11/19/2009 Poultry house ventilation system ` Basically consists of exhaust fans and air inlets. ` Exhaust fan draw in fresh air Poultry House Ventilation System Design Michael Czarick III The University of Georgia Poultry house ventilation system design ` How much exhaust fan capacity should a house have? Basically consists of exhaust fans and air inlets. ` ` Exhaust fan draw in fresh air Inlets direct the fresh air to where we want it to go. go Exhaust fan capacity rule of thumb Example: ` 60’ X 300’ broiler/turkey house ` ` 60’ X 300’ X 7 = 126,000 cfm (25 – 24” fans) Minimum exhaust fan capacity for a power-ventilated broiler/turkey house: ` 7 cfm per square foot of floor space (130 m3/hr per m2) ` ` This should ensure that there is no more than a 5oF (2.7oC) increase from the inlet to the exhaust fans 4 – 5 cfm per square foot of floor space for house which is curtain-ventilated during hot weather 1 11/19/2009 This is minimum… ` Heat produce by broilers has increased approximately 20% in the last 20 years. The typical U.S. broiler/turkey house: ` ` 8 – 10 cfm per square foot of floor space. 60’ X 300’ = 144,000 – 160,000 cfm 50 years ago 30 years ago Today Turkeys have changed as well… What type of fan should a house be equipped with? Exhaust fan selection criteria Exhaust fan selection criteria 1. To obtain desired air exchange rate exhaust fan capacity must be determined at a minimum static pressure of 0.10” (25 Pa). Energy efficient 2. ` It is not how much power a fan uses…it is how many cubic feet per minute it can move with each watt of power: ` ` ` Cfm/watt The higher the rating…the lower your operating costs will be. Desired energy efficiency rating ` Should have an energy efficiency of at least 20 cfm/watt @0.10” (34 cmh/watt)…..ideally +20.8 cfm/watt (35 cmh/watt) or better 2 11/19/2009 Not only do we want a fan that is energy efficient, we want a powerful fan as well. Exhaust fan air flow ratio 3. ` Fan output vs. static Pressure (48” fans, between 20,000 and 22,000 cfm) ` An indicator of how well the fan will hold up to high static pressures caused by: ` Dirty fan shutters Clogged inlet screens Cfm m ` Air flow ratio = air flow (0.20”)/ airflow (0.05”) 26,000 24,000 22,000 20,000 18,000 16,000 14,000 12,000 10,000 8,000 6,000 4,000 2,000 0 0 0.05 0.84 Not only do we want a fan that is energy efficient, we want a powerful fan as well. An indicator of how well the fan will hold up to high static pressures caused by: ` ` ` Dirty fan shutters Clogged inlet screens Winds Wind p pressure (in) ` 0.84 0.15 0.2 Static Pressure 0.86 0.74 0.25 0.76 0.3 0.35 0.67 A fan with a high air flow ratio is less affected by the wind Exhaust fan air flow ratio 3. 0.1 0.2 0.18 0.16 0.14 0.12 0.1 0.08 0.06 0.04 0.02 0 0 5 10 15 20 Wind speed (mph) Fan output vs. static Pressure (48” fans, between 20,000 and 22,000 cfm) ` Cfm m This is a serious problem with variable speed fans! Air flow ratio = air flow (0.20”)/ airflow (0.05”) 26,000 24,000 22,000 20,000 18,000 16,000 14,000 12,000 10,000 8,000 6,000 4,000 2,000 0 0 0.05 0.84 0.1 0.84 0.15 0.2 Static Pressure 0.86 0.74 0.25 0.76 0.3 0.35 0.67 3 11/19/2009 Air flow ratio ` ` Minimum acceptable Ideal Fan performance information is available at = 0.73 = 0.78 or higher ` WWW.BESS.UIUC.EDU Estimated initial fan cost Exhaust fan selection criteria 60’ X 300’ house with 126,000 cfm of fan capacity Size ` ` ` Keep small fans to a minimum They are very effective for minimum ventilation but… Small fans are a very poor investment: ` ` ` Fan C Cost ($) 4. Higher initial cost Higher operating cost Higher maintenance cost $12,000 $11,000 $10,000 $9,000 $8,000 $7,000 $6,000 $5,000 $4,000 $3,000 $2,000 $1,000 $0 12 24 36 48 60 Fan Size (“) Fan size and energy efficiency Fan operating cost (the larger the fan the more energy efficient it tends to be) (100,000 cfm for 24 hours @ $0.10 per Kw*hr) Energy Efficie ency (cfm/watt) 23 $29.00 $27.00 $25.00 $23.00 $21.00 $19.00 $17.00 $15.00 $13.00 $11.00 $9.00 $7.00 $5.00 21 19 17 15 13 11 9 7 5 12 24 36 Fan Size (“) 48 60 12 24 36 48 60 Fan Size (“) 4 11/19/2009 This does not mean you can’t install a few small fans but… ` The optimal exhaust fan system stages from small to large fans quickly: ` ` ` Two - four 24” fans – minimum ventilation fans Two - four36” fans – moderate weather Then 48” fans or larger for the remainder of the required fan capacity it – hot h t weather th Another advantage of keeping the number of small fans to a minimum ` Reduces the potential for shutter air leakage 100.0°F 100 ½ the shutters… ½ the cold spots 90 80 70 60.0°F Cold spots near exhaust fans Problems with leaky shutters can be further reduced by placing exhaust fans in groups Fan shutter leakage Minimizing cold spots Leakage exits adjacent minimum ventilation fans 5 11/19/2009 The fact is that fans do not have to be evenly spaced down the length of the house Poultry house with a single fan and four air inlets Poultry house with two fans and air four inlets Poultry house with a single fan and eight air inlets Poultry house with a single fan and 16 air inlets Poultry house with a single fan and 16 air inlets 6 11/19/2009 Poultry house with a single fan and 16 air inlets .08” .08” .08” .08” .08” .08” .08” .08” 950 ft/min 950 ft/min 950 ft/min 950 ft/min 950 ft/min 950 ft/min 950 ft/min 950 ft/min Outside But you MUST establish a negative pressure if you want to gain control over the environment Ventilation system design ` ` ` Chimney fans? It is very important to realize that though fan placement can be of some importance… Inlet design/placement is by far, more important when it comes to maintain proper environmental control +80% of ventilation system design is proper inlet design and placement maybe 20% or less is exhaust fan placement Chimney fans with poor inlets 7 11/19/2009 Chimney fans with poor inlets Poor side wall inlet Cool side wall Poor conditioning of incoming air Air inlet system design Air inlet capacity ` How much inlet area should a house have? ` General rule of thumb: ` ` ` 1 square foot for every 750 cfm of exhaust fan capacity. or 1 square meter for every 4,800 m3/hr 8 11/19/2009 Air inlet example: 40’ X 300’ with 84,000 cfm (7 cfm/ft2) ` ` ` ` ` ` Inlet area = 84,000 cfm / 750 cfm = 168 square feet (16 m2) If the house had a single continuous inlet… It is specifically designed to bring in just enough air to maintain air quality during very cold weather: ` ` ` For optimal control a modern poultry house should have a minimum of two inlet system….ideally three Each inlet system is specifically designed to be used to obtain specific objectives 2) Moderate weather inlet system ` Designed to control house temperature during moderate weather. Maximize heating of incoming cold air Distribute fresh air throughout the house evenly ` ` Without causing drafts With t causing Without i excessive i ffuell usage 3) Hot weather inlet system ` ` Inlet width = total inlet area/ house length = 168 ft2/300 ft = 0.56’ feet or 6” or 15.2 cm 1) Cold weather inlet system ` Air inlet system(s) Minimum ventilation inlet system Designed to maximize bird heat removal ` Produce high air velocities over the birds to maximize heat removal 9 11/19/2009 Minimum ventilation inlet system ` Specifically designed for use for very cold weather for use with just a few exhaust fans…minimum ventilation fans. ` ` ` 1 – 2 cfm per square foot. 60’ X 300’ X 1.5 = 27,000 cfm Might consist of only 20 to 30 inlets Minimum ventilation inlet guidelines Located towards the center of the house 1) ` ` That is where your hottest air tends to accumulate Furthest distance from the birds 99.0°F 99.4 97.4 95 94.2 90 92.1 89.6 86.1 85 83.6°F Example of minimum ventilation inlets Example of minimum ventilation inlets Desired air flow pattern from minimum ventilation inlet Desired air flow pattern from minimum ventilation inlet 96.2°F 95 90 85 80 75.0°F 10 11/19/2009 Minimum ventilation inlet guidelines Attic vs. outside temperatures Draw air out of the attic 2) ` ` 85.0°F 85 Less affected by wind Warmer air for a portion of the day 80 90 85 75 80 75 70 70 erature (F) Tempe 65 65 60 55 50 60.0°F 45 40 35 78.2°F 30 25 75 21-Feb 19-Feb 17-Feb 9-Feb 15-Feb 7-Feb 13-Feb 5-Feb 11-Feb 3-Feb 1-Feb 30-Jan 28-Jan 26-Jan 24-Jan 22-Jan 20-Jan 18-Jan 16-Jan 8-Jan 14-Jan 6-Jan 12-Jan 10-Jan 4-Jan 2-Jan 20 70 Date 65 attic 60 55 53.1°F Minimum ventilation inlets above tube heaters Minimum ventilation inlet guidelines 3) Located above a house’s heating system to help temper incoming cold air 95.0°F 90 71.5 57.9 43.4 80 70 60 44.5 55.0°F 95.0°F 58.2 73.7 90 80 70 60.0°F Minimum ventilation inlets above hot water fin pipes Minimum ventilation inlets above hot water system 105.0°F 100 90 80 70 60 53.4°F 11 11/19/2009 Generally, it is best to have a single row of minimum ventilation inlets… Minimum ventilation inlets Heating system location have reduce problems with minimum ventilation inlets near the side walls Offset minimum ventilation inlets Offset minimum ventilation inlets Generally, it is best to have a single row of minimum ventilation inlets… Could be single direction inlets, but should be located near centerline 12 11/19/2009 Two rows of bidirectional minimum ventilation inlets Two rows of bidirectional minimum ventilation inlets Beam deflecting air jet 105.0°F 105.0°F 100 100 90 90 80 80 70 70 60 60 55.0°F 55.0°F A continuous inlet is a very poor minimum ventilation inlet Beam deflecting air jet 105.0°F 100 90 80 70 60 55.0°F 13 11/19/2009 Very difficult to obtain a uniform small opening… Side wall or a ceiling continuous inlet 100.0°F 100 90 80 70 60.0°F 60.0 F 100.0°F 100 100.0°F 100 90 90 80 80 70 70 60.0°F 60.0°F To maximize the tempering of the incoming air… Continuous inlets do not tend to produce adequate tempering of incoming air ` We must keep the air away from the birds as long as possible 5C 10 C Little tempering/mixing of incoming air 15 C 20 C Air dumping to floor during minimum ventilation.. 103.5°F 100 95 90 85 80 78.3°F 14 11/19/2009 Heating not being utilized on the far side of the house. Birds becoming chilled directly under inlet. Fan side of house birds are significantly warmer. In order for a minimum ventilation inlet system to work proper… ` ` All the air should enter through the inlets If the houses are loose… ` Air entering through cracks will not mix. ` ` ` Loose door Drafts Poor fresh air distribution R d d litter Reduced l d drying Loose door 37.8°C 37.8°C 35 35 30 30 105.0°F 25 25 100 21.1°C 21.1°C 90 37.8°C 35 80 30 70.0°F 25 21.1°C 15 11/19/2009 Loose door Loose door 39.0°C 37.8°C 33.5 38 35 36 34 30 32 25 30 26.5 28 28.0°C 21.1°C Loose door Loose fan shutters 38.0°C 38 100.0°F 100 36 95 34 90 32 12.0 30 85 28 80 79.7°F 26 26.0°C Loose fan covers Loose side walls 72.1°F 105.0°F 70 100 53.4 90 60 80 50 56.4 70 60.6 40.0°F 65.0°F 16 11/19/2009 Side wall leakage Crack in side wall 105.0°F 100 90 80 70 60.0°F 0.3 0.28 0.26 0.24 0.2 0.22 0.18 0.16 0.14 0.1 0.12 0 ` Turn on a two 36” fans (four 24” fans) Measure the resulting static pressure Then use the following chart to determine if the house is tight enough 0.08 ` 60 55 50 45 40 35 30 25 20 15 10 5 0 0.06 ` Static pressure vs Opening 0.04 ` We want all the air to enter through the inlets. House tightness test should be conducted from time to time. 0.02 ` Leakagee Area (ft2) Houses must be tight to maximize air quality Static Pressure Optimally tight house (0.65 square feet of leakage per 1,000 square feet of floor space) Air inlet systems 1) 2) Cold weather - minimum ventilation Moderate weather – temperature control 17 11/19/2009 Moderate weather inlets ` More needed than minimum ventilation inlets ` 4 - 5 cfm per square foot of floor space ` ` ` Inlets on both sides of the house maximum temperature and air quality uniformity Around three times as much as minimum ventilation inlets If not tunnel ventilated (7+ cfm/ft2) Located along both side walls pulling air from directly outside t id the th house h Attic inlets during for use for moderate ventilation? Attic inlets during hot weather What makes a good temperature control inlet? Air flow directed toward ceiling at an angle ` Directs the air where you want it to go. 18 11/19/2009 Air flowing out of recessed inlet in 50’ wide house What makes a good temperature control inlet ` ` Surface mounted inlet sits on the wall… a recessed inlet sits in the wall. Directs the air when you want it to go. Recessed inlet Cold air exiting sides of air inlet Air flowing out side of inlet Warm air flowing the side of recessed inlet 90.0°F 90 85 80 75 70.0°F 19 11/19/2009 Air focused at top of the inlet which improves throw Examples of recessed side wall inlets 85.0°F 85 80 75 70 65 60.0°F Moderate weather inlets ` More needed than minimum ventilation inlets ` 4 - 5 cfm per square foot of floor space ` ` ` ` Air flow along the floor during warmer weather Around three times as much as minimum ventilation inlets If not tunnel ventilated (7+ cfm/ft2) Located along both side walls pulling air from directly outside t id the th house h Ideally can direct the air up toward the ceiling during cooler weather and down toward the floor during warmer weather Side wall inlet capable of directing incoming air downward Deflector board for hot weather bird cooling 20 11/19/2009 Deflector board for hot weather bird cooling Air inlets ` ` ` Cold weather – minimum ventilation Moderate weather – temperature control Hot weather – bird heat removal system ` Importance of air movement when it comes to cooling birds Hot weather is whenever it is warmer outside than you want it inside. In order to cool a bird we have to get air to move over its body... 100.0°F 100 95 90 85 80 More air speed… more cooling Still Air - 25oC 75.0°F 300 ft/min - 25oC 21 11/19/2009 Turkeys 0.75 m/sec - 26oC (26oC – 150 ft/min) 39.0°C 38 36 34 32 30 28 26 26.0°C 2 m/sec - 26oC 2 m/sec - 26oC 39.0°C 38 36 34 32 30 28 26 26.0°C Air movement in traditional cross- Designed to conserve heat and not to produce air movement over the birds ventilation during hot weather 5C 10 C 15 C 20 C 22 11/19/2009 Very little air movement at floor level during cold weather Designed to produce little air movement at bird level 5 m/sec 3.5 m/sec 2.5 m/sec 1.5 m/sec less than 0.25 m/sec During the summer they will tend to conserve heat also… Very little air movement during hot weather as well 2.5 m/sec 26oC 26.5oC 1 m/sec 5 m/sec 27oC 28oC 0.75 m/sec to 0.5 m/sec over limited areas Things are improved if you have inlets on both sides of the house 2.5 m/sec Attic inlets during hot weather 1 m/sec 5 m/sec 0.75 m/sec to .025 m/sec 23 11/19/2009 Inlets in the center of the house Side wall of house Attic inlets during hot weather Center of house Inlets directed to the floor Downward facing hot weather inlet improves the situation even more 5 m/sec 2.5 m/sec 0. 5 m/sec <0.25 m/sec 24 11/19/2009 Downward facing inlets on both sides of th house even better Downward inlet on one side of a house 35.0°C 35 35.0°C 35 30 30 25 25 20 20.0°C 20 20.0°C 103.0°F 103.0°F 5 m/sec 100 100 95 95 90 90 85 85 1.5 m/sec 1 m/sec 80 80 75.0°F 75.0°F Even with inlets that direct air downward cooling fans may be required. Using circulation fans for bird cooling 5 m/sec 1.5 m/sec 1 m/sec 36” circulation fan coverage area 15’ 50’ 50’ 50’ Poor air movement distribution 50’ 40’ wide house 25 11/19/2009 36” circulation fans blowing across the house Limited coverage area 39.0°C 38 36 34 32 30 29.0°C Most houses don’t have enough circulation fans to provide the necessary air movement. Birds directly in front of fan 39.0°C 38 36 34 32 30 29.0°C Air inlets ` ` ` Best heat removal system is tunnel ventilation Cold weather – minimum ventilation Moderate weather – temperature control Hot weather – heat removal system ` tunnel ventilation is just another inlet system 26 11/19/2009 Air exchange and air velocity Cross ventilation vs. Tunnel ventilation 100.0°F 100 95 Air velocity of between 2 and 3 m/sec 90 85 80 100.0°F 100 75.0°F Air exchange typically less than every 60 seconds 95 90 85 80 75.0°F Tunnel ventilation is just an additional stage of ventilation ` Minimum ventilation For most of the year the house is no different from what you may already be doing. ` ` Fewer side wall/chimney fans Fewer side wall inlets +0.5 C Moderate ventilation +1.5 C Moderate ventilation +2 C 27 11/19/2009 Low level tunnel ventilation +3 C High level tunnel ventilation Medium level tunnel ventilation +4 C mczarick@uga.edu (706) 540-9111 +4.5 C www.poultryventilation.com 28