Low-Peak® CUBEFuse® With and Without Indication

advertisement
Low-Peak® CUBEFuse® With and Without Indication
Finger-Safe, Dual-Element, Time-Delay Class J Performance Fuse, 1-100A, 600Vac/300Vdc
Catalog Numbers (amp rating)
Indicating CUBEFuse
TCF6
TCF10
TCF15
TCF30
TCF35
TCF40
TCF70
TCF80
TCF90
Non-Indicating CUBEFuse
TCF1RN TCF3RN
TCF6RN
TCF20RN TCF25RN TCF30RN
TCF50RN TCF60RN TCF70RN
TCF17-1/2
TCF45
TCF100
TCF20
TCF50
TCF25
TCF60
TCF10RN
TCF35RN
TCF80RN
TCF15RN
TCF40RN
TCF90RN
TCF17-1/2RN
TCF45RN
TCF100RN
Features and Product Benefits
70-100A Case Size
35-60A Case Size
1-30A Case Size
Catalog Symbols: TCF_ Indicating fuse (6-100A)
TCF_RN Non-indicating fuse (1-100A)
Dual-Element, Time-Delay Fuse: 10 Seconds Minimum Operating Time at
500% Rated Current
Ampere Rating: 1 to 100A
Voltage Rating: 600Vac/300Vdc
Interrupting Rating: 300kA RMS Sym. (UL)
200kA RMS Sym. (CSA)
100kA DC (UL & CSA)
Agency Information:
• UL Listed Special Purpose Fuse: Guide JFHR, File E56412
• CSA Certified Fuse: Class 1422- 02, File 53787
• CE compliance for the European Union low voltage directive
Other Ratings/Specifications:
•
•
•
•
•
•
•
•
•
•
•
•
•
The world’s first finger-safe power fuse system.
Smallest footprint of any class fuse including Class J, CC, T and RK.
Meets Class J time-delay electrical performance requirements.
Available with and without open fuse indication to meet every customer
requirement.
The indicating version features easyID™ open fuse technology for faster
troubleshooting and reduced downtime.
Faster response to damaging faults to help reduce destructive thermal and
magnetic forces.
True dual-element fuse construction with a minimum of 10 seconds timedelay at 500% of rating.
Long time-delay minimizes nuisance circuit openings due to temporary
overloads and transient surges.
High interrupting rating to safely interrupt faults up to 300kA.
No venting of arc or molten metal and gases during opening.
Robust cycling and inrush current withstand.
Low let-through currents under fault conditions.
Provides Type 2 “No Damage” protection for IEC motors starters when
properly sized.
Easy selective coordination with any other Cooper Bussmann® Low-Peak®
Class L, J and RK1 fuse with simple 2:1 amp ration between upstream and
downstream fuses.
Watts Loss at rated current: TCF30: 3.99W
TCF60: 6.23W
TCF100: 9.51W
Operating and Storage Temperature Range: 14 to 149°F(-10 to 65°C)
Material Specifications:
•
• Case: Glass filled PES (Polyethersulfone)
• Terminals: Copper alloy
• Terminal plating: Electroless tin
• Indicator lens: PES (Polyethersulfone)
(indicating version only)
CUBEFuse Holders, Disconnects and Safety Switch
• Indicator: Energetic chemical
The CUBEfuse is used in the following Cooper Bussmann® products.
Carton Quantity and Weight
Amp
Carton Weight Per Carton
Rating
Qty.
lbs
kg
TCF1-30A
12
1.39
0.63
TCF35-60A
12
1.42
0.65
TCF70-100A
6
1.74
0.79
TCFH_N 100, 60 & 30A Holders.
Data Sheet 9007
0309
BU-SB09230
CCP_CF 1-, 2- & 3-Pole
switched disconnects
Data Sheet 1157
Page 1 of 2
CCPB 1-, 2- & 3-Pole disconnects for
the Quik-Spec™ Coordination
Panelboard. Data Sheet 1160
CF_ Quik-Spec™ Safety
Switch disconnect (optional
window). Data Sheet 1156
Data Sheet 9000
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TCF_ and TCF_RN Dimensions – in (mm)
Fuse
Amps
1-15
17.5-20
25-30
35-40
45-50
60
70-100
Time-Current Characteristic Curves–Average Melt
A
1.88
(47.75)
1.88
(47.75)
1.88
(47.75)
2.13
(54.10)
2.13
(54.10)
2.13
(54.10)
3.01
(76.45)
B
0.75
(19.05)
0.75)
(19.05)
0.75
(19.05)
1.00
(25.40)
1.00
(25.40)
1.00
(25.40)
1.00
(25.40)
Dimensions - in (mm)
C
D
E
1.00
0.23
0.04
(25.40)
(5.84)
(1.02)
1.00
0.27
0.04
(25.40)
(6.86)
(1.02)
1.00
0.31
0.04
(25.40)
(7.94)
(1.02)
1.13
0.36
0.04
(28.58)
(9.14)
(1.02)
1.13
0.40
0.04
(28.58)
(10.16)
(1.02)
1.13
0.44
0.04
(28.58)
(11.11)
(1.02)
1.26
0.57
0.06
(32.00)
(14.4)
(1.60)
F
0.63
(15.88)
0.63
(15.88)
0.63
(15.88)
0.63
(15.88)
0.63
(15.88)
0.63
(15.88)
0.63
(15.88)
G
0.27
(6.86)
0.27
(6.86)
0.27
(6.86)
0.38
(9.65)
0.38
(9.65)
0.38
(9.65)
0.39
(9.93)
Current Limitation Curves
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
© 2009 Cooper Bussmann
St. Louis, MO 63178
www.cooperbussmann.com
0309
BU-SB09230
Page 1 of 2
Data Sheet 9000
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Fuse Holders for Low-Peak® CUBEFuse®
Finger-Safe, 1-100A, 600Vac/300Vdc
Features and Product Benefits
Catalog Symbols: TCFH30N (1-30A)
TCFH60N (1-60A)
TCFH100N (1-100A)
Construction: Finger-safe
Mounting: DIN Rail or panel mount
Ampacities:
TCFH30N - holds any 1-30A CUBEFuse
TCFH60N - holds any 1-60A CUBEFuse
TCFH100N - holds any 1-100A CUBEFuse
Voltage Rating: 600Vac/300Vdc
Withstand Rating: 300kA RMS Sym. (UL)
200kA RMS Sym. (CSA)
100kA DC (UL & CSA)
Agency Information:
• UL Listed Fuse Holder: Guide IZLT, File E14853
• CSA Certified Fuse Holder: Class 6225-01, File 47235
• CE compliance for the European Union low voltage directive
Operating and Storage Temperature Range: 14 to 149°F(-10 to 65°C)
Material Specifications:
• Holder case: Glass filled PBT
• Interface clips: Copper alloy
• Interface clip plating: Tin
• Terminals: Steel
• DIN Rail spring: Stainless steel
• Holder for the world’s first finger-safe power fuse system.
• Holder and CUBEFuse together deliver Class CF and Class J fuse
performance with dual-element, time-delay and current limitating operation.
See Data Sheet 9000 for indicating and non-indicating CUBEFuse
performance characteristics.
• Smallest fuse and holder footprint of any class fuse installation including
Class J, CC, T and RK.
• DIN Rail or panel mount for easy installation.
• Holders dovetail together to easily achieve the required number of poles.
• All holders (TCFH30N, TCFH60N and TCFH100N) dovetail together to permit
mixing ampacities.
• All holders accept equal and lower amp rated TCF_ indicating and TCF_RN
non-indicating CUBEFuse - no need for a fuse reducer.
• Dual wire rated terminals for wiring ease.
• High 300kA withstand rating stands up to high fault currents.
Conductors/Wire Range - 75ºC Cu Wire Only
Holder/
Ampacity
TCFH30N
TCFH60N
TCFH100N
No. of
Poles*
1
1
1
Single
Wire
18 to 8 AWG
18 to 4 AWG
18 to 1 AWG
Dual
Wire
18 to 10 AWG
18 to 6 AWG
6 AWG
* Holders dovetail together to achieve the desired number of poles for the application.
Carton Quantity and Weight
Part
Number
TCFH30N
TCFH60N
TCFH100N
Carton
Qty.
12
12
6
Weight Per Carton
lbs
kg
2.42
1.10
2.57
1.17
1.38
0.63
Terminal Torque Ratings by Conductor and Holder Size (75°C Cu only)
TCFH30N
TCFH60N
TCFH100N
Single
Dual
Single
Dual
Single
Dual
10-8 AWG 25lb-in 18-10 AWG 25lb-in 18-10 AWG 20lb-in 18-10 AWG 20lb-in 18-10 AWG 25lb-in
6 AWG 45lb-in
18-12 AWG 20lb-in
8-4 AWG 35lb-in
8-6 AWG 35lb-in
8-1 AWG 40lb-in
0710
BU-SB10812
Page 1 of 2
Data Sheet 9007
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TCFH Dimensions – in (mm)
A
A
B
D
B
C
C
D
TCFH30N & TCFH60N
E
Holder
A
2.30
TCFH30N
(58.50)
2.60
TCFH60N
(66.12)
2.91
TCFH100N
(73.81)
B
0.76
(19.37)
1.03
(26.23)
1.05
(26.74)
C
1.357
(34.24)
1.60
(40.64)
2.01
(50.93)
D
0.15
(3.76)
0.17
(4.34)
0.15
(3.81)
E
0.80
(20.39)
F
A
F
2.51
(63.65)
TCFH100N
CUBEFuse Availability and Applications
The indicating Low-Peak® CUBEFuse® (TCF_) and non-indicating Low-Peak
CUBEfuse (TCF_RN) are available in amp ratings from 1-100A. See Data
Sheet 9000. The CUBEFuse is also used in these other Cooper Bussmann®
circuit protection solutions.
TCF_ Indicating and TCF_RN non-indicating CUBEFuse.
Data Sheet 9000
70-100A Case Size
35-60A Case Size
1-30A Case Size
CCP_CF 1-, 2- & 3-Pole CCPB 1-, 2- & 3-Pole disconnects for
switched disconnects
the Quik-Spec™ Coordination
Data Sheet 1157
Panelboard. Data Sheet 1160
CF_ Quik-Spec™ Safety
Switch disconnect (optional
window). Data Sheet 1156
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This
bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice,
any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
© 2010 Cooper Bussmann
St. Louis, MO 63178
www.cooperbussmann.com
0710
BU-SB10812
Page 2 of 2
Data Sheet 9007
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Download