Slide 1 Unfaulted unearthed network A B C ΣI01 = 0 ΣI01 UA C0 R0 IcB IcA UB UC IcC U0=0 ΣI02 = 0 ΣI02 UA IcB IcA UB UC IcC • Phase-to-ground voltages form a symmetrical system and their sum equal to zero at every time instance • Capacitive charging currents (IcA, IcB, IcC) flow through the phase-to-earth capacitances and form a symmetrical system • I0 measurement in feeder #1 (ΣI01) measures the sum of the charging currents of that feeder, which equals to zero • I0 measurement in feeder #2 (ΣI02) measures the sum of the charging currents of that feeder, which equals to zero Single phase to earth fault in unearthed network Slide 2 Single-phase to earth fault in phase C Equivalent circuit Positive current direction Busbar UA UB UC +U0 IcA ~ A IcB ~ ~ B C Ief C0 • In healty phases charging current flows towars the busbar • In faulty phase the earth fault current (sum of charging currents of the healty phases) flows towards the fault location • Positive current direction is selected to be from busbar to feeders Single phase to earth fault in unearthed network Slide 3 Single-phase to earth fault in phase C - What happens to voltages? UA UCA UA UAB UA = -UCA UAB +U0 UC UBC Voltage phasors before the fault UB UC UB = UBC UB Voltage phasors after the fault • Faulty phase voltage UC = 0 • Healty phase voltages equal the line voltages • Note the direction of the voltage +U0 Single phase to earth fault in unearthed network Slide 4 Single-phase to earth fault in phase C - What happens to currents ? IcA + IcB UA IcB This phasor is measured in healty phases IcB IcA UA = -UCA IcA +U0 UB UC UB = UBC IcC Charge current phasors before the fault Charge current phasors after the fault • Charging current leads corresponding phase voltage by 90o • The direction of the earth fault current is opposite to that of the charging current in healty phases: Ief vs. (IcA + IcB) = 1800 (see figure in slide 2 !) This phasor is the earth fault current Ief Single phase to earth fault in unearthed network Single-phase to earth fault in phase C - What happens to currents ? • By turning the +U0-phasor in order to have it pointing upwards, the previous figure can be drawn as: UA = -UCA +U0 UB = UBC IcB IcA + IcB Direction of currents in healty feeders Ief Direction of currents in faulty feeder IcA -U0 • NOTE that in REF the characteristics for directional earth fault protection are drawn using -U0 Slide 5 Single phase to earth fault in unearthed network Single-phase to earth fault in phase C - What happens to currents ? • By turning the phasors so that -U0-phasor is pointing upwards, the previous figure can be drawn as: -U0 IcA Ief IcA + IcB Direction of currents in faulty feeder IcB UB = UBC +U0 UA = -UCA • In REF the characteristics for directional earth fault protection are drawn using -U0 Direction of currents in healty feeders Slide 6 Slide 7 Earth fault in unearthed network Assumptions: 1. Equal feeder lengths A B C ΣI01 - U0 2. Resistive leakage R0 losses neglected 3. Rf = 0 ohm 4. Positive current direction is from bus to feeders U0 C0 ΣI01 R0 ΣI02 - U0 Ief ΣI02 • ΣI02 ≠ Ief • I0 measurement in healty feeder (ΣI01) includes only charging currents (healty phases) of that feeder • I0 measurement in faulty feeder (ΣI02) includes charging currents of the galvanically connected background network, but not the charging currents of it’s own (these flow in both directions through the measurement point and cancel each other) • Directional EF-protection is based on the angle of measured I0 versus U0 (-U0 in REF) Earth fault in unearthed network Equivalent circuit Ief Up U0 ~ Rf 3·C0 U0 = Up I ef = 2 3 ⋅ ω ⋅ C0 1 + (3 ⋅ ω ⋅ C0 ⋅ R f ) • U0 is the voltage drop which is created when Ief flows through the phase-to-earth capacitances • Rf is NOT included in these!!! See equivalent circuit!!! Slide 8 Slide 9 Earth fault in 100% compensated network A B C Assumptions: 1. Equal feeder lengths ΣI01 - U0 2. Resistive leakage R0 losses neglected 3. Rf = 0 ohm 4. Positive current direction is from busbar to feeders C0 ΣI02 L RL ΣI01 R0 - U0 U0 ΣI02 Ief • Earth-fault current is cancelled by feeding an equal inductive current with a compensation coil • I0 measurement in healty feeder (ΣI01) includes only charging currents (healty phases) of that feeder • I0 measurement in faulty feeder (ΣI02) includes now both the resistive current created by the additonal resistor and it’s own charging currents • Directional EF-protection is based on the angle of measured I0 versus U0 (-U0 in REF) Earth fault in compensated network Slide 10 Equivalent circuit Ief Rf IRL Up ~ U0 RL IR0 R0 IL ω⋅L ω⋅ IC 3·ω ω ⋅C0 U0 = I ef 2 1 1 + 3 ⋅ ω ⋅ C 0 − ω ⋅ L R 0 2 • U0 is the voltage drop which is created when Ief flows through the impedance of the parallel connection of phase-to-earth capacitances, reactor L, additional resistor RL and leakage resistance R0 of the lines • Rf is NOT included in these!!! See equivalent circuit!!! Slide 11 Earth fault in 50% under-compensated network A B C Assumptions: 1. Equal feeder lengths ΣI01 - U0 2. Resistive leakage R0 losses neglected 3. Rf = 0 ohm 4. Positive current direction is from busbar to feeders C0 ΣI01 R0 ΣI02 L RL - U0 ΣI02 U0 Ief • 50% of the earth-fault current is cancelled by feeding an inductive current with a compensation coil • I0 measurement in healty feeder (ΣI01) includes only charging currents (healty phases) of that feeder • I0 measurement in faulty feeder (ΣI02) includes now only the resistive current created by the additonal resistor (background network’s and feeders charging current flow in opposite directions in the measurement point and cancel each other) • Directional EF-protection is based on the angle of measured I0 versus U0 (-U0 in REF) Slide 12 Earth fault in 150% over-compensated network A B C Assumptions: 1. Equal feeder lengths ΣI01 - U0 2. Resistive leakage R0 losses neglected 3. Rf = 0 ohm 4. Positive current direction is from busbar to feeders C0 ΣI02 L RL ΣI01 R0 - U0 U0 ΣI02 Ief • 150% of the earth-fault current is cancelled by feeding an inductive current with a compensation coil • I0 measurement in healty feeder (ΣI01) includes only charging currents (healty phases) of that feeder • I0 measurement in faulty feeder (ΣI02) includes now both the resistive current created by the additonal resistor, it’s own charging currents and the overrest of the inductive current • Directional EF-protection is based on the angle of measured I0 versus U0 (-U0 in REF) Slide 13 Earth fault in high resistance earthed network Assumptions: 1. Equal feeder lengths A B C 2. Resistive leakage R0 losses neglected ΣI01 - U0 3. Rf = 0 ohm 4. Positive current direction is from busbar to feeders C0 5. IRe = Ictot ΣI02 ΣI02 Re ΣI01 R0 - U0 U0 Ief • Earth-fault current includes a resistive part defined by the size of Re (≤ 1/(3 ·ω·C0tot)) • I0 measurement in healty feeder (ΣI01) includes only charging currents (healty phases) of that feeder • I0 measurement in faulty feeder (ΣI02) includes now both the resistive current created by the earthing resistor and capacitive charging current of the galvanically connected background network • Directional EF-protection is based on angle of measured I0 versus U0 (-U0 in REF) Earth fault in high resistance earthed network Slide 14 Equivalent circuit Rf Ief Up ~ IRe U0 Re IC 3·ω ω ⋅C0 U0 = I ef 2 1 + (3 ⋅ ω ⋅ C 0 )2 Re • U0 is the voltage drop which is created when Ief flows through the impedance of the parallel connection of phase-to-earth capacitances and earthing resistor Re • Rf is NOT included in these!!! See equivalent circuit!!!