S803C-K25
Extended Product Type:
Product ID:
EAN:
Catalog Description:
Long Description:
S803C-K25
2CCS883001R0517
7612271212865
S803C-K25 High Performance Circuit Breaker
The S803C-K25 is a 3-pole High Performance Circuit breaker with K-Characteristic, with cage terminal and a rated current of 25 A. It is a current limiting device with a maximum breaking capacity of 25kA at 240/415V. It can be used for voltages up to 254/440V and in
DC as well. It has two different tripping mechanisms, the thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection.
The S803C-K25 complies with IEC/EN 60898-1 and IEC/EN 60947-2 and allows the use for residential, commercial and industrial applications. It has numerous of approvals, therefore it can be used worldwide. The extensive range of accessory makes the use of S803C-K25 more comfortable. Due to the fast arc extinction of S803C-K25 your application will be secured.
Products » Low Voltage Products and Systems » Modular DIN Rail Products » High Performance Circuit Breakers HPCBs
Minimum Order Quantity:
Customs Tariff Number:
EAN:
1 piece
85362020
7612271212865
Product Net Depth:
Product Net Height:
Product Net Weight:
Product Net Width:
Package Level 1 Width:
Package Level 1 Length:
Package Level 1 Height:
Package Level 1 Gross Weight:
Package Level 1 EAN:
Package Level 1 Units:
82.5 mm
95 mm
0.74 kg
81 mm
105 mm
86 mm
99 mm
0.77 kg
7612271212865
1 piece
Ambient Air Temperature:
Resistance to Shock acc. to IEC
60068-2-27:
Resistance to Vibrations acc. to IEC
60068-2-6:
Environmental Conditions:
RoHS Status:
Operation -25 ... +60 °C
Storage -40 ... +70 °C
5 g
30 ms
2 - 13.2 Hz / 1mm
13.2 - 100Hz / 0.7g
with load 100% x Ie
Damp Heat Cyclic acc. to IEC 60068-2-30 12+12 cycle
Damp Heat Cyclic acc. to IEC 60068-2-30 55°C @ 90-96%
Damp Heat Cyclic acc. to IEC 60068-2-30 25°C @ 90-100%
Dry Heat Test B acc. to IEC 60068-2-2 16 hour @ 55 °C
Dry Heat Test B acc. to IEC 60068-2-2 2 hour @ 70 °C
Following EU Directive 2002/95/EC August 18, 2005 and amendment
Number of Poles:
Tripping Characteristic:
Rated Current (I n
):
Rated Operational Voltage:
Power Loss:
Rated Insulation Voltage (U i
):
Operational Voltage:
Rated Frequency (f):
Rated Ultimate Short-Circuit
Breaking Capacity (I cu
):
3
K
25 A
254/440 V at Rated Operating Conditions per Pole 4.3 W
500 V AC
Maximum 230/400 V AC
Minimum 12 V AC
50 / 60 Hz
(240 / 415 V AC) 25 kA
(254 / 440 V AC) 15 kA
Rated Service Short-Circuit
Breaking Capacity (I cs
):
Energy Limiting Class:
Overvoltage Category:
Pollution Degree:
Rated Impulse Withstand Voltage
(U imp
):
Housing Material:
Contact Position Indication:
Degree of Protection:
Remarks:
Electrical Endurance:
Mechanical Endurance:
Terminal Type:
Connecting Capacity:
Tightening Torque:
Recommended Screw Driver:
Mounting on DIN Rail:
Mounting Position:
Standards:
(125 V DC) 10 kA
(240 / 415 V AC) 18 kA
(254 / 440 V AC) 10 kA
(125 V DC) 10 kA
3
IV
3
8 kV
Insulation group I, RAL 7035
ON / OFF / TRIP acc. to IEC 60529 IP20
Connection from top and bottom
Connecting with CU only
IP40 in enclosure with cover
Cage terminal with captive screw
10000 cycle
10000 cycle
Screw Terminals
Stranded 1 ... 50 mm²
Flexible 1 …70 mm²
3.5 N·m
31 in·lb
Pozidriv 2
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Any
IEC/EN 60947-2 IEC/EN 60898-1
Instructions and Manuals:
Data Sheet, Technical Information:
Declaration of Conformity - CE:
RoHS Information:
2CCC413016M0004
2CCC413003C0203
2CCC413016D060
2CCC413008D0204
ETIM 4:
ETIM 5:
ETIM 6:
Object Classification Code:
EC000042 - Miniature circuit breaker (MCB)
EC000042 - Miniature circuit breaker (MCB)
EC000042 - Miniature circuit breaker (MCB)