Flow PDF

advertisement
FLOW
HUMIDITY
Kele Provides Solutions for Air and Fluid Movement, Measurement, and Control.
220B | p. 291
NFP Series | p. 310
626600A | p. 320
FLOW
KOAMS | p. 273
Recordall | p. 337
Disc Meter
EE65 | p. 282
FLOW
Products manufactured
in the United States
Products that are
new to the catalog
DTFXL Series | p. 301
FLOW
FT2A Series | p. 286
DPFS Series | p. 280
kele.com
MODEL/SERIESPAGE
Air Flow
KOAMS Series — Kele Outdoor Airflow Measuring System . . . . . . . . . . . . . .
KMS Series — Airflow Measuring Station . . . . . . . . . . . . . . . . . . . . . . . . . . . .
KIP Series — Fan Inlet Airflow Measuring Probe. . . . . . . . . . . . . . . . . . . . . . .
160 Series — Stainless Steel Pitot Tubes. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FXP Series — Differential Pressure Air Velocity Sensors. . . . . . . . . . . . . . . . .
AMP Series — Ampliflow Air Velocity Sensor. . . . . . . . . . . . . . . . . . . . . . . . . .
DPFS Series — Low-Cost Differential Pressure Flow Sensor . . . . . . . . . . . . .
SSS-1000 Series — Differential Pressure Flow Sensors. . . . . . . . . . . . . . . . .
EE65 and EE66 Series — Air Velocity Transmitters. . . . . . . . . . . . . . . . . . . . .
AVS-200 — Air Velocity Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A2G-20 Series — Air Flow. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FE-1000 Series — Insertion Type Airflow Sensing Element. . . . . . . . . . . . . . .
FE-1050 Series — Fan Inlet Airflow Sensing Element. . . . . . . . . . . . . . . . . . .
273
275
276
277
278
279
280
281
282
283
284
341
342
Gas Flow
FT2A Series — Thermal Mass Flow Meter. . . . . . . . . . . . . . . . . . . . . . . . . . . . 286
Liquid Flow
SDI Series — Flow Sensor with Integral Flow Transmitter . . . . . . . . . . . . . . . .
200 Series Overview — Flow Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
220B, 220SS — Brass & Stainless Steel Flow Sensors. . . . . . . . . . . . . . . . . .
225B, 226B, 226SS Series — Hot Tap Flow Sensors . . . . . . . . . . . . . . . . . . .
228B, 228C, 228SS — Tee-Mounted Flow Sensors. . . . . . . . . . . . . . . . . . . . .
250B — Tee Mounted Flow Sensor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
228PV Series — PVC Tee Flow Sensors. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
310 Series — Programmable Analog Flow Transmitter . . . . . . . . . . . . . . . . . .
UFT-1 Series — Universal Flow Transmitter. . . . . . . . . . . . . . . . . . . . . . . . . . .
3000, 3050 Series — Flow and Energy Monitor. . . . . . . . . . . . . . . . . . . . . . . .
DTFXL Series — Ultrasonic Flowmeter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
M-2000 Series — Magnetic Flow Meter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2200, 3100 Series — Fixed and Retractable Insertion Vortex Flow Meters . . .
V-BAR 700 — Insertion Vortex Flow Meter. . . . . . . . . . . . . . . . . . . . . . . . . . . .
NFP Series — Target Flow Meter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
340 Series — BTU Transmitter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
380 Series — BTU Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DE/DB Series — Ultrasonic Energy Meter, Flow Meter . . . . . . . . . . . . . . . . . .
626600A — Paddle Flow Switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FS1-6 — Flow Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
F61 Series — Flow Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EDC Condensate Pumps — COU, LIM, JAG, and PAN Models. . . . . . . . . . .
DXN Series — Portable Ultrasonic Flow and Energy Meter. . . . . . . . . . . . . . .
IOG Series — Industrial Oval Gear Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RCDL Compound Series — Recordall® Compound Series Meter . . . . . . . . .
RCDL Nutating Disc — Recordall® Nutating Disc Meters . . . . . . . . . . . . . . . .
RCDL Turbo Series — Recordall® Turbo Series Meters . . . . . . . . . . . . . . . . .
289
290
291
292
293
294
295
296
297
299
301
303
307
309
310
312
314
316
320
322
324
326
327
331
335
337
339
NEW!
FLOW
KELE OUTDOOR AIRFLOW MEASURING SYSTEM
KOAMS SERIES
DESCRIPTION
The Kele KOAMS Series outdoor airflow measuring
system consists of multiple airflow elements, factory
mounted and pre-piped in a casing designed for flanged
connection to ductwork, control dampers, louvers, etc. An
optional inlet bell is available for plenum applications. The
integral signal processor utilizes current state-of-the-art digital
microprocessor technology with unequaled 24-bit A/D and
12-bit D/A signal conversion resolution and has twelve-point
linearization capability. The KOAMS is capable of measuring
down to 100 fpm and providing full scale operating ranges as
low as 693 fpm. The signal processor accepts a temperature
input signal for air density compensation for standard (scfm)
or actual (acfm) airflow calculations.
6
KOAMS with Inlet Bell
FEATURES
•
•
•
•
•
•
•
•
•
Full scale spans as low as 693 fpm (3.52 m/s) velocity
Excellent AD/DA resolution: 24-bit A/D and 12 bit D/A
Twelve point linearization and four point flow correction
Large back lit LCD for configuration and local indication
of the measured process
Auto zeroing function
Temperature compensation for air density correction
NEMA 4 rated enclosure
Modbus communication
Certified LonWorks® or BACnet MS/TP® communication
option
FLOW
• Accuracy of ±0.5% through the velocity range of 200 to
1,200 fpm and ±5% accuracy at 100 FPM
• Multiple total and static pressure sensing ports to
comply with ASHRAE Standard 111 for duct traversing
• Not affected by condensation or moisture
• Aerodynamically designed to resist fouling by airborne
particulates
• Factory mounted and pre-piped in a flanged duct
section (casing)
• Optional inlet bell for plenum applications
• Airflow station can be operated in humidity ranges of 0
to 100% with no effect on the station
SPECIFICATIONS
Supply Voltage
Supply VA
20 to 28 VAC/VDC
Standard processor: 4.6 VA at 24
VAC, 2.7 VA at 24 VDC
Full-option processor: 6 VA at 24
VAC/VDC
Accuracy
Within ±0.5% of actual flow through
the range of 200 to 1,200 fpm,
and ±5% at 100 fpm velocity,
when installed in accordance with
publlished recommendations
Operating TemperatureProcessor: 32° to 122°F (0° to 50°C)
Station: up to 350°F (177°C)
continuous operation
Operating Humidity
Processor: 0 to 95% RH, noncondensing
Station: 0 to 100% RH
Velocity Range
100 to 2,800 fpm
March 2014
Materials Of Construction
Elements: 6063-T5 anodized
aluminum
Casing: 16 ga. G90 galvanized steel
(other materials available special
order)
Enclosure Rating
NEMA 4X with proper connectors
Dimensions
Processor housing 6.7"H x 4.7"W x
2.7"D (16.9 x 11.9 x 6.9 cm)
Analog Output
Jumper selectable 0-5 VDC, 0-10
VDC (1KΩ minimum), or 4-20 mA
(500Ω maximum)
Digital Outputs
Optional high/low alarm, two single
(one Form C) dry contact
Contact Rating
5A at 30 VAC/VDC, 10A at 120 VAC
resistive load
Communication
LonWorks®, BACnet MS/TP®,
Modbus
WE MAKE IT EASY.
kele.com
888-397-5353 USA
273
FLOW
NEW!
KELE OUTDOOR AIRFLOW MEASURING SYSTEM
KOAMS SERIES
SIGNAL PROCESSOR FIELD CONNECTIONS
6
ORDERING INFORMATION
DIMENSIONS
FLOW
MODEL DESCRIPTION
KOAMS Outdoor airflow measuring system
CASING WIDTH (inches, minimum increments of 1/4")
CASING HEIGHT (inches, minimum increments of 1/4")
CASING LENGTH (5", 8", 12"; custom lengths available)
“W”
“L”
PROBE DIRECTION
“F”
Static
pressure
port
2
Casing height
SIGNAL PROCESSOR MOUNTING LOCATION
3
Flow
Total
pressure
port
Remote
OUTPUT
“H”
1
4-20 mA
2
0-5 VDC
3
0-10 VDC
2
TEMPERATURE TRANSMITTER
OPTIONS
Flanged Stations for Ducted Applications
1
Inlet bell (not available w/5˚ casing)
3
High/Lo alarm
4
LonWorks Communication
5
BACnet MS/TP Communication
6
Modbus Communication
7
Optional 0.1% F.S. Accuracy
“W”
“L”
“F”
Static
pressure
port
KOAMS - 20 - 30 - 12 - 2 - 3 - 1 - 2 - 1
Flow
Example: KOAMS-20-30-12-2-3-1-2-1
20" x 30" station with 12'' casing length,
4-20 mA output, and inlet bell
“H”
Total
pressure
port
4"
Stations with Optional Inlet Bell for Plenum Applications
Note: Dimension "F"= 1-1/2' (stations 8'-72") or 2' (stations > 72")
274
888-397-5353 USA
kele.com
KOAMS-TT
RELATED PRODUCTS
Replacement outside air temperature transmitter
(-30° to 130°F)
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
FLOW
AIRFLOW MEASURING STATION
KMS SERIES
DESCRIPTION
The Kele KMS Series airflow measuring stations utilize
multiple averaging sensors for static pressure measurements
and a bullet-nose probe for total pressure. The sensors are
distributed across the flow stream to conform to the industry
standard rules for equal-area averaging (the standard pitot
traverse). The standard unit includes a 16-gauge galvanized
casing with flanged duct connection, 3/8'' hexagon-celled
aluminum flow straightening vanes, and internal copper
sensors constructed to ASTM B88. Instrument connections
are 1/2'' FNPT. Other configurations are available on request.
APPLICATION
When utilized with a differential pressure transmitter, the
KMS Series provides an accurate, repeatable airflow signal
for building automation and HVAC applications. Air velocity
may be determined by the formula: Velocity (fpm) = 4004√∆P,
where ∆P is differential pressure in "W.C. Then, flow rate
may be determined by the formula: CFM = AV, where A is the
effective area of the flow measuring station in square feet,
and V is the velocity obtained above. The proper range for a
differential pressure transmitter to use with the KMS Series
airflow measuring station may be determined by the formula:
∆P = (Max Velocity/4004)2.
KMS Front and
Back
6
SPECIFICATIONS
1/2" FNPT HI/LO pressure pickups,
factory-mounted on the long
side dimension when station is
rectangular
Accuracy
±2% within design flow range
Minimum Velocity
1000 fpm (305 mpm)
Maximum Velocity
6000 fpm (1830 mpm)
Mounting
Duct flanges standard
Media Compatibility
Clean HVAC duct air
Media Temperature Range
400°F (204°C) maximum
Maximum Pressure
6" W.C. maximum duct static
Pressure Drop
<0.13" W.C. @ 2000 fpm
Materials Of Construction
Casing: 16-gauge galvanized sheet
steel; pickup sensors: rigid copper
(hard drawn to ANSI H23.1 and
ASTM B88 standards); internal
fittings: copper (ANSI B-16.22);
straightening vanes: 3/8" aluminum
hexagon cell
Dimensions
Casing depth 12" (30.5 cm);
H x W dimensions made-to-order
Warranty
1 year
FLOW
Connections
ORDERING INFORMATION
MODEL
KMS
KMS
DESCRIPTION
Airflow measuring station
SHAPE
811 Round with flanges
911 Rectangular with flanges
DIMENSIONS
W x H Diameter or width x height (inches)
911
48 x 24 Example: KMS-911-48 x 24 Rectangular airflow station with 16-gauge galvanized
casing, 3/8'' straightening vanes, and copper probes 48'' wide x 24'' high
Note: Standard location for flow connections is on the "long" dimensions side of a rectangular station. Stations can
be rotated. If connections must be located on the "short" side, specify it on the order; a cost adder applies.
KMS-PAK-B
March 2014
ACCESSORIES
1/2" FNPT to 1/4" OD tubing barb fitting
WE MAKE IT EASY.
kele.com
888-397-5353 USA
275
FLOW
NEW!
FAN INLET AIRFLOW MEASURING PROBE
KIP SERIES
DESCRIPTION
The Kele KIP Series fan inlet airflow measuring probe
provides a reliable and economical means to measure airflow
at fan inlets. Similar to airflow stations, the probe measures
velocity pressure with multiple averaging pickups for total and
static pressure. Rugged, lightweight, and easy to install, it is
used with industry-standard differential pressure transmitters,
gauges, or manometers. KIP Series probes install easily at
the fan inlet and do not require straight duct runs. They are
particularly applicable for jobs where fitting a flow measuring
station is difficult or impossible.
6
FEATURES
• Easy and quick to install
• Accurate and repeatable
• Economical
• Lightweight and rugged
• No straight duct runs required
• High velocity, high differential
• Standard airflow calculations
For fan inlet depth > 3.5"
For fan inlet depth
0.5" to 3.5"
FIGURE 1. FAN INLET
FLOW
SPECIFICATIONS
Connections
3/16" barbs for 1/4" OD poly tubing
Accuracy
±2% within design flow range
Minimum Velocity
400 fpm (122 mpm)
Maximum Velocity
12,000 fpm (3658 mpm)
Mounting
Drill/screw on fan inlet
Media Compatibility
Clean HVAC duct air
Media Temperature Range
400°F (204°C) maximum
Materials Of Construction
Aluminum with anodized finish
Dimensions
Made-to-order
Warranty
1 year
1
2
Distance
varies with
inlet
diameter
2
Inlet Flow View
Y
Mount ultraprobe
in smallest diameter
Isometric View
Dimension Y is the smallest fan inlet diameter. The probes will be built
for proper spacing using this dimension, which is required for ordering.
APPLICATION
The fan inlet diameter (dimension Y) shown in Figure 1, must be correctly determined and specified. Each set of probes is made to order and
cannot be returned for credit if the dimensions are incorrectly specified.
If the fan inlet depth is 3.5" (8.9 cm) or greater, order the KIP-Y-3.5. Each KIP Series probe will have both static (low) and total (high) pressure
pickup barbs. “Tee” the high-pressure pickups together and the low pickups together. If the fan inlet depth is less than 3.5" (8.9 cm), order the KIPY-.5. One KIP Series probe will have a single static (low) pressure pickup barb, and the other probe will have a single total (high) pressure pickup
barb.
Determining the differential (velocity) pressure for a KIP Series probe is the same as for a pitot tube or flow measuring station (see KMS Series
catalog page for formulas).
ORDERING INFORMATION
Model
KIP-Y-.5
KIP-Y-3.5
Description
Probe set for fan inlet depth 0.5" to 3.5" (specify Y; = inlet diameter range 6" to 96" (15 to 244 cm)
Probe set for fan inlet depth > 3.5" (specify Y; = inlet diameter range 6" to 96" (15 to 244 cm)
Note: One KIP includes a pair of pickup probes for measuring airflow at a fan inlet. For dual inlet fans, two KIPs must be ordered.
CX, RX, XLdp Series
M264 Series
T-101
276
888-397-5353 USA
kele.com
RELATED PRODUCTS
Ashcroft differential pressure transmitters
Setra differential pressure transmitter
1/4" OD black poly tubing, 1 coil, 250 ft (76 m)
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
PAGE
1014
901
March 2014
NEW!
FLOW
STAINLESS STEEL PITOT TUBES
160 SERIES
DESCRIPTION
The Dwyer 160 Series stainless steel pitot tubes are
designed for use with differential pressure transmitters,
manometers, or air velocity gauges to measure air flow in
ducts. See Measuring Air Flow in the Technical Reference
Section for complete application information. The 160 Series
is designed per ASME and meets AMCA and ASHRAE
standards. Insertion depth is stamped on the side of the pitot
tubes, and the static pressure port is parallel to the sensing
tube to allow easy alignment with air flow. A Model A-158 split
flange mounting kit allows for simple, leak-free mounting of
the 160 Series.
160-12 tube and A-158 mounting flange
FEATURES
•
•
•
•
6
• Air velocity calculator, flow charts, and instructions
included
• 1/4" connections for 3/8" OD tubing
• Handy A-158 split flange for duct mounting
• One year warranty
304 stainless steel construction
ASME design
Accurate even with up to 15° misalignment
Insertion depth markings stamped on tube
DIMENSIONS
8.0 (20.32), 12.0 (30.48), 18.0 (45.72), 24.0 (60.96), 0.5 (1.27)
36.0 (91.44) or 48.0 (121.92)
FLOW
in
(cm)
Total pressure
connection
0.31
(0.79)
5.0
(12.7)
2.66
(6.75)
0.25 (Fits 3/8'' OD
(0.64) poly tubing,
Model T-110)
Static pressure
8 - 0.040 diameter holes
(0.10) equally spaced
Total pressure
0.125 diameter hole
(0.32) (face into air flow)
3.63
(9.21)
Static pressure
connection
0.25 (Fits 3/8'' OD
(0.64) poly tubing,
Model T-110)
Note: See Measuring Airflow in
the Technical Reference section
for application of 160 Series pilot
tubes for flow measurement.
ORDERING INFORMATION
MODEL DESCRIPTION
160
Stainless steel pitot tube
LENGTH
XX Length (inches) - 8, 12, 18, 24, 36, 48
160
March 2014
18
Example: 160-18 Pitot tube with 18" insertion length
CX, RX, XLdp Series
M264 Series
T-110
RELATED PRODUCTS
Ashcroft differential pressure transmitters
Setra differential pressure transmitter
3/8" OD black poly tubing, 1 coil, 250 ft (76 m)
A-158
ACCESSORIES
160 Series pitot tube mounting flange (required for duct mount)
WE MAKE IT EASY.
PAGE
1014
901
kele.com
888-397-5353 USA
277
FLOW
NEW!
DIFFERENTIAL PRESSURE AIR VELOCITY SENSORS
FXP SERIES
DESCRIPTION
The Kele FXP Series probe is a differential air pressure
sensor designed to measure air velocities in HVAC ductwork.
It uses multiple sensing points to measure total and static
pressures and incorporates a unique design to amplify the
differential pressure by approximately 2.5 times for accurate
measurement of air velocities down to 200 fpm. It is easy to
install and cost effective.
FEATURES
6
•
•
•
•
•
•
Multiple sensing points for greater accuracy
Easy installation
Chamfered sensing points for consistent readings
2% accuracy
2.5X signal amplification
Accepts 1/4" OD tubing
FXP -10
PERFORMANCE CHART
FLOW
INSTALLATION
Check that the FXP probe size corresponds with the duct or
terminal where it is installed.
The FXP probe is mounted in the duct by drilling a 1"
diameter hole.
Check that the air flow direction in the duct corresponds with
the arrow on the FXP probe.
For round ducts, install the FXP probe diagonally in the duct
for best results. This equalizes both horizontal and vertical
irregular air approach.
FXP Calibration Curve fpm
Air Velocity (fpm)
10.000
1.000
SIZING THE PRESSURE TRANSMITTER
•
•
•
•
•
CFM- Cubic feet per minute (customer furnished)
A- Area square feet (customer furnished)
V- Velocity feet per minute (customer furnished)
∆P- Differential pressure in WC"
Use formula B to calculate the ∆P for transmitter
V(FPM) = CFM
A
∆P = V
Kv
V = Kv * ΔP
Formula A
Formula B
FXP Calibration Chart
Size Kv
Size Kv
Size
4"
2225 7"
2450 12"
5"
2325 8"
2480 14"
6"
2400 10" 2440 16"
18" and up
2550
278
888-397-5353 USA
2
kele.com
Kv
2500
2525
2550
100
0.001
0.010
0.100
Differential Pressure ("w.g.) Fpm=2213
∆P
1.000
mps=11242
10.000
∆P
ORDERING INFORMATION
MODEL DESCRIPTION
FXP
FXP air velocity sensor
WIDTH
XX Duct width (up to 48")
RELATED PRODUCTS PAGE
T-101
1/4" OD black poly tubing, 1 coil, 250 ft (76 m)
901
M264 Series
Setra differential pressure transmitter
1014
CX, RX, XLdp Series Ashcroft differential pressure transmitters
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
FLOW
AMPLIFLOW AIR VELOCITY SENSOR
AMP SERIES
DESCRIPTION
The Kele AMP Series ampliflow air velocity sensor is
designed to measure air flow velocity in HVAC duct systems.
The design of the AMP Series allows it to amplify the
velocity pressure by a factor of three, which, in turn, allows
low air flow velocities to be accurately measured. Sensing
holes along the length of the tube yield an average velocity
pressure reading for greater accuracy. The simple design
of the AMP Series allows quick, easy installation in new or
existing ductwork.
AMP-18
FEATURES
Multipoint readings for average velocity pressure
Simple installation
Rugged, extruded aluminum construction
Double taps allow field check connections
Three-to-one ratio pressure signals
Adaptable to round, square, or oval ducts
1/4" barbs for 3/8" OD tubing
One year warranty
6
PERFORMANCE
AMPLIFLOW SENSOR CALIBRATION CURVE
5000
4000
3000
2000
INSTALLATION
Mount the AMP Series at least three (10 is ideal) duct
diameters downstream of coils, dampers, or elbows, and
through the width of the duct for best results. Cut a hole
0.75"H x 0.88"W (1.9 x 2.3 cm) in the duct. Drill holes in the
opposite side of the duct to allow the field pressure taps to
protrude through the duct. Remove the rubber caps from
the field pressure taps and insert the AMP Series into the
duct so that the field pressure taps protrude. Attach the AMP
Series to the duct with sheet metal screws and replace the
rubber caps on the field pressure taps.
AMPLIFLOW
VELOCITY PRESSURE
1000
900
800
700
600
500
FLOW
Air Velocity (fpm)
•
•
•
•
•
•
•
•
400
300
200
100
.01
.02
.03
.04 .05 .06.07.08 .1
.2
.3
.4
.5 .6 .7 .8 .9 1.0
1.5 2.0
∆P Pressure Drop ("W.C.)
Velocity (fpm) = 2213 ∆P
Velocity (mps) = 11.242 ∆P
ORDERING INFORMATION
MODEL DESCRIPTION
AMP
Ampliflow air velocity sensor
WIDTH
XX Duct width (up to 30")*
Note: The ampliflow will be constructed so that the field pressure taps
in the end of the sensing tube protrude through the duct.
* Lengths 30'' to 96'' available by special order.
Provide field-constructed support for sensors >30''.
Nailor Ind. U.S. Patent No. 4,735,100
CX, RX, XLdp Series
M264 Series
T-110
March 2014
RELATED PRODUCTS
Ashcroft differential pressure transmitters
Setra differential pressure transmitter
3/8" OD black poly tubing, 1 coil, 250 ft (76 m)
WE MAKE IT EASY.
PAGE
1014
901
kele.com
888-397-5353 USA
279
FLOW
NEW!
DIFFERENTIAL PRESSURE FLOW SENSOR
DPFS SERIES
The Kele DPFS Series differential pressure flow sensor
is the most economical way to sense airflow velocity in VAV
ducts, and other small size branch ducts in HVAC systems.
The DPFS Series is available in 4 different lengths for flow
sensing in duct sizes from 4" to 18" (10 to 46 cm) and can
reliably sense velocities above 1000 FPM (feet/minute) or 305
MPM (meters/minute).
FLOW
6
INSTALLATION
Select the appropriate DPFS model to fit the duct size; the
flow sensor length needs to be at least half the duct width
in order to get a good reading of the velocity pressure. The
DPFS-1 is for 4" to 6" ducts; the DPFS-2 is for 6" to 8" ducts;
the DPFS-3 is for 8" to 10" ducts and the DPFS-4 is for 10" to
18" ducts. Mounting the DPFS Series sensor requires a 7/8"
(2.2 cm) hole in the duct, through which the probe insert.
The DPFS requires 10 straight duct diameters upstream and
10 downstream for accurate readings. The sensor must be
mounted with the flow direction arrow accurately pointing in
the direction of the airflow. To ensure reliable performance,
the sensor pickup openings must be kept free of dirt and dust
accumulation.
Using 1/4" OD poly tubing, connect the DPFS "H" port to a
differential pressure gauge or transmitter "High" input port,
and the "L" port to the gauge or transmitter's "Low" input port
FLOW PERFORMANCE
0.900
0.800
Differential Pressure ("WC)
DESCRIPTION
0.700
0.600
DPFS-1
0.500
DPFS-2
DPFS-3
0.400
DPFS-4
0.300
0.200
0.100
0.000
500
1000
1500
2000
2500
3000
Velocity (FPM)
DPFS-1
DPFS-2
DPFS-3
DPFS-4
Velocity = 3285(√∆P)
Velocity = 3365(√∆P)
Velocity = 3490(√∆P)
Velocity = 3425(√∆P)
Notes: 1. Test data based on round duct sizes 6" (DPFS-1), 8" (DPFS-2),
10" (DPFS-3) and 12" (DPFS-4 )
2. Flow coefficients were derived by averaging data for each sensor size.
SPECIFICATIONS
Connections
3/16" (0.48 cm) OD connections for
1/4" (0.64 cm) OD poly tubing
Operating Temperature40° to 120°F (4° to 49°C)
Mounting Flange
4" x 2" flange with integral foam
gasket and two 3/16" holes spaced
3.3" (8.4 cm) center-to-center
Materials Of Construction
ABS
Dimensions
DPFS-1
4.0"W x 2.1"H x 3.6"L
(10.2 x 5.3 x 9.1 cm)
DPFS-2
4.0"W x 2.1"H x 6.0"L
(10.2 x 5.3 x 15.2 cm)
DPFS-3
DPFS-4
Approvals
Weight
DPFS-1
DPFS-2
DPFS-3
DPFS-4
Warranty
4.0"W x 2.1"H x 8.3"L
(10.2 x 5.3 x 21.1 cm)
4.0"W x 2.1"H x 10.6"L
(10.2 x 5.3 x 26.9 cm)
RoHS
0.04 lb (0.02 kg)
0.06 lb (0.03 kg)
0.07 lb (0.032 kg)
0.08 lb (0.036 kg)
2 years
ORDERING INFORMATION
MODEL
DPFS-1
DPFS-2
DPFS-3
DPFS-4
DESCRIPTION
Differential pressure flow sensor, 3.0" insertion, for 4" to 6" ducts
Differential pressure flow sensor, 5.2" insertion, for 6" to 8" ducts
Differential pressure flow sensor, 7.5" insertion, for 8" to 10" ducts
Differential pressure flow sensor, 9.7" insertion, for 10" to 18" ducts
CX, RX, XLdp Series
M264 Series
T-101
RELATED PRODUCTS
Ashcroft differential pressure transmitters
Setra differential pressure transmitter
1/4" OD black poly tubing, 1 coil, 250 ft (76 m)
Cost-saving 10-packs are available; order model with "...-10PAK" suffix.
280
888-397-5353 USA
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
PAGE
1014
901
March 2014
NEW!
FLOW
DIFFERENTIAL PRESSURE FLOW SENSORS
SSS-1000 SERIES
DESCRIPTION
The SSS-1000 Series airflow sensors sense differential (velocity)
pressure of VAV units and other locations in main or branch ducts.
Four different lengths allow selection of the sensor to yield accurate
readings on terminal box inlet diameters from 4" to 16" (10.2 to 40.6
cm).
SPECIFICATIONS
Operating Temperature Mounting
Length
SSS-1002
SSS-1003
SSS-1004
SSS-1005
Storage Temperature
Approvals
Weight
SSS-1002
SSS-1003
SSS-1004
SSS-1005
Warranty
1/4" (6.4 mm) OD connections, fit 3/8"
(9.5 mm) OD polyethylene tubing
40°F to 120°F (4°C to 49°C)
Integral flange with foam gasket
3.16" (8.0 cm) insertion
(one sensing point)
5.41" (13.7 cm) insertion
(two sensing points)
7.66" (19.4 cm) insertion
(three sensing points)
9.91" (25.2 cm) insertion
(four sensing points)
-40° to 140°F (-40° to 60°C)
RoHS
SSS-1000 Series
PERFORMANCE
0.04 lb (0.02 kg)
0.05 lb (0.02 kg)
0.06 lb (0.03 kg)
0.07 lb (0.03 kg)
2 years
DIMENSIONS
H
FLOW
3.5
(8.89)
in
(cm)
6
∆P Inches "W.C.
Connections
L
1.25
(3.18)
Flow
0.1875 (0.477) diameter
mounting holes (2)
1000
2000
Velocity (fpm)
2.75
(6.99)
SSS-1002
SSS-1003
SSS-1004
SSS-1005
Note: See specifications for insertion dimensions
Velocity = 3450
Velocity = 3300
Velocity = 3200
Velocity = 3200
∆P
∆P
∆P
∆P
INSTALLATION
The SSS-1000 Series sensor requires a 7/8" (2.22 cm) diameter cutout for the insertion portion and two pilot holes for sheet
metal screws or rivets to hold the flange against the ductwork. Sensors should be installed as level as possible to ensure accurate
velocity pressure readings.
ORDERING INFORMATION
Model
SSS-1002
SSS-1003
SSS-1004
SSS-1005
March 2014
Description
Differential pressure flow sensor, 3.16" insertion
Differential pressure flow sensor, 5.41" insertion
Differential pressure flow sensor, 7.66" insertion
Differential pressure flow sensor, 9.91" insertion
B-265
ACCESSORIESPAGE
Barb coupling, 3/8" OD tubing to 1/4" OD tubing
903
CX, RX, XLdp Series
M264 Series
T-110
RELATED PRODUCTS
Ashcroft differential pressure transmitters
Setra differential pressure transmitter
3/8" OD black poly tubing, 1 coil, 250 ft (76 m)
WE MAKE IT EASY.
PAGE
1014
901
kele.com
888-397-5353 USA
281
FLOW
AIR VELOCITY TRANSMITTERS
EE65 AND EE66 SERIES
DESCRIPTION
The E+E EE65 and EE66 Series airflow velocity transmitters are
ideal for accurate ventilation control applications. They incorporate
innovative hot film anemometer technology which guarantees good
accuracy at low airflow velocity and is superior to conventional
anemometers with commercial temperature sensors or NTC bead
thermistors. The hot film sensor is also less sensitive to dust and dirt,
for high reliability and low maintenance costs. The EE65 and EE66
series are available with current or voltage output with the measuring
range and the response time jumper selectable in the field.
The EE66 is specifically designed for very low airflow velocities and is
accurate down to approximately 30 fpm (0.15 m/s).
NEW!
FEATURES
6
• Adjustable insertion length for precise measurement
• Jumper selectable ranges and outputs for application
flexibility
• Jumper selectable time constant for signal stability
• Dust and splash-proof NEMA 4 (IP65) enclosure allows
installation in potentially wet areas
• Very low flow velocity EE66 model for clean rooms and other
low velocity applications
WIRING
DIMENSIONS
0.47 (12.0)
1.46
(37.2)
0.71
(18.0)
A
Power supply
24 VAC/VDC ± 20%
3.15
(80.0)
+
~
V+
~
FLOW
EE65-01-VB5
V+ = supply voltage
GND = ground
AV = airflow output
GND
AV
1
2
3
A = 3.9" (100) or
7.9" (200)
V/mA
3.15
(80.0)
SPECIFICATIONS
Supply Voltage
Supply Current
Output Signal
Loads
24 VAC ±20%, 50/60 Hz, 24 VDC ±20%
150 mA @ 24 VAC, 90 mA @ 24 VDC
0-10 VDC or 4-20 mA; jumper selectable
0-10 VDC output, 10kΩ minimum
resistance; 4-20 mA output, 450Ω
maximum resistance
Terminal strip with 1/2" NPT conduit
connector or M16x1.5 cable gland for
0.18" to 0.39" (0.45 to 10.0 cm) cable
diameter
Wiring
Accuracy
EE65
EE66
Response Time ±40 fpm (0.2 m/s), plus 3% of measured
value, at 68°F (20°C) and 45% RH
±7.9 fpm (0.04 m/s), plus 2% of measured
value, at 68°F (20°C) and 45% RH
0.7 or 4 seconds, jumper selectable
Operating Temperature
Probe= Electronics= Velocity Range
EE65
EE66
Enclosure Rating
Dimensions
-VB3
-VB5
Weight
-VB3
-VB5
Approvals
Warranty
-13°F to 122°F (-25°C to 50°C)
14°F to 122°F (-10°C to 50°C)
0-2000 fpm (0-10 m/s), 0-3000 fpm
(0-15 m/s) or 0-4000 fpm (0-20 m/s)
0-200 fpm (0-1.0 m/s), 0-300 fpm
(0-1.5 m/s) or 0-400 fpm (0-2.0 m/s)
NEMA 4 (IP 65)
3.2"H x 3.2"W x 5.4"D
(8.0 x 8.0 x 13.7 cm)
3.2"H x 3.2"W x 9.3"D
(8.0 x 8.0 x 23.7 cm)
0.25 lb (0.11 kg)
0.30 lb (0.14 kg)
CE, RoHS
1 year
ORDERING INFORMATION
282
MODEL
EE65-01-VB3
EE65-01-VB5
EE66-01-VB3
EE66-01-VB5
DESCRIPTION
Air velocity transmitter, probe length 3.9" (100 mm)
Air velocity transmitter, probe length 7.9" (200 mm)
Low flow transmitter, probe length 3.9" (100 mm)
Low flow transmitter, probe length 7.9" (200 mm)
691-K0A
DCP-1.5-W
RELATED PRODUCTS
Control transformer, 120:24 VAC, 40 VA, Class 2
Power supply, 24 VAC IN to 24 VDC OUT
888-397-5353 USA
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
PAGE
979
995
March 2014
NEW!
FLOW
AIR VELOCITY TRANSMITTER
AVS-200
DESCRIPTION
The Kele AVS-200 is an electronic air velocity transmitter
for use in HVAC systems, laboratories, and industrial
applications. It features three DIP switch-selectable velocity
ranges and two analog outputs (one voltage, one current).
The AVS-200 also has a selectable time constant (the time
it takes to register 63.2% of a velocity change) of 3 or 10
seconds. The sensing probe has an adjustable insertion
length of up to 8" (20.3 cm) and a 4.5' (1.4 m) cable.
AVS-200
FEATURES
•
•
•
•
Three DIP switch-selectable velocity ranges
Two analog outputs
Selectable time constant
Dust- and splash-proof (IP44) enclosure
6
SPECIFICATIONS
Supply Voltage
Supply VA
Output Signal
Loads
Wiring
Accuracy
Repeatability
Temperature Effect
WIRING
INSTALLATION
AVS-200
1
-
Internal Connection
2
+
24 VAC
3
4
5
0-20 mA
or
4-20 mA
0-10 VDC
Common
Note: Any device sharing a transformer with the AVS-200 must have a common power negative "-" and signal negative "-" terminal, and polarity must be
observed. Otherwise, a separate transformer must be used.
March 2014
Time Constant
63.2% for 3 or 10 seconds
Operating Temperature
Electronics
32° to 122°F (0° to 50°C)
Sensing Tip
-4° to 140°F (-20° to 60°C)
Velocity Range
0-1000 fpm (0.5.1 m/s), 0-2000 fpm
(10.2 m/s), or 0-3000 fpm (0-15.3
m/s); DIP switch selectable
Probe Length Range Adjustable 1" to 8" (2.5 to 20.3 cm)
Enclosure Rating
IP44
Approvals CE, RoHS
Weight
1.8 lb (0.8 kg)
Warranty
1 year
FLOW
24 VAC ±10%, 50/60 Hz
5 VA
0-10 VDC, 0/4-20 mA
0-10 VDC output: 1kΩ minimum
resistance; 4-20 mA output: 600Ω
maximum resistance
4.5' (1.4 m) cable from transmitter
to probe; screw terminals inside
transmitter housing
±5% of measured value plus 0.5%
of measuring range
0.5% of measuring range
Maximum 0.1%/°C (0.2%/°F)
The sensing probe must be installed through a 5/8"(16mm)
hole in the duct with the arrow on the mounting flange
pointing in the direction of the airflow. The tab on the
mounting flange should be aligned with the line on the probe
to ensure proper airflow measurement. The insertion length is
adjustable. Loosen the set screw, and move the probe to the
selected position. The scale on the probe shows the insertion
length. Always install the sensing probe downstream of filters
and coils. Avoid placement directly in the outside air stream.
For best accuracy, locate the sensing probe a minimum of 10
duct diameters (or widths) upstream of any obstruction and a
minimum of 10 duct diameters downstream.
ORDERING INFORMATION
MODEL
AVS-200
DESCRIPTION
Air velocity transmitter
691-K0A
RELATED PRODUCTS
Control transformer, 120:24 VAC, 40 VA, Class 2
WE MAKE IT EASY.
PAGE
979
kele.com
888-397-5353 USA
283
FLOW
AIR FLOW
A2G-20 SERIES
DESCRIPTION
The Wika A2G-20 Series air velocity transmitter is
jumper selectable and features a separate signal out for
temperature, three velocity ranges, and one temperature
range. Applications include supply and exhaust fan tracking;
clean room air; lab air handling and paint booth supply air. For
both the air velocity (FPM) and for the temperature signals,
the user can select either of two outputs (0-10V or 4-20 mA).
Additional options include a digital display and a SPDT relay.
The digital display shows both the measured value and the
relay settings.
6
FEATURES
• Three ranges; jumper selectable: 0 to 390 FPM, 0 to
1970 FPM, 0 to 3940 FPM
• One temperature range 32° to 122°F (0° to 50°C)
• User selectable output signals: 0-10V or 4-20 mA
• Duct installation
FLOW
NEW!
A2G-20 Series
SPECIFICATIONS
Supply Voltage
Output Signal
(Air Velocity)
Output Signal
(Temperature)
Wiring
Accuracy (Air)
0 to 390 FPM
0 to 1,970 FPM
0 to 3940 FPM
AC/DC 24V ± 10%
0-10 V (linear to FPM), load min or
4-20 mA (linear to FPM), load max
0-10 V (linear to °F), load min 1kΩ
or 4-20 mA (linear to °F), load max
400Ω
PG-gland M16
<19.6 FPM (±5%)
<98.1 FPM (±5%)
<196.2 FPM (±5%)
Accuracy
(Temperature)
>1.2°F (<0.5°C)
Velocity Range (Air)
0 to 390 FPM 2 m/s range selectable by jumper
0 to 1,970 FPM 10 m/s range selectable by jumper
0 to 3940 FPM 20 m/s range selectable by jumper
Temperature Range
32° to 122°F (0° to 50°C)
Operating Temperature32° to 122°F (0° to 50°C),
max. 85% rH
Enclosure Rating
Plastic (ABS) Nema 3
Approvals
RoHS, WEEE
Warranty
1 year
WIRING
284
888-397-5353 USA
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
FLOW
AIR FLOW
A2G-20 SERIES
DIMENSIONS
6
FLOW
ORDERING INFORMATION
March 2014
MODEL
A2G20-V00-3X-1AAF-M-Z
A2G20-V00-3X-1AAF-M-A
A2G20-V00-3X-1AAF-M-B
DESCRIPTION
Air velocity transmitter, no digital display and no relay
Air velocity transmitter with digital display, no relay
Air velocity transmitter with digital display and SPDT relay
DCPA-1.2
691-K0A
DCP-1.5-W
RELATED PRODUCTSPAGE
Power supply, 120 VAC IN to 24 VAC/24 VDC OUT 994
Control transformer, 120:24 VAC, 40 VA, Class 2 979
Power supply, 24 VAC IN to 24 VDC OUT 995
WE MAKE IT EASY.
kele.com
888-397-5353 USA
285
FLOW
THERMAL MASS FLOW METER
FT2A SERIES
DESCRIPTION
The Fox FT2A Series thermal mass flow meters are perfect
for measuring flow of natural gas, compressed air, propane,
oxygen, and most common gases. The flow meters measure
both flow rate and temperature with isolated 4-20 mA outputs
for both variables. In addition, a separate pulse output can be
used for logging total gas flow. The FT2A mass flow meters
measure gas flow velocity as low as 50 sfpm (standard feet/
minute) and as high as 50,000 sfpm, without the need for
temperature or pressure compensation.
6
Each flow meter is calibrated at the factory using the same
gas as the application. As a result, the FT2A more than
meets EPA accuracy requirements for monitoring both boiler
intake gas and combustion emissions.
FLOW
Standard models include a 2 line x 16 character bright white
backlit display for viewing flow rate, flow total, elapsed time,
process gas temperature and alarms. The FT2A has an
integral keypad for setting parameters such as signal spans,
pulse frequency scaling, pipe area, zero cutoff, filtering,
diagnostics and alarms.
The FT2A Series is available in two styles, inline or
insertion. The inline models (male NPT) include built-in flow
conditioners which reduce the need for long straight runs of
upstream and downstream pipe. The most common inline
sizes are 1/2" to 2" and other inline sizes are available. The
insertion models install in a 3/4" coupling (field provided) and
are available in insertion lengths to fit pipes from 1-1/2" to 72".
Both inline and insertion styles come standard with stainless
steel wetted parts, an integral NEMA 4X enclosure rated for
Class I, Div. 2, Groups B,C,D hazardous areas, and a NIST
calibration certificate.
NEW!
C
FM
US
APPROVED
APPLICATION
Natural gas, air, ammonia, biogas, butane, compressed air,
carbon monoxide, carbon dioxide, ethane, ethylene, helium,
hydrogen, methane, nitrogen, oxygen, propane, and more
FEATURES
• Measures gas flow rate in SCFM, SCFH, NM3M, NM3H,
KG/M, KG/H, and more, for complete choice in units
• Two 4-20 mA analog outputs, flow rate and temperature
• RS485-Modbus, Isolated BACnet MS/TP, Profibus-DP,
DeviceNet and Ethernet Modbus TCP models available
for network communication
• Insertion or inline mounting styles for installation
choices
• All welded 316SS sensor construction and no moving
parts for durability and long life
• Field programmable for flexibility in configuration
• Standard NEMA 4X enclosure designed for Class I,
Division 2, Groups B, C, and D
• NIST traceable calibration standard to assure accuracy
• Free FT2A View™ Software available
SPECIFICATIONS
Supply Voltage
Supply Watts
Output Signal
Wiring
Wiring Terminations
Communication
Interface
Accuracy
Temperature Repeatability
Mounting
286
24 VDC ±10%, 85-264 VAC
50/60 Hz
20 Watts DC, 12 Watts AC
2 isolated 4-20 mA outputs (one
for flow and one for temperature);
1 isolated pulse output 0-100Hz,
10V p/p for flow (can be used for
alarming)
Two 3/4" NPT conduit connections on
sides of housing
Screw terminals
USB Port-optional: for connection
to computer, models available with
RS485-Modbus
BACnet MS/TP, Profibus-DP,
DeviceNet and Ethernet Modbus
TCP
Flow: ±1% of reading, ±0.2% of full
scale
±1.8°F (±1.0°C) over -40° to 250°F
(-40° to 121°C)
±0.2% of full scale
1/2" MNPT pipe section to 2" MNPT
pipe section (standard inline), 3/4"
888-397-5353 USA
kele.com
MNPT coupling, 6" length probe for
1-1/2" to 6" pipes (standard insertion,
other lengths available)
Operating Temperature32° to 140°F (0° to 60°C)
Media Compatibility
Standard configuration for natural
gas; other gases such as air, biogas,
butane, carbon monoxide, carbon
dioxide, nitrogen, methane, oxygen,
propane, etc. optional.
Media Temperature
Range
-40° to 250°F (-40° to 121°C)
Maximum Pressure
Rating
300 psig (21 bar)
Materials Of
Construction 316 stainless steel sensor and flow
body
Enclosure Rating
NEMA 4X, designed for Class
I, Division 2, Groups B, C & D
hazardous areas
Approvals
CE, FM/FMc
Weight
8.0 lb (3.6 kg) to 10.0 lb (4.5 kg)
inline models, 6.0 lb (2.7 kg)
6" insertion model
Warranty
1 year
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
FLOW
THERMAL MASS FLOW METER
FT2A SERIES
WIRING
Figure 1: Connections for 24VDC Supply
Figure 2: Connections for Optional AC Power
+24VDC
24V Return
Earth Ground
AC
AC
76
76
)
FT2A
76
76
$& $& 76
4 to 20mA FLOW RATE
24VDC Return
+24VDC
4 to 20mA TEMPERATURE OR
FLOW RATE
Customer PLC or DCS
+24VDC
76
(+) (-)(
Figure 3: 4 to 20mA Output Wiring for Customer-Supplied Power Source
Earth Ground
24VDC Return
76
76
6
Figure 4: 4 to 20mA Output Wiring for Loop Power Provided by FT2A
Figure 5: Frequency/Alarm Output Isolated (Recommended)
24V
76
+
Customer PLC or DCS
FT2A
76
-
76
76
4 to 20mA FLOW RATE
-
+
2.4K to 10K OHM
4 to 20mA TEMPERATURE
OR FLOW RATE
+24VDC
Frequency or Alarm Output
-
24VDC Return
FLOW
Customer PLC or DCS
76
+
FT2A
76
76
76
DIMENSIONS
3.3
(8.4)
Signal
Wiring
Input
Power
1.4
(3.5)
Signal
Wiring
Input
Power
3.2
(8.1)
3.9
(10.0)
1.50
(3.8)
5.35
(13.6)
2x 3/4 inch NPT Female
7.12
(18.1)
7.12
(18.1)
MODEL TFH1000
Gas Mass Flowmeter & Temperature Transmitter
Female
“HH”
MODEL TFH1000
Gas Mass Flowmeter & Temperature Transmitter
“H”
“LL”
2x NPT Male Thread
FLOW
CL
CL
“L”
March 2014
WE MAKE IT EASY.
kele.com
888-397-5353 USA
287
FLOW
THERMAL MASS FLOW METER
FT2A SERIES
MODEL
FT2A
6
NEW!
ORDERING INFORMATION
DESCRIPTION
Gas Mass Flowmeter
PROBE/BODY
05P 1/2" MNPT Inline, flow range 0-48 scfm
075P 3/4" MNPT Inline, flow range 0-120 scfm
10P 1" MNPT Inline, flow range 0-192 scfm
125P 1 1/4" MNPT Inline, flow range 0-320 scfm
15P 1 1/2" MNPT Inline, flow range 0-450 scfm
20P 2" MNPT Inline, flow range 0-750 scfm
06IE Insertion, 6" probe, flow range (see table)
SENSOR MATERIAL
SS 316 Stainless steel sensor and flowbody
SENSOR TYPE
ST Standard, -40-250°F (-40-121°C)
ENCLOSURE/POWER
E1 Local NEMA 4X, 24 VDC Power
E2 Local NEMA 4X, 85-264 VAC Power
BUS OPTIONS
B0 No communication bus
FLOW
MB Modbus, BN, BACnet, MS/TP
BN BACnet, MS/TP
BD DeviceNet
BP ProfiBus-DP
BE Ethernet Modbus TCP
CALIBRATION
G1 Air, N2; max flow less than 1200 SCFM (2040 NM3H)
G2 Air, N2; max flow greater than 1200 SCFM (2040 NM3H)
Ar, CO2, H2, CH4, Natural Gas, O2; max flow less than 1000 SCFM
G3
(1700 NM3H)
Ar, CO2, H2, CH4, Natural Gas, O2; max flow greater than 1000
G4
SCFM (1700 NM3H)
CO, He, Ammonia, Propane, Digester gas; max flow less than 700
G5
SCFM (1190 NM3H)
CO, He, Ammonia, Propane, Digester gas; max flow greater than 700
G6
SCFM (1190 NM3H)
Example: FT2A-05P-SS-ST-E1-B0-G3; 1/2" NPT inline, 316SS, standard temp., 24 VDC power,
display/keypad, no communication, for natural gas <1000 SCFM.
NOTE: An FT2A Series Application Data form must be filled out and sent in with the purchase order. Details
regarding application and media parameters are required for factory calibration. The form is located at www.kele.
com under Flow/FT2 Series/Related Products.
102299
102878
104870
DCP-1.5-W
DCPA-1.2
288
888-397-5353 USA
ACCESSORIESPAGE
90° elbow mounting kit, makes housing upright in vertical pipe installations
Teflon ferrule kit, for ease in removal of the insertion models
USB Cable
Power supply, 24 VAC IN to 24 VDC Out
995
Power supply, 120 VAC In to 24 VAC/24 VDC Out
994
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
FLOW
FLOW SENSOR WITH INTEGRAL FLOW TRANSMITTER
SDI SERIES
DESCRIPTION
The Badger Meter SDI Series flow sensor has an integral
transmitter and is available in either brass or stainless steel.
Hot tap stainless steel models include isolation valve and
mounting hardware which enables flowmeter installation
and removal while the piping system is pressurized; system
shutdown is unnecessary. Hot tap stainless steel models
are also available for bidirectional flow measurement. The
impeller is rugged and non-fouling and requires no custom
calibration. The SDI Series is available with a frequency
output, analog output, or a scaled-pulse output and the
display is optional; programming is done using the A301-20
Programming Kit. Stainless steel models are available with a
PEEK (polyetheretherketone) tip for high fluid temperatures
(up to 300 °F).
SDI Series
6
FEATURES
•
•
•
•
•
•
•
•
Direct insertion or hot tap installation
Fits pipe sizes 1.5" to 36"+ (3.8 to 91+ cm)
Mounts in 1" NPT tap, weld-on or pipe saddle
Low pressure drop
Optional 8 character 3/8" (0.95 cm) LCD
NEMA 4X enclosure standard
Bidirectional models available
Field programmable with optional software
Supply Voltage
8-35 VDC
Supply Current
25 mA
Maximum Output Impedance
750Ω @ 24 VDC
Output Signal
Models with standard frequency pulse,
two-wire 4-20 mA, scaled pulse, or
bi-directional (hot-tap models only)
Wiring Terminations
Screw terminals
Conduit Connection
1/2" FNPT
Configuration
A-SDI Programming software kit,
includes 20' cable
Accuracy
± 1% of flow rate
Repeatability
± 0.5%
Display
One line, eight character 3/8" (.95 cm)
LCD, annunciators for rate, total, input,
output
Operating Temperature 14° to 150°F (20° to 65°C)
Velocity Range
0.3 to 20 fps (.09 to 6.1 mps)
Installation
Install in straight pipe section with a
minimum distance of 10 pipe diameters
upstream and 5 pipe diameters
downstream to any bend, obstruction or
transition
Mounting
1" MNPT, mount in Thredolet® or pipe
saddle
Media Temperature RangeMaximum 300°F (149°C) for PEEK tip;
180°F (82°C) for PPS tip
Maximum Pressure
1000 psig (6895 kPa) for stainless steel,
600 psig (4137 kPa) for brass
Pressure Drop
0.5 psid (3.5 kPa), or less, at 10 fps
velocity
Materials Of Construction Polypropylene enclosure with Viton®
sealed dacrylic cover, probe and sensor
materials vary by model number (see
ORDERING INFORMATION)
Enclosure Rating
NEMA 4X
Warranty
1 year
March 2014
MODEL DESCRIPTION
SDI Flow sensor with integral transmitter
MATERIAL
0D1N Stainless steel insertion with PPS tip for 1.5" to 10" pipes
0D2N Stainless steel insertion with PPS tip for 12"" to 36" pipes
0D3N Stainless steel insertion with PPS tip for 36"+ pipes
1D1N Brass insertion with PPS tip for 1.5" to 10" pipes
1D2N Brass insertion with PPS tip for 12" to 36" pipes
1D3N Brass insertion with PPS tip for 36"+ pipes
2D1N Stainless steel insertion with PEEK tip for 1.5" to 10" pipes
2D2N Stainless steel insertion with PEEK tip for 12" to 36" pipes
2D3N Stainless steel insertion with PEEK tip for 36"+ pipes
0H1N Stainless steel hot tap with PPS tip for 1.5" to 10" pipes
0H2N Stainless steel hot tap with PPS tip for 12" to 36" pipes
0H3N Stainless steel hot tap with PPS tip for 36"+ pipes
2H1N Stainless steel hot tap with PEEK tip for 1.5" to 10" pipes
2H2N Stainless steel hot tap with PEEK tip for 12" to 36" pipes
2H3N Stainless steel hot tap with PEEK tip for 36"+ pipes
OUTPUT
0 Standard frequency pulse
1 4-20 mA
2 Scaled pulse
5 Bidirectional, 4-20 mA + direction (hot tap, PPS tip only)
6 Bidirectional, scaled pulse (hot tap, PPS tip only)
DISPLAY
0 No display
1 LCD option (not available with output option 0)
CONSTRUCTION
0200 Viton O-ring, Carbide shaft, stainless steel
impeller, Torlon bearing (std)
1200 EPDM O-ring, Carbide shaft, stainless steel
impeller, Torlon bearing
SDI
2D1N
1
8132030
A-1027
A301-20
WE MAKE IT EASY.
1
FLOW
SPECIFICATIONS
ORDERING INFORMATION
0200 Example: SDI2D1N11200 Flow sensor with
integral transmitter, stainless steel
insertion with PEEK tip, 4-20 mA
output, display, standard construction.
ACCESSORIES
Replacement ball valve for hot tap install
Hot tap adapter nipple, required for hot
tap
Flow/BTU transmitter programming kit,
Includes cable
kele.com
888-397-5353 USA
289
FLOW
FLOW SENSORS
200 SERIES OVERVIEW
DESCRIPTION
6
The Badger Meter 200 Series flow sensors feature a sixbladed impeller with a proprietary nonmagnetic sensing
mechanism. The design provides higher and more constant
torque than four-bladed impeller designs and is less prone
to be fouled by waterborne debris. The forward curveshape, coupled with the absence of magnetic drag, provides
improved operation and repeatability at lower flow rates. This
is especially true where the impeller is exposed to metallic or
rust particles found in steel or iron pipes. As the liquid flow
turns the impeller, a low impedance signal is transmitted
with a frequency proportional to the flow rate. This signal
can travel up to 2,000' (610m) between the sensor and the
transmitter without the need for amplification. All sensors are
supplied with 20' (6.10m) of Belden type 9320 (two-conductor
shielded) cable. Standard construction of the 200 Series
sensors consists of EPDM O-rings, tungsten carbide shaft,
nylon impeller, and UHMWPE bearings.
228 SS-2
226B
250B
220B
FLOW
A complete line of flow transmitters is available for use with
these flow sensors. The 200 Series can be used for potable
water and the following pages contain details on each model.
NEW!
225B
SELECTION CHART
MODEL
DESCRIPTION
PIPE SIZE in (cm)
220B
220SS
225B
226B
226SS
228C-2
228B-2
228SS-2
2-1/2 (6.35) and up
2-1/2 (6.35) and up
2-1/2 (6.35) and up
2-1/2 (6.35) and up
2-1/2 (6.35) and up
2 (5.08)
2 (5.08)
2 (5.08)
250B
Brass, insertion type
Stainless steel, insertion type
Brass, retractable with gate valve
Brass, retractable with ball valve
Stainless steel, retractable with ball valve
Brass sensor in a 2" (5.08 cm) cast iron tee
Brass sensor in a 2" (5.08 cm) brass tee
Stainless steel sensor in a 2" (5.08 cm)
stainless steel tee
Removable sensor in a cast bronze tee
228PV
4000 Series
Removable sensor in a PVC tee
PVC
290
888-397-5353 USA
kele.com
1/2 (1.27) , 3/4 (1.91), 1 (2.54), 1-1/4 (3.18),
1-1/2 (3.81)
1-1/2 to 4 (3.81 to 10.16) PVC
1/2 (1.27), 3/4 (1.91), 1 (2.54) PVC
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
FLOW
BRASS & STAINLESS STEEL FLOW SENSORS
220B, 220SS
DESCRIPTION
The 220B (brass) and 220SS (stainless steel) flow sensors
mount in a 2" NPT pipe saddle or Thredolet® and are used
in general flow measuring applications in metallic or PVC
pipes from 2-1/2" to 40" (6.4 to 101 cm) size. Positioning nuts
on the three threaded retaining rods allow the sensor to be
accurately positioned to a standard insertion depth of 1-1/2"
into the pipe. When this insertion depth is maintained, and
there are at least 10 upstream and 5 downstream diameters
of straight uninterrupted flow, an accuracy of ±1% of actual
flow rate can be obtained between flow velocities of 0.5 to
30 ft/sec. The standard 200 Series flow sensor are rated
for water temperatures to 221 °F. For higher temperature
requirements, see the SDI Series.
220B
6
SPECIFICATIONS
Connections
Materials Of Construction
220B
Standard construction is Admiralty
brass UNS C44300 sleeve, glassreinforced nylon impeller, Pennlon®
UHMWPE bearings, tungsten
carbide shaft, glass reinforced PPS
housing, and ethylene propylene
EPDM o-rings (other materials
available special order).
220SS
Standard construction is 300
series stainless steel sleeve, glassreinforced nylon impeller, Pennlon®
UHMWPE bearings, tungsten
carbide shaft, glass reinforced PPS
housing, and ethylene propylene
EPDM o-rings (other materials
available special order).
Dimensions
7.1"H x 3" diameter (18.1 x 7.6 cm)
Approvals
CE
Weight
4.1 lb (1.9 kg)
Warranty
1 year
FLOW
2" MNPT
(mount in Thredolet® or tee)
Wiring
20' (6.1 m) Belden 9320 twoconductor shielded cable
Accuracy
±1% of full scale
Repeatability
±0.3% of full scale
Linearity
±0.2% of full scale
Rangeability
60:1
Velocity Range
0.5 to 30 fps (.15 to 9.0 mps)
Media Compatibility
Hot water, chilled water, water/glycol,
potable water (verify application is
compatible with flow sensor materials
of construction, check material
compatibility resources prior to
ordering)
Media Temperature Range
Maximum 221°F (105°C)
Maximum Pressure
400 psig (2758 kPa) @ 100°F
(37.8°C) media temperature
ORDERING INFORMATION
March 2014
MODEL
220B
220SS
DESCRIPTION
Brass flow sensor
Stainless steel flow sensor
310-00
UFT-1A
RELATED PRODUCTS
Programmable analog flow transmitter
Universal flow transmitter, pulse and calibrated 4-20 mA output
230-FRK
2X2.5-3THD
2X4-6THD
2X8-36THD
ACCESSORIES
Repair kit for 200 Series flow sensors (includes impeller, shaft, bearing, and O-ring)
2" Thredolet ® for 2-1/2" and 3" pipes
2" Thredolet ® for 4", 5" and 6" pipes
2" Thredolet ® for 8" to 36" pipes
WE MAKE IT EASY.
kele.com
PAGE
296
297
888-397-5353 USA
291
FLOW
HOT TAP FLOW SENSORS
225B, 226B, 226SS SERIES
DESCRIPTION
6
The Badger Meter 225B, 226B, 226SS Series hot
tap flow sensors feature an elongated sensor, special
mounting adapter, pipe nipple, and isolation valve to
allow the nonmagnetic impeller sensor to be installed
into a pressurized pipe while the pipe is in service. This is
accomplished by first attaching a 2'' saddle or Thredolet®
onto the pipe and screwing the nipple and isolation valve into
the saddle or fitting. A hole is then drilled through the pipe
using a commercial tapping machine. When complete, the
tapping apparatus is removed, the isolation valve is closed,
and the sensor is installed. The 225B, 226B, 226SS Series
can be used for pipe sizes 2-1/2" to 40" (6.4 to 101 cm).
The hot tap flow sensor is also recommended for any
application where it would be difficult to shut down or drain
the pipeline to remove the sensor for service. The overall
length of the sensor tube is 18" (46 cm); however, a clearance
height of 36" (91 cm) should be allowed for the fully extended
length of the insertion tool.
NEW!
Model HTT
Model 225B
Model 226B
SPECIFICATIONS
FLOW
Connections
Wiring
2" MNPT
20' (6.1 m) two-conductor 20 AWG U.L.
Type PTLC shielded cable
Accuracy
±1% of full scale
Repeatability
±0.3% of full scale
Linearity
±0.2% of full scale
Rangeability
60:1
Velocity Range
0.5 to 30 fps (.15 to 9.0 mps)
Media Compatibility
Hot water, chilled water, water/glycol,
potable water (verify application is
compatible with flow sensor materials of
construction, check material compatibility
resources prior to ordering)
Media Temperature RangeMaximum 221°F (105°C)
Maximum Pressure
225B
300 psig (2069 kPa) @ 100°F (37.8°C)
media temperature
226B, 226SS
400 psig (2758 kPa) @ 100°F (37.8°C)
media temperature
Materials Of Construction
225B, 226B
Standard construction is Admiralty brass
226SS
Dimensions
Approvals
Weight
225B
226B, 226SS
HTT
Warranty
UNS C44300 sleeve, glass-reinforced
nylon impeller, Pennlon® UHMWPE
bearings, tungsten carbide shaft, glass
reinforced PPS housing, and ethylene
propylene EPDM o-rings (other materials
available special order).
Standard construction is 300 series
stainless steel sleeve, glass-reinforced
nylon impeller, Pennlon® UHMWPE
bearings, tungsten carbide shaft, glass
reinforced PPS housing, and ethylene
propylene EPDM o-rings (other materials
available special order).
18"H x 3" diameter (46 x 7.6 cm) plus
valve handle
CE
17.5 lb (7.9 kg)
13.0 lb (5.9 kg)
12.0 lb (5.4 kg)
1 year
ORDERING INFORMATION
292
MODEL
225B
226B
226SS
DESCRIPTION
Brass hot tap flow sensor with gate-type isolation valve
Brass hot tap flow sensor with ball-type isolation valve
Stainless steel hot tap flow sensor with ball-type isolation valve
230-FRK
2X2.5-3THD
2X4-6THD
2X8-36THD
813144-1211
HTT
81873
ACCESSORIES
Repair kit for 200 Series flow sensors (includes impeller, shaft, bearing, and O-ring)
2" Thredolet® for 2-1/2" and 3" pipes
2" Thredolet® for 4", 5" and 6" pipes
2" Thredolet® for 8" to 36" pipes
Replacement sleeve assembly for 225B, 226B flow sensors
Hot tap tool
Replacement gate valve for 225B, 2"
310-00
UFT-1A
RELATED PRODUCTS
Programmable analog flow transmitter
Universal flow transmitter, pulse and calibrated 4-20 mA output
888-397-5353 USA
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
PAGE
296
297
March 2014
NEW!
FLOW
TEE-MOUNTED FLOW SENSORS
228B, 228C, 228SS
DESCRIPTION
The Badger Meter 228B is a brass flow sensor mounted
in a 2" bronze tee with 2" copper solder couplings included,
the 228C is a brass flow sensor mounted in a 2" cast iron tee,
and the 228SS is a stainless steel flow sensor mounted in a
2" stainless steel tee.
228 SS-2
SPECIFICATIONS
Connection Type
228B
228C, 228SS
Wiring
228C
228SS
Dimensions
Approvals
Weight
228B
228C
228SS
Warranty
6
FLOW
2" solder
2" FNPT
20' (6.1 m) 2-conductor 20 AWG shielded
UL type PTLC wire, rated to 221°F
(105°C). May be extended to 2000’
maximum with similar cable
Accuracy
±1% of full scale
Repeatability
±0.3% of full scale
Linearity
±0.2% of full scale
Velocity Range
0.5 to 30 fps (.15 to 9.0 mps)
Media Compatibility
Hot water, chilled water, water/glycol,
potable water (verify application is
compatible with flow sensor materials of
construction, check material compatibility
resources prior to ordering)
Media Temperature RangeMaximum 221°F (105°C)
Maximum Pressure
228B
200 psig (1379 kPa) @ 100°F (37.8°C)
media temperature
228C
175 psig (1207 kPa) @ 100°F (37.8°C)
media temperature
228SS
400 psig (2758 kPa) @ 100°F (37.8°C)
media temperature
Materials Of Construction
228B
Standard construction is cast bronze tee
(Class 125 per ASME B16.15), copper
couplings, admiralty brass UNS C44300
sleeve, glass-reinforced nylon impeller,
Pennlon® UHMWPE bearings, tungsten
carbide shaft, glass reinforced PPS
housing, and ethylene propylene EPDM
o-rings (other materials available special
order).
Standard construction is cast iron tee
(class 125 per ASME B16.4), admiralty
brass UNS C44300 sleeve, glassreinforced nylon impeller, Pennlon®
UHMWPE bearings, tungsten carbide
shaft, glass reinforced PPS housing, and
ethylene propylene EPDM o-rings (other
materials available special order).
Standard construction is 316 stainless
steel tee, 300 series SS sleeve, glassreinforced nylon impeller, Pennlon®
UHMWPE bearings, tungsten carbide
shaft, glass reinforced PPS housing, and
ethylene propylene EPDM o-rings (other
materials available special order).
8.4"H x 7.9"W x 3.0"D
(21.3 x 20.0 x 7.6 cm)
CE
8.8 (4.0 kg)
7.2 lb (3.3 kg)
12.0 lb (5.4 kg)
1 year
ORDERING INFORMATION
March 2014
MODEL
228B-2
228C-2
228SS-2
DESCRIPTION
Brass flow sensor mounted in a 2" (5.08 cm) bronze tee (copper solder couplings included)
Brass flow sensor mounted in a 2" (5.08 cm) cast iron pipe tee
Stainless steel flow sensor mounted in a 2" (5.08 cm) stainless steel pipe tee
230-FRK
813124-1211
ACCESSORIES
Repair kit for 200 Series flow sensors (includes impeller, shaft, bearing, and O-ring)
Replacement sleeve assembly for 220B, 228B, 228BC flow sensors
310-00
UFT-1A
RELATED PRODUCTS
Programmable analog flow transmitter
Universal flow transmitter, pulse and calibrated 4-20 mA output
WE MAKE IT EASY.
kele.com
PAGE
296
297
888-397-5353 USA
293
FLOW
TEE MOUNTED FLOW SENSOR
250B
DESCRIPTION
The Badger Meter 250B Series flow sensors consist of a
removable flow sensor mounted in a cast bronze housing.
They are available for 1/2'' to 1-1/2'' (1.3 to 3.8 cm) pipe sizes.
NEW!
250B-0.5
6
SPECIFICATIONS
reinforced nylon impeller, Pennlon®
UHMWPE bearings, tungsten
carbide shaft, glass reinforced PPS
housing, and ethylene propylene
EPDM o-rings
FLOW
Connection Type
Wiring
1/2" FNPT to 1-1/2" FNPT
20' (6.1 m) 2-conductor 20 AWG
shielded UL type PTLC wire, rated to
221°F (105°C). May be extended to
2000' maximum with similar cable
Accuracy
±1% of full scale
Repeatability
±0.7% of full scale
Linearity
±0.7% of full scale
Rangeability
60:1
Velocity Range
0.3 to 15 fps (.09 to 4.5 mps)
Media Compatibility
Hot water, chilled water, water/glycol,
potable water (verify application is
compatible with flow sensor materials
of construction, check material
compatibility resources prior to
ordering)
Media Temperature Range
Maximum 221°F (105°C)
Maximum Pressure
400 psig (2758 kPa) @ 100°F
(37.8°C) media temperature
Materials Of Construction
Cast bronze UNS C83600 tee, glass-
Dimensions
250B-0.5, -0.75
250B-1
250B-1.25
250B-1.5
Approvals
Weight
250B-0.5
250B-0.75
250B-1
250B-1.25
250B-1.5
Warranty
4.6"H x 4.0"W x 1.6"D
(11.7 x 10.2 x 4.1 cm)
4.8"H x 5.5"W x 2.1"D
(12.2 x 14.0 x 5.3 cm)
5.0"H x 6.1"W x 2.4"D
(12.7 x 15.5 x 6.1 cm)
5.2"H x 6.5"W x 2.6"D
(13.2 x 16.5 x 6.6 cm)
CE
4.6 lb (2.1 kg)
4.8 lb (2.2 kg)
6.2 lb (2.8 kg)
6.5 lb (2.9 kg)
7.6 lb (3.4 kg)
1 year
ORDERING INFORMATION
294
MODEL
250B-0.5
250B-0.75
250B-1
250B-1.25
250B-1.5
DESCRIPTION
Brass flow sensor mounted in a 1/2" (1.3 cm) NPT bronze pipe tee
Brass flow sensor mounted in a 3/4" (1.9 cm) NPT bronze pipe tee
Brass flow sensor mounted in a 1" (2.5 cm) NPT bronze pipe tee
Brass flow sensor mounted in a 1-1/4" (3.2 cm) NPT bronze pipe tee
Brass flow sensor mounted in a 1-1/2" (3.8 cm) NPT bronze pipe tee
310-00
813107-1211
UFT-1A
RELATED PRODUCTS
Programmable analog flow transmitter
Replacement sensor assembly for 250B, includes 20' cable
Universal flow transmitter, pulse and calibrated 4-20 mA output
888-397-5353 USA
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
PAGE
296
297
March 2014
NEW!
FLOW
PVC TEE FLOW SENSORS
228PV SERIES
DESCRIPTION
The Badger Meter 228PV flow sensors are designed to
measure water flow in PVC pipes. These sensors consist of
a removable, nonmagnetic sensor in a schedule 80 PVC tee
with solvent-weld socket end connections. They are available
in 1-1/2" to 4" (3.8 to 10.2 cm) sizes.
228PV
6
SPECIFICATIONS
Connection Type
Wiring
Materials Of Construction
PVC per ASTM D-2462 and D-2467
virgin unplasticized PVC resin,
approved for potable water, PPS
housing, EPDM o-ring, tungsten
shaft, nylon impeller, Pennlon
bearings
Dimensions
228PV1505
5.2"H x 5.0"W x 2.4"D
(13.1 x 12.7 x 6.0 cm)
228PV2005
5.6"H x 5.6"W x 2.9"D
(14.3 x 14.3 x 7.3 cm)
228PV3005
6.8"H x 6.5"W x 4.2"D
(17.3 x 16.5 x 10.7 cm)
228PV4005
6.8"H x 7.4"W x 5.4"D
(17.3 x 18.7 x 13.7 cm)
Approvals
CE
Weight
228PV1505
1.0 lb (.45 kg)
228PV2005
1.0 lb (.45 kg)
228PV3005
1.5 lb (.68 kg)
228PV4005
2.5 lb (1.1 kg)
Warranty
1 year
FLOW
Schedule 80 PVC
20' (6.1 m), 20 AWG two-conductor
shielded UL type PTLC cable, rated
to 221°F (105°C), may be extended
to 2000' maximum with similar cable
Accuracy
±1% of full scale
Repeatability
±0.3% of full scale
Linearity
±0.2% of full scale
Pulse Rate
3.2 to 200 Hz, 5 ms ±25% width,
9-20 VDC power @ 2 mA maximum;
5V CMOS and LSTTL compatible
Velocity Range
0.5 to 30 fps (0.15 to 9 mps)
Media Compatibility
Hot water, chilled water (verify
application is compatible with flow
sensor materials of construction,
check material compatibility
resources prior to ordering)
Media Temperature Range
Maximum 140°F (60°C)
Maximum Pressure
100 psig (689 kPa) @ 77°F (25°C)
media temperature, decreasing to 40
psig (276 kPa) @ 140°F (60°C)
ORDERING INFORMATION
March 2014
MODEL
228PV1505-1211
228PV2005-1211
228PV3005-1211
228PV4005-1211
DESCRIPTION
Flow sensor in 1-1/2" PVC tee, pulse output
Flow sensor in 2" PVC tee, pulse output
Flow sensor in 3" PVC tee, pulse output
Flow sensor in 4" PVC tee, pulse output
UFT-1A
RELATED PRODUCTS
Universal flow transmitter, pulse and calibrated 4-20 mA output
WE MAKE IT EASY.
kele.com
PAGE
297
888-397-5353 USA
295
FLOW
NEW!
PROGRAMMABLE ANALOG FLOW TRANSMITTER
310 SERIES
DESCRIPTION
The Badger Meter 310 Series programmable analog
flow transmitter is a loop-powered device that converts
the signal from a 200 or 4000 Series flow sensor into a
linear 4-20 mA signal. An integral, adjustable electronic filter
dampens the analog output for smooth, stable operation.
The microprocessor-based 310 Series can be ordered preconfigured, or it can be field-configured with a computer.
An A301-20 Programming Kit will configure all 310 Series
transmitters.
6
SPECIFICATIONS
FEATURES
• 4-20 mA loop powered
• Compact size
• Computer programmable
• Electronic signal dampening
Supply Voltage
Input Signal
Output Signal
Maximum Output
Impedance
Configuration
WIRING
24 VDC
Power
Supply
+
Shield (if applicable)
(black)
(red)
FLOW
_
200 Series
Flow Sensor
Power (4000 only)
Signal (+)
Signal (-)
Shield Ground
4-20 mA loop (+)
_
4-20 mA loop (-)
FLOW
4-20 mA
Signal
310-00
Calibration
Port
Sensor Inputs
+
Model 310
NOTE: Call Kele for
4000 Series wiring.
Accuracy
Response Time
Operating Temperature
Mounting
310-00
310-01
310-02
310-03
310-04
Dimensions
310-00, -04
310-01, -02, -03
Warranty
Loop powered, 9-35 VDC
0.4 to 10 kHz, unscaled raw pulses from
Data Industrial flow sensor, or sine wave
4-20 mA, 2-wire
750Ω @ 24 VDC
A301-20 programming kit (order
separately) cable connects to DIC
communication port and DB9 COM port
on a computer. Transmitter must be looppowered for programming (9-24 VDC will
work)
±0.04% of reading over entire span
Varies with filter, typically 1 second
10% to 90% step response
-20° to 158°F (-29° to 70°C)
Surface mount, transmitter only
Surface mount, in NEMA 4X enclosure
Surface mount, in metal enclosure
Surface mount, in plastic enclosure
DIN rail mount, with clips
1.8"H x 3.7"W x 1.5"D
(4.4 x 9.3 x 3.8 cm)
2.8"H x 4.5"W x 2.0"D
(7.1 x 11.3 x 5.1 cm)
1 year
ORDERING INFORMATION
MODEL
310
310
DESCRIPTION
Programmable analog flow transmitter
MOUNTING
00
Transmitter only
01
Transmitter in NEMA 4X enclosure
02
Transmitter in metal enclosure
03
Transmitter in plastic enclosure
04
Transmitter with DIN rail mount
OPTIONS
XR Pre-configured option
00
XR Example: 310-00-XR Preconfigured programmable
analog flow transmitter for field mounting
For preconfigured flow sensors, specify pipe size, schedule,
and maximum flow rate at time of order.
A301-20
200 Series
296
888-397-5353 USA
RELATED PRODUCTSPAGE
Flow/BTU transmitter programming kit, includes cable
Data Industrial impeller type flow sensors with pulse output
290
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
FLOW
UNIVERSAL FLOW TRANSMITTER
UFT-1 SERIES
DESCRIPTION
The Kele UFT-1 Series universal flow transmitter is a solidstate, digital signal converter designed to operate with Data
Industrial 200 Series flow sensors. Both analog (4-20 mA)
and pulse outputs are available. The UFT-1 may be mounted
in an optional NEMA 4X enclosure or with digital display of
gpm or totalized flow (in a non-watertight enclosure).
UFT-1
FEATURES
•
•
•
•
•
Analog and pulse outputs
Optional watertight (NEMA 4X) enclosure
Optional displays for flow rate and totalization
Excitation voltage for flow sensors
LED indication of pulse activity
UFT-1E-1
6
OPERATION
APPLICATION
INSTALLATION AND CALIBRATION
The UFT-1 transmitter can be mounted in any position. NEMA 4X
enclosed models have a watertight seal; when a display option is
selected, however, the enclosure becomes non-watertight. Field
calibration is not required with the UFT-1 and flow conversion must
be accomplished at the monitoring computer. The information below
is provided for making the conversion calculations.
ANALOG OUTPUT (RATE)
The UFT-1 analog transmitter converts a Data Industrial digital flow
signal into a precalibrated 4-20 mA signal. It must be calibrated for
each Data Industrial flow sensor installation. The pipe type, size, and
maximum flow rate must be specified at the time of order if 4-20 mA
output is to be used.
TOTALIZED FLOW
Totalized gallons = (Flow factor) x (Output divider) x (Total pulses)
For totalized m3, multiply the above by 0.00379.
Output divider = 10 or 100 depending on jumper-selection. Flow
factors per pulse are shown in Table 1.
FLOW
PULSE OUTPUT (TOTALIZATION)
The UFT-1 pulse output divides the Data Industrial digital flow signal
by a jumper-selectable 10 or 100 to provide a more usable digital
pulse. The pulse output is normally used where flow totalization is
required. A simple conversion formula (using the flow factors for Data
Industrial Flow Sensors on the next page) can convert the digital
pulses to totalized gallons.
The pulse output is an optoisolated transistor switch that can be
wired to source or sink pulses to totalizer equipment.
FLOW RATE
Flow (gpm) = ((mA measured - 4 mA) x Maximum gpm)/16 mA.
Maximum gpm is the flow rate at 20 mA output on the transmitter
and must be specified at the time the UFT-1 is ordered for proper
calibration.
NOTE: The UFT-1 Series is not intended for field setup or field
calibration.
SPECIFICATIONS
Supply Voltage
24 VDC
Input Signal
15 to150 Hz FS, dry or electric contact
Maximum Output Impedance
750Ω @ 24 VDC
Output Signal
UFT-1
Solid state switch;
UFT-1A
4-20 mA
Pulse Output
40 VDC @ 200 mA
Configuration
Factory configure only; provide pipe size/
schedule and maximum flow rate at time
Accuracy
Response Time
Operating Temperature
Operating Humidity
Mounting
UFT-1, -1A
UFT-1E, -1AE
Approvals
Warranty
of order
± 0.5%
5 seconds from 10% to 90%
32° to 140°F (0° to 60°C)
5% to 90% RH non-condensing
Snap track
Surface mount, enclosed
RoHS
18 months
WIRING
Output pulse divider
selection jumper
(10 or 100) 100
10
Pulse
out +
Pulse
out
Totalize
Pulse
out –
mA signal
out
(red)
XDCR
signal in
24 VDC
power
XDCR
Sig in
PWR Common
Transducer power option jumper
(Leave on for Data Industrial flow sensors.
Remove for devices with their own power supply.)
March 2014
+
Flow
sensor
(black)
+
–
+
– Power
Typical
totalizer
hookup
+ 4-20 mA
– Output
–
24 VDC
power supply
WE MAKE IT EASY.
kele.com
888-397-5353 USA
297
FLOW
UNIVERSAL FLOW TRANSMITTER
UFT-1 SERIES
DIMENSIONS
NEW!
FLOW FACTORS FOR DATA INDUSTRIAL FLOW
SENSORS
in
(cm)
MODEL
Pulse
out +
Pulse
out –
mA signal
out
XDCR
signal in
6
24 VDC
power
Common
FLOW
3 .25
(8 .25)
2 .19
(5 .56)
228PV-1.5
228PV-2
228B-2
228C-2
250B-0.5
250B-0.75
250B-1
250B-1.25
250B-1.5
220B-2.5
220B
220B
220B
220B
220B
220B
220B
220B
220B
220B
PIPE SIZE
in (cm)
FLOW
FACTOR
1-1/2 (3.81)
2 (5.08)
2 (5.08)
2 (5.08)
1/2 (1.27)
3/4 (1.91)
1 (2.54)
1-1/4 (3.18)
1-1/2 (3.81)
2-1/2 (6.35)
3 (7.62)
4 (10.16)
5 (12.7)
6 (15.24)
8 (20.32)
10 (25.40)
12 (30.48)
14 (35.56)
16 (40.64)
18 (45.72)
0.03118
0.04611
0.04579
0.04731
0.005646
0.007514
0.007015
0.01280
0.01780
0.03800
0.07280
0.1396
0.2457
0.3611
0.6710
1.080
1.630
1.944
2.502
3.158
GALLONS/PULSE
JUMPER IN
JUMPER IN
10 POSITION 100 POSITION
0.3118
0.4611
0.4579
0.4731
0.05646
0.07514
0.07015
0.1280
0.1780
0.3800
0.7280
1.396
2.457
3.611
6.710
10.80
16.30
19.44
25.02
31.58
3.118
4.611
4.579
4.731
0.5646
0.7514
0.7015
1.280
1.780
3.800
7.280
13.96
24.57
36.11
67.10
108.0
163.0
194.4
250.2
315.8
Notes
1. Flow factors for a Model 225 and 226 are the same as Model 220.
* 2. Flow factor for Model 228S is the same as 228C.
3. PV Series is sized for schedule 80 PVC pipe.
All other series are sized for schedule 40 black iron pipe.
ORDERING INFORMATION
MODEL
UFT-1
UFT-1A
UFT-1E
UFT-1AE
UFT-1
DESCRIPTION
Universal flow transmitter pulse output only
Universal flow transmitter with pulse and calibrated 4-20 mA output*
Universal flow transmitter pulse output in NEMA 4X enclosure
Universal flow transmitter with pulse and calibrated 4-20 mA output* in NEMA 4X enclosure
DISPLAY OPTION (enclosed models only,, enclosure changes to non-watertight)
1
Flow totalization only
2
Flow rate only
3
Flow totalization and flow rate**
1
maximum flow rate must be
specified at time of order.
** When a UFT-1AE3 is ordered
the UFT-1A will be in one enclosure
and the totalizer and rate display
will be in a separate enclosure.
Example: UFT-1A-E-2 Basic transmitter with calibrated 4-20 mA flow rate
output (4 mA = no flow; 20 mA = max flow), enclosed with LCD
flow rate indication
200 Series
DCP-1.5-W
298
* Pipe size, schedule, and
888-397-5353 USA
RELATED PRODUCTS
Data Industrial impeller type flow sensors with pulse output
Power supply, 24 VAC IN to 24 VDC OUT
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
PAGE
290
995
March 2014
NEW!
FLOW
FLOW AND ENGERY MONITOR
3000, 3050 SERIES
DESCRIPTION
The Badger Meter 3000 and 3050 Series flow and energy
monitors are economical, full-featured, compact units
designed for flow and BTU measurement applications. Outputs
include one mechanical relay and one solid state pulse output,
both featuring unit/pulse and set-point control independently
based on flow or total readings.
OPTIONAL FEATURES
An analog 4-20 mA or 0-20 mA output is optional and USB,
RS-485 Modbus, and BACnet/MSTP provide high-level
communication. A two-line by 16-character, 3/8" high backlit
LCD display is configured by the user to display flow rate and
flow total. Custom units can be created during field setup. The
flow sensor input features flexible scaling options and signal
type selections that permit the use of most Data Industrial
meter sensors, or other frequency (sine/pulse) or linear
devices. Matched 10 kΩ thermistors (ordered separately)
provide temperature differential for BTU calculations.
6
3050-1-0
One mechanical relay and one solid state relay output
Optional 0/4-20 mA output
USB, RS-485, Modbus, and BACnet/MSTP all in one unit
FLOW
FEATURES
• Menu-driven programming or Windows based
programming
• NEMA 4X rated enclosure
• Two-line x 16-character display
• Password-restricted access
• Non-volatile memory
• Temperature sensor zeroing
SPECIFICATIONS
Supply Voltage Input
8 to 28 VAC, 5 VA; 8-35 VDC,
280 mA
Data Industrial flow sensor or other
frequency (sine/pulse) device
Sensor Input
Two 2-wire 10 kΩ type II thermistors
or 100Ω 3-wire platinum RTDs or
field-defined custom temperature
inputs
Maximum Output Impedance
1 kΩ @ 24 VDC
Output
Solid state pulse output rated at 1A
@ 30 VAC or 35 VDC; closed 0.5Ω
@ 1A; open >10 MΩ
Relay Output
Relay and pulse output are fully
functional as either totalizing or
setpoint outputs
Relay Output Rating
5A @ 120 VAC or 30 VDC resistive;
1A @ 120 VAC or 30 VDC inductive
Analog Output
4-20 mA, 0-20 mA (isolated, sinking
or sourcing); loop powered (sinking)
30 VDC @ 0 mA maximum, 3 VDC
@ 20 mA minimum; self powered
(sourcing) 600Ω maximum load
Pulse Rate
1 pulse per 1.0000000 to 99999999
units; any predefined or custom
unit can be used for flow or BTU
totalizing; contact time 1 to 9999
milliseconds
Setpoints
Setpoint alarm for flow rate, BTU
rate, Temp1, Temp2, DeltaT using
March 2014
any predefined or custom unit
Compensation for variances between
input sensors by adjusting T2 to
match T1
Communication Interface
USB 2.0A to mini-B 5-pin cable
required, provides access to all
programming and operation features
Communication Protocol
RS485 supports Modbus and
BACnet/MSTP
Display
Backlit LCD, 16 characters/line,
0.31"H (0.79 cm), two lines
Engineering Units
Flow and Total in gal, liters, ft3,
acre-ft, or bbl; Energy rate kBTU/
hr, BTU/min, KW, Tons, J/sec or
field-programmed custom; energy
total units can be MBTU, kBTU,
kWh, MWh, kJ, or field-programmed
custom
Operating Temperature-4° to 158°F (-20° to 70°C)
Enclosure Rating
NEMA 4X
Approvals CE
Weight
Panel mount
0.8 lb (0.34 kg)
Wall mount
1.2 lb (0.54 kg)
Warranty
1 year
Zero Adjustments
WE MAKE IT EASY.
kele.com
888-397-5353 USA
299
NEW!
FLOW
FLOW AND ENGERY MONITOR
3000, 3050 SERIES
WIRING
Badger 3050 BTU Monitor
24 VDC
Supply
J1-1 Temp 1 IN+
J1-2 Temp 1 INJ1-3 Temp GND
J1-4 Shield
J17-3 GND
J17-2 Temp 2 INJ17-1 Temp 2 IN+
J14-1 Relay 1 NO
J14-2 Relay 1 NC
J14-3 Relay 1 COM
J13-1 Relay 1 OUT
J13-2 Relay 2 OUT
J6-1 Analog IN+
J6-2 Analog INJ6-3 Shield
J8-1 Sensor IN
J8-2 GND
J8-3 Shield
J8-4 Sensor Power
4-20 mA
J9-3 GND
(red)
10 K Type II
Thermistor
(black)
bare wire
10 K Type II
Thermistor
J10-1 RS485 A
J10-2 RS485 B
J10-3 RS485 Iso GND
J9-1 Loop+
J9-2 Loop-
Pulse
Counter
DC
Power
J12-1 USB Power
J12-2 USB DataJ12-3 USB Data+
J12-4 N/C
J12-5 Shield
USB
Connection
200 Series
Flow Sensor
6
J1-1 Earth
J1-2 ACC/DC J1-3 ACL/DC +
12-24 VDC/VAC
Power Supply
DIMENSIONS
4.33"
110 mm
FLOW
3.57"-3.60"
90.6 mm-91.4 mm
1/8"
3.2 mm
(4 PLACES)
3.54"
90 mm
3.49"
88.7 mm
MOUNTING TEMPLATE
PANEL
CUTOUT
2.21"
56 mm
TOP
3.57"-3.60"
90.6 mm-91.4 mm
4.80"
122 mm
3.78"
96 mm
3.23"
82 mm
Data
®
Industrial
Data
®
Industrial
Series 3050
Series 3050
SIDE
3.78"
96 mm
3.62"
92 mm
3.49"
88.7 mm
4.72"
120 mm
SIDE
ORDERING INFORMATION
MODEL
3000
3050
200 Series
ST-U24B-XP
ST-U24S-XP
300
888-397-5353 USA
DESCRIPTION
Flow meter with display
BTU monitor with display
ANALOG OUTPUTS
0 No analog output
1 Analog output, RS485 (BACnet/Modbus), and USB
MOUNTING
0 Panel mount
1 Wall mount
RELATED PRODUCTS
PAGE
Data Industrial impeller type flow sensors with pulse output
290
Temperature sensors, matched ±0.1°F, brass wells
Temperature sensors, matched ±0.1°F, stainless steel wells
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
FLOW
ULTRASONIC FLOWMETER
DTFXL SERIES
DESCRIPTION
The Dynasonics DTFXL Series ultrasonic flow meter
measures water flow in a wide variety of pipe sizes and
pipe materials, using clamp-on sensors that attach to the
outside of the pipe. This non-invasive, non-contact flow
meter provides instantaneous flow rate and accumulated
flow and provides a 4-20 mA output as well as pulse outputs.
The DTFXL Series flow meter is easy to install, has a large
bidirectional flow range, and comes with or without a display.
Configuration, monitoring, and calibration of the DTXFL is
accomplished with an easy-to-use software package via a
cable connection from a PC to the flow meter.
For systems using water/glycol solutions, the higher-powered
DB Series ultrasonic flow meter may perform better.
FEATURES
Transit-time technology in an economical package
Can handle some suspended solids and gas pockets
Bidirectional flow range for changeover systems
Multiple totalizers for forward, reverse, net
Models with or without display
Selectable standard or metric engineering units
Non-invasive, no system down time to install
4-20 mA output plus choice of pulse outputs
Optional armored cable
High temperature transducers available
6
APPLICATION
The DTFXL Series is available in 3 basic transmitter/
transducer arrangements for installation and application
flexibility.
Models with integral transducers are available for pipe sizes
1/2" to 2"; the transmitter is attached to the transducers which
clamp on to the pipe for a local mount arrangement.
Models with remote small pipe (1/2" to 2") clamp-on
transducers require the transmitter to be wall- or panelmounted away from the pipe.
FLOW
•
•
•
•
•
•
•
•
•
•
DTFXL4-AN1-NN
Models with remote large pipe (2-1/2" to 100") strap-on
transducers also require the transmitter to be wall or panelmounted away from the pipe.
Transmitters are available with or without display.
SPECIFICATIONS
Supply Voltage
Frequency
11 to 30 VDC
0-1000 Hz for Turbine output (nonground referenced AC and 100 mV
pp minimum), switch selectable; 5
VDC pp ground-referenced square
wave for TTL output
Supply Current
0.25 A
Maximum Output Impedance
900Ω maximum for 4-20 mA output;
source power can share common
with power supply
Outputs
4-20 mA and Turbine or TTL
Conduit Opening
1/2" conduit knockout (7/8" hole, 2.2
cm)
Cable Length
Remote transducer models available
with 20' (6.1m), 50' (15m), or 100'
(30m) cables
Accuracy
± 1.0% of reading above 1 fps (0.3
mps) velocity, ± 0.01% of reading
below 1 fps (0.3 mps)
Response Time
0.3 to 30 seconds, adjustable
March 2014
Display
Two-line x eight-character LCD
Operating Temperature-40° to 185°F (-40° to 85°C); remote
DTTS/DTTN transducers have upper
limit of 250°F (121°C) and high
temperature DTTH transducers have
upper limit of 400°F (200°C)
Velocity Range
0.1 to 40 fps (feet/second), 0.03
to 12.4 mps (meters/second),
bi-directional
Pipe Size Range
1/2" to 100" (1.2 to 254 cm)
Media Compatibility
Most clean liquids or liquids with
some suspended solids or aeration,
not recommended for glycol
solutions, not for steam; for water/
glycol systems the DE Series is
recommended
Enclosure Rating
NEMA 4X as long as a liquid-tight
connector is used
Approvals
ANSI/ISA 582.01;
CSA C22.2 No. 213, E79-15-95
Warranty
1 year
WE MAKE IT EASY.
kele.com
888-397-5353 USA
301
FLOW
ULTRASONIC FLOWMETER
DTFXL SERIES
in (mm)
PC cable
connection
Note: Power ground and
4-20 mA common are
connected internally.
Upstream (red)
Upstream (black)
Downstream (black)
Downstream red)
NEW!
DIMENSIONS- INTEGRAL MODELS
WIRING
Transducer
connections
6.66
(169.2)
TRANSIT TIME FLOWMETER
–
4-20 mA
+
4-20 mA output –
+
Turbine or TTL output
Turbine or TTL Pulse
Power –
+
+
–
24 VDC
power
supply
3.17
(80.5)
2.57
(65.3)
0.875 (22.2)
diameter
conduit hole
B
Note: Integral model transmitters have conduit knockout connection on the right
side of the enclosure. Remote models have two conduit holes on the bottom
side of the enclosure.
D
A
C
Dimensions A, B, C and D vary by pipe size, the D dimension being slightly larger
than the outside diameter of the pipe.
6
ORDERING INFORMATION
FLOW
MODEL
DTFXL1
DTFXL2
DTFXL3
DTFXL4
Remote transducers for small pipes (with “Y” pipe size)
DESCRIPTION
Transmitter without display
Transmitter with display
Transmitter without display, UL enclosure
Transmitter with display, UL enclosure
PIPE SIZE
A 1/2" ANSI carbon steel
B 3/4" ANSI carbon steel
C 1" ANSI carbon steel
D 1 1/4" ANSI carbon steel
E 1 1/2" ANSI carbon steel
F 2" ANSI carbon steel
G 1/2" copper
H 3/4" copper
I
1" copper
J 1 1/4" copper
K 1 1/2" copper
L 2" copper
M 1/2" tubing (plastic)
N 3/4" tubing (plastic)
P 1" tubing (plastic)
Q 1 1/4" tubing (plastic)
R 1 1/2" tubing (plastic)
S 2" tubing
X For DTTN, DTTH transducers
Y
MODEL DESCRIPTION
DTTS Remote transducers for 1/2" to 2" pipes
DTTC High Temperature transducer for 1/2” to 2” pipes
PIPE SIZE
D 1/2"
F 3/4"
G 1"
H 1 1/4"
J 1 1/2"
L 2"
PIPE TYPE
P ANSI carbon steel
C Copper
T Tubing
CABLE LENGTH
020 20 feet (6.1 m)
050 50 feet (15 m)
100 100 feet (30 m)
CABLE ARMOR OPTION
N No armor
A Flexible armor
CABLE ARMOR LENGTH
000 No armor
020 20 feet (6.1 m)
050 50 feet (15 m)
100 100 feet (30 m)
For DTTS, DTTC transducers
CONNECTOR OPTIONS
N 1/2" conduit knockout
OUTPUT SIGNALS
1-NN 4-20 mA and pulse
D002-2007-001
D005-0803-104
D005-2116-004
D010-0204-001
D010-2102-010
DCP-1.5-W
DCPA-1.2
302
888-397-5353 USA
Remote transducers for large pipes (with “X” pipe size)
MODEL DESCRIPTION
DTTN Standard transducer for 2 1/2" to 20" pipes
DTTH High temperature transducer for 2 1/2" to 100" pipes
CABLE LENGTH
020 20 feet (6.1 m)
050 50 feet (15 m)
100 100 feet (30 m)
CABLE ARMOR OPTION
N No armor
A Flexible armor
CABLE ARMOR LENGTH
000 No armor
020 20 feet (6.1 m)
050 50 feet (15 m)
100 100 feet (30 m)
OPTIONS
N Normal area rating
NOTE: Add -C suffix to transmitter model
number for factory-configured transmitter and fill
out the application data sheet located on Kele's
website. The UltraLink software is required to
reset the DTFXL totalizer and to field configure,
monitor, and diagnose the DTFXL. The PC cable
is required to connect a PC to the DTFXL and
the software is available on CD or free from
www.dynasonics.com.
RELATED PRODUCTS
Additional 36" stainless straps for DTTN/H transducers
(two straps included standard with remote transducers)
UltraLink software CD
USB to DB-9 Serial Communications Cable
PC to transmitter cable
Mounting track assembly for DTTN/DTTH transducers, for <10" pipes
Power supply, 24 VAC IN to 24 VDC OUT
Power supply, 120 VAC IN to 24 VAC/24 VDC OUT
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
PAGE
995
994
March 2014
NEW!
FLOW
MAGNETIC FLOW METER
M-2000 SERIES
DESCRIPTION
The Badger Meter M-2000 Series magnetic flow
meter is the result of years of research and field use in
electromagnetic flow meters. The M-2000 can measure
almost any liquid, slurry or paste that has minimum electrical
conductivity. These meters are perfect for flow measurement
in commercial HVAC water systems, wastewater, reclaimed
water, irrigation and industrial applications because they can
handle suspended solids, have no pressure drop, no moving
parts, and their accuracy is not affected by temperature,
pressure, viscosity, density or flow profile. They are NSF
listed for use in potable water. The ANSI 150 RF flanged
pipe spool makes them easy to install and they are available
with the NEMA 4X (IP66) integral amplifier (transmitter and
display housing) mounted atop the flow detector housing,
or with the amplifier remotely mounted. For the remote
mount configuration, a 30 ft. cable is standard (other lengths
available) and the detector housing comes with either a
NEMA 4X or NEMA 6P (submersible) junction box. Each
meter is factory calibrated and tested and a certificate is
included.
• Empty pipe detection feature generates error message
when pipe is not full
• NEMA 4X (IP66) enclosure for installation in exposed
areas
• Large backlit 4-line, 20 character LCD display for local
indication and programming even in low light conditions
• Modbus RTU via RS232 communications for network
systems
FLOW
FEATURES
• High accuracy of +/- 0.25% and flow range of 300:1 for
reliable measurement
• Unaffected by most solids contained in the fluid for
application flexibility
• Pulsed DC magnetic field for zero point stability
• Corrosion resistant liners provide long life
• Grounding rings included for non-conductive piping
• Bidirectional flow sensing and totalization for reversing
system application
6
SPECIFICATIONS
Supply Voltage
Supply Watts
Digital Inputs
Maximum Output
Impedance
Outputs
Analog output
Digital outputs
Pulse outputs
Frequency output
Alarm
Wiring Terminations
Communication
Accuracy
Repeatability
Display
March 2014
85-265 VAC (45-65 Hz)
15 W
Maximum 30 VDC, programmable as
positive zero return, external totalizer
reset, or preset batch start
800 ohms @ 24 VDC
0-20 mA, 4-20 mA, 0-10 mA, or 2-10 mA
Four configurable, 24 VDC sourcing
outputs (maximum of two) 50 mA each
or 100 mA total, sinking open collector
outputs (maximum of four) 100 mA each
or 30 VDC total, AC solid state relay
(maximum of two) 48 VAC
500 mA maximum
Scalable up to 10 kHz, passive open
collector up to 10 kHz active switched
24 VDC, up to two outputs (forward and
reverse flow), pulse width programmable
from 1 to 1,000 ms or 50% duty cycle
Scaleable up to 10 kHz open collector,
up to 1 kHz solid state relay
High/low flow alarm, error alarm, empty
pipe alarm outputs
1/2" NPT conduit connection and 3
cord grips on amplifier housing; 30 ft.
standard length cable for remote mount
configurations (other lengths available)
RS232 - Modbus RTU or remote display
±0.25% of flow rate for velocities
greater than 1.64 fps (0.5 mps;
±0.004% for lower velocities
±0.1%
Backlit, 4 line, 20 character LCD and
3-button progamming keys
Engineering Units
Pipe Size Range
Flow Range
Velocity Range
Operating Temperature
Operating Humidity
Media Compatibility
Media Temperature
Range
Maximum Pressure
Materials Of
Construction
Enclosure Rating
Approvals
Warranty
WE MAKE IT EASY.
Ounces, pounds, liters, US gallons,
imperial gallons, barrels, hectoliters,
megagallons, cubic meters, cubic feet,
acre feet
1" to 24" standard (1/4", 1/2" and 28"
to 54" also available), ANSI 150 RF
flanges standard
Unidirectional or bidirectional with two
separate totalizers (programmable)
0.10 to 39.4 fps (0.03 to 12 mps)
-4° to 140°F (-20° to 60°C)
Up to 90% non-condensing
Many fluid applications including hot or
chilled water, glycol solutions; minimum
conductivity 5.0 µΩ/cm
178°F (80°C) with rubber liner; 212°F
(100°C) with PTFE liner and local mount
amp; 311°F (155°C) with PTFE liner and
remote mount amp
285 psig at ambient temperature, refer
to ANSI B16.5 standard for 150 lb RF
flanges for temperature/pressure spec
Meter housing and flanges: carbon steel
Liner: Rubber
Electrodes: Alloy C
Pipe spool: 316 SS
Grounding rings: stainless steel
Amplifier housing: cast aluminum with
powder-coat paint
NEMA 4X (IP66) amplifier housing;
NEMA 4X or NEMA 6P detector
housing junction box for remote mount
configuration
NSF Listed, CE
1 year
kele.com
888-397-5353 USA
303
FLOW
MAGNETIC FLOW METER
M-2000 SERIES
WIRING
NEW!
FLOW
6
304
888-397-5353 USA
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
FLOW
MAGNETIC FLOWMETER
M-2000 SERIES
DIMENSIONS
Note: Dimension D in table below is
overall height (similar to dimension
B) to the top of junction box, for
assemblies with remote amplifier
configuration.
6
DIMENSIONS AND FLOW RANGES
A
B
C
D
Weight
Flow Range
1" (DN25)
8.9" (22.5 cm)
14.4" (36.6 cm)
4.3" (10.8 cm)
11.7" (29.8 cm)
18 lb (8.0 kg)
0.3 to 93 gpm (1.2 to 350 lpm)
1-1/4" (DN32)
8.9" (22.5 cm)
15.2" (38.6 cm)
4.6" (11.7 cm)
12.5" (31.8 cm)
20 lb (9.0 kg)
0.5 to 150 gpm (2.0 to 575 lpm)
1-1/2" (DN40)
8.9" (22.5 cm)
15.4" (39.0 cm)
5.0" (12.7 cm)
12.7" (32.2 cm)
21 lb (9.5 kg)
0.8 to 239 gpm (3 to 900 lpm)
2" (DN50)
8.9" (22.5 cm)
15.9" (40.3 cm)
6.0" (15.2 cm)
13.2" (33.5 cm)
26 lb (11.5 kg)
1 to 373 gpm (4.7 to 1400 lpm)
2-1/2" (DN65)
11.0" (28.0 cm)
17.1" (43.4 cm)
7.0" (17.8 cm)
14.4" (36.6 cm)
52 lb (23.5 kg)
2 to 631 gpm (8 to 2400 lpm)
3" (DN80)
11.0" (28.0 cm)
17.3" (44.0 cm)
7.5" (19.1 cm)
14.7" (37.2 cm)
54 lb (24.5 kg)
3 to 956 gpm (12 to 3600 lpm)
4" (DN100)
11.0" (28.0 cm)
18.4" (46.6 cm)
9.0" (22.9 cm)
15.7" (39.8 cm)
56 lb (25.5 kg)
5 to 1493 gpm (19 to 5600 lpm)
5" (DN125)
15.8" (40.0 cm)
19.6" (49.8 cm)
10.0" (25.4 cm)
16.9" (43.0 cm)
58 lb (26.0 kg)
8 to 2334 gpm (30 to 8800 lpm)
6" (DN150)
15.8" (40.0 cm)
20.6" (52.4 cm)
11.0" (27.9 cm)
17.9" (45.6 cm)
60 lb (27.0 kg)
11 to 3361 gpm (40 to 12,700 lpm)
8" (DN200)
15.8" (40.0 cm)
22.5" (57.2 cm)
13.5" (34.3 cm)
20.4" (51.8 cm)
86 lb (39.0 kg)
20 to 5975 gpm (75 to 22,600 lpm)
10" (DN250)
19.7" (50.0 cm)
26.8" (68.1 cm)
16.0" (40.6 cm)
24.1" (61.3 cm)
178 lb (81 kg)
30 to 9336 gpm (120 to 35,300 lpm)
12" (DN300)
19.7" (50.0 cm)
28.9" (73.4 cm)
19.0" (48.3 cm)
26.2" (66.6 cm)
207 lb (94 kg)
45 to 13,444 gpm (170 to 50,800 lpm)
14" (DN350)
19.7" (50.0 cm)
30.8" (78.2 cm)
21.0" (53.3 cm)
28.2" (71.6 cm)
258 lb (117 kg)
60 to 18,299 gpm (230 to 69,200 lpm)
16" (DN400)
23.6" (59.0 cm)
33.7" (85.6 cm)
23.5" (59.7 cm)
31.0" (78.8 cm)
306 lb (139 kg)
80 to 23,901 gpm (300 to 90,400 lpm)
18" (DN450)
23.6" (59.0 cm)
35.0" (89.0 cm)
25.0" (63.5 cm)
32.4" (82.2 cm)
400 lb (181 kg)
100 to 30,250 gpm (380 to 114,000 lpm)
20" (DN500)
23.6" (59.0 cm)
38.2" (96.9 cm)
27.5" (69.9 cm)
35.5" (90.1 cm)
493 lb (224 kg)
125 to 37,346 gpm (470 to 140,000 lpm)
22" (DN550)
23.6" (59.0 cm)
39.6" (100 cm)
29.5" (74.9 cm)
36.9" (93.7 cm)
523 lb (237 kg)
150 to 45,188 gpm (570 to 170,000 lpm)
24" (DN600)
23.6" (59.0 cm)
42.2" (107 cm)
32.0" (81.3 cm)
39.5" (100 cm)
552 lb (251 kg)
180 to 53,778 gpm (680 to 200,000 lpm)
March 2014
WE MAKE IT EASY.
kele.com
888-397-5353 USA
FLOW
Size
305
NEW!
FLOW
MAGNETIC FLOWMETER
M-2000 SERIES
APPLICATION AND INSTALLATION
The M-2000 provides two amplifier mounting options, integral or remote. The amplifier housing is NEMA 4X rated and can be
located outdoors; observe the operating temperature range of -4° to 140°F (-20° to 60°C). If located outdoors, provide a roof or
shield over the amplifier to protect the LCD display from direct sunlight. If the amplifier is to be remote mounted, standard available cable lengths are 15', 30', 50' and 100' (up to 500' optional).
Magnetic flowmeters can operate accurately in any pipeline orientation and can measure flow in both directions. A "Forward
Flow" direction arrow is printed on the detector label. They also perform best when placed in a vertical pipe with the liquid flowing upward; this assures a full pipe at all times and minimizes sediment deposits on the liner and electrodes. If mounting in a
horizontal pipe, mount the detector such that the electrodes are on the sides of the pipe, not the top and bottom, also to minimize
deposits and build-up on the electrodes. Avoid locations where a partially-filled piping situation can occur; the meter will display
an "Empty Pipe Detection" message and will stop measuring flow until the pipe is full.
6
Sufficient straight-pipe runs are required for optimum accuracy and performance. A minimum of 3 diameters upstream and 2
diameters downstream are required (more is better).
Grounding is critical for magnetic flow meters; they must be electrically connected to the liquid media. If using non-conductive
piping, the grounding rings (included) must be properly installed. See the M-2000 manual for details.
FLOW
ORDERING INFORMATION
MODEL DESCRIPTION
M2K- Magnetic flowmeter
SIZE CODE PIPE SIZE
010
1"
013
1-1/4"
015
1-1/2"
020
2"
025
2-1/2"
030
3"
040
4"
050
5"
060
6"
080
8"
100
10"
120
12"
140
14"
160
16"
180
18"
200
20"
220
22"
240
24"
LINER CODE LINER MATERIAL
RRubber
TPTFE
AMPLIFIER OPTIONS
LC
Local mount amplifier, NEMA 4X (IP66) housing
RM-N4X Remote mount amp, 30 ft. cable, NEMA 4X junction box on detector tube
RM-N6P Remote mount amp, 30 ft. cable, NEMA 6P junction box on detector tube
M2K-
306
040
888-397-5353 USA
R-
kele.com
LC
Example: M2K-040R-LC 4" magnetic flowmeter with
rubber liner, local mount amplifier
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
FLOW
FIXED AND RETRACTABLE INSERTION VORTEX FLOW METERS
2200, 3100 SERIES
DESCRIPTION
The 2200 Series fixed insertion and 3100 Series
retractable vortex flow meters are used to measure the flow
rate of water or water/glycol mixtures in 2" to 20" pipes. Each
flow meter is factory calibrated and scaled to provide precise
output signals. No complex field adjustments or confusing
measurement routines are required to install the flow meters.
Simple design, easy installation, reliable performance, and
low cost make these flow meters an excellent choice for
commercial HVAC applications.
FEATURES
• No moving parts
• Easy to install
• Reliable and robust design
• Wide flow range - 15:1 turndown ratio
• Microprocessor based piezo resistive sensor
technology
• Optional integral display
FIGURE 1. VORTICES CREATED BY
A BLUFF BODY
FIGURE 2. EXAMPLES OF
VORTEX EFFECT
Bluff
body
OPERATION
As flow passes a bluff body in the flow stream, vortices are
alternately formed on either side of the bluff body (Figure
1). According to well-proven physical laws, the frequency at
which vortices are alternately formed is directly proportional
to the average flow velocity. The vortices create low- and
high-pressure zones behind the bluff body. A vortex flow
meter has a sensing element that detects these low- and
high-pressure zones and the frequency at which they are
created to measure flow.
The fluttering of a flag (Figure 2) is one example of how
vortices are created. The flag pole acts as a bluff body to the
blowing wind as the flag waves from the force of the vortices
alternately created.
6
FLOW
Bluff
body
2200 Series with optional
display and Thredolet® mount
SPECIFICATIONS
Supply Voltage
10-32 VDC
Maximum Output Impedance
R(load) = 50 (Vs-10)
Output Signal
4-20 mA loop-powered standard
(pulse output available special order)
Connections
2200: 1-1/2" MNPT
3100: 2" MNPT
Wiring Terminations Screw terminals inside housing
Conduit Connection
3/4" FNPT
Configuration
For factory pre-configuration, specify
pipe size, pipe material/schedule
and maximum flow rate. Separately
available Hydro-Flow Field-Pro
software is available for field
configuration
Accuracy
± 1% of full scale (combined linearity
and repeatability)
Display
Optional, LCD alternates between
showing 4-digit flow rate and 8-digit
total flow
Engineering Units
English, gallons; metric, cubic meters
(other units available upon request or
can be configured using Hydro-Flow
Field-Pro software)
Operating Temperature-20° to 140°F (-29° to 60°C)
Velocity Range
1 fps (0.3 mps) minimum, 15 fps
(4.5 mps) maximum
March 2014
Pipe Size Range
Installation
2200: 2" to 20" (5 to 50 cm)
3100: 3" to 20" (8 to 50 cm)
Install in straight pipe section with
a minimum distance of 10 pipe
diameters upstream and 5 pipe
diameters downstream to any bend,
obstruction or transition
Mounting
Thredolet®, or piping tee (2200
Series only)
Media Compatibility
Water, water/glycol mixtures,
condensate
Media Temperature Range
32° to 160°F (0° to 71°C)
Maximum Pressure
400 psig (2759 kPa) for Thredolet®
mount, 150 psig (1035 kPa) for piping
tee mount
Materials Of Construction
Reinforced polycarbonate enclosure,
Ultem® plastic vortex shedder, 316
SS shedder bar, stainless steel stem,
EPDM o-rings, brass compression
fitting, aluminum/nickel-plated
retractor (3300 Series only)
Enclosure Rating
NEMA 6
Warranty
2 years
WE MAKE IT EASY.
kele.com
888-397-5353 USA
307
NEW!
FLOW
FIXED AND RETRACTABLE INSERTION VORTEX FLOW METERS
2200, 3100 SERIES
WIRING
Vs
(10 to 32 VDC)
*Rload
4-20 mA wiring
* Rload maximum = 50 (Vs - 10)
6
FLOW RANGES
Pipe size in (mm)
FLOW
Minimum flow
2200 gpm (m3/h)
Series Maximum flow
gpm (m3/h)
Minimum flow
3100 gpm (m3/h)
Series Maximum flow
gpm (m3/h)
2" (50)
3" (80)
4" (100)
6" (150)
8" (200)
10" (250)
12" (300)
14" (350)
16" (400)
10.6 (2.4)
23.4 (5.4)
40 (9.2)
100 (23)
167 (38)
267 (61)
368 (83)
418 (95)
568 (129)
734 (167)
934 (212)
160 (36.3) 350 (79.5)
18" (450)
20" (500)
600 (136)
1500 (341)
2500 (557)
4000 (909)
5500 (1249)
6250 (1420)
8500 (1931)
11000 (2498)
14000 (3180)
N/A
26.6 (6.0)
40 (9.0)
100 (23)
167 (38)
267 (61)
366 (83)
417 (95)
567 (129)
733 (167)
933 (212)
N/A
400 (90.8)
600 (136)
1500 (341)
2500 (557)
4000 (909)
5500 (1249)
6250 (1420)
8500 (1931)
11000 (2498)
14000 (3180)
ORDERING INFORMATION
MODEL
2200
3100
DESCRIPTION
Fixed insertion vortex flow meter
Retractable insertion vortex flow meter
PIPE SIZE DESCRIPTION
02
2" pipe (fixed insertion only)
03
3" pipe
04
4" pipe
06
6" pipe
08
8" pipe
10
10" pipe
12
12" pipe
14
14" pipe
16
16" pipe
18
18" pipe
20
20" pipe
MOUNTING DESCRIPTION
1
Thredolet®
4
Tee (2" size only)
OUTPUT, DISPLAY OPTIONS DESCRIPTION
2-1-1
4-20 mA output, no display
2-2-1
4-20 mA output, display, English units
2200
06
2-1-1
1
Example: 2200-06-1-2-1-1 Fixed insertion flow meter,
6" pipe, Thredolet® mount, 4-20 mA, no display
Notes: Other options and configurations available. Separately ordered configuration software also available for
field configuration. Consult Kele with calibration information when ordering (pipe size, fluid temperature
and pressure, max flow rate).
Software - FieldPro - EC10011
308
888-397-5353 USA
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
FLOW
INSERTION VORTEX FLOW METER
V-BAR 700
DESCRIPTION
The V-Bar 700 insertion vortex flow meter can be used to
measure the flow rates of most liquids, gases, and steam.
The same V-Bar 700 will fit pipe sizes from 3" to 80" (8 to 200
cm), features no moving parts, adds negligible head loss to
the system, and comes with an easily programmable integral
local flow rate indicator and totalizer. The microprocessorbased electronics condition the signal and provide a
frequency output, a scaled pulse output, or a 4-20 mA output.
OPERATION
Vortex flow meters are devices that measure the frequency
of vortices created in the flow stream. Vortices are like tiny
eddies produced by an obstruction (called a bluff body) in the
flow and are actually areas of low pressure. These vortices
travel with the flow downstream until they run out of energy.
Inserting a bluff body (Figure 1) into the stream creates these
vortices that alternate from side to side. The frequency of
these vortices or pressure pulses can be measured and are
directly proportional to the average flow rate. A flag waving
in the wind is an example of this vortex effect (Figure 2). The
flagpole is the bluff body, and the high- and low-pressure
areas are seen as high and low ridges in the flag. These
ridges alternate as they travel across the flag and cause the
flag to appear to be waving.
FEATURES
• Measures flow rates of liquids, gases, or steam
• 2000 psig (13,790 kPa) pressure rating
• 500°F temperature rating
• No moving parts
• Integral transmitter with local display
• Stainless steel construction
6
FIGURE 1. VORTICES CREATED BY
A BLUFF BODY
FIGURE 2. EXAMPLES OF
VORTEX EFFECT
FLOW
Bluff
body
Bluff
body
SPECIFICATIONS
Supply Voltage
Isolated 18-40 VDC
Supply Current
35 mA maximum
Maximum Output Impedance
R(load) = 50 (Vs-18)
Output Signal
4-20 mA two-wire loop-powered, scalable
frequency voltage pulse (3-wire 0-3000
Hz square wave, 50% duty cycle, low level
= 0-1 V, high level = power supply
voltage-load)
Connections
2" MNPT process connection,
1/4" pressure tap
Wiring Terminations
Screw terminals inside housing
Conduit Connection
3/4" FNPT
Configuration
Factory pre-configuration required,
see Ordering Information
Accuracy
± 1.0% of flow rate for water applications,
± 1.5% of flow rate for steam and gas
Repeatability
± 0.15% of flow rate
Response Time
Adjustable from 1 to 100 seconds
Display
2-line by 8-character LCD alternately
shows flow rate and total flow. Four-button
interface enables local programming
modifications
Engineering Units
English, gallons; metric, cubic meters
(other units available upon request)
Operating Temperature
Operating Humidity
Velocity Range
-20° to 140°F (-29° to 60°C)
5 to 100% RH non-condensing
Liquid flow: 1.5 fps (0.5 mps) minimum,
32 fps (9 mps) maximum
Pipe Size Range
3" to 80" (8 to 200 cm)
Installation
Straight pipe section, minimum 10 pipe
diameters upstream, 5 pipe diameters
downstream
Mounting
Thredolet®, or piping tee
Media Compatibility
Liquid, gas or steam
Media Temperature Range-200° to 500°F (-129° to 260°C)
Maximum Pressure
2000 psig (138 bar)
Materials Of Construction Wetted parts: 316 stainless steel
(or cast equivalent)
External parts: Aluminum, 316 SS,
carbon steel
Electrical enclosure: 383 Aluminum
Enclosure Rating
NEMA 4X
Dimensions
Maximum overall height 32.5" (82.6 cm);
insertion 3" minimum to 10" maximum
(7.6 to 25.4 cm), recommended service
clearance 12" (30.5 cm)
Weight
9 lb (4.1 kg) maximum
Warranty
2 years
ORDERING INFORMATION
Please call Kele for specific application and prices. The following information is required:
March 2014
1. Pipe size and schedule
2. Type of gas or liquid
3. Operating pressure
4. Maximum flow rate (lb/hr, scfm)
5. Temperature
6. Constant or varying pressure
WE MAKE IT EASY.
kele.com
888-397-5353 USA
309
FLOW
TARGET FLOW METER
NFP SERIES
DESCRIPTION
6
The Niagara NFP Series ForceMeter™ is an insertion
type flow meter that can measure water or steam. It
utilizes a hermetically sealed strain-gage bridge circuit to
convert flow force to a two-wire 4-20 mA output signal that is
proportional to flow rate. All wetted parts are 316L stainless
steel and the meter mounts to 4" and larger pipes using a 2"
or 4" ANSI 150# or 300# raised face flange. The NFP Series
comes pre-calibrated and configured based on the application
parameters provided at the time of order; the meter only
needs to be zeroed to adjust for installation orientation. Many
different models and configuration options are available, such
as retractable insertion types, inline models, and hazardous
approval.
NEW!
FLOW
FEATURES
C
FM
US
APPROVED
• Quick response time for flow change display in less
than 1 second, can be dampened
• Rugged design includes no moving parts to wear out
• All welded sensor construction for durability
• Hermetically sealed to withstand challenging
environmental conditions
• Maintenance-free keeps cost of ownership down
• Integral display for local indication of flow and
totalization
NFP Series
SPECIFICATIONS
Supply Voltage
Output Signal
Accuracy
Repeatability
Response Time
Display
Wiring Terminations
Conduit Connection
Configuration
Flow Range
Pipe Size Range
Turn Down
Installation
310
24 VDC ±10%
2-wire, 4-20 mA @ 500Ω
± 1.0% of rate
± 0.15% of flow rate
0.33 mS
2-line alphanumeric with bar graph
Screw terminals
3/4" FNPT
Factory pre-configuration required
to assure application/product match:
specify pipe size and material/
schedule, fluid/gas type, operating
pressure and temperatures, and
minimum/maximum flow rates
19.6 gpm (4" pipe) to 98,000 gpm
(60" pipe)
4" to 60" (100 to 1500 cm)
15:1
Install in straight pipe section with
a minimum distance of 10 pipe
diameters upstream and 5 pipe
diameters downstream to any bend,
obstruction or transition
888-397-5353 USA
kele.com
Mounting
ANSI flanges standard
Media Compatibility
Liquid, non-volatile gases, or steam
Media Temperature Range
-65° to 425°F (-54° to 218°C), other
ranges special order
Operating Temperature-4° to 170°F (-20° to 75°C)
Maximum Pressure
>1000 psi (69 bar) for primary
sensing elements; piping connections
per applicable ANSI specs
Materials Of Construction
316L stainless steel wetted parts,
Polyester powder coated aluminum
housing
Enclosure Rating
NEMA 4X
Dimensions
Height 10.8" (32.4 cm) from
mounting flange to top of transmitter;
insertion length depends on pipe
size specified, force sensor locates in
center of pipe
Approvals
CE, FM
Weight
9 lb (4.1 kg) maximum
Warranty
2 years
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
FLOW
TARGET FLOW METER
NFP SERIES
WIRING
DIMENSIONS
Typical Remote Enclosure
Integral Transmitter Wiring
Enclosure Mounted on Flowmeter (Backside)
Conduit Entry
for Customer
Wiring
4.5
(11.4)
Conduit Entry
for Customer
Wiring
GND
+
–
8.25
(20.96)
(approx.)
Customer
Wiring
4-20mA Output
+
–
6
4
(10.2)
Power
Supply
18-36 VDC
+
–
BAS
–
E
+
L
FLOW
6.0
(15.2)
Flow
Typical Integral Enclosure
ORDERING INFORMATION
MODEL DESCRIPTION
NFP
Flow Meter
LINE SIZE (inches) DESCRIPTION
4, 5, 6, 8, 10, 12, etc. Select pipe size (larger insertion and smaller in-line models are available)
MOUNTING DESCRIPTION
M
2" raised flange
P
4" raised flange
FLANGE RATING DESCRIPTION
01
150 # raised-face ANSI
02
300 # raised-face ANSI
BODY, ELEMENT DESCRIPTION
Y1V1ZV
SS316L Body, unidirectional
Gas, Liquid or Steam
G, L, or S
NFP
4
M
01
Y1V1ZV
5.5
(13.97)
G
Example: NFP-4-M-01-Y1V1ZV-G Insertion target flow meter for water, 4" pipe size,
2" RF 150 # mounting flange, 303/304 SS body, 1,000 psi, 425 DF -rating
DCPA-1.2
DCP-1.5-W
March 2014
RELATED PRODUCTSPAGE
Power supply, 120 VAC IN to 24 VAC/24 VDC OUT
994
Power supply, 24 VAC IN to 24 VDC OUT
995
WE MAKE IT EASY.
kele.com
888-397-5353 USA
311
FLOW
BTU TRANSMITTER
340 SERIES
DESCRIPTION
The Badger Meter 340 Series is an inexpensive and easy-toapply BTU transmitter which calculates energy usage based
on liquid flow rate from a Data Industrial impeller flow sensor
and differential temperature using two 10 kΩ thermistor
inputs. The onboard microcontroller and digital circuitry
provide precise measurements and produce accurate driftfree outputs. Configuration is accomplished with a Windows®
based software programming kit. The 340 Series is available
with onboard communication technology for LonWorks,
BACnet, Johnson Controls N2 Metasys, or Modbus networks.
NEW!
6
FEATURES
AC or DC powered for installation flexibility
Field programmable makes changes easy
Small footprint saves space
Uses two matched 10Ωk thermistors
Used with Data Industrial flow sensors
340-00
FLOW
•
•
•
•
•
SPECIFICATIONS
Supply Voltage
Supply Current
Input Signal
Output Signal
-- Output
BN Output
LW Output
N2 Output
Pulse Output
312
12-35 VAC ±5% or 12-24 VDC ±10%
60 mA @ 12 VDC
All flow sensors: Excitation voltage
3-wire, 7.9-11.4 VDC, 270Ω source
impedance Pulse sensors: Signal
amplitude 2.5 VDC threshold, signal
limit <35V AC or DC peak, frequency
0-10 kHz, pull-up 8.5 VDC @ 2
kΩ source impedance Sine wave
sensors: Signal amplitude 10 mV
p-p threshold, signal limit <35V AC
or DC peak, frequency 0-10 kHz
Temperature sensors: Two matched
10 kΩ @ 25°C, two-wire, type II
Pulse, isolated solid state switch
programmed for units of energy or
flow
BACnet and Modbus communication
LonWorks communication
N2 communication
Voltage range: 0 to ±60V (DC or
AC peak); On-state load current:
700 mA maximum; On-state load
resistance: 700 mΩ; Off-state
leakage: < 1µA @ 60 V peak; Pulse
width: adjustable from .05 to 5.0
seconds
888-397-5353 USA
kele.com
User Interface
Communication
Configuration
Computer connection allows visibility
of real-time flow rate, flow total,
temperature readings, energy rate
and energy total
BACnet and Modbus, LonWorks,
Metasys N2, or Modbus
Windows® based A30120 programming kit (order
separately) cable connects to DIC
communication port and DB9 COM
port on a computer for calibration of
flow sensor information, units, output
scaling; unit must be powered to
configure
Mounting
-00 Enclosure
Surface mount, no enclosure
-02 Enclosure
Surface mount, in metal enclosure
-03 Enclosure
Surface mount, in plastic enclosure
-04 Enclosure
DIN rail mount, with clips
Operating Temperature-20° to 158°F (-29° to 70°C)
Weight
0.3 lb (0.14 kg) without enclosure
Warranty
1 year
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
WIRING
Pulse input
device
BTU TRANSMITTER
340 SERIES
DIMENSIONS
in
(cm)
(–) (+)
AC/DC
power +
supply –
Flow
Sensor
FLOW
1.6
(4.1)
Pulse –
AC Line or DC+
AC Common or DC– output +
3.65
(9.3)
Power out
Signal (+)
Signal (–)
Shield
(red)
(black)
0.88
(2.2)
Shield
(if applicable)
6
2.95
(7.5)
Temp 1
0.6
(1.5)
Temperature
sensors
Temp 2
* Network communications terminals
vary slightly per model
FLOW
ORDERING INFORMATION
MODEL DESCRIPTION
340
BTU meter
OUTPUT
LW
Transmitter for use with LONWorks networks
N2
Transmitter for use with Johnson Metasys networks
BN
Transmitter for use with BACnet and Modbus networks
ENCLOSURE
00 Transmitter only
02 Transmitter with metal enclosure
03 Transmitter with plastic enclosure
04 Transmitter with DIN rail mounting clips
340
March 2014
_ – _ 02 Example: 340 Series BTU meter with standard pulse output
and metal enclosure
200 Series
A301-20
ST-U24B-XP
ST-U24S-XP
RELATED PRODUCTS
Data Industrial impeller type flow sensors with pulse output
Flow/BTU transmitter programming kit, includes cable
Temperature sensors, matched ±0.1°F, brass wells
Temperature sensors, matched ±0.1°F, stainless steel wells
691-K0A
DCP-1.5-W
ACCESSORIESPAGE
Control transformer, 120:24 VAC, 40 VA, Class 2
979
Power supply, 24 VAC IN to 24 VDC OUT
995
WE MAKE IT EASY.
PAGE
290
kele.com
888-397-5353 USA
313
FLOW
BTU METER
380 SERIES
DESCRIPTION
The Badger Meter 380 Series BTU meters provide
an inexpensive solution to monitoring thermal energy
consumption in cold or hot water systems. The integrated flow
and temperature sensors along with the internal metering
components make installation and commissioning easy. With
on-board Modbus and BACnet communication and a compact
design that will fit in a wall, the 380 Series is perfect for
networking and multi-tenant billing applications.
NEW!
FEATURES
FLOW
6
• AC or DC power
• Field programmable
• Scaled pulse or RS-485 (Modbus and BACnet) output
standard
• Two temperature sensors included
• Compact, fits within a standard 2X4 stud wall
• Compatible with potable water and water/glycol
mixtures
WIRING
APPLICATION
•
•
•
•
•
380CS07
Strip Malls
Multi-tenant buildings
Office buildings
Thermal storage systems
Sustainable design buildings
2
POWER
1
3
GND
2
-
1
+
2
1
RS 485
PULSE
OUTPUT
SPECIFICATIONS
Supply Voltage
Supply VA
Supply Current
Sensor Input
Output
Wiring
Wiring Terminations
Communication
Repeatability
Size
Connections
Velocity Range
Accuracy 314
12-28 VAC or 12-35 VDC
5 VA
200 mA maximum
0.24" diameter RTD probe, meets
IEC751 Class B; 6.5' (2 m) cable for
remote sensor, custom fitting for 1/8"
NPT pipe tap included
Scaled pulse: 10, 50, 150, 200 or
250 ms
Two cable glands, PG6 and PG9
Screw terminals inside enclosure
Modbus RTU, BACnet
±0.5%
3/4", 1", 1-1/4", 1-1/2", 2"
FNPT
1 to 15 fps
± 2% of range
888-397-5353 USA
kele.com
Operating Temperature-4° to 149°F (-20° to 65°C)
Media Temperature Range
Cold service
-4° to 140°F (-20° to 60°F)
Hot service
39° to 257°F (4° to 125°C)
Materials Of Construction
Cast bronze tee, 316 SS impeller,
PEEK flow sensor, polyurethane
potting material, polycarbonate
housing
Enclosure Rating
NEMA 4
Weight
3/4"
6 lb (2.7 kg)
1"
7 lb (3.2 kg)
1-1/4"
8 lb (3.6 kg)
1-1/2"
9 lb (4.1 kg)
2"
13 lb (5.9.kg)
Warranty
1 year
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
FLOW
BTU METER
380 SERIES
DIMENSIONS
TOP VIEW
Ø8" (20.3 cm)
360°
Pivot area
case from
center
of tee
Custom
RTD fitting
1/8" NPT
B
Overall height
PG-7
PG-9
D
Hex
6
C
Tee length
A
Overall length
E
Width
T2
length
6.5 ft. (2 m)
Dimensions in (cm)
TEE/NPT
SIZE
2"
Ø0.24" (0.6 cm)
A
7.9
(20.1)
7.3
(18.5)
7.1
(18)
6.7
(17.1)
6.7
(17.1)
1.5"
1.25"
1"
3/4"
B
8.5
(21.6)
8.3
(21.1)
8.1
(20.6)
7.9
(20.1)
7.9
(20.1)
C
7.8)
(19.8)
6.7
(17.1)
6.3
(16)
5.4
(13.7)
5.4
(13.7)
D
3.3
(8.4)
3.8
(9.7)
2.4
(6.1)
2
(5.1)
2
(5.1)
E
3.5
(8.9)
3.5
(8.9)
3.5
(8.9)
3.5
(8.9)
3.5
(8.9)
FLOW
INSTALLATION
24 AWG twisted, shielded
pair
Series
380 Btu
meter
Modbus or
BACnet
device
Series
380 Btu
meter
Series
380 Btu
meter
Series
380 Btu
meter
(Up to 32 units)
Model 3700 Data Acquisition
Server (Modbus) or similar
Modbus or BACnet device
ORDERING INFORMATION
March 2014
MODEL
380CS07
380CS10
380CS12
380CS15
380CS20
380HS07
380HS10
380HS12
380HS15
380HS20
DESCRIPTION
380 BTU System, cold service, 3/4" FNPT
380 BTU System, cold service, 1" FNPT
380 BTU System, cold service, 1-1/4" FNPT
380 BTU System, cold service, 1-1/2" FNPT
380 BTU System, cold service, 2" FNPT
380 BTU System, hot service, 3/4" FNPT
380 BTU System, hot service, 1" FNPT
380 BTU System, hot service, 1-1/4" FNPT
380 BTU System, hot service, 1-1/2" FNPT
380 BTU System, hot service, 2" FNPT
3700
A304-1M
RELATED PRODUCTS
Data acquisition server
Model 380 programming software
WE MAKE IT EASY.
kele.com
888-397-5353 USA
315
FLOW
NEW!
ULTRASONIC ENERGY METER, FLOW METER
DE/DB SERIES
DESCRIPTION
The DE Series ultrasonic energy meter and DB Series ultrasonic
flow meter attach externally to water distribution piping to measure
flow rate and (the DE Series) supply/return temperature difference
to calculate energy consumption. Since they are non-invasive, they
add no pressure head loss to the system and can be installed on
existing piping systems without shutdown or interruption. Installation
is easy and fast, there are no moving parts, and they measure
bi-directional flow. The DE energy meter measures energy usage
in BTU, MBTU, MMBTU, Tons, kJ, kW, MW and is perfect for retrofit
of existing hot water or chilled water hydronic systems. Network
communication models include Modbus RTU over RS485, Modbus
TCP/IP, and Ethernet communication includes BACNet®/IP, EtherNet/
IP® protocols.
6
The DE and DB meters have a backlit display (available with or
without a keypad interface), a USB port for programming, and integral
or remote clamp-on flow transducer configurations. The DE Series
uses strap-on RTD temperature sensors (immersion sensors are also
available). The DE and DB meters work with pipe sizes 1/2" to 100",
are available in 24 VAC, 120 VAC, or 24 VDC power, and have a 4-20
mA analog output for flow rate and a pulse output for totalizing. Free
ULTRALINK™ software is used to configure the meters.
APPLICATION
FLOW
•
•
•
•
Heating/chilled/condenser water
Potable water
Irrigation water
Rain/reclaimed water
FEATURES
• Backlit display for easy reading in low light
• USB Port for configuration and monitoring
• No fluid contact means no fluid compatibility issues,
no pressure drop, and no plant shutdown necessary for
installation
• Bi-directional flow measurement for reversing flow systems
• Selectable engineering units for international preferences
• No moving parts to maintain or replace minimizes service
costs
• Works with small amounts of suspended solids or aeration
• Totalizer options include forward, reverse and net total for
flow measurement flexibility
• Network communication models available for large projects
(up to 126 meters per network)
• Keypad models allow access to many parameters
• Free Ultralink™ software for configuration
SPECIFICATIONS
Supply Voltage
95-264 VAC, 47-63 Hz
20-28 VAC, 47-63 Hz
10-28 VDC
Frequency
DTTS small transducers: 2 MHz
DTTN remote transducers: 1 MHz
DTTL large pipe transducers 500 kHz
Supply VA
17 VA maximum @ 95-264 VAC
Supply Watts
5W @ 10-28 VDC
Supply Current
0.35 A @ 20-28 VAC
Maximum Output ImpedanceAC powered: 400 Ω maximum
DC powered: Maximum loop resistance =
(Vsupply-7)/0.02
Outputs
DE: 4-20 mA internal power, can span
negative-to-positive flow/energy rates
DB: 4-20 mA internal power, can span
negative-to-positive flow/energy rates; two
0-1,000 Hz open collector transistors that
can be configured for flow rate, alarming or
totalizing
Wiring
Transducer cables: RG59 coaxial 75 Ω or
Twinaxial 78 Ω, (optional armored conduit),
maximum length 990' (300 m) in 10' (3m)
increments
RTDs (DE meters only): Platinum 385, 1 kΩ,
3-wire PVC jacket cable
Conduit Opening
Two 1/2" FNPT and one 3/4" FNPT
Cable Length
Remote transducer models available with 20'
(6.1m), 50' (15m), or 100' (30m) cables
Communication
USB: 2.0 for connection to PC running
ULTRALINK™ configuration utility
RS485: Modbus RTU command set,
ENERGYLINK network monitoring software
10/100 Base-T: RJ45 communication via
Modbus TCP/IP, Ethernet/IP and BACnet®/IP
Configuration
PC running free ULTRALINK™ software or
via integral display keypad (limited access to
parameters)
316
888-397-5353 USA
kele.com
Accuracy
Repeatability
Sensitivity
Display
Engineering Units
Pipe Size Range
Velocity Range
Operating Temperature
Media Compatibility
Materials Of Construction
Enclosure Rating
Approvals
Warranty
Flow: ± 1.0% of reading above 1 fps (0.3
mps) velocity, ± 0.01% of reading below
1 fps (0.3 mps)
Temperature (DE only): 0.45°F (0.25°C)
0.5% of reading
Flow: 0.001 fps (.0003 mps)
Temperature: 0.05°F (.025°C)
Two-line LCD, LED backlit, top row: 0.7" (1.8
cm) height, 7-segment; bottom row: .35"
(0.9 cm) height, 14-segment; flow rate and
totalization indication
DB: flow rate in gallons, cubic feet, million
gallons, barrels, acre-feet, lbs., meters, cubic
meters, liters, million liters, kg.
DE: flow rates above plus BTU, MBTU,
MMBTU, Tons, kJ, kW, MW
1/2" to 100" (1.2 to 254 cm)
0.1 to 40 fps (feet/second), 0.03 to 12.4 mps
(meters/second), bi-directional
-40° to 185°F (-40° to 85°C); remote DTTS/
DTTN transducers have upper limit of 250°F
(121°C) and high temperature DTTH have
upper limit of 400°F (200°C)
Most clean liquids or liquids with some
suspended solids or aeration
Enclosure: powder-coated aluminum,
polycarbonate, stainless steel, polyurethane,
nickel-plated steel mounting brackets
Transducers: NEMA 6 (IP67), PVC/CPVC,
Ultem®, Nylon cord grip, PVC cable jacket
NEMA 4 (IP65) as long as a liquid-tight
connectors are used
CSA C22.2 No. 61010-1 (24 VDC, 120 VAC
only); CE EN61326-1:2006
1 year
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
FLOW
ULTRASONIC ENERGY METER, FLOW METER
DE/DB SERIES
INSTALLATION (DE MODEL SHOWN; DB DOES NOT HAVE TEMPERATURE TRANSDUCERS)
Bottom
Botto
om View
Integral Flow Transducer
Remote
Flow Transducers
Front View
Supply
Supply
Temperature Transducers
Temperature Transducers
Return
Return
Transmitter with remote transducers
Transmitter with integral transducers
6
DIMENSIONS AND FLOW RANGES
Mechanical Dimensions: Inches (MM)
Remote System
DTTS/DTTN Transducer Dimensions: Inches (MM)
Pipe
Size
4.20
(106.7)
Pipe
Material
ANSI/DN
6.00
(152.4)
½"
ANSI/DN
4.32
(110)
¾"
Pipe mount
Wall mount
ANSI/DN
2.12
(53.8)
1"
1.38
(35.1)
6.50
(165.1)
2.90
(73.7)
2.30
(58.4)
ANSI/DN
1-¼"
1.20
(30.5)
.19 DIA (4.8)
2 Mounting
holes
ANSI/DN
1-½"
Integral System
2.12
(53.8)
ANSI/DN
2"
B
D
C
C (Min Clearance)
B
A
* Varies due to U-bolt configuration
A
DTTN/DTTH
Pipes larger than 2" (50 mm)
A
DTTN 2.95
(74.9)
DTTH 2.95
(74.9)
DTTS
Pipes/Tubing ½" to 2" (12 mm to 50 mm)
B
2.75
(69.8)
2.75
(69.8)
C
3.00
(76.2)
3.00
(76.2)
DTTL 3.40 2.94 3.20
(86.4) (74.7) (81.3)
B
D
A
March 2014
FLOW
Measuring
Range
2 - 38 GPM
8 - 144 LPM
1.8 - 27 GPM
7 - 102 LPM
1.5 - 18 GPM
6 - 68 LPM
2.75 - 66 GPM
10 - 250 LPM
2.5 - 54 GPM
10 - 204 LPM
2.5 - 45 GPM
10 - 170 LPM
3.5 - 108 GPM
13 - 409 LPM
3.5 - 95 GPM
13 - 360 LPM
3.5 - 85 GPM
13 - 320 LPM
5 - 186 GPM
19 - 704 LPM
4.5 - 152 GPM
17 - 575 LPM
4 - 136 GPM
15 - 514 LPM
6 - 250 GPM
23 - 946 LPM
5 - 215 GPM
19 - 814 LPM
5 - 200 GPM
19 - 757 LPM
2.375
8 - 420 GPM
(60.3)* 30 - 1590 LPM
2.125
8 - 375 GPM
(54.0)* 30 - 1419 LPM
8 - 365 GPM
30 - 1381 LPM
DTTS U-Bolt Connections
ANSI/DN & Copper 2" (50 mm) Models
B
D
C
WE MAKE IT EASY.
A
kele.com
C
888-397-5353 USA
317
NEW!
FLOW
ULTRASONIC ENERGY METER, FLOW METER
DE/DB SERIES
IN: 18-36VAC
OUT: 15VDC
ASD06-24S15
POWER WIRING FOR 120 VAC
ACN
OUT−
OUT+
-IN+
POWER WIRING FOR 24 VAC
R
Chassis Gnd.
24 VAC
AC Neutral
Signal Gnd.
Control 1
Control 2
Frequency Out
4-20 mA Out
Reset Total
Modbus Gnd
Modbus B
Modbus A
O1
N
2 3 4
-Vo
R2807
95 - 264 VAC
AC Neutral
Signal Gnd.
Control 1
Control 2
Frequency Out
4-20 mA Out
Reset Total
Modbus Gnd
Modbus B
Modbus A
Modbus
TFX Rx
TFX Tx
O1
N
Modbus
TFX Rx
TFX Tx
+
Downstream
Upstream
+
Test
P1
+Vo
ACL
+
Downstream
Upstream
+
6
strodyne
www.astrodyne.com
PWC-15E 0.15A
AC IN : 100-240VAC,50/60Hz
DC OUT : +15V / 0.3A
2 3 4
24 VAC
Transformer
POWER WIRING FOR 24 VDC
4-20 mA Out
Reset Total
Modbus Gnd
TD(A)TD(B)+
GND
GND
+12V
Modbus B
Modbus A
10 - 28 VDC
Power Gnd.
Signal Gnd.
Control 1
Control 2
Frequency Out
4-20 mA Out
Reset Total
Modbus Gnd
Modbus B
Modbus A
RS-485
Model 485SD9TB
To 12 VDC
Supply
RS-232
O1
N
TEMPERATURE SENSOR WIRING
2 3 4
Modbus
TFX Rx
TFX Tx
10 -28
VDC
+
Downstream
Upstream
+
RS-485 Converter
FLOW
COMMUNICATIONS WIRING (model specific)
Power
Ground
4-20 mA OUTPUT WIRING
WHITE
RED
PIN #8
PIN #6
PIN #5
RTD2
BLACK
GREEN
PIN #4
PIN #3
PIN #2
PIN #1
BROWN
RTD1
BLUE
DRAIN
WHITE
BLACK
RED
DRAIN
GREEN
BLUE
BROWN
318
888-397-5353 USA
kele.com
PIN#5
PIN#3
PIN#1
PIN#8
PIN#6
PIN#4
PIN#2
*Loop
Resistance
1
Signal Gnd.
2
Control 1
3
Control 2
4
Frequency Out
5
4-20 mA Out
6
Reset Total
DE/DB Series
*Loop resistance maximum = 400 ohms for AC powered units or (supply voltage – 7
VDC/0.02 for DC powered units.
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
FLOW
ULTRASONIC ENERGY METER, FLOW METER
DE/DB SERIES
ORDERING INFORMATION
MODEL
DE
DB
DESCRIPTION
BTU Meter
Flowmeter
PIPE SIZE
IA
1/2" ANSI pipe
IB
3/4" ANSI pipe
IC
1" ANSI pipe
ID
1 1/4" ANSI pipe
IE
1 1/2" ANSI pipe
IF
2" ANSI pipe
IG
1/2" copper
IH
3/4" copper
II
1" copper
IJ
1 1/4" copper
IK
1 1/2" copper
IL
2" copper
IM
1/2" OD tubing
IN
3/4" OD tubing
IP
1" OD tubing
IQ
1 1/4" OD tubing
IR
1 1/2" OD tubing
IS
2" OD tubing
RZ Remote Flow Transducers (see DT, DS tables)
6
TRANSDUCER MATERIAL/TEMPERATURE
L
PVC: -40 to +185˚F (-40 to +185˚C)
H
CPVC: -40 to +250˚F (-40 to +121˚C)
N
None (select for Remote Transducer Only)
POWER
90-264 VAC
A
C
20-28 VAC
D
11-28 VDC
KEYPAD
Keypad
Y
N
No keypad
COMMUNICATIONS
Y
N
10/100 Base-T (EtherNet/IP, BACnet/IP, Modbus TCP/IP)
No communications
ENERGY TEMPERATURE RANGE (Separately ordered RTD kit required)
+32 to +122˚F (0 to +122˚C)
+32 to +212˚F (0 to +100˚C)
N
None (for DB flowmeter)
H
-40 to +350˚F (-40 to +177˚C)
X
-4 to +85˚F (-20 to +30˚C)
FLOW
L
M
APPROVALS
N
General safety (power supply C only)
OPTIONS
0
None, plugged ports
1
Cable Gland Kit
Remote transducers for small pipes (with “RZ” pipe size)
MODEL DESCRIPTION
DTTS
Remote transducers for 1/2" to 2" pipes
DTTC
High Temperature transducer for 1/2” to 2” pipes
PIPE SIZE
D 1/2"
F 3/4"
G 1"
H 1 1/4"
J 1 1/2"
L 2"
PIPE TYPE
P ANSI carbon steel
C Copper
T Tubing
CABLE LENGTH
020 20 feet (6.1 m)
050 50 feet (15 m)
100 100 feet (30 m)
CABLE ARMOR OPTION
N No armor
A Flexible armor
CABLE ARMOR LENGTH
000 No armor
020 20 feet (6.1 m)
050 50 feet (15 m)
100 100 feet (30 m)
D002-2007-005
D005-0350-300
D005-0803-104
D005-2117-003
D005-2117-004
D010-2102-010
D010-2102-016
D010-3000-120
D010-3000-121
D010-3000-122
March 2014
Remote
MODEL
DTTN
DTTH
DTTL
transducers for large pipes (with “RZ” pipe size)
DESCRIPTION
Standard transducer for 2 1/2" to 20" pipes
High temperature transducer for 2 1/2" to 100" pipes
Large transducer for 22" to 100" pipes
CABLE LENGTH
020 20 feet (6.1 m)
050 50 feet (15 m)
100 100 feet (30 m)
CABLE ARMOR OPTION
N No armor
A Flexible armor
CABLE ARMOR LENGTH
000 No armor
020 20 feet (6.1 m)
050 50 feet (15 m)
100 100 feet (30 m)
OPTIONS
N
Normal area rating
Note: Shaded selections are special order.
Note: DT remote transducers come with 36"
straps that fit pipes up to 10".
(P/N D002-2007-001)
ACCESSORIES
72" stainless steel straps, 1 pair, for DTTN/DTTH, for pipes up to 20"
RTD Connector Kit (required for non-standard sensors)
UltraLink PC software for DE/DB Meters
USB A/B Cable, 10 ft. (3 m) for DE/DB Series Meters
USB A/B Cable, 15 ft. (4.6 m) for DE/DB Series Meters
Mounting track assembly for DTTN/DTTH transducers, for <10" pipes
Mounting track assembly for DTTN/DTTH transducers, for 10" to 16" pipes
RTD kit for DE Energy Meter, strap-on, 20 ft. cables
RTD kit for DE Energy Meter, strap-on, 50 ft. cables
RTD kit for DE Energy Meter, strap-on, 100 ft. cables
WE MAKE IT EASY.
kele.com
888-397-5353 USA
319
FLOW
PADDLE FLOW SWITCH
626600A
DESCRIPTION
The 626600A Flow Switch from Caleffi is used to prove
liquid flow in 1" to 8" pipes containing water, 50% or less
glycol solutions, or other liquids that are compatible with
stainless steel, brass, and EPDM. It is designed for use in
HVAC systems, heat exchangers, pumping systems, water
treatment, and process systems in general.
The high quality of Model 626600A makes it ideal for
controlling pumps, burners, compressors, refrigerators,
motorized valves, or for activation of signaling units or
warning devices.
NEW!
6
FEATURES
• 316L stainless steel bellows for durability and long life
• NEMA 5 (IP54) environmental rating for use in humid or
dusty environments
• Six stainless steel blades to fit 1" to 8" pipes
• Insulated cover over microswitch contacts for safety
• Large, easily-accessible calibration screw with locking
nut to maintain setpoint
FLOW
626600A
WIRING
SPECIFICATIONS
Contact Rating
Resistive/Inductive: 15A @ 240
VAC maximum; Lamp load: 3A @
125 VAC for the N.C. contact, 1.5A
@ 125 VAC for the N.O. contact;
Motor load: 5A, 1/4 HP @ 125 VAC
for the N.C. contact, 2.5A, 1/8 HP
@ 125 VAC for the N.O. contact
Pipe Size Range
1" to 8" (2.5 to 20 cm)
Connections
1" MNPT
Operating Temperature130°F (55°C) maximum ambient
Media Temperature
Range -22° to 250°F (-30° to 121°C)
Maximum System
Pressure
150 psig (1 bar)
Materials Of
Construction
Wetted parts: P-Cu Zn40 Pb2 brass
body, 316L stainless steel bellows,
EPDM o-ring; Housing cover:
Class UL94V-0 self-extinguishing
polycarbonate
Approvals
CE, UL File E307420
Weight
1.7 lb (0.8 kg)
Warranty
2 years
320
888-397-5353 USA
kele.com
1
COMMON
3
NO
2
NC
Shown in no-flow, normal position
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
FLOW
PADDLE FLOW SWITCH
626600A
DIMENSIONS
1/2" FNPT
conduit
connection
3"-DN 80
$
1"
1.25"
1.5"
2"
2.5"
3.4
(87)
in
(mm)
5.5
(135)
3.1
(80)
4"-DN100
5"-DN125
6"-DN150
DN 175
8"-DN200
6
Select the blade marked with the diameter of the pipe in which the switch will be installed. For pipe sizes 1" to 2.5", remove all extra pre-fitted
blades. For pipes 3" and above, leave all pre-fitted blades installed and add the long blade and trimming as shown for pipe size. Install the switch
in the pipe, observing the flow direction arrows shown on the body casting and housing cover. The distance between the top of the pipe and
the upper surface of the brass housing should be 3.1" (80 mm).
The switch can be installed in a horizontal or vertical pipe, but avoid installing the switch below horizontal; dirt and deposits may collect in the
switching mechanism and affect operation.
OPERATION
1"
1.25"
1.5"
2"
2.5"
3"
4"
5"
6"
8"
Minimum calibration
Operating flow rate with
increasing flow
5.7
(21.7)
7.5
(28.4)
11.4
(43.4)
13.2
(50.1)
22.0
(83.5)
29.9
(113)
44.0
(167)
61.1
(232)
72.6
(275)
162
(618)
Minimum calibration
Operating flow rate with
decreasing flow
4.0
(15.0)
5.5
(20.9)
8.4
(31.7)
9.7
(36.7)
16.3
22.9
(61.8) (86, 8)
37.4
(142)
51.5
(197)
63.8
(242)
145
(551)
Maximum calibration
Operating flow rate with
increasing flow
12.3
(46.8)
16.7
(63.5)
26.0
(98.5)
29.5
(112)
51.5
(195)
69.5
(264)
94.6
(359)
136
(518)
189
334
(718) (1269)
Maximum calibration
Operating flow rate with
decreasing flow
11.9
(45.1)
16.3
(61.8)
25.5
(96.9)
29.0
(110)
50.6
(192)
68.6
(260)
92.4
(351)
127
(484)
158
308
(601) (1169)
Diameter of Pipe
FLOW
Operating flow rates:
gpm (lpm)
CALIBRATION
B
A
C
If the required operating flow rate differs from that given in the table below, the necessary correction
should be carried out as follows: turn the calibration screw (A) in a clockwise direction for the contacts
to close at higher flow rate values or in a counterclockwise direction for lower flow rate values. When the
adjustment has been made, lock the screw (A) with the locking ring nut (B). Avoid all contact with the
presetting screw (C). An incorrect setting would seriously impair the operation of the switch.
ORDERING INFORMATION
MODEL
626600A
March 2014
DESCRIPTION
Paddle flow switch, 1" to 8" pipes, NEMA 5
WE MAKE IT EASY.
kele.com
888-397-5353 USA
321
FLOW
FLOW SWITCH
FS1-6
DESCRIPTION
The Kele FS1-6 paddle flow switch is designed to
prove liquid flow in a wide variety of HVAC and industrial
applications. The corrosion-resistant flow switch is mounted
in a weather-resistant box for simple wiring connections. The
polyphenylene sulfide plastic vane is field trimmable for 1"
(2.54 cm) and larger pipes, and it is magnetically coupled to
the SPDT switch to prevent liquid from entering the switch
housing.
NEW!
FEATURES
FLOW
6
•
•
•
•
•
Weather-resistant construction
Simple installation
Leak-proof magnetic switch operation
Field adjustable for 1" (2.54 cm) and larger pipes
SPDT snap-acting switch
DIMENSIONS
SPECIFICATIONS
Contact Arrangement SPDT; black wire = common, red
wire = normally open (at no flow),
blue wire = normally closed (at no
flow)
Contact Rating
5A @ 125/250 VAC
Wiring
18" (46 cm) leads, 18 AWG
Pipe Size Range
1" to 12" (2.5 to 30 cm)
Connections
1" MNPT
Media Temperature
Range
212°F (100°C) maximum
Maximum System
Pressure
150 psig (1 bar)
Materials Of
Construction
Wetted parts: Polyphenylene
sulfide vane, ceramic 8 magnet,
316 stainless steel spring and pin
Weight
1 lb (.45 kg)
Warranty
1 year
in
(cm)
2.75
(6.99)
2.25
(5.72)
4.50
(11.43)
13.25*
(33.66)
1" NPT
pipe connection
5.00*
(12.70)
1.00
(2.54)
WIRING
Black - Common
Red - Normally open (no flow)
Blue - Normally closed (no flow)
322
888-397-5353 USA
kele.com
* Dimension with vane full length for 6" and larger pipe installation
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
FLOW
FLOW SWITCH
FS1-6
INSTALLATION
1. Carefully unpack switch, making sure to remove any packing from the lower housing. Adjust the actuation or deactuation point
by trimming the vane to the length desired. If using a pipe with weld-o-let, cond-o-let, or plastic PVC fittings, use graduations
indicated on the vane. If using standard 125 or 250 lb (57 or 113 kg) bronze, iron, or steel fittings, trim the vane 0.125" (0.32
cm) above the marking provided. Because of the great variation in fittings and process connections, it is recommended the unit
be checked when installed to ensure proper operation and that there is no interference between the vane and the fittings. For
pipes larger than 6" (15.24 cm), leave the vane full length.
2. This flow switch is intended to be used in clean process media where particles, scale, and debris are not present. Buildup of
such materials may cause inaccurate signals.
3. The switch must be indexed during installation in the line with the flow arrow on the side of the switch pointing in the direction
of the flow. Pipe sealant is required at the 1" NPT thread connection. It is important to not get the sealant in the vane assembly
as it may prevent proper operation and cause misleading signals. When installing the unit, be certain not to over-torque the
housing. Damage may occur if excessive force is used.
6
4. Connect the switch wires in accordance with local electrical codes. The FS1-6 is not intended to be a load-carrying conduit
connection. Loads may damage the switch and stop operation.
PIPE
SIZE
1
1.25
1.5
2
3
4
6
8
10
12
ACTUATION
gpm (lpm)
10.7 (40.5)
9.5 (36.0)
8.1 (30.7)
9.8 (37.1)
12.4 (46.9)
20.2 (76.5)
43.0 (163)
74.2 (281)
116.7 (442)
167.1 (632)
FLOW
PERFORMANCE
DEACTUATION
gpm (lpm)
9.3
7.7
6.3
8.5
8.9
12.7
32.8
56.6
89.0
127.4
(35.2)
(29.1)
(23.9)
(32.2)
(33.7)
(48.1)
(124)
(214)
(337)
(482)
ORDERING INFORMATION
MODEL
FS1-6
March 2014
DESCRIPTION
Weather-resistant flow switch
WE MAKE IT EASY.
kele.com
888-397-5353 USA
323
FLOW
FLOW SWITCH
F61 SERIES
DESCRIPTION
6
The Johnson Controls F61 Series paddle flow switches
are used to prove flow on liquid lines using water, ethylene
glycol solutions, or other liquids compatible with brass and
phosphor bronze parts. The SPDT contact switch is activated
by liquid flow through the pipe and the set point is adjustable.
The F61KD (NEMA 1 enclosure) and F61MD (NEMA 3R
enclosure) are inline models for 1/2" NPT and 3/4" NPT pipe.
The F61KB-11 (NEMA 1 enclosure) and F61MB-1 (NEMA
3R enclosure) are for 1" (2.5 cm) and larger pipes. They are
furnished with a stainless steel paddle in three segments for
pipes 1" to 3" (2.5 to 7.6 cm) in diameter. Paddle segments
may be removed or trimmed as needed. A 6" (15 cm) paddle
is also furnished for 4" (10 cm) diameter pipes and larger.
NEW!
F61KB-11
F61KD-3
FLOW
SPECIFICATIONS
Media Temperature Range
KB-11, KD-3, KD-4
32°F to 250°F (0°C to 121°C)
MB-1, MD-1, MD-2
-20°F to 250°F (-30°C to 121°C)
Maximum System
Pressure
150 psig (1034 kPa)
Materials Of Construction
KB-11, MB-1, KD-3,
KD-4 MD-1, MD-2
Approvals
Warranty
Brass fittings, phosper bronze
bellows, stainless steel paddle
Brass fittings, stainless steel
bellows, stainless steel paddle
UL recognized, File E5368
1 year
WIRING
ELECTRICAL RATINGS
MOTOR RATINGS
Horsepower
AC full load amps
AC locked rotor amps
120V 208V
1
1
16
8.8
96
52.8
Noninductive or
Resistance load amps
240V 277V
1
–
8
–
48
–
16
16
16
Pilot duty – 125 VA 24/277 VAC
16
Action on increase
of flow
B
Y
R
F61 Series
DIMENSIONS
324
Model
Size
Connections
Dimensions
Weight
Enclosure
Rating
F61KD-3
1/2"
FNPT inline
5.0"H x 4.0"W x 2.8"D (12.8 x 10.1 x 7.1 cm)
2.1 lb (.95 kg)
NEMA 1
F61MD-1
1/2"
FNPT inline
5.0"H x 4.0"W x 2.8"D (12.8 x 10.1 x 7.1 cm)
2.2 lb (1.0 kg)
NEMA 3R
F61KD-4
3/4"
FNPT inline
5.0"H x 4.0"W x 2.8"D (12.8 x 10.1 x 7.1 cm)
2.1 lb (.95 kg)
NEMA 1
F61MD-2
3/4"
FNPT inline
5.0"H x 4.0"W x 2.8"D (12.8 x 10.1 x 7.1 cm)
2.2 lb (1.0 kg)
NEMA 3R
F61KB-11
1"
1" MNPT insertion
8.4"H (3" paddle) x 4.0"W x 2.8"D (21.3 x 10.2 x 7.1 cm)
1.7 lb (.77 kg)
NEMA 1
F61MB-1
1"
1" MNPT insertion
8.7"H (3" paddle) x 4.8"W x 2.8"D (22.1 x 12.2 x 7.1 cm)
2.4 lb (1.1 kg)
NEMA 3R
888-397-5353 USA
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
FLOW
FLOW SWITCH
F61 SERIES
ADJUSTMENTS: TYPICAL FLOW RATES — gpm (m3/hr)
LINE PIPE SIZE (in)
Flow
increases
R to Y
closes
Flow
decreases
R to B
closes
Flow
increases
R to Y
closes
Flow
decreases
R to B
closes
MODEL
F61KB-11
F61MB-1
Minimum
adjustment
Maximum
adjustment
1
1-1/4
1-1/2
2
2-1/2
3
4.2
(1.0)
5.8
(1.3)
7.5
(1.7)
13.7
(3.1)
18.0
(4.1)
27.5
(6.2)
2.50
(0.6)
3.70
(0.8)
5.00
(1.1)
9.50
(2.2)
12.50
(2.8)
19.00
(4.3)
8.80
(2.0)
13.30
(3.0)
19.20
(4.4)
29.00
(6.6)
34.50
(7.8)
53.00
(12.0)
8.50
(1.9)
12.50
(2.8)
18.00
(4.1)
27.00
(6.1)
32.00
(7.3)
50.00
(11.4)
4*
5*
6*
8*
65.0
(14.8)
37.0†
(8.4)
50.0
(11.4)
27.0†
(6.1)
128.0
(29.1)
81.0†
(13.4)
122.0
(27.7)
76.0†
(17.3)
125.0
(28.4)
57.0†
(12.9)
101.0
(22.9)
41.0†
(9.3)
245.0
(55.6)
118.0†
(26.8)
235.0
(53.4)
111.0†
(25.2)
190.0
(43.1)
74.0†
(16.8)
158.0
(35.9)
54.0†
(12.3)
375.0
(85.2)
144.0†
(32.7)
360.0
(81.8)
135.0†
(30.7)
375.0
(85.2)
205.0†
(46.6)
320.0
(72.7)
170.0†
(38.6)
760.0
(172.6)
415.0†
(94.2)
730.0
(165.8)
400.0†
(90.8)
MODEL
INLET/OUTLET
SIZE
(Female NPT)
NEMA
Enclosure
1/2" x 1/2"
3/4" x 3/4"
1/2" x 1/2"
3/4" x 3/4"
1
1
3R
3R
F61KD-3
F61KD-4
F61MD-1
F61MD-2
FLOW
*Flow rates for these sizes are calculated.
† These gpm figures are for switch with 6" paddle. For 4" and 5" line pipe the paddle is trimmed.
6
ADJUSTMENT RANGE – gpm (m3/hr)
R to Y closes
flow increase
R to Y opens
flow decrease
Minimum 0.6 (0.14)
Maximum 1.1 (0.25)
Minimum 0.3 (0.07)
Maximum 0.9 (0.2)
ORDERING INFORMATION
MODEL
F61KD-3
F61MD-1
F61KD-4
F61MD-2
F61KB-11
F61MB-1
March 2014
DESCRIPTION
Flow switch inline 1/2" x 1/2" NPT, NEMA 1
Flow switch inline 1/2" x 1/2" NPT, NEMA 3R
Flow switch inline 3/4" x 3/4" NPT, NEMA 1
Flow switch inline 3/4" x 3/4" NPT, NEMA 3R
Flow switch for pipe 1" diameter and larger, NEMA 1
Flow switch for pipe 1" diameter and larger, NEMA 3R
WE MAKE IT EASY.
kele.com
888-397-5353 USA
325
FLOW
COU, LIM, JAG, AND PAN MODELS
EDC CONDENSATE PUMPS
DESCRIPTION
Kele offers a variety of condensate removal pumps that are small,
quiet running, and high performance for air conditioning and
ventilation systems. Rigorously tested for total efficiency over a long
life-span, these devices are in use all over the world.
FEATURES
DRAIN PAN PUMP (COU)
• Electronic Energy Control System (EECS) for quiet start/stop
• Designed for low-cost installations
• Compact dimensions
• Completely encapsulated electronics
• Auto-sensing power, one model for 110/120 or 208/240 VAC
6
LIMPET CONDENSATE DISCHARGE (LIM)
• Electronic Energy Control System (EECS) for quiet start/stop
• 120V or 240V auto sensing
• Built-in alarm circuit
• Thermal protection
• Built-in non-return valves
CONDENSATE PUMP (JAG)
• Electronic Energy Control System (EECS) for quiet start/stop
• Electronic control with high water alarm
• Fits all wall-mount air conditioners
• Mounts vertically or horizontally
NEW!
COU
LIM
JAG
PAN
CONDENSATE REMOVAL (PAN)
• Electronic Energy Control System (EECS) for quiet start/stop
• Small footprint, low profile for ease of mounting
• Electronic control with high water alarm
• Tiny remote mount reservoir/sensing unit
• Fits all wall-mount splits
FLOW
COMMON SPECIFICATIONS
Supply Voltage 120-240 VAC 50/60 Hz auto sensing
Supply Watts
17W
Operating Temperature 32° to 104°F (0° to 40°C)
Media Temperature Range104°F (40°C) maximum
Alarm Relay 5A, 30 VDC, 250 VAC breaks on fault
Maximum Capacity
3.2 gallons/hour (12 liters/hour)
Maximum Discharge
Lift Approvals
Warranty
65' (20 m)
CE, UL94 5 VA flame retardant
ABS material
2 years
DIMENSIONS
Model
Dimensions
Wiring
COU.6000.0
1.7"H x 1.3"W x 6.3"L (4.3 x 3.43 x 16.0 cm) with .25" (.6 cm) ID discharge tube
18" (46 cm) 5-conductor cable, alarm contacts rated
5A @ 250 VAC, 30 VDC, break on fault
LIM.6000.0
2.4"H x 2.0"W x 11.3"L (6.1 x 5.3 x 28.6 cm) with .25" (.6 cm) ID discharge tube
18" (46 cm) 5-conductor cable, alarm contacts rated
5A @ 250 VAC, 30 VDC, break on fault
JAG.6000.0
1.8"H x 1.6"W x 6.9"L (4.6 x 4.0 x 17.5 cm) with .25" (.6 cm) ID discharge tube
40" (1 m) 18 AWG 5-conductor cable, alarm contact
rating 5A @ 250 VAC maximum, break on fault
PAN.6000.0
Pump: 1.3"H x 1.8"W x 5.3"L (3.2 x 4.6 x 13.5 cm) with .25" (.6 cm) ID discharge tube
Remote Sensor: 1.4" dia. x 1.8"W (3.6 x 4.5 cm) with 5' (1.5m) x 0.125" (3.3 mm) tube
40" (1 m) 18 AWG 5-conductor cable, alarm contact
rating 5A @ 250 VAC maximum, break on fault
ORDERING INFORMATION
326
MODEL
COU.6000.0
LIM.6000.0
JAG.6000.0
PAN.6000.0
DESCRIPTION
Drain pan pump, 110-230 VAC auto sensing, 3.2 gph (12 lph)
Condensate discharge system, 110-230 VAC auto sensing, 3.2 gph (12 lph)
Condensate pump, 110-230V 50/60 Hz auto sensing, 3.2 gph (12 lph)
Condensate pump with remote sensor, 110-230V 50/60 Hz auto sensing, 3.2 gph (12 lph)
ACC.0038.0
ACC.0056.0
DPP.0076.0
LIM.0071.0
PCF.0061.0
ACCESSORIES
Inline filter kit for PAN, JAG pumps
Anti-syphon valve kit
Drain pan pump skirt filter
Replacement filter element for LIM.4000 system
Acoustic jacket for JAG, PAN pumps
888-397-5353 USA
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
FLOW
PORTABLE ULTRASONIC FLOW AND ENERGY METER
DXN SERIES
DESCRIPTION
The Badger Meter DXN Series portable ultrasonic flow
and energy meter is a true hybrid instrument, capable of
measuring liquid flow with multiple technologies, including:
Doppler, transit time and liquid thermal (heat energy) flow.
Easy to install by clamping onto the outside of the pipe,
the DXN measures flow using non-invasive ultrasonic
sensors. Compatible with a pipe wall thickness gauge,
inside pipe diameter can be verified to ensure accurate
ultrasonic measurements when piping details are unknown or
unavailable.
The DXN Series has a number of advanced features
including a touchscreen interface, full-color graphing,
wizard-based start-up configuration, USB connectivity, and
Modbus TCP/IP connectivity. These features make it easy for
technicians to obtain accurate readings while capturing flow
surges and high-speed batch operations. The DXN Series
captures and displays multiple user-defined and application
parameters at once and can record the data with an easy-touse data logging function. The ability to monitor and record
several parameters at once allows technicians to verify and
troubleshoot permanent flow installations with ease.
6
DXN w Transducers
SPECIFICATIONS
Input Signal
Digital Inputs
Cable Length
Repeatability
Display
Pipe Size Range
Velocity Range
Storage Temperature
Approvals
Ambient Conditions
Battery
Breakout Box
Connector
Digital Output
Rate or Total Pulse
User Selectable
Enclosure
Energy or Temperature
Flow Rate Accuracy
March 2014
80kΩ input impedance
14 V @ 50 mA max for powering current
or voltage sensors
Totalizer reset, external pull-up
Transit time: 20' (6 m) paired coaxial
cable, BNC to BNC,
Doppler: 20' (6 m) paired coaxial cable,
BNC to 4-pin
±0.1% of reading
800 x 480 WVGA Color Outdoor
Readable Display; Gloved-operation
resistive touch screen
1/2" and larger; US standard pipe tables
are built into User interface
Transit Time: Bi-directional to 40 FPS
(12 MPS)
Doppler: Uni-directional to 40 FPS (12
MPS)
Do not exceed 175°F (80°C)
Safety: UL61010-1, CSA C22.2 No.
61010-1, EN61010-1
Directives: 2006/95/EC Low Voltage,
2004/108/EC EMC
Battery powered: -4° to 110°F
(-20° to 45°C)
Externally powered: -20° to 140°F
(-30° to 60°C)
Internal 11.1 V lithium ion battery, 75W-hr.
Provides 6-9 hrs of continuous operation
with battery and indefinitely on external
power. Charging 32° to 104°F (0° to
40°C), 12 hours while in use; 4 hours
powered off
0.2" quick disconnect screw terminals;
15 pin to adapter box; 6' (1.8 m) of cable
(DSUB to DSUB connectors)
15-pin high-density DSUB
Open collector, external or pull-up
Rate pulse: 0-1000 Hz
Total pulse: 33 ms duration
Water/Dust resistant [IP 64]
2x RTDs PT1000 tab type; can handle
various temperature ranges from -58° to
570°F (-50° to 300°C), based on RTD
type
Transit Time: ±1% of reading or ±0.01
Flow Sensitivity
Housing Material
Liquid Types
Logging Sampling Rate
Measurement Update
Output Current
Output Voltage
FPS (0.003 MPS), whichever is greater
Doppler: 2% of full scale
0.001 FPS (0.0003 MPS)
DTTSU: CPVC, Ultem®, and anodized
aluminum track system; Nickel-plated
brass connector with Teflon® insulation
DTTN/DTTL/DT94: CPVC, Ultem®;
Nickel-plated brass connector with
Teflon® insulation
Liquid dominant fluids
>300 sites stored in 1 GB; downloads to
USB Flash drive
0.1-10 seconds update/filter rate. Transit
time, up to 50 Hz high speed mode
4-20 mA active/passive 1% accuracy
0-5 V or 0-10 V output voltage, 1%
accuracy
FLOW
Software Scaling
and Control
Sensor Input
Voltage input. 0-5V or 0-10 V,
1% accuracy
Software Scaling
and Control
100Ω output impedance
Pipe Surface Temperature DTTSU/DTTN/DTTL: -40° to 250°F
(-40° to 121°C)
DT94: -40° to 250°F (-40° to 121°C)
Pipe Thickness
Dual mode transducer with 6' (1.8 m) of
cable (BNC ends)
Power Cords
North American plug (2 flat & 1 round
prong; NEMA 5/15P); China plug (3 flat
prongs; GB2099); Euro plug (2 round
prongs; CEE7/7); U.K. plug (3 rectangular
prongs; BS1363A); Japan plug (2 flat & 1
round, JIS8303, w/ 3-2 prong adapter)
Power Requirements
10-30 VDC via-3-pin connector, 40 W min;
3.6A resettable fuse
Supplies: Desktop adapter: 100-240 VAC
50/60 Hz 50 W 10V-18V; Cigarette lighter
adapter: 5A fused
RTDs
2x platinum 385, 1000Ω, 3-wire PVC
jacketed cable standard with quick
connector
Temperature Accuracy
Absolute 0.5°F (1°C); Difference 0.2°F
(0.5°C);
Resolution 0.02°F (0.01°C)
Transducer Frequency
DTTSU: 2 MHz, DTTN: 1 MHz, DTTL: 500
kHz DT94: 625 kHz
User Menu
Windows .NET fully integrated user
menu; multi-language: English, Spanish,
German, French, Portuguese, Japanese,
Russian, Italian, Dutch, Norwegian, and
Swedish
Approvals
CSA
Warranty 1 year
WE MAKE IT EASY.
kele.com
888-397-5353 USA
327
FLOW
NEW!
PORTABLE ULTRASONIC FLOW AND ENERGY METER
DXN SERIES
SENSOR AND HARDWARE KIT OPTIONS
Basic
All Transit
Time
Basic Kit and large pipe transducers
Hybrid
Basic kit and Doppler transducers
Energy
Basic kit and non-invasive RTDs
(1) Silicone Heat Sink Compound; 5 oz syringe
(1) RTD Installation tape, 36 ft
Full
Basic kit plus all, transit time, Doppler, RTDs and pipe wall
thickness gauge
(1) Silicone Heat Sink Compound; 5 oz syringe
(1) RTD Installation tape, 36 ft
(2) Stainless steel straps (1/2" wide, 21-1/4" max dia.,
worm drive clamp)
PARTS AND ACCESSORIES
Power Cords/Cables
FLOW
6
Small pipe and standard pipe transit time transducers
(1) Couplant, grease; 5.3 oz; Dow 111
(1) Couplant, Ultrasound gel; 0.25 liter bottle
(4) Stainless steel straps (1/2" wide, 12-5/16" max dia.,
worm drive clamp)
Part Number
Description
D005-2109-013
North American plug (2 flat & 1 round prong; NEMA 5/15P)
D005-2109-015
UK plug (3 rectangular prongs; BS1363A)
D005-2109-016
Euro plug (2 round prongs; CEE7/7)
D005-2109-017
Japan plug (2 flat & 1 round, JIS8303, w/ 3-2 prong adapter)
D005-2109-014
China plug (3 flat prongs; GB2099)
D005-2129-020
Transit time Cables, 20' (6 m)
D005-2129-050
Transit time Cables, 50' (15 m)
D005-2129-100
Transit time Cables, 100' (30 m)
D005-2130-020
Doppler Cables, 20' (6 m)
D005-2130-050
Doppler Cables, 50' (15 m)
D005-2130-100
Doppler Cables, 100' (30 m)
Transducers (Heads with case)
Part Number
Description
D010-2200-002-C
DTTSU universal small pipe
Minimum Pipe O.D.
D071-0110-000-C
DTTN standard pipe
D071-0110-200-C
DTTL large pipe
D071-0112-001-C
DT94 Doppler transducer
Maximum Pipe O.D.
0.5" (12 mm)
2.4" (60.3 mm)
2" (50 mm)
98" (2500 mm)
16" (400 mm)
120" (3050 mm)
1" (25 mm)
60" (1524 mm)
RTDs/Accessories/Spare Parts
328
Part Number
Description
D002-2007-004
0… 392º F (200º C) RTD Silicone stretch tape
D002-2007-001
36" (914 mm) SS Hose clamp / transducer strap
D002-2007-005
72" (1829 mm) SS Hose clamp / transducer strap
D002-2011-001
Acoustic couplant, grease (Dow 111), 150° F (65° C) 5.3 oz tube
D002-2011-011
D010-3000-128
Acoustic couplant, paste high temperature, 142 gram tube, 392° F (200° C)
Industrial RTD Kit,1 1000 Ohm, 392° F (200° C); 20' (6 m) cable
D010-3000-129
Building Automation RTD Kit,1 1000 Ohm, 266° F (130° C); 20' (6 m) cable
888-397-5353 USA
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
FLOW
PORTABLE ULTRASONIC FLOW AND ENERGY METER
DXN SERIES
DIMENSIONS
DTTSU Transit Time Transducer
7.00
(177.8)
1.65
(41.9)
1.54
(39.1)
0.3
1.0
1.5
2.0
9.45
(240)
DTTN Transit Time Transducer
6
3.45
(87.6)
3.50
(88.9)
7.78
(197.6)
1.54
(39.1)
FLOW
3.77
(95.7)
1.70
(43.2)
DTTL Transit Time Transducer
4.21
(106.9)
DXN Connection Panel
Doppler Transducer
Transit Time Transducer (Upstream)
Transit Time Transducer (Downstream)
Auxiliary I/O
3.90
(99.0)
2.48
(63.0)
2.50
(63.5)
Power/Charger USB
On/Off Switch
Ethernet
Transducer Pipe Size Requirements
Minimum Pipe O.D.
DTTSU
.5" (12 mm)
Maximum Pipe O.D.
1.70
(43.2)
4.13
(104.9)
1.89
(48.0)
2.4" (60.3 mm)
DTTN
2" (50 mm)
98" (2500 mm)
DTTL
16" (400 mm)
120" (3050 mm)
DT94
1" (25 mm)
60" (1524 mm)
March 2014
DT94 Doppler Transducer
WE MAKE IT EASY.
kele.com
888-397-5353 USA
329
NEW!
FLOW
PORTABLE ULTRASONIC FLOW AND ENERGY METER
DXN SERIES
ORDERING INFORMATION
MODEL
DXNP
DESCRIPTION
Portable Clamp-on Ultrasonic Flow Meter
POWER CORD
A
North American
U
U.K., Singapore
E
Euro
J
Japan
C
China
SENSOR & HARDWARE KIT
B
Basic
T
All transit time
H
Hybrid
E
Energy
F
Full
CARRYING CASE
S
Standard - Outer case with shoulder strap
APPROVALS
N
CE + General Safety, U.S., Canada, and EU
OPTIONS
N
None
DXNP
A
FLOW
6
330
888-397-5353 USA
B
S
kele.com
N
N
Example: DXNP-A-B-S-N-N Portable clamp-on
ultrasonic flow meter with North American
power cord, basic sensor and hardware kit,
standard carrying case, CE + General Safety
approvals and no options
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
FLOW
INDUSTRIAL OVAL GEAR METER
IOG SERIES
DESCRIPTION
The Badger Meter Model IOG (industrial oval gear
meter), is a modular flow meter design, economical yet
highly accurate and rugged. The Model IOG is designed for
a variety of chemical applications including petroleum based
fluids, water solutions, and any other liquid compatible with
the materials of construction.
OPERATING PRINCIPLE
Fluid enters the inlet port and then passes through the
metering chamber. Inside the chamber, fluid forces the
internal gears to rotate before exiting through the outlet port.
Each rotation of the gears displaces a specific volume of
fluid. As the gears rotate, a magnet on each end of the gear
passes a reed switch in the top-mounted register’s circuit
board. The reed switches send pulses to the microprocessor
in the register to change the LED display segments. The
oval gear meter can be used in conjunction with a variety of
industrial registers. See the online documentation for Oval
Gear Meter Registers, ER-420 Flow Rate/Totalizer, and the
ER-500 Flow Monitor for more information on the available
register options.
6
Industrial Oval Gear
APPLICATION
•
•
•
•
•
Due to the rugged nature of this particular flow measurement
technology, the Industrial Oval Gear Meter can be used in
a number of applications where conventional meters are
not acceptable. Whether the liquid being measured is very
viscous or highly corrosive, the oval gear meter can handle
it. The Industrial Oval Gear Meter is designed for a variety
of applications including petroleum based fluids, water
solutions, and any other liquid compatible with the materials
of construction.
•
•
•
•
Compact size
High accuracy and repeatability
Factory calibrated (stated in pulses per liter)
Flow range of 0.067-185 gpm
Flexibility of installation options (vertical installation or
horizontal installation)
Low pressure drop
Minimum number of wearable parts for long product
life and easy field servicing
Wide range of instrumentation available for control
system interfacing
Certifcations: UL File#913, CSA
Pressure Rating (psi)
Port
Size
1/4"
1/2"
3/4"
1"
1" HF
1-1/2"
2"
3"
March 2014
Housing
Material
Stainless
Aluminum
Stainless
Aluminum
Stainless
Aluminum
Stainless
Aluminum
Stainless
Aluminum
Stainless
Aluminum
Stainless
Aluminum
Stainless
Aluminum
Rotor Material
Operating Temperature Range
NPT/BSP
ANSI 150#
ANSI 300#
Stainless Steel
-22° to 240°F (-30° to 120°C)
1000
1500
3000
2000
3000
2000
3000
2000
3000
2000
2000
1500
1500
1000
1000
750
-
740
740
740
740
740
740
-
LCP
-22° to 176°F (-30° to 80°C)
285
285
285
285
285
285
285
FLOW
FEATURES
SPECIFICATIONS
Approvals
Warranty
WE MAKE IT EASY.
CSA
1 year
kele.com
888-397-5353 USA
331
NEW!
FLOW
INDUSTRIAL OVAL GEAR METER
IOG SERIES
DIMENSIONS
FLOW
6
Port Size
A
B
C
D
E
F
G
H
J
K
L
M
N
1/4"
2.17"
(55 mm)
1.54"
(39 mm)
2.05"
(52 mm)
—
—
—
—
—
—
—
—
—
—
1/2"
3.94"
(100 mm)
3.44"
(87.5 mm)
3.62"
(92 mm)
9.70"
5.12"
8.93"
10.10"
6.69"
8.45"
7.68"
8.89"
3.94"
4.84"
(246.4 mm) (130 mm) (226.8 mm) (256.5 mm) (170 mm) (214.6 mm) (195.1 mm) (225.8 mm) (100.2 mm) (122.9 mm)
3/4"
3.94"
(100 mm)
3.84"
(97.5 mm)
3.62"
(92 mm)
10.10"
5.12"
9.33"
10.50"
6.69"
8.70"
7.93"
9.14"
3.94"
4.84"
(256.5 mm) (130 mm) (236.9 mm) (266.7 mm) (170 mm) (220.9 mm) (201.4 mm) (232.2 mm) (100.2 mm) (122.9 mm)
1"
3.94"
(100 mm)
3.84"
(97.5 mm)
3.62"
(92 mm)
10.10"
5.12"
9.33"
10.50"
6.69"
8.70"
7.93"
9.14"
3.94"
4.84"
(256.5 mm) (130 mm) (236.9 mm) (266.7 mm) (170 mm) (220.9 mm) (201.4 mm) (232.2 mm) (100.2 mm) (122.9 mm)
1" HF
3.94"
(100 mm)
3.89"
(98.9 mm)
3.62"
(92 mm)
10.15"
5.12"
9.38"
10.55"
6.69"
8.60"
7.83"
9.04"
3.94"
4.84"
(257.8 mm) (130 mm) (238.3 mm) (268.0 mm) (170 mm) (218.4 mm) (198.8 mm) (229.6 mm) (100.2 mm) (122.9 mm)
1-1/2"
5.51"
4.93"
4.92"
11.15"
5.12"
10.38"
11.51"
8.35"
8.90"
8.13"
9.31"
(140 mm) (125.3 mm) (125 mm) (283.2 mm) (130 mm) (263.7 mm) (292.4 mm) (212 mm) (226.1 mm) (206.5 mm) (236.5 mm)
—
—
2"
5.91"
5.34"
5.28"
11.60"
5.12"
10.83"
11.96"
10.39"
9.16"
8.39"
9.57"
(150 mm) (135.6 mm) (134 mm) (294.6 mm) (130 mm) (275.1 mm) (303.8 mm) (264 mm) (232.7 mm) (213.1 mm) (243.1 mm)
—
—
3"
8.27"
6.35"
7.09"
12.57"
5.12"
11.80"
12.93"
13.54"
9.58"
8.81"
9.99"
(210 mm) (161.4 mm) (180 mm) (319.3 mm) (130 mm) (299.7 mm) (328.4 mm) (344 mm) (243.3 mm) (223.8 mm) (253.8 mm)
—
—
332
888-397-5353 USA
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
FLOW
INDUSTRIAL OVAL GEAR METER
IOG SERIES
FLOW RANGE AND MATERIALS OF CONSTRUCTION
FLOW RANGE
American (gpm)
Port Size
1/4"
1/2"
3/4"
1"
1" HF
1-1/2"
3"
Low
High
Low
High
Fluid Viscosity
.067
2.2
0.25
8.3
> 5.0 cP
Accuracy
(%)
± 1.0
0.11
2.2
0.44
8.3
< 5.0 cP
± 2.5
0.25
8.0
1.0
30
> 5.0 cP
± 0.5
0.50
6.6
2.0
25
< 5.0 cP
± 2.0
0.50
16
2.0
60
> 5.0 cP
± 0.5
1.20
14
4.5
53
< 5.0 cP
± 2.0
0.6
18
2.3
68
> 5.0 cP
± 0.5
1.4
16
5.3
60
< 5.0 cP
± 2.0
1.5
45
5.7
170
> 5.0 cP
± 0.5
2.5
40
9.5
151
< 5.0 cP
± 2.0
2.5
65
9.5
246
> 5.0 cP
± 0.5
4.0
60
15
227
< 5.0 cP
± 1.0
4.0
100
15
379
> 5.0 cP
± 0.5
6.0
100
23
379
< 5.0 cP
± 1.0
5.0
185
19
700
> 5.0 cP
± 0.5
10
185
38
700
< 5.0 cP
± 1.0
Repeatability
(%)
± 0.03
± 0.03
± 0.03
6
± 0.03
± 0.03
± 0.03
± 0.03
± 0.03
FLOW
2"
SI (lpm)
MATERIALS OF CONSTRUCTION
Wetted Parts
Port Size
1/4"
1/2"
3/4"
1"
1" HF
1-1/2"
2"
3"
Housing
Cover
316 SS
316 SS
6061 Al
6061 Al
316 SS
316 SS
6061 Al
6061 Al
316 SS
316 SS
6061 Al
6061 Al
316 SS
316 SS
6061 Al
6061 Al
316 SS
316 SS
6061 Al
6061 Al
316 SS
316 SS
6061 Al
6061 Al
316 SS
316 SS
6061 Al
6061 Al
316 SS
316 SS
6061 Al
6061 Al
Spindle
Gears
Bearings
Magnet
O-Ring
316 SS
316 SS
Fluorosint
500
Neodymium
Au Plated
Aflas
316 SS
Graphalloy
316 SS
316 SS
316 SS
LCP
316 SS
Graphalloy
LCP
316 SS
Graphalloy
LCP
Alnico
Alnico
Alnico
Viton
Aflas
Viton
Aflas
Viton
Aflas
Viton
Aflas
316 SS
316 SS
Fluorosint
Neodymium
Ni Plated
316 SS
316 SS
Fluorosint
Neodymium
Ni Plated
316 SS
316 SS
Fluorosint
Neodymium
Ni Plated
Viton
316 SS
316 SS
Fluorosint
Neodymium
Ni Plated
Viton
kele.com
888-397-5353 USA
Viton
Aflas
Viton
Aflas
Aflas
Bolts
316 SS
316 SS
316 SS
316 SS
316 SS
316 SS
316 SS
316 SS
NOTE: Upon request, additional O-Ring options are Buna-N and EPDM.
March 2014
WE MAKE IT EASY.
333
NEW!
FLOW
INDUSTRIAL OVAL GEAR METER
IOG SERIES
ORDERING INFORMATION
MODEL
IOG
6
DESCRIPTION
Industrial Oval Gear Meter
PORT SIZE (for 1/4" port size see the 4 part numbers listed below)
050
1/2 inch port
075
3/4 inch port
100
1 inch port
HF
1 inch high flow
150
1.5 inch port
200
2 inch port
300
3 inch port
HOUSING
SS
Stainless Steel
AL
Aluminum
CONNECTIONS
NPT
National Pipe Thread
BSP
Britsh Standard Pipe
150
150 LB Flange
300
300 LB Flange
FLOW
METER MOUNT REGISTER STANDARD
R0
ILR-700 Local Display w/ Rate and Total
T1
ILR-710 Display w/ Scaled Pulse Output
T2
ILR-720 Display w/ Dual Scaled Pulse Output
T3
ILR-730 Local Display w/ Ananlog Output
METER MOUNT NON-SCALED TRANSMITTERS
T4
ILR-740 Unscaled Pulse Output
T5
ILR-741 Unscaled Pulse Output, Explosion Proof
METER MOUNT REGISTER LARGE DISPLAY
R1
ER-420 Scalable Rate Flow Counter 115-230 VAC
RJ
ER-420 Scalable Rate Flow Counter 24 VDC
RK
ER-420 Scalable Rate Flow Counter, Loop Powered
RL
ER-500 Standard
RM
ER-500 Advanced w/ Modbus
NO REGISTER or TRANSMITTER
RX
None
IOG
050
SS
NPT
T1
Example: IOG-050-SS-NPT-T1 1.2 inch port, stainless
steel w/ IRL-710 Display w/ Scaled Pulse Output
1/4" Port Size Part Numbers
1/4" IOG, Aluminum, NPT - IOG-025-AL-NPT-01
1/4" IOG, Aluminum, BSP - IOG-025-AL-BSP-01
1/4" IOG, Stainless Steel, NPT - IOG-025-SS-NPT-11
1/4" IOG, Stainless Steel, BSP - IOG-025-SS-BSP-11
334
888-397-5353 USA
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
FLOW
RECORDALL® COMPOUND SERIES METER
RCDL COMPOUND SERIES
DESCRIPTION
The Badger Meter Recordall Compound Series meters
meet or exceed the most recent revision of AWWA Standard
C700 and are available in a leadfree bronze alloy. The
Compound Series meters comply with the lead-free
provisions of the Safe Drinking Water Act, are certified to
NSF/ANSI Standards 61 and 372 (Trade Designation: LL-NS)
and carry the NSF-61 mark on the housing. All components
of the lead-free bronze alloy meter (housing, measuring
element, seals, and so on) comprise the certified system.
Badger Meter Recordall® Compound Series meters combine
two metering technologies in one innovative package. A
positive displacement chamber measures low flow, while a
turbine chamber records high flow.
OPERATION
At low flow rates, the Compound Series meter diverts water
up through a bypass to the disc chamber. Leaving the
chamber’s outlet port, water flows beyond the turbine element
and main valve. As the flow rate increases, a pressure
differential is created that opens the main valve. The water
then flows straight through the turbine chamber. In addition, a
portion still flows through the disc chamber before exiting the
meter.
FEATURES
• Offered in four sizes
• Patented design that eliminates the need for a trigger
valve and maintains crossover accuracy
• Permanently sealed, tamper-resistant register or encoder
Compound Series Family
APPLICATION
Use the Recordall Compound meter for measuring potable
cold water in commercial and industrial applications where
flow is in one direction only. The meter is an ideal choice
for facilities that experience rapid and wide fluctuations in
water demand, such as hospitals, universities, residential
complexes and manufacturing or processing facilities.
FLOW
METER INSTALLATION
The meter is designed for installations where flow is in one
direction only. A separate strainer is provided to ensure
optimum flow conditioning and protection of the measuring
element. Companion flanges for installation of meters on
various pipe types and sizes are available in cast iron or NL
bronze as an option.
6
• An optional summator can be provided as an integral
part of the register assembly. All register options are
removable from the meter without disrupting water
service
• Certifcations: NSF/ANSI Standard 61 Certified, Annex G
SPECIFICATIONS
Compound Series Model
Meter Flanges, Class 150
Typical Operating Range
2" (50 mm)
3" (80 mm)
4" (100 mm)
6" (150 mm)
2" elliptical or round
3" round
4" round
6" round
(50 mm)
(80 mm)
(100 mm)
(150 mm)
0.5…200 gpm
0.5…450 gpm
0.75…1000 gpm
0.75…2000 gpm
(0.1…45 m3/h)
0.25 gpm (0.06 m3/h)
(0.1…102 m3/h)
0.25 gpm (0.06 m3/h)
(0.17…227 m3/h)
0.375 gpm (0.09 m3/h)
(0.17…454.4 m3/h)
0.375 gpm (0.09 m3/h)
Maximum Continuous Flow
170 gpm (38.3 m3/h)
400 gpm (90.3 m3/h)
800 gpm (181.6 m3/h)
1500 gpm (340.5 m3/h)
Pressure Loss at Maximum
Continuous Flow
5.4 psi at 170 gpm
(0.38 bar at 38.3 m3/h)
6.0 psi at 400 gpm
(0.41 bar at 90.3 m3/h)
11.0 psi at 800 gpm
(0.75 bar at 181.6 m3/h)
9.3 psi at 1500 gpm
(0.64 bar at 340.5 m3/h)
Crossover Flow Rate, Typical
12 gpm
12 gpm
20 gpm
30 gpm
Pressure Loss at Crossover
3.5 psi (0.24 bar)
4.0 psi (0.28 bar)
4.0 psi (0.28 bar)
5.0 psi (0.35 bar)
97%
97%
97%
95%
(100% ± 1.5%)
Low Flow Registration
(97% minimum)
Minimum Crossover Accuracy
Maximum Operating Pressure
150 psi (10 bar)
Maximum Operating
Temperature
105° F (41° C)
Test Plug
March 2014
1-1/2"
2"
WE MAKE IT EASY.
kele.com
888-397-5353 USA
335
FLOW
NEW!
RECORDALL® COMPOUND SERIES METER
RCDL COMPOUND SERIES
DIMENSIONS
Compound Series Model
2" Elliptical
(50 mm)
Meter & Pipe Size
2" (50 mm)
Net Weight
45 lb (20.4 kg)
Shipping Weight
63 lb (28.5 kg)
3" (80 mm)
4" (100 mm)
6" (150 mm)
3" (80 mm)
4" (100 mm)
6" (150 mm)
71.5 lb (32.4 kg)
85 lb (38.4 kg)
152 lb (68.7 kg)
99.5 lb (45 kg)
120 lb (53.8 kg)
200 lb (90.4 kg)
Length (A)
15-1/4" * (387 mm)
17" (432 mm)
20" (508 mm)**
24" (610 mm)
Width (B )
7-3/8" (187 mm)
9-1/4" (235 mm)
9-1/8" (232 mm)
12-3/8" (314 mm)
Height (C)
5-7/8" (149 mm)
6-5/8" (168 mm)
7-1/4" (184 mm)
8-7/8" (225 mm)
5/8" (16 mm)
3/4" (19 mm)
7/8" (22 mm)
15/16" (24 mm)
6" (152 mm)
7-1/2" (190.5 mm)
9-1/2" (241 mm)
3-5/8" (92 mm)
4-1/4" (108 mm)
5-3/8" (137 mm)
4
8
8
Flange (D)
6
2" Round
(50 mm)
Bolt Circle (E)
4-1/2" (114 mm)
Centerline (C) to Base (F)
Number of Bolts
4-3/4" (121 mm)
2-3/4" (70 mm)
2
4
* Adapter available to increase total length to 17” (432 mm).
**Adapter available to increase total length to 24” (610 mm).
FLOW
Elliptical Flange (2" only)
B
C
F
D
A
E
Round Flange
B
D
C
F
E
A
ORDERING INFORMATION
MODEL
UM1-0008-6032
UM1-0008-6034
UM1-0008-6035
UM1-0008-6037
336
888-397-5353 USA
DESCRIPTION
2" Compound Meter with Pulse
3" Compound Meter with Pulse
4" Compound Meter with Pulse
6" Compound Meter with Pulse
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
FLOW
RECORDALL® NUTATING DISC METERS
RCDL NUTATING DISC
DESCRIPTION
The Badger Meter Recordall Model Nutating Disc Series
meters meet or exceed the most recent revision of AWWA
Standard C700 and are available in a lead-free bronze alloy.
The meters comply with the lead-free provisions of the Safe
Drinking Water Act, are certified to NSF/ANSI Standards 61
and 372 (Trade Designation: M25-LL) and carry the NSF-61
mark on the housing. All components of the lead-free bronze
alloy meter (housing, measuring element, seals, and so on)
comprise the certified system.
Operation: Water flows through the meter’s strainer and into
the measuring chamber where it causes the disc to nutate.
The disc, which moves freely, nutates on its own ball, guided
by a thrust roller. A drive magnet transmits the motion of the
disc to a follower magnet located within the permanently
sealed register. The follower magnet is connected to the
register gear train. The gear train reduces the disc nutations
into volume totalization units displayed on the register or
encoder face.
Operating Performance: The Recordall Nutating Disc
Series meters meet or exceed registration accuracy for
the low flow rates (95%), normal operating flow rates (100
± 1.5%), and maximum continuous operation flow rates as
specifically stated in AWWA Standard C700.
Industrial RCDL Disc Meters
APPLICATION
For use in measurement of potable cold water in residential,
commercial and industrial services where flow is in one
direction only.
Connections: Tailpieces/Unions for installations of meters on
various pipe types and sizes, including misaligned pipes, are
available as an option.
FLOW
Construction: Recordall Nutating Disc Series meter
construction, which complies with ANSI/AWWA standard
C700, consists of three basic components: meter housing,
measuring chamber, and permanently sealed register. The
water meter is available in a lead-free bronze alloy with
externally-threaded spuds. A corrosion-resistant engineered
polymer material is used for the measuring chamber.
6
Certifications: NSF/ANSI Standards 61 and 372 Certified
SPECIFICATIONS
Typical Operating Range
(100% ± 1.5%)
Low Flow (Min. 95.0%)
25
0.5…25 gpm
(0.11…5.7 m3/hr)
n/a
Low Flow (Min. 97.0%)
n/a
Low Flow (Min. 98.5%)
0.25 gpm (0.057 m3/hr)
Maximum Continuous
15 gpm (3.4 m3/hr)
Operation
Pressure Loss at Maximum
3.5 psi at 15 gpm
Continuous Operation
(0.24 bar at 3.4 m3/hr)
Maximum Operating
Temperature
Maximum Operating
Pressure
Measuring Element
Available in NL bronze
and thermoplastic to
Meter Connections
fit 0.625" (DN 15mm)
spud thread bore
diameter sizes
Test Plugs
March 2014
n/a
MODEL
35
70
120
0.75…35 gpm
1.25…70 gpm
2.5…120 gpm
(0.17…7.9 m3/hr)
(0.28…16 m3/hr)
(0.57…27 m3/hr)
n/a
0.75 gpm (0.17 m3/hr) 1.25 gpm (0.28 m3/hr)
0.375 gpm
n/a
n/a
(0.085 m3/hr)
n/a
n/a
n/a
25 gpm (5.7 m3/hr)
50 gpm (11.3 m3/hr)
80 gpm (18 m3/hr)
5.0 psi at 25 gpm
6.5 psi at 50 gpm
4.8 psi at 80 gpm
(0.37 bar at 5.7 m3/hr) (0.45 bar at 11.3 m3/hr) (0.33 bar at 18 m3/hr)
170
2.5…170 gpm
(0.57…39 m3/hr)
1.5 gpm (0.34 m3/hr)
n/a
n/a
100 gpm (23 m3/hr)
3.3 psi at 100 gpm
(0.23 bar at 23 m3/hr)
80°F (26°C)
150 psi (10 bar)
Nutating disc, positive displacement
Available in NL bronze Available in NL bronze
1.5" AWWA two-bolt el- 2.0" AWWA two-bolt
and engineered polymer and engineered polymer
liptical flange, drilled or elliptical flange, drilled
to fit 0.75" (DN 20
to fit 1.0" (DN 25 mm)
1.5…11.5 NPT internal or 2…11.5 NPT internal
mm) spud thread bore
spud thread bore
pipe threads
pipe threads
diameter sizes
diameter sizes
Optional 1.0" NPT test
1.0" NPT test plug (TP)
plug (TP) available on
n/a
n/a
available on elliptical
elliptical long and short
long and short versions
versions
WE MAKE IT EASY.
kele.com
888-397-5353 USA
337
FLOW
NEW!
RECORDALL® NUTATING DISC METERS
RCDL NUTATING DISC
DIMENSIONS
Meter Size
Meter Model
5/ " (15 mm)
8
3/ " (20 mm)
4
25
1" (25 mm)
1-1/2" (40
mm)
70
35
120 EL Hex
120 EL, TP
170 EL Hex
170 EL, TP
2" (50 mm)
A Laying
Length
1
7- /2" (190 mm)
7-1/2" (190 mm)
10-3/4" (273 mm)
B Height Reg.
4-15/16" (125 mm)
5-1/4" (133 mm)
6-1/2" (165 mm)
C Centerline Base
Width
1-11/16" (42 mm)
4-1/4" (108 mm)
1-5/8" (41 mm)
5" (127 mm)
2-5/16" (59 mm)
7-3/4" (197 mm)
Approx. Shipping
Weight
1
4- /2 lb (2 kg)
5-1/2 lb (2.5 kg)
11-1/2 lb (5.2 kg)
12-5/8" (321 mm)
7" (178 mm)
2-3/8" (60 mm)
8-3/4" (222 mm)
19 lb (8.6 kg)
15-1/4" (387 mm)
8" (203 mm)
2-7/8" (73 mm)
9-1/2" (241 mm)
30 lb (13.6 kg)
6
FLOW
Meter Spud and Connection Sizes
Size Designation
x
“L”
Laying
Length
5/8"
x
7-1/2"
“B”
Bore Dia.
5/8"
Coupling
Nut and
Spud
Thread
3/4" (5/8")
Tailpiece Pipe
Thread (NPT)
1/2"
Meter Spud and Connection Sizes
Size Designation x
3/4"
3/4"
3/4" x 1"
x
x
x
“L”
Laying
Length
“B”
Bore Dia.
7-1/2"
9"
9"
3/4"
3/4"
3/4"
Coupling
Nut and
Spud
Thread
1" (3/4")
1" (3/4")
1-1/4" (1")
Tailpiece
Pipe
Thread
(NPT)
3/4"
3/4"
1"
Meter Spud and Connection Sizes
Size
Designation
1"
x
“L”
Laying
Length
“B”
Bore Dia.
x
10-3/4"
1"
Coupling
Nut and
Spud
Thread
1-1/4" (1")
Tailpiece
Pipe
Thread
(NPT)
1"
ORDERING INFORMATION
MODEL
UM1-0008-6014
UM1-0007-5863
UM1-0007-2649
UM1-0008-6016
UM1-0008-6017
338
888-397-5353 USA
DESCRIPTION
Model 25 Pulse Water Meter
Model 35 Pulse Water Meter
Model 70 Pulse Water Meter
Model 120 Pulse Water Meter
Model 170 Pulse Water Meter
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
FLOW
RECORDALL® TURBO SERIES METERS
RCDL TURBO SERIES
DESCRIPTION
The Badger Meter Recordall Turbo Series meters meet or
exceed the most recent revision of AWWA Standard C701 Class
II Standards and are available in a lead-free bronze alloy for sizes
1-1/2" through 10" and cast iron for 12" meters. Turbo Series
meters comply with the lead-free provisions of the Safe Drinking
Water Act. Sizes 1-1/2" through 10" meters are also certified
to NSF/ANSI Standards 61 and 372 (Trade Designation: Turbo
Series LL-NS) and carry the NSF-61 mark on the housing. All
components of the lead-free alloy meter (housing, measuring
element, seals and so on) comprise the certified system.
Operation & Performance: Direct magnetic drive is achieved
when the magnet carrier is driven by a gear train coupled to the
rotor. The gear train consists of two sets of gears connected by a
vertical transmission shaft. One gear set is at the magnet carrier,
the other is a worm gear set at the rotor shaft. When water flows
into the Turbo Series meter measuring element, it contacts the
multi-vaned rotor. The resulting rotor rotation is then transmitted
by magnetic coupling to a sealed register or encoder. The direct
magnetic drive is built to provides a reliable meter-to-registration
coupling.
6
Industrial Turbo Meters
APPLICATION
• Models 160 through 6200 are designed for 1-1/2" through
12" applications
• Direct coupled turbine based on an exclusive "floating
rotor"design that reduces bearing friction—and
associated wear and tear
• Low pressure loss for improved system efficiency
• Exceptional registration accuracy across low flow rate,
normal operating flow rate and maximum continuous
operation flow
• Permanently sealed, tamper-resistant register or encoder
• Integral strainer option for sizes 1-1/2" through 4" help
protect your system from damaging debris and related
downtime
• NSF/ANSI Standards 61 and 372 Certified
Recordall Turbo Series meters are designed for cold water,
commercial and industrial applications where flows are consistent
medium to high flows. Applications include hotels, apartment
buildings, irrigations centers and manufacturing and processing
plants. Turbo Series meters help reduce day-today maintenance
costs while delivering accurate and efficient performance.
FLOW
FEATURES
SPECIFICATIONS
Turbo Series Model
Meter Flanges AWWA
125 Pound Class
Typical Operating
Range (100% ± 1.5%)
Typical Low Flow
(95% min.)
Max. Continuous Flow
Maximum Intermittent
Flow
Pressure Loss at Max.
Continuous Flow
Pressure Loss at Max.
Continuous Flow: With
Integral Strainer
Max. Operating
Pressure
Max. Operating
Temperature
Optional Integral
Strainer
Optional External
Strainer
Test Plug
March 2014
160
1-1/2" (40 mm)
200
2" (50 mm)
450
3" (80 mm)
1000
4" (100 mm)
2000
6" (150 mm)
3500
8" (200 mm)
5500
10" (250 mm)
6200
12" (300 mm)
Elliptical
Elliptical or Round
Round
Round
Round
Round
Round
Round
AWWA 125 lb class
4…200 gpm
(0.9…45.4 m3/h)
2.5 gpm
(0.6 m3/h)
160 gpm
(36 m3/h)
200 gpm
(45.4 m3/h)
3.8 psi
(0.26 bar)
4…310 gpm
(0.9…70.4 m3/h)
2.5 gpm
(0.6 m3/h)
200 gpm
(45.4 m3/h)
310 gpm
(70.4 m3/h)
3.1 psi
(0.21 bar)
5…550 gpm
(1.1…124.9 m3/h)
4 gpm
(0.9 m3/h)
450 gpm
(102.2 m3/h)
550 gpm
(124.9 m3h)
1.8 psi
(0.12 bar)
10…1250 gpm
(2.3…284 m3/hr)
6 gpm
(1.4 m3/h)
1000 gpm
(227.1 m3/h)
1250 gpm
(284 m3h)
7.3 psi
(0.50 bar)
20…2500 gpm
(4.5…568 m3/h)
12 gpm
(2.7 m3/h)
2000 gpm
(454 m3/h)
2500 gpm
(568 m3/h)
4.8 psi
(0.33 bar)
30…4500 gpm
(6.8…1022 m3/h)
20 gpm
(4.5 m3/h)
3500 gpm
(795 m3/h)
4500 gpm
(1022 m3/h)
2.5 psi
(0.17 bar)
50…7000 gpm
(11.4…1590 m3/h)
30 gpm
(6.8 m3/h)
5500 gpm
(1250 m3/h)
7000 gpm
(1590 m3h)
1.6 psi
(0.11 bar)
90…8800 gpm
(20.5…1998 m3/h)
65 gpm
(14.8 m3/h)
6200 gpm
(1408 m3/h)
8800 gpm
(1988 m3/h)
0.8 psi
(0.05 bar)
9.9 psi
(0.68 bar)
8.3 psi
(0.57 bar)
5 psi
(0.43 bar)
17.8 psi
(1.2 bar)
—
150 psi (10 bar)
120° F (49° C)
Built into inlet end.
Removable cover plate permits access to strainer for cleaning.
—
—
Available for Models 200, 450, 1000, 2000, 3500, 5500 and 6200.
Standard with integral strainer; optional for other models.
Optional for Models 2000 and 3500.
WE MAKE IT EASY.
kele.com
—
888-397-5353 USA
339
NEW!
FLOW
RECORDALL® TURBO SERIES METERS
RCDL TURBO SERIES
DIMENSIONS OF METERS WITH INTEGRAL STRAINER
6
Turbo Series Model
160
200
200
450
1000
Elliptical
Elliptical
Round
Round
Round
Meter & Pipe Size
1-1/2" (40 mm)
2" (50 mm)
2" (50 mm)
3" (80 mm)
4" (100 mm)
Net Weight
14.3 lb (6.5 kg)
24 lb (11 kg)
26 lb (12 kg)
49 lb (22 kg)
60 lb (27.22 kg)
Shipping Weight
16.8 lb (7.6 kg)
28 lb (13 kg)
30 lb (14 kg)
55 lb (25 kg)
70 lb (31.75 kg)
Number of Bolts
2
2
4
4
8
NPT Test Port & Test
Plug (Standard)
1" (25.4 mm)
1-1/2" (40 mm)
1-1/2" (40 mm)
2" (50 mm)
2" (50 mm)
Length (A)
13" (330 mm)
17" (432 mm)
17" (432 mm)
19" (483 mm)
23" (584 mm)
Width (B )
5-7/32" (133 mm)
5-27/32" (148 mm)
6" (152 mm)
7-1/2" (191 mm)
9" (229 mm)
Height (C)
6-9/32" (159 mm)
6-1/2" (165 mm)
7-3/32" (180 mm)
8-15/16" (227 mm)
9-21/32" (245 mm)
Flange (D)
FLOW
Meter Flanges
51/64" (20 mm)
27/32" (47 mm)
5/8" (16 mm)
27/32" (21 mm)
13/16" (21 mm)
Bolt Circle (E)
4" (102 mm)
4-1/2" (114 mm)
4-3/4" (121 mm)
6" (152 mm)
7-1/2" (191 mm)
Centerline (F)
1-27/32" (47 mm)
2-1/16" (52 mm)
2-5/8" (67 mm)
3-19/32" (91 mm)
4-5/16" (109 mm)
ORDERING INFORMATION
MODEL
UM1-0007-6445
UM1-0008-6020
UM1-0008-6021
UM1-0008-6023
UM1-0008-6024
UM1-0008-6025
UM1-0008-6026
340
888-397-5353 USA
DESCRIPTION
1 1/2" Turbine Water Meter with Pulse
2" Turbine Water Meter with Pulse
3" Turbine Water Meter with Pulse
4" Turbine Water Meter with Pulse
6" Turbine Water Meter with Pulse
8" Turbine Water Meter with Pulse
10" Turbine Water Meter with Pulse
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
FLOW
INSERTION TYPE AIRFLOW SENSING ELEMENT
FE-1000 SERIES
DESCRIPTION
The Paragon Controls FE-1000 insertion type airflow
sensing element is designed for quick, easy installation
through a small cutout in the existing ductwork. Where
multiple elements are required for proper duct traversing,
the output ports are manifolded together, external to the
ductwork. Each element is furnished complete with mounting
hardware, sealing gaskets and all brass compression fittings
required to manifold the elements together.
FEATURES
• Multiple total and static pressure sensing ports along
the length of the element
• Averaging internal manifold
• Insensitive to flow angle variations of as much as ±20°
when faced in the normal direction of flow
• ±2% accuracy throughout the velocity rages of 100 fpm
and over
6
FE-1000
SPECIFICATIONS
Connections
Within 2% of actual flow (even in
moderately turbulent flows) with
approach angle variation of ±20°,
when installed in accordance with
published recommendations
1/4" compression, suitable for use
with thermoplastic or copper tubing;
thermoplastic tubing requires the use
of tubing inserts, which are supplied
with the fittings
Velocity Range
100 to 10,000 fpm
Operating Temperature350°F (177°C) continuous operation
(in air)
400°F (204°C) intermittent operation
(in air)
Operating Humidity
0 to 100% RH, non-condensing
Materials Of
Construction
6063-T5 anodized aluminum
(standard)
Warranty
1 year
FLOW
Accuracy
ORDERING INFORMATION
MODEL
FE-1000
March 2014
DESCRIPTION
Insertion type airflow sensing element
DIMENSIONS
1
Inches
2
Millimeters
DUCT CONFIGURATION
1
Rectangular
2
Circular
3
Oval
ELEMENT LENGTH (SPECIFY)
INTERNAL INSULATION (SPECIFY)
MATERIAL TYPE
1
Aluminum (standard)
MOUNTING CONFIGUATION
1
Insertion (standard)
2
Internal Mount
3
Bayonet Tip
TAKEOFF CONFIGURATION
1
1/8-27 Female NPT (standard)
WE MAKE IT EASY.
kele.com
888-397-5353 USA
341
FLOW
NEW!
FAN INLET AIRFLOW SENSING ELEMENT
FE-1050 SERIES
DESCRIPTION
The Paragon Controls FE-1050 is an airflow measuring
element assembly specifically designed for installation in the
inlet cone of centrifugal fans or inlet bell of vane-axial fans.
The design of these primary elements provides a means
of accurate measurement of fan capacity along with ease
of installation. Each assembly is complete with two airflow
measuring elements and pivot mounting hardware.
FEATURES
• Multiple total and static pressure sensing ports along
the length of the element
• Averaging internal manifold
• Insensitive to flow angle variations of as much as ±20°
when faced in the normal direction of flow
• ±2% accuracy throughout the velocity ranges of 100
fpm and over
FE-1050
FLOW
6
SPECIFICATIONS
Accuracy
Connections
Velocity Range
342
Within 2% of actual flow when
installed in accordance with
published recommendations
1/4" compression, suitable for use
with thermoplastic or copper tubing;
thermoplastic tubing requires the use
of tubing inserts, which are supplied
with the fittings
100 to 8,000 fpm
888-397-5353 USA
kele.com
Operating Temperature350°F (177°C) continuous operation
(in air)
400°F (204°C) intermittent operation
(in air)
Operating Humidity
0 to 100% RH, non-condensing
Materials Of Construction
6063-T5 anodized aluminum
(standard)
Warranty
1 year
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
March 2014
NEW!
FLOW
FAN INLET AIRFLOW SENSING ELEMENT
FE-1050 SERIES
DIMENSIONS
6
FLOW
Note: The 0.585 inch diameter probe is used for minimum fan inlets less than
or equal to 28 inches and the 1 inch diameter probe is used for minimum fan
inlets greater than 28 inches.
ORDERING INFORMATION
MODEL
FE-1050
March 2014
DESCRIPTION
Fan inlet airflow sensing element
DIMENSIONS
1
Inches
2
Millimeters
INLET CONFIGURATION
1
Single inlet (SWSI)
2
Double inlet (DWDI)
MOUNTING CONFIGUATION
1 Minimum inlet diameter (standard)
2 Mid-bell installation
DIAMETER OF SENSING PLANE (SPECIFY)
MATERIAL TYPE
1 Aluminum
WE MAKE IT EASY.
kele.com
888-397-5353 USA
343
FLOW
MEASURING AIRFLOW
Averaging Differential Pressure Devices
To take some of the guesswork out of determining average
duct velocity, an averaging tube may be used. An averaging tube operates basically the same way as a pitot tube to
determine average duct velocity pressure, except instead of
measuring one point within the duct, the averaging tube measures multiple points to determine a true average velocity. As
an added benefit, some averaging tubes are designed so that
the differential pressure measured is two to three times the
actual velocity pressure. This amplification is accomplished
by the shape and design of the tube and results in greater
resolution and the ability to measure lower air velocities.
6
NEW!
In Summary
• Only the average duct velocity and duct cross-section area
must be known to determine airflow.
• By piping the total pressure to the high-pressure port
and the static pressure to the low-pressure port of a
differential pressure transmitter, the velocity pressure will
be measured.
• When the duct center velocity is measured with a pitot
tube, the average velocity will be approximately 90% of
the measured velocity.
• By using an averaging tube, the average duct velocity
may be measured directly. The averaging tube may
also amplify pressure for greater resolution and higher
accuracy at low flow rates. Flow coefficients for use with
averaging tubes will be provided by the manufacturer.
FLOW
• Always install airflow measurement devices at least 7.5
duct diameters downstream and 1.5 diameters upstream
of anything in the duct that could cause turbulence.
QUICK TIPS
(for use with pitot tubes only)
Device Placement in the Duct
When measuring airflow with either a pitot tube or an averaging tube, the best results will be obtained when the flow
measuring device is located at least 7.5 duct diameters downstream and 1.5 diameters upstream from any disturbance
(elbows, obstructions, etc.). Also, for best results, straightening vanes may be used 1.5 to 5 diameters upstream of the
flow measuring device.
FIGURE 2. FLOW COEFFICIENTS FOR DIFFERENTIAL
PRESSURE TRANSMITTERS
(for use with pitot tubes only)
Differential
Pressure
Transmitter
Range
"W.C.
0 .1
0 .2
0 .3
0 .5
1 .0
2 .0
3 .0
5 .0
344
Maximum
Air Velocity
(fpm)
Flow
Coefficient
(Cf)
1265
1790
2190
2830
4000
5660
6930
8950
316
448
549
708
1000
1420
1733
2240
888-397-5353 USA
kele.com
By applying the two simple facts below, air velocity
may be quickly estimated in the field .
Fact 1. 4000 fpm velocity = 1" velocity pressure
Fact 2. Velocity pressure varies as the flow squared or
2
P 2 = V2
or V2 = P2
P1
V1
V1
P1
( )
Example:
If a velocity pressure is known, the velocity may be
calculated by using 4000 fpm and 1" differential as
V1 and P1 . Assume the velocity pressure is 0 .25" .
What is the air velocity?
or
V2
V 2 = P2
V1
P1
4000
or V2 = 2000 fpm
=
0 .25
1
If a velocity is known, velocity pressure may be
calculated in a similar manner . Assume velocity is
1000 fpm, what is velocity pressure?
( )
2
or
P2
P2 = V2
P1
V1
1
or P2 = 0 .0625" W .C .
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
( )
= 1000
4000
2
March 2014