POSSIBLE MEASUREMENT ERRORS IN RELATION TO HARMONICS AND FLICKER J.P. Braun, V.J. Gosbell, S. Perera School of Electrical, Computer and Telecommunications Engineering, University of Wollongong jbraun@ieee.org Abstract The measurement of harmonics and flicker in the MV and LV systems can be made either line-toline or line-to-neutral. Standards provide little guidance on this. As the choice is left to the operator, it may result in some discrepancies in the reporting for compliance. This paper investigates the possible errors between the two measurements in relation to harmonics and flicker in two situations: (i) a large single phase MV load and (ii) the normal variation in LV systems due to lack of perfect balance across the phases. The problem is first analysed theoretically and then supported with field measurements. 1. INTRODUCTION Standards tend to stipulate the acceptable limits for PQ disturbances, but leave the choice of measurement to the utilities. For example the Electricity Distribution code [1] of the state of Victoria only specifies level limits and the measurement location for unbalance and harmonics. Similarly, IEC 61000-2-2 [2] sets limits, but does not address the measurement techniques. On the other hand EN 50160 [3] is very specific as it sets the disturbance limits with respect to the nominal voltage, which is defined as the line-toneutral voltage in a four-wire LV system and line-toline in the case of a three-wire MV system. In both three-wire MV and four-wire LV systems, it is possible to measure PQ disturbances between line-toline or line-to-neutral. In LV systems, no VTs are required for the connection of the instrument to the network, and therefore it is possible to use either method as several instruments are designed with this in mind. However, in MV systems, VTs are always required and the type of measurement is determined by their configuration. In LV systems, the line-to-neutral measurements are preferred as most loads are connected between line-toneutral. In addition, this gives voltage and current readings from which it is easy to calculate volt-ampere and impedance values [4]. However, delta-connected loads such as motors are exposed to disturbance levels that correspond to those measured line-to-line. MV systems require voltage transformers which can be connected to give signals proportional to line-line or line-neutral values. Unfortunately, no standard practice has evolved in distribution systems. The advantage of line-line voltage signals is that these reflect how most MV loads are connected. It also reflects the voltage seen by the downstream LV loads because of the use of delta/star distribution transformers. The advantage of line-neutral voltage signals is the ease of determination of volt-ampere and impedance values. The question that comes to mind is how the line-toneutral measurements compare with those made between lines. The common belief is that these measurements yield similar results but this is based on the assumption of balanced PQ disturbances. Two situations will be investigated in this paper where there is not a high level of balance. The first is the large single phase MV load (e.g. traction), connected between two phases, and which can be examined theoretically. The second is the normal unbalance which occurs in LV systems due to the momentary unbalance between the single phase loads. This needs to be investigated by actual PQ monitor readings. 2. THEORETICAL STUDY 2.1 Fundamental voltage At fundamental frequency, vectors best represent the various voltages as shown in Figure 1. The line-to-line voltage can be computed with equation 1 where X and Y representing two line-to-neutral phasors. 2 V XY = VYN2 + V XN − 2VYN V XN cos(θ Y − θ X ) (1) The traditional 3 can be used in the special case where all line-to-neutral voltages are identical and the angle between them 120 degrees. VC Vh_ca Vh_cn A Vh_an θB V θA Figure 2 Unbalanced harmonics at order h N rectifier at its front end, it is representative of many distorting loads. The study shows that the phase angles of higher harmonics are sensitive to the load power (up to 180 degrees) while at lower frequencies the changes are much less significant. Hence unbalance between harmonics is likely to be small at low frequency, increasing with the harmonic order. V AB VC V BC θC The THD is dominated by the lower frequencies and is more likely to be balanced. Figure 1 Voltage phasors 2.2 Harmonic voltages 2.3 The line-to-line voltage at a given harmonic frequency is the phasor difference of its respective phase-toneutral harmonic voltages. Therefore, the phasor diagram in Figure 1 as well as equation (1) can be used at each harmonic frequency. It can be noted that the spectrum of the line-to-line voltage contains all components present in the corresponding line-toneutral voltages. In the worse case the relative line-to-line harmonic voltage could exceed the line-to-neutral value by about 15% as shown in equation (1). This can be considered as a limiting value for large single phase loads with no significant balanced distorting loads. This shows the possibility that a site may be acceptable if assessed on line-neutral values but be unacceptable if assessed on line-neutral values. Vh _ XY V1 _ XY = 2 ⋅ Vh _ XN 3 ⋅ V1 _ XN = 1.15 ⋅ Vh_ba Vh_bn V AN BN Vh_bc Vh _ XN V1 _ XN (2) With normal unbalance effects in LV systems, the situation is not so deterministic and the application of theory is limited. While great care is taken to minimise unbalance in a distribution system at system frequency, the harmonic behavior can be rather different. According to equation 1, the line-to-line voltage harmonic magnitude could possibly range from zero to the sum of the two line-to-neutral harmonic voltages. A much more likely situation is the intermediate case shown in Figure 2. The magnitude and phase of the harmonic current generated by a distorting load varies with the power. The case of a 3kW single-phase variable speed drive has been investigated [5]. As this type of load is designed with a capacitor-filtered diode bridge Flicker voltage The analysis of the line-to-line flicker is much more complicated than the one for harmonics because of the underlining measurement process based on the “lamp – eye – brain” model [6]. However, if the analysis is based on a stationary flicker made up of sinusoidal fluctuations, the method used so far becomes applicable. A modulated fundamental frequency waveform voltage can be expressed by the following equation: V XN = V cos(ωt + α )1 + p ∑V m m =1 ⋅ cos(Ω m t + α m ) (3) The first term is the fundamental waveform while the second (between parentheses) represents the voltage fluctuation composed exclusively of sinusoids. Using simple trigonometric relations, it is possible to transform (3) into a sum containing two series: V XN = cos(ωt + α ) + p VVm cos((ω + Ω m )t + γ 1) + 2 m =1 ∑ (4) p VVm cos((ω − Ω m )t + γ 2) 2 m =1 ∑ Equation (4) represents the spectrum of the line-to neutral-voltage. The line-to-line flicker voltage can now be examined using equation 1 for each component of equation 4 present in the line-to-neutral voltage. And again, each side band can assume a value ranging from zero (cancellation) to the direct sum of the two line-toneutral voltages. Thus, if we make the assumption that the fundamental is balanced, the magnitude ratio between each side band to the fundamental or harmonic can be at best increased by the same factor 2 ÷ 3 . As a result, the line-to-line flicker could be lower or larger by up to 15% than that of the line-toneutral flicker. The question that remains is how the Pst associated with each type of measure are related. This requires the understanding of how the IEC flickermeter processes the waveform [6]. Figure 3 shows a simplified block, (partial) diagram of the flickermeter. U(t) Voltage Adaptor Squarer Filters Squarer LP Filter (0.53 Hz) IFL measured the voltage between lines. The GPS synchronises all samples and data to the Universal Time Coordinated (UTC) within an accuracy of 1 microsecond [8]. The following Arbiter 1133A data were used: Phasors: Harmonics: Magnitude and phase angle of harmonics to the 50th. Available once per second. Flicker: Figure 3 IEC flickermeter 3. MEASUREMENT RESULTS To investigate the validity of the above theoretical considerations at typical sites, field measurements were undertaken in a distribution network. A first set of measurements was taken at a zone substation and a second at the power laboratory of the University of Wollongong. Also, as shown previously, it is important that the magnitude and phase of each voltage is measured at the same time so as to permit their vectorial addition. This also requires the simultaneous measurement of the line-to-neutral and line-to-line voltages. This was achieved by means of two GPS synchronised Arbiter 1133A PQ analysers as shown in Figure 4. 3.1 Pst and Plt computed as per IEC 610004-15 [6]. Synchronised intervals allow direct comparison. Measurements at a zone substation Measurements on the 11kV bus are made through an auxiliary transformer acting as a measurement VT. The disturbances measured across the transformer are those present in the 11kV system. Being a delta/star transformer and with only a small load on the secondary, no zero-sequence situation has been assumed. 3.1.1 Harmonics The dominant harmonic at this site was the 5th. Figure 5 and 6 show the voltage measurements. The line-toline phase relation for the 5th harmonic is shown in Figure 7. This must be contrasted with the same measurement made on the 17th harmonic (Figure 8), showing clearly that higher order harmonics have larger phase angle fluctuations. 4 .8 A C 4 .6 4 .4 4 .2 Voltage (V) While beyond the scope of the this paper, it can be shown [7] that the instantaneous flicker level (IFL) present at the output of the low pass filter in Figure 3 is the sum of the IFL due to by each side band on its own. As a result, the Pst measured between lines can theoretically range between zero and 1.15 times the Pst in relation to phase-to-neutral voltage. Magnitude and absolute phase angle (relative to UTC) of the fundamental. Available 20 times per second. 4 3 .8 3 .6 3 .4 A B C N B 3 .2 3 4 3 :0 0 4 6 :0 0 4 9 :0 0 5 2 :0 0 5 5 :0 0 5 8 :0 0 T im e [ m in : s e c ] Figure 5 Line-to-neutral 5th harmonic voltage 8 CA CB 7 .5 GPS Arbiter 1133 A Figure 4 Synchronised measurements of PQ disturbances 7 Voltage (V) GPS Arbiter 1133 A 6 .5 6 5 .5 BC The first instrument was set up to measure the voltages between lines and neutral while the second 5 4 3 :0 0 4 6 :0 0 4 9 :0 0 5 2 :0 0 5 5 :0 0 T im e [ m in : s e c ] Figure 6 Line-to-line 5th harmonic voltages 5 8 :0 0 3 .5 150 3 2 .5 Pst (1 min) 100 CA Angle (deg) 50 0 4 3 :0 0 4 6 :0 0 4 9 :0 0 5 2 :0 0 5 5 :0 0 5 8 :0 0 2 1 .5 1 -5 0 0 .5 AB 0 1 3 :0 0 -1 0 0 1 4 :0 0 1 5 :0 0 1 6 :0 0 1 7 :0 0 T im e [ H o u r s ] -1 5 0 Figure 9 T im e [m in :se c ] Line-to-neutral flicker for phase A Figure 7 Line-to-neutral 5th harmonic phase angles 3 .5 150 3 100 Angle (deg) 50 AC 0 4 3 :0 0 4 6 :0 0 4 9 :0 0 5 2 :0 0 5 5 :0 0 5 8 :0 0 Pst (1 Min) 2 .5 -5 0 2 1 .5 1 AB 0 .5 -1 0 0 0 1 3 :0 0 -1 5 0 1 4 :0 0 1 5 :0 0 1 6 :0 0 1 7 :0 0 T im e [ H o u r s ] -2 0 0 Figure 10 Line-to-neutral flicker for phase B T im e [ m in : s e c ] Figure 8 Line-to-neutral 17th harmonic phase angles 3 .5 The 95% harmonic distortion levels for the 5th harmonic are: AB: BC: CA: 1.87% 1.66% 1.91% It can be seen that the there is a small difference in the harmonic voltages assessed by the two sets of readings, but not enough to affect the acceptability of the site. It is usual to report a site using only the largest of the three assessed voltages. This would give values of 1.97% using line-neutral voltages and 1.91% using line-line voltages. At higher harmonics, the discrepancy would be expected to be larger while the limits are smaller, and there is the possibility of significant discrepancies. 3.1.2 Flicker The flicker present at this location was relatively high due mainly to the presence of a smelter up-stream in the system. The measurements made line-to-neutral are similar in all the phase as shown in Figures 9, 10. The high peaks that can be noticed in these figures are due to the operation of the ripple control system. The line-to-line flicker, shown in Figure 11, is surprisingly very similar to the line-to-neutral measurements. This tends to suggest that the flicker on all phases are correlated and balanced. As this site was fairly well balanced for all frequencies, no important difference was observed between line-to-line and line-to-neutral measurements. Pst (1 min) A: 1.97% B: 1.71% C: 1.80% 3 2 .5 2 1 .5 1 0 .5 0 1 3 :0 0 1 4 :0 0 1 5 :0 0 1 6 :0 0 1 7 :0 0 T im e [ H o u r s ] Figure 11 3.2 Line-to-line flicker between phase A and B Measurements at user side The measurements in the LV voltage side were made in the power laboratory at the University of Wollongong. The three-phase supply was monitored in a similar fashion as at the zone substation. No major loads were operating in the laboratory during the measurements. 3.2.1 Harmonics While the low order harmonics were again observed to have relative phase angles of 1200, the case of the 11th was rather different. It showed on average an angle of 900 between the phase A and B and 1400 for A and C as shown in Figure 12. As a result, the line-to-line harmonic voltages were affected as follows: AB was smaller while BC and CA were respectively higher compared to what they would have been if all the angles were 1200 as for line-to-neutral. This is a clear case where harmonic levels vary with the type of measurement. Figure 13 and 14 show respectively the line-to-neutral and line-to-line 11th harmonic voltages. 0 .5 200 150 0 .4 Pst (10 min) Angle (deg) 100 AC 50 0 3 0 :0 0 3 2 :0 0 AB 3 4 :0 0 3 6 :0 0 3 8 :0 0 0 .3 0 .2 4 0 :0 0 -5 0 0 .1 -1 0 0 0 1 3 :0 0 -1 5 0 1 4 :0 0 1 5 :0 0 1 6 :0 0 1 7 :0 0 T im e [ H o u r s ] T im e [ m in : s e c ] Figure 16 Line-to-line flicker Figure 12 Line-to-neutral 11th harmonic phase angles 4. 1 .2 A CONCLUSIONS 1 Voltage (V) 0 .8 0 .6 0 .4 B C 0 .2 0 3 0 :0 0 3 2 :0 0 3 4 :0 0 3 6 :0 0 3 8 :0 0 4 0 :0 0 Because of the lack of clarity in standards, the measurement of PQ disturbances can be made either line-to-line or line-to-neutral in MV and LV systems. This paper investigated the possible discrepancies between the two sets of measurement in the case of harmonics and flicker. T im e [m in :sec ] Figure 13 Line-to-neutral 11th harmonic voltage Based on a vectorial analysis done at the frequencies contained in these disturbances, it was shown that the line-to-line measurement could range between 0 and 1.15 times that measured between line-to-neutral voltages at any given frequency. These two extreme cases correspond to an angle between two vectors of respectively 0 and 180 degrees. This is highly unlikely in practice except at sites dominated by one single phase load. 2 1 .8 CA 1 .6 Voltage (V) 1 .4 1 .2 1 0 .8 BC AB 0 .6 0 .4 0 .2 0 3 0 :0 0 3 2 :0 0 3 4 :0 0 3 6 :0 0 3 8 :0 0 4 0 :0 0 T im e [ m in : s e c ] Figure 14 Line-to-line 11th harmonic voltage The 95% harmonic distortion levels for the 11th harmonic are: A: 0.42% B: 0.30% C: 0.37% AB: BC: CA: 0.31% 0.35% 0.41% Surprisingly, no major discrepancy is noticeable despite a clear case of higher line-to-line voltage. 3.2.2 Flicker Similar to the MV case, the flicker measured line-toneutral or line-to-line is almost identical for all phases as shown in Figure 15 and 16. Field measurements at more typical sites show that these extreme cases are not observed and that harmonics and flicker measured line-to-neutral are very similar to those measured line-to-line. Some visible discrepancies seem to occur only at high order harmonics. While more systematic measurements are required, it cannot be excluded that discrepancies can possibly occur notably at sites having single-phase distorting loads or at more normal sites at high harmonic frequencies. It is recommended that standards should state clearly which set of voltages (line-line or lineneutral) should be used for assessment purposes. 5. REFERENCES [1] Office of the Regulator-General, Victoria, “Electricity Distribution Code”, January 2002 [2] IEC 61000-2-2, “Compatibility levels for lowfrequency conducted disturbances and signalling in public low voltage power supply systems – Basic EMC publication”, 2002 [3] EN50160, “Voltage characteristics of electricity supplied by public distribution systems”, 2000 0 .5 Pst (10 min) 0 .4 0 .3 0 .2 0 .1 0 1 3 :0 0 1 4 :0 0 1 5 :0 0 1 6 :0 0 T im e [ H o u r s ] Figure 15 Line-to-neutral flicker 1 7 :0 0 [4] J. Schlabbach, D. Blume, T. Stephanblome, “Voltage quality in electrical power systems”, IEE Power and Energy Series 36, 2001 [5] A. Mansoor, W.M. Grady, A. Chowdhury, M.J. Samotyj, “An investigation of harmonics attenuation and diversity among distributed single-phase power electronic loads”, IEEE Transaction on Power Delivery, Vol 10, No 1, January 1995, p467-473 [6] IEC 61000-4-15, “Flickermeter – Functional and design specifications”, 2003 [7] K. Srinivasan, “Digital measurement of voltage flicker”, IEEE Power Delivery, Vol. 6, No. 4, Oct. 1999, p1593-1598 [8] Arbiter Systems, Inc., “Model 1133A Power Sentinel Operation Manual”, 2001