Form10/00 UK ABWR Document ID Document Number Revision Number : : : GA91-9101-0101-16003 HPE-GD-H018 A UK ABWR Generic Design Assessment Generic PCSR Sub-chapter 16.3 : Heating Ventilating and Air Conditioning System Hitachi-GE Nuclear Energy, Ltd. NOT PROTECTIVELY MARKED Form01/03 UK ABWR Page ii /ii DISCLAIMERS Proprietary Information This document contains proprietary information of Hitachi-GE Nuclear Energy, Ltd. (Hitachi-GE), its suppliers and subcontractors. This document and the information it contains shall not, in whole or in part, be used for any purpose other than for the Generic Design Assessment (GDA) of Hitachi-GE’s UK ABWR. This notice shall be included on any complete or partial reproduction of this document or the information it contains. Copyright No part of this document may be reproduced in any form, without the prior written permission of Hitachi-GE Nuclear Energy, Ltd. Copyright (C) 2014 Hitachi-GE Nuclear Energy, Ltd. All Rights Reserved. GA91-9101-0101-16003 Rev. A NOT PROTECTIVELY MARKED Form05/01 NOT PROTECTIVELY MARKED Generic Pre-Construction Safety Report UK ABWR Revision A Table of Contents 16.3.1 16.3.2 16.3.3 16.3.4 System Summary Description .......................................16.3-1 System Roles ....................................................................16.3-1 Function Delivered ..........................................................16.3-1 Basic Configuration ........................................................16.3-2 16.3.5 Mode of Operation ..........................................................16.3-5 16.3.4.1 Reactor Area (R/A) HVAC ............................................................ 16.3-2 16.3.4.2 Emergency D/G Electrical Equipment Zone HVAC (DGEE/Z HVAC) ............................................................................................. 16.3-3 16.3.4.3 Turbine Building (T/B) HVAC ...................................................... 16.3-3 16.3.4.4 Heat Exchanger Building Normal and Emergency (Hx/B-N and Hx/B-E) HVAC ........................................................................ 16.3-3 16.3.4.5 Control Building Emergency Electrical Equipment Zone (CBEEE/Z) HVAC .......................................................................... 16.3-4 16.3.4.6 Main Control Room (MCR) HVAC .............................................. 16.3-4 16.3.4.7 Radwaste Building (Rw/B) HVAC ................................................ 16.3-4 16.3.4.8 Service Building (S/B) HVAC ........................................................ 16.3-4 16.3.4.9 Backup Building (B/B) HVAC ....................................................... 16.3-5 16.3.5.1 16.3.5.2 16.3.5.3 16.3.5.4 16.3.5.5 16.3.5.6 16.3.5.7 16.3.6 16.3.7 R/A HVAC ....................................................................................... 16.3-5 DGEE/Z HVAC ............................................................................... 16.3-5 Hx/B (Hx/B-N and Hx/B-E) HVAC ............................................... 16.3-6 CBEEE/Z HVAC ............................................................................ 16.3-6 MCR HVAC .................................................................................... 16.3-6 B/B HVAC ....................................................................................... 16.3-7 Other HVACs .................................................................................. 16.3-7 Design Basis .....................................................................16.3-7 System Design Description .............................................16.3-9 16.3.7.1 Overall Design and Operation ....................................................... 16.3-9 16.3.7.2 Equipment Design and Operation ............................................... 16.3-11 16.3.8 16.3.8.1 16.3.8.2 16.3.8.3 16.3.8.4 16.3.8.5 Main Support Systems..................................................16.3-28 Control and Instrumentation (C&I) Systems............................. 16.3-28 Power Supply Systems .................................................................. 16.3-28 HVAC Normal Cooling Water System (HNCW) ....................... 16.3-28 HVAC Emergency Cooling Water System (HECW) ................. 16.3-28 Heating Steam/Heating Steam Condensate Return System (HS/HSCR) .................................................................................... 16.3-29 16.3.8.6 Reactor Building Cooling Water System (RCW) ...................... 16.3-29 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System : Table of Contents Ver. 0 NOT PROTECTIVELY MARKED i NOT PROTECTIVELY MARKED Form05/01 Generic Pre-Construction Safety Report UK ABWR 16.3.1 Revision A System Summary Description This section is a general introduction to the HVAC where the system roles, system functions, system configuration and modes of operation are briefly described. 16.3.2 System Roles The HVAC is designed to achieve the following purposes. (1) The HVAC has a function of keeping the negative pressure within the area so the contaminants are not spread and providing the function of dilution of the contaminants when they are generated by ensuring sufficient ventilation rate. In addition, exhaust air is treated with the filter before discharging from the area. (2) The HVAC has a function of removing heat from radiant equipment such as electric panels, mechanical facilities and piping with high temperature. (3) The HVAC has a function of providing outdoor fresh air for operator and occupants. (4) The HVAC has a function of discharging smoke in the case of fire and supplying fresh air in exchange. It also has the function of preventing smoke from moving into clean areas thus ensuring egress routes for operators. 16.3.3 Function Delivered The HVAC is designed to provide the following functions. (1) Isolation and independency of the system The HVAC is independently for each radiation controlled/ non-controlled area and building, in order that they are provided with sufficient physical barrier to separate from each other. The HVAC division of equipment for emergency is corresponded with emergency power division. (2) Exhaust Exhaust air from the potential contaminated area is discharged from the main exhaust stack. Filters are installed in the Exhaust Air Treatment Facilities of the systems that discharge exhaust air through main exhaust stack. On the other hand, air is directly discharged to the atmosphere through the local place without any treatment of filters only if the area is assured to noncontaminated. (3) Ventilation Ventilation method is decided in consideration of the system required functions and economical efficiency from following Type-1, Type-2 or Type-3. (a) Type-1 ventilation method This is a ventilation method of using Supply Fan for supplying air and Exhaust Fan for discharging air. There are two methods for this ventilation type. One is “Once-through ventilation method” which discharges whole air volume that is supplied, and another method is “Mixing outdoor air and recirculated air ventilation method.” (i) Once-through ventilation This is a method that Supply Fans supply air from outdoor and the same amount of air is discharged by Exhaust Fans. Mainly, this method is used for the HVAC within radiation controlled area. (ii) Mixing outdoor air and recirculated air ventilation This is a method of recirculating part of exhaust air back to the place where the air supplied wherein these air are mixed the same amount of incoming air is discharged to 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-1 NOT PROTECTIVELY MARKED Form05/01 Generic Pre-Construction Safety Report UK ABWR Revision A outdoor by means of the Exhaust Fan. This method is mainly used for HVAC within radiation non-controlled area. (b) Type-2 ventilation method This is a method to supply air by means of the Supply Fan and exhaust air through openings. Since the pressure within the building is positive, this method is used for the ventilation of radiation non-controlled area. (c) Type-3 ventilation method This is a method to use opening to supply outdoor air and discharge the air by means of the Exhaust Fan. This method is used for the local ventilation. (4) Cooling and heating Outdoor air cooling is done by the chilled water from the Refrigerators supplied to the HVAC Cooling coil. In principle, the HVAC Normal Cooling Water System (HNCW) is used for the normal system whereas the HVAC Emergency Cooling Water System (HECW) is used for the emergency system. Local Cooling Unit used for local cooling can be divided into either the Normal Local Cooling Unit or Emergency Local Cooling Unit. Chilled or cooling water is used for following. - Local Cooling Unit for normal use; HNCW - Local Cooling Unit for emergency use; the Reactor Building Cooling Water System (RCW) Heating is carried out by the Heating Steam (HS) through the HVAC heating coil. It should be noted that there is a case when cooling/heating is carried out by Fan Coil Unit (FCU) or MultiSplit Air Conditioning unit when there is a necessity to control room temperature individually for each room such as the general habitable area located within radiation non-controlled area. (5) Dust removal from the outdoor air Middle efficiency air filter is used when supplying outdoor air to minimize the amount of dust etc. that could infiltrate into the building. (6) Air flow control and ensuring negative pressure Air flow direction within the building is directed from less contaminated area to more contaminated area and the contamination is prevented from spreading to other areas. As for the HVAC located within the radiation controlled area, differential pressure of the inside/outside of the building is adjustable so the pressure of the whole areas are ensured to negative. (7) Functionality of the smoke purging Smoke purging is necessary for the human access by means of the HVAC Exhaust Fan, or smoke Purge Fan specifically made for discharging smoke while supplying outdoor fresh air by means of the Supply Fan. The smoke generated within each fire zone designated as safety zone, is not allowed to infiltrate into adjacent clean area. 16.3.4 Basic Configuration The HVAC consists of sub-systems as following. 16.3.4.1 Reactor Area (R/A) HVAC The summary of the main components are as following. (1) Supply Fan 3 units - 50 % each (Used both for exchanging outdoor air and discharging smoke) 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-2 Form05/01 NOT PROTECTIVELY MARKED Generic Pre-Construction Safety Report UK ABWR (2) (3) (4) (5) (6) (7) (8) (9) Revision A Exhaust Fan 3 units - 50 % each (Combined use with the Smoke Purge Fan) Supply Air Treatment Facility single unit - 100 % (Cooling coils and filters are mounted) Exhaust Air Treatment Facility 3 units - 50 % each (Filters are mounted) R/A Supply Air Isolation Damper and Accumulator Tank 2 units each (Mounted on the Supply Duct of the R/A HVAC) R/A Exhaust Air Isolation Damper and Accumulator Tank 2 units each (Mounted on the Exhaust Duct of the R/A HVAC) Normal Local Cooling Unit 4 units Emergency Local Cooling Units 12 units Duct, damper and accessory 1 set 16.3.4.2 Emergency D/G Electrical Equipment Zone HVAC (DGEE/Z HVAC) This system consists of the divisions A, B and C. The summary of the main components are as following. (1) DGEE/Z Supply Fan 2 units [per division] - 100 % each [per division] (Used both for exchanging outdoor air and discharging smoke) (2) DGEE/Z Exhaust Fan 2 units [per division] - 100 % each [per division] (3) DGEE/Z Smoke Purge Fan single unit [per division] - 100 % [per division] (4) DGEE/Z Supply Air Treatment Facility single unit [per division] - 100 % [per division] (Cooling coils and filters are mounted) (5) Duct, damper and accessory 1 set (6) ED/G Room Emergency Supply Fan 2units [per division] - 50 % each [per division] 16.3.4.3 Turbine Building (T/B) HVAC The summary of the main components are as following. (1) Supply Fan 3 units - 50 % each (Used both for exchanging outdoor air and discharging smoke) (2) Exhaust Fan 3 units - 50 % each (Combined use with the Smoke Purge Fan) (3) Supply Air Treatment Facility single unit – 100 % (Cooling coils and filters are mounted) (4) Exhaust Air Treatment Facility 3 units - 50 % each (Filters are mounted) (5) Local Cooling Unit 8 units (6) Duct, damper and accessory 1 set 16.3.4.4 Heat Exchanger Building Normal and Emergency (Hx/B-N and Hx/B-E) HVAC The summary of the main components are as following. (1) Hx/B-N HVAC (a) Supply Fan single unit - 100 % (Used both for exchanging outdoor air and discharging smoke) (b) Supply Air Treatment Facility single unit – 100 % (Cooling coils, heating coils and filters are mounted) (c) Duct, damper and accessory 1 set (2) Hx/B-E HVAC This system consists of the divisions A, B and C. (a) Supply Fan single unit [per division] - 100 % [per division] (Used both for exchanging outdoor air and discharging smoke) 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-3 Form05/01 NOT PROTECTIVELY MARKED Generic Pre-Construction Safety Report UK ABWR Revision A (b) Supply Air Treatment Facility single unit [per division] - 100 % [per division] (Filters are mounted) (c) Duct, damper and accessory 1 set 16.3.4.5 Control Building Emergency Electrical Equipment Zone (CBEEE/Z) HVAC This system consists of the divisions A, B and C. The summary of the main components are as following. (1) Supply Fan 2 units [per division] - 100 % [per division] (Used both for exchanging outdoor air and discharging smoke) (2) Exhaust Fan 2 units [per division] - 100 % [per division] (3) Smoke Purge Fan single unit [per division] - 100 % [per division] (4) Supply Air Treatment Facility single unit [per division] - 100 % [per division] (Cooling coils and filters are mounted) (5) Local Cooling Unit 2 units (6) Duct, damper and accessory 1 set 16.3.4.6 Main Control Room (MCR) HVAC This system consists of the divisions A and B one of which is provided as a redundancy. The summary of the main components are as following. (1) Supply Fan single unit [per division] - 100 % [per division] (2) Exhaust Fan single unit [per division] - 100 % [per division] (3) Recirculation Supply Fan single unit [per division] - 100 % [per division] (4) Smoke Purge Supply Fan single unit [per division] - 100 % [per division] (5) Supply Air Treatment Facility single unit [per division] - 100 % [per division] (Cooling coil and filters are mounted) (6) Emergency Filter Train single unit [per division] - 100 % [per division] (Iodine removal charcoal filters are mounted) (7) Duct, damper (Including the motor operated MCR Isolation Dampers) and accessory 1set 16.3.4.7 Radwaste Building (Rw/B) HVAC The summary of the main components are as following. (1) Supply Fan 2 units - 100 % each (Used both for exchanging outdoor air and discharging smoke) (2) Exhaust Fan 2 units - 100 % each (Combined use with the Smoke Purge Fan) (3) Supply Air Treatment Facility single unit - 100 % (Cooling coils and filters are mounted) (4) Exhaust Air Treatment Facility 2 units - 100 % each (Filters are mounted) (5) Duct, Damper and accessory 1 set 16.3.4.8 Service Building (S/B) HVAC The summary of the main components are as following. (1) Supply Fan 3 units - 50 % each (Used both for exchanging outdoor air and discharging smoke) (2) Exhaust Fan 3 units - 50 % each (Combined use with the Smoke Purge Fan) (3) Supply Air Treatment Facility single unit - 100 % (Cooling coils and filters are mounted) (4) Exhaust Air Treatment Facility 3 units - 50 % each (Filters are mounted) 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-4 NOT PROTECTIVELY MARKED Form05/01 Generic Pre-Construction Safety Report UK ABWR Revision A (5) Fan Coil Unit or Multi-Split Air Conditioning Unit TBD (6) Duct, Damper and accessory 1 set 16.3.4.9 Backup Building (B/B) HVAC The summary of the main structural components are as following. (1) Supply Fan 2 units - 100 % each (Used both for exchanging outdoor air and discharging smoke) (2) Exhaust Fan 2 units - 100 % each (Combined use with the Smoke Purge Fan) (3) Supply Air Treatment Facility single unit - 100 % (Electric heating coil and filters are mounted) (4) Duct, Damper and accessory 1 set (5) ED/G Room Emergency Supply Fan 2 units - 50 % each System outline of each HVAC sub-system are shown in the Figure 16.3-1 to 16.3-15. 16.3.5 Mode of Operation 16.3.5.1 R/A HVAC This system is subjected to be in operation during the plant normal/emergency operation, or when smoke purging is required. Operation modes of the system are as following. (1) Normal operation mode Except for the Emergency Local Cooling Units, all of equipment is in operation during the output operation of the reactor and when conducting inspections. (2) Emergency operation mode Upon receiving emergency signal (“drywell pressure high”, “reactor water level low”, “R/A exhaust radioactivity high” or “refuelling area radioactivity high”), the R/A Isolation Dampers mounted on the Supply/Exhaust duct are automatically closed to isolate R/A while preventing exfiltration of the radioactive gas to outdoor by switching into the Standby Gas Treatment System (SGTS). In the event of Loss of Off-site Power (LOOP), the R/A HVAC shut down, but cooling is still possible with the power supply provided by the ED/G within the room wherein Engineered Safety Features (ESFs) [such as Emergency Core Cooling System (ECCS) pumps] are installed. (3) Smoke purge operation mode “Once-through ventilation method” is employed for supplying air and discharging smoke by means of the Supply Fan and the Exhaust Fan. 16.3.5.2 DGEE/Z HVAC This system is subjected to be in operation during the plant normal/emergency operation, or when smoke purging is required. Operation modes of the system are as following. (1) Normal operation mode Except for the ED/G Room Emergency Supply Fan and the Smoke Purge Fan, all of equipment is in operation during the plant normal operation and the plant normal shutdown. (2) Emergency operation mode 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-5 Form05/01 NOT PROTECTIVELY MARKED Generic Pre-Construction Safety Report UK ABWR Revision A Operation is continuously carried out by receiving the power supply provided by the ED/G in the event of LOOP. In addition, the ED/G Room Emergency Supply Fan is operated after the ED/G is activated. (3) Smoke purge operation mode “Once-through ventilation method” is used for supplying air by the Supply Fan, and the Exhaust Fan is shutdown. The Smoke Purge Fan is operated for discharging smoke. 16.3.5.3 Hx/B (Hx/B-N and Hx/B-E) HVAC This system is operated during the plant normal operation and when smoke purging is required. However, the Emergency Supply Fan within the Hx/B-E is subjected to be in operation only for the event of emergency in addition to the necessity of operation when discharging smoke as required. Operation modes of the system are as following. (1) Normal operation mode Except for the Supply Fan within Hx/B-E, all of equipment is in operation during the plant normal operation and when plant normal shut down. (2) Emergency operation mode In the event of the LOOP, the HVAC within Hx/B-N is shutdown, and the Hx/B-E Supply Fan is in operation by means of the power supply provided by the ED/G. (3) Smoke purge operation mode During the plant normal operation, the Hx/B-N Supply Fan is used for supplying outdoor air and discharging smoke whereas the Hx/B-E Supply Fan is used during the plant emergency operation both of which belong to “Type-2 ventilation method.” 16.3.5.4 CBEEE/Z HVAC This system is subjected to be in operation during the plant normal/emergency operation, or when smoke purging is required. Operation modes of the system are as following. (1) Normal operation mode Except the Smoke Purge Fan, all of equipment is operated during the plant normal operation and the plant normal shut down. (2) Emergency operation mode Operation is continuously carried out by receiving the power supply provided by the ED/G in the LOOP. (3) Smoke purge operation mode “Once-through ventilation method” is used for supplying air by means of the Supply Fan, and the Exhaust Fan is shutdown. The Smoke Purge Fan is operated for discharging smoke. 16.3.5.5 MCR HVAC This system is subjected to be in operation during the plant normal/emergency operation, or when smoke purging is required. Operation modes of the system are as following. (1) Normal operation mode Except for the MCR Recirculation Supply Fan, the MCR Emergency Filter Train and the Smoke Purge Supply Fan, all of equipment is in operation during the plant normal operation and when plant normal shut down. 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-6 NOT PROTECTIVELY MARKED Form05/01 Generic Pre-Construction Safety Report UK ABWR Revision A (2) Emergency operation mode When isolating the MCR in the event of emergency, this system is isolated by the MCR Isolation Dampers, and the part of recirculation air is directed to the MCR Emergency Filter Train. In addition, the MCR Isolation Dampers for supplying outdoor air is opened and the air is continuously supplied as needed. After mixing the part of indoor recirculation air, it will be filtered by the MCR Emergency Filter Train for supplying the air. As for the air purging, the MCR Exhaust Fan is operated after opening the MCR Isolation Dampers before discharging the exhaust air to the atmosphere. Operation is continuously carried out by receiving the power supply provided by the ED/G in the event of LOOP. (3) Smoke purge operation mode “Once-through ventilation method” is used for supplying outdoor air and discharging smoke by means of the Smoke Purge Supply Fan and the Exhaust Fan. 16.3.5.6 B/B HVAC This system is subjected to be in operation during the plant normal/emergency operation, or when smoke purging is required. Operation modes of the system are as following. (1) Normal operation mode Except for the ED/G Room Emergency Supply Fan, all of equipment is operated during the plant normal operation the plant normal shutdown. (2) Emergency operation mode Operation is continuously carried out by receiving provided by the ED/G in the LOOP. In addition, ED/G Room Emergency Supply Fan is operated after the ED/G is activated. (3) Smoke purge operation mode “Once-through ventilation method” is used for supplying outdoor air and discharging smoke by means of the Supply Fan and the Exhaust Fan. 16.3.5.7 Other HVACs Following systems are operated during the plant normal operation and/or when smoke purging is required but these systems are shutdown in the event of LOOP. T/B HVAC Rw/B HVAC S/B HVAC 16.3.6 Design Basis This section describes the design basis for HVAC. The HVACs are designed to meet the following safety functions. (1) Normal/Emergency and Emergency HVAC The Normal/Emergency and Emergency HVACs are directly related to the nuclear safety function such as the emergency shutdown of the reactor, cooling for the reactor core, and removal of the heat after shutting down the reactor. They have the important roles as for cooling, or removing heat load to ensure the functions related to Structures, Systems and Components (SSCs) (or its related systems). Any failures of the HVAC could consequently inhibit to the objectives from ensuring its intended functions so as to keep the required functions subjected for the SSCs. Thus, safety class is equivalent to that of the SSCs safety category as Table 16.3-1 shows. 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-7 NOT PROTECTIVELY MARKED Form05/01 Generic Pre-Construction Safety Report UK ABWR Revision A Table 16.3-1: Objects of SSCs and that of HVAC (Provisional) Related HVAC HVAC safety division Category Class RHR, RCIC, HPCF ECCS Local Cooling Units among R/A HVAC Emergency A 1 FPC (Emergency makeup water system) FPC Pump Room Local Cooling Unit among R/A HVAC Emergency A 1 Emergency onsite power system DGEE/Z HVAC Normal/Emergency A 1 ED/G Emergency Supply Fan Emergency A 1 Normal/Emergency A 2 B/B ED/G Emergency Supply Fan Emergency A 2 CBEEE/Z HVAC Normal/Emergency A 1 Emergency A 1 Normal/Emergency A 1 Emergency B 2 Emergency B 2 Emergency B 2 Objects (SSCs) B/B HVAC Direct current power supply system Emergency component cooling water system MCR emergency ventilation system Reactor Building (R/B) SGTS FCS Hx/B-E HVAC MCR HVAC (Relevant system) Isolation Damper and Accumulator tank among R/A HVAC Local Cooling Unit for the SGTS room among R/A HVAC Local Cooling Unit for the FCS room among R/A HVAC 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-8 NOT PROTECTIVELY MARKED Form05/01 Generic Pre-Construction Safety Report UK ABWR Revision A (2) Normal HVAC The Normal HVACs are operated during the plant normal operation/shutdown process in order to contain radioactive contaminants, and remove heat load from the normal electric panels, equipment and facilities while keeping the environmental habitability and conformity that are to be ensured for operators and occupants. Any failures of the HVAC could consequently inhibit to the objectives from ensuring its intended functions as mentioned above. Thus, SSCs used for the normal plant operation are subjected to be cooled, and the design is be categorized as “Safety Category C” and classified as “Safety Class 3” in terms of “ALARP”. Related HVACs are as following. (a) R/A HVAC (Except for the R/A Isolation Damper and Accumulator) (b) T/B HVAC (c) Hx/B-N HVAC (d) Rw/B HVAC (e) S/B HVAC 16.3.7 System Design Description This section described the design of the HVAC. 16.3.7.1 Overall Design and Operation 16.3.7.1.1 R/A HVAC The R/A HVAC is categorized for establishing two functions. (1) Normal function This system provides ventilation and air conditioning function for the R/A during the plant normal operation. In case smoke is generated within fire area it is discharged to outdoor and fresh air is supplied in exchange. In addition, heat has to be removed by means of the Local Cooling Unit for cooling the heat source if the heat load is significantly high at the local area during the plant normal operation. During the plant normal shutdown, the nitrogen gas is exchanged with air within the Primary Containment Vessel (PCV) to provide access route for operators and workers. To do so, HVAC supply air for the R/A is partially directed to the Atmospheric Control system (AC) via the purging filter. Consequently, air is returned to the R/A HVAC exhaust system by means of the PCV Purge Exhaust Fan. (2) Emergency function Upon receiving emergency signal (“drywell pressure high”, “reactor water level low”, “R/A radioactivity high” or “refuelling area radioactivity high”), the R/A Isolation Damper mounted on the supply/exhaust duct of the R/A HVAC are automatically closed to isolate R/A while preventing exfiltration of the radioactive gas to outdoor by switching into SGTS. In addition, rooms wherein equipment that are related to ESFs (such as ECCS pumps) are installed intended for the operation in the event of emergency, heat is removed by the Emergency Local Cooling Unit. The power is supplied by the ED/G. System outline of the R/A HVAC is shown in the Figure 16.3-1. 16.3.7.1.2 DGEE/Z HVAC The DGEE/Z HVAC provides ventilation and air conditioning function for DGEE/Z during the plant normal/emergency operation. In case smoke is generated within fire area it is discharged to outdoor 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-9 NOT PROTECTIVELY MARKED Form05/01 Generic Pre-Construction Safety Report UK ABWR Revision A and fresh air is supplied in exchange. DGEE/Z has their own HVAC according to the adequate conformity for each electrical power division classified as divisions A, B and C. In addition, the ED/G Room Emergency Supply Fans specifically designed for emergency use are provided according to the needs of each division of system A, B and C located within ED/G room. System outline of the DGEE/Z HVACs are shown in the Figure 16.3-2 to 16.3-4. 16.3.7.1.3 T/B HVAC The T/B HVAC provides ventilation and air conditioning function within the T/B during the plant normal operation while having a function of discharging smoke generated within fire zone to outdoor and supplying outdoor fresh air into the building in exchange. In addition, heat has to be removed by means of the Local Cooling Unit for cooling the heat source if the heat load is significantly high at the local area during the plant normal operation. System outline of the T/B HVAC is shown in the Figure 16.3-5. 16.3.7.1.4 Hx/B (Hx/B-N and Hx/B-E) HVAC The Hx/B-N HVAC provides ventilation and air conditioning function for the Hx/B during the plant normal operation. In case smoke is generated within fire area it is discharged to outdoor and fresh air is supplied in exchange. System outline of the Hx/B-N HVAC is shown in the Figure 16.3-6. The Hx/B-E HVAC provides ventilation function for the Hx/B during the plant emergency operation. In case smoke is generated within fire area it is discharged to outdoor and fresh air is supplied in exchange. This system is individually provided for this system according to the needs of division A, B and C for each RCW division. System outline of the Hx/B-E HVAC is shown in the Figure 16.3-7. 16.3.7.1.5 CBEEE/Z HVAC During the plant normal/emergency operation, the CBEEE/Z HVAC is provides ventilation and air conditioning function within CBEEE/Z. In case smoke is generated within fire area it is discharged to outdoor and fresh air is supplied in exchange. The CBEEE/Z HVAC consists of 3 divisions and each role of CBEEE/Z assigned for divisions 1 through 4. The objective for making these configurations as described below is to ensure to provide the HVAC with sufficient redundancies by incorporating various system combinations. The HVAC division A (Ventilation area: CBEEE/Z division 1 and division 4), the HVAC division B (CBEEE/Z division 2 and division 4), and the HVAC division C (CBEEE/Z division 3). Thus, divisions 1 through 4 for CBEEE/Z are provided with their own HVAC individually. In addition, the Local Cooling Unit is used for removing heat where the local heat load is significantly high. The exhaust air from battery room for each division is discharged to outdoor directly through exhaust duct and openings by the exhaust fans. System outline of the CBEEE/Z HVACs are shown in the Figure 16.3-8 to 16.3-10. 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-10 NOT PROTECTIVELY MARKED Form05/01 Generic Pre-Construction Safety Report UK ABWR 16.3.7.1.6 Revision A MCR HVAC During the plant normal/emergency operation, the MCR HVAC is provided with sufficient functions required for the ventilation and air conditioning intended for the MCR. In case smoke is generated within fire area it is discharged to outdoor and fresh air is supplied in exchange. This system consists of division A and B one of which is provided as a redundancy. During the plant normal operation, “Mixing outdoor air and recirculated air ventilation method” is adopted and the exhaust air is directly discharged to outdoor. In case of emergency, there is not to be any interference with the outdoor environment and in this case, “Inner Recirculating method” is adopted through which the air is filtered by means of iodine removal charcoal filter integrated within the MCR Emergency Filter Train. However, have the structure a capability of supplying outdoor air through iodine removal charcoal filter as needed. System outline of the MCR HVACs are shown in the Figure 16.3-11 and 16.3-12. 16.3.7.1.7 Rw/B HVAC The Rw/B HVAC provides ventilation and air conditioning function within the Rw/B during the plant normal operation. In case smoke is generated within fire area it is discharged to outdoor and fresh air is supplied in exchange. System outline of the Rw/B HVAC is shown in the Figure 16.3-13. 16.3.7.1.8 S/B HVAC The S/B HVAC provides ventilation and air conditioning function within the S/B during the plant normal operation. In case smoke is generated within fire area it is discharged to outdoor and fresh air is supplied in exchange. As for the general habitable area, the Fan Coil Unit or Multi-Split Air Conditioning Unit is used individually for cooling and heating, considering the habitability of the occupants if needed. System outline of the S/B HVAC is shown in the Figure 16.3-14. 16.3.7.1.9 B/B HVAC The B/B HVAC has a function of the ventilation and air conditioning within the B/B during the plant normal/emergency operation. In case smoke is generated within fire area it is discharged to outdoor and fresh air is supplied in exchange. In addition, the ED/G Room Emergency Supply Fans specifically designed for emergency use are provided for the ED/G room. The exhaust air from battery room is discharged to outdoor directly through exhaust duct and opening. System outline of the B/B HVAC is shown in the Figure 16.3-15. 16.3.7.2 Equipment Design and Operation 16.3.7.2.1 HVAC System Air Flow Rate Table 16.3-2 shows about the system air flow rate (provisional) provided for each HVAC subsystem in order to ventilate and remove heat from each building and area. 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-11 NOT PROTECTIVELY MARKED Form05/01 Generic Pre-Construction Safety Report UK ABWR Revision A Table 16.3-2: HVAC System Air Flow Rate (1/2) (Provisional) Bldg. R/B T/B System System Air Flow Rate Remarks 3 R/A HVAC 170000 m /h DGEE (A)/Z HVAC 35000 m3/h DGEE (B)/Z HVAC 36000 m3/h DGEE (C)/Z HVAC 28000 m3/h ED/G (A) Room HVAC 202000 m3/h* * Including ED/G combustion air. ED/G (B) Room HVAC 202000 m3/h* * Including ED/G combustion air. ED/G (C) Room HVAC 202000 m3/h* * Including ED/G combustion air. T/B HVAC 379000 m3/h Hx/B Hx/B-N HVAC 110000 m3/h Hx/B-E (A) HVAC 91000 m3/h Hx/B-E (B) HVAC 84000 m3/h Hx/B-E (C) HVAC 83000 m3/h (Continued) 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-12 NOT PROTECTIVELY MARKED Form05/01 Generic Pre-Construction Safety Report UK ABWR Revision A Table 16.3-2: HVAC System Air Flow Rate (2/2) (Provisional) Bldg. C/B System System Air Flow Rate CBEEE (A)/Z HVAC 17000 m /h CBEEE (B)/Z HVAC 23000 m3/h CBEEE (C)/Z HVAC 29000 m3/h MCR (A) HVAC 100000 m3/h MCR (B) HVAC 100000 m3/h Rw/B Rw/B HVAC 80000 m3/h S/B S/B HVAC 82000 m3/h B/B B/B HVAC 135000 m3/h ED/G Room HVAC 202000 m3/h* 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 Remarks 3 *Including ED/G combustion air. NOT PROTECTIVELY MARKED 16.3-13 NOT PROTECTIVELY MARKED Form05/01 Generic Pre-Construction Safety Report UK ABWR 16.3.7.2.2 Revision A Supply, Exhaust Fan and Smoke Purge Fan The Supply/Exhaust Fan and Smoke Purge Fan of HVAC are designed to perform as following Table 16.3-3. (Provisional) 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-14 NOT PROTECTIVELY MARKED Form05/01 Generic Pre-Construction Safety Report UK ABWR Revision A Table 16.3-3: HVAC Fan and Smoke Purge Fan Design Specifications (1/3) (Provisional) Bldg. Equipment name Quantity R/B R/A Supply Fan 3 (1 stand-by) 3 (1 stand-by) 1 R/A Exhaust Fan PCV Purge Exhaust Fan DGEE (A)/Z Supply Fan DGEE (B)/Z Supply Fan DGEE (C)/Z Supply Fan DGEE (A)/Z Exhaust Fan DGEE (B)/Z Exhaust Fan DGEE (C)/Z Exhaust Fan DGEE (A)/Z Smoke Purge Fan DGEE (B)/Z Smoke Purge Fan DGEE (C)/Z Smoke Purge Fan ED/G (A) Room Emergency Supply Fan ED/G (B) Room Emergency Supply Fan ED/G (C) Room Emergency Supply Fan T/B T/B Supply Fan Rated Air Flow Rate (per unit) 85000 m3/h 84200 m3/h 22000 m3/h 2 (1 stand-by) 2 (1 stand-by) 2 (1 stand-by) 2 (1 stand-by) 2 (1 stand-by) 2 (1 stand-by) 1 35000 m3/h 1 TBD 1 TBD 2 81500 m3/h 2 81500 m3/h 2 81500 m3/h 3 (1 stand-by) T/B Exhaust Fan 3 (1 stand-by) Hx/B Hx/B-N Supply 2 Fan (1 stand-by) Hx/B-E (A) Supply 1 Fan Hx/B-E (B) Supply 1 Fan 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 36000 m3/h 28000 m3/h 3000 m3/h 3000 m3/h 3000 m3/h TBD 189500 m3/h 188700 m3/h 110000 m3/h 91000 m3/h 84000 m3/h NOT PROTECTIVELY MARKED (Continued) 16.3-15 NOT PROTECTIVELY MARKED Form05/01 Generic Pre-Construction Safety Report UK ABWR Revision A Table 16.3-3: HVAC Fan and Smoke Purge Fan Design Specifications (2/3) (Provisional) Bldg. Equipment name Quantity Hx/B Hx/B-E (C) Supply Fan C/B CBEEE (A)/Z Supply Fan CBEEE (B)/Z Supply Fan CBEEE (C)/Z Supply Fan CBEEE (A)/Z Exhaust Fan CBEEE (B)/Z Exhaust Fan CBEEE (C)/Z Exhaust Fan CBEEE (A)/Z Smoke Purge Fan CBEEE (B)/Z Smoke Purge Fan CBEEE (C)/Z Smoke Purge Fan MCR (A) Supply Fan MCR (A) Exhaust Fan MCR (A) Recirculation Supply Fan MCR (A) Smoke Purge Supply Fan MCR (B) Supply Fan MCR (B) Exhaust Fan MCR (B) Recirculation Supply Fan MCR (B) Smoke Purge Supply Fan Rw/B Rw/B Supply Fan 1 Rated Air Flow Rate (per unit) 83000 m3/h 2 (1 stand-by) 2 (1 stand-by) 2 (1 stand-by) 2 (1 stand-by) 2 (1 stand-by) 2 (1 stand-by) 1 17000 m3/h 1 TBD 1 TBD 1* 100000 m3/h 1* 5000 m3/h 1* 8000 m3/h 1* TBD 1* 100000 m3/h 1* 5000 m3/h 1* 8000 m3/h 1* TBD 2 (1 standby) 2 (1 standby) 80000 m3/h Rw/B Exhaust Fan 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 23000 m3/h 29000 m3/h 4000 m3/h 1600 m3/h 2400 m3/h TBD 80000 m3/h NOT PROTECTIVELY MARKED (Continued) 16.3-16 NOT PROTECTIVELY MARKED Form05/01 Generic Pre-Construction Safety Report UK ABWR Revision A Table 16.3-3: HVAC Fan and Smoke Purge Fan Design Specifications (3/3) (Provisional) Bldg. Equipment name S/B S/B Supply Fan S/B Exhaust Fan B/B B/B Supply Fan B/B Exhaust Fan Quantity 3 (1 stand-by) 3 (1 stand-by) 2 (1 stand-by) 2 (1 stand-by) 2 Rated Air Flow Rate (per unit) 41000 m3/h 41000 m3/h 135000 m3/h 115000 m3/h ED/G Room 81500 m3/h Emergency Supply Fan Notes: * MCR HVAC has a redundancy and operates either division (A) or (B). 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-17 NOT PROTECTIVELY MARKED Form05/01 Generic Pre-Construction Safety Report UK ABWR 16.3.7.2.3 Revision A Supply Air Treatment Facility and Exhaust Air Treatment Facility The Supply Air Treatment Facility and Exhaust Air Treatment Facility Exhaust Fan are designed to perform as following Table 16.3-4. (Provisional) 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-18 NOT PROTECTIVELY MARKED Form05/01 Generic Pre-Construction Safety Report UK ABWR Revision A Table 16.3-4: Supply Air Treatment Facility and Exhaust Air Treatment Facility Design Specifications (1/3) (Provisional) Bldg . Equipment Name Quantity R/B R/A Supply Air Treatment Facility 1 R/A Exhaust Air Treatment Facility PCV Purge Supply Filter Unit DGEE (A)/Z Supply Air Treatment Facility DGEE (B)/Z Supply Air Treatment Facility DGEE (C)/Z Supply Air Treatment Facility ED/G (A) Room Supply Air Treatment Facility 3 (1 stand-by) ED/G (B) Room Supply Air Treatment Facility ED/G (C) Room Supply Air Treatment Facility Air Flow Rate (per unit) Coils 170000 m3/h Cooling coil Cooling medium HNCW Heating coil Heating medium HS 84200 m3/h - 1 22000 m3/h - 1 35000 m3/h Cooling coil Cooling medium HECW 1 36000 m3/h Cooling coil Cooling medium HECW 1 28000 m3/h Cooling coil Cooling medium HECW 1 202000 m3/h - 1 202000 m3/h 1 202000 m3/h - (Continued) 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-19 NOT PROTECTIVELY MARKED Form05/01 Generic Pre-Construction Safety Report UK ABWR Revision A Table 16.3-4: Supply Air Treatment Facility and Exhaust Air Treatment Facility Design Specifications (2/3) (Provisional) Bldg. Equipment name Quantity T/B T/B Supply Air Treatment Facility 1 T/B Exhaust Air 3 Treatment Facility (1 stand-by) Air Flow Rate (per unit) Coils 379000 m3/h Cooling coil Cooling medium Heating coil Heating medium 3 188700 m /h - HNCW HS Hx/B Hx/B-N Supply Air Treatment Facility 1 Hx/B-E (A) Supply Air Treatment Facility Hx/B-E (B) Supply Air Treatment Facility Hx/B-E (C) Supply Air Treatment Facility Rw/B Rw/B Supply Air Treatment Facility 1 110000 m3/h Cooling coil Cooling medium HNCW Heating Coil Heating medium HS 91000 m3/h - 1 84000 m3/h - 1 83000 m3/h - 1 80000 m3/h Cooling coil Cooling medium Heating coil Heating medium 3 80000 m /h - Rw/B Exhaust Air 2 Treatment Facility (1 stand-by) 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED HNCW HS (Continued) 16.3-20 Form05/01 NOT PROTECTIVELY MARKED Generic Pre-Construction Safety Report UK ABWR Revision A Table 16.3-4: Supply Air Treatment Facility and Exhaust Air Treatment Facility Design Specifications (3/3) (Provisional) Bldg. Equipment name Quantity C/B CBEEE (A)/Z Supply Air Treatment Facility CBEEE (B)/Z Supply Air Treatment Facility CBEEE (C)/Z Supply Air Treatment Facility MCR (A) Supply Air Treatment Facility MCR (B) Supply Air Treatment Facility S/B S/B Supply Air Treatment Facility 1 1 1 1* 1* 1 S/B Exhaust Air 3 Treatment Facility (1 stand-by) B/B B/B Supply Air Treatment Facility 1 Air Flow Rate (per unit) Coils 17000 m3/h Cooling coil Cooling medium HECW 23000 m3/h Cooling coil Cooling medium HECW 29000 m3/h Cooling coil Cooling medium HECW 100000 m3/h Cooling coil Cooling medium HECW 100000 m3/h Cooling coil Cooling medium HECW 82000 m3/h Cooling coil Cooling medium Heating coil Heating medium 3 41000 m /h - 135000 m3/h Heating coil Heating medium 3 202000 m /h - HNCW HS Electricity ED/G Room 1 Supply Air Treatment Facility Notes: * MCR HVAC has a redundancy and operates either division (A) or (B). 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-21 NOT PROTECTIVELY MARKED Form05/01 Generic Pre-Construction Safety Report UK ABWR 16.3.7.2.4 Revision A Local Cooling Unit Table 16.3-5 shows the design specifications of the Local Cooling Unit. (Provisional) 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-22 NOT PROTECTIVELY MARKED Form05/01 Generic Pre-Construction Safety Report UK ABWR Revision A Table 16.3-5: Local Cooling Unit Design Specifications (1/3) (Provisional) Unit Quantity 1 Fan Quantity 1 Air Flow Rate (per unit) 10000 m3/h 1 1 10000 m3/h RCW 1 1 10000 m3/h RCW 1 1 15100 m3/h RCW 1 1 15100 m3/h RCW 1 1 2300 m3/h RCW FPC Pump (A) Room Local Cooling Unit 1 1 1300 m3/h RCW FPC Pump (B) Room Local Cooling Unit 1 1 1300 m3/h RCW FCS (A) Room Local Cooling Unit 1 1 2400 m3/h RCW FCS (B) Room Local Cooling Unit 1 1 2400 m3/h RCW SGTS (A) Room Local Cooling Unit 1 1 600 m3/h RCW Bldg. Equipment Name R/B RHR Pump (A) Room Local Cooling Unit RHR Pump (B) Room Local Cooling Unit RHR Pump (C) Room Local Cooling Unit HPCF Pump (B) Room Local Cooling Unit HPCF Pump (C) Room Local Cooling Unit RCIC Pump Room Local Cooling Unit Cooling Medium RCW (Continued) 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-23 NOT PROTECTIVELY MARKED Form05/01 Generic Pre-Construction Safety Report UK ABWR Revision A Table 16.3-5: Local Cooling Unit Design Specifications (2/3) (Provisional) Bldg. Equipment Name R/B SGTS (B) Room Local Cooling Unit R/B MS Tunnel Room Local Cooling Unit Refuelling Machine Control Room Local Cooling Unit ISI Room Local Cooling Unit RIP FMCRD Handling Tool Control Room Local Cooling Unit MSR (A) Room Local Cooling Unit MSR (B) Room Local Cooling Unit T/D-RFP Room Local Cooling Unit IPB/Z Local Cooling Unit T/B 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 Unit Quantity 1 Fan Quantity 1 Air Flow Rate (per unit) 600 m3/h 1 7500 m3/h HNCW 1 2 (1 stand-by) 1 5400 m3/h HNCW 1 1 3700 m3/h HNCW 1 1 2220 m3/h HNCW 1 2 (1 stand-by) 2 (1 stand-by) 2 (1 stand-by) 2 (1 stand-by) 18200 m3/h HNCW 18200 m3/h HNCW 14400 m3/h HNCW 37300 m3/h HNCW 1 1 1 NOT PROTECTIVELY MARKED Cooling Medium RCW (Continued) 16.3-24 NOT PROTECTIVELY MARKED Form05/01 Generic Pre-Construction Safety Report UK ABWR Revision A Table 16.3-5: Local Cooling Unit Design Specifications (3/3) (Provisional) Bldg. Equipment Name T/B T/B Supply Fan Room Local Cooling Unit T/B Exhaust Fan Room Local Cooling Unit R/A Supply Fan Room Local Cooling Unit R/A Exhaust Fan Room Local Cooling Unit IA/SA Compressor Area Local Cooling Unit MG Set I Room Local Cooling Unit MG Set II Room Local Cooling Unit TBD C/B S/B 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 Unit Quantity 1 1 1 1 1 1 1 TBD Fan Quantity 2 (1 stand-by) 2 (1 stand-by) 2 (1 stand-by) 2 (1 stand-by) 2 (1 stand-by) 2 (1 stand-by) 2 (1 stand-by) TBD Air Flow Rate (per unit) 13500 m3/h Cooling Medium HNCW 18300 m3/h HNCW 13500 m3/h HNCW 18300 m3/h HNCW 9500 m3/h HNCW 9200 m3/h HNCW 9200 m3/h HNCW TBD HNCW NOT PROTECTIVELY MARKED 16.3-25 NOT PROTECTIVELY MARKED Form05/01 Generic Pre-Construction Safety Report UK ABWR 16.3.7.2.5 Revision A MCR Emergency Filter Train Table 16.3-6 shows the design specifications of the MCR Emergency Filter Train. (Provisional) 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-26 NOT PROTECTIVELY MARKED Form05/01 Generic Pre-Construction Safety Report UK ABWR Revision A Table 16.3-6: MCR Emergency Filter Train Design Specifications (Provisional) Bldg. C/B Equipment Name MCR (A) Emergency Filter Train Quantity Charcoal Filter Iodine removal charcoal filter (Bed depth of 50 mm) Efficiency 91 % (Simple substance test) *Relative humidity at less than or equal 70 % 90 % (In-place test) *Relative humidity at less than or equal 70 % MCR (B) 1* 8000 m3/h Type Iodine removal charcoal filter Emergency Filter (Bed depth of 50 mm) Train Efficiency 91 % (Simple substance test) *Relative humidity at less than or equal 70 % 90 % (In-place test) *Relative humidity at less than or equal 70 % Notes: * MCR HVAC has a redundancy and operates either division (A) or (B). 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 1* Air Flow Rate (per unit) 8000 m3/h Type NOT PROTECTIVELY MARKED 16.3-27 NOT PROTECTIVELY MARKED Form05/01 Generic Pre-Construction Safety Report UK ABWR 16.3.8 Revision A Main Support Systems The main support systems supporting mechanical SSCs for the delivery of the HVAC Normal/Emergency, Emergency and Normal functions are described as follows. 16.3.8.1 Control and Instrumentation (C&I) Systems Principal objective in adapting the method of control and instrumentation is to performance and reliability of the HVAC sub-system. For further details refer to Generic PCSR Chapter 14 “C&I”. 16.3.8.2 Power Supply Systems The summary of the main power supply systems are shown below. For further details on the design refer to Generic PCSR Chapter 15 “Electrical Power Supplies”. (1) Power supply for the Supply/Exhaust Fan of the Normal HVAC is given by the normal bus. (2) Power supply for each Supply/Exhaust Fan that belongs to the Normal/Emergency HVAC, is given by the emergency bus from each emergency system (divisions A, B and C). In the event of LOOP, the power supply will be given by ED/G (divisions A, B and C). (3) Power supply for the Normal HVAC Local Cooling Unit, the Supply Fans used for Fan Coil Unit and the Multi-Split Air Conditioning Unit is given by the normal bus. (4) Power supply for the Supply Fan used for the Emergency HVAC Local Cooling Unit is given by the emergency bus based on the power supply division wherein emergency equipment that are subjected to be cooled, are installed. In the event of LOOP, the power supply will be given by the ED/G. 16.3.8.3 HVAC Normal Cooling Water System (HNCW) The HNCW is a system which provides chilled water to the cooling coils within the normal Supply Air Treatment Facilities and Normal Local Cooling Units as following. (1) R/A HVAC (2) T/B HVAC (3) Hx/B-N HVAC (4) Rw/B HVAC (5) S/B HVAC For further details refer to Generic PCSR Chapter 16 “Auxiliary Systems” Water Systems. 16.3.8.4 HVAC Emergency Cooling Water System (HECW) The HECW is a system which provides chilled water to the cooling coils within the Normal/Emergency Supply Air Treatment Facilities and consists of 3 divisions (divisions A, B and C). Chilled water is supplied according to the needs from each HVAC division. (1) Chilled water for HVAC supplied by HECW(A), (B) and (C) - DGEE/Z (A), (B), (C) HVAC and CBEEE/Z (A), (B), (C) HVAC (2) Chilled water for HVAC supplied by HECW(A) and (B) - MCR (A), (B) HVAC For further details refer to Generic PCSR Chapter 16 “Auxiliary Systems” Water Systems. 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-28 Form05/01 NOT PROTECTIVELY MARKED Generic Pre-Construction Safety Report UK ABWR Revision A 16.3.8.5 Heating Steam/Heating Steam Condensate Return System (HS/HSCR) The HS/HSCR is a system which provides steam to the steam coils within the normal Supply Air Treatment Facilities as following. (1) R/A HVAC (2) T/B HVAC (3) Hx/B-N HVAC (4) Rw/B HVAC (5) S/B HVAC For further details refer to Generic PCSR Chapter 16 “Auxiliary Systems” Steam Supply System. 16.3.8.6 Reactor Building Cooling Water System (RCW) The RCW is a system which provides cooling water for the R/A Emergency Local Cooling Units. For further details refer to Generic PCSR Chapter 16 “Auxiliary Systems” Water Systems. 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-29 Form05/01 NOT PROTECTIVELY MARKED Generic Pre-Construction Safety Report UK ABWR Revision A Figure 16.3-1: Outline of the R/A HVAC 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-30 NOT PROTECTIVELY MARKED Form05/01 Generic Pre-Construction Safety Report UK ABWR Revision A Figure 16.3-2: Outline of the DGEE (A)/Z HVAC 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-31 NOT PROTECTIVELY MARKED Form05/01 Generic Pre-Construction Safety Report UK ABWR Revision A Figure 16.3-3: Outline of the DGEE (B)/Z HVAC 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-32 NOT PROTECTIVELY MARKED Form05/01 Generic Pre-Construction Safety Report UK ABWR Revision A Figure 16.3-4: Outline of the DGEE (C)/Z HVAC 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-33 Form05/01 NOT PROTECTIVELY MARKED Generic Pre-Construction Safety Report UK ABWR Revision A Figure 16.3-5: Outline of the T/B HVAC 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-34 Form05/01 NOT PROTECTIVELY MARKED Generic Pre-Construction Safety Report UK ABWR Revision A Figure 16.3-6: Outline of the Hx/B-N HVAC 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-35 Form05/01 NOT PROTECTIVELY MARKED Generic Pre-Construction Safety Report UK ABWR Revision A Figure 16.3-7: Outline of the Hx/B-E HVAC 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-36 NOT PROTECTIVELY MARKED Form05/01 Generic Pre-Construction Safety Report UK ABWR Revision A Figure 16.3-8: Outline of the CBEEE (A)/Z HVAC 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-37 NOT PROTECTIVELY MARKED Form05/01 Generic Pre-Construction Safety Report UK ABWR Revision A Figure 16.3-9: Outline of the CBEEE (B)/Z HVAC 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-38 NOT PROTECTIVELY MARKED Form05/01 Generic Pre-Construction Safety Report UK ABWR Revision A Figure 16.3-10: Outline of the CBEEE (C)/Z HVAC 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-39 Form05/01 NOT PROTECTIVELY MARKED Generic Pre-Construction Safety Report UK ABWR Revision A Figure 16.3-11: Outline of the MCR (A) HVAC 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-40 Form05/01 NOT PROTECTIVELY MARKED Generic Pre-Construction Safety Report UK ABWR Revision A Figure 16.3-12: Outline of the MCR (B) HVAC 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-41 Form05/01 NOT PROTECTIVELY MARKED Generic Pre-Construction Safety Report UK ABWR Revision A Figure 16.3-13: Outline of the Rw/B HVAC 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-42 Form05/01 NOT PROTECTIVELY MARKED Generic Pre-Construction Safety Report UK ABWR Revision A Figure 16.3-14: Outline of the S/B HVAC 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-43 Form05/01 NOT PROTECTIVELY MARKED Generic Pre-Construction Safety Report UK ABWR Revision A Figure 16.3-15: Outline of the B/B HVAC 16. Auxiliary Systems 16.3 Heating Ventilating and Air Conditioning System Ver. 0 NOT PROTECTIVELY MARKED 16.3-44