PRODUCT DATA
Leviton’s photocell sensors precisely monitor
either task or ambient light levels. As part of a
Leviton lighting and energy solution, photocells
work with other components in the system
to automatically adjust light levels to a userdefined level. Photocells are most suitable for
installation in rooms with windows and open
spaces receiving substantial ambient light.
Photocells must be hardwired to a compatible
Leviton lighting control system. The photocell
measures ambient light in a specific area and
sends this data to a dimmer or relay that, in
turn, adjusts fixtures to a constant lighting
level as measured in that specific area. Daylight
harvesting is achieved as lights in a room (with
windows or significant, artificial ambient light)
automatically brighten or dim depending on how
much light the photocell detects.
BENEFITS
• Constant lighting at the optimal level for
greater visual comfort and acuity, which
contributes to improved productivity
• Provides convenient, automatic hands-free
daylight harvesting when integrated with
Leviton lighting control products
• Lowers electric bills by reducing usage of
lighting where ambient natural light is also
present
• Lumen maintenance opportunity compatible
DAYLIGHT HARVESTING
With daylight harvesting, ambient (often natural)
light supplements in-room, artificial light in
order to keep a constant lighting level while
simultaneously saving energy. This ensures
unnecessary overhead lighting remains dimmed
or OFF. This constant level is programmed into
a compatible control device. Once hardwired to
the photocell, the dimmer or relay receives the
photocell’s real-time light measurement and
maintains a steady level within the photocell’s
area of detection.
RULES OF OPERATION
Measured light level = Light Maintain Level
Action: Output to lights remains constant
Measured light level < Light Maintain Level
Action: Lights are brightened
Measured light level > Light Maintain Level
Action: Lights are dimmed
Footcandles
Energy
Savings
Begin
Light
Maintain
Level
Min.
Light
Level
Perceived
Light
Level
6AM
8AM
10AM
NOON
Light generated from
fixture attached to Leviton
Lighting Control System
2PM
4PM
6PM
Ambient light
Leviton Manufacturing Co., Inc. Lighting & Energy Solutions
20497 SW Teton Avenue, Tualatin, OR 97062 • Telephone: 1-800-736-6682 • Fax: 503-404-5594 • Tech Line (6:00AM-4:00PM P.S.T. Monday-Friday): 1-800-959-6004
© 2015 Leviton Manufacturing Co., Inc. All rights reserved. Subject to change without notice.
Photocells
Photocells
Photocells
PRODUCT DATA
FEATURES
• Indoor photocells designed with a flat Fresnel lens looks
downward in a 60° cone of reference to measure actual
light on the work surface and reduce the influence of
stray light striking the photocell from nearby windows or
incidental side lighting
• Outdoor photocells are IP54 rated to guarantee ultimate
protection from dirt, dust, oil and other non-corrosive
material
• Measures light from any source in the visible spectrum
within a 60º cone or 180º angle of response depending on
the model
• ODC0P-00W photocell with 60° clear lens operates
between 1-1,600FC. ODC0P should be surface mounted or
direct to ceiling box
• ODC0P-S0W switching photocell with 60° clear lens
operates between 1-1,600FC. ODC0P should be surface
mounted or direct to ceiling box
• ODC0P-D0W dimming photocell with 60° clear lens
operates between 1-1,600FC. ODC0P should be surface
mounted or direct to ceiling box
• PCCxD-00W, PCCxS-00W, PCCSD-00W line voltage
photocells with 60° clear lens for applications where zone
control switching, dimming, and demand response are
required. Operates between 1-1,600FC. PCC photocells
should be mounted to the ceiling in standard 4”x4” square
or octagon electrical boxes
• PCIND-000 indoor photocell with 60° clear Fresnel lens
is default setting = 75-800FC sensing range; can be field
adjusted to 800FC max sensing range. PCIND should be
mounted to the ceiling, facing down
• PCIND-0SV side view photocell for applications where
ceiling mounting is required yet the view should be of
the lighting entering the space through a window; or, for
installation to the wall of skylights where the view should
be up into the skylight. Default setting = 0-30FC sensing
range; can be field configured with a jumper for a 3FC,
30FC, 300FC, or 600FC max sensing range
• PCOUT-000 outdoor photocell is enclosed in a
weatherproof housing with a visor for shading and lens
protection. Default setting = 50-750FC sensing range
• PCOUT-0SV side view photocell for applications where
wall mounting is required yet the view should be of the
lighting entering the space through a top/side and/or
face of the photocell. Reference placement diagrams.
Default setting = 0-30FC sensing range; can be field
configured with a jumper for a 3FC, 30FC, 300FC, or 600FC
max sensing range
• PCATR-000 atrium photocell with opaque dome lens
filters 33% of light level in upper atrium. Default setting
= 215-2,690FC sensing range; can be field adjusted to
2,690FC max sensing range
• PCSKY-000 skylight photocell with dark dome lens
filters 90% of light level in skylight. Default setting =
1,076-8,072FC sensing range; can be field adjusted to
8,072FC max sensing range
DIMENSIONS
PHOTOCELL
(ODC0P)
Diameter: 2.51”
0.76”
0.23”
0.99”
PHOTOCELL
(PCCxD, PCCxS, PCCSD)
1.16”
4.81”
1.09”
0.94”
2.39”
OUTDOOR
(PCOUT)
INDOOR
(PCIND)
1.85”
1.15”
1.35”
1.28”
SIDE VIEW PHOTOCELL
(PCIND-0SV/PCOUT-0SV)
1.36”
Diameter: 2.04”
ATRIUM/SKYLIGHT
(PCATR/PCSKY)
2.25”
1.28”
PHOTOCELL PLACEMENT
ODC0P/PCIND INDOOR PHOTOCELL MOUNTING LOCATION
6-8 FT.
ATRIUM PHOTOCELL MOUNTING LOCATION
ODC0P,
PCIND or
PCCxx
PCATR
Ideal photocell location is in the
middle of the atrium glass pointing
toward the glass
REFLECTING WALL USING INDOOR SENSOR
LOW VOLTAGE PHOTOCELL WITH OCCUPANCY
SENSOR ROOM CONTROL
Violet 1-10V Dim Out
Gray 1-10V Common
18”
Sconces
Orange
Red
Black
PCIND, PCCxx
ODC0P-D0W
Low Voltage Photocell
Light well - with sconces - (UP or UP/DOWN)
Mount photocell in elevation on centerline
of fixture. Do not mount directly in line
with sconces.
PCIND
LOAD
Violet 1-10V Dim Out
LOAD
Gray 1-10V Common
Blue
Red
Black
60
Blue
White
Black
OPP20-RD3
Blue
Light well - no sconces - indoor photocell
SKYLIGHT APPLICATION WITH SKYLIGHT PHOTOCELL
Gray
Blue
Occupancy Sensor
Red
H
Black
NOTE: Power Pack and the load switched by the power pack MUST be fed from the same phase.
OUTDOOR PHOTOCELL MOUNTED IN 1/2” CONDUIT
Top of photocell should
be level with top of
skylight curb
North
Snow Line
Photocell in 1/2” conduit.
Photocell must be at
least 12” from side of
skylight and facing up
UNISTRUT
NOTE:
Support conduit from
unistrut as required
per NEC
1/4” ANGLE
SUPPORT
Outdoor photocell mounted horizontally on roof or equal,
facing northern sky
Hooded portion on top, pointed away from any nighttime
light sources
JUNCTION BOX
Leviton Manufacturing Co., Inc. Lighting & Energy Solutions
20497 SW Teton Avenue, Tualatin, OR 97062 • Telephone: 1-800-736-6682 • Fax: 503-404-5594 • Tech Line (6:00AM-4:00PM P.S.T. Monday-Friday): 1-800-959-6004
© 2015 Leviton Manufacturing Co., Inc. All rights reserved. Subject to change without notice.
Photocells
N
PRODUCT DATA
INSTALLATION
• Low Voltage Class 2 Wiring
- Connect directly to dimmer or relay panel
SPECIFICATIONS
ODC0P00W
Input Voltage
ODC0PS0W
ODC0PD0W
24VDC
PCCxS00W
12-24VDC
Input Current
IP Rating
30mA
32
30
1-1,600 FC
(10-16,000 LUX)
Output
Voltage
Switched:
12-24VDC/
Dimmed:
1-10V Sinking
12-24VDC
N/A
Operating
Temperature
Range
32-131°F
(0 -55°C)
32-104°F
(0-40°C)
Storage
Temperature
Range
14-185°F
(-10-85°C)
14-160°F
(-26-71°C)
Warranty
Limited 5-Year Warranty
PCIND000
PCIND0SV
PCOUT000
PCOUT0SV
Input Voltage
24VDC
Input Current
10mA
IP Rating
20
Default
Range
75-800 FC
(807- 8,611 LUX)
Output
Voltage
Operating
Temperature
Range
PCCSD00W
120-277VAC
10mA
Default Range
Photocells
PCCxD00W
54
PCSKY000
54
65
0-30 FC
(0-322 LUX)
10VDC full output
12-140°F
(-11-60°C)
PCTAR000
215-2,690FC
(2,314-2,8954 LUX)
1,076-8,072 FC
(11,581- 8,6886 LUX)
0-10VDC
10VDC full output
-40-122°F
(-40-50°C)
12-140°F
(-11-60°C)
Storage
Temperature
Range
14-185°F
(-10-85°C)
Warranty
Limited 2-Year Warranty
SELECTION
PHOTOCELL
LENS
MOUNTING
ORIENTATION
HEIGHT
DIAMETER
0.99” (25.14mm)
2.51” (63.75mm)
1.09” (27.91mm)
1.09” (27.91mm)
2.00” (50.8mm)
1.00” (25.4mm)
ODC0P-00W
ODC0P-S0W
ODC0P-D0W
PCCxD-00W
Clear
Ceiling
Down
PCCxS-00W
PCCSD-00W
PCIND-000
Fresnel
PCIND-0SV
Diffuse
Ceiling/Wall
Up/Down
1.36” (34.54mm)
2.04” (51.81mm)
PCOUT-000
Clear Hood
1/2” IPT
Horizontal
1.85” (46.99mm)
1.28” (32.51mm)
PCOUT-0SV
Diffuse
Ceiling/Wall
Up/Down
1.36” (34.54mm)
2.04” (51.81mm)
2.25” (57.15mm)
1.28” (32.51mm)
PCATR-000
PCSKY-000
Dome/Frost
1/2” IPT
Horizontal
Up
ADJUSTABLE CORRESPONDING FC RANGES
SENSOR
MAXIMUM
ODC0P-00W
ODC0P-S0W
ODC0P-D0W
PCCxD-00W
1-1,600 FC
PCCxS-00W
PCCSD-00W
PCIND-000
75-800 FC
PCIND-0SV
3, 30, 300 or 600 FC
PCOUT-000
50-750 FC
PCOUT-0SV
3, 30, 300 or 600 FC
PCATR-000
215-2,690 FC
PCSKY-000
1,076-8,072 FC
ORDERING INFORMATION
DESCRIPTION
ODC0P-00W
Photocell
ODC0P-S0W
Switching Photocell
ODC0P-D0W
Dimming Photocell
PCCxD-00W
Line Voltage Dimming Photocell
PCCxS-00W
Line Voltage Switching Photocell
PCCSD-00W
Line Voltage Dimming/Switching
Photocell
PCIND-000
Indoor Photocell
PCIND-0SV
Indoor Side View Photocell
PCOUT-000
Outdoor Photocell
PCOUT-0SV
Outdoor Side View Photocell
PCATR-000
Atrium Photocell
PCSKY-000
Skylight Photocell
COLOR
White
Leviton Manufacturing Co., Inc. Lighting & Energy Solutions
20497 SW Teton Avenue, Tualatin, OR 97062 • Telephone: 1-800-736-6682 • Fax: 503-404-5594 • Tech Line (6:00AM-4:00PM P.S.T. Monday-Friday): 1-800-959-6004
© 2015 Leviton Manufacturing Co., Inc. All rights reserved. Subject to change without notice.
Photocells
CAT. NO.
Photocells
PRODUCT DATA
Leviton Manufacturing Co., Inc. Lighting & Energy Solutions
20497 SW Teton Avenue, Portland, OR 97062 Telephone: 1-800-736-6682 • FAX: 503-404-5594 • Tech Line (6:00-4:00 Monday-Friday): 1-800-959-6004
Leviton Manufacturing Co., Inc. Global Headquarters
201 N. Service Rd. Melville, NY 11747-3138 • Tech Line: 1-800-824-3005 • Fax: 1-800-832-9538
Leviton Manufacturing of Canada, Ltd.
165 Hymus Boulevard, Pointe Claire, Quebec H9R 1E9 • Telephone: 1-800-469-7890 • FAX: 1-800-563-1853
Leviton S. de R.L. de C.V.
Lago Tana 43, Mexico DF, Mexico CP 11290 • Tel. (+52) 55-5082-1040 • FAX: (+52) 5386-1797 • www.leviton.com.mx
Visit our Website at: www.leviton.com/les
2015 Leviton Manufacturing Co., Inc. All rights reserved. Subject to change without notice.
G-7189E/D15-AA
REV APR 2015