Feature When is a Fuse Not a Fuse by Rick Youngblood American Electrical Testing Co. M any utilities still use the S&C power fuse as their distribution transformer primary protection for faults. Most technical people are aware that this protection only works if the fuse opens the source during the fault incident. The problem is many of our maintenance technicians and engineers are not aware of a serious potential issue with S&C type SMD-1A, -2B, -2C and -3 power fuses. Most maintenance personnel do not regularly receive factory service advisories and seldom have opportunity to attend seminars providing the safety and reliability information needed to make sound decisions pertaining to the systems they are tasked to maintain. A. Stainless-steel drive spring provides stored energy to drive arcing rod upward through arcextinguishing medium during fuse operation B. Solid-material arc-extinguishing medium C. Silver-clad copper arcing rod D. Filament-wound glass-epoxy tube E. Fusible element — helically coiled silver or pretensioned nickel-chrome — provide precise melting characteristics and nondamageable performance www.netaworld.org Most of us who have been using the S&C power fuse for more than 40 years trust its ability to protect our valuable assets during a fault condition. All older S&C fuses and many newer designs are susceptible to center bore close down as a result of moisture ingress into the boric acid core used to provide the arc interruption gas during fault. The resulting water ingress causes the boric acid to grow and adhere to the fuse link over a period of time. When this happens the link cannot be pulled away by the link spring. The link spring is used to stretch the arc beyond its ionization limit as the fuse mechanically opens, disrupting the arc and protecting the transformer. During a fault the link coated with boric acid burns in two, and gas is formed in the fuse barrel, but the arc will continue due to the close proximity of the mating parts. Additionally, the fuse will fail to fall open and the transformer will continue to see the fault until the fuse burns physically in two or the fault is interrupted elsewhere. Even with the rain shield end cap provided by S&C, water ingress happens naturally because of rain and high humidity. Improper storage outdoors will cause the condition to be worsened if the fuses are hung upside down or laid on the wet ground. All removed or spare fuses should be stored indoors or inside a weatherproof cabinet to prevent this condition from beginning. S&C provided information in the maintenance section of Instruction Sheet 212-501 on a method to airflow test their SMD-1A, -2B, and -2C fuses to determine if bore close down has begun. The test is relatively easy and fast to perform by measuring a specific flow rate at a given pressure for each model of fuse, and provides the vital information needed to determine fuse health and reliably protect the equipment. An airflow test instrument is available from S&C. The SMD-3 fuses are not suitable for airflow testing but can be returned to S&C for a disassembly inspection. S&C recommends checking the fuse-unit bore periodically, whenever the protected equipment is taken out of service for routine maintenance. Winter 2006-2007 NETA WORLD An additional problem not related to weather occurs when a fuse is dropped on its end cap. There is an internal spring used to pull the calibrated link apart when the link is melted by a fault. The fuse uses a tensioning wire to prevent the link from being pulled apart under normal operating conditions. This wire also melts during a fault permitting the spring to tension the link. Premature fuse failure can occur with rough handling due to failure of the tensioning wire. Precautions should be taken to prevent fuse damage and ultimate failure creating a false (no fault) outage of the transformer at an inopportune time after maintenance to the substation has been recently performed. For more information contact S&C directly or Rick Youngblood of American Electrical Testing Company 1-800-992-3826 Rick Youngblood graduated from Indiana State University in 1973 after leaving active duty in the Air Force. Rick joined Cinergy Corporation in 1982 then known as Public Service of Indiana. Rick was promoted to Project Engineer after receiving his BSEE from Purdue University in 1985. In 1987 Rick became the Manager of Technical Services in their Northern Division. Rick was responsible for implementing Cinergy’s CMM System and creation of its Predictive and Preventive Maintenance Programs. In 2000 Rick was promoted to Supervising Engineer for Substation Services where he remained until taking early retirement in 2004. Rick joined American Electrical Testing Company in August of 2004 as Regional Manager heading up the Midwest office located in Indiana. Rick holds a Level III NETA test technician certification. NETA WORLD Winter 2006-2007 www.netaworld.org