Module 7 Power System Review Course Protection & Coordination By: Dr. Hamid Jaffari Fuse Transformer Typical Distribution System 7500 KVA OA 9375 KVA(125%) FA 10,000 KVA (135%) FOA 7500 KVA OA 9375 KVA(125%) FA 10,000 KVA (135%) FOA Protection & Coordination System Protection Instrumentaion Principals of Protection Protection Devices (Circuit breakers, Reclosers, Fuses) Principals of Coordination Coordination Study Fuse-Fuse Coordination Recloser-Recloser Coordination Recloser-Fuse Coordination Relay-Recloser-Fuse Coordination Power System Review System Protection Components Instrument Transformers PTs CTs Circuit Breakers & Relays Mechanical Digital Reclosers Fuses Power System Review Protective Devices Characteristics Breaker: Distribution Class 12 kA<Isymmetrical Rating<20 kA Transmission Class> 50 kA Extinguishing arc by means of: Oil, air blast, sulfur hexafluoride gas (sF6), vacuum, or simple arc chutes Recloser: 4 kA< Isymmetrical Rating<12 kA Interrupting occurs in Oil or vacuum Designed to “reclose” after fault is cleared Sectionalizers: interrupting capability<10KA Master minded by Reclosers Power System Review Protective Devices Characteristics Expulsion Fuses: Typically 8 kA to 16 kA Subject to X/R (interrupting capability decreases as ↑ X/R ) Power Fuse are generally available for Operating Voltage <169KV with 15KA<X/R<25KA Distribution Fuse are generally good for Operating Voltage<40K with 5KA<X/R<15KA less accurate, inexpensive, but effective. Current limiting fuses (CLFs) As much as 50 kA May have minimum interrupting capability, additional protection may be needed Oil switches: limited current interrupting capability. Power System Review Fault calculations Note: I-fault drops off as inverse of Distance 1/d Power System Review Principals of Protective Devices Definition of Protective Devices: Protective Devices have Time-Current, Time-Voltage, or Time-Frequency Characteristics Protective Devices are responsible for removing undesired conditions: Voltage Current Frequency Power System Review What is the purpose? Clear Temporary faults and restore power when possible. Interrupt Permanent Faults and Lock Out Interrupt Faults in Proper Sequence Remove undesired power conditions to maintain: Steady State Stability Power System Review EPRI Fault Study Faults Percentage Phase-to-Ground 65% Phase-to-Phase 11% Phase-Phase to Ground 2% Three Phase 2% One Phase on the Ground 15% Two Phase on the Ground 2% Others 3% Power System Review Protection & Coordination What is Coordination? Definition: Proper trip sequencing of protective devices to isolate the fault and minimizing outage. This means proper coordination between time and current curves during power system abnormal conditions. Coordination is : 1/3 Science 1/3 Art 1/3 Luck Coordination Protective Devices with Time-Current characteristics are: Relays, Reclosers, Fault Interrupters, and Fuses. How about Sectionalizers?? Device Relay Recloser FI Fuse Relay Relay-Relay Relay-Recloser Relay-FI Relay-Fuse Recloser Recloser-Relay Recloser-Recloser Recloser Recloser-Fuse FI FI-Relay FI-Recloser FI-FI FI-Fuse Fuse Fuse-Relay Fuse-Recloser Fuse-FI Fuse-Fuse Fuse-Fuse Coordination Fuse Selection Process Fuse Type/Class Expulsion(Dist, Substation, etc) CLF Voltage Class Fuse Isymm interrupting capability rating X/R ratio Fuse continuous current rating i.e. K(150%), T(150%), QA(100%) Fuse Application Fuses are generally: CLF-used for short-circuit protection Non-CLF or Expulsion Fuse is used for Overload protection Selection Criteria: Non-CLF: 140% of full load CLF: 150% of full load Expulsion Fuse Fuse Clearing Time @1/2 cycle Zero Crossing CT = MT+ Arcing Time Transient Voltage @ Clearing time 100 Isc Ifull load x Z% Current Limiting Fuse(CLF) 60,000 A 7,400 A B Curtsey of www.littlefuse.com Fuse Types & Porperties Fuse has two TCC curves Minimum Melting Total Clearing Common fuse types through 27kV are: Slow: T Fast: K Avoid mixing different type fuses for better coordination Skip at least a size in each fuse class (K, T, H, C, etc) for better coordination between two fuses(i.e. 20K, 40K, 65K, etc) Power System Review Fusing Philosophy Lateral tap fuse selection Criterion: I = 2x ILoad Cold load Daily/monthly/Seasonal cyclic Load Peak load Transformer Fuse Selection Criterion: Minimum Fuse Size= Irated x 1.2 Cold Load Inrush Current Operational Limits lateral Power System Review Fuse Speed & Continuous Rating Fuse Allowable Continuous current Rating(%) K-tin 150% K-silver 100% N 100% T 150% QA 100% S 150% Fuse speed from fast to slow → N>QA>K>T>S Power System Review Fusing Distribution Transformers Why? In order to protect the transformer against internal faults, downstream bolted faults, high impedance secondary faults. Fuse must withstand transient surge currents caused by lightening, XFMR magnetizing inrush current, and cold-load pickup. Therefore, fuse must be capable of handling: Cold Load Pickup Inrush Current Power System Review Dist Transformer using…continued Steps to select XFMR fuse size: 1. Calculate Cold Load Pickup withstand level: 1. I = 3 x I (full load for 10 seconds) 2. Calculate Inrush Current withstand limits: 1. I inrush= 12 x I (Full Load for 0.1 seconds) 2. I inrush= 25 x I (full load for .01 seconds) 3. Select the nearest primary fuse rating that: 1. 2. cold-load Starts with 120% of XFMR rated load: Minimum Fuse Size = IRated x 1.2 Meets the Cold load & Inrush Requirements (Steps 1 &2) 4. Select the Fuse type (K, T,H, QA,etc) and coordinate it with upstream & downstream fuses in service. Note: Using EEI-NEMA type K, T, and T Fuses Provides protection between 200% to 300% of Rated Load Power System Review Transformer Fusing…continued Example: Determine the minimum size fuse for a 300 KVA, 13.8kV/277/480 volts XFMR using “K” type fuse? Ifull load 300 KVA 3 x 13.8kV 300 12.55 Amp 23.9 ICold load @ 10Sec 3x12.55 37.65 Amp IInrush@ 0 .1Sec 12 x12.55 150.6 Amp Iinrush@ .01Sec 25x12.55 313.75 Amp MinimumFuse : 15K (120%) ? OR 20K (160%) ? Power System Review Transformer Fusing…continued Problem Area Power System Review Substation Transformer Protection Plot XFMR operational limits: Thermal & Mechanical limits (Damage Curve). Use FA Rating for XFMR Damage Curve Plot XFMR Inrush &Cold-Load pickup. Apply applicable NEMA & IEEE Standards: IEEE C57.109-1993 oil immersed XFMR IEEE C57.12.59-2001 dry-type XFMR Example: 22.86 kV / 4.16 kV Z 6% 7500 KVA OA 9375 KVA(125%) FA 10,000 KVA (135%) FOA Power System Review Transformer Operating Limitations t(sec) FLA 200 Thermal I2t = 1250 (D-D LL) 0.87 Infrequent Fault (D-R LG) 0.58 Frequent Fault Mechanical 2 K=(1/Z)2t Inrush 2.5 Isc I (pu) 25 Power System Review Devices’ Damage Curves t Time 2 It I2t I2t I2 2 t Motor Xfmr Cable Gen I2t I-Current =Let-through Energy Power System Review Transformer Prim Fuse Protection Capacitor Fusing Capacitor fuse must be between 135% to 165% of its full load current rating depending on manufacturer. Capacitor Fuse Full Load x 1.35 or Capacitor Fuse Full Load x 1.65 Example: Find appropriate fuse size for a 1800 KVAR cap bank installed on a 22.86kV line. Ifull load 1800 KVAR 1800 45.5 Amp 3 x 22.86kV 39.6 Note: Check fuse continuous/overload capability (100%-150%) Capacitor Fuse *1.5 45.5 *1.35 Fuse 40.5 Amp Select 50 K or 60QA Fuse Fuse-Fuse Coordination Time A Source B Fuse Fuse CTof A Fault MT of A Load CT of B Fuse A (75% of MT) Current coordination limit Fuse-fuse coordination must follow the following rule: CT (down stream fuse) Time Ratio of 75% MT (upstream fuse) Desirable coordination: Time Ratio of two fuses Must Not Exceed the 75% Ratio tCT ( downstream fuse) tMT (upstream) * 0.75 Power System Review Fuse-Fuse Coordination Example: What is the minimum size fuse that coordinates with 50K lateral tap fuse if calculated fault current is 1000Amp at point B? MT(A Fuse)=0.051 sec for Fault Current @ 1000 Amp CT (down stream fuse B) 0.75 MT (upstream fuse A) 50 K A CT (down stream fuse B) 0.75 CT 0.75 x0.051 .051 CT 0.038 sec Power System Review B ?K 26 amp I G 1000 amp 50K Fuse-20K Fuse Coordination 50 K A B 20 K 26 amp I G 1000 amp Coordination Limit Fuse-Fuse Coordination Example: Select a fuse size at point C That can achieve proper coordination with upstream fuses. Ifault Max 2000 amp A 90 amp 100 K 65K 80 amp B Ifault Max 1500 amp C 35 amp ? KI fault Max Power System Review 1000 amp Fuse-Fuse coordination Ifault Max 2000 amp A 90 amp 100 K 65K 80 amp B Ifault Max 1500 amp C 35 amp ? KI fault Max 1000 amp Recloser-Fuse Coordination Recloser Defined in ANSI/IEEE C37.60 Settings Require Selecting: Minimum Pick up or Coil size Curve Selection: Fast Curve Slow Curve Operating Sequence: Number of Fast Curve shots Number of Slow Curve shots Shots to lockout Reset time Power System Review Recloser Two Types: Hydraulic Minimum Pickup is done by selecting appropriate rating for Series Coil inside the tank TCC Curve Selection & Settings are done inside the tank Electronics Minimum Pickup: Trip Resistors TCC Curves and Timing plugs are done at the front panel Control Hydraulic Solid State Microprocessor Power System Review Electronic Recloser Settings TCC Curve Curve Selection/Type Settings: Min Trip Setting Phase & Ground Instantaneous Trip Setting Phase & ground Constant Time Adder Amp Multiplier Reclosing Operation Setting Typically Two Fast/Two Delay 0.5 sec<Reclosing intervals<60 sec Power System Review Electronic Recloser Settings Phase Trip Setting Minimum Trip= (Range of 2 to 2.5) x Max Load Current This facilitates cold load pick up & load growth Ground Trip Setting Minimum Trip= (Range of 0.3 to 0.5)x Phase Minimum Trip Min trip setting helps to protect against high impedance faults Instantaneous Setting Trip Setting= (Range of 4 to 16)X Minimum Trip Power System Review Hydraulic Recloser Phase Trip-Setting Estimate the Peak load Determine the Coil Size: Inrush Current dictates the coil rating selection Coil Size(Amp)=1.25 x Peak Load Calculate the Minimum Phase Trip Setting: Minimum Trip(Amp)=2 x Peak-Load Some utilities use factor of 2.5 or 3.0 Example (W type Hydraulic Recloser; coil sizes are 100, 140, 200, 280, 400, and 560): Assume Peak Load= 150A Coil Size= 1.25 x 150= 187.5→ Thus select 200 A Minimum Trip= 2x150= 300A→ Select 400A Min Trip Level (Note: 200A Coil has Minimum Trip Rating of 400A) Power System Review Hydraulic Recloser Ground Trip-Setting Steps: 1. Calculate the Normal Load Unbalance Iground MinTrip I 1( Normal Load Unbalance) I 2( Load UnbalanceCreated bythe Largest Single Phase Device) I 1 INormal Load Unbalance 10% of Peak Load I 2 ILargest Load Unbalance Largets Tap Fuse(Amp) 2. Calculate the end-of-line minimum fault current level. The Iground-Trip must be bellow Imin-Fault. Iground MinTrip IEnd of Line Min fault 3. Estimate the Ground Minimum Trip Level. IUnbalance Load( I 1 I 2) Iground Min Trip IEnd of Line Min fault Power System Review TCC Coordination Time Margins Recloser-Reloser Hydrolic Reclosers: Min Trip and continuous current are both dependent of the coil size Reclosing intervals are 1, 1.5, and 2 seconds Small Reclosers have Series coil : H, VH, L, and E series TCC Curve Separation >12 Cycles (0.2 sec); typically 0.25-0.30 sec Large Reclosers have High-Voltage solenoid : D, V, W, VW series TCC Curve Separation > 8 Cycles(0.133 sec); typically 0.2 sec Electronic Reclosers: Unlike Hydraulic recloses, Min Trip is independent of the Recloser’s continuous rating Reclosing intervals are 2, 5, and 15 seconds Min Trip selection must allow for the cold-load pick up & load growth TCC Curve Separation > 0.30 Sec 0.30 Sec=0.22 sec (CT saturation& errors)+0.08 sec (Breaker Opening time) TCC Coordination Time Margins Electronic Recloser to Hydraulic Recloser: TCC Curve Separation > 0.2 Sec; typically 0.25 sec Recloser-Fuse Methode#1: Use K factor for Recsloser: Range of 1.25<K<1.8 Methode#2: ADD Recloser Cumulative Times Add the cumulative reclose interval for a 2A-2C recloser sequence and coordinate with Fuse Minimum Clearing curve x 0.75 Power System Review Recloser-Fuse Coordination Recloser Cumulative Time Method R Time Fuse ' ' b a <Coordination Limit < B' 2 A 2B Temp Fault: Recloser operates; Fuse is saved. Permanent Fault: Recloser operates first, then fuse blows B delay A' 2 A A(Fast) a' a b' b Current 75% of fuse MT curve (fuse damage curve) Power System Review Recloser-Fuse Coordination K-Factor Method ' a <Coordination Limit< b ' Refer to Manufacturer’s Time Supplied Tables Extract applicable K-Factor Multiply Curves by K-Factor Note: K-factor is a t-Multiplier B K(Time Multiplier) * Curve B B delay A K(Time Multiplier) * Curve A A(Fast) a' a b' b Current 75% of fuse MT curve (fuse damage curve) Power System Review Cooper Reclosers K-Factor Table Below -Curtsey of Cooper Power Systems •What is K-Factor? •K-Factors are Time multiplying factors for various Reclosing Intervals. K-Factor shifts the curves up increasing the time value by K-Factor for the same current value. Power System Review Source Fuse-Recloser Coordination Phase Trip Setting Steps: FUSE 5000 KVA Z 6% R 1. Calculate Full Load Iprim & Isec Iprim 5000 22.86 3 126.3 A I sec 5000 4.16 3 694 A R 22.86 kV / 4.16 kV 3 - Fault 4500A - G Fault 3800A I 400A(Peak) RX Recloser 2 A & 2C g 1A2 & 1E 2. Select an Appropriate Fuse size Fuse Size: 1.5x126.3A=189.5A → Select 200K 3. Select an Appropriate Recloser Coil Size: End of Line FAULT Calculate Coil Size: 1.25x400=500A 3 - Fault 1500A G Fault 175 A Select Coil size: 560A 4. Desired Minimum Phase Trip= 2.5 x Peak Load to override the Inrush IPhase 2.5x 400 1000 A Note: Cooper W & RX type Recloser Ratings: Coil Size Min Trip Rating Interrupting Rating 560 A 1120 A 10,000 A Source Fuse-Recloser Coordination Ground Trip Setting Steps: 1. Estimate Normal Load unbalance: 10% of Peak-Load Example: Iunbalance= 10% of Peak Load Iunbalance-Normal= 0.1 x 400=40A 2. Estimate the load unbalance created by the largest single-phase device: Example: Assume the largest single phase Load is 90A Fuse. Iunbalance-Load=90A 3. Calculate Unbalanced downline Ground Current: IGround Iunbalance Normal Iunbalance Load IGround 90 40 130 A 4. Select Minimum Ground Trip: Ig Min Trip 140 A IG Unbalanced (130A) IGround Setting (140A) IMin Fault (175A) Source Side Fuse-Recloser Coordination Recloser-Fuse (Load Side) Coordination •Determine an appropriate Fuse size @ Point B •Which fuse coordinates the best (100K or 140K?) •Answer 140K; Why? FUSE 5000 KVA Z 6% R R 22.86 kV / 4.16 kV 400 Amp RX Recloser 2 A2C B 90 Amp FAULT Power System Review G 1900 A Min Fault 600 A Recloser-Fuse (Load Side) Coordination FUSE 5000 KVA Z 6% R 3 - Fault 4500A - G Fault 3800A R 22.86 kV / 4.16 kV I 400A(Peak) RX Recloser 2 A & 2C g 1A2 & 1E B End of Line FAULT 3 - Fault 1500A G Fault 175 A 3 - Fault 1500A G Fault 175 A Fuse 100 K 140 K Coordination Limit 1112 A 2380 A Relays Mechanical & Digital Protection System Elements Protective relays Circuit breakers Current and voltage transducers Communications channels DC supply system Control cables Three-Phase Diagram of the Protection Team CB + CTs Protected Equipment Control SI DC Station Battery Relay Relay Contact SI Relay 52a 52 TC VTs – Circuit Breaker Red Lamp Most Common Protective Relays Protection Principles for Transmission & Distribution Lines: Overcurrent (50, 51, 50N, 51N) Directional Overcurrent (67, 67N) Distance (21, 21N) Differential (87) Circuit Breaker Selection Relay (The Brain) CT Ratio PT or VT Ratio Interrupting Cycle Voltage Class K =(VMAX/Vmin) BIL rating rating Power System Review Relay-Circuit Breaker Operation A B C Ground relay Phase relays Circuit Breaker In CTs Ia IbIb Ic In Ia Ib Ic Ic Load LOAD Load Ib Power System Review Ia Induction-Type Relays Power System Review Relay Classification Overcurrent Overvoltage Undervoltage Differential Directional Under Frequency Distance Power System Review Relays for Phase Faults Time overcurrent 51 Instantaneous & time overcurrent Directional Time Overcurrent 50/51 67 Instantaneous & directional time over current 50/67 Directional Instantaneous Overcurrent 67 Step Time Overcurrent 51 Directional Instantaneous and directional 67 Zone Distance 21 Power System Review Relays for Ground Faults Time Overcurrent 51N Instantaneous & Time Overcurrent 50N/51N Product Overcurrent 67N Instantaneous and Product Overcurrent 67N/50N Directional time overcurrent 67N Instantaneous and directional time overcurrent 67N Directional Instantaneous Overcurrent 67N Three-zone distance system 21N Power System Review Transformer Protection Open-Phase Condition CTRatio 120 Ia 3.3330, Ib 0, Ic 3.333 120 In Ia Ib Ic Ia Ic In 3.333 1.667 j 2.886 In 1.666 j 2.886 In 3.33360 A B C 400 a 0 a 400 a In 3.33360 In CTs=600/5 3.30 Ia 0 Ib 3.3 120 Ic In Ia 0 Ic In Ic Ia Open Ground Relay Could Pickup Single-Phase to Ground Fault A CTRatio 120 B Ia 500, Ib 3.333 120 Ic 3.333 120 C In Ia Ib Ic 400 a 400 a In 50 1.667 1.667 ISC In 46.6660 In In 46.70 CTs=600/5 Ia 500 Short ISC 6,000a 3.3 120 3.3 120 Ic In Ib Ground & Phase Relays both Pickup Ia Line-to-Line to Ground Fault ISC A B C 400 a ISC CTRatio 120 Ia 500, Ib 50 120 Ic 3.333 120 In Ia Ib Ic In 50 25 j 43.301 1.667 j 2.886 In 23.333 j 40.415 In 46.67 60 In 46.7 60 In CTs=600/5 Ia 500 Short Ia 50 120 Ib 3.3 120 IC 6,000a Ic Ia Ib Ground & Phase Relays both Pickup In Three-Phase to Ground Fault A B C Ia 12,000 ISC Ia 12,000 CTRatio 120 Ia 1000, Ib 100 120 Ic 100 120 In Ia Ib Ic In 0 Ia 12,000 ISC ISC In 0 In CTs=600/5 Ia 1000 Ia 12,000 Ib 100a 2 Ib 12,000 Ic 12,000 Ic 100a Ic Ib Short Ic Ia Ib Only Phase Relays Pickup Ia Relay Settings Two Settings: 1. Time Overcurrent 2. Instantaneous Instantaneous Setting Time Overcurrent pickup must be capable of & time setting must be handling: capable of handling: XFMR Inrush Peak Load Capacitor Inrush Cold-Load Pickup Asymmetrical Faults Motor starting Safety factor=1.2xSymm Fault Power System Review Relay Settings Phase Time Over Current (TOC) Setting Phase pick up: Method 1: 2xImax < I Pick up < I Min (phase-phase Fault current) Note: Ensure I Min-Fault ≥ 2 x I Peak- Load I Min=Iphase-to-Phase=0.866 x I Three-Phase fault Method 2: 25% Margin ; IPickup= Ifull-load/0.80 Ground Time Over Current (TOC) Setting Ground Pick up: Method 1: 2xI Normal ground Current < I Pick up< I Min Ground Fault Current Where; Normal Ground Current Range: 10% to 20% of Load Current Method 2: Ipickup=(0.40 to 0.75)x Ipeak-Load Power System Review Instantaneous Relays Pickup Settings Instantaneous Pickup Range: 2 x IPhase Pickup Iins tan tan eous 10 x IPhase Pickup Typical Instantaneous Phase & Ground Pick up= 2x Time Over Current relay pick ups Power System Review How to determine Pickup & Time Dial? Step 1: Calculate Short Circuit Current @ each Bus ( usually Phase-Phase Fault) Step 2: Identify CT Ratio & Breaker Interrupting Cycles at each Bus Step 3: Calculate Relay Minimum Pickup for each Device Step 3: Starts with the last relay and apply Time Margin of 0.3 to 0.4 sec (ANSI/IEEE Std-242 )between Relays: o CB’s operating time (5 cycles): o Relay Over travel time: o Safety factor (CT saturation, Errors): Total Power System Review 0.08 sec 0.1 sec 0.22 sec 0.4 Seconds Relay-Relay Setting 0.4 Sec Power System Review TCC Coordination Time Margins Relay-Fuse TCC Curve Separation Rule: Mechanical Relay requires minimum time margin of 0.3 sec time interval Digital Relay requires minimum time margin of 0.2 sec time interval Relay-Relay (Mechanical) TCC Curve Separation Rule: According to ANSI/IEEE Std-242:1986, the rime interval between two relays in series must be 0.3 to 0.4 seconds. This time interval components are: Circuit Breaker Operating Time(5cycle): 0.08 sec Relay Overtravel Time: 0.1 sec Safety factor for CT Saturation & errors: 0.22 sec Power System Review TCC Coordination Time Margins Relay-Relay (Digital)TCC Curve Separation: Time margin between series Relays must be minimum of 0.25 sec. This time separation consists of the following: 5 Cycle Breaker (0.08 sec) Relay Accuracy (0.04 sec) Safety factor & CT Ration (0.13 sec) Relay-Recloser Time Margin between Mechanical Relay & Hydraulic Recloser must be minimum of 0.28-0.30 sec Time Margin between Mechanical Relay & Electronic Recloser must be minimum of 0.25 sec Power System Review Relay-Recloser-Fuse Coordination In the following CKT coordinate Breaker B1, Cooper Form-4C Recloser, ABB PCD2000 Reclsoer, and 100K Tap Fuse. B2 Load 231A 2 3 Cooper Form 4C 25MVA Load 400A 115kV / 22.86kV 115 kV BUS ABB PCD2000 B1 Load 300A R Load 200A R3 1 100K FAULT @ Bus3 FAULT @ Bus2 FAULT @ Bus1 3 6000A Φ N 2000A 3 4000A Min Fault 1000A 3 3000 A Min Fault 443 A L1 Power System Review L2 L3 Relay-Recloser-Fuse Coordination Relay settings: Phase setting: PU=2.4 x 400=960A Ground setting: PU= 960/2=480 A Cooper Recloser Form 4C settings: Phase setting: PU=2x300=600A Ground setting: 160A<PU=600/3=200A<443A ABB Recloser Model PCD2000 settings: Phase setting: PU=2x200=400A Ground setting: 140A<(PU=150 A)<443 Power System Review Relay-Recloser-Fuse Coordination Over Voltage Protection Insulation Voltage Class Basic Impulse Level (BIL) Nameplate Rating Surge arrestors. Power System Review Overvoltage Protection Sources of Overvoltage: Ferroresonance Low Order Hormonics Voltage Regulation (XFMR LTC Malfunction) Transients caused by: Lightning surge Switching operations Line-to-Ground faults Capacitor Bank Switching Protection methods: Surge Arresters(ANSI C62.1-1981) Static Wires Useful IEEE/ANSI Standards Graph of Curves can be found in ANSI/IEEE Standard C37.91-1985, “Guide for Protective Relay Applications to Power Transformers,” ANSI/IEEE C57.109-1993, “Guide for Transformer Through-Fault Current Duration.” IEEE/ANSI Standards 141&242 IEEE Std 242 – Buff Book IEEE Std 141 – Red Book IEEE Std 399 – Brown Book •IEEE C37.90 – Relays IEEE C37.91 – Transformer Protection IEEE C37.102 – Guide for AC Generator Protection References 1. J.D. Golver, M.S. Sarma, Power System Analysis and design, 4th ed., (Thomson Crop, 2008). 2. M.S. Sarma, Electric Machines, 2nd ed., (West Publishing Company, 1985). 3. A.E. Fitzgerald, C. Kingsley, and S. Umans, Electric Machinery, 4th ed. (New York: McGraw-Hill, 1983). 4. P.M. Anderson, Analysis of Faulted Power systems(Ames, IA: Iowa Satate university Press, 1973). 5.W.D. Stevenson, Jr., Elements of Power System Analysis, 4th ed. (New York: McGraw-Hill, 1982). Solution Break Time !!!!! Answer: 37.5 KVA