Installation Instructions Model DLC

advertisement
Installation Instructions
Model DLC
Device Loop Card
INTRODUCTION
The SIEMENS Model DLC Device Loop Card is the interface
for connection of FireFinder-XLS smoke detectors, manual
stations, monitor devices, and control devices to the
FireFinder-XLS System. The DLC uses one network address
on the system. The application program that is loaded into
the on-board microprocessor controls the DLC operation.
DLC
RESET
POWER
CARD FAIL
HNET FAIL
GND FAULT
ALARM
The DLC contains 12 LEDs for diagnosis of problems.
Ground fault detection is provided by loop.
All field devices connected to the DLC are addressed and
tested using the Device Programming Unit (DPU).
OPERATION
ZONES STATUS
Z
O
N
E
1
Z
O
N
E
2
CLASS A OPEN
CLASS A RETURN
SHORT
CLASS A OPEN
CLASS A RETURN
SHORT
The DLC initializes, operates, and maintains all devices
residing on the loop. The DLC communicates all relevant
device and event information, such as alarms and troubles,
to the System CPU. The sensitivity of any intelligent smoke
detector and the logic functions of any intelligent output
devices can be checked and adjusted from the PMI through
the DLC. All information about the devices on the loop can
be displayed on the PMI. The DLC allows the System
polarity insensitive devices to be connected without
generating errors.
The DLC supports only one loop (two isolated parallel
zones) of up to 252 FireFinder-XLS intelligent field devices
as well as device accessories (relay bases, audible bases,
and remote lamps) in any combination. The microprocessor
controls the on-board isolator to isolate either zone from the
loop if one of them is shorted. When one zone is isolated
from the loop, the other zone will still work.
The on-board microprocessor provides the DLC with the
ability to function and initiate alarm conditions even if the
main FireFinder-XLS CPU fails.
P/N 315-033090-5
TROUBLE
+
+
+
1
2
3
-
-
-
HNET
Figure 1
DLC Device Loop Card
Siemens Building Tec
hnologies
echnologies
Fire S
afety
Safety
Controls and Indicators
The front panel of the DLC contains one reset switch, 12 LEDs, and one HNET
address switch, as shown in Figure 1. A reset switch is located on the top of the front
panel. Pushing the reset switch re-initializes the DLC operation.
The LEDs follow the reset switch and their functions are defined as follows:
POWER
(Green)
Normally ON. When illuminated, indicates the power for the DLC is applied to
the card.
CARD FAIL
(Yellow)
Normally OFF. When illuminated, indicates the card microprocessor has failed.
HNET FAIL
(Yellow)
Normally OFF. When illuminated, indicates that the HNET communication with
the DLC has terminated and the card
goes into degrade mode.
GND FAULT
(Yellow)
Normally OFF. When illuminated, indicates that the DLC has detected either a
negative or positive ground fault on its
field wiring.
ALARM
(Red)
Normally OFF. When illuminated, indicates
that the DLC has detected an alarm.
TROUBLE
(Yellow)
Normally OFF. When illuminated, indicates that the DLC has detected a
trouble on its field wiring.
CLASS A OPEN–ZONE 1
(Yellow)
Normally Off. When illuminated, indicates
a Zone 1 wire is open if the loop was set
to Class A.
CLASS A RETURN–ZONE 1
(Yellow)
Normally Off. When illuminated, indicates
a Zone 1 return wire is reversed if the
loop was set to Class A.
SHORT–ZONE 1
(Yellow)
Normally Off. When illuminated, indicates
a Zone 1 wire short.
CLASS A OPEN–ZONE 2
(Yellow)
Normally Off. When illuminated, indicates
a Zone 2 wire is open if the loop was set
to Class A.
CLASS A RETURN–ZONE 2
(Yellow)
Normally Off. When illuminated, indicates
a Zone 2 return wire is reversed if the
loop was set to Class A.
SHORT–ZONE 2
(Yellow)
Normally Off. When illuminated, indicates
a Zone 2 wire short.
A three-position switch at the bottom of the front panel is used to set the HNET
network address of the DLC. All field devices connected to the DLC are addressed
and tested using the Device Programming Unit (DPU). Refer to the DPU Manual,
P/N 315-033260 for further information.
Siemens Building Technologies
Fire Safety
2
P/N 315-033090-5
PRE-INSTALLATION
Set the three-digit HNET network address for the DLC using the three-position switch
located near the bottom of the front panel. (Refer to Figure 1 for the location of the
switch.) The address for the DLC must be the same as the address selected for it in
the Zeus Programming Tool. To increment each digit of the address, press the “+”
button above the desired digit; to decrement each digit, press the “-” button below
the desired digit. The range of allowable addresses is from 001 to 251.
INSTALLATION
The DLC plugs perpendicularly into one slot in the CC-5 card-cage via two 96-pin DIN
connectors and can occupy any slot in the card cage.
(Refer to Figure 2.)
Insert the DLC card into the card guides rightside up
(lettering on the front panel is legible)
Slide the card in until the card edge connectors contact
the receptacles on the motherboard.
Verify that the DIN connectors of the card and the cardcage aligned properly. The card can only plug in one
direction to the card cage, if it does not align, DO NOT
FORCE the card.
Place thumbs on the front panel adjacent to the captive
screws and gently apply even pressure on the card
until the connectors seat in the receptacles on the
motherboard.
Secure with the captive screws.
Figure 2
Installing The DLC
WIRING
Disconnect BATTERY and AC prior to working on equipment.
All field wiring to the DLC is connected to the terminal blocks of the CC-5 card cage
slot in which it is installed.
To Connect External Wiring
1.
Lift the WHITE cover on the terminal block.
2.
Loosen the screw of the terminal by turning it counterclockwise.
3.
Insert the wire into the side of the terminal block.
4.
Tighten the screw of the terminal block by turning it clockwise.
Connect +24V from the PSC-12 to terminal 17 and -24V from the PSC-12 to terminal
18 of the slot in the CC-5 where the DLC will be installed. (Refer to Figure 3.)
Siemens Building Technologies
Fire Safety
3
P/N 315-033090-5
LINE 1 (RETURN)
LINE 2 (RETURN)
LINE 2 (OUT)
LINE 1 (OUT)
LINE 1 (RETURN)
LINE 2 (RETURN)
LINE 2 (OUT)
ZONE 2
LINE 1 (OUT)
ZONE 1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
23
24
DO NOT USE
ONE SLOT OF CC-5
17
24V+
18
19
20
24V-
21
22
DO NOT USE
TO 24VDC FROM THE PSC-12
Figure 3
Wiring The 24VDC Power Lines To The DLC Slot In The CC-5
CLASS A WIRING*
CLASS B WIRING**
NO T-TAPPING ALLOWED
BOTH ZONES MUST BE WIRED AS CLASS A
T-TAPPING ALLOWED
BOTH ZONES MUST BE WIRED AS CLASS B
ZONE 1
ZONE 2
ZONE 1
ZONE 2
INITIATING
DEVICE
NOT USED
5
LINE 2
4
LINE 1
NOT USED
LINE 2
NOT USED
CC-5
LINE 1
NOT USED
LINE 2 (OUT)
LINE 2 (RETURN)
LINE 1 (RETURN)
LINE 1 (OUT)
LINE 2 (OUT)
LINE 2 (RETURN)
LINE 1 (OUT)
LINE 1 (RETURN)
INITIATING
DEVICE
CC-5
1
2
9
3
10
4
11
12
5
13
6
14
7
15
1
8
9
16
Siemens Building Technologies
Fire Safety
10
3
11
12
13
6
14
7
15
8
16
**OPERATES IN FULL CONFORMANCE WITH STYLE 4
*OPERATES IN FULL CONFORMANCE WITH STYLE 6
Figure 4
DLC Wiring Diagram
2
NOTES:
1. NO END OF LINE DEVICE REQUIRED.
2. BOTH CIRCUITS SUPERVISED AND POWER LIMITED PER NEC 760.
4
P/N 315-033090-5
The DLC circuit can be wired Style 4 (Class B) or Style 6 (Class A). On-board switches
controlled by microprocessor allow selection of Class A or B without using jumpers
for Class B. The DLC field circuit wiring does not require twisted, shielded wire. It can
be installed in conduit containing low voltage power, notification appliance circuits,
audible and speaker zone circuits, and RS-485 and other data circuits without restrictions.
Electrical connections for the two zones are shown in Figure 4. The wiring style is set
in the Zeus Programming Tool without using external jumpers. Once the wiring style
is set, both zones will be set to the same style.
Do not wire the two zones in different styles.
If the return wires are reversed in each zone (Class A), the CLASS A RETURN LED
will turn on. Switch the two return wires to remove this trouble. Eliminate all other
troubles before completing the installation.
COMPATIBILITY
1.
The DLC supports only FireFinder-XLS intelligent devices. The compatibility
identifiers for the compatible devices are the model numbers listed in Table 1.
Use any combination of those listed.
2.
The DLC supports one loop (with 2 isolated zones) of up to 252 FireFinderXLS intelligent field devices. Up to 252 devices can be distributed in either
zone, but the total number is limited. For example, if 100 devices are in Zone
1, then the number of the devices in Zone 2 must be 152 or less.
3.
All circuits are power limited to NFPA 70 per NEC 760. The DLC supports
the use of 18 AWG min non-shielded, non-twisted, thermoplastic fixture
wire without conduit, if permitted by local building codes.
4.
No end of line device is required.
5.
Total circuit resistance of each zone must not exceed 50 ohms when 252
devices are loaded into one zone. (Refer to the chart on page 6.)
TABLE 1
DLC Compatible Devices
Compatible
Devices
AD-11P
ADBH-11
AD-HR
DB-11
DB-HR
HFP-11
HFPT-11
HLIM
HMS-2S
HMS-M
HMS-S
HMS-SA
HMS-D
HTRI-D
HTRI-M
HTRI-R
HTRI-S
HZM
ILED-HC
ILED-HW
RL-HC
RL-HW
Installation
Instructions
P/N 315-095659-9
P/N 315-033210-3
P/N 315-033280-3
P/N 315-094193-7
P/N 315-033220-2
P/N 315-033290-3
P/N 315-033290-3
P/N 315-033170-2
P/N 315-033430-2
P/N 315-033450-2
P/N 315-033200-2
P/N 315-033430-2
P/N 315-033200-2
P/N 315-033300-2
P/N 315-034000-2
P/N 315-033300-2
P/N 315-033300-2
P/N 315-034850-2
P/N 315-048637-1
P/N 315-048637-1
P/N 315-033230-2
P/N 315-033230-2
Maximum capacitance:
0.5µF between line+ and line1.0µF between line and chassis
6.
T-tapping is not allowed on Class A loops.
ELECTRICAL RATINGS
Siemens Building Technologies
Fire Safety
24V Back Plane Current
0
Screw Terminal 24V Current
100mA + 1.8mA per device
6.2V Back Plane Current
200mA max
24V Standby Current
145mA + 1.8mA per device
Device Loop: 30VDC peak
375mA max (power limited)
5
P/N 315-033090-5
260
250
240
230
220
210
200
Line Resistance (ohm)
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
260
Max Number of Devices Per Zone
DLC LINE RESISTANCE vs MAX NUMBER OF DEVICES
Note: The total number of devices in two zones can not exceed 252.
For CE applications in Cerberus E100 systems refer to
Installation Instruction A24205-A334-B844 (English) or A24205-A334-A844 (German).
Siemens Building Technologies, Inc.
8 Fernwood Road
Florham Park, New Jersey 07932
Siemens Building Technologies, Ltd. Siemens Gebäudesicherheit
2 Kenview Boulevard
GmbH & Co. oHG
Brampton, Ontario L6T 5E4 CN
D-80930 München
P/N 315-033090-5
Download