stenciled on the piping in a contrasting colour with the colour coded bands, if any, located at appropriate and strategic points. Colour codes selected for general equipment, building and others items in a sewage treatment plant shall be adhered to. The types of paint and surface preparation used shall be as recommended by the paint manufacturer. 7.24 Plumbing Works Plumbing works and fire protection to follow local authorities’ requirements. Inspection and cleaning access shall be provided at all bends and junction of soil and waste pipes. 49 SPAN TS 1402:2016 Table 28 Plumbing Work Requirements Item Description 1 Piping material 2 Gradient 3 Waste piping from basin/sink 4 Floor traps 5 6 Soil pipes under carriageway Manholes cover on carriageway Requirement UPVC BS 4514, BS 5255 and MSD 15 (above ground soil, waste and vent) UPVC BS 4660 (underground soil & waste pipes) 32mm dia. - (1:12.5); 40mm dia. – (1:15.0); 50mm dia. – (1:20.0); 75mm dia. – (1:30.0); 100mm dia. – (1:40.0); 150mm dia. – (1:60.0) 50mm dia. and below; shall be chased in brick wall wherever possible 100mm dia. and complete with stainless grating and access for cleaning To be encased in min. 150mm concrete and reinforced with one layer BMC A7 Heavy duty type 7.25 General Mechanical and Electrical Table 29 Bolt and Nut Requirements Item Description Bolt and Nut 1 Material Holding down bolts 1 Materials Requirement J-bolt OR Chemical grouting Stainless steel Grade 316 if contact with sewage or Chemical grouting. Table 30 Piping Works Requirements Item Description Pipe works 1 Material Pipe support/ bracket 1 Material 2 Clearance Pipe support bracket Pipe joint Requirement Ductile iron with cement lining or mPVC 3-layer Stainless steel 304 100mm from floor concrete slab to flange; 3m interval for ductile iron and 1m for 3 layer mPVC; Pipe per length shall be jointed at every 6m Flexible coupling shall be provided for 3 layer mPVC pipe Additional requirement for pipe works: i) External surface of pipework (D.I. type) in chambers and wells shall be epoxy coated; ii) Buried ductile iron pipe shall have polyethylene sleeving; 50 SPAN TS 1402:2016 iii) Pipe within wells and pits shall have flanged joints, while pipe laid in the ground shall have spigot and socket joints; iv) Pipe work shall be adequately supported on concrete plinths or steel structural supports; v) Flanges shall be located at least 150 mm away from structures; vi) Dismantling joints such as bends shall be provided; vii) Pumping thrust shall be resisted using pipe supports inside chambers and by mass concrete thrust blocks poured against undisturbed soil in the ground outside chambers; viii) No welding joints are allowed. Table 31 Emergency Shutoff Switch, Junction Box & Electrical Services Requirements Item Description Emergency shutoff switch 1 Switch 2 Type Junction box 1 Enclosure 2 Temperature 3 Resistance 4 Mounting type Electrical Services 1 GI conduit (Exposed) 2 UPVC conduit (Concealed) 3 Final combined earthing system resistance Earth resistance 4 5 Protective conductor - Cross-sectional area of protective conductor Auto restart facilities Requirement For every motorised equipment/ machines Mushroom IP66 dust damp proof according to IEC 529 Up to 75 deg. C To chemical, detergent solvent, grease and oil; Watertight surface Heavy gauged (class B) hot dipped galvanised, threaded; 20mm dia. & 1.52mm thickness; Location at M&E plant room; Machinery plant; Substation / switch room High impact rigid conduit; 20mm dia. & 1.80mm thickness; Not exceeding 1 ohm Electrical system < 5 ohms each chamber 2 lightning protection system < 10 ohms each chamber S<16mm2 - Smm2 16≤S<35mm2 - 16mm2 S>35mm2 - S/2mm2 Equipped for all electrical items for quick reoperation in the event of power failure 51 SPAN TS 1402:2016 8.0 Reporting Format Competent Person is to submit the Summary of Design Declaration form and endorsed Mass Balance and Hydraulic Profile calculation sheet as stipulated in Annex D. 9.0 Construction and Installation 9.1 General The construction and installation works shall be executed in compliance with the relevant statutory and legislative regulations of Malaysia. The complete installation construction and material stated shall comply with the current rules and requirement of local authority and any other relevant authorities having jurisdiction over the installation. 9.2 Quality control Before commencement of the construction works, a quality control program shall be developed, implemented and maintained consistent with the requirements of the works. Quality shall be maintained in all areas of work. 9.3 Health and safety requirements The following shall be considered throughout the construction and installation period to ensure safe working conditions for workers and ensure protection of adjoining properties and the public: a) Site layout; b) Provision of welfare facilities; c) Safe access and egress; d) Requirement of competent/designated persons; e) Earthworks; f) Temporary working platforms; g) Piling and excavation works; h) Working at height; i) Permit to work; j) Working in confined space; k) Lifting appliances and method; l) Registration of plant/equipment; 52 SPAN TS 1402:2016 m) Machine guarding; n) Safe use of portable tools; o) Site tidiness/housekeeping; p) Accident reporting and investigation; q) Emergency prevention, preparedness and response; r) Compliance to Environmental Quality Act 1974, Occupational Safety and Health Act 1994 and Factories and Machinery Act 1967 requirements s) Health and Safety Audits; t) The plant shall also be designed to comply with other related legislations such as IEE, Akta Bekalan Elektrik 1990 (Akta 448) and Peraturan-Peraturan Elektrik 1994 and the relevant IEEE Standards; u) Safety level for all electronically operated electrical device such as soft starters, variable speed drive and others shall conform to IEC, EN, UL, NFC and VDE. Thus it shall fulfill EN 50178, EN 60204, BS EN 60950, IEC 61800; v) Where appropriate, IEE and Akta 448 (1990) and Peraturan Elektrik 1994 must be complied within all electrical installation; w) The following shall be provided: i) All moving parts shall be protected by suitable guards. Where inspection is required, an open mesh with frame and suitably supported maybe used. The maximum aperture of the mesh shall be 6 mm; ii) All guards shall be readily removable and replaceable to the correct orientation only. However the guard shall be designed with features to prevent accidental dislocation from its' original position. The fasteners when dropped during dismantling, must be easily retrievable and should not damage any equipment or endanger personnel, else fixed fasteners shall be used; iii) An emergency stop button, preferably of mushroom head type shall be located adjacent to all equipment. More than one emergency stop button shall be used, if access around the item is restricted; iv) Long items, such as conveyor belts, shall have an emergency lanyard applied to each accessible length of conveyor; v) Surfaces which are greater than 50°C shall be guarded; vi) Permanent warning signs shall be posted at visible location tall dangerous areas and shall clearly indicate the nature of risk at that area. This includes warning signage at digesters area, high tension room, low voltage room, generator room and other hazardous areas; 53 SPAN TS 1402:2016 vii) Automatic CO2discharge triggered by heat and smoke sensors shall be installed in high voltage switch room, transformer room, low voltage switch room and generator room; viii) High tension room shall have signage to clearly indicate the purpose of the room and also safety signage to prevent unauthorized entry. Calcium and sodium hypochlorite are hazardous chemicals to handle and use. Calcium hypochlorite is classified as a corrosive agent. Eye protection, access to an emergency eyewash system and showers must be made available to the operators. Also, direct contact with the undiluted hypochlorite is likely to cause burns to the skin and clothing. Therefore, it is imperative that protective clothing which includes rubber gloves, must be worn by operators when working with these chemicals. When calcium hypochlorite is being transported in the powder form and mixed in water to form solutions, the operator should always wear eye protection and dust masks. All areas exposed to hypochlorite should be washed thoroughly. 9.4 Inspection For the purpose of inspection, a guide has been prepared but is not limited to Annex C. This guide comprises common components as well as a typical defect list that shall be referred to by the CP during the inspection exercise. The inspection guides including all relevant test records are not required to be submitted but has to be kept properly by the CP and made available upon request. 10.0 Testing and Commissioning All testing and commissioning (T&C) shall be carried out in accordance with the relevant operation and maintenance manual witnessed and endorsed by CP. Records of pre-commissioning tests and commissioning tests should be properly maintained by CP and made available upon request. The functionality test shall be carried out on the following but not limited to:a) Inlet Chamber - Manual Screen Test; b) Pump Sump - Raw Sewage Pump; c) Secondary Screen Chamber - Manual Screen Test; d) Aeration Tank - Diffuser Test; e) Clarifier Tank - RAS / WAS Pump; f) Sludge Holding Tank - Diffuser Test; g) Blower Room - Blowers, Main Control Panel. 54 SPAN TS 1402:2016 ANNEX A: REFERENCES Malaysian Standards • MS 144 Steel wire for the reinforcement of concrete products – specification • MS 145 Steel fabric for the reinforcement of concrete – specification • MS 146 Steel for the reinforcement of concrete - weldable reinforcing steel - bar, coil and decoiled product – specification • MS 415 Code of practice for composite construction in structural steel and concrete • MS 739 Specification for hot-dip galvanized coatings on iron threaded fasteners • MS 740 Specification for hot-dip galvanized coatings on iron and steel articles • MS 822 Specification for sawn-timber foundation piles • MS 1037 Specification for sulphate-resisting portland cement • MS 1195: Part 2 Code of practice for structural use of concrete: Special circumstances • MS 1226: Part 1 Pulverized-fuel ash: Specification for pulverized-fuel ash for use as a cementitious component in structural concrete • MS 1241 One-piece glass fibre reinforced polyester (GRP) water tanks - nominal capacity of 100 000 litres and below – specification • MS 1292 Rubber seals - water stops for sealing joints in concrete - specification of materials • MS 1390 Glass-fibre reinforced polyester panels and panel water tanks – specification 55 SPAN TS 1402:2016 • MS EN 934 Admixtures for concrete • MS EN 12620 Aggregates for concrete • MS EN 15167-1 Ground granulated blast furnace slag for use in concrete, mortar and grout - part 1: Definitions, specifications and conformity criteria • MS EN 15167-2 Ground granulated blast furnace slag for use in concrete, mortar and grout - part 2: Conformity evaluation British Standards • BS 4-1 Structural steel sections. Specification for hot-rolled sections • BS 476 Fire tests on building materials and structures • BS 1161 Specification for aluminium alloy sections for structural purposes • BS 3396-1 Woven glass fibre fabrics for plastics reinforcement. Specification for loom-state fabrics • BS 3532 Method of specifying unsaturated polyester resin systems • BS 3749 Specification for E glass fibre woven roving fabrics for the reinforcement of polyester and epoxy resins systems • BS 4449+A2 Steel for the reinforcement of concrete. Weldable reinforcing steel. Bar, coil and decoiled product. Specification • BS 4514 Unplasticized PVC soil and ventilating pipes of 82.4 mm minimum mean outside diameter, and fittings and accessories of 82.4 mm and of other sizes. Specification 56 SPAN TS 1402:2016 • BS 4660 Thermoplastics ancillary fittings of nominal sizes 110 and 160 for below ground gravity drainage and sewerage • BS 4868 Specification for profiled aluminium sheet for building • BS 4921 Specification for sherardized coatings on iron or steel • BS 5255 Specification for thermoplastics waste pipe and fittings • BS 5493 Code of practice for protective coating of iron and steel structures against corrosion • BS 7079 General introduction to standards for preparation of steel substrates before application of paints and related products • BS EN 197-1 Cement. Composition, specifications and conformity criteria for common cements • BS EN 485 Aluminium and aluminium alloys. Sheet, strip and plate • BS EN 754 Aluminium and aluminium alloys. Cold drawn rod/bar and tube • BS EN 755 Aluminium and aluminium alloys. Extruded rod/bar, tube and profiles • BS EN 934-2 Admixtures for concrete, mortar and grout. Concrete admixtures. • BS EN 1676 Aluminium and aluminium alloys. Alloyed ingots for remelting. Specifications • BS EN 1990+A1 Eurocode. Basis of structural design • BS EN 1992-1-1+A1 Eurocode 2: Design of concrete structures. General rules and rules for buildings 57 SPAN TS 1402:2016 • BS EN 1992-3 Eurocode 2: Design of concrete structures. Liquid retaining and containing structures • BS EN 1999-1-1+A2 Eurocode 9: Design of aluminium structures. General structural rules • BS EN 1999-1-3+A1 Eurocode 9: Design of aluminium structures. Structures susceptible to fatigue • BS EN 1999-1-4+A1 Eurocode 9: Design of aluminium structures. Cold-formed structural sheeting • BS EN 10088-1 Stainless Steels. List of Stainless Steels • BS EN 10088-3 Stainless steels. Technical delivery conditions for semi-finished products, bars, rods, wire, sections and bright products of corrosion resisting steels for general purposes • BS EN 14118-1 Reinforcement. Specifications for textile glass mats (chopped strand and continuous filament mats). Designation • BS EN 14118-2 Reinforcement. Specifications for textile glass mats (chopped strand and continuous filament mats). Methods of test and general requirements • BS EN 14118-3 Reinforcement. Specifications for textile glass mats (chopped strand and continuous filament mats). Specific requirements • BS EN 15743+A1 Supersulfated cement. Composition, specifications and conformity criteria • BS EN 60950 Information technology equipment. Safety • BS EN 61000-6-1 Electromagnetic compatibility (EMC). Generic standards. Immunity for residential, commercial and light-industrial environments • BS EN 61000-6-2 Electromagnetic compatibility (EMC). Generic standards. Immunity for industrial environments 58 SPAN TS 1402:2016 • BS EN 61672-1 Electroacoustics. Sound level meters. Specifications • BS EN 61672-2 Electroacoustics. Sound level meters. Pattern evaluation tests • BS EN 61672-3 Electroacoustics. Sound level meters. Periodic tests • BS EN ISO 3210 Anodizing of aluminium and its alloys. Assessment of quality of sealed anodic oxidation coatings by measurement of the loss of mass after immersion in phosphoric acid/chromic acid solution • BS EN ISO 17660-1 Welding. Welding of reinforcing steel. Load-bearing welded joints • BS EN ISO 17660-2 Welding. Welding of reinforcing steel. Non load-bearing welded joints European Standards • EN 10025 Hot rolled products of structural steels • EN 10029 Hot-rolled steel plates 3 mm thick or above - Tolerances on dimensions and shape • EN 10162 Cold-rolled steel sections - Technical delivery conditions - Dimensional and crosssectional tolerances • EN 10210 Hot finished structural hollow sections of non-alloy and fine grain steels • EN 10296 Welded circular steel tubes for mechanical and general engineering purposes Technical delivery conditions • EN 10297 Seamless circular steel tubes for mechanical and general engineering purposes Technical delivery conditions • EN 10305 Steel tubes for precision applications - Technical delivery conditions 59 SPAN TS 1402:2016 • EN 14020 Reinforcements - Specification for textile glass rovings • EN 50178 Electronic equipment for use in power installations • EN 60204 Safety of machinery - electrical equipment of machines • EN ISO 2063 Thermal spraying - metallic and other inorganic coatings - Zinc, aluminium and their alloys • EN ISO 9445 Continuously cold-rolled stainless steel - Tolerances on dimensions and form ASTM Standards • ASTM C582 Standard specification for contact-molded reinforced thermosetting plastic (RTP) laminates for corrosion-resistant equipment • ASTM E84 Standard test method for surface burning characteristics of building materials AS Standards • AS/NZS 2312.1:2014 Guide to the protection of structural steel against atmospheric corrosion by the use of protective coatings - Paint coatings • AS/NZS 3750.2 Paints for steel structures - Ultra high-build paint • AS/NZS 3750.12 Paints for steel structures - Alkyd/micaceous iron oxide IEEE Standard • IEC 61800 Adjustable speed electrical power drive systems 60 SPAN TS 1402:2016 Other Reference Materials Environmental Quality Act 1974 (Act 127) Factories and Machinery Act 1967 (Act 139) Electricity Supply Act 1990 (Act 447) Electricity Supply (Successor Company) Act 1990 (Act 448) Occupational Safety and Health Act 1994 (Act 514) Water Services Industry Act 2006 (Act 655) Electricity Regulations 1994 Environmental Quality (Sewage) Regulations 2009 SPAN. 2009. Malaysian Sewerage Industry Guidelines. National Water Services Commission Malaysia. DOE. 2012. Guidelines for Siting and Zoning of Industry and Residential Areas. Department of Environment Malaysia. 61 SPAN TS 1402:2016 ANNEX B: STANDARD STP DRAWINGS 62 SPAN TS 1402:2016 SEWAGE TREATMENT SYSTEM: STANDARD STP, PART 1 -EXTENDED AERATION (150 - 5000 PE) STANDARD STP DRAWINGS TYPE A (150 - 1000 PE) 63 SPAN TS 1402:2016 SEWAGE TREATMENT SYSTEM: STANDARD STP, PART 1 - EXTENDED AERATION (150 - 5000 PE) STANDARD STP DRAWINGS TYPE B (1001 - 3000 PE) 64 SPAN TS 1402:2016 SEWAGE TREATMENT SYSTEM: STANDARD STP, PART 1 - EXTENDED AERATION (150 - 5000 PE) STANDARD STP DRAWINGS TYPE C (3001 - 5000 PE) 65 SPAN TS 1402:2016 SEWAGE TREATMENT SYSTEM: STANDARD STP, PART 1 - EXTENDED AERATION (150 - 5000 PE) STANDARD STP DRAWINGS TYPICAL DETAILS 66 SPAN TS 1402:2016 ANNEX C: INSPECTION GUIDE & TYPICAL LIST OF DEFECTS 67 SPAN TS 1402:2016 Standard STP - Extended Aeration (EA) Inspection Guide Reinforcement Location : Designation : Checklist No. ___________________________ Item Yes Description No Remarks by Engineer FIXED REINFORCEMENT 1 Main Re-Bar 1.1 Grade 1.2 Bar size ………………..………… mm 1.3 Spacing ………………………….. mm 1.4 Lapping length ……...…………… mm 1.5 Final Inspection for this item 2 Secondary Re-Bar 2.1 Grade 2.2 Bar size ………………..………… mm 2.3 Spacing ………………………….. mm 2.4 Lapping length ……...…………… mm 2.5 Final Inspection for this item 3 Reinforcement 3.1 Minimum cover achieved 3.2 Free from mud, oil, grease, etc. 3.3 Cleanliness of re-bars (free from excessive rust) 3.4 Starter bars & dowel bars installed properly 3.5 Position of re-bars around openings as required based as per drawings 3.6 Tying wire and supports (sufficient number of spacers and chairs) 3.7 Others ……………………………. 3.8 Final Inspection for this item Inspected by : Signature : Date: (Name) Remarks by Engineer : The Contractor is : ALLOWED NOT ALLOWED to proceed with the works. Non-conformance raised during inspection / re-inspection? Inspected by : Signature : YES NCR No.: NO Date: (Name) Please √ off w here appropriate 68 SPAN TS 1402:2016 Standard STP - Extended Aeration (EA) Inspection Guide Formwork Location : Designation : Checklist No. ___________________________ Description Item Yes No Remarks by Engineer FORMWORK 1 Forms 1.1 Levels and chambers 1.2 Closeness and joints 1.3 Forms are adequate for required class of surface finish (F1, F2, F3, ……) 1.4 Alignment and plumb 1.5 Application of form oil 1.6 Free from ponding of water 2 Openings and Penetrations 2.1 Dimensions as per drawings 2.2 Position as per drawings 2.3 Embedment plates installed 2.4 Fixings and supports 2.5 Cast-in pipe and conduits 2.6 Chamfers installed 3 Wall and Column Forms 3.1 Type of form (steel, timber, other, ………) 3.2 Tie bolts (number, location, etc) 3.3 Fixings and supports 3.4 Concrete cover (…………mm) Inspected by : Signature : Date: (Name) Remarks by Engineer : The Contractor is : ALLOWED NOT ALLOWED to proceed with the works. Non-conformance raised during inspection / re-inspection? Inspected by : Signature : YES NCR No.: NO Date: (Name) Please √ off w here appropriate 69 SPAN TS 1402:2016 Standard STP - Extended Aeration (EA) Inspection Guide Cast In-Situ Reinforced Concrete Concreting Location : Designation : Checklist No. ____________________________ Description Item Yes No Remarks by Engineer FINAL CHECK PRIOR TO CASTING 1 Inspection of formwork (dimensions, plumb, level, alignment, rigidity). 2 Cleanliness of forms (mould oil applied) 3 Construction joints (cleanliness, position, preparation, properly secured) 4 Inspection of reinforcement (cover, size, numbers, spacing, cleanliness laps, links, stirrups) 5 Mechanical (opening for duct & pipe sleeve, trimming bars, inserts, rigidity) 6 Electrical (conduit and box earthing conductor, opening for equipment rigidity) 7 Slump test recorded (at the batch plant……….mm; on site…………mm) 8 Mix acceptable (concrete grade as required) check D/O for night grade 9 Testing laboratory notified and required number of cubes taken 10 Vibrators and stand-by vibrators available 11 Weather condition acceptable (good, fair, rain) 12 Time limitation 120 min. (time measured from batching to fully discharged concrete time) 13 If in-use concrete pumps clean and ready 14 Mobile cranes & concrete hoppers available as means of concrete placement 15 Concrete free fall not more than 1.6m 16 Safety measures covering this activity are adequate (barricades, platform, etc.) 17 Dowel bars, waterstop, joint filter installed as required 18 Others 19 Final inspection for this item Inspected by : Signature : Date: (Name) Remarks by Engineer : The Contractor is : ALLOWED NOT ALLOWED to proceed with the works. Non-conformance raised during inspection / re-inspection? Inspected by : Signature : YES NCR No.: NO Date: (Name) Please √ off w here appropriate 70 SPAN TS 1402:2016 Standard STP - Extended Aeration (EA) Inspection Guide Cast In-Situ Reinforced Concrete Concreting Location : Designation : Checklist No. ____________________________ Description Item Yes No Remarks by Engineer INSPECTION DURING CASTING AND POST-CASTING 1 Compaction in horizontal layers of less than 450mm 2 Thoroughly worked between forms and reinforcement 3 Pouring time START…………………..FINISH…………………. 4 Alignment, elevations and supports checked during pouring 5 Construction joints (horizontal) in required position 6 Finish of concrete as specified (type/ class of finish…………………….) 7 Concrete curing applied as specified (type of curing…………………….) 8 Amount of concrete poured…………………m 3 9 Others 10 Final inspection for this item Inspected by : Signature : Date: (Name) Remarks by Engineer : The Contractor is : ALLOWED NOT ALLOWED to proceed with the works. Non-conformance raised during inspection / re-inspection? Inspected by : Signature : YES NCR No.: NO Date: (Name) Please √ off w here appropriate 71 SPAN TS 1402:2016 Standard STP - Extended Aeration (EA) Inspection Guide Installation of Penstock Location : Designation : Checklist No. ____________________________ Description Item Yes No Remarks by Engineer 1 Approved material : _______________________________________ 2 Correct bolt holes depth, position and spacing 3 Bolting (chemical anchor bolt) penstock to wall 4 Correct vertically 5 Correct horizontally 6 Correct spindle alignment 7 Grouting of penstock frame 8 Headstock and actuator installed 9 _______________________________________________ 10 _______________________________________________ Inspected by : Signature : Date: (Name) Remarks by Engineer : The Contractor is : ALLOWED NOT ALLOWED to proceed with the works. Non-conformance raised during inspection / re-inspection? Inspected by : Signature : YES NCR No.: NO Date: (Name) Please √ off w here appropriate 72 SPAN TS 1402:2016 Standard STP - Extended Aeration (EA) Inspection Guide Installation of Pumpset Location : Designation : Checklist No. ____________________________ Item Yes Description No Remarks by Engineer 1 Approved handling and working method 2 Correct pump plinth and/ or motor pedestal footing setting out 3 Correct hold down bolt type & size for pump/ motor pedestal/ shaft pedestal 4 Correct pump level and alignment 5 Correct motor level and alignment 6 Correct shaft alignment - pump, motor, intermediate shaft (attach results) 7 Bolting and gasket at flange joint 8 Grouting of pump foot/ shaft pedestal/ motor pedestal 9 Auxiliary piping installed 10 All damaged surface made good 11 _______________________________________________ Inspected by : Signature : Date: (Name) Remarks by Engineer : The Contractor is : ALLOWED NOT ALLOWED to proceed with the works. Non-conformance raised during inspection / re-inspection? Inspected by : Signature : YES NCR No.: NO Date: (Name) Please √ off w here appropriate 73 SPAN TS 1402:2016 Standard STP - Extended Aeration (EA) Inspection Guide Cast In-Situ Reinforced Concrete Concreting Location : Designation : Item Checklist No. ____________________________ Description Yes No Remarks by Engineer 1 Correct chamber level and opening size 2 Correct vertically and horizontality - Bottom section 3 Correct vertically and horizontality- Intermediate section 4 Correct vertically and horizontality - Upper intermediate section 5 Bolting and grouting of frame sections to wall 6 Correct vertically and horizontality - Head section 7 Scarificial anodes installed correctly 8 Assembly of equipments at head section in order 9 Correct installation of roler chain and mesh panel 10 Wash water system installed correctly Inspected by : Signature : Date: (Name) Remarks by Engineer : The Contractor is : ALLOWED NOT ALLOWED to proceed with the works. Non-conformance raised during inspection / re-inspection? Inspected by : Signature : YES NCR No.: NO Date: (Name) Please √ off w here appropriate 74 SPAN TS 1402:2016 Standard STP - Extended Aeration (EA) Inspection Guide Installation of Valve Location : Designation : Checklist No. Description Item Yes 1 Correct plinth dimension and level 2 Flange dimension comply to Appendix 3.1 (Specification) 3 Correct J-bolt installed 4 Correct valve level 5 Correct vertically, horizontality and orientation (flow direction) 6 Correct bolts and gasket as flange joint 7 Correct bolt tightening torque 8 Correct alignment of extendd spindle 9 Headstock and/or actuator installed 10 Grouting at plinth 11 All damaged surface make good Inspected by : No Signature : Remarks by Engineer Date: (Name) Remarks by Engineer : The Contractor is : NOT ALLOWED to proceed with the works. ALLOWED Nonconformance raised during inspection /re-inspection? Inspected by : Signature : YES NO NCR No.: Date: (Name) Please √ off w here appropriate 75 SPAN TS 1402:2016 Standard STP - Extended Aeration (EA) Inspection Guide Installation of Submersible Equipment (e.g VERTICAL MIXERS / SLUDGE MIXERS / SUBMERSIBLE PUMPS) Location : Designation : Checklist No. Item Yes Description 1 Correct level (tank/sump….etc) 2 Approved submerged part material 3 Correct alignment of guide rail (sub. pump) 4 Drive unit secured to position 5 Correct alignment of rotatiing shaft (ver. mixer) 6 Lifting equipment installed (i.e slewing jib, hoisting chain) 7 _________________________________________________ 8 _________________________________________________ 9 _________________________________________________ 10 _________________________________________________ Inspected by : No Signature : Remarks by Engineer Date: (Name) Remarks by Engineer : The Contractor is : NOT ALLOWED to proceed with the works. ALLOWED Nonconformance raised during inspection /re-inspection? Inspected by : Signature : YES NO NCR No.: Date: (Name) Please √ off w here appropriate 76 SPAN TS 1402:2016 Standard STP - Extended Aeration (EA) Inspection Guide Cast In-Situ Reinforced Concrete Concreting Location : Designation : Item Checklist No. ____________________________ Description Yes No Remarks by Engineer 1 Approved pipe material & size : ______________ 2 Piping layout, level and alignment as per approved drawing 3 All valves, fittings and etc in order 4 Correct piping jointing 5 Approved pipe support and brackets 6 Approves surface coating at site : __________________ 7 _________________________________________________ 8 _________________________________________________ 9 _________________________________________________ 10 _________________________________________________ Inspected by : Signature : Date: (Name) Remarks by Engineer : The Contractor is : ALLOWED NOT ALLOWED to proceed with the works. Non-conformance raised during inspection / re-inspection? Inspected by : Signature : YES NCR No.: NO Date: (Name) Please √ off w here appropriate 77 SPAN TS 1402:2016 Standard STP - Extended Aeration (EA) Inspection Checklist Pump Performance Test Location : Designation : Checklist No. : ___________________________ Pump Make/ Model :_______________________________ Pump Serial No : _________________________________ Motor Rating : ____________________kW, Voltage : ________________ Motor Make/ Model :_______________________________ Motor Serial No : _________________________________ Pumpset No : ___________________________________ Specified Pump Duty : Flow : ______________________ Total head : ___________________ Speed : ______________________ Suction pipe diameter : _______________________ Discharge pipe diameter : ________________________ Suction gauge elevation above pump C/L suction : ____________________ Discharge : __________________ No Description 1 2 3 4 5 6 7 8 9 10 11 12 Flowrate ( ) Delivery Head (m) Suction Head (m) Current (A) Voltage (V) Motor Input power (kW) 1 2 3 4 Valve fully closed Duty Point 1 Duty Point 2 Duty Point 3 5 6 Intermediate Valve fully Point open Test date : _______________ Time start : ____________ Recorded by : _______________ (Contractor) Name : _______________________ Inspected by : _______________ (Consultant) Name : _______________________ Witnessed by : _______________ (Employer) Name : _______________________ Remarks Time finish : _____________________ Please √ off w here appropriate 78 SPAN TS 1402:2016 Standard STP - Extended Aeration (EA) Inspection Guide Inspection of Lifting Equipment (OVERHEAD CRANE / PORTAL CRANE / MONORAIL / SLEWING JIB) Location : Designation : Checklist No. ____________________________ Description Item Yes No Remarks by Engineer 1 Approved beam/girader launching method 2 Correct level of corbel ; with shim if necessary (overhead crane) / floor (portal crane or slewing jib) / beam (monorail) 3 Correct plates, beam and girder dimension 4 Correct span of runway 5 Correct anchor bolts size and spacing 6 Grouting of anchor bolt pocket 7 Runway beam / jib standard bolted to structure 8 Tie member bolted to column & welded to runway beam overhead crane 9 All members bolted correctly (portal crane) 10 Stooper plate installed 11 All damage surface make good 12 End carriage / hoist / electrical festoon installed 13 Saftey feature & sinage installed (buzzer, etc.) Inspected by : Signature : Date: (Name) Remarks by Engineer : The Contractor is : ALLOWED NOT ALLOWED to proceed with the works. Non-conformance raised during inspection / re-inspection? Inspected by : Signature : YES NCR No.: NO Date: (Name) Please √ off w here appropriate 79 SPAN TS 1402:2016 Standard STP - Extended Aeration (EA) Inspection Guide Inspection of Ventilation Fan Location : Designation : Checklist No. ____________________________ Description Item Yes No Remarks by Engineer 1 Correct opening size 2 Correct fan type, make, capacity and spec. 3 Correct fan orientation 4 Correct fan level and alighment 5 Fan assembly bolted correctly to wall / plinth 6 Correct duct size 7 Correct duct alighment 8 Sufficient fan and duct support 9 Duct insulated (for pump motor exhaust) 10 Opening gap sealed 11 Grouting of pllnth 12 All damage surface make good Inspected by : Signature : Date: (Name) Remarks by Engineer : The Contractor is : ALLOWED NOT ALLOWED to proceed with the works. Non-conformance raised during inspection / re-inspection? Inspected by : Signature : YES NCR No.: NO Date: (Name) Please √ off w here appropriate 80 SPAN TS 1402:2016 Standard STP - Extended Aeration (EA) Inspection Guide Installation of Equipment on Plinth Location : Designation : Checklist No. ____________________________ Description Item Yes No Remarks by Engineer 1 Approved type, make, model and capacity 2 Correct plinth dimensions 3 Assembly in order 4 Correct level (skims if necessary) 5 Correct alighment and orientation (flow) 6 Correct bolt type, size and tightening 7 Grouting of plinth (if necessary) 8 Auxilary piping and fixing installed 9 ____________________________________ 10 ____________________________________ Inspected by : Signature : Date: (Name) Remarks by Engineer : The Contractor is : ALLOWED NOT ALLOWED to proceed with the works. Non-conformance raised during inspection / re-inspection? Inspected by : Signature : YES NCR No.: NO Date: (Name) Please √ off w here appropriate 81 SPAN TS 1402:2016 Guidance on List of Defects (not limited to) 82 SPAN TS 1402:2016 ITEM DEFECTS TYPE OF DEFECTS CATEGORY OF DEFECTS A General 1 Clean Site compound Visual Minor 2 Clean perimeter drain Visual Minor 3 Clean inner channel Visual Minor 4 Clean inspection/valve chambers Visual Minor 5 Clean debris from site Visual Minor 6 Soil settlement at site Civil Major 7 Site flooded Civil Major 8 Premix to internal road Maintenance Minor 9 Provide internal drains Maintenance Minor 10 Repair perimeter drain Maintenance Minor 11 Repair Fencing Maintenance Minor 12 Repair kerbs Maintenance Minor 13 Repair fencing posts/gates Maintenance Minor 14 Replace RC slab/grating cover Material Minor 15 Penstock not installed Equipment Major 16 Penstock leaking Equipment Minor 17 Tank leaking Structural Major 18 Repair RC crack to structures Structural Major 19 Provide hand railing Minor 20 Paint hand railing yellow Safety Visual 21 Re-paint hand railing Visual Minor 22 Paint RC walls Visual Minor 23 Provide grating for opening Screening plants surrounding fencing Safety Visual Minor 24 25 Trim grass up to 5 ft outside fencing Visual Minor 26 Landscaping Visual Minor 27 Provide warning signboard Safety Minor 28 Provide water supply Maintenance Minor 29 Provide toilet facility with wash basin Operation Minor 30 Provide stop log Equipment Minor 31 Rectify effluent channel Civil Minor Minor Minor 32 Access road to STP Access Major 33 Stainless steel nuts & bolts Material Minor B Screen & Chambers 1 Lifting chain for basket screen to be SS Operation Minor 2 Electric chain hoist for basket screen Operation Minor 3 Guide rails for basket screen Operation Minor 4 Working platform for static screen Access Minor 83 SPAN TS 1402:2016 ITEM DEFECTS TYPE OF DEFECTS CATEGORY OF DEFECTS B Screen & Chambers (continued) 5 Platform for mechanical screen Access Minor 6 Clear access to stairway etc Access Minor 7 Provide perforated screenings bin Equipment Minor 8 Relocate electrical cable for screen Maintenance Minor 9 Bar screen to be removable Maintenance Minor 10 Clean screen chamber Maintenance Minor C Pump Station 1 Cracked wall Structural Major 2 Provide SS guide rails Material Minor 3 Provide SS lifting chain Material Minor 4 Clear pump sump Maintenance Minor 5 Provide overflow pipe Operation Minor 6 Leaking gate valve Equipment Safety Minor 7 Provide hand railing around pump sump 8 Grating for pump opening 9 Minor Safety Minor Label all pumps Operation Minor 10 Noisy pump –vibrating Equipment Major 11 Adjust level regulator-floats Operation Minor 12 Isolation switch for pumps Safety Major 13 Re-install guide rails Maintenance Minor D Pipework & fittings Minor 1 Repair pipe leaks Pipe/fitting 2 Label pipes with flow direction Operation Minor 3 Noisy check valve Pipe/fitting Minor Maintenance Minor Minor 4 Provide valve chamber 5 Provide extension spindle for gate valve 6 Provide valves for diffuser pipes Operation Pipe/fitting 7 Valve leaking Pipe/fitting Minor 8 Force main to be properly secured Maintenance Minor 9 Replace GI pipes with DI 10 Relocate pipe works Minor Material Minor Maintenance Minor 11 Paint pipe work to colour codes Operation Minor 12 Incorrect pipe size Pipe/fitting Major E Grit Removal 1 Provide grating 2 Provide collection bin Safety Minor Equipment Minor 3 Filtrate return to sump Operation Minor 4 Provide stop log for distribution channel Equipment Minor 84 SPAN TS 1402:2016 ITEM DEFECTS E Grit Removal (continued) 5 Provide access ramp and platform 6 Leaking sand classifier F Oil & Grease Removal TYPE OF DEFECTS CATEGORY OF DEFECTS Access Minor Equipment Minor 1 Provide access platform Access Minor 2 Provide hand railing Safety Minor 3 Provide baffles Operation Minor 4 Skimmer pipe to be non-corrosive Material Minor 5 Paint belting cover Maintenance Minor G Mechanical 1 Screen conveyor overload Blower motor burnt Electrical Equipment Major 2 3 Noisy check valve Equipment Minor Major 4 To provide spare parts Maintenance Minor 5 Label all equipment Maintenance Minor 6 Set equipment working on timer Grease all bearings & chains Operation Maintenance Minor 7 8 Install all equipment 1 m from wall Maintenance Minor 9 Ventilation system in dry well/chamber malfunction Safety Major H Electrical Minor 1 Rectify timer Electrical Minor 2 Repaint switchboard panel Electrical Minor 3 Check efficiency of capacitor Electrical Minor 4 Beacon light not functioning Electrical Minor 5 Re-calibrate current overload Electrical Minor 6 Provide rubber mat at control room Safety Minor 7 Replace non-functioning indicator lights Electrical Minor Equipment Major 8 Aerator trip 9 Replace capacitor/contactor Electrical Minor 10 Provide individual isolator switch Electrical Major 11 Repair junction box Electrical Major 12 Exposed electric cable Electrical Major Minor 13 Replace PVC conduits with GI Electrical 14 Incoming cable sizing not correct for amps Electrical Major 15 Replace single MCB with 3-phase Electrical Major 16 Provide spot light for wet well Electrical Minor 17 Junction box to complete with isolator Electrical Minor Minor 18 Provide 3-pin outlet socket Maintenance 19 Calibrate earth fault relay Electrical Major 20 Replace malfunctioned light fittings Maintenance Minor 85 SPAN TS 1402:2016 ITEM DEFECTS TYPE OF DEFECTS CATEGORY OF DEFECTS H Electrical (continued) 21 Ammeter non functioning Electrical Minor 22 Hour-meter non functioning Electrical Minor 23 Replace auto-trans for pump Electrical Major 24 Check incoming cable to MCCB Electrical Minor 25 Switchboard to comply to specs Electrical Minor 26 Indicate MCB rating for mechanical screen Electrical Minor 27 Indicate MCB rating for belt press Electrical Minor 28 Provide compound light Electrical Minor 29 Relocate junction box Electrical Minor 30 Cover bus-bar Safety Major 31 Junction box to be weather proof Electrical Minor 32 Sand fill & concrete cover for incoming trench Electrical Major 33 Outdoor cable tray to be GI Material Minor 34 Replace damaged cable trunk Electrical Major 35 Replace power factor regulator Electrical Major 36 Replace malfunctioned starter Electrical Major 37 Carry out impedance test Electrical Minor 38 Provide earthing chamber Safety Minor 39 Provide fire extinguisher Safety Minor 40 Provide electrical line diagram Electrical Minor 41 Provide first aid kit Safety Minor Safety Minor I Blower Room 1 Provide sound proofing 2 Provide ventilation Safety Minor 3 Provide acoustic doors Safety Minor 4 Provide silencer for blowers Safety Major Pipe/fitting Minor Safety Minor Major 5 Replace piping & check valve 6 Carry out sound test 7 Oil leakage at pressure gauge Maintenance 8 Nuts & bolts for blower frame Material Minor 9 Repair cracks in blower room walls Structural Major 10 Blower not functioning 11 Provide lifting device for blower 12 Blower undersized 13 Provide cover for belt drive Equipment Major Maintenance Minor Equipment Major Safety Minor Equipment Major J Aeration Tank 1 Noisy aerator 2 De-silt tank Maintenance Minor 3 Structural cracks Structural Major 4 Aerator malfunction Equipment Major 86 SPAN TS 1402:2016 ITEM DEFECTS TYPE OF DEFECTS CATEGORY OF DEFECTS J Aeration Tank (continued) 5 Diffuser imbalances air Pipe/fitting Minor 6 Surface aerator vibrating Equipment Major 7 Access to aeration tank Access Minor 8 Replace slabs with grating at openings Material Minor 9 Metal stairway corroded Access Minor Operation Minor Access Minor Operation Minor 10 Adjust surface aerator submergence 11 Access to discharge channels K Secondary Clarifier 1 Scum skimmer adjustment 2 Repaint sludge scraper bridge General Minor 3 Adjust level of scum box Operation Minor 4 Adjust overflow weir plate Operation Minor 5 Access to bridge Access Minor 6 Clean launder Maintenance Minor 7 Clear rubbish from scum box Maintenance Minor 8 Provide safety grating for opening Safety Minor 9 Skimmer pipe leaking Pipe/fitting Minor 10 Hand railing for bridge Safety Minor 11 Noisy motor Equipment Major 12 Provide water tap for maintenance Maintenance Major 13 RAS pump malfunction Maintenance Major 14 Check for equal distribution Operation Major 15 Provide access for sludge collection chamber Access Minor 16 Clarifier scraper malfunction Equipment Major 17 Clarifier tank leaking Structural Major L Lifting Devices 1 Provide 1 ton chain block Maintenance Major 2 Provide lifting davit Maintenance Minor 3 Adjust height/location I-beam Maintenance Minor 4 Safe working load for I-beam to comply to DOSH Safety Major 5 SWL painted on davit Safety Minor 6 Electrically operated lifting device Maintenance Minor 7 Lifting chain to be stainless steel Maintenance Minor M Flow Measurement 1 Calibrate flow measurement equipment Maintenance Minor 2 Hard-standing / concrete working area Maintenance Minor 3 Test & certify flow recorder Maintenance Minor 4 Hand railing for parshall flume Safety Minor 5 Flow meter device not provided Instrument Minor 87 SPAN TS 1402:2016 ITEM N DEFECTS TYPE OF DEFECTS CATEGORY OF DEFECTS Holding Tank 1 Provide desludging pipe Operation Minor 2 Provide overflow pipe to inlet Operation Minor 3 Repair desludging pipe Pipe/fitting Minor 4 Provide stairway and extended platform Access Minor 5 Provide cover for opening Safety Minor 6 Provide SHT mixer Equipment Major 88 SPAN TS 1402:2016 ANNEX D: MASS BALANCE AND HYDRAULIC PROFILE 89 SPAN TS 1402:2016 HYDRAULIC PROFILE 18 16 Top Water Level (m) 14 12 10 8 EXAMPLE 6 4 2 0 Inlet Chamber Primary Screen Chamber Pump Sump Secondary Screen Chamber Grit Chamber Grease Chamber Anoxic Tank Aeration Tank Clarifier Tank Chlorination Sludge Chamber Holding Tank Process Unit Top Water Level (TWL) m Signature & Endorsement: Ground Level Company Stamp: 90 SPAN TS 1402:2016 EXAMPLE Signature & Endorsement: Company Stamp: 91 SPAN TS 1402:2016 ANNEX E: PROCESS DESIGN CALCULATION