A Technical Note from the Experts in Business-Critical Continuity™ Importance of Managing Impedances in the Bypass Path for a Distributed Static Switch (1+N) System: Performance Improvements with a Bypass Sharing Inductor Introduction This paper explains how the impedances of the bypass paths should be controlled for paralleled distributed static switch (1+N) UPS systems and provides recommendations for controlling the cabling impedances to ensure efficient bypass power sharing. When a system is on inverter, the inverter power sharing algorithm controls each UPS module’s output voltage magnitude and phase angle to evenly distribute the power. However, when the system is on bypass, the power flows through the Backfeed Breakers (BFB) and Bypass Static Switches (BPSS) and is not actively controlled. Bypass current sharing can only be achieved by controlling the impedance difference between each unit. For this reason, a Sharing Inductor is included with the Liebert NXL UPS to permit some variation of cable length (and impedance) while maintaining equivalent load sharing between units. For example, if two UPS modules without sharing inductors are paralleled and the impedance in each bypass path is identical then each unit will have exactly 50% of the load. Any mismatch in the impedance will cause one unit to have more than 50% of the load while the other UPS will have less than 50%. For a redundant system Emerson Network Power defines the worst case system load rating with the redundant module out of service. Our philosophy is that the customer’s load should be supported if there is enough connected UPS capacity to support the critical load. For example, in the case of a Liebert NXL three (3) module system, if the system is on the static bypass switches and the customer’s load is 3 x 100% of the module ratings, the system should NEVER shutdown due to imbalance in load sharing between units. Therefore, in order for each module to carry its’ rated load, it is important for the impedances in the bypass paths to be sufficiently matched. Otherwise, if they are not closely matched, a 100% system load could cause one UPS to have, for example, 120% of the load current while the other UPS only has 80% and thus one UPS will begin an overload shutdown time. 2 Bypass Sharing Operating in Redundancy and Capacity Modes Operating in a redundant mode implies that there is at least one more UPS module online than needed to support the total critical load. In this scenario accurate bypass sharing is not very critical since the load on the bypass path of each module will never be near 100% of the full load capacity. Operating in a capacity mode system implies that there are only enough UPS modules available to support the load. In other words, each UPS bypass must share the load equally. Getting the bypass circuits to share the current is strictly a function of the impedance difference between each unit’s bypass paths. Figure 1 shows the simplified electrical circuit for the bypass paths in a Liebert NXL 1+N system. The circuit is composed of three (3) major impedance elements, namely the input cabling impedance (1), the bypass Sharing Inductor (2) and the output cabling impedance (3). These three impedance elements are summed together to create the total impedance of the bypass path. For the data that will be presented next, the cabling impedance is the sum of both the input and output field cabling to the UPS. It is assumed that the Input Switchgear, circuit breakers, and System Paralleling Cabinet have negligible impedance. In the example, the cabling chosen is 600kcmil per phase. MBB MIB UPS Module Input Switchgear BFB 1 CB1 2 DC Bus Rectifier System Paralleling Cabinet 3 Inverter CB2 MOB AC UPS Module BFB CB1 DC Bus Rectifier Inverter CB2 MOB UPS Module BFB CB1 DC Bus Rectifier Inverter CB2 MOB Figure 1 - 1+N Bypass Electrical Circuit 3 Bypass Power Sharing with Cabling Impedance Differences Based on a 1+N system of (3) 750kVA 480V Liebert NXL with 2,250kVA of load at 0.9 lagging power factor, Table 1 shows the bypass loads when the cabling length is varied while UPS modules power the load via their static bypass switches with a Sharing Inductor. The percent difference shown is based on UPS1 & UPS2 with the cable lengths as listed and UPS3 bypass cabling is reduced by the percentage in the table. Tables 2 shows the current sharing difference with share inductors not installed. The red shaded data indicates an overload situation. The values over 110% are an unacceptable overload. Table 1: Bypass Current Sharing Liebert NXL with Share Inductor (4) 600kcmil per phase 100% System load 750kVA,480V, 0.9pf, 50ft Percent cable Difference % Current UPS #1 % Current UPS #2 % Current UPS #3 0% (50, 50, 50) 100.0% 100.0% 100.0% 10% (50, 50, 45) 99.8% 99.8% 100.4% 25% (50, 50, 37.5) 99.4% 99.4% 101.2% 50% (50, 50, 25) 98.7% 98.7% 103.4% 100% System load 750kVA,480V, 0.9pf, 100ft Percent cable Difference % Current UPS #1 % Current UPS #2 % Current UPS #3 0% (100, 100, 100) 100.0% 100.0% 100.0% 10% (100, 100, 90) 99.8% 99.8% 100.4% 25% (100, 100, 75) 98.5% 98.5% 103.0% 50% (100, 100, 50) 96.5% 96.5% 107.0% 100% System load 750kVA,480V, 0.9pf, 200ft Percent cable Difference % Current UPS #1 % Current UPS #2 % Current UPS #3 0% (200, 200, 200) 100.0% 100.0% 100.0% 10% (200, 200, 180) 99.3% 99.3% 101.5% 25% (200, 200, 150) 97.0% 97.0% 106.0% 50% (200, 200, 100) 93.0% 93.0% 114.0% 100% System load 750kVA,480V, 0.9pf, 500ft Percent cable Difference % Current UPS #1 % Current UPS #2 % Current UPS #3 0% (500, 500, 500) 100.0% 100.0% 100.0% 10% (500, 500, 450) 99.0% 99.0% 102.0% 25% (500, 500, 375) 95.5% 95.5% 109.0% 50% (500, 500, 250) 89.0% 89.0% 122.0% 4 Table 2: Bypass Current Sharing Other manufacturers UPS without Share Inductor (4) 600kcmil per phase 100% System load 750kVA,480V, 0.9pf, 50ft Percent cable Difference % Current UPS #1 % Current UPS #2 % Current UPS #3 0% (50, 50, 50) 100.0% 100.0% 100.0% 10% (50, 50, 45) 96.5% 96.5% 107.0% 25% (50, 50, 37.5) 90.0% 90.0% 120.0% 50% (50, 50, 25) 75.0% 75.0% 150.0% 100% System load 750kVA,480V, 0.9pf, 100ft Percent cable Difference % Current UPS #1 % Current UPS #2 % Current UPS #3 0% (100, 100, 100) 100.0% 100.0% 100.0% 10% (100, 100, 90) 96.5% 96.5% 107.0% 25% (100, 100, 75) 90.0% 90.0% 120.0% 50% (100, 100, 50) 75.5% 75.5% 149.0% 100% System load 750kVA,480V, 0.9pf, 200ft Percent cable Difference % Current UPS #1 % Current UPS #2 % Current UPS #3 0% (200, 200, 200) 100.0% 100.0% 100.0% 10% (200, 200, 180) 97.0% 97.0% 106.0% 25% (200, 200, 150) 90.0% 90.0% 120.0% 50% (200, 200, 100) 75.5% 75.5% 149.0% 100% System load 750kVA,480V, 0.9pf, 500ft Percent cable Difference % Current UPS #1 % Current UPS #2 % Current UPS #3 0% (500, 500, 500) 100.0% 100.0% 100.0% 10% (500, 500, 450) 97.0% 97.0% 106.0% 25% (500, 500, 375) 91.0% 91.0% 118.0% 50% (500, 500, 250) 76.0% 76.0% 148.0% Table 1 – Affects of cabling impedances The bypass static switch of each Liebert NXL UPS is rated for 110% continuous. Any unit with a bypass current in excess of the 110% limit will initiate an overload timeout for the entire system. Without an overload timeout a bypass circuit can be overloaded causing protection devices to trip without warning. A comparison of Table 1 and Table 2 demonstrates that controlling the cabling impedance (i.e., cable size and length) is very important if the bypass paths are to share the load current without getting into an overload situation prematurely. 5 Recommendations Emerson Network Power recommends that the impedance in the bypass path be carefully matched for paralleled systems. The impedance mismatch can be minimized by controlling the wiring length of each unit. In other words, the installation of a parallel system requires that the cabling impedance be as closely matched as possible. The design and the layout of the UPS system and associated panels and cabling should be examined closely to ensure that cable lengths and impedances are closely matched. To minimize the impact of cable impedance mismatch the Liebert 1+N UPS module is supplied with a sharing reactor. The cabling impedance must be carefully controlled to ensure good bypass current sharing. 1. For Liebert NXL Systems, the cabling impedances need to be within 10% from maximum to minimum. If the cabling impedances need to be greater than 10%, contact your Emerson representative to calculate if the system will result in an overload condition when operating on bypass. 2. When bringing the 1+N system online for the first time or after removing one unit, it is recommended that the bypass current mismatch be checked. This is accomplished by placing a load on the bypass of each UPS module and then viewing the output current of each unit. The accuracy of the currents displayed on the UPS module is sufficient for this check. If the mismatch is greater than 10% it will be necessary to balance the bypass impedances or limit the load to less than maximum rating. 6 Emerson Network Power 1050 Dearborn Drive P.O. Box 29186 Columbus, Ohio 43229 800.877.9222 (U.S. & Canada Only) 614.888.0246 (Outside U.S.) Fax: 614.841.6022 EmersonNetworkPower.com Liebert.com While every precaution has been taken to ensure accuracy and completeness in this literature, Liebert Corporation assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2011 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice. All names referred to are trademarks or registered trademarks of their respective owners. ®Liebert and the Liebert logo are registered trademarks of the Liebert Corporation. Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2011 Emerson Electric Co. TN-00009-R06-11 Emerson Network Power. The global leader in enabling Business-Critical Continuity™. AC Power Connectivity DC Power Embedded Computing Embedded Power Infrastructure Management & Monitoring Printed in USA EmersonNetworkPower. com Outside Plant Power Switching & Controls Precision Cooling Racks & Integrated Cabinets Services Surge Protection