Fuse switch-disconnectors, fuse disconnectors and fuse holders for cylindrical fuse-links Varius SUMMARY OF MODELS OPVP10 OPVP14 OPVP22 OPT22/OPT20 OPVF10 Rated operating current Ie 32 A 63 A 125 A 63 A 30 A Rated operating voltage Ue AC 690 V AC 690 V AC 690 V AC 1 500 V DC 440 V DC 440 V DC 440 V DC 1 000 V DC 1 000 V 10x38 14x51 22x58 22x127, 20x127 10x38 Utilization category of fuse link gG, aM, gR, aR gG, aM, gR, aR gG, aM, gR, aR gR/gS, gR, aR gR, gPV Utilization category at AC 400 V AC-21B AC-21B AC-21B - - Utilization category at AC 1 500 V - - - AC-20B - Utilization category at DC 250 V DC-21B DC-21B DC-21B - - Utilization category at DC 1 000 V - - - DC-20B DC-20B S1L-..., S2L-..., S3... S3L-... CS-OPV22-... - - Type Fuse-link size Accessories Interconnecting busbars Terminal extension AS-... CS-FH000-.. - - Adapter for busbar system with spacing 60 mm GA-... - - - - - Remote signalling of fuse-link state B2 MD-M3 Fuse switch-disconnectors, fuse disconnectors and fuse holders for cylindrical fuse-links Varius SUMMARY OF MODELS Description Connection block Enables power supply of interconnecting busbars by conductors of cross-section up to 35 mm2. The blocks can be assembled in series to create a multi-pole connection unit. Degree of protection IP20. End caps For covering the ends of interconnecting busbars. Outlet cover It enables isolation of unused outlets of interconnecting busbars. For covering five unused outlets. Interconnecting busbar Terminal extension Accessory for switch-disconnector OPVP22-3... For connection of Cu/Al conductor of cross-section 35 ÷ 95 mm2. Possibility of connection of two stranded conductors up to 25 mm2. For interconnection of 1- to 3-pole fuse switch-disconnectors. Adapter for busbar system Busbar spacing 60 mm. Busbar thickness 5 or 10 mm. Busbar width 12 ÷ 30 mm. Cable outlet bottom. Max. current 63 A. Accessory for switch-disconnector OPVP10 and OPVP14. For connection of Cu conductor. Cross-section of Cu conductor 6 ÷ 50 mm2. Accessory for switch-disconnector OPVP14. For connection of Al or Cu conductor. Cross-section of Cu/Al conductor 2.5 ÷ 50 mm2. B3 Varius Fuse switch-disconnectors, fuse disconnectors and fuse holders for cylindrical fuse-links OPT FUSE DISCONNECTORS OPT Fuse disconnectors are intended for cylindrical Delivered with P-terminal, it can be removed, and the fuse- links PT22. For the circuits of photovoltaic systems, trolleybuses and trams. Hole in the cover for check of fuse amperage. fuse disconnector can be connected by cable lugs and screws M8. Fixed to the panel by screws M6. Fuse disconnector In [A] Type Order code OEZ:08474 OEZ:08344 OEZ:08700 OEZ:08345 OEZ:34403 OPT22/1 OPT22/2 OPT22/3 OPT22/4 OPT20 63 Number of poles Weight [kg] 0.48 0.96 1.44 1.92 0.48 1 2 3 4 1 Package [pcs] 4 2 1 1 1 Specifications Type OPT22, OPT20 Standards IEC 60947-1 IEC 60947-3 EN 602947-1 EN 602947-3 Approval marks Rated operating current Rated operating voltage Utilization category 63 A AC 1 500 V / DC 1 000 V AC-20B DC-20B 22x127, 20x127 15 W Ie Ue Fuse-link size Max. power losses of the fuse-link Connection Connection cross-section diameter x length Pv Torque Operating conditions Mechanical endurance Degree of protection, cover closed Operating ambient temperature Max. sea level Cu Al 1 ÷ 50 mm2 solid 2.5 ÷ 50 mm2 3.5 ÷ 4 Nm operating cycles 2 200 IP20 -25 ÷ +55 °C 2 000 m Dimensions 96 76 186 5 A 102 A [mm] Type 1pól 40 40 OPT22 OPT20 2pól 80 - 3pól 120 - 4pól 160 - Diagram OPT2.-1 B12 OPT22-2 6.5 50 200 2x OPT22-3 OPT22-4 1 1 3 1 3 5 1 3 5 7 2 2 4 2 4 6 2 4 6 8