Product Description Power Transfer Switches for Limited Service Controllers Description—Firetrol® Power Transfer Switches are available completely assembled with Firetrol Limited Service Controllers. The power transfer switches are built in two versions: FTA975 — For use when the normal power source is a utility and the emergency power source is a generator set. FTA976 — For use when both the normal and emergency power sources are utilities. The entire package of power transfer switch and controller is completely factory assembled, wired, tested and shipped as a complete unit for easy field connection to the power sources and the fire pump motor. Approvals—Firetrol power transfer switches are listed by Underwriters’ Laboratories, Inc., in accordance with UL218, Standard for Fire Pump Controllers; UL1008, Automatic Transfer Switches; UL508, Industrial Control Equipment and CSA, Standard for Industrial Control Equipmentl. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and the latest editions of NFPA 20, Installation of Centrifugal Fire Pumps, and NFPA 70, National Electrical Code. • FTA975 FTA976 Standard Features—The following are included as standard with each transfer switch: Emergency power source disconnect switch sized for connected motor horsepower and voltage (FTA975 only) molded case isolating switch (FTA976 only) thermal-magnetic circuit breaker 3-pole, double throw transfer switch mechanism, electrically operated, mechanically held Control module providing for the following: Differential voltage sensing on all phases of the normal power source Voltage sensing of the emergency power source Frequency sensing of the emergency power source Transfer time delay to compensate for momentary power outages of the normal source Retransfer from emergency to normal source is automatically delayed unless the emergency source fails Cool-down timer for unloaded running of the generator set after retransfer to the normal power source Instantaneous retransfer to normal if the emergency source fails and the normal source is available 3 second transfer restart delay to reduce current surges when transferring to or from the emergency source NO and NC engine control contacts to start the generator set when the normal power source fails Transfer Switch Normal Pilot Light Transfer Switch Emergency Pilot Light Emergency Isolating Switch Open Pilot Light Test Selector Switch Transfer By-pass Switch Silence Alarm Pushbutton Emergency Isolating Switch Open and Transfer Switch in Emergency Audible Alarms Output contacts (NO and NC) for Generator Start, Emergency Isolating Switch Open and Transfer Switch position indicators Standard Withstand Rating, emergency side only FTA975 (Generator set equipped with molded case circuit breaker) 3-30HP, 200-600V, 10,000 Amps, RMS Sym. FTA976 3-20HP, 200-240V, 10,000 Amps, RMS Sym. 25-30HP, 200-240V, 18,000 Amps, RMS Sym. 3-30HP, 380-600V, 14,000 Amps, RMS Sym. NEMA Type 2 (IEC IP11) enclosure Note: The withstand rating of the normal power source side of the transfer switch will be the same as the withstand rating of the fire pump controller assembled with the power transfer switch. Options—The following are available as options to FTA976 Power Transfer Switches: Special Enclosures -T NEMA Type 3R (IEC IP14) -E NEMA Type 4 (IEC IP56) -F NEMA Type 4X (#304 Stainless Steel) (IEC IP56) -G NEMA Type 12 (IEC IP52) Special paint color or finish - Consult Factory Circuit Breaker Option -B Intermediate withstand rating 200-480V - 65,000 Amps, RMS Sym. 550-600V - 18,000 Amps, RMS Sym. Modifications—The following are available as modifications to all transfer switches: Anti-condensation Space Heaters -H 120 Volt space heater -J 120 Volt space heater with thermostat -K 120 Volt space heater with humidistat -L 240 Volt space heater -M 240 Volt space heater with thermostat -N 240 Volt space heater with humidistat Explanation of Catalog Number FTA975-BL100B-ED Type 975 Gen Set 976 Second Utility 208 Start Option -B Automatic Withstand rating -A Standard (FTA976) -B Intermediate (FTA976) -D Standard (FTA975) Modifications Voltage -H 200-A 220-240 -F 380-415 -B 440-480 -C 550-600 Ampere rating 100 Example—FTA975-BD100B-ED FTA975 Power Transfer Switch for generator set emergency power source, 100 Amp, 440-480 Volts, with load shed circuits. Note—Due to continual product enhancements, dimensions and specifications may change at any time without notice. Contact the factory or local representative for current specifications. Alarms -BX Contacts for remote indication, second utility source phase failure/phase reversal (FTA976 only) Miscellaneous -ED Load shed circuits -TM Microprocessor type (Group 5) control module -TN As above, with serial communications port -S Tropicalization (919) 460-5200 • www.firetrol.com • Sales Office: Cary, NC 27518 USA PD975-01(12-15-08) ©ASCO 2008