Cymbal Analog Servo Amplifier Installation Guide November 2011 (Ver. 1.3) www.elmomc.com Notice This guide is delivered subject to the following conditions and restrictions: • This guide contains proprietary information belonging to Elmo Motion Control Ltd. Such information is supplied solely for the purpose of assisting users of the Cymbal servo drive in its installation. • The text and graphics included in this manual are for the purpose of illustration and reference only. The specifications on which they are based are subject to change without notice. • Elmo Motion Control and the Elmo Motion Control logo are trademarks of Elmo Motion Control Ltd. • Information in this document is subject to change without notice. Document no. MAN‐CYMIG (Ver. 1.3) Copyright © 2011 Elmo Motion Control Ltd. All rights reserved. Catalog Number Revision History Ver. 1.0 (Jan. 2008) Initial Release Ver. 1.1 (April 2008) Updated Power Ratings table in Chapter 4 Ver. 1.2 (May 2009) MTCR 05‐009‐54: 3.5.1.3: Added the xx/400 note; A‐1: Added auxiliary power data for CYM 18/400. Ver. 1.3 (Nov. 2011) PR changed to VN‐ Elmo Worldwide Head Office Elmo Motion Control Ltd. 60 Amal St., P.O. Box 3078, Petach Tikva 49516 Israel Tel: +972 (3) 929‐2300 • Fax: +972 (3) 929‐2322 • info‐il@elmomc.com North America Elmo Motion Control Inc. 42 Technology Way, Nashua, NH 03060 USA Tel: +1 (603) 821‐9979 • Fax: +1 (603) 821‐9943 • info‐us@elmomc.com Europe Elmo Motion Control GmbH Hermann‐Schwer‐Strasse 3, 78048 VS‐Villingen Germany Tel: +49 (0) 7721‐944 7120 • Fax: +49 (0) 7721‐944 7130 • info‐de@elmomc.com China Elmo Motion Control Technology (Shanghai) Co. Ltd. Room 1414, Huawen Plaza, No. 999 Zhongshan West Road, Shanghai (200051) China Tel: +86‐21‐32516651 • Fax: +86‐21‐32516652 • info‐asia@elmomc.com Asia Pacific Elmo Motion Control #807, Kofomo Tower, 16‐3, Sunae‐dong, Bundang‐gu, Seongnam‐si, Gyeonggi‐do, South Korea Tel: +82‐31‐698‐2010 • Fax: +82‐31‐698‐2013 • info‐asia@elmomc.com Cymbal Installation Guide MAN-CYMIG (Ver. 1.3) Table of Contents Chapter 1: 1.1. 1.2. 1.3. 1.4. 1.5. Warnings .................................................................................................................... 7 Cautions ..................................................................................................................... 7 Directives and Standards ........................................................................................... 8 CE Mark Conformance ............................................................................................... 8 Warranty Information ............................................................................................... 8 Chapter 2: 2.1. 2.2. 2.3. 2.4. 3.2. 3.3. 3.4. 3.5. 3.6. 3.7. Installation ................................................................................................. 11 Before You Begin ..................................................................................................... 11 3.1.1. Site Requirements .................................................................................... 11 Unpacking the Amplifier .......................................................................................... 11 Mounting the Cymbal .............................................................................................. 12 Connecting the Cables ............................................................................................. 13 3.4.1. Wiring the Cymbal .................................................................................... 13 Cymbal Connection Diagram ................................................................................... 16 3.5.1. Connecting the Power Cables ................................................................... 17 3.5.1.1. Connecting the Motor Cable ................................................... 19 3.5.1.2. Connecting the DC Power ........................................................ 19 3.5.1.3. Connecting the Optional Backup Supply Cable ....................... 22 3.5.2. Control, I/Os and Halls Cable Assemblies ................................................. 24 3.5.3. J2 Control Port .......................................................................................... 25 3.5.3.1. J3 General I/O Port .................................................................. 27 3.5.3.2. J4 Hall’s Signal Port .................................................................. 28 DC Power Supply ..................................................................................................... 29 3.6.1. Powering Up ............................................................................................. 29 3.6.2. Initializing the System ............................................................................... 29 Heat Dissipation ....................................................................................................... 29 3.7.1. Cymbal Thermal Data ............................................................................... 30 3.7.2. Heat Dissipation Data ............................................................................... 30 3.7.3. How to Use the Charts .............................................................................. 32 Chapter 4: 4.1. 4.2. 4.3. Introduction ................................................................................................. 9 Product Description ................................................................................................... 9 Standard Features ..................................................................................................... 9 Fault Protection ....................................................................................................... 10 How to Use this Guide ............................................................................................. 10 Chapter 3: 3.1. Safety Information ....................................................................................... 6 Servo Control Operation ............................................................................. 33 Cymbal Connected to DC Motors ............................................................................ 33 Current Command Input ......................................................................................... 33 External Current Limit ‐ Continuous (ECLC) ............................................................. 33 4 Cymbal Installation Guide Table of Contents MAN-CYMIG (Ver. 1.3) 4.4. 4.3.1. External Voltage ........................................................................................ 33 4.3.2. External Resistor ....................................................................................... 34 4.3.3. External Current Limit ‐ Peak (ECLP) ......................................................... 34 4.3.4. External Voltage ........................................................................................ 34 4.3.5. External Resistor ....................................................................................... 34 4.3.6. Latch Mode (LM) ....................................................................................... 34 Status Indications .................................................................................................... 35 Chapter 5: 5.1. 5.2. 5.3. Technical Specifications .............................................................................. 36 General Specifications ............................................................................................. 36 Dimensions .............................................................................................................. 38 Compliance with Standards ..................................................................................... 39 5 Cymbal Installation Guide 6 MAN-CYMIG (Ver. 1.3) Chapter 1: Safety Information In order to achieve the optimum, safe operation of the Cymbal servo drives, it is imperative that you implement the safety procedures included in this installation guide. This information is provided to protect you and to keep your work area safe when operating the Cymbal as well as the accompanying equipment. Please read this chapter carefully before you begin the installation process. Before you start, ensure that all system components are connected to earth ground. Electrical safety is provided through a low‐resistance earth connection. Only qualified personnel may install, adjust, maintain and repair the servo drive. A qualified person has the knowledge and authorization to perform tasks such as transporting, assembling, installing, commissioning and operating motors. The Cymbal servo drives contain electrostatic‐sensitive components that can be damaged if handled incorrectly. To prevent any electrostatic damage, avoid contact with highly insulating materials, such as plastic film and synthetic fabrics. Place the product on a conductive surface and ground yourself in order to discharge any possible static electricity build‐up. To avoid any potential hazards that may cause severe personal injury or damage to the product during operation, keep all covers and cabinet doors shut. The following safety symbols are used in this manual: Warning: This information is needed to avoid a safety hazard, which might cause bodily injury. Caution: This information is necessary for preventing damage to the product or to other equipment. www.elmomc.com Cymbal Installation Guide Safety Information MAN-CYMIG (Ver. 1.3) 1.1. Warnings • To avoid electric arcing and hazards to personnel and electrical contacts, never connect/disconnect the servo drive while the power source is on. • Power cables can carry a high voltage, even when the motor is not in motion. Disconnect the Cymbal from all voltage sources before it is opened for servicing. • The Cymbal servo drives contain grounding conduits for electric current protection. Any disruption to these conduits may cause the instrument to become hot (live) and dangerous. • After shutting off the power and removing the power source from your equipment, wait at least 1 minute before touching or disconnecting parts of the equipment that are normally loaded with electrical charges (such as capacitors or contacts). Measuring the electrical contact points with a meter, before touching the equipment, is recommended. 1.2. Cautions • The Cymbal servo drives contain hot surfaces and electrically‐charged components during operation. • The maximum DC power supply connected to the instrument must comply with the parameters outlined in this guide. • When connecting the Cymbal to an approved 12 to 95 VDC auxiliary power supply, connect it through a line that is separated from hazardous live voltages using reinforced or double insulation in accordance with approved safety standards. • Before switching on the Cymbal, verify that all safety precautions have been observed and that the installation procedures in this manual have been followed. www.elmomc.com 7 Cymbal Installation Guide Safety Information MAN-CYMIG (Ver. 1.3) 1.3. 8 Directives and Standards The Cymbal conforms to the following industry safety standards: Safety Standard Item In compliance with UL 508C Power Conversion Equipment In compliance with UL 840 Insulation Coordination, Including Clearance and Creepage Distances of Electrical Equipment In compliance with UL 60950‐1 (formerly UL 1950) Safety of Information Technology Equipment, Including Electrical Business Equipment In compliance with EN 60204‐1 Low Voltage Directive, 73/23/EEC The Cymbal servo drives have been developed, produced, tested and documented in accordance with the relevant standards. Elmo Motion Control is not responsible for any deviation from the configuration and installation described in this documentation. Furthermore, Elmo is not responsible for the performance of new measurements or ensuring that regulatory requirements are met. 1.4. CE Mark Conformance The Cymbal servo drives are intended for incorporation in a machine or end product. The actual end product must comply with all safety aspects of the relevant requirements of the European Safety of Machinery Directive 98/37/EC as amended, and with those of the most recent versions of standards EN 60204‐1 and EN 292‐2 at the least. According to Annex III of Article 13 of Council Directive 93/68/EEC, amending Council Directive 73/23/EEC concerning electrical equipment designed for use within certain voltage limits, the Cymbal meet the provisions outlined in Council Directive 73/23/EEC. The party responsible for ensuring that the equipment meets the limits required by EMC regulations is the manufacturer of the end product. 1.5. Warranty Information The products covered in this manual are warranted to be free of defects in material and workmanship and conform to the specifications stated either within this document or in the product catalog description. All Elmo drives are warranted for a period of 12 months from the time of installation, or 18 months from time of shipment, whichever comes first. No other warranties, expressed or implied — and including a warranty of merchantability and fitness for a particular purpose — extend beyond this warranty. www.elmomc.com Cymbal Installation Guide 9 MAN-CYMIG (Ver. 1.3) Chapter 2: Introduction This Installation Guide is intended for design engineers who are integrating Elmo Motion Control Cymbal servo amplifiers into a machine. 2.1. Product Description The Cymbal series of servo amplifiers is designed to operate in the current mode controlling permanent‐magnet trapezoidal brushless motor and DC brush motor. The Cymbal exhibits “the highest density of power and intelligence” and can deliver up to 11.3 kW of continuous power or 13.6 kW of peak power in a most compact and efficient package. The Cymbal operates from a DC power source in the range from 12 to 195 VDC. The Power stage of the Cymbal is fully isolated from other sections of the Cymbal, such as the control stage and the heatsink. This contributes very significantly to the safety and the EMI immunity of the Cymbal. In addition it simplifies the requirements of the DC power supply used to power the DC bus of the Cymbal and allows also the operation with a non‐isolated DC power source. The Cymbal incorporates full custom mixed analog/digital ICs and a hybrid power stage. The basic configuration is a current mode amplifier targeting the OEM market. As such, no trimmers are used in the basic version. In addition to its compliance with relevant MIL standards, the Cymbal amplifier also meets UL 508C and the relevant CE regulations. The Cymbal power stage is implemented on ceramic substrates. This design enables very high thermal conductivity, high current carrying capacity, improved EMC and good mechanical strength. The control section is implemented by dedicated custom ICs that contribute to enhanced performance and reliability. 2.2. Standard Features • Operates in current mode • Internal DC‐to‐DC converter, which allows for operation from a single supply • Zero dead‐band • Excellent linearity • One differential input • Motor current monitor • Current gain change for low inductance motors • Remote current gain control • Status indication and remote control functions by four open collector transistors • External continuous and peak current‐limit adjustments • Package: plated‐aluminum base plate, plastic housing, UL 94V0 recognized • Ultra‐lightweight of 700 grams (24.7 oz) www.elmomc.com Cymbal Installation Guide Introduction MAN-CYMIG (Ver. 1.3) 2.3. Fault Protection Built‐in protection against possible fault conditions, including: • Shorts between the outputs or between each output and the power input/return • Overheating • Undervoltage/overvoltage • Failure of internal power supplies • Latch mode for each protective feature 2.4. How to Use this Guide Installation is the first step in integrating and operating the Elmo Cymbal servo amplifiers. After carefully reading the safety instructions in the first chapter, the following chapters provide you with installation instructions as follows: • Chapter 3, Installation, provides step‐by‐step instructions for unpacking, mounting and connecting the Cymbal. • Chapter 4, Servo Control Operation, explains how to control the operation of the servo amplifier. • Chapter 5, Technical Specifications, lists all the drive ratings and specifications. www.elmomc.com 10 Cymbal Installation Guide 11 MAN-CYMIG (Ver. 1.3) Chapter 3: 3.1. Installation Before You Begin 3.1.1. Site Requirements You can guarantee the safe operation of the Cymbal by ensuring that they are installed in an appropriate environment. Feature Value Ambient operating temperature 0 °C to 50 °C (32 °F to 122 °F) Maximum non‐condensing humidity 90% Operating area atmosphere No flammable gases or vapors permitted in area Note: Models for extended environmental conditions are available. Caution: The Cymbal dissipates its heat by convection. The maximum ambient operating temperature of 0 °C to 50 °C (32 °F to 122 °F) must not be exceeded. 3.2. Unpacking the Amplifier To unpack the Cymbal: 1. Carefully remove the servo amplifier from the box and the Styrofoam. 2. Check the amplifier to ensure that there is no visible damage to the instrument. If any damage has occurred, report immediately to the carrier that delivered your amplifier. 3. To ensure that the Cymbal you have unpacked is the appropriate type for your requirements, find the part number sticker on the side of the product: The P/N gives the type designation as follows: 4. Verify that the Cymbal type is the one that you ordered, and ensure that the voltage meets your specific requirements. www.elmomc.com Cymbal Installation Guide Installation MAN-CYMIG (Ver. 1.3) 3.3. Mounting the Cymbal The Cymbal has been designed for Wall Mount along the back (it can also be mounted horizontally on a metal surface) M5 socket head cap screws, one through each opening in the heatsink, are used to mount the Cymbal (see the diagram below). For full power output capability the Cymbal is designed to be mounted on an external heatsink. It is highly recommended that the wall on which the Cymbal is mounted will have heat dissipation capabilities. The Cymbal at “free air convection” (without an additional heatsink) can dissipate around 12 W to 15 W. Figure 1: Mounting the Cymbal www.elmomc.com 12 Cymbal Installation Guide Installation MAN-CYMIG (Ver. 1.3) 3.4. Connecting the Cables 3.4.1. Wiring the Cymbal Once the Cymbal is mounted, you are ready to wire the device. Proper wiring, grounding and shielding are essential for ensuring safe, immune and optimal servo performance of the Cymbal. Caution: Follow these instructions to ensure safe and proper wiring: • Use twisted pair shielded cables for control, feedback and communication connections. For best results, the cable should have an aluminum foil shield covered by copper braid, and should contain a drain wire. The drain wire is a non‐insulated wire that is in contact with parts of the cable, usually the shield. It is used to terminate the shield and as a grounding connection. • The impedance of the wire must be as low as possible. The size of the wire must be thicker than actually required by the carrying current. A 24, 26 or 28 AWG wire for control and feedback cables is satisfactory although 24 AWG is recommended. • Use shielded wires for motor connections as well. If the wires are long, ensure that the capacitance between the wires is not too high: C < 30 nF is satisfactory for most applications. • Keep all wires and cables as short as possible. • Keep the motor wires as far away as possible from the feedback, control and communication cables. • Ensure that in normal operating conditions, the shielded wires and drain carry no current. The only time these conductors carry current is under abnormal conditions, when electrical equipment has become a potential shock or fire hazard while conducting external EMI interferences directly to ground, in order to prevent them from affecting the drive. Failing to meet this requirement can result in drive/controller/host failure. • After completing the wiring, carefully inspect all wires to ensure tightness, good solder joints and general safety. www.elmomc.com 13 Cymbal Installation Guide Installation MAN-CYMIG (Ver. 1.3) 14 Figure 2: Cymbal Connection Diagram www.elmomc.com Cymbal Installation Guide Installation 15 MAN-CYMIG (Ver. 1.3) Type Function Port Barrel Connector + M6 Spring Washer + M6 Nut Power VP+, VN‐ Motor M1, M2, M3 Ground Barrel Connector + M5 Flat Washer + M5 Spring Washer + M5 screw Connector Location PE, PE, PE, PE PE PE Table 1: Power Connectors on the Cymbal Type Function Port Connector Location 15‐Pin D‐Sub female Halls signals J4 9‐Pin D‐Sub female Inputs, Outputs (IO) J3 J3 Female: I/O J4 Female: Halls signals Table 2: Halls signals and I/O Connectors on the Cymbal Type Function Port Connector Location 9‐Pin D‐Sub male Backup Supply J1 15‐Pin High Density D‐Sub male Control J2 J1 Male: Optional Backup Supply J2 Male: logic Table 3: Controls and Backup Connectors on the Cymbal www.elmomc.com Cymbal Installation Guide Installation MAN-CYMIG (Ver. 1.3) 3.5. 16 Cymbal Connection Diagram Figure 3: Cymbal Connection Diagram www.elmomc.com Cymbal Installation Guide Installation 17 MAN-CYMIG (Ver. 1.3) 3.5.1. Connecting the Power Cables The main power connector located at the bottom of the Cymbal, as follows: Pin Function Cable Pin Positions VP+ Pos. Power input Power VN‐ Neg. Power input Power PE Protective earth Power PE Protective earth AC Motor Cable DC Motor Cable Motor Motor M1 Motor phase Motor N/C M2 Motor phase Motor Motor M3 Motor phase Motor Motor PE PE PE PE Note: When connecting several motors, all must be wired in an identical manner. Table 4: Connector for Main Power and Motor Cables www.elmomc.com Cymbal Installation Guide Installation MAN-CYMIG (Ver. 1.3) 18 M6 nut (available with the drive) M6 spring washer M5 screw Barrel connector M5 spring washer Barrel connector M5 flat washer Step 1: PE Connection M5 screw Barrel connector M5 spring washer M5 flat washer Step 2: Power and Motor Connection M6 nut (available with the drive) M6 spring washer Barrel connector Table 5: Connecting the Main Power and Motor Cables Note: PE connection can be accomplished also by attaching the Cymbal to ground surface. www.elmomc.com Cymbal Installation Guide Installation MAN-CYMIG (Ver. 1.3) 3.5.1.1. Connecting the Motor Cable Connect the motor power cable to the M1, M2, and M3 terminals of the main power connector and the fourth wire to the PE (Protective Earth) on the heatsink (see diagram above). Notes for connecting the motor cables: • For best immunity, it is highly recommended to use a shielded (not twisted) cable for the motor connection. A 4‐wire shielded cable should be used. The gauge is determined by the actual current consumption of the motor. • Connect the shield of the cable to the closest ground connection at the motor end. • Connect the shield of the cable to the PE terminal on the heatsink. • Be sure that the motor chassis is properly grounded. • To close the motor cable into the drive, use the barrel connector, M6 spring washer and M6 nut (in the drive). The required torque is 3 to 4 Nm. • To close the PE wire into the drive, use the barrel connector, M5 flat washer, M5 spring washer and M5 screw to the heatsink. The required torque is 3 to 4 Nm. • Use flex wire 6/8/10 AWG to barrel connector. Figure 4: AC Motor Power Connection Diagram 3.5.1.2. Connecting the DC Power The Power stage of the Cymbal is fully isolated from other sections of the Cymbal, such as the control stage and the heatsink. This contributes very significantly to the safety and the EMI immunity of the Cymbal. In addition it simplifies the requirements of the DC power supply used to power the DC bus of the Cymbal and allows also the operation with a non‐isolated DC power source. 3.5.1.2.a Operation with an Isolated DC power Supply The PE (Protective Ground of the AC network) is connected to the VN‐ terminal (the Negative Power Input terminal). www.elmomc.com 19 Cymbal Installation Guide Installation MAN-CYMIG (Ver. 1.3) 20 Figure 5: Isolated DC Power Supply In this case the isolation is achieved by the isolation transformer. It is highly recommended to connect the network PE to the Return (negative terminal) of the Power Supply. Figure 6: Isolated Power Supply In this case the isolation is achieved by using a battery. It is highly recommended to connect the PE to the Return (negative terminal) of the Power Supply. 3.5.1.2.b Operation with a Non‐Isolated DC power Supply: The PE (Protective Ground of the AC network) must not be connected to the Negative Power Input (the VN‐ terminal) of the Cymbal. www.elmomc.com Cymbal Installation Guide Installation 21 MAN-CYMIG (Ver. 1.3) Figure 7: Non‐Isolated DC Power Supply The Power Supply is directly connected to the AC line (The AC must be limited to 135 VAC not to exceed the max 190 VDC in case of 200 VDC drive). The network PE must not be connected to the Return of the Power Supply. Figure 8: Non‐Isolated DC Power Supply The Power Supply is directly connected to the AC line through an Autotransformer. The network PE must not be connected to the Return of the Power Supply. Caution: Connecting the PE to the VN‐ with a non‐ isolated power supply will cause damages to the system (Any component that is connected to the system might be damaged). www.elmomc.com Cymbal Installation Guide Installation MAN-CYMIG (Ver. 1.3) Notes for connecting the DC power supply: • Be aware: The Cymbal can operate from either an: isolated DC power supply or non‐isolated DC power supply • For best immunity, it is highly recommended to use twisted cables for the DC power supply cable. A 3‐wire shielded cable should be used. The gauge is determined by the actual current consumption of the motor. • Connect both ends of the cable shield to the closest ground connection, one end near the power supply and the other end to the PE terminal on the Cymbal’s heatsink. • For safety reasons connect the VN‐ of the power supply to the closest ground connection. • To close the power supply cable into the drive, use the barrel connector, M6 spring washer and M6 nut (in the drive). The required torque is 3 to 4 Nm. • To close the PE wire into the drive, use the barrel connector, M5 flat washer, M5 spring washer and M5 screw to the heatsink. The required torque is 3 to 4 Nm. 3.5.1.3. Connecting the Optional Backup Supply Cable Power to the Cymbal is provided by a 12 to 195 VDC source (depending on model type). A “smart” control‐supply algorithm enables the Cymbal to operate with the power supply only, with no need for an auxiliary supply voltage. If backup functionality is required for storing control parameters in case of power‐outs, an external 12 to 195 VDC power supply can be connected, providing maximum flexibility and optional backup functionality when needed. Note: In the 400 V product line (CYM xx/400), there is no internal connection to enable the main input to power the internal SMPS for low logic voltages. Therefore, a 24 VDC auxiliary power supply must be connected in order to activate the 400 V drive’s internal SMPS. For the xx/400 model, the 24 VDC auxiliary power supply can also carry out the backup functionality described above. To connect the backup supply to the Auxiliary port, use the Cymbal's J1 connector (Back up supply connector). Remember, you are working with DC power so be sure to exercise caution. Notes for backup supply connections: • Use a 24 AWG twisted pair shielded cable. The shield should have copper braid. • The source of the backup supply must be isolated. • For safety reasons, connect the return of the backup supply source to the closest ground. • Connect the cable shield to the closest ground near the power source. • Before applying power, first verify the polarity of the connection. www.elmomc.com 22 Cymbal Installation Guide Installation MAN-CYMIG (Ver. 1.3) Pin Signal Function J1‐9 Backup+ Supply +VDC backup supply J1‐8 Backup‐ Supply Return (common) of the backup supply 23 Pin Position J1 Male Table 6: Backup Cable Plug Figure 9: Backup Supply Connection Diagram Note: The return of the backup supply must not be connected to PE, as such a connection can damage the drive. “Smart” Control Supply Options Internal DC‐to‐DC converter that allows operation from DC power (no need for auxiliary external supply for normal operation). 12 to 195 VDC supply for backing up the control parameters if DC power is shut off. www.elmomc.com Cymbal Installation Guide Installation 24 MAN-CYMIG (Ver. 1.3) 3.5.2. Control, I/Os and Halls Cable Assemblies The Cymbal features easy‐to‐use D‐Sub type connections for all Control, I/Os and halls cables. Below are instructions and diagrams describing how to assemble these cables. • Use 24, 26 or 28 AWG twisted‐pair shielded cables (24 AWG cable is recommended). For best results, the shield should have aluminum foil covered by copper braid. • Use only a D‐Sub connector with a metal housing. • Attach the braid shield tightly to the metal housing of the D‐type connector. • On the motor side connections, ground the shield to the motor chassis. • On controller side connections, follow the controller manufacturer’s recommendations concerning the shield. Metal Housing Make sure that the braid shield is in tight contact with the metal housing Figure 10: Control, I/Os and Halls Cable Assemblies Note: All D‐Sub type connectors, used with the Cymbal, should be assembled in this way. www.elmomc.com Cymbal Installation Guide Installation MAN-CYMIG (Ver. 1.3) 3.5.3. 25 J2 Control Port Port J2 has a 15‐pin High‐Density D‐Sub male connector. When assembling this Control cable, follow the instructions in Section 3.5.2 Control, I/Os and Halls Cable Assemblies using a 15‐pin High‐ Density metal case D‐Sub female cable connector (socket). Pin Signal Function Description 1 ANLRET Return Analog Return signal 2 CREF‐ Current Command negative Negative input of a differential amplifier. Current Command positive Positive input of a differential amplifier: 3 CREF+ Pin Location Same specification as in pin J2/3. Input operating voltage range: ±10 V Maximum input voltage: ±20 V Maximum common mode voltage: ±6 V Differential input impedance: 40 kΩ 4 GAIN Current gain change J2 Male 15‐Pin High‐Density D‐Sub Shorting this pin to LMRET pin (J2/10) reduces The proportional gain of the current loop by 70%. 5 LATCH Latch mode Latch mode input. For more details see the Latch Mode (LM) section in Chapter 4. 6 CMRET Return Current monitor (CM) signal return. 7 ECLRET Return Current limit signals return. 8 ECLRET Return Current limit signals return. 9 GAINRET Return Return for Gain signal 10 LMRET Return Return for Latch Mode signal. 11 CM Current monitor Analog output with a scale of ±3.9 V for ± Ip. Output resistance: 1 kΩ www.elmomc.com Cymbal Installation Guide Installation MAN-CYMIG (Ver. 1.3) Pin Signal Function Description 12 External current limit peak External voltage scales down the rated value. 13 14 ECLP ECLC EN+ External current limit continuous Enable + Pin Location Voltage range: 0 V to 3.75 V (3.75 V = rated Ip) External voltage scales down the rated value. Voltage range: 0 V to 3.75 V (3.75 V = rated Ic) Positive voltage input of the “Amplifier Enable” function. To enable operation of the amplifier, the optocoupler must be energized by applying voltage between this pin (+) and pin J2/15 (‐). The optocoupler is isolated from the amplifier. “OFF” voltage: 0 V < Vin < 1 V. “ON” voltage: 2.5 V < Vin < 10 V, 5 V typically with current consumption 2.5 mA. 15 EN‐ Enable ‐ Negative voltage input of “Amplifier Enable” function. Optocoupler is isolated from the amplifier. For details, see pin J2/14. Table 7: J2, Control Connector Cable‐ Pin Assignments Note: All of the XXRETs are shorted internally. www.elmomc.com 26 Cymbal Installation Guide Installation MAN-CYMIG (Ver. 1.3) 3.5.3.1. 27 J3 General I/O Port Port J3 has a 9‐pin D‐Sub female connector. When assembling this I/O cable, follow the instructions in Section 3.5.2 Control, I/Os and Halls Cable Assemblies using a 9‐pin a metal case D‐Sub male connector (plug). Pin Signal Function Description 1 AOK Amplifier OK When the amplifier under normal operating conditions, this output is in the “active low“ state. When a failure occurs, this output is changed to the “open” state. The optocoupler is an isolated, open collector NPN type. Maximum voltage = 30 V Maximum current = 8 mA “On” voltage: V OUT(On) < 0.8 V 2 SO1 Status output 1 Status indication output 1. Specification same as in pin J3/1. Status output 2 Status indication output 2. Specification same as in pin J3/1. 3 SO2 4 SO3 Status output 3 Status indication output 3. Specification same as in pin J3/1. 5 EN+ Enable + “Amplifier Enable” function. To enable operation of the amplifier, the optocoupler must be energized by applying voltage between this pin (+) and pin J3/6 (‐). The optocoupler is isolated from the amplifier. “OFF” voltage: 0 V < Vin < 1 V. “ON” voltage: 2.5 V < Vin < 10 V, 5 V typically with current consumption 2.5 mA. 6 EN‐ Enable ‐ 7 SORET Status output return Negative voltage input of “Amplifier Enable” function. Optocoupler is isolated from the amplifier. For details, see pin J3/5. Status output common AOK, SO1, SO2, SO3. Isolated from circuit common. 8 SORET Status output return Status output common AOK, SO1, SO2, SO3. Isolated from circuit common. 9 SORET Status output return Status output common AOK, SO1, SO2, SO3. Isolated from circuit common. Pin Position J3 Female 9‐Pin Female Table 8: J3 I/O Cable ‐ Pin Assignments Note: Amplifier enable (EN+, EN‐) can be enabled from J2 or J3. www.elmomc.com Cymbal Installation Guide Installation MAN-CYMIG (Ver. 1.3) 3.5.3.2. J4 Hall’s Signal Port Port J4 is a 15‐pin D‐Sub female connector. When assembling this cable, follow the instructions in Section 3.5.2 Control, I/Os and Halls Cable Assemblies using a 15‐pin a metal case D‐Sub male connector (plug). Pin Signal Function Description 1 HALL+15V +15 V Hall supply voltage:15 V ± 10% at 30 mA +15 V supply voltage for Hall sensors. Output current: maximum of 30 mA. 2 HALL+ 5V +5 V Hall supply voltage: 5 V ± 10% at 30 mA +5 V supply voltage for Hall sensors. Output current: maximum of 30 mA. 3 HARET Hall supply voltage return Return used only for Hall supply. 4 HARET Hall supply voltage return Return used only for Hall supply. 5 HA Hall A input Logic levels: TTL Maximum input voltage: 15 VDC. 6 HB Hall B input Logic levels: TTL Maximum input voltage: 15 VDC. 7 HC Hall C input Logic levels: TTL Maximum input voltage: 15 VDC. 8 N.C. 9 N.C. 10 N.C. 11 N.C. 12 N.C. 13 N.C. 14 N.C. 15 N.C. Pin Position J4 Female 15‐Pin Female Table 9: J4 Halls Cable ‐ Pin Assignments www.elmomc.com 28 Cymbal Installation Guide Installation MAN-CYMIG (Ver. 1.3) 3.6. DC Power Supply The DC power supply can be at any voltage in the range defined in the technical specifications (Chapter 5 of this guide). The supply source must comply with the safety aspects of the relevant requirements, in accordance with the most recent version of the standard EN60950 or equivalent Low Voltage Directive Standard, all according to the applicable over‐voltage category. If the power source to the power supply is the AC line (through an isolated or a non‐ isolated transformer), safety margins must be considered, in order to avoid activating the undervoltage/overvoltage protection due to line variations and/or voltage drop under load. In addition to the above, the transformer must comply with the safety aspects of the relevant requirements in accordance with the most recent version of the standard EN 60742 (Isolating and Safety Isolating Transformers). The nominal DC bus voltage should be in the following range: 1.2 Vdcmin < Vdc < 0.9 Vdcmax Where: Vdcmin is the minimum DC bus Vdcmax is the maximum DC bus The transformer power should be calculated such that it will be able to deliver power to the amplifier (including peak power) without significant voltage drops. The power supply should be located as close as possible to the amplifier. While driving high‐ inertia loads, the power supply must be equipped with a shunt regulator; otherwise, the amplifier will be disabled whenever the capacitors are charged above the maximum voltage, during motor break down. 3.6.1. Powering Up After the Cymbal is connected to its devices, the Cymbal is ready to be powered up. Caution: Before applying power, ensure that the DC supply is within the specified range and that the proper plus‐minus connections are in order. 3.6.2. Initializing the System After the Cymbal has been connected and mounted, the system must be set up and initialized. 3.7. Heat Dissipation For full power output capability the Cymbal is designed to be mounted on an external heatsink. It is highly recommended that the “Wall” on which the Cymbal is mounted will have heat dissipation capabilities. The Cymbal at “free air convection” (without an additional heatsink) can dissipate around 12 W for 40 °C ambient temperature and not exceeding 80 °C on the heatsink. When “Free Air Convection” is sufficient for the application it is recommended to leave approximately 10 mm of space between the Cymbal's heatsink and any other assembly. www.elmomc.com 29 Cymbal Installation Guide Installation MAN-CYMIG (Ver. 1.3) 3.7.1. Cymbal Thermal Data • Free air convection thermal resistance (θ): Approximately 3.6 to 4 °C/W. • Thermal time constant: Approximately 40 minutes/ 2400 seconds (thermal time constant means that the Cymbal will reach 2/3 of its final temperature after 4 minutes). • Self heat dissipation capability (no external heatsink): 12 W for 40 °C/W temperature rise. • Shut‐off temperature: 86 °C to 88 °C (measured on the heatsink). • The thermal resistance when connecting to an external heat sink: 30 The surface of the external heatsink is 50 μm: 0.18 °C/W. Thermal conductive compound. By proper Smearing of the surface a significant improvement of the thermal resistance is achieved: 0.13 °C/W 3.7.2. Heat Dissipation Data Heat Dissipation is shown in graphically below: Power Dissipation 60V series 100 90 80 Power Dissipation (W) 70 12VDC 20VDC 30VDC 40VDC 50VDC 56VDC 60 50 40 30 Heatsink Required 20 10 Standard 40 °C Ambient Temp. 0 0 12 20 30 40 50 60 70 80 90 Heatsink not Required Motor's Current (Ampere) www.elmomc.com Cymbal Installation Guide Installation MAN-CYMIG (Ver. 1.3) 31 Power Dissipation 100V series 120 Power Dissipation (W) 100 80 20VDC 40VDC 60VDC 80VDC 96VDC 60 40 20 Heatsink Required Standard 40 °C Ambient Temp. 0 0 8.3 16.7 25.0 33.3 41.7 50.0 58.3 66.7 75.0 Heatsink not Required Motor's Current (Ampere) www.elmomc.com Cymbal Installation Guide Installation MAN-CYMIG (Ver. 1.3) 32 Power Dissipation 200V series 250 Power Dissipation (W) 200 40VDC 80VDC 120VDC 160VDC 196VDC 150 100 50 Heatsink Required 0 0 6.7 13.3 20.0 26.7 33.3 40.0 46.7 53.3 60.0 Heatsink not Required Motor's Current (Ampere) 3.7.3. How to Use the Charts The charts above are based upon theoretical worst‐case conditions. Actual test results show 30% to 50% better power dissipation. To determine if your application needs a heatsink: 1. Allow maximum heatsink temperature to be 80°C or less (shunt down is 6 °C to 8 °C higher). 2. Determine the ambient operating temperature of the Cymbal as ≤ 40 °C. 3. Calculate the allowable temperature increase as follows: For an ambient temperature of 40°C, ΔT= 80 °C – 40 °C = 40 °C 4. Use the chart to find the actual dissipation power of the drive. Follow the voltage curve to the desired output current and then find the dissipated power. 5. If the dissipated power is below 12 W the Cymbal needs no additional cooling. Note: The chart above shows that no heatsink is needed when the heatsink temperature is 80 °C, ambient temperature is 40 °C and heat dissipated is 4 W. www.elmomc.com Cymbal Installation Guide 33 MAN-CYMIG (Ver. 1.3) Chapter 4: Servo Control Operation 4.1. Cymbal Connected to DC Motors In order to connect the Cymbal to a DC motor, connect Hall A (J4 pin 5 of the drive to Hall return (J4 pin 3 of the drive). The motor should be connected to M2, M3. 4.2. Current Command Input The Cymbal has a single differential input. The input operating voltage range is ±10 V, meaning that a 10 V signal will result in a fully rated peak current. The current limit circuits will override this signal if the peak duration exceeds 2.7 seconds and/or the required current exceeds the values set by the ECLC and ECLP signals. If the input command voltage exceeds 10 V, input scaling must be implemented by adding a pair of external resistors, according to the following formula: Rin (KΩ) = (5.33 * Vin) – 53.6 Be careful not to apply input voltage above the maximum allowed input voltage as this will cause the input operational amplifier to operate beyond its limits (±20 V) and in extreme cases, may even damage it. 4.3. External Current Limit - Continuous (ECLC) The continuous current limit of the Cymbal amplifiers can be scaled down by an external voltage or by an external resistor connected from pin J2/13 (ECLC) to pin J2/8 (ECLRET). 4.3.1. External Voltage IC(new) = VECLC 3.75V * Ic(nom) An external positive voltage (0 to 3.75 V) to terminal J2/13 (ECLC) in reference to terminal J2/8 (ECLRET) will control the continuous current limit from zero to Ic (nom). The voltage is internally clamped to 3.75 V whenever the external VECLC is greater than 3.75 V. The external voltage source must be able to source/ sink at least ±0.2 mA. The maximum absolute VECLC allowed to be connected is 5 V. www.elmomc.com Cymbal Installation Guide Servo Control Operation MAN-CYMIG (Ver. 1.3) 4.3.2. External Resistor Connect an external resistor between terminal J2/13 (ECLC) and terminal J2/8 (ECLRET). RECLC (Kohm) = 37.4 * Ic(new) -1 Ic(nom) The resistor value is given by: 0 < RECLC < 36.4 K (1/8 Watt) At RECLC greater than 36.4 K, the current limit will be internally clamped to the nominal value. Ic (nom) is the nominal continuous current limit of the amplifier. 4.3.3. External Current Limit ­ Peak (ECLP) The peak current limit of the Cymbal amplifiers can be scaled down by an external voltage or by an external resistor connected between pin J2/12 (ECLP) and J2/7 (ECLRET). 4.3.4. External Voltage An external positive voltage (0 to 3.75 V) to terminal J2/12 (ECLP) in reference to terminal J2/7 (ECLRET) will control the peak current limit from zero to Ip(nom). Ip(new) = VECLP 3.75V * Ip(nom) The voltage is internally clamped to 3.75 V whenever the external VECLP is higher than 3.75 V. The external voltage source must be able to source/sink at least ±0.2 mA. The maximum absolute VECLP allowed to be connected is 5 V. RECLP (Kohm) = 37.4 * 4.3.5. Ip(new) Ip(nom) -1 External Resistor Connect an external resistor between terminal J2/12 (ECLP) and terminal J2/7(ECLRET). The resistor value is given by: 0 < RECLP < 36.4 K (1/8 Watt) At RECLP greater than 36.4 K, the current limit will be internally clamped to the nominal value. Ip(nom) is the nominal peak current limit of the amplifier. 4.3.6. Latch Mode (LM) By connecting J2/5 to J2/10, the amplifier is latched to disable mode whenever a Short, Commutation or Over Temperature failure occurs. Disabling the amplifier temporarily by removing the power from Enable pin J2/14 resets the latch. Be sure to restore the Enable connection when the reason for the event no longer exists. www.elmomc.com 34 Cymbal Installation Guide Servo Control Operation MAN-CYMIG (Ver. 1.3) 4.4. 35 Status Indications The following table lists the Cymbal amplifier status indications. Function Latch Option AOK SO1 SO2 SO3 1 Amplifier OK (AOK) N/A Low Open collector Open collector Open collector 2 External disable No Low Low Open collector Low 3 Current limit No Low Open collector Open collector Low 4 Short Yes Open collector Low Open collector Low 5 Over temperature Yes Open collector Open collector Low Low 6 Internal supplies protection No Open collector Low Low Open collector 7 Under voltage No Open collector Low Open collector Open collector 8 Over voltage No Open collector Open collector Low Open collector 9 Shunt* No Low Open collector Low Open collector 10 Power up reset No Open collector Open collector Open collector Open collector 11 Commutation failure Yes Open collector Low Low Low * This indication can be used as a digital input for activating an external shunt regulator. Table 10: Cymbal Status Indications Notes: • Without latch mode: The status indications are reset when the fault disappears. • With latch mode: The Short, Over Temperature and Commutation Failure status indications are reset when the enable signal is temporarily removed from the enable input. • Multiple faults: Only the reading of the first fault is reliable. Additional faults add on to the status outputs and the indication is therefore meaningless. www.elmomc.com Cymbal Installation Guide Technical Specifications 36 MAN-CYMIG (Ver. 1.3) Chapter 5: Technical Specifications 5.1. General Specifications Feature Units 70/48 70/60 R90/60 50/100 R75/100 35/200 R60/200 18/400 Minimum supply Voltage VDC 11 12 18 36 72 Nominal supply Voltage VDC 42 50 85 170 360 Maximum supply voltage VDC 48 59 95 195 390 Maximum continuous power output W Efficiency at rated power % > 97 Maximum output voltage 97% of DC bus voltage at f=32 kHz DC and trapezoidal commutation continuous current limit (Ic) A Peak current limit A Weight 3200 4000 70 70 2 x Ic 2 x Ic 5100 4600 6900 6600 11300 6800 90 50 75 35 60 18 No Peak 2 x Ic No Peak 2 x Ic No Peak 2 x Ic g (oz) 700 g (24.7 oz) mm (in) 134 x 95 x 60 (5.3" x 3.7" x 2.4") Mounting method Panel mount Auxiliary power supply Isolated DC source only Auxiliary supply input voltage 24 VDC ± 30% Auxiliary supply input power 2 VA Dimensions www.elmomc.com Cymbal Installation Guide Technical Specifications MAN-CYMIG (Ver. 1.3) Feature Units Specification PWM switching frequency kHz 32 ± 5% default on motor Switching method Advanced Unipolar PWM Current loop bandwidth kHz Up to 4 Ambient operating temperature °C (°F) 0 °C to 50 °C (32 °F to 122 °F) Maximum case temperature °C (°F) 87 °C (188 °F) Storage temperature °C (°F) ‐40 °C to 100 °C (‐40 °F to +212 °F) Maximum non‐condensing humidity % 90% Maximum operating altitude m (ft) Up to 10,000 (30,000) Servo Modes Current Commands ±10 VDC Feedbacks Digital Halls www.elmomc.com 37 Cymbal Installation Guide Technical Specifications MAN-CYMIG (Ver. 1.3) 5.2. 38 Dimensions www.elmomc.com Cymbal Installation Guide Technical Specifications MAN-CYMIG (Ver. 1.3) 5.3. 39 Compliance with Standards Specification Details Quality Assurance ISO 9001:2008 Quality Management Design In compliance with MIL‐HDBK‐ 217F • IPC‐D‐275 • IPC‐SM‐782 • IPC‐CM‐770 Reliability Prediction of Electronic Equipment (rating, de‐rating, stress, etc.) Printed wiring for electronic equipment (clearance, creepage, spacing, conductors sizing, etc.) • UL 508C • UL 840 In compliance with VDE0160‐7 (IEC 68) Type testing Safety Recognized UL 508C Power Conversion Equipment In compliance with UL 840 Insulation Coordination Including Clearances and Creepage Distances for Electrical Equipment In compliance with UL 60950 Safety of Information Technology Equipment Including Electrical Business Equipment In compliance with EN 60204‐1 Low Voltage Directive 73/23/EEC EMC In compliance with EN 55011 Class A with EN 61000‐6‐2: Immunity for industrial environment, according to: IEC 61000‐4‐2 / criteria B IEC 61000‐4‐3 / criteria A IEC 61000‐4‐4 / criteria B IEC 61000‐4‐5 / criteria B IEC 61000‐4‐6 / criteria A IEC 61000‐4‐8 / criteria A IEC 61000‐4‐11 / criteria B/C Electromagnetic compatibility (EMC) Workmanship In compliance with IPC‐A‐610, level 3 Acceptability of electronic assemblies PCB In compliance with IPC‐A‐600, level 2 Acceptability of printed circuit boards (PCBs) www.elmomc.com Cymbal Installation Guide Technical Specifications MAN-CYMIG (Ver. 1.3) Specification Details Packing In compliance with EN 100015 Protection of electrostatic sensitive devices Environmental In compliance with 2002/96/EC Waste Electrical and Electronic Equipment regulations (WEEE) Note: Out‐of‐service Elmo drives should be sent to the nearest Elmo sales office. In compliance with 2002/95/EC (effective July 2006) Restrictions on Application of Hazardous Substances in Electric and Electronic Equipment (RoHS) www.elmomc.com 40