DOE 2.2 - Work-Arounds to Hidden Problems: eQUEST - A half hour to learn; three years to master. Building Energy Simulation Forum (BESF) April 20, 2011 Portland, OR Reid Hart, PE Associate Director, Technical Research Group Announcing: Final draft available covers: DCV Modeling of – – – – – Movie Theaters Meeting/Lecture Classrooms Gym/Fitness Retail Includes prototype eQUEST models Demand Controlled Ventilation (DCV) Measure Analysis Guide Research Funded by: Bonneville Power Administration Final Draft available at: http://energytrust.org/Business/building-energy-simulation/ Final soon available at: www.peci.org & www.bpa.gov/energy/n/commercial.cfm DOE 2.2 – Work-Arounds to Hidden Problems: eQUEST - A half hour to learn; three years to master. Learning Objectives: • Understand correct modeling of outside air economizers for single-stage dX cooling • Distinguish commercial ventilation requirements and modeling: What to do if you aren’t in California! • Understand DOE 2 limits and proper modeling of unoccupied fan operation • List issues for proper VFD fan modeling • Know how to model DCV 4 Understand Correct Modeling of Outside Air Economizers for Single-Stage dX RTUs DOE 2.2 – Work-Arounds to Hidden Problems: eQUEST - A half hour to learn; three years to master. 5 Basic OSA Economizer Idea 6 Savings from Economizer Levels Outside Air Economizer Potential Savings 200.0 Standard Economizer 180.0 160.0 kWh / Ton 140.0 Premium Economizer 120.0 100.0 Ideal Economizer 80.0 60.0 40.0 Required Cooling 20.0 0.0 37 42 47 52 57 62 67 72 77 82 87 92 97 Outside Air Temp - Eugene OR Ideal economizer does not happen in RTUs. Get most of savings with alternating integration. 7 102 Integrated Economizer for RTUs • Thermostat with dedicated stage for economizer. – Single stage at thermostat requires “either/or” operation with low (55 F) changeover setting. Result: very little savings. – Dedicated first stage on thermostat allows economizer to operate before compressor. • For dX cooling with minimal stages; must locate primary control sensor in discharge air, not mixed air position. – Mixed air sensors notoriously inaccurate (poor mixing) – Otherwise DA too cold, economizer will be disabled 8 Three specific economizer modeling issues: • Maximum outside air is usually less than the 100% default included in eQUEST • The minimum outside air position is often greater than required • Single zone packaged units with single-stage dX cooling coils operate in alternating integration while DOE 2.2 PSZ system incorrectly models full integration 9 Max OA Fraction • Code may call for 100%; do you get it? Packaged Unit Available OSA Flow Ecotope Study of 16 Packaged Units 6 Frequency 5 4 3 2 1 0 <20% Average: 64% Median: 66% 30% 50% 60% 70% 80% 90% 100% OSA Airflow; Damper Full Open • 70% is more reasonable for RTUs without exhaust fans 10 Suggested Max_OA_Fraction OA fraction improved with: • Barometric relief damper • Motorized exhaust damper • Seals and good closure on return damper • Powered exhaust fan • Return fan with return damper seals 11 Configuration MAX_OA_FRACTION No relief damper 0.50 Barometric relief damper (most common) 0.55 to 0.75 (0.70 suggested) Motorized relief/exhaust damper 0.60 to 0.80 (0.75 suggested) Good seals on return damper 0.75 to 0.85 (0.80 suggested) Powered exhaust fan activated at 50% OSA 0.80 to 0.90 (0.85 suggested) Return Fan with good seals on return damper 0.80 to 0.90 (0.85 suggested) Minimum Ventilation Rate • MIN-OUTSIDE-AIR at system level • ZONE keywords take precedence OUTSIDE-AIR-FLOW, OA-CHANGES, OA-FLOW/PER or EXHAUST-FLOW • Office typically 7% to 13% required; Actual ~20% 5 4 3 12 e 0 M or 80 60 40 30 20 15 OSA percent (bin up to) 10 n= 16 mean = 20.6% 10 5 2 1 0 0 Frequency RTU Percentage OSA Ecotope/EWEB 2001 Baseline? • Use 20%? May be appropriate for low density buildings • Prototypes use ASHRAE 90.1 area + 50% default people base case; matching most codes Alternating Integration Fix – – – – – 13 Economizer only Econo + Stage 1 dX Econo + Stage 2 dX Min OA + Stage 1 dX Min OA + Stage 2 dX Alternating Integration OSA=65; RA=75 250% deg F 75 200% 65 150% 55 100% 45 50% 35 0% 25 Cool Stage DA MA OSA% 1 342 5 76 8 1109 1112 1134 1156 1187 2290 2212 2234 2256 2278 3390 3312 3334 3356 3378 4490 4412 4434 4465 4478 5590 5521 5534 5556 5578 6690 6612 6634 6656 6687 9 • Rtus (PSZ) with staged dX do NOT have full integration • DOE 2 says they do • Economizer must throttle back when dX is on . . . Why? • Need to model all modes during each hour OSA High Limit or “changeover” sequence When is it too hot to use economizer? • Mode of Control – Single (OSA only) fixed (snap disc) – Single (OSA only) adjustable (analog) – Differential or Comparative (OSA vs. RA) • Type of Sensor – Dry-bulb measures temperature only – Enthalpy adjusts for humidity – Separate dry-bulb and humidity sensors 14 Dry-Bulb Differential Changeover • Dry-bulb analog OA & RA sensors • Differential changeover logic – Both OA & RA sensors pprovided – NO snap discs • Single changeover OK with aggressive setpoint 15 Differential Changeover • Differential or Comparative Changeover – RA & OSA sensor – Avoids confusion; no guesswork – Adapts to loads; avoids callbacks • How it works – Compares temperature or energy content (enthalpy) of both RA & OSA – Allows economizer if OSA is cooler or has less enthalpy or heat energy depending on sensor – Maximize integration or time both the economizer can function with cooling 16 Dry-bulb Changeover in the West • ARI map shows where evaporative cooling works. • Economizer climates in West (ASHRAE 90.1): – 95% dry – 5% intermediate – 0% humid • Changeover Sensor: – West: dry-bulb – East: enthalpy 17 Enthalpy Sensors See Iowa Humidity Sensor Testing: NBCIP PTR: Duct Mounted Relative Humidity Transmitters. April 2004; Rev. November 2004 www.energy.iastate.edu/Efficiency/Commercial/download_nbcip/PTR_Humidity_Rev.pdf 18 Modeling dX Cooling Economizer in eQUEST • DOE 2.2 will overstate economizer energy savings for Packaged Single Zone (PSZ) and PVVT systems using single stage DX cooling coils. • DOE 2.2 models a fully integrated economizer strategy instead of actual alternating integration. • In actuality, a single-stage dX cooling unit must throttle back the outside air during integrated operation. • In order to simulate an alternating economizer strategy in DOE 2.2 a work around has been developed. – Adjust the high limit to reduce economizer savings – Described in Appendix A of DCV modeling guide 19 High Limit Adjustment – Low Density Occupancies Adjusting DOE 2.2 PSZ from full integration to alternating integration Low Density Occupancies such as offices OAT Balance: OAT High Limit Adjusted High Limit Input, °F Reduction in High Limit, °F 57 52 47 57 52 47 Light Med Heavy Light Med Heavy 75.0 71.3 69.6 68.6 3.7 5.4 6.4 72.5 70.2 69.2 68.2 2.3 3.3 4.3 70.0 69.1 68.2 67.2 0.9 1.8 2.8 67.5 66.5 65.7 64.8 1.0 1.8 2.7 65.0 64.5 64.2 63.7 0.5 0.8 1.3 62.5 62.1 61.7 61.2 0.4 0.8 1.3 60.0 59.8 59.6 59.3 0.2 0.4 0.7 57.5 57.5 57.1 56.7 0.0 0.4 0.8 55.0 55.0 54.8 54.5 0.0 0.2 0.5 Internal loads are characterized as light, medium and heavy. 20 Heavy: Lighting at 2.3 Watts/square foot with high occupancy; Call center Medium: Lighting at 1.7 Watts/square foot; moderate occupancy; open office Light: Lighting at 0.7 Watts/square foot with low density occupancy High Limit Adjustment – High Density Occupancies Adjusting DOE 2.2 PSZ from full integration to alternating integration High Density Occupancies (with increased ventilation) OAT Adjusted High Limit Input Reduction in High Limit 52 47 37 52 47 37 Hi Limit Light Med Heavy Light Med Heavy 75.0 70.7 69.5 67.8 4.3 5.5 7.2 72.5 69.8 69.1 67.9 2.7 3.4 4.6 70.0 69.1 68.4 66.4 0.9 1.6 3.6 67.5 66.7 66.2 64.7 0.8 1.3 2.8 65.0 64.6 64.4 63.6 0.4 0.6 1.4 62.5 62.0 61.7 60.8 0.5 0.8 1.7 60.0 59.7 59.5 58.9 0.3 0.5 1.1 57.5 57.3 57.1 56.4 0.2 0.4 1.1 55.0 54.9 54.7 54.1 0.1 0.3 0.9 Balance: Internal loads are characterized as light, medium and heavy. 21 Heavy: Retail with high lighting or appliance and people density Medium: Moderately full classrooms, meeting rooms, and lecture halls Light: Theatre or assembly with intermittent occupancy, low light levels Development of Economizer High Limit Adjustment Values • Use a simplified bin method to find: – Bin cooling loads and occupied hours – OSA % for 53°F DAT with mechanical cooling – Time of economizer only operation in each bin • Percentage of full integrated economizer delivered by alternating integration • Match those percentage reductions in savings to parametric DOE2 runs. 22 Integration Increases Savings +Internal gains + Solar - Heat loss - Ventilation • Balance Point: cooling not needed • Internal gains are reducing – Efficient lights – LCD monitors Snap Disc 2.50 Cooling Savings kWh/sf • Cooling load: Cooling Savings vs. Changeover Setpoint at Various Building Balance Points (BP) 9 SEER dX, 70% Max OSA Differential & Aggressive Analog Integrated 2.00 1.50 1.00 0.50 0.00 50 55 60 65 70 75 80 Changeover Temp OSA High BP=25 Core BP=32 Strip BP=40 Mod BP=45 Med BP=55 Low BP=70 • Save more with higher OSA changeover – High changeover requires integration – Little savings at snap disc changeover points 23 Impact of Changeover Temperature on % dX PSZ Economizer Savings Impact of Changeover Temperature on dX PSZ Economizer Savings For single stage dX cooling systems, reduce simulated high limit (changeover) by about 2F to 6F (depending on internal loading) below actual in DOE 2.2. Share of Ideal Economizer Savings 100.0% Internal Gain Light W/sf for 70% area 90.0% 80.0% 70.0% 60.0% L: 1.0 50.0% L: 2.0 40.0% L: 3.0 30.0% 20.0% 10.0% 0.0% 45.0 50.0 52.5 55.0 57.5 60.0 62.5 65.0 67.5 70.0 Drybulb Economizer High Limit (changeover) 24 72.5 75.0 Portland Cooling Loads in Economizer Range 60% 12% 50% 10% 40% 8% 30% 6% 20% 4% 2% 10% 0% 0% OAT Bin 25 Percentage of Peak Cooling Capacity 14% 47 .5 50 .0 52 .5 55 .0 57 .5 60 .0 62 .5 65 .0 67 .5 70 .0 72 .5 75 .0 Percent of Occupied Economizer Bin Hours Economizer Bin Cooling Loads Portland, Oregon PDX Econo Bin Hours Light Mech Cool Load Med Mech Cool Load Heavy Mech Cool Load Light / Med / Heavy refer to internal cooling load with Balance point of 57F / 52F / 47F Economizer Time and Share of Ideal by OAT Bin Economizer Alternating Integration Bin Share of Ideal Economizer 100% Time Econo Only or Share of Ideal Light Time Econo Only Med Time Econo Only Heavy Time Econo Only 90% Light Share of Ideal Med Share of Ideal 80% Heavy Share of Ideal 70% For a single stage dX cooling unit, the maximum comfortable (53 DAT) economizer % open is shown as green dotted line. Percent of time for economizer only (no mech cooling) is shown with the per bin share of an ideal economizer cooling that an alternating economizer would provide. 60% 50% 40% 30% 20% 45.0 50.0 55.0 60.0 OAT, deg F 26 Econo Max w/ Mech 65.0 70.0 75.0 Light / Med / Heavy refer to internal cooling load with Balance point of 57F / 52F / 47F Economizer Time–Weighted Effective dT by OAT Bin Economizer Alternating Integration Time-Weighted Econo Effective Sensible dT by individual OAT Bin Effective Sensible Temperature Difference, MAT - DAT, deg F 20.0 Fully Integrated Econo dT 18.0 Econo dT w/ 1 stage cool 16.0 Light Alternate Econo dT Med Alternate Econo dT 14.0 Heavy Alternate Econo dT 12.0 For a single stage dX cooling unit, the maximum comfortable (53 DAT) economizer dT is shown (green dotted) vs fully integrated economizer (orange). Time weighted dT are shown for alternating integration. Differential adjusted for 70% maximum outside air. 10.0 8.0 6.0 4.0 2.0 0.0 45.0 50.0 55.0 60.0 OAT, deg F 27 65.0 70.0 75.0 Light / Med / Heavy refer to internal cooling load with Balance point of 57F / 52F / 47F Economizer Delivered Cooling Sensible Effect by OAT Bin Alternating Integration Delivered Cooling Effect of Ideal Economizer Cooling and Hour Weighted Effect of All Bins 100.0% Percent Ideal Economizer Effect 98.0% Light Cooling Weighted Share 96.0% 94.0% 92.0% Med Cooling Weighted Share 90.0% 88.0% 86.0% Heavy Cooling Weighted Share 84.0% 82.0% 80.0% 47.5 50.0 52.5 55.0 57.5 60.0 62.5 65.0 67.5 70.0 72.5 75.0 High Limit Changeover Setting 28 Light / Med / Heavy refer to internal cooling load with Balance point of 57F / 52F / 47F Sacramento Cooling Loads in Economizer Range 29 Economizer Bin Cooling Loads Sacramento, California 12% 50% 45% 40% 35% 8% 30% 6% 25% 20% 4% 15% 10% 2% 5% 0% 0% SMF Econo Bin Hours Percentage of Peak Cooling Capacity 10% Light Mech Cool Load Med Mech Cool Load Heavy Mech Cool Load 47 .5 50 .0 52 .5 55 .0 57 .5 60 .0 62 .5 65 .0 67 .5 70 .0 72 .5 75 .0 Percent of Occupied Economizer Bin Hours • Climate does NOT matter for adjusted high limit inputs • eQUEST provides climate adjustment • Portland and Sacramento Adjustments all within 0.75°F OAT Light / Med / Heavy refer to internal cooling load with Balance point of 57F / 52F / 47F High Limit Adjustment – Low Density Occupancies Adjusting DOE 2.2 PSZ from full integration to alternating integration Low Density Occupancies such as offices OAT Balance: OAT High Limit Adjusted High Limit Input, °F Reduction in High Limit, °F 57 52 47 57 52 47 Light Med Heavy Light Med Heavy 75.0 71.3 69.6 68.6 3.7 5.4 6.4 72.5 70.2 69.2 68.2 2.3 3.3 4.3 70.0 69.1 68.2 67.2 0.9 1.8 2.8 67.5 66.5 65.7 64.8 1.0 1.8 2.7 65.0 64.5 64.2 63.7 0.5 0.8 1.3 62.5 62.1 61.7 61.2 0.4 0.8 1.3 60.0 59.8 59.6 59.3 0.2 0.4 0.7 57.5 57.5 57.1 56.7 0.0 0.4 0.8 55.0 55.0 54.8 54.5 0.0 0.2 0.5 Internal loads are characterized as light, medium and heavy. 30 Heavy: Lighting at 2.3 Watts/square foot with high occupancy; Call center Medium: Lighting at 1.7 Watts/square foot; moderate occupancy; open office Light: Lighting at 0.7 Watts/square foot with low density occupancy Distinguish Commercial Ventilation Requirements and Modeling: What to do if you aren’t in California! DOE 2.2 – Work-Arounds to Hidden Problems: eQUEST - A half hour to learn; three years to master. 31 Ventilation Rate History 32 Source: Fred Kohloss; ASHRAE Summer Meeting 2003 Health or Stinky Air? • Primary purpose is “acceptable indoor air quality” – Primary unit in testing is “olf” (olfactory unit) • Standard has a purpose to “minimize negative impacts on health” – Difficulty in proving objective healthy concentrations for contaminants of concern in commercial – Second hand smoke major restriction – Most commercial occupancies do not have significant health contaminant issues, with exception of dry cleaning, nail salons, light manufacturing and perhaps retail and warehousing 33 Standard 62.1 Procedures • Ventilation Rate Procedure (Prescriptive Path) – For given occupancy, provide minimum ventilation when occupied • IAQ Procedure – Provide a ventilation and air cleaning strategy that: • Addresses contaminants of concern • Is found acceptable based on survey or measurement – Now requires site specific investigation and monitoring • Natural Ventilation Procedure – Limited to almost always require mixed mode 34 ASHRAE Standard 62.1 Ventilation Rate Procedure • Determine an outside air ventilation rate and provide when occupied • Ventilation now has 2 components – Area ventilation rate – People ventilation rate • These 2 components are used to establish the total or “full” ventilation rate – Full ventilation rate = Area + People – There is NOT a requirement to provide the area rate to unoccupied areas! 35 People + Area Based Rate • Occupancy from – Default tables (ASHRAE 62.1 or code); usually high – Observation or architectural program – Owner information • Most codes set a floor for people basis to 50% of stated table default people densities • Less important to get people accurate if using DCV • Example; Conference Room, 1000 square feet: – Area: 1000 x 0.06 cfm/sf = 60 cfm – People: 50 x 5 cfm/per = 250 cfm – Total = 310 cfm or 26% of 1200 unit or zone cfm 36 Ventilation Codes • Most energy codes require DCV in high density spaces • Most PNW mechanical codes either – Allow ASHRAE 62.1 as an alternate – Or are modeled after 62.1 • Occupancy type lists are generally shorter than ASHRAE; tied to fire occupancies • California is different – Ventilation is maximum of area or people rate • Generally 0.15 cfm/sf area rate • Generally 15 cfm/person people – Requires pre-purge and continuous fan operation – DCV has general 1000 ppm setpoint – CO2 sensor in space with readout required 37 California is Different (of course) Standard: ASHRAE 62.1 38 California Title 24 Requirement (since 2001n) (2008/10 Compliance Manual) People; Area rates Sum Max (DOE 2.2 default) High density cfm per person down to 5 stay at 15 General area: cfm/sf 0.06 0.15 Ventilate when “actually occupied” “Usually occupied” Intermittent fan Short periods (~30 min) Only 5 minutes / hour DCV CR Setpoint Match space (800-1800) Always 1000 ppm DCV Sensors CO2 return air OK; schedule, counters CO2 only, in space, readout, trended if DDC Space purge Not required (recommended 1 hour or 3 air changes if non human contaminants) before occupancy Multiple zone Ventilation efficiency Min for space; Vent at fan Space & Zone OA Specs ASHRAE 62.1 vs CA T24 Area Rate: INF-FLOW/AREA Unoccupied Cfm/sq ft; not wind corrected Enter unoccupied; use INF-SCHEDULE to multiply for occupied 0.0263 + 0.12 = 0.1463 0.0263 x 5.56 = 0.12 People Rate: OA-FLOW/PER (Not: OA-FLOW/AREA) 39 Space: Zone (62.1): CA T24: Infiltration works for area as OSA is OSA for SZ units Prototype Minimum Ventilation • The minimum ventilation requirements used for the prototype models follow ASHRAE 62.12010 Ventilation Rate Procedure. • Ventilation = People Outdoor Air Rate + Area Outdoor Air Rate People Ventilation Requirement (CFM/Person) Area Ventilation Requirement (CFM/SQFT) 10 0.12 Gym 3.75 0.18 Lecture Hall 7.5 0.06 Movie Theater 10 0.06 Movie Theater Lobby 5 0.06 7.5 0.12 Space Type Classroom Retail 40 Understand DOE 2 Limits and Proper Modeling of Unoccupied Fan Operation DOE 2.2 – Work-Arounds to Hidden Problems: eQUEST - A half hour to learn; three years to master. 41 eQUEST Defaults at Work Night Cycle Fan Control Default: • “Stay Off” is default • eQUEST adds 2 hours/day to fan schedule Options: • “Cycle on Any” runs fan full hour on ANY load • No option for – “on” during occupied and – intermittent” during unoccupied 42 • Intermittent with a 24 hour fan schedule is intermittent all the time Solution: Use the Fan Schedule • Hourly outputs analyzed for unoccupied load • Monthly equivalent fan hours determined • Schedules built up for prototypes Not perfect, but closer than “cycle on any” 43 Class room Retail Gym Movie Theater Lecture Hall January 1 3 4 3 2 February 1 2 3 2 2 March 1 2 2 2 1 April 1 2 2 1 1 May 0 1 1 1 0 June 0 0 1 0 0 July 0 0 1 0 0 August 0 0 2 0 0 September 0 0 1 0 0 October 0 1 2 1 0 November 1 2 2 2 1 December 2 2 3 2 1 Longer Run Hours with VFD • Similar process • Lower speed results in longer hours 44 Class room Retail Gym Movie Theater Lecture Hall January 5 All All All All February 2 All All All All March 4 All All All 6 April 3 8 All All 5 May 1 4 6 3 1 June 0 1 4 1 0 July 1 0 5 0 0 August 2 0 8 0 0 September 0 0 5 1 0 October 1 5 7 5 2 November 4 7 All All 5 December All All All All 5 List Issues for Proper VFD Fan Modeling DOE 2.2 – Work-Arounds to Hidden Problems: eQUEST - A half hour to learn; three years to master. 45 FAN EIR-fPLR EIR-fPLR: – Energy Input Ratio – as a function of – Part Load Ratio • Dimensionless – Other formulas or inputs define 100% energy input – Systems finds CFM for the hour 100% 80% Fan Energy Input • FAN-EIR-FPLR Curves eQUEST defaults 60% eQ_FC-DD eQ_FC-IV eQ_VAV-VSD 40% 20% 0% 0% 25% 50% 75% 100% Fan Output • EIR-fPLR curve quickly translates hourly fan output (cfm) to energy input – Does not require complexity of a ductwork model inside DOE2 or TRACE – Allows any separately calculated relationship to be input • Default curves in the system for: – Forward Curve or Air Foil; Discharge Dampers or Inlet Vanes; – Any VSD; VaneAxial 46 Losses occur for each conversion of energy Wire Losses 2% Efficiency Meter Wire Motor Belt Fan System 80% 70% 52% Loss 2% 20% 6% 30% 48% kW 9.65 9.46 7.57 7.14 5.00 4.65 Motor Efficiency: 80% = Losses of 20% Fan Belt Losses 6% Air Flow Overall Fan System Efficiency Multiple Conversions = Multiple Losses Fan Efficiency: 70% = Losses of 30% Meter kW Motor Input kW Motor Shaft kW Fan Shaft kW Air kW = Work Losses Overall system efficiency = [5.0 kW work] / [9.65 kW in] = 52% 47 • Losses occur for each conversion of energy Wire Losses 2% Motor Efficiency: 80% = Losses of 20% Fan Belt Losses 6% Air Flow Overall Fan System Efficiency Multiple Conversions = Multiple Losses Fan Efficiency: 70% = Losses of 30% VSD Efficiency Meter Wire Motor Belt Fan System 48 80% 70% 52% Loss 2% 20% 6% 30% 48% kW 9.65 9.46 7.57 7.14 5.00 4.65 Meter kW Motor Input kW Motor Shaft kW Fan Shaft kW Air kW = Work Losses What is impact of VSD? • The old rule of thumb is added constant losses of 5-10% of peak input • Newer or larger units closer to 2%-3% of peak VFD Efficiency – A Research ? VFD losses must be included in EIR-fPLR curve • • Two available references for VFD efficiencies were used in FanSysCalc They have different part load curves, as shown at right The DOE-OIT method is based on a table published in three references: – – – • 49 USDOE OIT. Ask the clearinghouse: Variable speed drive part-load efficiency. January 2002. Energy Matters. Office of Industrial Technologies, US Department of Energy. http://www.ornl.gov/sci/buildings/20070205_ AuthorsManual_Jan2007.pdf Chan, Tumin. August 2004. "Beyond The Affinity Laws." Engineered Systems Magazine. http://www.esmagazine.com/Archives?issue=65 496 Rooks, JA & Wallace, AK. 2003. Energy efficiency of variable speed drive systems. Pulp and Paper Industry Technical Conference, 2003. The Bernier method uses an equation published in – Bernier, MA & Bourret, B. December 1999. Pumping energy and variable frequency drives. ASHRAE Journal. Compare VFD Efficiency Methods 100.0% VFD Efficiency • 80.0% 60.0% DOE-OIT 40.0% Bernier 20.0% 0.0% 0 50 100 150 Flow gpm Further Reading: Development of a Correlation for System Efficiency of a Variable-Speed Pumping System (ASHRAE 2008) Efficiencies of an 11.2 kW Variable Speed Motor and Drive (ASHRAE 2001) Non-Dimensional Pumping Power Curves for Water Loop Heat Pump Systems (ASHRAE 1999) Utilizing VFD for Building HVAC System Performance (ASHRAE 2008) Variable Flow in Chilled Water Systems-Benefits and Controls (ASHRAE 2006) VSD: 50 Size Matters Sellers, David. A Field Perspective on Engineering. Dec. 18, 2010. http://av8rdas.wordpress.com/2010/12/18/variable-frequence-drive-system-efficiency/ VSD: 51 Vintage Matters Sellers, David. A Field Perspective on Engineering. Dec. 18, 2010. http://av8rdas.wordpress.com/2010/12/18/variable-frequence-drive-system-efficiency/ Simulating Static Pressure Reset in eQUEST/DOE2; TRACE • Temperature reset FAN-EIR-FPLR Curves CCC FanSysCalc vs. eQuest defaults – very easy in wizard 100% • Static Pressure reset • The CCC FanSysCalc tool – is a good source to generate a realistic EIR-fPLR curve 52 80% ccc_Base Fan Input – requires a new – FAN-EIR-fPLR curve 60% ccc_LoSP ccc_ResetSP eQ_FC-DD 40% eQ_VAV-VSD 20% 0% 0% 25% 50% Fan Output 75% 100% Fan Cycling and VSD Control • Each DCV prototype was modeled with three different fan control methods: – constant volume, – fan cycling, and – variable speed drive. • The fan cycling and variable speed drive fan control methods respond to an increase or decrease in space temperature. • Most packaged rooftop units are controlled such that the fan will operate during night time hours to meet heating and cooling loads. 53 Know How to Model DCV DOE 2.2 – Work-Arounds to Hidden Problems: eQUEST - A half hour to learn; three years to master. 54 Demand Controlled Ventilation (DCV) • Idea here is to provide – area ventilation rate when occupied, – then proportion people ventilation rate to actual occupancy • Measure occupancy by: – – – – 55 Carbon dioxide (CO2) concentration Counters or security system Schedule approximation Camera technology Demand Controlled Ventilation – Use CO2 as a proxy for adequate ventilation with CO2 sensors • Odor: ~700 above background • Target 1000 to 1200 ppm • For 2-10 V CO2 sensor where 2 V is 800 ppm, we want damper to start at 4 V or 1100 ppm • Damper is full open at 10 V or 2000 ppm – For smaller areas: • Use occupancy sensors • Use scheduled ventilation 56 DCV Savings M illion Btu's Post ECM Baseline Gym is a great application – Go from 38% average OSA to 15% – Save $2200 per year, mostly heat 0.0 100.0 200.0 300.0 400.0 500.0 Heating Cooling Fans Lights Ocp Lt Unoc/Ext Equipm't Ocp Eq Unoc/Ext M illion Btu's Post ECM Baseline 0.0 Heating Cooling Fans Lights Ocp Lt Unoc/Ext Equipm't Ocp Eq Unoc/Ext 57 100.0 200.0 300.0 400.0 Office saves less, but may pay – Only need 10-15% OSA; might reduce by 5% – Save $153 per year – Save more if base case is over ventilated (typically is 20%) CO2 Sensors • Why are they used? – Energy Savings: • Only when not in OSA economizer mode – Eliminate over-ventilation when occupancy is low – Coordinated with OSA economizer maximizes benefit of ventilation control and savings – Establish transient space occupancy • Alternate methods – Schedules, camera visualization, counters – VOC sensors (if co-related to CO2) 58 CO2 as Proxy for Air Quality • Carbon Dioxide is JUST a proxy – Does not account for other chemicals – Does reflect space occupancy – Is not a “contaminant of concern” • What do CO2 levels mean? – – – – 59 Background outdoors 350 to 450 ppm Equivalent to 15-20 cfm/person: 1000 ppm OSHA limit for exposure > 8 hrs: 5000 ppm Submarines: 7000 normal, 30,000 dive! CO2 Target Is NOT 700 ppm! • DCV CO2 concentration setpoint – Earlier standard called for 700 ppm CO2 over ambient as target level – Ambient at 400 means 1100 ppm setpoint • Actually is based on specific occupancy • Explained well in the 62.1-2007 users manual – Steady state CO2 CR • Concentration lags occupancy – DCV allowed to control for steady state – Pre-purge not required; may be good 60 Find CR for your space • CR is target CO2 – – – – Think OA% “area” & “full”, not minimum Met varies due to activity Large ratio indicates more DCV savings potential Where possible, use actual people & CFM, not defaults! ASHRAE 62.1-2010 Area Type Art Classroom Office - default Office - open Class (age 9+) Retail Sales Grocery Call Center Lecture Class Movie Theater (actual) Conference Restaurant Assembly Rock Concert (dance) 61 Rp Pz 20 5 7 35 15 8 12 65 77 50 70 150 100 sf/p 50 200 143 29 67 125 83 15 13 20 14 7 10 met 1.2 1.2 1.2 1.2 1.5 1.7 1.2 1.1 1.0 1.1 1.4 1.0 2.0 Rs cfm/p cfm/sf 10 5 5 10 7.5 7.5 5 7.5 5 5 5 5 5 0.18 0.06 0.06 0.12 0.12 0.06 0.06 0.06 0.06 0.06 0.18 0.06 0.06 CR ppm 824 874 994 1001 1050 1162 1206 1278 1563 1592 1643 1644 2800 *For all types: area is 1000 square feet, COa = 400 ppm, Ez is 80%, unit cfm 1.2 cfm/sf OA% OA% area full Ratio 19% 40% 2.1 6% 9% 1.4 6% 10% 1.6 13% 49% 3.9 13% 24% 1.9 6% 13% 2.0 6% 13% 2.0 6% 57% 9.1 6% 46% 7.4 6% 32% 5.2 19% 55% 2.9 6% 84% 13.5 6% 58% 9.3 DCV: Step vs Analog Control • Step control: – “full %” when approaching CR or concentration target – Return to “area %” @ point between CR and 400 ppm • Analog control recommended by 62.1 User Manual – Area rate at 400-450 ppm – Area + people (full) rate at CR target ppm – Note difference in damper position vs OSA% • Analog is how DOE 2 models DCV according to people schedule OSA DCV Ventilation Sequence Set Area & Full Positions based on OSA% measurements 40% OApos 30% OSA% OAareaPos @ 400 20% 10% OAfullPos @ AQset 0% 62 0 500 1000 Space/Return CO2 PPM 1500 2000 CR as Indicator of People Concentration • CR good up to typical high density – Curve goes exponential at maximum densities – 200 people per 1000 sf is 5 sf a person – rock concert SRO – This is movie theater or assembly occupancy OSA CO2 CR as indicator of People 1.0 met, 5 cfm/person, 0.06 cfm/sf 50% 200 40% 160 30% 120 20% 80 10% 40 0% 0 63 500 1000 1500 Space/Return CO2 PPM 0 2000 OApos DCV OA% People Linear Control is Quite Conservative • Compare DCV to prescriptive rate – High at lower proportional occupancy – Helps offset lag due to space volume OSA DCV Conservative cf. Ventilation Rate Compare Vent OA% required and DCV OA% provided 50% 200 40% 160 30% 120 20% 80 10% 40 0% 0 500 1000 1500 Space/Return CO2 PPM 64 0 2000 OApos DCV OA% Vent OA% People DCV Integrated Fan Control (DCV-IFC) Yes, ASHRAE Standard 62.1 allows fan cycling – General thinking: commercial fans must be ON during the occupied period – Section 6.2.6.2 of ASHRAE Standard 62.1-2010 allows short-term interruption of ventilation if ventilation levels are maintained on average CO2 PPM as % of Full Design 3.0 hr Avg OA % of prescriptive • • Exceeds design occupancy • Fan Cycling Ventilation (cycles shown to meet ventilation only) Vent OA damper % Design Occupancy 160% 140% Allow ed maximum ventilation increases as OA approaches space temperature 120% • 100% 80% 60% • 40% 20% 65 Note: Startup ventilation compliant w ith 62.1 users manual is typically below prescriptive levels under CO2 sensor Fan operates 35.1% of tim e 5P M 4P M 3P M 2P M 1P M PM 12 AM 11 AM 10 9A M 8A M 0% Approach: -Record CO2 at fan off -Provide % air relative to comfort -Operate time needed to match ventilation rate -Duty cycle if off for 30 minutes with no heat or cool RTU DCV Ventilation Issues 66 Improve ventilation CO2 Transmitter Accuracy Fan cycling Control setup and adjustment Alterations & Code Current RTU Conditions AC-1 Pre-Retrofit Poor Ventilation Wed, Jan 14, 2009 Near & Far sensors in same space (Far adjusted) 2,700 2,400 2,100 1,800 1,500 1,200 900 Fan on PPM Carbon Dioxide Proxy for Air Quality • TAB rare for RTUs • OA minimum often set much too high • Specific study of senior center 600 300 : 00 12 PM 0 1 :0 PM 0 2 :0 PM 0 3:0 PM 0 4:0 Fan On CO2 outside CO2 RA CO2 Space Far - Adj CO2 Space Near CO2 Target • Like here, fan is often in auto position (~40% RTUs) • During January, little daytime fan operation – Heating load offset by internal gains • CO2 concentration almost triple desired level 67 PM 0 5 :0 PM 0 6 :0 PM Note: Fan is off most of the day because heat from occupants met heating load RTU DCV Brings Significant Ventilation Improvements • Fan slows when not heating or cooling, but remains on • CO2 sensor modulates damper to maintain proper ventilation rate AC-1 • Multiple Room CO2 Measurement Divergance Wed, May 27, 2009 8.0 7.0 1,100 6.0 5.0 900 4.0 700 3.0 2.0 500 1.0 300 0 9:0 68 Fan Amps PPM Carbon Dioxide Proxy for Indoor Air Quality 1,300 AM 0.0 A :00 10 M A :00 11 M P :00 12 M Fan Amps CO2 Return Air CO2 Computer Rm adj CO2 Billiard Rm CO2 outside CO2 Target • After retrofit, highest CO2 concentration within target limits. Single return air sensor worked for multiple rooms: – Computer lab – Billiard room Single CO2 Sensor Does It Easiest placement of the sensor is in the return air AC-1 Mon, Jun 15, 2009 69 PPM Carbon Dioxide Proxy for Indoor Air Quality 1,100 8.0 7.0 900 6.0 5.0 700 4.0 3.0 500 Fan Amps Concerns: – Studies suggest putting sensor in the breathing zone (California T24 code required) – When multiple rooms are served by one unit, an imbalance in ventilation quality may occur with uneven occupancy – With VSD, less air throw at the diffuser may reduce ventilation effectiveness. Multiple Room CO2 Measurement Divergance 2.0 1.0 300 0 1:0 PM 0.0 0 2:0 PM 0 3: 0 PM 0 4:0 PM Fan Amps CO2 Return Air CO2 Computer Rm - Adj CO2 Billiard Rm CO2 outside CO2 Target Testing results: • For smaller RTUs, even with one room heavily occupied, return air sensing can meet requirements with a slight ventilation setpoint adjustment • Testing multiple places in one room showed little variation with lower airflow CO2 Transmitter Accuracy Bin Occurance (Bars) 35% 100% 90% 80% 70% 60% 50% 40% 30% 20% 10% 0% 30% 25% 20% 15% 10% 5% 0% 5% 10% 15% 20% 25% 30% 35% Line is % of Units with Worse Accuracy CO2 Transmitter Error @ 1100 ppm 40% +/- error Source: National Building Controls Information Program. PTR. Iowa EC & CEC. June 2009. 70 Source: http://www.energy.iastate.edu/ Efficiency/Commercial/ download_nbcip/PTR_CO2.pdf NBCIP/ Iowa Energy Center Testing No manufacturers had all three samples within specs! • Count on being within 200 ppm, usually high • Many sensors saturate above 1700 ppm • Self calibrating sensors improve persistence Closer Look at Accuracy Impact CO2 Transmitter Error @ 1100 ppm 10 42.5% 37.5% 32.5% 27.5% 22.5% 17.5% 12.5% 7.5% 2.5% 0.0% -2.5% -7.5% -12.5% 0 -17.5% 5 -22.5% Frequency n=45 15 error boundary Source: National Building Controls Information Program. PTR. Iowa EC & CEC. June 2009. Eliminating 3 of 13 manufacturers keeps error within +/- 21% • Sensors are generally high; (mean = + 12%) • Relative accuracy will maintain with self-calibration • Particular manufacturers are at extremes 71 Questions ? Reid Hart, PE rhart@peci.org REFERENCES Hart, R., Price, W., Morehouse, D. (2006). The Premium Economizer: An Idea Whose Time Has Come. In Proceedings of the 2006 ACEEE Summer Study on Energy Efficiency in Buildings. Pacific Grove, CA: ACEEE. Hart, R., Price, W., Taylor, J., Reichmuth, H. & Cherniack, M. (2008). Up on the Roof: From the Past to the Future. In Proceedings of the 2008 ACEEE Summer Study on Energy Efficiency in Buildings. Pacific Grove, CA: [ACEEE] American Council for an EnergyEfficient Economy. Hart, R. (2009). “Premium Ventilation Package Testing: Short-Term Monitoring Report – Task 7.” Portland Energy Conservation, Inc. (PECI) for Bonneville Power Administration (BPA). www.peci.org (Resources, commercial retail). Jacobs, P., Smith, V., & Higgins, C. (2003). Small Commercial Rooftops: Field Problems, Solutions and the Role of Manufacturers. In National Conference on Building Commissioning: May (Vol. 20, p. 22). Maxwell, Gregory, “Product Testing Report: Wall Mounted Carbon Dioxide (CO2) Transmitters” (Iowa Energy Center, June 2009), http://www.energy.iastate.edu/Efficiency/Commercial/download_nbcip/PTR_CO2.pdf. Nassif, N., Kajl, S., and Sabourin, R. (2005). “Ventilation Control Strategy Using the Supply CO 2 Concentration Setpoint.” HVAC&R Research, 11(2), 239–262. 72 73