Installation & Maintenance Data IM 737 Group: Fan-coil Part Number: 106332800 Date: May 2002 Electric Valve Package Kits for THC Series Fan-coil Units Installation and maintenance are to be performed only by qualified personnel who are familiar with and in compliance with state, local and national codes and regulations, and experienced with this type of equipment. Caution: Sharp edges and coil surfaces are injury hazards. Avoid contact with them. The electric valve package kits are furnished completely soldered and leak tested at the factory. Four (4) solder connections are required to complete the installation of the valve package into the system (two at the coil supply and return connections and two at the supply and return runouts). ! The electric valve is to be in the open position, and ball valves in the closed position while soldering. Do not move the valve handles until the tubing has cooled for three (3) minutes. Installation 1. 2. Clean all connections before assembly with fine sandpaper. A good grade solder flux will help ensure a proper bond. A general purpose 50/50 solder is recommended. Do not silver solder or braze the valves or copper fittings in this kit. A chill block, or equivalent, must be used to prevent leaks in the factory connection or overheating the valve. Position the valve package on the unit by moving the kit piping slightly. Do not try to move the coil connections. ! WARNING To prevent electrical shock, disconnect electric power to system at main fuse or circuit breaker box until installation is complete. CAUTION 3. A hydrostatic test on all piping is recommended after all connections are complete. 4. Field wiring must be in accordance with local codes and/ or the National Electrical Code. Wiring should be routed to prevent the possibility of condensate dripping from the valve package piping onto the electrical conduit. Figure 1. Manual Operating Lever Release Button Mating Hole Valve Actuator Installation Stem Latch the manual operating lever in the engaged position (N.C. only). Depress the release button (See Fig. 1). Align the body with the actuator to ensure the stem is inserted into the large mating hole on the bottom side of the actuator. Engage the actuator on the body and release the button. Actuator AG2 is used for normally open operation. Actuator AG1 is used for normally closed operation. MH7186 MH25807 Figure 2. Mounting 360° 90° A 90° B The PopTop™ valve can be mounted vertically or horizontally. If mounted horizontally, the valve should be mounted within 90° of upright position (See Fig. 2). If mounted vertically, care should be taken to ensure moisture does not drip onto motor. The valve actuator should not be mounted upside down. Vertical ® 4900 Technology Park Boulevard • Upside Down Auburn, New York 13021-9030 • 800-432-1342 • www.mcquay.com IM 737 Pg 1 of 6 ©2002 McQuay International THC Series 2-Way, 2-Pipe Valve Assembly - Left Hand Unit Shown Figure 2-1. - Top View Figure 2-3. A ir F lo w Return Ball Valve Control Valve Actuator Coil Connect 1/2" Copper x MPT Adapter Supply Gate Valve Figure 2-2. - Front View Coil Return Figure 2-4. - End View Coil Supply Figure 2-5. - Wiring For THC Series 2-Pipe Heating/Cooling With Automatic Changeover Legend Wire No. 16 WHT ORG Wire Color Wire Connector CLG BLU Wire Connector Field Connector BLU C/O TCI RED HTG RED BLK BLK V WHT CLG Cooling HTG Heating TCI Thermostat V C/O IM 737 / Page 2 of 6 Valve Change over Switch (Manual or Auto) ©2002 McQuay International THC Series 3-Way, 2-Pipe Valve Assembly - Left Hand Unit Shown Figure 3-1. - Top View Figure 3-3. w Flo Air Return Ball Valve Control Valve Actuator Coil Connect 1/2" Copper x MPT Adapter Supply Gate Valve Figure 3-2. - Front View Coil Return Figure 3-4. - End View Coil Supply Figure 3-5. - Wiring For THC 2-Pipe Heating/Cooling With Automatic Changeover Legend Wire No. 16 WHT ORG Wire Color Wire Connector CLG BLU Wire Connector Field Connector BLU C/O TCI RED HTG RED BLK BLK V WHT CLG Cooling HTG Heating TCI Thermostat V C/O IM 737 / Page 3 of 6 Valve Change over Switch (Manual or Auto) ©2002 McQuay International THC Series 2-Way, 4-Pipe Valve Assembly - Left Hand Unit Shown Figure 4-3. Figure 4-1. - Top View Control Valve Actuator w Flo Air Coil Connect 1/2" Copper x MPT Adapter Return Ball Valves Supply Gate Valves Figure 4-2. - End View Figure 4-4. - Front View 7.52" (191mm) 11.67" (296mm) .77" (20mm) Coil Return 6.75" (171mm) Coil Return Coil Supply Coil Supply Figure 4-5. - Wiring For THC Series 4-Pipe Heating/Cooling Legend 16 WHT Wire Color Wire Connector ORG WHT CLG CLG BLU BLK V HTG HTG RED BLK V Wire Connector WHT TCI IM 737 / Page 4 of 6 Wire No. Field Connector CLG Cooling HTG Heating TCI Thermostat V WHT C/O Valve Change over Switch (Manual or Auto) ©2002 McQuay International THC Series 3-Way, 4-Pipe Valve Assembly - Left Hand Unit Shown Figure 5-1. - Top View Figure5-3. w Flo Air Return Ball Valves Control Valve Actuator Coil Connect 1/2" Copper x MPT Adapter Supply Gate Valves Figure 5-4. - Front VIew 7.69" (195mm) Figure 5-2. - End View .77" (22mm) 9.04" (230mm) 6.83" (173mm) Coil Return Coil Return Coil Supply Coil Supply Figure 5-5. - Wiring For THC Series 4-Pipe Heating/Cooling Legend 16 WHT Wire Color Wire Connector ORG WHT CLG CLG BLU BLK V HTG HTG RED BLK V Wire Connector WHT TCI IM 737 / Page 5 of 6 Wire No. Field Connector CLG Cooling HTG Heating TCI Thermostat V WHT C/O Valve Change over Switch (Manual or Auto) ©2002 McQuay International This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.mcquay.com. ® 4900 Technology Park Boulevard • Auburn, New York 13021-9030 • 800-432-1342 • www.mcquay.com IM 737 Pg 6 of 6 (5-02) ©2002 McQuay International