7 Theory of Personal Protective Grounding Section 7 www.hubbellpowersystems.com E-mail: hpsliterature@hps.hubbell.com Phone: 573-682-5521 Fax: 573-682-8714 210 North Allen Centralia, MO 65240, USA Copyright 2015 Hubbell Incorporated © Theory of Personal Protective Grounding Isolate/Insulate misleading as the contact points are not at equal voltage values as the name implies. The points are held to a preselected voltage difference by knowing the available current and calculating the maximum resistance of the connecting grounding cables. The only method of providing absolute protection to a worker is to completely eliminate any current path through the body. There are two ways of doing this. The first is to isolate the worker so that contact with an energized part cannot be made. While effective, this also eliminates the ability to work, so this often is not a viable method. This “equipotential zone” limits voltage across the body to a suitably low value to provide the required measure of safety. Again referring to Equation 2 (I = V / R), by estimating the body resistance and keeping the voltage below the safe level selected by the employer, the desired measure of safety can be achieved. The reduction in body voltage is achieved by limiting the maximum voltage that can be developed across the parallel circuit composed of both the body and the jumper. Information on the personal protective jumper is a known quantity. The jumper also will carry the largest amount of current compared to the body and can be used to develop the needed parallel voltage level. Again, it is the responsibility of each employer to specify a level of acceptable body voltage. At present, there are no standards that specify a value to be used. The second method uses suitably rated insulation to eliminate the body as a current path. This is the principle used when doing energized distribution voltage maintenance using rubber gloves. The gloves provide the insulation to eliminate the body as a current path. An alternate means is to completely cover all energized components with an insulating device to prevent any worker contact. While insulating products are available, they cannot be used in many of the maintenance tasks encountered by a lineman working aloft or by the ground man in support. Present insulating products are limited to distribution voltage applications. The key to a successful equipotential zone protection method is to place the worker in a parallel path with a conductor of sufficiently low resistance such that the rise in voltage is held at or below the selected level. The maximum jumper voltage is shown by Equation 2 (V = I X R). Shunting the fault current around the body, through the low resistance path, is the first key. Remember that some current will flow in every possible path, but it divides in inverse proportion to the path’s resistance. The use of a low resistance jumper is the major factor. The second key factor is to have the line protection equipment provide fast fault removal. Equipotential Protection A practical and more universal method is to provide a means of keeping the body extremities at the same or nearly the same voltage. If the difference in voltage across the body can be eliminated, the flow of current is eliminated, remembering Equation 2 (I = V / R). Without a difference in voltage there is no current flow. This is a theoretical solution that cannot be fully achieved in practice. If current flows through anything with resistance, a voltage drop will be developed. However, the principle of maintaining a sufficiently low level of voltage across the body is the basis for the development of an “equipotential zone.” The term is slightly 7-2 The use of the system neutral provides a low resistance path for the return of a fault current if it occurs. This does two things: It maximizes the fault current and tends to lower the voltage at the worksite. The maximum fault current ensures the fastest clearing possible of the fault by the system’s protective equipment, such as circuit breaker, reclosers, fuses, etc. The reduction in voltage occurs because the neutral conductor resistance is of a similar magnitude as the source conductor. The source and neutral conductors form a series circuit of two resistances, and a division of voltage results. Figure 7-1 illustrates this. The voltage at the worksite is reduced to that represented by the neutral resistance as a fraction of the total series circuit resistance (see Section 5 for a discussion of series resistances). I R1 IJ IM V1 V SOURCE VJ VM VN RN Voltage Division Using the Neutral Fig. 7-1 V1 is about equal to VN if they are about the same length and conductor size. The voltage of the conductor and neutral connections at the worksite will be about equal voltage because of the small voltage drop of the jumper, which we will discount. V1 =VN = VSOURCE x [RN / (R1 + RN)] but R1 = RN so V1 =VSOURCE x [RN / (RN + RN)] or V1 =VSOURCE x [RN / 2RN] or V1 =VSOURCE / 2 and =ISOURCE =(VSOURCE - (V1 – VN) [a very small difference] or VJ =VM IJ VJ The connection to overhead static or shield wires are of questionable benefit for use as a low resistance path for the return of fault current and should be evaluated before use. Many are not continuous to the power source, therefore, cannot be considered a full current return path. Most are steel conductor, which has a much higher resistance than a conductor designed to efficiently carry current. The higher resistance may become hot enough to fuse, depending upon the current level, resulting in its loss as a return path for protection if used alone. They may be used as a secondary current return path in addition to a primary return path as a means of increasing the margin of safety by providing multiple paths to and through the Earth. If the static or shield wire is included as part of the “work area” it should be electrically connected to the personal protective grounds at the worksite to extend the equipotential work zone. The use of the Earth alone represents a usable current return path for personal protective grounding. It has higher resistance than a conductor designed to carry current. This will lower the fault current because its resistance is greater than the conductive neutral, but possibly not to such a level that the system protective equipment would fail to recognize the fault. However, the resistance of the Earth varies widely. In areas of dry, sandy soil conditions the resistance may approach several hundred ohms. In a moist soil it may be in the low to mid teens. At the Hubbell Power Systems research laboratory, Centralia, MO, the Earth resistance approaches 18 Ohms. If the neutral is broken or fuses during a fault and it was the only return path to the source, worker protection could be lost. A current return path through the Earth could be used as a back-up path for the system neutral. The use of multiple jumpers and return paths is encouraged. Because this presentation is about accidents and avoiding accidents, a “belt and suspenders” approach may be prudent. 7-3