(*) Same menu as ”CONF” menu ESC (2) V> V> V>> V>> V> V>> V< V>> V< V< V<< V>> V< V<< V> V>> V< (*) V< V<< V< V<< V<< (1) V<< df/dt / Present passcode New passcode Repeat New passcode ESC (1) df/dt df/dt / Hz> Hz> Hz> Hz< df/dt (3) Hz> Hz< Hz> Hz< df/dt / Hz< df/dt df/dt V> df/dt V> V>> Hz< df/dt / Hz< df/dt / V> ESC (3) (2) ESC In the menu RESET , the key is used in setting voltages and times, in order to change de digit to set (Units; tens; cents; ...). Time Overvoltage (59T): See measuring range; Timing: 0 ÷ 600.0 s (0.1 s). Instant. Overvoltage (59 I): See measuring range; Timing: 0 ÷ 9.99 s (0.01 s). Time Undervoltage (27 T): See measuring range; Timing: 0 ÷ 600.0 s (0.1 s). Instant. Undervoltage (27 I): See measuring range; Timing : 0 ÷ 9.99 s (0.01 s). Return %: 2% ÷ 10% (1%). Unbalance: 5% ÷ 25% (1%); Timing: 0 ÷ 9.99 s (0.01 s) Reverse Phase Sequence. Minimum SupervisionVoltage (Frequency): See measuring range. Maximum Frecuency (81 M): 40 ÷ 70 Hz (0.01 Hz); Timing: 0 ÷ 9.99 s (0.01 s). Minimum Frecuency (81 m): 40 ÷ 70 Hz (0.01 Hz); Timing: 0 ÷ 9.99 s (0.01 s). Frequency Gradient: 0.1 ÷ 5 Hz/s (0.1 Hz/s); Maximum supervision Frequency: 40 ÷ 70 Hz (0.01 Hz). Digital Output Programming. Digital Input Programming. Frequency: 50 or 60 Hz. Star/Delta connection: Star or Delta. Ratio: 1 ÷ 999.9 (0.1). Comunicaciones: 4.88, 9.600 ó 19.200 baudios. (1) Negative Contact Logic: The output contact will be powered in survillance status and will be reseted when the undervoltage functions acts. (*) RV-U relay with 1% of return percentage. Measuring Range Digital Outputs Rated Voltage Range Step Voltage 63.5 V 38.1-88.9 V 0.1 V Vac 110 V 66-154 V 1V 230 V 138-322 V 400 V Select. Function 0 General Trip Vac 1 Trip 59 Instantaneous 1V Vac 2 Trip 59 Timed 240-560 V 1V Vac 3 Trip 27 Instantaneous 110 V (*) 88-132 V 1V Vac 4 Trip 27 Timed 4V 1,6-6 V 0.1 V Vac 5 Instantaneous Trip 12 V 5-20 V 0.1 V Vac 40 V 15-60 V 0.1 V Vac 6 Timed Trip 12 Vdc 7.2-16.8 Vdc 0.1 V Vdc 7 Trip 59 24 Vdc 14.4-33.6 Vdc 0.1 V Vdc 8 Trip 27 48 Vdc 28.8-67.2 Vdc 0.1 V Vdc 9 Over/Undervoltage trip 72 Vdc 43.2-99.9 Vdc 0.1 V Vdc 125 Vdc 75-175 Vdc 1V Vdc 220 Vdc 132-308 Vdc 1V Vdc Digital Input Option Function 0 Disabled 1 RESET of the trip signal and last fault data. 2 Function 59 disabled 3 Function 27 disabled 4 Function 81 disabled 5 Instantaneous and frequency functions disabled 6 27 & 59 instantaneous disabled 10 Unbalance trip 11 Reverse phase sequence trip 12 13 Alarm. Relay no operational. In normal circumstances (RV-U operational) the output relay is powered up. Trip 81M 14 Trip 81m 15 Trip 81 Mm 16 Trip 81 df/dt 17 Frequency trip 18 Trip 27 Instant. with negative contact logic (1). 19 Trip 27 Timed with negative contact logic (1). 20 Trip 27 with negative contact logic (1).