High Speed Fuses Ferrule — FWP 690V/700V (IEC/UL): 1-50A, Striker Optional FWP (14 x 51mm) Arc Voltage Specifications Description: Ferrule style high speed fuses with and without indicating striker. Dimensions: See dimensions illustrations. Ratings: Volts: — 690Vac (IEC) — 700Vac (UL) FWP with — 800Vdc (5-50A) striker option. Amps: — 1-50A IR: — 200kA RMS Sym. — 50kA @800Vdc Agency Information: CE, UL Recognition JFHR2.E91958, CSA Component Acceptance file Class 1422-30, 1422-90 (53787) for versions without indicator only. Designed and tested to IEC 60269: Part 4. Electrical Characteristics Total Clearing I2t 1.4 1.2 1.0 0.9 0.8 0.7 0.6 The total clearing I2t at rated voltage and at power factor of 15% are given in 0.5 the electrical 1) characteristics. For other 0.4 2) voltages, the clearing I2t is 0.3 found by multiplying by 200 correction factor, K, given as a function of applied working voltage, Eg, (rms). 1.4 1.2 103 9 8 7 6 Power Losses 3 Catalog Numbers 300 400 500 1) 5-30A Range 2) 32-50A Range 600 Eg 700 Without Striker 50.8 (2.000") 14.3 (0.563") 15.5 (0.610") With Striker 5 (0.197") Size 51 (2.00") 13 (0.511") • • • • 4 200 1.0 Kp 0.8 300 400 500 600 Eg 700 0.6 0.5 0.4 0.3 0.2 Ib 0.1 30 40 50 60 70 80 90 100% Electrical Characteristics Rated I2t (A2 Sec) Current Minimum Clearing At Watts RMS-Amps Melting Rated Voltage Loss 14 x 51mm (9⁄16" x 2") 14 x 51mm (9⁄16” x 2”) *Striker range is 600Vdc only • Watts loss provided at rated current. • See accessories on page 243. 59 (2.323") 14.3 (0.563") Catalog Numbers Without Striker FWP-1A14F FWP-2A14F FWP-2.5A14F FWP-3A14F FWP-4A14F FWP-5A14F FWP-10A14F FWP-15A14F FWP-20A14F FWP-25A14F FWP-30A14F FWP-32A14F FWP-40A14F FWP-50A14F With Striker* FWP-10A14FI FWP-15A14FI FWP-20A14FI FWP-25A14FI FWP-30A14FI FWP-32A14FI FWP-40A14FI FWP-50A14FI UL 5 Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current. K Dimensions - mm (in) 234 This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of theapplied working voltage, Eg, (rms) at a power factor of 15%. 1 2 2.5 3 4 5 10 15 20 25 30 32 40 50 10 15 20 25 30 32 40 50 — — — — — 1.6 3.6 8.6 26.0 46.5 58 68 84 200 3.6 8.6 26.0 46.5 58 68 84 200 — — — — — 11.0 38.5 70 230 375 485 600 750 1800 38.5 70 230 375 485 600 750 1800 Features and Benefits Excellent cycling capability and DC performance Low arc voltage and low energy let-through (I2t) Low watts loss in a compact size Used with finger-safe holders/blocks Data Sheet: 720025 For product data sheets, visit www.cooperbussmann.com/DatasheetsEle — — — — — 1.5 4 5.5 6 7 9 7.6 8 9 4 5.5 6 7 9 7.6 8 9 High Speed Fuses Ferrule — FWP 690V/700V (IEC/UL): 1-50A, Striker Optional Without Striker FWP 5-50A: 660V/700V (14 x 51mm) Time-Current Curve 104 6 4 2 103 6 4 2 Virtual Pre-Arcing Time In Seconds 102 FWP-25A14F FWP-30A14F FWP-32A14F FWP-40A14F FWP-50A14F 6 4 2 101 6 4 2 100 10–1 6 4 FWP-5A14F FWP-10A14F FWP-15A14F FWP-20A14F 2 6 4 2 10–2 6 4 2 10–3 6 4 2 10–4 2 4 6 8 2 101 4 6 8 2 102 4 6 8 103 High Speed Fuses Prospective Current In Amps RMS Peak Let-Through Curve 104 FWP-50A14F FWP-40A14F FWP-32A14F FWP-30A14F FWP-25A14F 6 4 2 Peak Let-Through Current 103 6 4 2 FWP-20A14F FWP-15A14F FWP-10A14F FWP-5A14F 102 6 4 2 101 101 2 4 6 102 2 4 6 103 2 4 6 104 Prospective Short-Circuit Current Symmetrical RMS 2 4 6 105 2 Data Sheet: 35785307 For product data sheets, visit www.cooperbussmann.com/DatasheetsEle 235 Bussmann ® Ferrule FWP 660V/700V (IEC/U.L.) Size Electrical Characteristics I2t (A2S) Rated Current Clearing RMS-Amps Pre-arc at 660V 1-50A ® Ordering Information 1 — — 2 — — 3 — — 4 — — 5 1.6 11 6 — — 14 ≈ 51mm 10 3.6 22 (·Ω¡§∑) 15 10 75 20 26 180 25 44 320 30 58 450 32 68 600 40 84 750 50 200 1800 n Interrupting rating 200kA RMS Symmetrical. n Watts loss provided at rated current. n (700 Vdc/Interrupting rating 50kA) U.L. Recognition. n CSA Component Acceptance: 5 - 30A. Watts Loss Part Number Carton Qty. Carton Weight (kg) — — — — 1.5 — 4 5.5 6 7 9 7.6 8 9 FWP-1A14F FWP-2A14F FWP-3A14F FWP-4A14F FWP-5A14F FWP-6A14F FWP-10A14F FWP-15A14F FWP-20A14F FWP-25A14F FWP-30A14F FWP-32A14F FWP-40A14F FWP-50A14F 10 0.225 Dimensions Curves Figure Number BIF # Fig. 1 35785307 1 kg = 2.2 lbs. 1 lb = 0.45 kg R Dimensions Fig. 1: 1-50 Amp Range 50.8 (2.000") 14.3 (0.563") 15.5 (0.610") Dimension in mm. 1mm = 0.0394∑ 1∑ = 25.4mm Electrical Characteristics Total Clearing I2t The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K , given as a function of applied working voltage, E g , (RMS). 1.4 1.2 1.0 0.9 0.8 0.7 0.6 0.5 0.4 1.4 1.2 103 9 8 7 6 K Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current . The correction factor, K p , is given as a function of the RMS load current, Ib , in % of the rated current . 1.0 Kp 0.8 UL 0.6 0.5 0.4 0.3 5 1) 0.2 4 2) 0.3 200 Arc Voltage This curve gives the peak arc voltage, U L , which may appear across the fuse during its operation as a function of the applied working voltage, E g , (RMS) at a power factor of 15%. Eg Eg 3 300 400 500 600 700 200 300 400 500 600 700 0.1 30 40 50 Ib 60 70 80 90 100% 1) 5-30 Amp Range 2) 32-50 Amp Range 7-18-01 SB01191 The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. Form No. Page 1 of 1 BIF Doc #720025 BIF Document Semiconductor Fuse 1-50A, 700 Volts 35785307 Size 14≈51 104 6 4 2 103 6 4 2 FWP-25A14F FWP-30A14F FWP-32A14F FWP-40A14F FWP-50A14F 2 10 Virtual Pre-Arcing Time In Seconds 6 4 2 101 6 4 2 100 6 4 FWP-5A14F FWP-10A14F FWP-15A14F FWP-20A14F 2 10–1 6 4 2 10–2 6 4 2 10–3 6 4 2 10–4 2 4 6 8 101 2 4 6 8 102 2 4 6 8 103 Prospective Current In Amperes RMS Pre-Arcing Time-Current Characteristic Curves FWP 1A14F-50A14F 1-17-01 SB00233 BUSSMANN P.O. Box 14460 St. Louis, MO 63178-4460 U.S.A. Phone: 636-394-2877 Fax: 800-544-2570 Int’l Fax: 636-527-1413 Approved: NN Rev. Date: SEPT-97 BUSSMANN U.K. Burton-on-the-Wolds Leicestershire LE12 5TH England Phone: 44-1509-882737 Fax: 44-1509-882786 Page Pub. Date: BUSSMANN DENMARK 5 Literbuen DK-2740 Skovlunde Copenhagen, Denmark Phone: 45-4485-0900 Fax: 45-4485-0901 Bussmann reserves the right without notice to change design and/or discontinue distribution of this product. 1 of 2 JAN-98 BIF Document Semiconductor Fuse 1-50A, 700 Volts 357815307 Size 14≈51 104 FWP-50A14F FWP-40A14F FWP-32A14F FWP-30A14F FWP-25A14F 6 4 Peak Let-Through Current 2 103 6 4 2 FWP-20A14F FWP-15A14F FWP-10A14F FWP-5A14F 2 10 6 4 2 101 101 2 4 6 102 2 4 6 103 2 4 6 104 2 4 6 105 2 Prospective Short-Circuit Current Symmetrical RMS Peak Let-Through Cut-Off Current Characteristic Curves FWP 1A14F-50A14F 1-17-01 SB00233 Approved: NN Rev. Date: SEPT-97 Page Pub. Date: 2 of 2 JAN-98 The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this BIF document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.