TECHNICAL DATA VENTING ® NOTES FOR MULTIPLE APPLIANCE VENTING (SEE TABLES 13.1, 14.1 AND 14.2) 1. Maximum Vent Connector Length 1-1/2 feet for every inch of connector diameter. Greater lengths require increase in size, rise or total vent height, to obtain full capacity. 2. Each 90-degree turn in excess of the first two reduces the connector capacity by 10 percent. 3. Each 90-degree turn in the common vent reduces capacity by 10 percent. 4. Where possible, locate vent closer to or directly over smaller appliance connector. 5. Connectors must be equal to or larger than draft hood outlets. 6. If both connectors are same size, common vent must be at least one size larger, regardless of tabulated capacity. 7. Common vent must be equal to or larger than largest connector. 8. Interconnection fittings must be same size as common vent. 9. Use sea level input rating when calculating vent size for high altitude installation. 10. Designation “NR” in Tables 13.1, 14.1 & 14.2 indicates not recommended. CAPACITY OF TYPE B DOUBLE-WALL VENT 13.1 Total Connector Vent Rise Height “R” “H” 1' 6' 2' 3' 1' 8' 2' 3' 1' 10' 2' 3' 1' 15' 2' 3' 1' 20' 2' 3' 1' 30' 2' 3' 1' 40' 2' 3' 60’ to 1' 100' 2' 3' 4" 5" 26 31 35 27 32 36 28 33 37 30 35 40 31 37 42 33 39 44 35 41 46 37 44 50 46 55 62 48 57 64 50 59 67 53 63 71 56 66 74 59 70 79 62 73 83 66 79 89 72 86 96 76 90 101 78 93 104 83 99 111 87 104 116 93 110 124 97 115 129 104 123 138 Total Vent Height "H" 3" Common Vent Diameter 4" 5" 6" 7" 8" 10" 12" 14" 16" Combined Appliance Input Rating in Thousands of Btu Per Hour 6' 8' 10' 15' 20' 30' 40' 60' 80' 100' – – – – – – – – – – 65 73 79 91 102 118 131 NR NR NR 103 114 124 144 160 185 203 224 NR NR 6" 7" Vent Connector Diameter-D 8" 10" 12" 14" 3" 16" 18” 20" 22" 24" 1180 1335 1510 1255 1420 1610 1310 1490 1690 1420 1610 1835 1510 1710 1945 1645 1855 2110 1735 1965 2240 1890 2150 2450 1425 1610 1830 1520 1720 1950 1585 1800 2040 1720 1950 2220 1830 2070 2350 1990 2240 2550 2100 2380 2710 2280 2590 2960 1700 1920 2180 1810 2050 2320 1890 2150 2430 2050 2320 2640 2190 2470 2800 2370 2670 3040 2500 2830 3230 2720 3090 3520 18" 20" 22" 24" 1345 1510 1645 1910 2140 2520 2830 3320 3710 4050 1660 1860 2030 2360 2640 3110 3500 4100 4590 5000 1970 2200 2400 2790 3120 3680 4150 4850 5420 5920 2390 2680 2920 3400 3800 4480 5050 5900 6600 7200 Maximum Appliance Input Rating in Thousands of Btu Per Hour 104 142 185 289 416 577 755 955 124 168 220 345 496 653 853 1080 139 189 248 386 556 740 967 1225 109 148 194 303 439 601 805 1015 129 175 230 358 516 696 910 1150 145 198 258 402 580 790 1030 1305 113 154 200 314 452 642 840 1060 134 182 238 372 536 730 955 1205 150 205 268 417 600 827 1080 1370 120 163 214 333 480 697 910 1150 142 193 253 394 568 790 1030 1305 160 218 286 444 640 898 1175 1485 125 171 224 347 500 740 965 1225 149 202 265 414 596 840 1095 1385 168 228 300 466 672 952 1245 1575 134 182 238 372 536 805 1050 1330 158 215 282 439 632 910 1190 1500 178 242 317 494 712 1035 1350 1710 140 190 248 389 560 850 1110 1405 166 225 295 461 665 964 1260 1590 187 253 331 520 748 1100 1435 1820 150 204 266 417 600 926 1210 1530 178 242 316 494 712 1050 1370 1740 200 272 355 555 800 1198 1565 1980 147 163 178 206 229 266 295 324 344 NR 200 223 242 280 310 360 405 440 468 479 260 290 315 365 405 470 525 575 610 625 410 465 495 565 640 740 820 900 955 975 588 652 712 825 916 1025 1180 1380 1540 1670 815 912 995 1158 1290 1525 1715 2010 2250 2450 1065 1190 1300 1510 1690 1990 2240 2620 2930 3200 See Figure 3 and Notes for Multiple Appliance Vents. April 2011R (Reviewed March 1996) AOSTD63110 C 013.0 TECHNICAL DATA VENTING CAPACITY OF A SINGLE-WALL METAL PIPE OR TYPE B ASBESTOS CEMENT VENT 14.1 14.2 Vent Connector Capacity Vent Connector Diameter-D Total Vent Height “H” Connector Rise “R” 3" 1' 2' 3' 1' 2' 3' 1' 2' 3' 21 28 34 23 30 35 25 31 36 6'-8' 15' 30' and up 4" 5" 6" 7" 8" Maximum Appliance Input Rating in Thousands of Btu Per Hour 40 53 61 44 56 64 49 58 68 68 86 98 77 92 102 84 97 107 102 124 147 117 134 155 129 145 164 146 178 204 179 194 216 190 211 232 205 235 275 240 265 298 270 295 321 Common Vent Diameter 4" 6' 8' 10' 15' 20' 30' 50' 48 55 59 71 80 NR NR 5" 6" 7" 8" 10" 12" Combined Appliance Input Rating In Thousands of Btu Per Hour 78 89 95 115 129 147 NR 111 128 136 168 186 215 NR 155 175 190 228 260 300 360 205 234 250 305 340 400 490 Total Vent Rise Height Connector “H” “R” 1' 2' 3' 1' 2' 3' 1' 2' 3' 6'-8' 15' 30' and up 320 365 395 480 550 650 810 NR 505 560 690 790 940 1190 3" Vent Connector Diameter-D 4" 5" 6" 7" Maximum Appliance Input Rating In Thousands of Btu Per Hour 21 28 34 23 30 34 24 31 35 39 52 61 43 54 63 47 57 65 66 84 97 73 88 101 80 93 105 100 123 142 112 132 151 124 142 160 140 172 202 171 189 213 183 205 229 8" 200 231 269 225 256 289 250 282 312 Common Chimney Capacity Total Vent Height “H” Common Vent Capacity Total Vent Height “H” CAPACITY OF A MASONRY CHIMNEY AND SINGLE-WALL VENT CONNECTORS Single-Wall Vent Connector Capacity 6' 8' 10' 15' 20' 30' 50' Minimum Internal Area of Chimney-”A” Square Inches 19 28 38 50 78 113 Combined Appliance Input Rating in Thousands of Btu Per Hour 45 52 56 66 74 NR NR 71 81 89 105 120 135 NR 102 118 129 150 170 195 NR 142 162 175 210 240 275 325 245 277 300 360 415 490 600 NR 405 450 540 640 740 910 See Table 12.3 Page C AOSTD63100 for Masonry Chimney Liner Sizes. 012.0 for Masonry Chimney Liner Sizes. See Figure FIgure 4 and and Notes Notes for for Multiple Multiple Appliance ApplicanceVents. Vents. See Figure 3 and Notes for Multiple Appliance Vents. 1. WATER HEATER VENT CONNECTOR SIZE EXAMPLE OF MULTIPLE VENT DESIGN Using Table 12-1 read down Total Vent Height “H” column to 15 feet and read across 1 foot connector rise “R” line to Btu rating equal to or higher than water heater input rating. This figure shows 53,000 Btu and is in the column for four-inch connector. Since this is in excess of the water heater input it is not necessary to find the maximum input for an 18 foot minimum total vent height. Use a four-inch connector. 2. FURNACE VENT CONNECTOR SIZE Under Vent Connector Tables read down Total Vent Height “H" column to 15 foot and read across 2 foot Connector Rise “R” line. Note 5 inch vent size shows 99,000 Btu per hour or less than furnace input. However, with 20 foot Total Height read across 2 foot connector rise line. Note 5 inch vent size shows 104,000 Btu per hour. Since 18 foot height is 3/5th of difference between 15 and 20 foot heights take difference between 99,000 and 104,000 or 5,000 and add 3/5ths of this to 15 foot figure of 99,000, 99,000 + 3,000 = 102,000 which is maximum input for 18 foot Total Vent Height. Therefore a 5-inch connector would be the correct size for the furnace, providing the furnace had a five-inch or smaller draft hood outlet. 3. COMMON VENT SIZE Total input to Common Vent is 145,000 Btu. Note that for 15 foot Total Vent Height “H” maximum Btu for 5 inch vent is 144,000. For 20 foot Total Vent Height “H” maximum Btu for 5 inch vent is 160,000. Therefore for 18 foot Total Vent Height maximum allowable input would be 3/5th of difference between 144,000 and 160,000 = 3/5 X 16,000 or 9,600. 144,000 + 9,600 = 153,600 which is greater than total input to common vent. Therefore common vent can be 5 inch diameter pipe. AOSTD63110 C 014.0 © A. O. Smith Corp., 1983 2011 Printed in U.S.A.