© FEBRUARY, 2012 ThyssenKrupp Elevator OILDRAULIC ELEVATOR CONTRACT DATA PLEASE VERIFY WALL THICKNESS AND TYPE AT EACH LANDING FLR WALL TYPE THKNESS ELEV # TYPE: AMEE 45 HLS SPEED: FPM UP CAPACITY: 4500 150 FPM DOWN MAX. OPERATION: CAR ENCLOSURE: DOOR TYPE: TWO SPEED - LEFT HAND PLATFORM THK: 4 7/8 FINISHED FLOOR: TELEPHONE: PIT LADDER: POWER UNIT: HP POWER SUPPLY: STARTING: GLOPU: JACK MODEL: TWIN GLOJ: OVERTRAVEL: TOP PLUNGER O.D.: CYLINDER O.D.: SAFETY BEAM REQ'D. PER OSHA 1926.502 PROVIDED & INSTALLED BY OTHERS, AS DIRECTED BY THYSSENKRUPP FIELD OFFICE DESIGN LOAD = (STATIC, NOT IMPACT) ASME A17.1 RULE 2.1.4 BUFFER REACTION (TYP. AT EACH BUFFER) = EST. WORKING PRESS. CAR FRAME FORMED CROSSHEAD 7GAx6"x2 1/2" S = 5.429 I = 21.71 A = 2.264 FORMED BOLSTER 7GAx8"x2 3/4" S = 1.38 I = 2.17 r = 1.009 FORMED STILE t = 10GA WITH TOP OVERTRAVEL OF 6" 1. A PLUMB, PROPERLY VENTILATED HOISTWAY (ACCORDING TO CODE AND SIZES SHOWN). 2. ADEQUATE SUPPORT FOR JACK, GUIDE RAIL BRACKETS, AND BUFFERS (FOR REACTIONS SHOWN ). 3. HOISTWAY BARRICADES AND ALL CUTTING AND PATCHING TO INSTALL HOISTWAY ENTRANCES, SILLS, HALL FIXTURES, OIL AND ELECTRIC LINES. IN FULL TOP OVERTRAVEL, PER CAR (ACCORDING TO CODE). NOTE: MUST BE CLEAR OF ALL ELEVATOR EQUIPMENT. 5. DEDICATED 120 VOLT,15 AMP. SERVICE, ALONG WITH TELEPHONE CIRCUIT WHEN REQUIRED, TO TERMINALS OF EACH REQUIRED CONTROLLER (AS LOCATED ON PLAN VIEW) FOR THE FOLLOWING: - CAR LIGHT AND ALARM CIRCUIT WITH GFCI PROTECTION PER NEC - GROUP CONTROL WHEN REQUIRED NOTE: IF STANDBY POWER IS SUPPLIED TO ELEVATOR, CAR LIGHT AND ALARM CIRCUIT AND GROUP CONTROL SERVICE MUST BE STANDBY POWER BACKED. 6. BRANCH CIRCUIT CONDUCTOR SIZING, MATERIALS, AND INSULATION (INCLUDING BRANCH CIRCUIT OVERCURRENT PROTECTIVE DEVICE) TO COMPLY WITH ALL LOCAL ELECTRICAL CODES. FIN. FLR. AMPS STARTING CURRENT WITH A MAX. ALLOWABLE VOLTAGE DROP OF 10%. AMPS FULL LOAD CURRENT WITH A MAX. ALLOWABLE VOLTAGE DROP OF 5%. AMPS RATED CURRENT WITH A MAX. ALLOWABLE VOLTAGE DROP OF 5%. 9" FINISHED FLOOR WITH ACTUAL OVERALL CAB HEIGHT = 7'-11" TOP OF O.A. CAB WITH CAB 7'-4" CEILING HEIGHT 10'-0 1/2" UNDER CROSSHEAD 7'-0" CLEAR OPENING 8'-3" 4. PIT LIGHTS AND SWITCH, CONVENIENCE OUTLETS WITH GFCI PROTECTION PER NEC, PIT LADDER MIN. ROUGH OPENING ABOVE 100 FPM 12'-5" MINIMUM CLEAR REQUIRED WITH TOP OVERTRAVEL OF 3" AT 100 FPM OR LESS S = 3.27 I = 9.82 A = 1.85 THE FOLLOWING CONDITIONS MUST BE MET BEFORE INSTALLATION IS COMPLETED, AND ARE NOT INCLUDED IN THE ELEVATOR CONTRACT: C 12'-2" MINIMUM CLEAR REQUIRED NET AREA CAR BUFFER STROKE: 2 1/2" BETWEEN PIT FLR. & CAR BOLSTER ON COMPRESSED BUFFER: 2'-2 5/8" SUPPORT TO BE PROVIDED BY GENERAL CONTRACTOR. 2" NOTE: VENT HOISTWAY AS REQUIRED WALL THK: BOTTOM CAR RUNBY: 6" TOP GUIDE RAIL BRACKET TO BE INSTALLED AS REQ'D. ABOVE FINISHED FLOOR IN OVERHEAD. BOTTOM WALL THK: C NOTE: ALSO, A FOURTH WIRE OF SAME SIZE AS THREE PHASE WIRES IS REQUIRED FOR GROUNDING A FLOOR-FLOOR PURPOSES TO MINIMIZE ELECTRICAL NOISE INTERFERENCE. THE GROUNDING WIRE MUST BE CONNECTED TO THE BUILDINGS ELECTRICAL SYSTEM GROUND. IF BATTERY OPER. LOWERING IS PROVIDED, A MECHANICAL AUX. CONTACT SHALL BE TRAVEL INSTALLED ON THE DISC SW. FOR EA. CAR. THE AUX. CONTACT SHALL BE = RAIL BRACKET MOUNTING SURFACE CONFIGURED AS SPST AT 1A 110VAC (MIN). THE AUX. CONTACT SHALL BE OPEN WHEN THE DISC SW. IS IN THE OPEN POSITION. IF A SHUNT TRIP CIRCUIT BREAKER IS PROVIDED, AN AUX. CONTACT SHALL BE INSTALLED ON THE CIRCUIT BREAKER. 8'-2" CLEAR HOISTWAY MAXIMUM UNSUPPORTED RAIL BRACKET SPACING = 12'-0" 3'-8" 2 3/4" GEN. CONTRACTOR MUST FORWARD POWER REQUIREMENTS TO ELEC. CONTRACTOR. 4'-6" 6'-10 1/2" BACK TO BACK OF GUIDE RAILS 7. AN ENCLOSED MACHINE AREA (ACCORDING TO CODE), WITH ADEQUATE LIGHT, HEAT, 1'-0 3/4" AND VENTILATION (MIN. 50°F., MAX. 90°F. WITH NON-CONDENSING HUMIDITY OF 10-90%), AND SEALED CONCRETE FLOOR SLAB SURFACE. NOTE: MUST PROVIDE ADEQUATE DOOR SIZE TO ALLOW INSTALLATION OF EQUIPMENT, 6'-3" BETWEEN GUIDE RAILS NET TRAVEL 1 1/2" + + 1 1/2" 8" 6'-0" PLATFORM OR LEAVE WALL OUT UNTIL EQUIPMENT IS IN PLACE. 1'-6" 8. ENTRANCE WALL WITH LINTELS MUST BE PROVIDED AFTER ENTRANCE FRAMES ARE SET OR LEAVE A ROUGH OPENING 15" WIDER AND 15" HIGHER THAN THE FRAME 5'-8" MIN. CLEAR INSIDE SUMP PIT BY G.C. 8" WIDE x 8" HIGH ELEC. RACEWAY, 8" x 8" PIPE SLEEVE, LOCATION TO BE COORDINATED WITH ELEVATOR SUPT. NOTE: MUST BE LOCATED AS DIRECTED BY ELEVATOR CONTRACTOR 12. PIPE SLEEVES, TRENCHING, AND BACK FILLING FOR OIL AND/OR CONDUIT LINES C C CAR RIDING LANTERN: RAIL FORCES 5" F1 F2 F1 F2 5'-0 1/4" 3" 4'- 0" PIT DEPTH VERIFY PLEASE 8'-9" PLATFORM 1'-0" C JACK (TYP.) FINISHED FLOOR LEVEL. 7'-9 1/2" MIN. CLEAR INSIDE C C BUFFER CAR STATION: 9'-6 1/2" WALL TO WALL C GUIDE RAILS AS SHOWN OR LOCATED BY ELEVATOR CONTRACTOR. MOUNT RAIL BRACKETS AT 9" BELOW EACH OIL LINE 9. POCKETS IN CORRIDOR WALL (PER FIXTURE DRAWINGS) FOR HALL FIXTURES. 11. CONDUIT AND WIRING FROM HOISTWAY TO ELEVATOR MONITORING PANELS (FOR SECURITY, LIFE, SAFETY, OR FIRE REQUIREMENTS). 4" FINISHED FLOOR TO ENSURE CONFORMANCE WITH THE LABELED ENTRANCE INTERFACE CONSTRUCTION. 10. SMOKE SENSORS (AS REQUIRED). SELECT. 7'-0" CLEAR OPENING PRIMARY FIRE SERVICE LOCATED AT FLR: W/ ALT AT FLR: MIN. ROUGH OPENING 8'-3" NOTE: IF DISTANCE BETWEEN FLOOR LEVELS EXCEEDS MAXIMUM, AN ADDITIONAL GUIDE RAIL BRACKET MUST BE PROVIDED MIDWAY. OPENING. SEE INSTALLATION PROCEDURES FOR FRAME-TO-WALL INTERFACE DETAILS 1 3/4" TOTAL TRAVEL 1'-0" BOTTOM O.T. JACKS C TOP O.T. PLEASE VERIFY 578 LBS. 667 LBS. OMEGA RAILS CAR STA. S DATE FRONT LEFT 7 3/4" AMEE 45 HLS Twin Post LH POWER REQUIREMENTS STATED IN NOTE 6 VERIFIED BY: HS 4 1/2" FACE OF RAIL SECTION VIEW NOT TO SCALE 11" 3 1/2" 4" 4'-6" CLEAR OPNG. 5'-9" ROUGH OPNG. 6'-8" BETWEEN CENTER LINE OF JACKS SYM. BY REVISION DESIGNED PER ASME A17.1 CHKD. DO NOT SCALE THIS DRAWING FOR: ELEV # ADDRESS: 2'-9" 2'-1 1/2" 1'-2" CITY: ARCHITECT: GENERAL CONTRACTOR: ELEVATOR CONTRACTOR: A HOISTWAY PLAN This drawing and all information thereon is the proprietary property of ThyssenKrupp Elevator and must not be made public or copied. This drawing is loaned subject to return on demand and is not to be used directly or indirectly in any manner detrimental to the interest of ThyssenKrupp Elevator. NOTE A: OIL PIPE LINES AND FITTINGS SHALL BE PROPERLY SUPPORTED TO RELIEVE STRAIN. NOTE B: ALL REACTIONS INCLUDE ALLOWANCE FOR IMPACT. NOTE C: THYSSENKRUPP ELEVATOR TO BE NOTIFIED OF ANY CHANGE TO ELEVATOR HOISTWAY OR MACHINE ROOM DESIGN. NOTE D: ELEVATOR DESIGN & FABRICATION BASED ON ESTIMATED CAB WEIGHT SHOWN. LAYOUT APPROVAL WILL BE CONSTRUED AS FINAL CAB WEIGHT, UNLESS OTHERWISE NOTIFIED. DRAWN DATE CHKD. BRANCH JOB NUMBER C45LHTWIN461 DRAWING NO. REV. SHEET NO. 1 OF 1