Surge Protection Device (SPD) for P1, P2, and P3 Lighting and Power Distribution Panelboards TPS 1(SAD or SAD/MOV) SAD or SAD/MOV Transient Protection System for Lighting and Appliance Panelboards: • P1 - Field Retrofit or Factory Install • P2 and P3 - Factory Install. Consult factory for Field Retrofit PANELBOARD FEATURES • Copper or aluminum bus • 200% rated panelboard neutral bus for harmonic-rich applications • Top or bottom feed • Flush or surface mounting panelboard trim • MB or MLO • Up to 42 circuit capacity • Standard panel trim package and can size APPLICATIONS • Provides main service entrance or downstream protection for sensitive computer and electronic loads: Standard SAD redundancy use Standard redundancy use Increased redundancy use Maximum redundancy use SPD SPECIFICATIONS 20kA 90kA 130kA 170kA • Protection: Silicon primary with MOV backup. Ensures lowest clamping voltage • Modes of Protection: SAD/MOV Hybrid: L-N, L-G, and N-G SAD Only: L-N • EMI/RFI filtering: Active tracking up to -50db from 100kHz to 100MHz • Less than 1/2 nanosecond response time • Pulse life of 5,000 Category C impulses • 200,000 AIR, surge rated fuses • Response time (Max.): < 5 Nanoseconds • Relative humidity range: 0 - 95% non-condensing • Operating Frequency: 47 - 63Hz • Operating temperature: - 40oC to +65oC cUL/UL 1449 Second Edition Revision (February 9, 2007, aka Rev 2.5) KEY BID SPECIFICATION ITEMS SPD FEATURES SPD FEATURES • 5 Year Warranty • Provides either SAD/MOV hybrid or SAD only protection. Combined with our direct bus connection capabilities, the TPS 1i(SAD or SAD/MOV) provides the lowest installed clamping voltage in the industry. Panelboard CSA 22.2 No. 29, UL 67, and UL 50 NEMA PB1 and NEMA 250 Federal Specification WP115C UL 1449 Rev. 2.5 Listed • Direct bus connections - no breaker required. Lower clamping when compared to externally mounted SPD. Direct bussing is unavailable on service entrance MLO panels • UL 1449 Second Edition Revision Effective Feb 9, 2007 (aka UL 1449 Rev 2.5) SPD STANDARD MONITORING • Designed and tested in accordance with IEEE C62.41.1, C62.41.2, and C62.45 Non-degrading, Bipolar SAD Technology with MOV backup. UL 1449 Rev. 2.5, UL 1283, and cUL Listed EMI/RFI Filtering UL Suppression of 330V/700V Modes of Protection: • LED Indicators • Audible Alarm with Silence and Test Buttons • Dry Contacts • Patented TranSafeTM Circuitry Design incorporating thermal cutouts and surge rated fuses SAD/MOV Hybrid: L-N/L-L, L-G, N-G SAD Only: L-N AVAILABLE OPTIONS • Field installation kits available for retrofit applications with UL 1449 Rev. 2.5 listing Surge Capacity: • Surge Counter • Remote Monitor • Installs into standard tub. Can be retrofitted into panelboards manufactured since 1991 Per Phase 20kA 90kA 130kA 170kA Category C High Tested ORDERING INFORMATION SAD/MOV Hybrid Catalog# TPS Voltage Code A = 120/240V 1∅ 3W C = 208Y/120V 3∅ 4W 01 Surge Current (kA) 020* 090 130 170 Options (**) R = Remote Monitor X = Surge Counter Example: TPSC1130X0 = TVSS for, 208Y/120V Panelboard with a surge capacity of 130kA/Phase and a surge counter. *SAD Only - Available only for the A and C voltage codes. Also, 20kA unavailable in SAD/MOV Hybrid configuration. ** When an option is not selected, include a zero (0) in the option field. VOLTAGE CODE A C SERVICE VOLTAGE Clamp Voltage Levels 120/240V 1∅ 3W 208Y/120V 3∅ 4W 6kV, 500A 6kV, 500A SAD Only Hybrid 288 L-N 288 L-N 320 L-N 320 L-N UL 1449 Rating MCOV 330 L-N 150 330 L-N 150 Siemens Energy & Automation, Inc. 3333 Old Milton Parkway Alpharetta, GA 30005 888.333.3545 info.sea@siemens.com www.sea.siemens.com/power ©2008 Siemens Energy & Automation, Inc. All Rights Reserved Siemens is a registered trademark of Siemens AG. Product names mentioned may be trademarks or registered trademarks of their respective companies. Specifications are subject to change without notice. Order # PBIS-TPS1iSADB-0307