Doepke Residual Current Circuit Breakers Doepke RCCBs meet EN61008 / EN62423 To reduce the risk of death or serious injury from electrocution and or fire, RCCBs are provided in AC circuits as an additional means of protection and must operate reliably when other means of protection have failed. Specifying, Purchasing and installing low quality products could endanger people's lives and put property at risk. Doepke RCCBs are manufactured in Doepke factories based in Germany, with individual testing and recording of the trip characteristic and a unique serial number marked on each product. This ensures that every product leaves the factory in safe working order and conforms to the requirements of the relevant standard or standards. RCCB's General Principles for Use Selection and installation: by “skilled/instructed” (electrical) persons only. Refer to the IET Wiring Regulations for guidance on the selection and use of RCCBs to meet the requirements for new and existing installations. The references below are based on BS 7671: 2008 incorporating Amendment No 3: 2015. Protection in the event of indirect contact - Fault Protection. Doepke RCCBs manufactured to the above standard are designed to protect persons against the hazards associated with indirect contact where exposed conductive parts of the installation are connected to a suitable earth electrode - see Regulation 411. Protection in the event of direct contact - Basic Protection. Doepke RCCBs with a trip rating not exceeding 30 mA, meet the requirements of Regulation 415 based on the supplementary bonding requirements. Using RCCBs as an additional means of protection does not negate the use of basic protection methods required under regulation 411. Fire protection. Doepke RCCBs with a trip rating not exceeding 300 mA meet the requirements of Regulation 532, however within the Regulations there are specific requirements where 300mA trip rating may not be appropriate - for example overhead heating see clause 422.3.9 Types of RCCB required by the IET Wiring Regulations. In addition to standard RCCBs (Type AC) Doepke manufacture a wide range of devices with specific functions for different applications. Please contact us if you require a product that is not listed in our standard documentation. Type S: used in applications where RCCBs have to be connected in series to achieve discrimination (Fig. 1) between upstream and downstream devices - see clause 5.31.2.9 and example application 740.411, or 534.2.6 ( Doepke Type S RCCBs are designed to have immunity to transient wave forms <5kA 8/20µs) Type A: used in applications with residual sinusoidal alternating currents and pulsating direct currents with a maximum of 6 mA smooth DC. - see clause 710.411.3.2 and 722.531.2.101 Type B: (IEC 62423) used in applications where in addition to the above, smooth DC residual currents above 6mA are present under certain fault conditions - see clause 712.411.3.2.1.2 and 722.531.2.101 Type AKV: used in applications where the RCCB could be subject to in rush currents < 3000 A , which would cause tripping of standard RCCB - see clause 534.2.6 Type F: used in applications where the RCCB is subjected to mixed frequency leakage currents, such as single phase inverter controlled washing machines, mixers or power tools. Type EV: used in electrical vehicle charging applications where the RCCB must trip if the smooth DC leakage current exceeds 6mA. 6 www.doepke.co.uk SELECTION & APPLICATION Operating and Installation Instructions for Residual Current Circuit Breakers DFS2, DFS4 Mounting position: Any position. Installation: By clipping onto DIN EN 50022 rails. Electrical connections: Take all phase conductors and the neutral conductor (N) through the switch. The direction of the flow of energy can be either way, i.e. the mains or the load can be connected to the upper or lower row of terminals. To ensure that the built-in testing system operates properly when 4-pole RCCBs are used in 2-pole applications, use the terminals as per wiring diagram. Aluminium conductors must be scraped and greased just before they are connected up to the terminals. Testing: Testing of the entire protective system when putting into operation must be performed according to the specifications of the valid national installation regulations. Test quarterly by pressing the test button T for stationary equipment and once every working day for mobile equipment. Please note that the above fuses provide no overload protection. At the design stage check that the downstream overload protection does not exceed the total rated current of the RCCB. Operating Temperature Range: Doepke RCCBs are calibrated for operation between +40°C to -5°C. For operation down to -25°C the maximum values of earth fault loop impedance defined in Table 41.5 must be reduced by 20 %. Voltage Range (Test Circuit Operation) DFS2 (230V 50Hz) and DFS4 (400V 50Hz) Test circuits will operate down to approximately 50% of the nominal voltage. For operation on a 110V supply order a 110V unit. Frequency Range DFS2 and DFS4 are calibrated to operate on 50 Hz supplies, for any other frequency order a special Doepke RCCB calibrated for the nominal supply frequency. General service and warning indications: Doepke residual current circuit breakers have been carefully tested at several stages of production and have left the factory in perfect condition witrh regard to safety. To ensure safe operation, please observe the following instructions and warnings. 1. Installation may only be performed by an authorized electrican, who is acquainted with the relevant national installation regulations. 2. Residual current circuit breakers without additional protective housings may be stored and operated in dry, low- dust areas only. Corrosive atmospheres must also be avoided. 3. User´s must be reminded, that all devices should be periodically tested, using the test button T. 4. Trips caused by leakage current due to surge voltage cannot be completely ruled out even with surge current proof RCCBs. In cases where an interruption in power supply could constitute a hazard to persons or animals or cause serious damage to property, the earth leakage system should comprise selective RCCBs with increased surge current strength and over voltage protection. In special cases the system should be monitored with an auxiliary contact on the RCCBs and a suitable signaling device. 5. If the device is opened the warranty becomes void! sales@doepke.co.uk 7 Doepke A world leader in RCCB design and manufacture Doepke produces over 2500 different variations of residual current circuit breakers. These RCCBs have a contact position indicator, in addition to a reset position, which shows whether the device has been switched off manually or has tripped due to a fault. They accept both pin and fork busbar, the pin terminal having a maximum cross-section of 50mm. There is also a facility to accept a circuit identification label behind a clear plastic window. The wide range of current values extends from 16 to125 amps in all the standard sensitivity settings. All these products have been manufactured to BSEN 61008. All our RCCBs are compatible with our MCB range’s in both size and terminal height. They also accept our half module auxilary switch which can be retrofitted by the installer. The terminals will accept a 50mm2 multicore cable thereby facilitating direct connection to the RCCB. The operating voltage of our RCCBs permits use in 110v circuits. The type AC RCCBs provide automatic protection in the event of a neutral/earth and phase/earth fault. The 10mA and 30mA are suitable for the protection of humans, whilst the 100mA, 300mA and 500mA are used to protect equipment and machinery. The use of time delay RCCBs enable the contractor to provide several RCCBs with selective disconnection. 8 www.doepke.co.uk Residual Current Circuit Breakers Type AC Type AC RCCBs For use in 50Hz AC electrical circuits feeding loads which do not interfere with the standard AC supply. Residual Current Devices (RCCBs) Type AC 2 Pole 2 Module Rating Sensitivity 16A 16A 16A 16A 16A 25A 25A 25A 25A 40A 40A 40A 40A 63A 63A 63A 63A 80A 80A 80A 80A 100A 100A 100A 100A 125A 125A 125A 125A 10mA 30mA 100mA 300mA 500mA 30mA 100mA 300mA 500mA 30mA 100mA 300mA 500mA 30mA 100mA 300mA 500mA 30mA 100mA 300mA 500mA 30mA 100mA 300mA 500mA 30mA 100mA 300mA 500mA Reference 4 Pole 4 Module Reference 16-2/0.01.DFS2 16-2/0.03.DFS2 16-2/0.10.DFS2 16-2/0.30.DFS2 16-2/0.50.DFS2 25-2/0.03.DFS2 25-2/0.10.DFS2 25-2/0.30.DFS2 25-2/0.50.DFS2 40-2/0.03.DFS2 40-2/0.10.DFS2 40-2/0.30.DFS2 40-2/0.50.DFS2 63-2/0.03.DFS2 63-2/0.10.DFS2 63-2/0.30.DFS2 63-2/0.50.DFS2 80-2/0.03.DFS2 80-2/0.10.DFS2 80-2/0.30.DFS2 80-2/0.50.DFS2 100-2/0.03.DFS2 100-2/0.10.DFS2 100-2/0.30.DFS2 100-2/0.50.DFS2 125-2/0.03.DFS2 125-2/0.10.DFS2 125-2/0.30.DFS2 125-2/0.50.DFS2 16-4/0.01.DFS4 16-4/0.03.DFS4 16-4/0.10.DFS4 16-4/0.30.DFS4 16-4/0.50.DFS4 25-4/0.03.DFS4 25-4/0.10.DFS4 25-4/0.30.DFS4 25-4/0.50.DFS4 40-4/0.03.DFS4 40-4/0.10.DFS4 40-4/0.30.DFS4 40-4/0.50.DFS4 63-4/0.03.DFS4 63-4/0.10.DFS4 63-4/0.30.DFS4 63-4/0.50.DFS4 80-4/0.03.DFS4 80-4/0.10.DFS4 80-4/0.30.DFS4 80-4/0.50.DFS4 100-4/0.03.DFS4 100-4/0.10.DFS4 100-4/0.30.DFS4 100-4/0.50.DFS4 125-4/0.03.DFS4 125-4/0.10.DFS4 125-4/0.30.DFS4 125-4/0.50.DFS4 Time Delay RCCBs Type AC 2 Pole 2 Module Rating Sensitivity 63A 63A 63A 100A 100A 100A 125A 125A 125A 100mA 300mA 500mA 100mA 300mA 500mA 100mA 300mA 500mA Reference 63-2/0.10.DFS2.S 63-2/0.30.DFS2.S 63-2/0.50.DFS2.S 100-2/0.10.DFS2.S 100-2/0.30.DFS2.S 100-2/0.50.DFS2.S 125-2/0.10.DFS2.S 125-2/0.30.DFS2.S 125-2/0.50.DFS2.S 4 Pole 4 Module Reference 63-4/0.10.DFS4.S 63-4/0.30.DFS4.S 63-4/0.50.DFS4.S 100-4/0.10.DFS4.S 100-4/0.30.DFS4.S 100-4/0.50.DFS4.S 125-4/0.10.DFS4.S 125-4/0.30.DFS4.S 125-4/0.50.DFS4.S Some of the above RCCBs are available in the following variations to special order only Surge current resistant KV with short time delay F Frequencies > 50 Hz 500 V 500 V versions sales@doepke.co.uk 9 Doepke Type A For use in 50Hz AC electrical circuits feeding loads which can generate pulsed wave forms on the AC supply. Residual Current Devices (RCCBs) Type A 2 Pole 2 Module Rating Sensitivity 16A 16A 16A 16A 16A 25A 25A 25A 25A 40A 40A 40A 40A 63A 63A 63A 63A 80A 80A 80A 80A 100A 100A 100A 100A 125A 125A 125A 125A 10mA 30mA 100mA 300mA 500mA 30mA 100mA 300mA 500mA 30mA 100mA 300mA 500mA 30mA 100mA 300mA 500mA 30mA 100mA 300mA 500mA 30mA 100mA 300mA 500mA 30mA 100mA 300mA 500mA Reference 16-2/0.01.DFS2.A 16-2/0.03.DFS2.A 16-2/0.10.DFS2.A 16-2/0.30.DFS2.A 16-2/0.50.DFS2.A 25-2/0.03.DFS2.A 25-2/0.10.DFS2.A 25-2/0.30.DFS2.A 25-2/0.50.DFS2.A 40-2/0.03.DFS2.A 40-2/0.10.DFS2.A 40-2/0.30.DFS2.A 40-2/0.50.DFS2.A 63-2/0.03.DFS2.A 63-2/0.10.DFS2.A 63-2/0.30.DFS2.A 63-2/0.50.DFS2.A 80-2/0.03.DFS2.A 80-2/0.10.DFS2.A 80-2/0.30.DFS2.A 80-2/0.50.DFS2.A 100-2/0.03.DFS2.A 100-2/0.10.DFS2.A 100-2/0.30.DFS2.A 100-2/0.50.DFS2.A 125-2/0.03.DFS2.A 125-2/0.10.DFS2.A 125-2/0.30.DFS2.A 125-2/0.50.DFS2.A 4 Pole 4 Module Reference 16-4/0.01.DFS4.A 16-4/0.03.DFS4.A 16-4/0.10.DFS4.A 16-4/0.30.DFS4.A 16-4/0.50.DFS4.A 25-4/0.03.DFS4.A 25-4/0.10.DFS4.A 25-4/0.30.DFS4.A 25-4/0.50.DFS4.A 40-4/0.03.DFS4.A 40-4/0.10.DFS4.A 40-4/0.30.DFS4.A 40-4/0.50.DFS4.A 63-4/0.03.DFS4.A 63-4/0.10.DFS4.A 63-4/0.30.DFS4.A 63-4/0.50.DFS4.A 80-4/0.03.DFS4.A 80-4/0.10.DFS4.A 80-4/0.30.DFS4.A 80-4/0.50.DFS4.A 100-4/0.03.DFS4.A 100-4/0.10.DFS4.A 100-4/0.30.DFS4.A 100-4/0.50.DFS4.A 125-4/0.03.DFS4.A 125-4/0.10.DFS4.A 125-4/0.30.DFS4.A 125-4/0.50.DFS4.A Time Delay RCCBs Type A 2 Pole 2 Module Rating Sensitivity 63A 63A 63A 100A 100A 100A 125A 125A 125A 100mA 300mA 500mA 100mA 300mA 500mA 100mA 300mA 500mA Reference 63-2/0.10.DFS2.A.S 63-2/0.30.DFS2.A.S 63-2/0.50.DFS2.A.S 100-2/0.10.DFS2.A.S 100-2/0.30.DFS2.A.S 100-2/0.50.DFS2.A.S 125-2/0.10.DFS2.A.S 125-2/0.30.DFS2.A.S 125-2/0.50.DFS2.A.S 4 Pole 4 Module Reference 63-4/0.10.DFS4.A.S 63-4/0.30.DFS4.A.S 63-4/0.50.DFS4.A.S 100-4/0.10.DFS4.A.S 100-4/0.30.DFS4.A.S 100-4/0.50.DFS4.A.S 125-4/0.10.DFS4.A.S 125-4/0.30.DFS4.A.S 125-4/0.50.DFS4.A.S Some of the above RCCBs are available in the following variations to special order only Surge current resistant KV with short time delay 10 F Frequencies > 50 Hz 500 V 500 V versions www.doepke.co.uk Residual Current Circuit Breakers Type A RCCBs DFL8 Type A MCCB & RCD module The DFL8 range incorporates type ‘A’ RCD trips with current ratings up to 250 Amps. Each unit comprises: 4 Pole Circuit Breaker (Ics 50kA at 415V & 5kA at 690V) with adjustable overload setting (0.8-1 x In) and short circuit trip (6-10 x In). RCCB trip function module available in non adjustable and adjustable versions (factory fitted). DFL8 A For use in 50Hz AC electrical circuits feeding loads which can generate pulsed wave forms on the AC supply. Residual Current Devices (RCCBs) Type DFL8 A Non adjustable I Rating 100A 125A 160A 200A 250A Sensitivity 30mA 30mA 30mA 30mA 30mA n = 0.03A Reference DFL8 100-4/0.03 A DFL8 125-4/0.03 A DFL8 160-4/0.03 A DFL8 200-4/0.03 A DFL8 250-4/0.03 A Adjustable I n : 0.3A-0.5A-1A Time delay: 60-150-300-450ms Rating 100A 125A 160A 200A 250A Sensitivity Adjustable Adjustable Adjustable Adjustable Adjustable Reference DFL8 100-4/X A DFL8 125-4/X A DFL8 160-4/X A DFL8 200-4/X A DFL8 250-4/X A Pictured above is the panel where the overload setting (0.8 -1 x In) and short circuit trip (6 -10 x In) can be adjusted. The illustration right shows the optional enclosure available for mounting a DFL8 device. The part No. is 09 200 028 Dimensions: 295W x 690H x 170D sales@doepke.co.uk 11 Doepke Type B For use in 50Hz AC electrical circuits feeding loads which can generate AC & DC leakage currents ‘B’ Type RCCBs AC-DC sensitive Application Many electrical installations now contain products which incorporate power electronics, such as inverters for PV installations, speed control in HVAC, some running machines, UPS, medical equipment etc. This type of equipment can produce, in addition to standard 50Hz earth leakage currents, pure DC and high frequency AC leakage currents which would not be detected by a standard AC or A type RCCB. ‘B’ type RCCBs in addition to normal AC, can detect high frequency AC and pure DC earth leakage currents. Reducing the risk of fire and/or electrocution through automatic disconnection of the electrical supply (Reg 411), relies on the selection and installation of the correct type of RCCB. The IEE Wiring Regs. make specific reference to ‘B’ type RCCBs (section 712) ‘B’ Types Available DFS4 B NK provides the “classic” 300mA fire protection up to 1,000,000 Hz (1MHz). DFS4 B SK provides a 2A tripping threshold above 2kHz. DFS4 B+ provides 420mA fire protection up to 20,000Hz. DFL8 B NK incorporating Type 'B' RCCB trips providing classic 300mA fire protection up to 100kHz. DFL8 B SK incorporating Type 'B' RCCB trips is suitable for use in installations designed to withstand high leakage currents. 12 www.doepke.co.uk Residual Current Circuit Breakers Type B RCCBs DFS4 B NK DFS4 B SK provides the “classic” 300mA fire protection up to 1,000,000Hz (1MHz). provides a 2A tripping threshold above 2kHz. Residual Current Devices (RCCBs) Type DFS4 B NK Type DFS4 B SK 4 Modules wide 4 Modules wide 4 Modules wide 4 Modules wide Rating Sensitivity 2 Pole Reference 4 Pole Reference 2 Pole Reference 4 Pole Reference 16A 16A 16A 16A 25A 25A 25A 25A 40A 40A 40A 40A 63A 63A 63A 63A 80A 80A 80A 80A 100A 100A 100A 100A 125A 125A 125A 125A 30mA 100mA 300mA 500mA 30mA 100mA 300mA 500mA 30mA 100mA 300mA 500mA 30mA 100mA 300mA 500mA 30mA 100mA 300mA 500mA 30mA 100mA 300mA 500mA 30mA 100mA 300mA 500mA DFS4 016-2/0.03-B NK DFS4 016-2/0.10-B NK DFS4 016-2/0.30-B NK n/a DFS4 025-2/0.03-B NK DFS4 025-2/0.10-B NK DFS4 025-2/0.30-B NK n/a DFS4 040-2/0.03-B NK DFS4 040-2/0.10-B NK DFS4 040-2/0.30-B NK n/a DFS4 063-2/0.03-B NK DFS4 063-2/0.10-B NK DFS4 063-2/0.30-B NK n/a DFS4 080-2/0.03-B NK DFS4 080-2/0.10-B NK DFS4 080-2/0.30-B NK n/a DFS4 100-2/0.03-B NK DFS4 100-2/0.10-B NK DFS4 100-2/0.30-B NK n/a DFS4 125-2/0.03-B NK DFS4 125-2/0.10-B NK DFS4 125-2/0.30-B NK n/a DFS4 016-4/0.03-B NK DFS4 016-4/0.10-B NK DFS4 016-4/0.30-B NK n/a DFS4 025-4/0.03-B NK DFS4 025-4/0.10-B NK DFS4 025-4/0.30-B NK n/a DFS4 040-4/0.03-B NK DFS4 040-4/0.10-B NK DFS4 040-4/0.30-B NK n/a DFS4 063-4/0.03-B NK DFS4 063-4/0.10-B NK DFS4 063-4/0.30-B NK n/a DFS4 080-4/0.03-B NK DFS4 080-4/0.10-B NK DFS4 080-4/0.30-B NK n/a DFS4 100-4/0.03-B NK DFS4 100-4/0.10-B NK DFS 4 100-4/0.30-B NK n/a DFS4 125-4/0.03-B NK DFS4 125-4/0.10-B NK DFS4 125-4/0.30-B NK n/a DFS4 016-2/0.03-B SK DFS4 016-2/0.10-B SK DFS4 016-2/0.30-B SK DFS4 016-2/0.50-B SK DFS4 025-2/0.03-B SK DFS4 025-2/0.10-B SK DFS4 025-2/0.30-B SK DFS4 025-2/0.50-B SK DFS4 040-2/0.03-B SK DFS4 040-2/0.10-B SK DFS4 040-2/0.30-B SK DFS4 040-2/0.50-B SK DFS4 063-2/0.03-B SK DFS4 063-2/0.10-B SK DFS4 063-2/0.30-B SK DFS4 063-2/0.50-B SK DFS4 080-2/0.03-B SK DFS4 080-2/0.10-B SK DFS4 080-2/0.30-B SK DFS4 080-2/0.50-B SK DFS4 100-2/0.03-B SK DFS4 100-2/0.10-B SK DFS4 100-2/0.30-B SK DFS4 100-2/0.50-B SK DFS4 125-2/0.03-B SK DFS4 125-2/0.10-B SK DFS4 125-2/0.30-B SK DFS4 125-2/0.50-B SK DFS4 016-4/0.03-B SK DFS4 016-4/0.10-B SK DFS4 016-4/0.30-B SK DFS4 016-4/0.50-B SK DFS4 025-4/0.03-B SK DFS4 025-4/0.10-B SK DFS4 025-4/0.30-B SK DFS4 025-4/0.50-B SK DFS4 040-4/0.03-B SK DFS4 040-4/0.10-B SK DFS4 040-4/0.30-B SK DFS4 040-4/0.50-B SK DFS4 063-4/0.03-B SK DFS4 063-4/0.10-B SK DFS4 063-4/0.30-B SK DFS4 063-4/0.50-B SK DFS4 080-4/0.03-B SK DFS4 080-4/0.10-B SK DFS4 080-4/0.30-B SK DFS4 080-4/0.50-B SK DFS4 100-4/0.03-B SK DFS4 100-4/0.10-B SK DFS4 100-4/0.30-B SK DFS4 100-4/0.50-B SK DFS4 125-4/0.03-B SK DFS4 125-4/0.10-B SK DFS4 125-4/0.30-B SK DFS4 125-4/0.50-B SK Both 2 & 4 pole devices are 4 modules wide. 2 pole items are rated at 230V 4 pole items are rated at 230/400V Time Delay & 500V versions of NK & SK devices are also available. Please contact our sales office for details. sales@doepke.co.uk 13 Doepke Type B For use in 50Hz AC electrical circuits feeding loads which can generate AC & DC leakage currents DFL8 Type B MCCB & RCD module The DFL8 range incorporates type ‘B’ RCD trips with current ratings up to 250 Amps. Each unit comprises: 4 Pole Circuit Breaker (Ics 50kA at 415V) with adjustable overload setting (0.8-1 x In) and short circuit trip (6-10 x In). RCCB trip function module available in non adjustable and adjustable versions (factory fitted). DFL8 B NK provides classic 300mA fire protection up to 100kHz. Residual Current Devices (RCCBs) Type DFL8 B NK Non adjustable I Rating Sensitivity 100A 125A 160A 200A 250A 30mA 30mA 30mA 30mA 30mA n = 0.03A Reference DFL8 100-4/0.03 B NK DFL8 125-4/0.03 B NK DFL8 160-4/0.03 B NK DFL8 200-4/0.03 B NK DFL8 250-4/0.03 B NK Adjustable I n : 0.3A-0.5A-1A Time delay: 60-150-300-450ms Rating DFL8 B SK for use in installations designed to withstand high leakage currents. 100A 125A 160A 200A 250A Sensitivity Adjustable Adjustable Adjustable Adjustable Adjustable Reference DFL8 100-4/X B NK DFL8 125-4/X B NK DFL8 160-4/X B NK DFL8 200-4/X B NK DFL8 250-4/X B NK Residual Current Devices (RCCBs) Type DFL8 B SK Non adjustable I Rating Sensitivity 100A 125A 160A 200A 250A 30mA 30mA 30mA 30mA 30mA n = 0.03A Reference DFL8 100-4/0.03 B SK DFL8 125-4/0.03 B SK DFL8 160-4/0.03 B SK DFL8 200-4/0.03 B SK DFL8 250-4/0.03 B SK Adjustable I n : 0.3A-0.5A-1A Time delay: 60-150-300-450ms Rating 100A 125A 160A 200A 250A 14 Sensitivity Adjustable Adjustable Adjustable Adjustable Adjustable Reference DFL8 100-4/X B SK DFL8 125-4/X B SK DFL8 160-4/X B SK DFL8 200-4/X B SK DFL8 250-4/X B SK Pictured above is the panel where the overload setting (0.8 -1 x In) and short circuit trip (6 -10 x In) can be adjusted. The illustration right shows the optional enclosure available for mounting a DFL8 device. The part No. is 09 200 028 www.doepke.co.uk Residual Current Circuit Breakers Type B RCCBs DFS4 B+ provides 420mA fire protection up to 20,000Hz. Residual Current Devices (RCCBs) Type DFS4 B+ 4 Modules wide Rating Sensitivity 16A 16A 16A 25A 25A 25A 40A 40A 40A 63A 63A 63A 80A 80A 80A 100A 100A 100A 125A 125A 125A 30mA 100mA 300mA 30mA 100mA 300mA 30mA 100mA 300mA 30mA 100mA 300mA 30mA 100mA 300mA 30mA 100mA 300mA 30mA 100mA 300mA 4 Modules wide 2 Pole Reference 4 Pole Reference DFS4 016-2/0.03-B+ DFS4 016-2/0.10-B+ DFS4 016-2/0.30-B+ DFS4 025-2/0.03-B+ DFS4 025-2/0.10-B+ DFS4 025-2/0.30-B+ DFS4 040-2/0.03-B+ DFS4 040-2/0.10-B+ DFS4 040-2/0.30-B+ DFS4 063-2/0.03-B+ DFS4 063-2/0.10-B+ DFS4 063-2/0.30-B+ DFS4 080-2/0.03-B+ DFS4 080-2/0.10-B+ DFS4 080-2/0.30-B+ DFS4 100-2/0.03-B+ DFS4 100-2/0.10-B+ DFS4 100-2/0.30-B+ DFS4 125-2/0.03-B+ DFS4 125-2/0.10-B+ DFS4 125-2/0.30-B+ DFS4 016-2/0.03-B+ DFS4 016-2/0.10-B+ DFS4 016-2/0.30-B+ DFS4 025-2/0.03-B+ DFS4 025-2/0.10-B+ DFS4 025-2/0.30-B+ DFS4 040-2/0.03-B+ DFS4 040-2/0.10-B+ DFS4 040-2/0.30-B+ DFS4 063-2/0.03-B+ DFS4 063-2/0.10-B+ DFS4 063-2/0.30-B+ DFS4 080-2/0.03-B+ DFS4 080-2/0.10-B+ DFS4 080-2/0.30-B+ DFS4 100-2/0.03-B+ DFS4 100-2/0.10-B+ DFS4 100-2/0.30-B+ DFS4 125-2/0.03-B+ DFS4 125-2/0.10-B+ DFS4 125-2/0.30-B+ Both 2 & 4 pole devices are 4 modules wide. 2 pole items are rated at 230V 4 pole items are rated at 230/400V A DHi 11 switch attached to a four pole RCCB. Accessories Description DFA 2 Remote Actuator Power supply RK 24 Auxiliary switch DHi 11 Modules Reference 4 09 100 110 2 09 980 654 0.5 09 200 040 DFA 2 is a remote RCCB actuator which is powered by a 24V supply (RK 24 see page 21). Applications include - Wind Farms Lighthouses - Telecoms - Water Treatment Pumping. The DHi 11 switch is retrofittable to all DFS2 & 4 RCCBs. Locking Facility Description for 2 & 4 pole RCCBs Reference WES To avoid reconnection during maintenance or repair work. Avoids the possibility of accidental connection to mains voltage. Made of stainless steel they are easily fitted. Dimensions: 17 x 29 x 3.5 mm. sales@doepke.co.uk 15 Doepke 16 Residual Current Circuit Breakers www.doepke.co.uk Type B Doepke RCCBs Types ‘AC’ & ‘A’ - 2 & 4 Pole Technical Data Dimensions Contact Assignments Number of poles 2-pole or 4-pole Rated voltage Un 230 V AC Frequency 50 Hz Max. operating voltage Un + 10 % Working voltage range of the test circuit 2P 100 V - 250 V AC 4P 185 V - 440 V AC Short circuit resistance (In 16-40A) 10 kA with 63 A fuse (In 63A) 10 kA with 80 A fuse (In 80A) 10 kA with 100 A fuse (In 100A) 10 kA with 125 A fuse (In 125A) 10 kA with 125 A fuse Ambient temperature -250 C to +400 C Resistance to climatic changes Conforming to DIN IEC 68 Parts 2 - 30 : damp, heat cyclic (550 C / 28 cycles) Impact resistance 20 g / 20 ms duration _ 80 Hz, duration > 30 min.) Vibration resistance > 5 g (f < Enclosure protection type IP 40 (after installation in distribution board) Terminals 1,5 up to 50mm2, multicore > _ 5000 switching cycles Service life Standards EN 61008 RCCBs Type DFL8 ‘A’ - 4 Pole Technical Data Dimensions Number of poles Rated voltage Un 4-poles 400/690 V AC 50/60Hz Residual current detection range AC: 50Hz or 60Hz Pulsating DC: 50 or 60Hz Working voltage range of the test circuit 280 -690 V AC Short circuit resistance 400/415 V AC 690 V AC Icu 50 kA 20 kA If short circuit current > Icu Back up fuse 250A/gL Tripping Char DFL8 A DFL8 AX Thermal Trip Ir Magnetic Trip Ii 0.8-1 x In 6-10 x In Design requirements: overload trip & residual current trip EN 60947-2 & EN 60947-2 Appx. B Surge current resistance Ics 50kA 5kA 0.03A fixed 0.3A; 0.5A; 1.0A Impact resistance Vibration resistance Protection Terminals Verification of CBR resistance to unintentional response due to surge currents caused by impulse voltages EN 60947-2:2003 (B.8.6) -250 C to +400 C Constant IEC 60068-2-78 Cyclic IEC 60068-2-30 20 g / 20 ms IEC 60068-2-27 1g @ f=1-200Hz IEC 60068-2-30 IP 20 1 x 185mm2 2 x 70mm2 Standards IEC 947-2 & Appx. B Ambient temperature Resistance to climatic changes 38 www.doepke.co.uk Contact Assignments (below) TECHNICAL SPECIFICATIONS RCCBs Type DFS4 ‘B’ - 2 & 4 Pole Technical Data Dimensions Number of poles Rated voltage Un AC Rated Frequency (NK version) Min operating voltage for detecting Type B residual current Working voltage range of the test circuit 2-pole 230 V or Contact Assignments 4-pole 400 V 0-1MHz 30 V AC 2P 100 V - 250 V AC 4P 185 V - 440 V AC Short circuit resistance with fuse back up Maximum fuse size 10kA In 16<80A 100 A/gL In 100<125A 125 A/gL Surge current resistance Ring wave 0.5ms/100kHz:200A Impulse 8/20 s: 3kA Ambient temperature Resistance to climatic changes -250 C to +400 C Conforming to DIN IEC 68 Parts 2 - 30 : damp, heat cyclic (550 C / 28 cycles) 20 g / 20 ms duration _ 80 Hz, duration > 30 min.) > 5 g (f < IP 40 (after installation in distribution board) 1,5 up to 50mm2, multicore > _ 5000 switching cycles EN 61008 & EN 62423 Impact resistance Vibration resistance Enclosure protection type Terminals Service life Standards RCCBs Type DFL8 ‘B’ - 4 Pole Technical Data Dimensions Number of poles Rated voltage Un 4-poles 400 V AC 50/60Hz Residual current detection range AC: 0-100kHz Pulsating DC: 50 or 60Hz Min operating voltage for detecting Type B residual current 50 V AC Working voltage range of the test circuit 50-400 V AC Short circuit resistance Icu Ics 50 kA 50kA 400/415 V AC If short circuit current > Icu Back up fuse 250A/gL Tripping Char DFL8 B DFL8 BX Thermal Trip Ir Magnetic Trip Ii 0.8-1 x In 6-10 x In Ambient temperature Resistance to climatic changes Impact resistance Vibration resistance Protection Terminals -250 C to +400 C Constant IEC 60068-2-78 Cyclic IEC 60068-2-30 20 g / 20 ms IEC 60068-2-27 1g @ f=1-200Hz IEC 60068-2-30 IP 20 1 x 185mm2 2 x 70mm2 Standards IEC 947-2 & Appx. B & J Contact Assignments (below) 0.03A fixed 0.3A; 0.5A; 1.0A sales@doepke.co.uk 39