Control and Operation of Multi-terminal VSC-HVDC Temesgen Haileselassie j Uhlen Kjetil 1 Conclusions / Hypothesis yp • A meshed HVDC grid has the potential to improve security it off supply! l ! • A multi-terminal HVDC grid in the North Sea can effectively integrate the synchronous interconnections (UK, UCTE and Nordic) • Can be operated as ONE control area (if desirable) • R Reserves ((primary i and d secondary) d ) can b be shared h d without “technical constraints” • Fast control and protection will enable network splitting to avoid risk of cascading outages and complete blackouts 2 • Fully integrate the power markets across the asynchronous areas. O tli Outline • Introduction: Why HVDC – VSC HVDC – Multi-terminal HVDC • Power system security and Control objectives • Modelling and control design • Examples (illustrating security control aspects) t ) 3 HVDC Why? y 1. To reduce total transmission loss for long distance power lines 4 Break even distance for onshore application is about 600km and less than 100km for subsea transmissions Cont… 2. AC transmission becomes weak ((unstable)) for very y large g distances 3. Subsea power transmission - Large capacitive currents in AC cables severly limit the transmission capacity of long distance AC cables - The most common application area of HVDC is for subsea power transmission 5 Limits of transmission capacity, Submarine HVAC cables (ref Nexans) 6 Why multiterminal VSC-HVDC (MTDC) in the N th S North Sea? ? 7 Grid integration 8 P Power system t security it Security standards: Deterministic (N-1) or risk based Ability to manage contingencies / outages: Availability of reserves Availability of transmission capacity Stability and control 9 Main challenges in operation and control • Primary control: Less primary reserves if new generation provide less frequency response • Secondary control: More need for secondary reserves with more variable generation • Tertiary control: Benefits with larger control areas and exchange of reserves. New possibilities with an offshore Multi-terminal HVDC grid! 10 Control objectives: Desired operational p capabilities p • Balancing of offshore wind power variation • Resilience, e.g. to loss of a VSC-HVDC terminal (≈load/generation ( load/generation loss) or line/cable • Frequency response enhancement of AC grids • Market integrated operation • AC and DC fault handling capabilities Controllers C t ll should h ld be b designed d i d to t meett the requirements specified above. 11 Modelling: Active and Passive AC grid Connections Time-average VSC model Passive AC grid connection: AC voltage control at PCC -AC -no synchronization -no no control of current Active AC grid connection: -Grid synchronization -control of current flow 12 maU dc mU , Vb b dc , 2 2 1 I o ma ia mbib mcic 2 Va Vc mcU dc 2 Control of VSC Connected to Passive AC Grid AC voltage control at PCC, |V| 13 Control of VSC Connected to Active AC grid g Two options: • |m|, δ control: uses phasor measurements • decoupled axes (dq) control : uses instantaneous measurements 14 |m|, δ control • Suitable for modelling VSC control in phasor based electric l t i power simulation i l ti tools t l (eg: ( DI SILENT) DIgSILENT). • Voltage and current phasor measurements introduce additional time constant into the controllers |m|* 0o ωt * P + PI δ δ* 120o P ωt * |V| or |Q| + - |m| ma* + |m|* cos × mb* |m|* 240o |V| or |Q| ωt 15 × + δ* * PI cos + * - * + + + δ* cos × mc* Decoupled axes (dq) control • • • • 16 Involves abc/dq transf. Fast control responses Mostl used Mostly sed in practice for VSC control Modelling g is p possible with electromagnetic transient softwares such as PSCAD Outer Controllers • • • 17 Set the references to active & reactive (inner) current controllers Active power and/or DC bus voltage control (there types shown below) Reactive power and/or AC voltage control (not shown here) Safe operating area of a VSC Controller actions are limited within safe operating area Safe operating area of a VSC: (a) U vs I safe operating region (b) U vs P safe operating region 18 Constant power control within the safe operating region P* = power reference 19 Constant DC voltage control within the safe operating region U* = DC voltage reference 20 DC voltage droop control within the safe operating region U* = DC voltage reference 21 Two terminal VSC-HVDC Control Rectifier (Source converter) S HVDC Inveter L (Load converter) transmission PS PL Control modes (3x3=9 combinations) Rectifier 22 Remarks Inverter Fixed power Fixed power X (Not viable) Fixed power DC Droop √ (With risk of DC overvoltage) Fixed power Fixed DC voltage √ (With risk of DC overvoltage) DC Droop Fixed power √ (Good, (Good P control by Inv Inv.)) DC Droop DC Droop √ (Good, P control by Both) DC Droop Fixed DC voltage √ (Good, (Good P control by Rect.) Rect ) Fixed DC voltage Fixed power √ (Good, P control by Inv.) Fi ed DC voltage Fixed oltage DC Droop √ (Good, (Good P control by b Inv.) In ) Fixed DC voltage Fixed DC voltage X (Not viable) DC Voltage Control Responses Rectifier (Source converter) S transmission ((Primary y & secondary y DC voltage g control)) UDC Operating point PL0 UDC PL1 PL0 L HVDC PS PL UDC PL1 PL0 PL1 C PS A A PS1 B PS1 PS0 B P 401 400 400 400 399 399 399 397 Rectifier (source) terminal DC bus voltage 395 10 20 30 40 50 60 DC voltage 401 398 398 397 Rectifier (source) terminal DC bus voltage 396 395 10 70 20 30 40 50 60 398 397 395 10 70 1000 1000 950 950 950 Power taken by inverter (load) terminal 800 750 10 20 30 40 Time (s) (a) 50 60 900 850 Power taken by inverter (load) terminal 800 70 Power (MW) 1000 Power (MW W) 1050 Power (MW)) 1050 850 750 10 20 30 40 Time (s) (b) 50 60 Rectifier (source) terminal DC bus voltage 396 1050 900 PS0 P 401 DC voltagee DC voltagge P 23 C A B 396 Inveter (Load converter) 20 30 50 60 70 900 850 Power taken by inverter (load) terminal 800 70 40 750 10 20 30 40 Time (s) (c) 50 60 70 Power flow control in DC grid : achieved by DC voltage droop 24 No need for communication between terminals Many converter terminals contribute to DC voltage regulation DC analogy to distributed frequency droop control in AC systems Similarities of AC grid frequency droop control and d DC voltage lt d droop control t l off MTDC 25 Steady state characteristic of: (a)synchronous generator (b)VSCHVDC terminal (The dots at the end of the characteristic lines show tripping points.) Test model: ”North North Sea DC grid” grid Offshore load (Oil/gas platform) Prated=250 MW C t t Power Constant P terminal All cable resistances: r=0.01 Ω/km All cable bl capacitances:c=5 i 5 μF/km F/k Bipolar DC transmission for all cases Rated DC voltage =+/-200 kV 5 50 =2 l 45 UK National Grid Km Scotland Prated=450 MW DC droop mode 1 l =500 km 14 l12=300 km Prated=1000 MW DC ddroop mode d NORDEL Grid 4 l34=700 km UCTE Grid l23=600 km 20 =1 l 26 England 6 km 2 Prated=800 MW DC droop mode 3 Prated=750 MW DC droop=∞ Prated=600 MW Variable (wind) power Offshore windfarm 26 S Security it analysis l i Examples p illustrating g security y aspects p related to operation and control • • • • Managing normal wind variations Outage of DC connections Outage of generation (wind farm tripping) Pi Primary control t l response tto ac grid id contingency (exchange of primary reserves) • Need for secondary control 27 500 Power (MW W) 480 460 Generated wind power from offshore WF 440 420 400 380 360 10 404 DC voltage (kV) Variations of DC voltage with fluctuating wind power and DC droop p control responses 20 30 40 50 60 70 DC bus 1 (Scotland) DC bus‐1 (Scotland) 400 DC bus‐2 (England) 398 DC bus‐3 (UCTE) 100 110 DC bus‐4 (NORDEL) 396 =2 l 45 392 10 600 DC bus‐5 (Oil/gas platform) DC bus‐6 (Offshore Windfarm) 50 20 30 40 50 60 70 80 90 100 110 Km From Scotland (via Conv‐1) 500 =1 l 26 20 Power (MW) 90 402 394 To England (via Conv‐2) 400 To UCTE (via Conv‐3) To UCTE (via Conv‐3) From NORDEL (via Conv‐4) 300 km To oil/gas platform (via Conv‐5) From offshore WF (via Conv‐6) 200 10 28 80 20 30 40 50 60 Time (s) 70 80 90 100 110 Outage of DC line 1-2 Terminal-1 (Conv-1) continues ti to t draw d power from DC grid via lines 1-3 and 1-4 when line 1-2 is disconnected. L Line Power (M MW) 250 Power via Line 1‐2 200 Power via Line 1‐3 150 5 Power via Line 1‐4 100 Power via Line 2‐3 50 Power via Line 4‐3 0 85 90 95 100 105 =2 l 45 DC volltage (kV) 402 DC bus‐1 (Scotland) 400 DC bus‐2 (England) 398 DC bus‐3 (UCTE) DC bus 4 (NORDEL) DC bus‐4 (NORDEL) 396 DC bus‐5 (Oil/gas platform) 50 394 Km DC bus‐6 (Offshore Windfarm) =1 l 26 20 km Power (MW W) 85 550 90 95 500 From Scotland (via Conv‐1) 450 To England (via Conv‐2) 400 To UCTE (via Conv‐3) 350 To oil/gas platform (via Conv‐5) 250 150 85 105 From NORDEL (via Conv‐4) 300 From offshore WF (via Conv‐6) 200 29 100 90 95 Time (s) 100 105 Outage of connection to windfarm 550 From Scotland From Scotland (via Conv‐1) 500 450 To England (via Conv 2) (via Conv‐2) 400 00 5 =2 l 45 Power (MW W) 350 To UCTE (via Conv‐3) 300 From NORDEL (via Conv‐4) 250 0 Km 200 To oil/gas platform (via Conv‐5) 150 100 20 =1 l 26 km From offshore WF (via Conv‐6) 50 0 83 84 85 86 87 88 89 90 91 Time (s) 30 Terminals 1, 2 and 4 compensate for lost power flow from offshore wind farm. 92 Frequency response enhancement of AC grids by VSC-HVDC VSC HVDC Frequency droop control implemetation on VSC-HVDC with: ( ) constant (a) t t power control t l (b) DC voltage lt droop d control t l 31 Frequency response enhancement example: two terminal VSC-HVDC 32 Effect of frequency droop control (in VSCHVDC ) on AC grid HVDCs) id ffrequency responses 33 Frequency response enhancement of AC grids by MTDC 50 =2 l 45 Grid ffrequency (p.u u.) 1.001 UK national grid 1 UCTE grid 0.999 NORDEL grid Oil/gas platform 0.998 Offshore WF 0.997 Km 100 110 120 130 140 150 160 170 180 =1 l 26 20 km DC voltaage (kV) 402 DC bus‐1 (Scotland) 400 DC bus‐2 (England) 398 DC bus‐3 (UCTE) 396 DC bus‐4 (NORDEL) DC bus‐5 (Oil/gas platform) 394 392 100 600 DC bus‐6 (Offshore Windfarm) 110 120 130 140 150 34 Power (MW W) 170 180 From Scotland (via Conv‐1) 500 UCTE grid frequency supported by NORDEL and UK (via two HVDC stations: i one at England l d and the other in Scotland) 160 To England (via Conv‐2) To UCTE (via Conv‐3) 400 From NORDEL (via Conv‐4) 300 To oil/gas platform (via Conv‐5) F From offshore WF (via Conv‐6) ff h WF ( i C 6) 200 100 110 120 130 140 Time (s) 150 160 170 180 Comparison of grid responses (UCTE grid): with and without frequency support from DC grid 1 0.9995 Grid freequency (p.u.) 0.999 0.9985 With frequency support by MTDC Without frequency support by MTDC 0.998 0.9975 0.997 0.9965 0.996 100 110 120 130 Time (s) ( ) 35 140 150 160 Frequency response improves with presence of frequency support from DC grid. Precise control of power flow Schedule/ dispatch Control Terminal PDC UDC (kV) type No No. (MW) 1 600 Droop 2 - 400 Droop 3 -750 - Fixed P 4 550 - Droop 5 -900 - Fixed P Control references Control Terminal PDC U ((kV)) type No No. (MW) DC 1 600 400 Droop 36 2 500 400 p Droop 3 -750 400 Fixed P 4 550 400 Droop 5 -900 400 Fixed P N t precise! Not i ! Cntd… Schedule/ dispatch Control Termina PDC U (kV) type l No. ((MW)) DC 1 600 Droop 2 400 Droop 3 -750 750 Fi d P Fixed 4 550 Droop 5 -900 Fixed P DC Power flow analyisis Control references Control Termina PDC t UDC (kV) type l No. (MW) 1 600.00 399.550 Droop 37 2 535.94 400.000 Droop 3 -750.00 396.613 Fixed P 4 550 00 396.928 550.00 396 928 Droop D Precise! 5 -900.00 385.247 Fixed P (Desired power flow achieved) F t Future works k on MTDC • • • 38 Protection schemes F lt detection Fault d t ti and d localization l li ti algorithms Communication based (?) Future works works… Impact of wide area MTDC (Stability, operational, …) 39 Thank you! 40