The Effects of Waveform Distortion on Power Protection Relays Laith Al-Musawi / Andrew Waye / Dr. Nafia Al-Mutawaly, McMaster University, Canada William Yu, OMICRON, USA Introduction With increased usage of Variable Frequency Drives (VFDs), solid state inverters and other non-linear loads, power quality is becoming a concern in distribution network performance. Harmonics produced by such loads can cause overheating of neutral conductors, transformers, and motors. Moreover, research has shown that high harmonic content can have negative impacts on power system performance, as protection relays are built to operate at a nominal frequency (50/60 Hz) [1]. Previous research indicated that some relays may mis-operate and trip under normal operating conditions, or, conversely, fail to trip entirely in the presence of harmonics [2]. False or missed relay tripping may result in system failure, service discontinuity or other economic losses. This paper outlines work that has been conducted to test various types of relays (electromechanical, digital and Intelligent Electronic Devices) and their performance in the presence of harmonics. Although previous investigations addressed this topic [2, 4], the findings did not comprehensively quantify the impact of harmonics on relay performance. The experiments discussed in this paper were conducted using an OMICRON relay test set (CMC 256). The tests conducted in this study examined various levels of Total Harmonic Distortion (THD) including individual harmonics up to the 49th, superimposing harmonic profiles and varying harmonic phase angles. Test Methodology General overview Protective relay performance testing was undertaken on both conventional (electromechanical) and modern (digital) relays. An OMICRON CMC 256plus high-precision relay test set was used to synthesize arbitrary waveforms and capture resultant tripping times. Conventional (60 Hz) AC waveforms were applied directly to all relays under test in order to determine the relay activation baseline (time). To produce the same energy as that of the fundamental frequency, a distorted waveform was then synthesized (including both fundamental and harmonic components) according to the following RMS energy formula [3]: A comparison between the tripping times of both injected waveforms was calculated as shown in the formula below: The testing was repeated for all relays with data collected, recorded (currents and harmonic distortion levels) and plotted for detailed analysis. Test Setup With OMICRON’s current channels connected directly to the relay (no current transformer), various types of relays were evaluated (figure 1). Fig. 1 Test Setup The relay output (trip signal) was connected directly to a OMICRON CMC 256plus digital input to determine the tripping time. Electromechanical, digital and Intelligent Electronic Device (IED) relays were tested, as shown in Table 1. Electromechanical Digital ABB CO-8 ABB REU 523 Westinghouse CO-11 SEL 451 (IED) Table 1 - Relays Tested Results The data obtained from various tests were recorded, tabulated and graphed to reflect relay performance. Experimental findings were organized into five categories: inverse time characteristic, © OMICRON 2013 – International Protection Testing Symposium definite tripping time, relay current transformer (CT) tap order, harmonic profiles and voltage distortion. Inverse Time Characteristics Electromechanical Relays Figure 2 presents the impact of a given harmonic order (marked points) and the variation of applied harmonic magnitude (trend lines) on trip time. Minimal impact was observed on relay performance for Individual Harmonic Distortion (IHD) <10%. However, when total harmonic distortion is 20% or higher, two trends become apparent: the low order harmonics have less impact on the tripping time, while the higher order harmonics (>19th) have an obvious impact. Fig. 2 Fig. 3 Inverse Time Characteristics - Electromechanical vs. Digital Relays Definite Trip Time Electromechanical Relays - Harmonic Order & Phase Angle Tripping time was impacted by harmonics; specifically, it was found that the tripping time is dependent on the harmonic order and phase angle. From figure 4, it is evident that the 3rd and 5th harmonics affect the device in different ways with respect to tripping time, a variation which is dependent on the harmonic phase shift relative to the fundamental. Inverse Time Characteristics Electromechanical Relays Digital Relays For digital relays, it was observed that respective harmonic orders or magnitudes have little to no effect on relay operation (the harmonics appear invisible to the relay). Literature on the subject indicates that digital filters eliminate harmonics when converting from analog to digital (A/D) quantities, as a filter in the relay’s digital signal processor (DSP) stage removes frequencies greater than 60Hz [4]. When comparing electromechanical versus digital relay performance, it is apparent that digital relay tripping time remains constant (independent of harmonic content), whereas electromechanical relay trip time is harmonic dependant (figure 3). Fig. 4 Trip Time - Harmonic Order and Phase Angle To quantify the effects of phase shifting the 3rd harmonic, the IHD levels were increased as a percentage of the fundamental, which resulted in an observed increase in tripping time (figure 5). Fig. 5 Trip Time - 3rd Harmonic Distortion Percentage © OMICRON 2013 – International Protection Testing Symposium Digital Relays - Harmonic Order & Phase Angle Harmonic order had limited (and minimal) impact on the performance of the digital relays; however, changing the phase angle of the 3rd harmonic resulted in a noticeable impact on tripping time. Figure 6 shows that the 5th and 7th order harmonics were not detected by the relay, however the 3rd order harmonic (at a 120-270 degree phase shift) resulted in increased tripping time. This can be attributed to the software algorithm for the DSP stage of the relay. Harmonic Profiles Electromechanical Relays Mixed harmonic distortion had a minimal impact on the tripping time of the electromechanical relays tested, as shown in figure 8. Fig. 8 Mix Distortion - Electromechanical Relays Digital Relays Fig. 6 Trip Time - Harmonic Phase Shifting There was no impact on digital relay tripping time due to mixed harmonic distortion (figure 9). Relay CT Tap Order Electromechanical Relays Tap order had a minimal impact on the performance of the relays tested. Fig. 9 Mix Distortion - Digital Relays Voltage Distortion Fig. 7 Tap Order - Electromechanical Relays Digital Relays As there are no tap connections on digital relays, there can be no impact to relay performance based on the tap setting. Digital Relays - Undervoltage Harmonics of all orders (20% total distortion) resulted in essentially the same impact to relay tripping time in an undervoltage condition. Figure 10 shows that a per-unit trip time of 1 (for fundamental voltage only) was observed as expected. Harmonics beyond the fundamental (up to the 49th) resulted in a per-unit trip time of less than 0.3, which indicates that voltage harmonics are completely filtered. © OMICRON 2013 – International Protection Testing Symposium Fig. 12 Electromechanical Relay’s Induction Disk [2] Fig. 10 Voltage Distortion - Digital Undervoltage Digital Relays - Overvoltage Harmonics of all orders (20% total distortion) resulted in essentially the same impact to relay tripping time in an overvoltage condition. Figure 11 shows that a per-unit trip time of 1 (for fundamental voltage only) was observed as expected. Harmonics beyond the fundamental resulted in a per-unit trip time of greater than 8. The relay takes longer to trip as the potential transformer (PT) is designed to detect only fundamental frequencies (50/60Hz). With fundamental pick-up current applied, torque of sufficient magnitude is generated to overcome the spring restraint, causing disk rotation [2]. This torque results from interaction between disc currents produced by each pole flux and the other two pole fluxes, with all forces in the same direction. Additionally, the total flux will decrease in inverse proportion to frequency (harmonics on input current) resulting in a net impact on the centre pole. As harmonics are added, the induced lag coil current remains largely unchanged, causing the third and centre pole fluxes to draw closer in phase, resulting in: Increase of pickup current Reduction in disc rotation speed Inconsistent tripping times In contrast, digital relays operate on the concept of capturing current and voltage waveforms, filtering the waveforms and processing them using Discrete Fourier Transform (DFT) methods. As shown in figure 13, the waveform is sampled every quarter cycle to ensure proper capture of the waveform energy (area under the curve). Fig. 11 Voltage Distortion – Digital Overvoltage Discussion Electromechanical relay induction discs consist of a three-pole electromagnet manufactured to operate on a nominal frequency of 50/60Hz. The centre pole is energized by the flow of mains current, while the outer pole is equipped with a lag coil, and the remaining pole receives flux generated by the other two poles (figure 12). Fig. 13 Sampling in Digital Relays © OMICRON 2013 – International Protection Testing Symposium Using the resulting samples, the relay DSP stage computes the magnitude of each harmonic based on the following equation: Where, m is sample number n is harmonic order N is total number of samples X(m) is the signal magnitude at sample m Data acquisition and filtering stages are essential parts of a digital relay. The presence of harmonic pollution on input signals may result in the malfunction of digital algorithms and therefore in the mis-operation of the relay [5]. Since microprocessor controlled relays implement low pass filters before digital filtering, digital relays do not respond to higher order harmonics [6]. As a result, they are incapable of including energy within the higher frequency harmonics into their trip algorithms [6]. Conclusions The tripping times of electromechanical relays, based on inverse time characteristics, were observed to be dependent on harmonic amplitude and order. IHD values of <10% were found to have little to no impact on relay performance; this can be attributed to the minimal magnetic flux introduced in the induction disk. IHD values of >20% resulted in an observable impact due to the generation of nonlinear magnetic flux. Harmonics greater than the 19th resulted in a significant variation in tripping time (figure 2). In contrast, digital relay tripping times remain constant regardless of harmonic amplitude and order due to filtering implemented within the relay; however, the tripping time of the digital relay did appear to have a constant offset in the presence of harmonics (figure 3). Definite tripping times on electromechanical relays were observed to be affected by the phase angles of lower-order harmonics (3rd and 5th). Little to no impact was observed with higher order harmonics or phase angles (figures 4 and 5). Digital relays experience minimal impact in the presence of 5th order harmonic phase-shifting, however a noticeable impact is observed with the 3rd order harmonic (figure 6). The phase angle imparts more impact for low order harmonics (3rd and 5th) whereas higher harmonics have minimal impact. Phase shifting the 3rd harmonic to 150-180 degrees will introduce a destructive effect on the fundamental; the inverse phenomenon applies to the 5th harmonic introducing an additive effect on the fundamental. However, with higher harmonics, an additive or destructive action due to phase shifting has relatively less impact on the fundamental. Electromechanical relays’ CT tap order had little to no impact on the relay’s performance; changing the tap will not modify the magnetic flux induced by the harmonics. Deviations in captured tripping times were apparent, but these increases were not attributable to the CT tap position (figure 7). With undervoltage distorted waveforms, the relay did not detect the presence of harmonics, treating the signal as a fundamental with a lower magnitude resulting in reduced tripping time (figure 10). Conversely, overvoltage distorted waveforms were observed to increase the tripping time as the relay cannot detect the harmonics energy (figure 11). However the results indicate that this change is irrespective of the harmonic order for both under and overvoltage conditions, as the resulting trip time change was constant. To the extent that the two types of relays tested yielded inconsistent tripping times (for the same energy input), it is difficult to identify a single solution as to how grading should be applied when harmonics are present in protection systems. Given that digital relays filter out harmonics (except for the 2nd and 4th harmonics in the case of inrush current for transformer energization) a parallel harmonic detection mechanism would be required to improve digital relay performance in the presence of high harmonic content. Electromechanical relays however, do not exhibit predictable performance changes when influenced by harmonics, and as such cannot be effectively modified to reliably detect harmonic content. This remains a concern, considering the widespread implementation of electromechanical relays throughout North America at this time. Future work Data recently collected (waveforms and harmonic profiles) from typical modern homes reveal the presence of significant harmonics and waveform distortion (figures 14 and 15). As such, the need for further investigation of harmonic distortion’s effects on the distribution system is clearly needed. Fig. 14 Data Collected from a Typical Modern Home © OMICRON 2013 – International Protection Testing Symposium About the Author Fig. 15 Typical Modern Home’s Harmonic Profile Laith Al-Musawi received his BTech. degree in Energy Eng. Tech. from McMaster University, Canada in 2013. He is currently enrolled in an MSc in Electrical Engineering at McMaster University. He is also working as a Research Assistant in the Engineering Technology department at McMaster University. His research interests include protection and control of power systems, power quality, and instrumentation. Acknowledgment The authors wish to thank the Natural Sciences and Engineering Research Council (NSERC) programs which helped to support this publication. References [1] Donohue, Paul; Islam, Syed: The Effect of Nonsinusoidal Current Waveforms on Electromechanical and Solid-State Overcurrent Relay Operation. IEEE Transactions on Industry Applications, Vol.46, No.6, November/December 2010 [2] A. Elmore, W.; A. Kramer, Cheryl; E. Zocholl, Stanley: Effect of Waveform Distortion on Protective Relays. IEEE Transactions on Industry Applications, Vol.29, No.2, March/April 1993 [3] Y., Recep; G., Kayhan; B., Altug; K., Celal; U., Mehmet: Analysis of Harmonic Effects on Electromechanical Instantaneous Overcurrent Relays with Different Neural Networks Models.Yildiz Technical University [4] E. Zocholl, Stanley; Benmouyal, Gabriel: How Microprocessor Relay Respond to Harmonics, Saturation, and Other Wave Distortions. The 24th Annual Western Protective Relay Conference, 1997 [5] Zamora, I.; Mazón, A.J.; Valverde, V.; San Martín, J.I.; Buigues, G.; Dyśko, A.: Influence of Power Quality on the Performance of Digital Protection Relays. IEEE [6] Medina, A.; Martínez-Cárdenas, F.: Analysis of the Harmonic Distortion Impact of the Operation of Digital Protection Systems. IEEE © OMICRON 2013 – International Protection Testing Symposium OMICRON is an international company serving the electrical power industry with innovative testing and diagnostic solutions. The application of OMICRON products allows users to assess the condition of the primary and secondary equipment on their systems with complete confidence. Services offered in the area of consulting, commissioning, testing, diagnosis and training make the product range complete. Customers in more than 140 countries rely on the company’s ability to supply leadingedge technology of excellent quality. Service centers on all continents provide a broad base of knowledge and extraordinary customer support. All of this together with our strong network of sales partners is what has made our company a market leader in the electrical power industry. For more information, additional literature, and detailed contact information of our worldwide offices please visit our website. www.omicron.at | www.omicronusa.com © OMICRON