code calculations Industrial Calculations: Feeder Loads – Part 2 By James Stallcup, Jr., NEC and OSHA Consultant I n this month’s column, we continue our discussion of calculating feeder loads for an industrial facility. We have shown you how to calculate the loads for feeders No. 1, No. 2, and No. 3. Now we’ll look at calculating the loads for feeders No. 4, No. 5, and No. 6. Then, we’ll size the conductors for each feeder based upon these calculated loads. Use the electrical one-line diagram (Fig. 1 at right) and the following tables for all calculations. Feeder No. 4. This load is a “given,” and it’s 15A. You don’t always need to calculate everything! Fig. 1. A side-by-side comparison of sizing conductors based on different terminal ratings. Fig. 1. THHN (90°C) conductors enable you to use the higher ampacity when adjusting conductor ampacity. Feeder No. 5. Based on the following loads, compute what size conductors are required to supply the motors on the secondary of the transformer per Part B to Art. 220. Step 1: Calculate total amps for all motor loads per Sec. 430-24. 10, 10 hp motors at 14A (ea.)510314A5140A 12, 15 hp motors at 21A (ea.)512321A5252A 15, 5 hp motors at 7.6A (ea.)51537.6A5114A 16, 3 hp motors at 4.8A (ea.)51634.8A576.8A Subtotal5582.8A Step 1a: Add to this total 25% of the highest rated motor in the group (Sec. 430-24). 21A325%55.25A Total load5582.8A15.25A5588.05A Step 2: Determine how many No. 3/0 THHN cu. conductors you must connect in parallel between 92 May 2001 • EC&M • www.ecmweb.com the transformer and the panel per Sec. 310-4 and Table 310-16. No. 3/0 cu.5200A No. of conductors5Total Ampacity4Ampacity of one conductor No. of conductors5588.05A4200A52.94, which we round to 3. Solution: The parallel connection requires three No. 3/0 THHN cu. conductors per phase. Step 3: Compute what size OCPD (CB) is required to protect the secondary conductors. Step 3a: Size OCPD based on the largest motor load per Secs. 430-62(a) and 430-52(c)(1), and Table 430-152. Remember, our largest motor load was 21A. Assuming we have an inverse time breaker, the maximum rating or setting of the breaker must be 250% of that 21A (Table 430-152). 21A3250%552.5A Step 3b: Select appropriate size OCPD per Sec. 430-52(c)(1) and Table 430-152. Remember, the breaker cannot exceed 52.5A, as calculated above. So, we select a 50A breaker. Step 3c: Size OCPD for tapped conductors per Secs. 430-28(1) and 430-62(a). Motor loads, in code calculations addition to the largest load, are: 10314A5140A 12321A5252A221A5231A 1537.6A5114A 1634.8A576.8A Add these loads to get a subtotal of 561.8A. Add in largest OCPD we calculated earlier at 50A. Total load5611.8A. Solution: Select OCPD for the secondary conductors per Secs. 430-62(a) and 240-6(a). The breaker rating cannot exceed the total load. This load of 611.8A requires the use of a 600A OCPD. Step 4: Compute what size copper grounding electrode conductor (GEC), bonding jumper (BJ) and grounded conductor (GC) are required to ground the secondary to building steel. Step 4a: Size the GEC per Sec. 250-30(a)(2), Table 250-66 and Table 8, Ch. 9. No. 3/05167,800 CM 3 3 conductors in parallel5503,400 CM (Table 8, Ch. 9.) kcmil5503,400 CM41,0005503.4 Solution: A 503.4 kcmil conductor requires a No. 1/0 cu. conductor. (Table 250-66). Step 5: Size the BJ per Secs. 250-30(a)(1) and 250-102(c), and Table 25066. Solution: A 503.4 kcmil conductor requires a No. 1/0 cu. conductor. Step 6: Size the GC per Secs. 250-24(b)(2) and 3104, and Table 250-66. Solution: A 503.4 kcmil conductor requires a No. 1/0 cu. conductor. Feeder No. 6. Based on the following loads, compute the load for feeder No. 6 per Part B to Art. 220. Step 1: Calculate total amps for loads per Sec. 430-24 and 430-25. 2 heavy load machines at 12.0A (ea.)5 23 12.0A 524.0A 7 large motors: 1320.0A520.0A 1326.0A526.0A 1315.0A515.0A 1325.0A525.0A 3350.0A5150.0A 1 distribution panel at 50.0A51350.0A550.0A Motor control center (5 motors) 1327.9A527.9A 1320.9A520.9A 1318.5A518.5A 237.6A515.2A Total Load5392.5A Step 1a: Add to this total 25% of the highest rated motor in the group. 50.0A325%512.5A Solution: Total load for this feeder5405A