connection energy management CDS load-shedding contactor function CDS When consumption exceeds the selected threshold, the load-shedding contactor temporarily stops supply to non-essential circuits. description technical data common to the CDS c ratings: v essential circuit: 90 A v non-essential circuits: - 15 A contact relay (100 000 operations) for resistive loads without current inrush on energisation - in all other cases, relaying by CT contactor is required c frequency: 50…60 Hz c load-shedding indication by yellow LEDs c power consumption: 12 VA c connection by tunnel terminals (captive screws): v essential circuit: 4 to 50 mm2 v non-essential circuits: 2.5 to 10 mm2 c fixing on symmetrical rail or panel c control of currents greater than 90 A: v utilisation of an In/5 current transformer v threshold setting: 5 A c utilisation temperature: -5...+55 °C c complies with standards: v NFC 61.750 v EN 500 81.1 v EN 500 81.2 The CDS: c increases the number of loads without changing output power, c reduces output power, c prevents nuisance tripping of the upstream circuit-breaker. specific technical data CDS c single-phase version: v load-shedding and restoration in cascading configuration of 2 non-essential circuits by 2 relays with time-delayed action v load-shedding time: - load shedding of circuit 1 only: • restoration after 5 min - load shedding of circuit 1 and circuit 2: • restoration of circuit 2: after 10 min • restoration of circuit 1: 5 min after circuit 2 c three-phase version: v separate load-shedding for each phase v 1 relay per phase v load-shedding time: 5 min for each channel c load-shedding override input c 1 A - 250 V NO contact for remote indication CDSc c load-shedding and restoration in cascading configuration, then in turn by rotation of 1 to 4 non-essential circuits c load-shedding override input c cyclic load-shedding: changing the order every 5 min CDSt c specially adapted for peak period tariff reduction systems c load shedding and restoration in cascading configuration of 2 non-essential circuits c 2 load-shedding thresholds according to the tariff period c "ON" override by pushbutton c indication of tariff condition status catalogue numbers type threshold (A) supply voltage (V AC) catalogue number width in mod. of 9 mm 230 15908 10 CDS 1P 5/10/15/20/25/30 40/45/50/60/75/90 aux 1 L1 aux 2 1 7 15908 92053/2 2 3 8 4 5 6 9 10 11 12 N Merlin Gerin connection energy management CDS load-shedding contactor catalogue numbers type threshold (A) supply voltage (V AC) catalogue number width in mod. of 9 mm 230 15913 16 15906 16 15912 16 CDS (continued) 3P 5/10/15/20/25/30 40/50/60/70/80/90 aux 1 aux 2 L2 L3 L1 1 15913 2 9 3 4 5 6 7 8 10 11 12 13 14 15 aux 3 16 N CDSc 1P 5/10/15/20/25/30 40/45/50/60/75/90 230 L 1 2 3 4 IS 9 10 5 6 7 8 12 13 14 15 I I III IV IS 11 N essential 16 non-essential CDSt 1P 5/10/15/20/25/30 40/45/50/60/75/90 230 EJP PCA 2 2 L 2 4 5 6 7 8 11 12 13 14 15 16 IS 15912 9 N 10 essential I II non-essential additional information Merlin Gerin dimensions: page 90148/2 92053/3