Generating Plant Type Verification Sheet for Fronius IG Plus 35V

advertisement
ENGINEERING RECOMMENDATION
RECOMMENDATION G59/2
MATERIALS & SAFETY - R&D
TR 13899
page 1 of 4
APPENDIX A13.1 GENERATING PLANT TYPE VERIFICATION TEST SHEET
GENERATING PLANT DETAILS
Generating Plant Type reference:
Fronius IG Plus 35V-1
Generating Plant Technology:
Photo voltaic
Manufacturer:
Fronius International GmbH
Tel:
+43-7242-241-0
Address:
Fax:
+43-7242-241-224
Guenter Fronius Str 1
4600 Wels-Thalheim, Austria
Technical file reference No.:
Maximum export capability (Generating Plant rating less parasitic load)
3500W
TEST HOUSE DETAILS
Name and address of test house
Fronius R&D Laboratories, Fronius International GmbH,
Guenter Fronius Str 1, A-4600 Wels-Thalheim, Austria
Telephone number
+43-7242-241-0
Facsimile number
+43-7242-241-224
E-mail address
pv@fronius.com
Generating Plant Type Verification Sheet for Fronius IG Plus 35V-1_TR13899.doc
Backup: Fronius IG Plus V UK
ENGINEERING RECOMMENDATION
RECOMMENDATION G59/2
MATERIALS & SAFETY - R&D
TR 13899
page 2 of 4
POWER QUALITY
Harmonics Emissions
Minimal Short Circuit Ratio Rsce: 33
Value of Short Circuit Power Ssc corresponding to Rsce: 347kVA
Equipment Phases: Single Phase
Description
Harmonic:
Limits at RSCE=33:
Test value
(max value of Phase1,2,3):
Harmonic Current
Distortion Factors (%)
Harmonic Current % = 100ln/l1
I3
I5
I7
I9
I11
I13
THD
PWHD
21,6
10,7
7,2
3,8
3,1
2,0
23
23
1,58
0,71
0,55
0,32
0,11
0,05
1,75
0,75
Notes:
Detailed requirements are specified in BSEN 61000-3-12.
Voltage Fluctuations
Equipment meets BSEN 61000-3-3
Yes
If equipment does not meet BSEN 61000-3-3:
i)
Does equipment require a supply rated ≥ 100A?
-
ii)
If answer to i) is no, specify the value of Zref:
-
iii)
If answer to i) is no, specify the value of Zmax:
-
Voltage Disturbance
Limit
(at Zref)
Actual Value
(at Zref)
Notes:
Pst
PIt
d(t) > 3,3%
dc %
dmax %
1.0
0.65
0.5
3.3
4.0
0,41
0,41
0,03
3,05
3,38
Detailed requirements are specified in BSEN 61000-3-11 and BSEN 61000-3-3.
Generating Plant Type Verification Sheet for Fronius IG Plus 35V-1_TR13899.doc
Backup: Fronius IG Plus V UK
ENGINEERING RECOMMENDATION
RECOMMENDATION G59/2
MATERIALS & SAFETY - R&D
TR 13899
page 3 of 4
DC injection
Power factor
Limit
20mA, tested at three power levels
0.95 lag–0.95 lead at three voltage levels
Test point
10%
55%
100%
212 V
230 V
248 V
± 30 mA *
± 30 mA *
± 30 mA *
0,99
0,99
0,99
Value measured
* Measured values are below 0,25% of the rated current.
PROTECTION TESTS
Protection
Setting
Test Results
Over Voltage Stage 1
Volts
Sec
Volts
Sec
L1-N or L1-L2
L2-N or L1-L3
L3-N or L1-L3
Over Voltage Stage 2
261 V
--Volts
1,0 sec
--Sec
<264 V
--Volts
1,0 – 1,3 sec
--Sec
L1-N or L1-L2
L2-N or L1-L3
L3-N or L1-L3
Under Voltage Stage 1
273 V
--Volts
0,5 sec
--Sec
<276 V
--Volts
0,5 -0,8 sec
--Sec
L1-N or L1-L2
L2-N or L1-L3
L3-N or L1-L3
Under Voltage Stage 2
211 V
--Volts
2,5 sec
--Sec
>209 V
--Volts
2,5 – 2,8 sec
--Sec
L1-N or L1-L2
L2-N or L1-L3
L3-N or L1-L3
Over Frequency Stage 1
194 V
--Hz
0,5 sec
--Sec
>192 V
--Hz
0,5 – 0,8 sec
--Sec
L1-N or L1-L2
L2-N or L1-L3
L3-N or L1-L3
Over Frequency Stage 2
51,48 Hz
--Hz
90,0 sec
--Sec
<51,5 Hz
--Hz
90,0 – 90,3 sec
--Sec
L1-N or L1-L2
L2-N or L1-L3
L3-N or L1-L3
Under Frequency Stage 1
51,98 Hz
--Hz
0,5 sec
--Sec
<52,0 Hz
--Hz
0,5 – 0,8 sec
--Sec
L1-N or L1-L2
L2-N or L1-L3
L3-N or L1-L3
Under Frequency Stage 2
47,52 Hz
--Hz
20,0 sec
--Sec
>47,5 Hz
--Hz
20,0 – 20,3 sec
--Sec
L1-N or L1-L2
L2-N or L1-L3
L3-N or L1-L3
Other relevant protection
47,02 Hz
---
0,5 sec
---
>47,0 Hz
---
0,5 – 0,8 sec
---
Generating Plant Type Verification Sheet for Fronius IG Plus 35V-1_TR13899.doc
Backup: Fronius IG Plus V UK
ENGINEERING RECOMMENDATION
RECOMMENDATION G59/2
MATERIALS & SAFETY - R&D
TR 13899
page 4 of 4
LOSS OF MAINS TEST
Method used
Frequency shift
Output power level*
10%
55%
100%
Trip setting
0,5 sec
0,5 sec
0,5 sec
Trip value
<0,5 sec
<0,5 sec
<0,5 sec
*indicative values are shown for minimum, medium and maximum power levels.
RECONNECTION TIMES
Reconnection Time
Under/Over voltage
Under/Over Frequency
Loss of mains
Minimum value
180 seconds
180 seconds
180 seconds
Actual setting
185 sec
185 sec
185 sec
Recorded value
192 sec
190 sec
192 sec
SHORT CIRCUIT CURRENT CONTRIBUTION
As Photovoltaic SSEGs are inverter-connected, they are deemed to automatically comply with regulations
and no further tests are required.
COMMENTS
Generating Plant Type Verification Sheet for Fronius IG Plus 35V-1_TR13899.doc