Dr Audih alfaoury 1 Sub-stations are important part of power system. At many places in the line of the power system(T&D) it may be necessary to change some characteristic such as (voltage, frequency, p.f. etc.) of electric supply. This is accomplished by suitable apparatus called sub-station. The following are the important points must take in consideration while laying out a sub-station : ( I ) It should be located at a proper site. As far as possible, it should be located at the centre of the load. (II) It should provide safe and reliable arrangement. For safety, and operation. (III) It should provide clearances for maintenance and facilities for carrying out repairs. (IV) It should be easily operated and maintained. (V) It should involve minimum capital cost. According to design feature ,the sub-station has many components (e.g. circuit breakers, switches, fuses, instruments etc.) which ensure continuous and reliable service, the sub-stations are classified as : (i) Pole-mounted sub-station (ii) Underground sub-station (iii) Outdoor sub-station (iv) Indoor sub-station Pole-Mounted Sub-Station Low tension oil circuit breaker Underground sub-station Underground Sub-Station: The underground sub-station requires more careful consideration than other types of sub-stations, the following points must be kept in view: (i) The size of the station should be as minimum as possible. (ii)Should be reasonable access for equipment and personnel. (iii)Should be provision(secured) for emergency lighting and protection against fire. (iv) Should be good ventilation. (v)Should be provision for remote indication of the rise in temperature so that H.V. supply can be disconnected. (vi) The transformers, switches and fuses should be air cooled. Symbols for Equipment in Sub-Stations 1- Security of supply: Security of supply may be considered in terms of the effect of the loss of supply ( arising from fault conditions or from outages due to maintenance). The British Code for the design of high voltage open terminal substations BS 7354 categorizes substation service continuity as: Category1: No outage necessary. Category2 : Short outage necessary to transfer the load to an alternative circuit for maintenance or fault conditions. Category3: Loss of a circuit or section. Category4: Loss of substation. Mesh arrangement disconnector CB1 CB3 CB2 (all busbars, circuit breakers (CB)and disconnectors must be capable of carrying the combined loads of both transformers and line circuit power transfers). 3-Normal operation is with the bypass disconnectors or optional circuit breaker open so that both transformers are not disconnected for a single transformer fault. Three switch mesh By pass An arrangement known as a three switch mesh. 1-only three circuit breakers controlling four circuits. 2-Any circuit breaker may be maintained at any time without disconnecting that circuit. 4-In case of a fault on one transformer circuit, with disconnects the healthy transformer circuit can continue the supply without affecting the feeders. 5- A fault on the bus section circuit breaker causes complete substation shutdown until isolated and power restored. A full mesh is composed from three switch arrangement for multiple circuit sub-stations is the full mesh layout as shown in Fig. section circuit breaker Full mesh 1- Operation of two circuit breakers is required to connect or disconnect a circuit and disconnection involves opening the mesh. 2- Line or transformer circuit disconnectors may then be used to isolate the particular circuit and the mesh reclosed. 3- Circuit breakers may be maintained without loss of supply . (the particular circuit may be fed from an alternative route around the mesh). 4- Busbar faults will only cause the loss of one circuit. Ring The ring busbar offers increased security compared to the single busbar arrangement. A typical scheme which would occupy more space than the single busbar arrangement is shown in Fig. (I) Category 1 : within the substation for maintenance or fault the 1 and 1⁄2 breaker scheme under maintenance conditions in the circuit breaker area is used . Isolator Circuit Breaker Isolator feeder Bypass isolator for circuit breaker maintenance GIS 132kV substation double switchyard arrangement indoor The circuit breaker bypass facilities and security of the mesh arrangement coupled with some of the flexibility of the double busbar scheme. This scheme is used at important high voltage sub-stations and large generating. 1- Additional costs of circuit breakers are involved together with complex protection arrangements. 2- It is possible to operate with any one pair of circuits, or group of pairs of circuits separated from the remaining circuits. 3- The circuit breakers and other system components must be rated for the sum of the load currents of two circuits. 4- High security against loss of supply. 5- High cost (II) Category2 The double busbar arrangement consists of two bus-bars, a “main” bus-bar and a “spare” bus-bar. Is the most popular open terminal outdoor substation throughout the world. It has the flexibility to allow the grouping of circuits onto separate busbars with facilities for transfer from one busbar to another for maintenance or operational reasons. A typical double busbar with transfer busbar arrangement is shown in Fig. 1-When circuit breakers are under maintenance the protection is arranged to trip the bus coupler breaker. 2-The system is considered to offer less flexibility buscoupler Double busbar scheme with bypass disconnector and buscoupler switch bypass disconnector bus-coupler busbar 1. Each circuit may be connected to either busbar using the busbar selector disconnectors. On-load busbar selection may be made using the bus-coupler circuit breaker. 2. Motorized busbar selector disconnectors may be used to reduce the time to reconfigure the circuit arrangements. 3. Busbar and busbar disconnector maintenance may be carried out without loss of supply to more than one circuit. 4. The use of circuit breaker bypass isolator facilities is not considered to offer substantial benefits since modern circuit breaker maintenance times are short and in highly interconnected systems alternative feeder arrangements are normally possible. 5. A variant on the scheme uses a ‘wrap around’ busbar layout arrangement as shown in Fig. in order to reduce the length of the substation. (III) Category 3 -Single busbar scheme is use Simple to operate, in figure we illustrates a five circuit breaker single busbar arrangement with four feeder circuits, one bus section and ten disconnectors. 1. Each circuit is protected by bus section its own circuit breaker and hence plant outage does not necessarily result in loss of supply. 2. A fault on a feeder or transformer circuit breaker causes loss of the transformer and feeder circuit one of which may be restored after isolating the faulty circuit breaker. bus section O.C.B oil circuit breaker C.T current transformer L.A lightning arrester P.T. Power transformer 3. A fault on a bus section circuit breaker causes complete shutdown of the sub-station. All circuits may be restored after isolating the faulty circuit breaker . 4. A busbar fault causes loss of one transformer and one feeder. Maintenance of one busbar section or disconnector will cause the temporary outage of two circuits. 5. Maintenance of a feeder or transformer circuit breaker involves loss of that circuit. The introduction of bypass isolators between the busbar and circuit isolator as in( Fig.a) .allows circuit breaker maintenance without loss of the circuit. Bypass may also be obtained by using a disconnector on the outgoing ways between two switchgear bays (Fig. b). Fig. b Fig.a (IV) Category 4 Loss of substation : Single bus bar without by pass section in busbar ,this arrangement is used the radial busbar decreased security compared to the double busbar arrangement since no alternative power flow routes are available. A typical scheme which would occupy less space than the other arrangements and is cheaper schemes. A fault on a feeder or transformer circuit breaker causes loss of the transformer and feeder circuit one of which may be restored after isolating the faulty circuit breaker 2 Extendibility :The design should allow for future extendibility. Adding bays of switchgear to a substation is normally possible ,as well as addition of overhead line or cable feeder bays are required then busbar disconnectors may be installed at the outset (known as ‘skeleton bays’). The use of gas insulated switchgear (GIS) not permit to add any future extension work, but an open terminal switchyard arrangement allows the user a choice of switchgear for future extension work. 3- Maintainability The design must take into account the electricity supply company system planning and operations procedures together with a knowledge of reliability and maintenance requirements for the proposed substation equipment. Portable earthing points and earthing switch/interlock requirements will also need careful consideration. Similarly standard minimum clearances for safe working and access to equipment with safety clearances. Clearances and ground clearances based on British practice (BS7354) are given in table The figures illustrate diagrammatically the clearances required between the different items of substation equipment 4 Operational flexibility Two transformer substation operation with the facility to take out of service one and restore to service, without loss of supply would be a normal design consideration. In general a multiple busbar arrangement will provide greater flexibility than a ring busbar. 5 Protection arrangements The design must allow for the protection of each system element by adding suitable CT locations to ensure overlapping of protection zones. The number of CB that require to be tripped, the type of protection and extent and type of mechanical or electrical interlocking must be considered. 6 Short circuit limitations In order to keep fault levels down parallel connections should be avoided. The system split is required. Multi-busbar arrangements with sectioning allow the system to be split or connected through a fault limiting reactor. It is also possible to split a system using circuit breakers in a mesh or ring type substation layout. 7 Land area The cost land in a densely populated area is considerable. Therefore the compact substation design is use of indoor gas insulated switchgear (GIS) substation designs or by using such configurations as the transformer feeder substation layout. 8 Cost A satisfactory cost comparison between different substation layout designs is extremely difficult because of the differences in performance and maintainability. plant, structural, civil and space costs, etc.. Diagram of 66/11 kV Sub-Station That part of power system which distributes electric power for local use is known as distribution system. It generally consists of feeders, distributors and the small cable. There is no definite line between transmission and distribution according to voltage or bulk capacity. In general, the a.c. distribution system is the electrical system between the step-down substation fed by the transmission system and the consumers. The a.c. distribution system is classified into: a) primary distribution system. which operates at voltages higher than general utilization and handles large electrical energy. The most commonly used primary distribution voltages are 11 kV, 6·6kV and 3·3 kV. The, primary distribution is carried out by 3-phase, 3-wire system. primary distribution system b) secondary distribution system. It is that part of a.c. distribution system which includes the range of voltages for ultimate consumer. The secondary distribution employs 400/230 V, 3-phase, 4-wire system. The substations are situated near the consumers’ localities and contain step-down transformers. At each distribution substation, the voltage is stepped down to 400V and power is delivered by 3-phase,4-wire a.c. system. The voltage between any two phases is 400 V and between any phase and neutral is 230V. The single phase domestic loads are connected between any one phase and the neutral, whereas 3-phase 400 V motor loads are connected across 3-phase lines directly. secondary distribution system Connection Schemes of Distribution System 1. Radial System: In this system, separate feeders radiate from a single substation and feed the distributors at one end only. (a) The consumers suffering from any fault on the feeder which cuts off supply who are on the side of the fault away from the substation. (b) The consumers at the distant end would be subjected of voltage fluctuations . (c)) Due to these limitations, this system is used for short distances only. 2-Ring main system: In this system, the distribution transformers form a loop. The loop circuit starts from the substation bus-bars, makes a loop through the area to be served, and returns to the substation. The ring main system has the following advantages: (a) There are less voltage fluctuations at consumer’s terminals. (b) The system is very reliable as each distributor (is fed via two feeders). Design Considerations in Distribution System Design of distributors requires careful consideration. (i) Feeders: A feeder is designed from the point of view of its current carrying capacity but voltage drop consideration is not important. (ii) Distributors. A distributor is designed from the point of view of the voltage drop in it (± 6% of rated value). The size and length of the distributor should be such that voltage at the consumer’s terminals is within the permissible limits. That’s all…………………Thanks