Code No. LIT-1900304 Issued February 1, 2009 SYSTEM 350™ APPLICATION NOTE Night Setback or Setup Using the A350 Temperature Control IMPORTANT: Use the A350 temperature control and S350 stage module only as operating controls. Where failure or malfunction of the A350 temperature control or S350 stage module could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of, or protect against, failure or malfunction of the A350 temperature control and S350 stage module. open (in the unoccupied mode), the sensor reading will be artificially shifted upward by the number of degrees that corresponds to the added resistance. System 350™ applications can be used in conjunction with any commercially available time clock that has dry contacts (rated to switch 1V at 1 mA or less) to perform night setback or setup. The offset from the daytime setpoint is accomplished by adding a resistor in series with the sensor (add 4.3 ohms for each degree (ºF) of offset from the occupied control point). Night Cooling Setup For setup of cooling, the clock contacts are open during the occupied mode. The occupied setpoint is adjusted to the desired occupied control point plus the number of degrees that corresponds to the resistance added. When the clock contacts open (in the occupied mode), the sensor reading will be artificially shifted upward by the number of degrees that corresponds to the added resistance. Night Heating Setback For setback of heating, the clock contacts are closed during the occupied mode. The setpoint is adjusted to the occupied value and the sensor reading is correct during the occupied mode. When the clock contacts Example Sensor Readings when Using Night Setback or Setup Examples Desired Occupied Temperature Desired Unoccupied Temperature A350 Setpoint D350 Sensor Reading Resistance Occupied Actual Temp Unoccupied Sensor Reading Actual Temp Sensor Reading Heating Setback, ºF (ºC) 70 (21) 60 (16) 70 (21) 70 (21) 70 (21) 60 (16) 70 (21) 43 ohms Cooling Setup, ºF (ºC) 78 (26) 88 (31) 88 (31) 78 (26) 88 (31) 88 (31) 88 (31) 43 ohms Time clocks shown in occupied mode. Heating (Setback) Cooling (Setup) Clock contacts closed in the occupied mode for heating, open in the occupied mode for cooling setup. Sens. A350 Y350 S350 S350 S350 D350 A350 COM To Heating A350 L1 and S350 COM Relay Contact 120 VAC Note: Both cooling S350 COM relay contacts must be wired to L1. L1 N Stage 1 Heating Stage 2 Heating Stage 1 Cooling Stage 2 Cooling 9305002:350setup.drw 9305001:fig1_01 A 43 ohm resistor will give an approximate 10 F° setup. Resistor should be mounted inside the clock enclosure. Figure 1: Night Setback or Setup Wiring Note: This method cannot perform cooling setup and heating setback on the same system. To lock out the opposite function, use a clock with double-pole/double-throw contacts and wire according to the diagram. The power to the relay contacts performing the function to be disabled must always be wired to a clock contact that will open in the unoccupied mode. IMPORTANT: Select a time clock that has dry contacts and is rated to switch 1V at 1 mA or less. Otherwise use the time clock contacts to energize a separate relay that has dry contacts. The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office. www.johnsoncontrols.com Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2009 Johnson Controls, Inc. 1 of 1