APPENDIX D
FIRE DEPARTMENT DETAILS
(Adopted for Reference Only)
SECTION D101
GENERAL
D101.1 Scope. The following pages provide common detail
that the Phoenix Fire Department, Fire Prevention office have
approved for both new and existing buildings located within
the City of Phoenix.
These details can be used by design professionals and contractors. These details can be modified and reviewed and
approved.
The CAD drawing for each of these details is available on
our website at: www.phoenix.gov/fire/prevention.
The remainder of this appendix is organized by components:
Fire Protection Signage Details
Fire Lane Signage
Controlled Access Gates
Hydrants
Directories
Stairways
Hazmat Identification
Section Valves
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
529
APPENDIX D
FIRE DEPT. SPRINKLER
RISER ROOM SIGN
FIRE DEPT.
12"
SPRINKLER
RISER RM.
1½" LETTERING WITH
.344 STROKE
(BETWEEN 5/16" & 3/8")
12"
NOTES:
1. THE SIGN FACE SHALL BE 12" X12" AND FABRICATED FROM .080 ALUMINUM
SHEET WITH 1½" RADIUS CORNERS.
2. FONT STYLE USED IS HANDEL GOTHIC BT CAPITAL FONTS, ADDITIONAL KERNING
BETWEEN LETTERS AS SHOWN.
3. THE SIGN FACE SHALL HAVE A WHITE 3M DIAMOND GRADE REFLECTIVE
SHEETING (DG³4090 SERIES OR EQUIVALENT) APPLIED AS A BACKGROUND TO
THE ALUMINUM PLATES.
4. LETTERING SHALL BE DONE ONE OF THE FOLLOWING WAYS:
A. 3M SCOTCHLITE ACRYLIC, TRANSPARENT, ELECTRONIC CUTTABLE FILM (RED
1172 SERIES) INVERSE CUT TO ALLOW WHITE REFLECTIVE BACKGROUND TO
SHOW THROUGH.
B. SCREEN PRINTED USING 3M 880 +OR 880Ä00 SERIES TRAFFIC SIGN RED
TRANSLUCENT INK.
BOTH PROCESSES ( A OR B ) WILL ACCOMPLISH A RED FIELD WITH WHITE COPY.
5. ALL SIGN IMAGING SHALL BE IN COMPLIANCE WITH THE REFLECTIVE SHEETING
MANUFACTURES MATCH COMPONENT SYSTEM.
6. REQUIRES PRE-APPROVAL BY A FIRE CODE OFFICIAL 602-262-6771.
FIGURE D.1
530
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
APPENDIX D
SPRINKLER CONNECTION
SIGN DETAIL
12"
18"
FIRE DEPT.
2“ RED LETTERING
3/8“ STROKE
2½“ LETTERING 5/8” STROKE ON
WHITE REFLECTIVE BACKGROUND
150’
2“ LETTERING 3/8” STROKE ON
WHITE REFLECTIVE BACKGROUND
BLDGS
4&5
RED ARROW
SPRINKLER
CONNECTION
1½“ RED LETTERING
3/8“ STROKE
5"
NOTES:
1. THE SIGN PLATE SHALL BE 12” X 18” WITH A THICKNESS OF .080
ALUMINUM CONSTRUCTION AND 1½” RADIUS CORNERS.
2. SIGN FACE SHALL HAVE A WHITE REFLECTIVE BACKGROUND WITH RED
LEGEND, USING THE STANDARD 3M SCOTCHLITE SIGN FACE NUMBER
R7-32 OR EQUIVALENT, WITH RED SCREED PRINTED LETTERING AS
SHOWN ABOVE.
3. INFORMATION LOCATED INSIDE RED ARROW WILL BE DETERMINED BY
FIRE PREVENTION EMERGENCY ACCESS OFFICER.
4. REQUIRES PRE-APPROVAL BY FIRE CODE OFFICIAL.
SPECIAL APPLICATION
FIGURE D.2
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
531
APPENDIX D
SPRINKLER CONTROL VALVE SIGN
FOR ZONE APPLICATIONS
14"
9
2 16
"
14"
SPRINKLER
CONTROL
VALVE FOR
1½" (1.5") LETTERING
ZONE 3
2¼" (2.25) LETTERING
SPRINKLER VALVE SIGN
Serves Floors 1 thru 4
NOTES:
1. THE SIGN FACE SHALL BE 14" X14" AND FABRICATED FROM .080 ALUMINUM
SHEET WITH 1½" RADIUS CORNERS.
2. FONT STYLE USED IS HANDEL GOTHIC BT CAPITAL FONTS. ADDITIONAL KERNING
BETWEEN LETTERS AS SHOWN.
3. THE SIGN FACE SHALL HAVE A WHITE 3M DIAMOND GRADE REFLECTIVE SHEETING
(DG³4090 SERIES OR EQUIVALENT) APPLIED AS A BACKGROUND TO THE
ALUMINUM PLATES.
4. LETTERING SHALL BE DONE ONE OF THE FOLLOWING WAYS:
A. 3M SCOTCHLITE ACRYLIC, TRANSPARENT, ELECTRONIC CUTTABLE FILM (RED
1172 SERIES) INVERSE CUT TO ALLOW WHITE REFLECTIVE BACKGROUND TO
SHOW THROUGH.
B. SCREEN PRINTED USING 3M 880 +OR 880Ä00 SERIES TRAFFIC SIGN RED
TRANSLUCENT INK.
BOTH PROCESSES ( A OR B ) WILL ACCOMPLISH A RED FIELD WITH WHITE
COPY.
5. ALL SIGN IMAGING SHALL BE IN COMPLIANCE WITH THE REFLECTIVE SHEETING
MANUFACTURES MATCH COMPONENT SYSTEM.
6. REQUIRES PRE-APPROVAL BY A FIRE CODE OFFICIAL. 602-262-6771
Special Application
FIGURE D.3
532
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
APPENDIX D
APPROVED PHOENIX FIRE DEPARTMENT
SPRINKLER SIGNS
Each fire department connection shall be identified by a permanent weather resistant sign. When the
building system supplied by the FDC does not supply the entire building or supplies multiple buildings the
sign shall identify the buildings or areas of the buildings supplied by the FDC. Fire department connections
shall designate service design - for example, AUTOSPKR., STANDPIPE, and DRYSTANDPIPE. A sign
shall also indicate the pressure required at the inlets to deliver the greatest systems demand if the system
demand pressure is greater than 150 psi.
12"
F.D.C.
3" X ½"
LETTERING
(TYPICAL FOR
ALL SIGNS)
7
9
1 16
" X 32
"
LETTERING
F.D.C.
12"
3" X ½"
LETTERING
F.D.C.
7
9
1 16
" X 32
"
LETTERING
3" X ½" LETTERING
(TYPICAL FOR ALL SIGNS)
F.D.C.
1
6"
5/1
11"
3" X ½"
LETTERING
7
9
1 16
" X 32
"
LETTERING
F.D.C.
3" X ½"
LETTERING
7
9
1 16
" X 32
"
LETTERING
200 W. WASH
1" LETTERING
WHITE REFLECTIVE BACKGROUND
RED TRANSPARENT FILM
CONSTRUCTION and INSTALLATION NOTES:
1.
THE SIGN FACE SHALL BE 12" X12" AND FABRICATED FROM .080 ALUMINUM SHEET
WITH 1½" RADIUS CORNERS.
2.
FONT STYLE USED IS HANDEL GOTHIC BT CAPITAL FONTS
3.
THE SIGN FACE SHALL HAVE A WHITE 3M DIAMOND GRADE REFLECTIVE SHEETING
(DG³4090 SERIES OR EQUIVALENT) APPLIED AS A BACKGROUND TO THE ALUMINUM PLATES.
4.
LETTERING / GRAPHICS SHALL BE DONE ONE OF THE FOLLOWING WAYS:
A. 3M SCOTCHLITE ACRYLIC, TRANSPARENT, ELECTRONIC CUTTABLE FILM
(RED 1172 SERIES) INVERSE CUT TO ALLOW WHITE REFLECTIVE BACKGROUND TO SHOW
THROUGH.
B. SCREEN PRINTED USING 3M 880 +OR 880Ä00 SERIES TRAFFIC SIGN RED TRANSLUCENT INK.
BOTH PROCESSES ( A OR B ) WILL ACCOMPLISH A RED FIELD WITH WHITE COPY.
ALL SIGN IMAGING SHALL BE IN COMPLIANCE WITH THE REFLECTIVE SHEETING MANUFACTURES
MATCH COMPONENT SYSTEM.
5.
6.
TO BE INSTALLED ON THE WALL 5 - 7 FEET ABOVE GRADE OVER F.D.C. INLET.
7.
REQUIRES PRE-APPROVAL BY A FIRE CODE OFFICIAL. 602-262-6771
FIGURE D.4
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
533
APPENDIX D
FIRE DEPT.
COMMAND ROOM SIGN
12"
COMMAND
1½" LETTERING WITH
.344 STROKE
(BETWEEN 5/16" & 3/8")
CENTER
12"
NOTES:
1. THE SIGN FACE SHALL BE 12" X12" AND FABRICATED FROM .080 ALUMINUM SHEET
WITH 1½" RADIUS CORNERS.
2. FONT STYLE USED IS HANDEL GOTHIC BT CAPITAL FONTS
3. THE SIGN FACE SHALL HAVE A WHITE 3M DIAMOND GRADE REFLECTIVE SHEETING
(DG³4090 SERIES OR EQUIVALENT) APPLIED AS A BACKGROUND TO THE
ALUMINUM PLATES.
4. LETTERING SHALL BE DONE ONE OF THE FOLLOWING WAYS:
A. 3M SCOTCHLITE ACRYLIC, TRANSPARENT, ELECTRONIC CUTTABLE FILM (RED
1172 SERIES) INVERSE CUT TO ALLOW WHITE REFLECTIVE BACKGROUND TO
SHOW THROUGH.
B. SCREEN PRINTED USING 3M 880+OR 880Ä00 SERIES TRAFFIC SIGN RED
TRANSLUCENT INK.
BOTH PROCESSES ( A OR B ) WILL ACCOMPLISH A RED FIELD WITH WHITE COPY.
5. ALL SIGN IMAGING SHALL BE IN COMPLIANCE WITH THE REFLECTIVE SHEETING
MANUFACTURES MATCH COMPONENT SYSTEM.
6. REQUIRES PRE-APPROVAL BY A FIRE CODE OFFICIAL. 602-262-6771
FIGURE D.5
534
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
APPENDIX D
RESIDENTIAL MULTIFAMILY
BROWN OR GREEN F.D.C. SIGNS
Each fire department connection shall be identified by a permanent weather resistant sign. When the
building system supplied by the FDC does not supply the entire building or supplies multiple buildings the
sign shall identify the buildings or areas of the buildings supplied by the FDC. Fire department connections
shall designate service design - for example, AUTOSPKR., STANDPIPE, and DRYSTANDPIPE. A sign
shall also indicate the pressure required at the inlets to deliver the greatest systems demand if the system
demand pressure is greater than 150 psi.
12"
F.D.C.
3" X ½"
LETTERING
(TYPICAL FOR
ALL SIGNS)
7
9
1 16
" X 32
"
LETTERING
F.D.C.
12"
3" X ½"
LETTERING
F.D.C.
7
9
1 16
" X 32
"
LETTERING
3" X ½" LETTERING
(TYPICAL FOR ALL SIGNS)
F.D.C.
1
6"
5/1
11"
3" X ½"
LETTERING
F.D.C.
7
9
1 16
" X 32
"
LETTERING
3" X ½"
LETTERING
7
9
1 16
" X 32
"
LETTERING
200 W. WASH
1" LETTERING
WHITE REFLECTIVE BACKGROUND
BROWN OR GREEN TRANSPARENT FILM
CONSTRUCTION and INSTALLATION NOTES:
1.
THE SIGN FACE SHALL BE 12" X12" AND FABRICATED FROM .080 ALUMINUM SHEET
WITH 1½" RADIUS CORNERS.
2.
FONT STYLE USED IS HANDEL GOTHIC BT CAPITAL FONTS
3.
THE SIGN FACE SHALL HAVE A WHITE 3M DIAMOND GRADE REFLECTIVE SHEETING
(DG³4090 SERIES OR EQUIVALENT) APPLIED AS A BACKGROUND TO THE ALUMINUM PLATES.
4.
LETTERING / GRAPHICS SHALL BE DONE ONE OF THE FOLLOWING WAYS:
A. 3M SCOTCHLITE ACRYLIC, TRANSPARENT, ELECTRONIC CUTTABLE FILM
(BROWN 1179 SERIES OR GREEN 1177 SERIES) INVERSE CUT TO ALLOW WHITE REFLECTIVE
BACKGROUND TO SHOW THROUGH.
B. SCREEN PRINTED USING 3M 880+OR 880Ä00 SERIES TRAFFIC SIGN BROWN TRANSLUCENT
INK.
BOTH PROCESSES ( A OR B ) WILL ACCOMPLISH A BROWN FIELD WITH WHITE COPY.
ALL SIGN IMAGING SHALL BE IN COMPLIANCE WITH THE REFLECTIVE SHEETING MANUFACTURES
MATCH COMPONENT SYSTEM.
5.
6.
TO BE INSTALLED ON THE WALL 5 - 7 FEET ABOVE GRADE OVER F.D.C. INLET.
7.
REQUIRES PRE-APPROVAL BY A FIRE CODE OFFICIAL. 602-262-6771
FIGURE D.6
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
535
APPENDIX D
F.D.C. SIGN POST
INSTALLATION DETAIL
CARRIAGE BOLTS
(TYPICAL 2 PLACES)
BEND BOLT TO
REDUCE TAMPERING
3" X ½" LETTERING
(TYPICAL FOR ALL SIGNS)
FIRE LANE SIGN
MOUNTED WITH
2- ¼" CARRIAGE BOLTS
2- FLAT OR FENDER WASHERS
2-NUTS
3" X ½" LETTERING
1 7 16" X 9 32" LETTERING
3" X ½" LETTERING
HEAVY DUTY
"U" CHANNEL POST
2 LBS. PER FT.
5FT REQUIRED
GRADE
18"
CLASS 'A'
CONCRETE
FOOTING
12" DIA
NOTES:
1. THE SIGN FACE SHALL BE 12" X 12" AND FABRICATED FROM .080 ALUMINUM SHEET WITH
1½" RADIUS CORNERS.
2.
FONT STYLE USED IS HANDEL GOTHIC BT CAPITAL FONTS
3.
THE SIGN FACE SHALL HAVE A WHITE 3M DIAMOND GRADE REFLECTIVE SHEETING
(DG³4090 SERIES OR EQUIVALENT) APPLIED AS A BACKGROUND TO THE ALUMINUM
PLATES.
4.
LETTERING SHALL BE DONE ONE OF THE FOLLOWING WAYS:
A. 3M SCOTCHLITE ACRYLIC, TRANSPARENT, ELECTRONIC CUTTABLE FILM (RED 1172
SERIES) INVERSE CUT TO ALLOW WHITE REFLECTIVE BACKGROUND TO SHOW
THROUGH.
B. SCREEN PRINTED USING 3M 880 +OR 880Ä00 SERIES TRAFFIC SIGN RED
TRANSLUCENT INK.
BOTH PROCESSES ( A OR B ) WILL ACCOMPLISH A RED FIELD WITH WHITE COPY.
ALL SIGN IMAGING SHALL BE IN COMPLIANCE WITH THE REFLECTIVE SHEETING
MANUFACTURES MATCH COMPONENT SYSTEM.
5.
ARIZONA
BLUE STAKE
CALL TWO WORKING DAYS
BEFORE YOU DIG
(602) 263-1100
1-800-STAKE-IT
6.
TO BE INSTALLED 5 FEET ABOVE GRADE, POST SHALL BE 12" TO 18" FROM BACK OF CURB
OR BACK OF SIDEWALK AND MUST FACE THE ONCOMING TRAFFIC.
6.
REQUIRES PRE-APPROVAL BY A FIRE CODE OFFICIAL. 602-262-6771
(OUTSIDE MARICOPA COUNTY)
www.azbsinc.com
FIGURE D.7
536
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
2" x ¼ " LETTERS
6. REQUIRES PRE-APPROVAL BY A FIRE CODE OFFICIAL. 602-262-6771
FIGURE D.8
6. INSTALLED KNOX KEY BOX MODEL 1658 NEXT TO LOCK ON FIRE DEPT. ACCESS DOOR.
5. ALL SIGN IMAGING SHALL BE IN COMPLIANCE WITH THE REFLECTIVE SHEETING MANUFACTURES MATCH
COMPONENT SYSTEM.
4. LETTERING / GRAPHICS SHALL BE DONE ONE OF THE FOLLOWING WAYS:
A. 3M SCOTCHLITE ACRYLIC, TRANSPARENT, ELECTRONIC CUTTABLE FILM (RED 1172 SERIES) INVERSE CUT TO
ALLOW WHITE REFLECTIVE BACKGROUND TO SHOW THROUGH.
B. SCREEN PRINTED USING 3M 880 +OR 880Ä00 SERIES TRAFFIC SIGN RED TRANSLUCENT INK.
BOTH PROCESSES ( A OR B ) WILL ACCOMPLISH A RED FIELD WITH WHITE COPY.
3. THE SIGN FACE SHALL HAVE A WHITE 3M DIAMOND GRADE REFLECTIVE SHEETING (DG³4090 SERIES OR
EQUIVALENT) APPLIED AS A BACKGROUND TO THE ALUMINUM PLATES.
2. FONT STYLE USED IS HANDEL GOTHIC BT CAPITAL FONTS
NOTES:
1. THE SIGN FACE SHALL BE 12" X18" AND FABRICATED FROM .080 ALUMINUM SHEET WITH 1½" RADIUS CORNERS.
18"
12"
KNOX KEY
BOX 1658
WET STANDPIPE SIGN DETAIL
APPENDIX D
537
APPENDIX D
CONSTRUCTION ACCESS SIGN
DURING CONSTRUCTION
FIGURE D.9
538
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
APPENDIX D
APPROVED PHOENIX FIRE DEPARTMENT
FIRE LANE SIGNS
12"
12"
2"
18"
1½"
P
3/4"
1¼" X 3/16"
BLACK
WHITE
8½" DIA.
2"
3/4"
1¼" X 3/16"
RED
3/4"
4 1/16" 5"
1¼" X 3/16"
1¼" X 3/16"
MOUNTING
HOLES
1. THE SIGN PLATE SHALL BE A MINIMUM OF 12" X 18" WITH A
THICKNESS OF .080 ALUMINUM CONSTRUCTION.
2. THE SIGN FACE SHALL HAVE A WHITE REFLECTIVE
BACKGROUND WITH A RED LEGEND. USE THE STANDARD 3M
SCOTCHLITE SIGN FACE NUMBER R7-32 OR EQUIVALENT, WITH
RED SCREEN PRINTED LETTERING AS SHOWN ABOVE.
3. SPECIAL APPLICATION DETAILS MUST BE PRE-APPROVED BY A
FIRE CODE OFFICIAL 602-262-6771
SPECIAL APPLICATION
FIGURE D.10
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
539
APPENDIX D
FIRE LANE SIGN POST AND INSTALLATION
CARRIAGE BOLTS
(TYPICAL 2 PLACES)
BEND BOLT TO
REDUCE TAMPERING
12"
FIRE LANE SIGN
MOUNTED WITH
2-CARRIAGE BOLTS
2-WASHERS
2-NUTS
18"
HEAVY DUTY
"U" CHANNEL POST
2 LBS. PER FT.
(SEE DETAIL 1.4)
7 FT REQUIRED
GRADE
18"
CLASS 'A'
CONCRETE
FOOTING
12" DIA
RECOMMEND
THE FOLLOWING MATERIALS FOR INSTALLATION:
10 FT LONG U-CHANNEL GALVANIZED OR PAINTED POST
FIRE SIGN (12" X 18") .080 ALUMINUM CONSTRUCTION WITH WHITE
REFLECTIVE BACKGROUND AND RED SCREEN PRINTED LEGEND
(SEE DETAIL 1.1)
¼" BOLTS & NUTS LARGE FLAT OR FENDER WASHERS
ARIZONA
BLUE STAKE
CALL TWO WORKING DAYS
BEFORE YOU DIG
(602) 263-1100
1-800-STAKE-IT
(OUTSIDE MARICOPA COUNTY)
www.azbsinc.com
SIGN MUST FACE THE ONCOMING TRAFFIC
POST SHALL BE INSTALLED 12" TO 18" FROM BACK OF CURB OR BACK
OF SIDEWALK
FIRE DEPT. RECOMMENDS YOU BLUE STAKE BEFORE YOU DIG.
FIGURE D.11
540
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
APPENDIX D
APPROVED WALL MOUNT
BRACKET FIRE LANE SIGN
P
P
P
7 FT
GRADE
NOTES:
11 "
1716
1. SEE DETAIL FOR PROPER FIRE LANE
PAINT STRIPING.
13 "
1116
1" SQUARE
TUBING
2. THE SAME DISTANCES FOR SIGNAGE
ON POSTS ALSO APPLIES TO THE
WALL MOUNTED SIGNS.
3. FLAG MOUNT SIGNS MAY ONLY BE
USED WHEN THERE IS NO ROOM FOR
A POST.
20"
5/16"Ø HOLES
(TYP. 4)
4. MUST BE PRE-APPROVED BY A FIRE
CODE OFFICIAL 602-262-6771
3
16" THICK X 4"
FLAT BAR BASE PLATE
4"
FIGURE D.12
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
541
APPENDIX D
FIRE LANE STRIPING FOR HYDRANTS
R 4FT BACK OF CURB
BLUE HYDRANT REFLECTOR
4" STEAMER CAP
FIRE LANE RED CURB
8½' to 9'
8½' to 9'
16' TYPICAL
LANDSCAPING
ISLAND
TYPICAL
PARKING SPACE
TYPICAL
PARKING SPACE
TYPICAL
PARKING SPACE
4 FT CLEARANCE FOR
FIRE FIGHTER ACCESS
8½' to 9'
FIRE LANE RED CURB
WHITE STENCIL SHALL BE CENTERED
15 FT
15 FT
1 FT TO 6 FT
BACK OF CURB
CURB
SIDEWALK
NOTES:
TYPICAL PARALLEL PARKING
STREET DETAIL
FOR HYDRANT INSTALLATION
FIGURE D.13
542
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
APPENDIX D
ALTERNATIVE FIRE LANE
MARKING SYSTEM
SPECIAL APPLICATION DETAILS
MUST BE PRE-APPROVED BY A
FIRE CODE OFFICIAL
602-262-6771
FIRE LANE
8" WHITE THERMOPLASTIC
STRIPING OR WHITE GLASS
BEAD PAINT - APPLY 2 COATS
35 FT RADIUS
FIRE LANE
MIN. 45 FT CENTER
TURNING RADIUS
55 FT RADIUS
E
AN
EL
FIR
FIRE LANE LEGEND
PLACED EVERY 100 FT
8" WHITE
THERMOPLASTIC STRIPING
FIRE LANE
MIN. 45 FT CENTER
TURNING RADIUS
100 FT
LETTERS 24"HT.
4" STROKE
USING HANDEL
GOTHIC CAPTIAL
LETTERS
INSTALL PREFORMED PAVEMENT
MARKINGS TYPE 1
(AZ. DOT. SECT. 705-705-2.01)
FIRE LANE
12 FT - 3 IN
20 FT
FIRE LANE
20 FT
21 FT- 4 IN
MINIMUM WIDTH
SPECIAL APPLICATION
FIGURE D.14
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
543
APPENDIX D
ALTERNATIVE FIRE LANE
MARKING FOR HARD SURFACES
ALTERNATIVE FIRE
LANE MARKING FOR
HARD SURFACES
100FT
50FT
50FT
ON CENTER
WAREHOUSE
TYPICAL PERIMETER
FIRE LANE MARKING SYSTEM
BLUE HYDRANT
MARKER
PASSING AREA
OR PULL OUT
HYDRANT
FIRE LANE
SIGN
FIRE LANE
SIGN
RED REFLECTIVE
MARKER
100 FT
FIRE DEPT.
APPROVED
PIPE GATE
20' WIDE DRIVEWAY
20FT
PARKING LOT
INSTALLATION INSTRUCTIONS for HARD SURFACES (Asphalt / Concrete):
3 TYPES OF ADHESIVE ARE ACCEPTABLE FOR INSTALLING RED & BLUE
HYDRANT MARKERS
A. WEDCO A-4036 EPOXY PART A RESIN
PART B CATALYST
B. THERMOSET EP-308 EPOXY RESIN PART 'A'
EP-308 EPOXY HARDENER PART 'B'
C. BITUMINOUS ADHESIVE
NOTE: LIQUID NAILS TYPE ADHESIVE IS UNACCEPTABLE
REFLECTOR REQUIREMENTS
The adhesive shall be placed uniformly on the cleaned pavement surface in an amount sufficient
to result in complete coverage of the area of contact of the markers, with no void present and
with a slight excess after the markers have been placed. The markers shall be placed in position
and pressure applied until firm contact is made with the pavement. The marker shall be
protected against impact until the adhesive has set to the degree acceptable to the Engineer.
SPECIAL APPLICATION DETAILS MUST BE PRE-APPROVED BY A
FIRE CODE OFFICIAL 602-262-6771
FIGURE D.15
544
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
APPENDIX D
ALTERNATIVE SURFACE
INTERIOR FIRE LANE DETAIL
LIGHTING FIXTURES TO BE
OUTSIDE OF THE 20 FT
CLEAR FIRE LANE
STANDARD FIRE LANE
SIGN AT TERMINATION POINT
8"
RED REFLECTORS
2" ABOVE GRADE
10"
GRASS, DECOMPOSED
GRANITE OR PAVING
SYSTEM
CONCRETE CURB
R 55 FT
R 35 FT
8" WIDTH CURB
SEE DETAIL 1
DECOMPOSED GRANITE OR
APPROVES GRASS PAVING
SYSTEM
20 FT
RED REFLECTORS
25 FT ON CENTERS
REMOVABLE FIRE
LANE SIGN
HYDRANT
3 TYPES OF ADHESIVE ARE ACCEPTABLE FOR INSTALLING
RED MARKERS
A. WEDCO A-4036 EPOXY PART A RESIN
PART B CATALYST
B. THERMOSET EP-308 EPOXY RESIN PART 'A'
EP-308 EPOXY HARDENER PART 'B'
C. BITUMINOUS ADHESIVE
NOTE: LIQUID NAILS TYPE ADHESIVE IS UNACCEPTABLE
REFLECTOR REQUIREMENTS
The adhesive shall be placed uniformly on the cleaned
pavement surface in an amount sufficient to result in
complete coverage of the area of contact of the markers,
with no void present and with a slight excess after the
markers have been placed. The markers shall be placed in
position and pressure applied until firm contact is made with
the pavement. The marker shall be protected against
impact until the adhesive has set to the degree acceptable
to the Engineer.
20 FT MIN
STANDARD FIRE 25 FT
LANE SIGN
RED MARKERS INSTALLATION INSTRUCTIONS:
ALTERNATIVE SURFACE
INTERIOR FIRE LANE
N.T.S.
1. FIRE LANES SHALL HAVE A VERTICAL CLEARANCE OF NO LESS THAN 14 FT. AND A MIN. WIDTH OF 20 FT.
2. FULL 20 FT. FIRE LANE WIDTH SHALL BE CONSTRUCTED WITH A COMBINATION OF HARD SURFACE AND
PRE-ENGINEERED PLASTIC PAVER SYSTEM AS APPROVED BY THE CITY.
3. FIRE LANE CAN MEANDER, BUT SHALL NOT EXCEED THE MIN. 45 FT CENTER LINE TURNING RADIUS.
(35' RADIUS INSIDE / 55' RADIUS OUTSIDE)
4. AREAS OUTSIDE AND BETWEEN WALKS MUST BE DECOMPOSED GRANITE OR APPROVED GRASS
PAVING SYSTEM IN THE FIRE LANE AREA.
5. REFER TO STANDARD ALTERNATIVE SURFACE FIRE APPARATUS ROAD STIPULATIONS PAGE
AND PHOENIX FIRE CODE CHAPTER 9.
FIGURE D.16
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
545
APPENDIX D
INTERIOR FIRE LANE DETAIL
8"
RED REFLECTORS
2" ABOVE GRADE
STANDARD FIRE LANE SIGN
TERMINATION POINT
20' MIN
GRASS OR
DECOMPOSED GRANITE
10"
CONCRETE CURB
RED REFLECTORS 25 FT ON CENTERS
4'-6"
4' 3' 4'
4'-6"
LIGHTING TO BE OUTSIDE OF
THE 20 FT CLEAR FIRE LANE
20' MIN.
25FT O.C
RED REFLECTORS.
REMOVABLE
FIRE LANE SIGN
COLLECTOR
SIDEWALK
INTERSECTING SIDEWALKS &
CROSSOVERS CAN OCCUR AT
ANY POINT AS NEEDED
DECOMPOSED GRANITE OR
APPROVED GRASS PAVING
SYSTEM
REMOVABLE FIRE LANE SIGN
CONCRETE SIDEWALK RIBBONS;
THICKNESS AS REQ'D.
PER SOILS REPORT
PEDESTRIAN SIDEWALK
R=55'
R=45'
R=35'
ROLLED CURB PAINTED RED
20' MIN
STANDARD FIRE
LANE SIGN
8" WIDTH CURB FROM
DRIVEWAY TO BEGINNING
OF DOUBLE SIDEWALK
SEE DETAIL #2
4'
20' MIN
DRIVEWAY WIDTH
VARIES
SIDEWALK
SINGLE SIDEWALK RIBBON ONLY
TO EXTEND TO CURB, IF NEEDED.
(COLLECTOR SIDEWALK PARALLEL TO
CURB PREFERRED, TO DISCOURAGE
UNAUTHORIZED ACCESS. SEE DETAIL #1 ABOVE)
1. FIRE LANES SHALL HAVE A VERTICAL CLEARANCE OF NO LESS THAN 14 FT., AND A MIN. WIDTH OF 20 FT.
2. FULL 20 FT. FIRE LANE WIDTH SHALL BE CONSTRUCTED WITH A COMBINATION OF HARD SURFACE AND
PRE-ENGINEERED PLASTIC PAVER SYSTEM AS APPROVED BY THE CITY.
3. FIRE LANE CAN MEANDER, BUT SHALL NOT EXCEED THE MIN. 45 FT CENTER LINE TURNING RADIUS.
(35' RADIUS INSIDE / 55' RADIUS OUTSIDE)
4. AREAS OUTSIDE AND BETWEEN WALKS MUST BE DECOMPOSED GRANITE OR APPROVED GRASS
PAVING SYSTEM IN THE FIRE LANE AREA.
5. REFER TO STANDARD ALTERNATIVE SURFACE FIRE APPARATUS ROAD STIPULATIONS PAGE
AND PHOENIX FIRE CODE CHAPTER 9
6. RED MARKERS INSTALLATION INSTRUCTIONS:
3 TYPES OF ADHESIVE ARE ACCEPTABLE FOR
INSTALLING RED MARKERS
A. WEDCO A-4036 EPOXY PART A RESIN
PART B CATALYST
B. THERMOSET EP-308 EPOXY RESIN PART 'A'
EP-308 EPOXY HARDENER PART 'B'
C. BITUMINOUS ADHESIVE
NOTE: LIQUID NAILS TYPE ADHESIVE IS
UNACCEPTABLE
REFLECTOR REQUIREMENTS
The adhesive shall be placed uniformly on the cleaned pavement
surface in an amount sufficient to result in complete coverage of the
area of contact of the markers, with no void present and with a slight
excess after the markers have been placed. The markers shall be
placed in position and pressure applied until firm contact is made with
the pavement. The marker shall be protected against impact until the
adhesive has set to the degree acceptable to the Engineer.
FIGURE D.17
546
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
APPENDIX D
REMOVABLE FIRE LANE BOLLARD
4"
1 1/
2 3/4"
4½"
1 1/2"
3"
/4"
13
21
/2"
10"
Ø8"
6"
5"
Ø68
7"
10"
6" SQUARE TUBE X 4' - 10" L
3/16" WALL BOLLARD
BOLLARDS SHALL BE PAINTED
CHROME YELLOW
BOLLARD SHALL BE
6" DIA. INSIDE X
6 5/8" DIA. OUTSIDE
SCHEDULE 40 PIPE
2" X 4" SLOTTED
HAND HOLE
BOTH SIDES
3'
2" WIDE STEEL
COLLAR WITH
CUT OUT FOR
4" LOCKING L - BRACKET
7" SQ. TUBE X 2'-4" L
X 3/8" WALL SLEEVE
4'-10"
SLEEVE PIPE SHALL BE
6 7/8" DIA INSIDE X
8" DIA OUTSIDE
SCHEDULE 160 PIPE
GRADE
ANGLE IRON
STITCH WELD
TO SLEEVE
2'-4"
2'
2'-6"
1'
ARIZONA
BLUE STAKE
CALL TWO WORKING DAYS
BEFORE YOU DIG
(602) 263-1100
1'-6"
1-800-STAKE-IT
(OUTSIDE MARICOPA COUNTY)
www.azbsinc.com
FIGURE D.18
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
547
APPENDIX D
APPROVED PHOENIX FIRE DEPT.
GATE ACCESS SIGN
8"
4"
NOTES:
1. THE SIGN FACE SHALL BE 8" X 4" AND FABRICATED FROM .080 ALUMINUM SHEET
WITH ½" RADIUS CORNERS.
2. LETTERS 1¼" X ¼"STROKE, FONT STYLE USED IS HANDEL GOTHIC BT CAPITAL FONTS.
3. THE SIGN FACE SHALL HAVE A WHITE 3M DIAMOND GRADE REFLECTIVE SHEETING
(DG³4090 SERIES OR EQUIVALENT) APPLIED AS A BACKGROUND TO THE ALUMINUM
PLATES.
4. LETTERING / GRAPHICS SHALL BE DONE ONE OF THE FOLLOWING WAYS:
A. 3M SCOTCHLITE ACRYLIC, TRANSPARENT, ELECTRONIC CUTTABLE FILM
(RED 1172 SERIES) INVERSE CUT TO ALLOW WHITE REFLECTIVE BACKGROUND TO
SHOW THROUGH.
B. SCREEN PRINTED USING 3M 880 OR 88000 SERIES TRAFFIC SIGN RED
TRANSLUCENT INK.
BOTH PROCESSES ( A OR B ) WILL ACCOMPLISH A RED FIELD WITH WHITE COPY.
5. ALL SIGN IMAGING SHALL BE IN COMPLIANCE WITH THE REFLECTIVE SHEETING
MANUFACTURES MATCH COMPONENT SYSTEM.
6. REQUIRES PRE-APPROVAL BY A FIRE CODE OFFICIAL. 602-262-6771
FIGURE D.19
548
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
GCB
GCB
20 FT
6
GCB
SEE STROBE DETAIL ABOVE
PROPERTY SIDE
2
GCB
20 FT
GCB
FIGURE D.20
KNOX KEY SWITCH
FLUSH MOUNTED 6
5
2 SEE DETAIL BELOW
90° ELBOW
4 ELECTRICAL
JUNCTION BOX
WITH MODULE UNIT
4 TAMPER
RESISTANT SCREWS
4" X 4" SQUARE
METAL POST
LOCK NUT
STROBE DETECTOR 3
GATE
CONTROLLER
BOX (GCB)
6
KNOX KEY
SWITCH
OPEN
Requires Permit
THE MINIMUM OVERALL WIDTH
OF GATE SHALL BE 20 FEET
STREET SIDE
THE MINIMUM OVERALL WIDTH
OF GATE SHALL BE 20 FEET
APPROVED EMERGENCY KEY SWITCH SHALL BE INSTALLED ON THE ENTRANCE AND EXIT SIDE OF
EACH ACCESS GATE. ENTRANCE SWITCH SHALL BE LOCATED ABOVE THE RESIDENCE KEY PAD 5½
FT FROM GRADE. EXIT SWITCH SHALL BE RECESSED INTO THE 4" X 4" POST WITH THE DUAL
DETECTORS AND POWER MODULE UNIT.
3 4" X 4" POST WITH
SEE STROBE DETAIL
PREEMPTION STROBE DETECTOR
ELEVATION VIEW
6
F.D.
ACCESS
THE 4" X 4" SQUARE POST WITH DETECTOR AND POWER MODULE SHALL BE INSTALLED ON THE
PROPERTY SIDE OF THE GATE.
THE POWER MODULE SHALL BE MOUNTED IN AN ELECTRICAL JUNCTION BOX, UNDER THE
DETECTORS ON THE SAME 4" X 4" METAL POST.
5
4
DETECTORS SHALL POINT TOWARD THE APPROACH PATH AND EXIT PATH OF THE EMERGENCY
VEHICLES. DETECTORS MUST ACTIVATE WITHIN 150 FEET FROM GATE.
DETECTORS SHALL BE MOUNTED 8 TO 10 FEET FROM GRADE ON A 4" X 4" METAL POST.
DETECTORS SHALL BE ON SEPARATE POST, NOT ON GUIDE POST.
2
3
EACH AUTOMATIC GATE SHALL HAVE TOMAR MODEL 2795-2 DUAL HEAD UNIT.
1
NOTES:
OPEN
F.D.
ACCESS
5½ FT
5
MODULE
LOCATION
GATE
CONTROLLER
BOX
APPROVED AUTOMATIC VEHICLE ACCESS GATE
PREEMPTION DETECTORS WITH KNOX KEY SWITCHES
6 FT
8 FT
ELECTRIC LINES
IN CONDUIT
APPENDIX D
549
APPENDIX D
ENTRANCE ISLAND DETAILS FOR COMMUNITIES
WITHOUT AUTOMATIC GATES
F.D. KNOX KEY SWITCH
(PERMIT REQUIRED)
ACCESS SIGN
REQUIRES PERMIT
SITE
DIRECTORY
(REQUIRES
PRE-APPROVAL)
TENANT KEY PAD
BLDG 1
BLDG 5
1
2
4
5
7
8
#
0
3
6
9
*
TENANT CARD ACCESS
BLDG 2
BLDG 4
BLDG 3
24"
MINIMUM
GRADE / PAVEMENT
8"
ACCESS SIGN
F.D.
ACCESS
4"
F.D.
ACCESS
F.D. KNOX KEY SWITCH FOR
SINGLE GATE APPLICATION
MODEL #3502
FOR DOUBLE GATE APPLICATION
SWITCH MODEL #3513
FLUSH MOUNT TO FACE PLATE
F.D. KNOX KEY
SWITCH
TENANT KEY PAD
5½ FT
TENANT KEY PAD
SITE
DIRECTORY
GRADE / PAVEMENT
NOTES:
1. MUST HAVE AN ORIGINAL ORDER FORM AND FIRE
DEPT. GATE PERMIT TO PURCHASE KEY SWITCH.
2. ORDER FORMS FOR KNOX KEY SWITCHES ARE
AVAILABLE THROUGH THE INSPECTORS IN FIRE
PREVENTION. CALL 602-262-6771 FOR ORDER FORMS.
Permit Required
FIGURE D.21
550
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
APPENDIX D
AUTOMATIC GATE ENTRANCE WITH 3
STROBE DETECTORS
OFFICE BUILDING
PROPERTY SIDE OF GATE
PROPERTY SIDE OF GATE
65°
65°
GU
SH ARD
AC
K
PREEMPTION
POST W/ KEY SWITCH
MINIMUM OVERALL WIDTH
OF GATE SHALL BE 20 FEET
65°
F.D KNOX KEY SWITCH
TENANT KEY PAD
OR CARD ACCESS
SITE DIRECTORY
1. DETECTORS SHALL BE MOUNTED 8 TO 10 FEET FROM GRADE ON A 4" X 4" METAL POST.
NO MIRRORS SHALL SUBSTITUTE THE REQUIREMENTS OF TWO DETECTORS PER GATE.
2. DETECTORS SHALL POINT TOWARD THE APPROACH PATH AND EXIT PATH OF THE EMERGENCY
VEHICLES. DETECTORS MUST ACTIVATE 150 FEET FROM GATE.
3. THE POWER MODULE SHALL BE MOUNTED IN AN ELECTRICAL JUNCTION BOX, UNDER THE
DETECTORS ON THE SAME 4" X 4" METAL POST.
4. THE 4" X 4" SQUARE POST WITH DETECTOR AND POWER MODULE SHALL BE INSTALLED ON THE
PROPERTY SIDE OF THE GATE. ( NOT ON GUIDE POST )
5. APPROVED EMERGENCY KEY SWITCH SHALL BE INSTALLED ON THE ENTRANCE AND EXIT SIDE OF
EACH ACCESS GATE. ENTRANCE SWITCH SHALL BE LOCATED ABOVE THE RESIDENCE KEY PAD 5½
FT FROM GRADE. EXIT SWITCH SHALL BE LOCATED ON THE 4" X 4" POST WITH THE DUAL
DETECTORS AND POWER MODULE UNIT.
FIGURE D.22
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
551
APPENDIX D
3 TOMAR PREEMPTION DETECTORS
MODEL 2795-3
65°
65°
65°
30°
STROBE SWITCH
DETECTOR
MODEL 2795-3
TOMAR ELECTRONICS, INC.
2100 W. OBISPO AVE
GILBERT, AZ 85233
30°
NOTE:
3 HEADS ARE REQUIRED WITH 90° TURNING LAYOUTS
FIGURE D.23
552
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
L. Hertz
F. D.
ACCESS
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
Requires Permit
APPROVED FIRE DEPT. ACCESS SIGN WITH WHITE 3M DIAMOND GRADE DG³
BACKGROUND PLACED BACK TO BACK.
LOCKING BAR LENGTH IS DETERMINED BY THE FRAME WIDTH AND THE GAP
WIDTH BETWEEN THE 2 GATES. REMOVE ALL SHARP EDGES
& ROUND ALL CORNERS.
WELD MODIFIED L-BRACKET TO GATE FRAME. ROUND ALL EDGES.
(TYPICAL 2 PLACES)
THE MINIMUM OVERALL WIDTH OF THE GATE OPENING SHALL BE 20 FT.
(LARGER IS BETTER).
6" RED PARKING LOT STRIPING AT THE LOCATIONS SHOWN ON CONCRETE CURBS
AND APPLIED TO ASPHALT (SEE EMERGENCY ACCESS DETAIL 8.5)
APPROVED FIRE LANE SIGNS WITH REFLECTIVE BACKGROUND, PLACED BACK TO
BACK, AND FASTENED ON ALL 4 CORNERS.
FIRE DEPT. PADLOCK SHALL BE ACCESSIBLE FROM BOTH SIDES OF GATE.
ORDER FORMS FOR KNOX PADLOCKS ARE AVAILABLE THROUGH EITHER THE
GATE INSPECTORS IN FIRE PREVENTION OR CALL F.P. 602-262-6771 FOR ORDER
FORMS.
PROPERTY OWNER / MANAGEMENT PADLOCK
ROUND ALL EDGES
FIGURE D.24
5/8" ° HOLE
LOCKING BAR
PICKETS
6"
10"
LENGTH VARIES
L-BRACKET WELDED
TO GATE FRAME
11/16"
2"
OWNERS PADLOCK
5/8" DIA.
2"
F. D.
ACCESS
2" SQUARE
GATE FRAME
2"
2" SQUARE
GATE FRAME
MANUAL SWING GATE
APPROVED SIGN, WITH REFLECTIVE BACKGROUND, TO IDENTIFY THE NAME OF THE
APARTMENT COMPLEX AND THE LOCATION OF THE ACCESS ENTRANCE
RED STRIPING FOR FIRE LANE
SHALL BE ON BOTH
SIDES OF GATE
NAME OF
APARTMENT
BLDG
ENTRANCE ON
STREET NAME
FIRE APPARATUS ACCESS GATE
4"
KNOX PADLOCK
LOCKING SYSTEM
DETAIL
F. D.
ACCESS
GAP
½" - 1" MIN
FIRE DEPT.
KNOX PADLOCK
DUAL LOCKING
SYSTEM
2" X ½" STEEL BAR
ROUND ALL EDGES
F. D.
ACCESS
8"
APPENDIX D
553
FNAME:CLF_GATE_DET.CDR
CALL FIRE PREVENTION-ACCESS OFFICER
FOR QUESTIONS OR ASSISTANCE
(602)256-3382 OR (602)262-6771
5/8” DIA
HOLE
(TYP. 2 PLACE)
plan view
4
4 LOCKING BAR
2” X LG VARIES X ½”
bar detail
4
5
NOTES:
FIGURE D.25
F. D.
ACCESS
DUAL LOCK HASP DETAIL
FOR CHAIN LINK FENCES
FIRE DEPT KNOX PADLOCK
MANUAL CHAIN LINK
SECURITY GATE DETAILS
7. FIRE DEPT. KNOX PADLOCK SHALL BE ACCESSIBLE FROM BOTH SIDES OF
THE GATE. ORDER FORMS FOR KNOX PADLOCKS ARE AVAILABLE THROUGH
GATE INSPECTORS IN FIRE PREVENTION. CALL 602-262-6771 FOR ORDER
FORMS.
6. THE MINIMUM OVERALL WIDTH OF THE GATE OPENING SHALL BE
20 FT.
5. WELD MODIFIED L-BRACKET TO GATE FRAME.
4. LOCKING BAR LENGTH IS DETERMINED BY THE FRAME WIDTH AND GAP
WIDTH BETWEEN THE 2 GATES. REMOVE ALL SHARP EDGES/ROUND ALL
CORNERS. 3/4” DIA HOLE MIN, HOLE DIAMETER DETERMINED BY SIZE
OF PADLOCK.
3. STRIPING SHALL BE PAINTED SAFETY RED. 6” WIDE HASH STRIPING
APPROX. 4FT TO 6FT APART. (SEE DETAIL 8.5)
2. APPROVED FIRE DEPT. ACCESS SIGN W/ WHITE 3M DIAMOND GRADE D 3
REFLECTIVE BACKGROUND PLACED BACK TO BACK SEE IFC)
1. APPROVED FIRE LANE SIGNS WITH REFLECTIVE BACKGROUND, PLACED
BACK TO BACK AND FASTENED ON ALL 4 CORNERS (SEE IFC)
Requires P e r m i t
l bracket
DETAIL
2
PULL BAR
PROPERTY MANAGEMENT
PADLOCK
TENSION BAR
TENSION BAND
2” ROUND GATE POST
BAR UNLOCKED DETAIL
5
2
5 L-BRACKET
WELD TO
GATE FRAME
2”ROUND
GATE POST
3
2” X ½” STEEL LOCKING BAR
MIN. 3/4” DIA HOLES
(TYP BOTH SIDES)
2” ROUND GATE POST
L-BRACKET WELDED
TO FRAME OF GATE
SEE DETAIL
2” 3”
6”
554
DUAL LOCK HASP DETAIL
STREET SIDE
4
PROFILE VIEW
STREET SIDE
1
APPENDIX D
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
36"
6"
2
3
P
5" HEAVY DUTY BARREL HINGES (TYPICAL 4 PLACES)
G3
FIGURE D.26
Requires Permit
3" X 3" X .120 POST 7 FT W/ CAP APPROVED COLOR CHROME YELLOW
2" X 2" X .120 RAILS APPROVED COLOR CHROME YELLOW
G2
POST GATE NOTES:
NOTES: GATE MANUFACTURED IN 3 SIZES- 16 FT, 20 FT AND 24 FT.
RECOMMENDED POSTS/GATE COLOR CHROME YELLOW
SEE FIRE LANE STRIPING DETAILS.
18"
F.D.
ACCESS
G1
ABOVE GRADE
P
1
APPROVED FIRE DEPT. ACCESS SIGN WITH WHITE 3M DIAMOND GRADE DG³ BACKGROUND
PLACED BACK TO BACK.
9
48" 36"
LOCKING BAR LENGTH IS DETERMINED BY THE FRAME WIDTH AND THE GAP WIDTH BETWEEN
THE 2 GATES. REMOVE ALL SHARP EDGES / ROUND ALL CORNERS.
8
4
WELD MODIFIED L-BRACKET TO GATE FRAME. ROUND ALL EDGES. (TYPICAL 2 PLACES)
7
4
THE MINIMUM OVERALL WIDTH OF THE GATE OPENING SHALL BE 20 FT.
6
4
FIRE LANE STRIPING SHALL BE PROVIDED AT EACH MANUAL GATE. SEE F.D. DETAIL 8.5 FOR
STRIPING EXAMPLES.
5
G2
APPROVED FIRE LANE SIGNS WITH REFLECTIVE BACKGROUND, PLACED BACK TO BACK AND
FASTENED ON ALL 4 CORNERS. ¼" X 1½" MOUNTING STRAPS.
4
20 FT
MINIMUM OPENING
7 8
9
FIRE DEPT. PADLOCK SHALL BE ACCESSIBLE FROM BOTH SIDES OF GATE. ORDER FORMS FOR
KNOX PADLOCKS ARE AVAILABLE THROUGH EITHER THE GATE INSPECTORS IN FIRE
PREVENTION OR CALL 602-262-6771 FOR ORDER FORMS.
3
4
PROPERTY OWNER/MANAGEMENT PADLOCK
2
1
G1
G2
5/8" ° HOLE
LOCKING BAR
8
5/8" DIA.
2"
FIRE DEPT KNOX PADLOCK
9
2" SQUARE
GATE FRAME
REFER TO APPROVED
PFD ACCESS DETAIL
F.D.
ACCESS
8"
4"
ROUNDED L-BRACKET
WELDED TO GATE FRAME G2
2"
8 2" x ½" STEEL BAR
ROUND ALL EDGES
3
7
L-BRACKET WELDED
TO GATE FRAME
TOP OF GATE FRAME
8
6"
ROUND ALL EDGES
2"
LENGTH
VARIES
MANUAL POST VEHICLE
SECURITY GATE
G3
PROPERTY
PADLOCK 2
MANAGEMENT
7
GATE FRAME G2
GATE FRAME G1
11/16"
MIN.
APPROVED SIGN, WITH REFLECTIVE BACKGROUND, TO IDENTIFY THE NAME OF THE APARTMENT
COMPLEX AND THE LOCATION OF THE ACCESS ENTRANCE. ¼" X 1½" MOUNTING STRAPS.
2" 3"
6"
GENERAL NOTES:
APPENDIX D
555
4 REBAR
ANGLE IRON
2'-6"
48"
12"
24"
10
36"
24" X 36" CONCRETE POST FOOTINGS
10
GRADE
APPROVED FIRE DEPT. ACCESS SIGN WITH WHITE 3M DIAMOND GRADE DG³ BACKGROUND
PLACED BACK TO BACK.
9
DRIVEWAY
P
20 FT
MINIMUM OPENING
G3
G2
G1
STOP
POST
FIGURE D.27
Requires Permit
SEALED 5" HEAVY DUTY BARREL HINGES (TYPICAL 2 PLACES)
2" GATE FRAME (SQUARE OR ROUND) 11 GAUGE APPROVED COLOR
CHROME YELLOW
2
11/16"
6" MINIMUM POST (SQUARE OR ROUND) ROUND POST SCHEDULE 40,
SQUARE POST ¼" STOCK. POST 7 FT W/ CAP APPROVED COLOR CHROME
YELLOW
POST GATE NOTES:
NOTE: GATE MANUFACTURED IN 3 SIZES-16FT, 20 FT AND 24 FT.
RECOMMENDED POSTS / GATE COLOR CHROME YELLOW.
4
1
4
LOCKING BAR LENGTH IS DETERMINED BY THE FRAME WIDTH AND THE GAP WIDTH BETWEEN
THE 2 GATES. REMOVE ALL SHARP EDGES / ROUND ALL CORNERS.
8
36"
WELD MODIFIED L-BRACKET TO GATE FRAME. ROUND ALL EDGES. (TYPICAL 2 PLACES)
7
F.D.
ACCESS
THE MINIMUM OVERALL WIDTH OF THE GATE OPENING SHALL BE 20 FT.
6
G2
FIRE LANE STRIPING SHALL BE PROVIDED AT EACH MANUAL GATE. SEE F.D. DETAIL 8.5 FOR
STRIPING EXAMPLES.
5
9
APPROVED FIRE LANE SIGNS WITH REFLECTIVE BACKGROUND, PLACED BACK TO BACK AND
FASTENED ON ALL 4 CORNERS. ¼" X 1½" MOUNTING STRAPS.
4
G3
FIRE DEPT. PADLOCK SHALL BE ACCESSIBLE FROM BOTH SIDES OF GATE. ORDER FORMS FOR
KNOX PADLOCKS ARE AVAILABLE THROUGH THE GATE INSPECTORS IN FIRE PREVENTION, OR
CALL 602-262-6771 FOR ORDER FORMS.
3
G1
PROPERTY OWNER/MANAGEMENT PADLOCK
2
PLAN VIEW
4
FIRE LANE SIGNS
APPROVED SIGN, WITH REFLECTIVE BACKGROUND, TO IDENTIFY THE NAME OF THE APARTMENT
COMPLEX AND THE LOCATION OF THE ACCESS ENTRANCE. ¼" X 1½" MOUNTING STRAPS.
1
MIN. HT FROM ABOVE
GRADE TO TOP OF GATE
6"
LENGTH
VARIES
3
PROPERTY SIDE
2"
9
8
8"
REFER TO APPROVED
PFD ACCESS DETAIL
F.D.
ACCESS
VARIES
ROUNDED L-BRACKET
WELDED TO
FRAME OF GATE
GATE FRAME
G2 2" SQUARE
5/8" DIA.
2"
4"
FIRE DEPT KNOX PADLOCK
8 2" x ½" STEEL BAR
ROUND ALL EDGES
3
7 ROUNDED L-BRACKET
WELDED TO GATE FRAME G2
G1 GATE FRAME
SINGLE MANUAL SWING
SECURITY GATE
8 SEE
DETAIL
8
ROUND ALL EDGES
2"
G2
PROPERTY
MANAGEMENT 2
PADLOCK
7
MIN.
GATE FRAME G2
2" 3"
556
6"
GENERAL NOTES:
APPENDIX D
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
1'
20'
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
20'
20'
20'
MINIMUM
RED FIRE LANE STRIPING MUST BE A
MINIMUM OF ONE HALF THE DISTANCE
OF AREA BEHIND GATE.
10'
20'
MINIMUN
FIGURE D.28
10'
Requires Permit
STRIPING SHALL BE PAINTED
SAFETY RED. 6 INCHES WIDE
HASH STRIPING RUNNING
APPROX. 4 FT. TO 6 FT. APART.
20'
MINIMUM
4'TO 6'
FIRE LANE STRIPING DETAILS FOR MANUAL GATES
APPENDIX D
557
APPENDIX D
MANUAL GATE APPLICATION
FIRE LANE AND DIRECTIONAL SIGN
.080 Aluminum Sheet
WHITE 3M 4090 Diamond Grade,
DG3 Reflective Sheeting
See Note 3
See Note 4 & 5
FIGURE D.29
558
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
APPENDIX D
APPROVED PEDESTRAIN GATE
REQUIREMENTS
4" X 4" SQUARE POST
SELF LATCHING
DEVICE
4" X 4" SQUARE POST
5 FT
MINIMUM
4 FT
WELD KNOX KEY
BOX TO WROUGHT
IRON FENCE
OWNERS PADLOCK
KNOX KEY BOX
MODEL 1658
54" MIN.
VERTICAL CLEARANCE
SEE NOTE 4
GRADE
24" X 24" X 24" FOOTING
(TYPICAL BOTH SIDES-2 PLACES)
KEY TO LOCK MUST BE PLACED IN THE APPROVED FIRE DEPT. KEY BOX.
KEY BOX MUST BE WELDED ONTO FENCE PICKET FACING STREET.
THE MINIMUM OVERALL WIDTH OF THE GATE OPENING SHALL BE 4 FT.
THE VERTICAL CLEARANCE MINIMUM OF 2" AND A MAXIMUM OF 4"
REFER TO BUILDING CODE REQUIREMENTS.
ALL DIMENSIONS MUST COMPLY WITH THE PHOENIX CODE.
FIGURE D.30
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
559
APPENDIX D
BARRIERS FOR SWIMMING POOLS
SPAS & HOT TUBS
TURN
OPEN
KNOX KEY SWITCH DETAIL FOR
MAG LOCKING APPLICATIONS
ON PEDESTRIAN GATES
4" X 4" SQUARE POST
SELF LATCHING
DEVICE
4" X 4" SQUARE POST
KNOX KEY SWITCH
PART # 3502
KNOX KEY SWITCH
RECESSED IN 4" POST
FOR FIRE DEPT. ACCESS
OWNERS ACCESS
CARD OR KEYPAD
4 FT
6"
10"
11"
5 FT
MINIMUM
54" MIN.
VERTICAL CLEARENCE
SEE NOTE 4
MAGNETIC LOCKING
DEVISED
GRADE
24" X 24" X 24" FOOTING
(TYPICAL BOTH SIDES-2 PLACES)
KNOX KEY SWITCH ACCESSIBLE FROM BOTH SIDES OF GATE
THE MINIMUM OVERALL WIDTH OF THE GATE OPENING SHALL BE 4 FT.
THE VERTICAL CLEARANCE MINIMUM OF 2" AND A MAXIMUM OF 4"
REFER TO BUILDING CODE REQUIREMENTS.
ALL DIMENSIONS MUST COMPLY WITH THE UNIFORM BUILDING CODE
FOR SPECIAL USE AND OCCUPANCY SECTION 419 THRU 421.
FIGURE D.31
560
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
APPENDIX D
HYDRANT COLORS
FOR PRIVATE AND PUBLIC
HI, I’M A PRIVATE
HYDRANT
COOL, I’M A
PUBLIC HYDRANT
NOTES:
2 PUBLIC HYDRANTS SHALL BE PAINTED WITH OSHA APPROVED FEDERAL
YELLOW
2 PRIVATE HYDRANTS SHALL BE PAINTED WITH OSHA APPROVED FEDERAL
YELLOW AND HAVE A WHITE REFLECTIVE BONNET
FIGURE D.32
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
561
562
GRADE
ELECTRICAL
CONDUIT
110 VOLT
ALUMINUM LIP
ON OFF SWITCH
FLUORESCENT
FIXTURES
(TYP. 3)
CONCRETE
MASONRY
UNIT (CMU)
EQUAL
48"
50"
64"
EQUAL
EQ
EQ
48"
8"
8"
24"
50"
REQUIRES PERMIT
FIGURE D.33
NOTE:
1. SHOULD INCLUDE PHOTO CELL.
2. REFER TO ENTRANCE ISLAND DETAIL MORE FOR
DIMENSION SPECIFICATIONS.
80"
96"
TO POWER SUPPLY
8"
8"
80"
8"
80"
50"
EQ
20"
10"
16"
EQ
GRADE
ELECTRICAL
CONDUIT
110 VOLT
APPENDIX D
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
APPENDIX D
CORRIDOR SPREAD PLATE
SAMPLE
24"
1" TYP.
1"
22"
1"
NUMBER SIZE (FOUR DIGIT PLATE)
FOUR FLOORS
4" X 5/8" BRUSH STROKE
4 DIGIT NUMBERS - THOUSAND SERIES
2"
10"
¼" LINE
NUMBER SIZE (FOUR DIGIT PLATE)
THREE FLOORS
18"
4" X 5/8" BRUSH STROKE
4 DIGIT NUMBERS - THOUSAND SERIES
20"
NUMBER SIZE (THREE DIGIT PLATE)
THREE FLOORS
18"
4" X 5/8" BRUSH STROKE
3 DIGIT NUMBERS - HUNDREDS SERIES
101 - 199 NUMBER RANGE
NOTE:
1. THE FONT USED IS SEAGULL MD. FONTS USED FOR
ADDRESSING MUST BE LEGIBLE AND EASY TO READ.
2. THE USE OF DIFFERENT FONTS MUST BE
PRE-APPROVED BY A FIRE CODE OFFICIAL.
FIGURE D.34
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
563
APPENDIX D
MULTI-FAMILY NUMBERING DETAIL
FOR COMMUNITIES WITH
LESS THAN 100 TOTAL UNITS PER FLOOR
3
18" BLDG. NUMBER
3" STROKE
7" X 1"
27.5"
7" LETTERS
1" STROKE
36"
ALL NUMBERING IS GILL SANS FONT
NOTE:
1. THE FONT USED IS SEAGULL MD. FONTS USED FOR
ADDRESSING MUST BE LEGIBLE AND EASY TO READ.
2. THE USE OF DIFFERENT FONTS MUST BE
PRE-APPROVED BY A FIRE CODE OFFICIAL.
FIGURE D.35
564
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
APPENDIX D
APARTMENT DIRECTIONAL SIGN
.080 Aluminum Sheet
WHITE 3M 4090 Diamond Grade,
DG3 Reflective Sheeting
See Note 3
See Note 4 & 5
FIGURE D.36
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
565
APPENDIX D
PRIVATE COMMUNITY STREET SIGNS
24"
3¼" ( 3.25) LETTERING
9/16" STROKES
43 4"
STREET SIGN
7"
10"
7"
2
1 5/8" (1.625) LETTERING
3/8" STROKES
6
3¼" (3.25) LETTERING
9/16" STROKES
DEAD END STREET SIGN
NOTES:
1. THE STREET SIGN PLATE SHALL BE 24" X 4 3 4 ", THE DEAD END STREET SIGN PLATE
SHALL BE 24" X 8" BOTH ARE FABRICATED FROM .080 ALUMINUM SHEET.
2. FONTS USED FOR ADDRESSING MUST BE LEGIBLE AND EASY TO READ.
3. THE SIGN FACE SHALL HAVE A WHITE 3M DIAMOND GRADE REFLECTIVE SHEETING (DG³
4090 SERIES OR EQUIVALENT) APPLIED AS A BACKGROUND TO THE ALUMINUM PLATES.
4. LETTERING / NUMBERING SHALL BE DARK CONTRASTING, 3M SCOTCHLITE ACRYLIC,
TRANSPARENT, ELECTRONIC CUTTABLE FILM (3M 1170 SERIES) INVERSE CUT TO ALLOW
WHITE REFLECTIVE BACKGROUND TO SHOW THROUGH.
5. ALL SIGN IMAGING SHALL BE IN COMPLIANCE WITH THE REFLECTIVE SHEETING
MANUFACTURES MATCH COMPONENT SYSTEM.
6. TO FORM A GRAFFITI BARRIER 3M 1160 PROTECTION OVERLAY FILM MAYBE APPLIED
OVER SIGN.
7. REQUIRES PRE-APPROVAL BY A FIRE CODE OFFICIAL. 602-262-6771
FIGURE D.37
566
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
APPENDIX D
PRIMARY AND SECONDARY HIGHRISE
STAIRWELL SIGNAGE
12"
N.W. STAIR
STANDPIPE
14"
B
PARKING
B THRU 4
BRAILLE SHALL BE GRADE 2 TYPE, INDICATING
STAIRWELL LOCATION AND FLOOR NUMBER.
(EXAMPLE: N.E. STAIRWELL FLOOR 4)
THE BRAILLE AND RAISE
NUMBERS SHALL BE PLACED NO
MORE THAN 2" APART AND SHALL
BE CENTERED ON THE SIGN.
N.E. STAIR
NO STANDPIPE
2
B THRU 4
1¼" X ¼" LETTERING
1" X 3 16" LETTERING
5" X 7 8" LETTERING
1" X
3
16"
LETTERING
N.W. STAIR
STANDPIPE
20
B THRU 24
1" X 3 16" LETTERING
WITH ADA RAISED
INFORMATION
1¼" X ¼" LETTERING
1" X 3 16" LETTERING
43 4 " X 7 8" LETTERING
1¼" X 3 16" LETTERING
1" X 3 16" LETTERING
WITH ADA RAISED
INFORMATION
N.W. STAIR
1¼" X ¼" LETTERING
1 " LETTERING, 3/16" STROKE
5" LETTERING,
1¼" X
3
16"
7
8"
STANDPIPE
STROKE
LETTERING
20
B THRU 24
1" LETTERING, 3 16" STROKE
WITH ADA RAISED
INFORMATION
N.E. STAIR
NO STANDPIPE
3
B THRU 4
S.E. STAIR
1¼" X ¼" LETTERING
1" LETTERING, 3/16" STROKE
43 4 " LETTERING,
1¼" X
3
16"
7
8"
STROKE
LETTERING
NO STANDPIPE
4
B THRU 4
1" LETTERING, 3 16" STROKE
WITH ADA RAISED
INFORMATION
ADA DISCLAIMER
THE INFORMATION PROVIDED ON THE BOTTOM 2" PORTION OF THIS SIGN IS ONLY
INTENDED TO AID PEOPLE WITH VISUAL IMPAIRMENTS EXITING THE BUILDING. THE
BRAILLE AND RAISED #'S INDICATING STAIRWELL LOCATION AND FLOOR # MEETS ADA
REQUIREMENTS FOR DIRECTIONAL SIGNAGE. ADDITIONAL INFORMATION DISPLAYED ON
THE SIGN IS INTENDED FOR F.D. USE ONLY.
NOTES:
1. THE SIGN FACE SHALL BE 12" X 14" AND FABRICATED FROM .080 ALUMINUM SHEET
WITH 1½" RADIUS CORNERS.
2. FONT STYLE USED IS HANDEL GOTHIC BT CAPITAL FONTS
3. THE SIGN FACE SHALL HAVE A WHITE 3M DIAMOND GRADE REFLECTIVE SHEETING
(DG³4090 SERIES OR EQUIVALENT) APPLIED AS A BACKGROUND TO THE
ALUMINUM PLATES.
4. LETTERING / NUMBERING SHALL BE HIGH PERFORMANCE, NON-REFLECTIVE,
CUTTABLE VINYL (3M 7725 SERIES) INVERSE CUT TO ALLOW WHITE REFLECTIVE
BACKGROUND TO SHOW THROUGH.
5. ALL SIGN IMAGING SHALL BE IN COMPLIANCE WITH THE REFLECTIVE SHEETING
MANUFACTURES MATCH COMPONENT SYSTEM.
6. TO FORM A GRAFFITI BARRIER 3M 1160 PROTECTION OVERLAY FILM MAYBE APPLIED
OVER SIGN.
7. REQUIRES PRE-APPROVAL BY A FIRE CODE OFFICIAL. 602-262-6771
Special Application
FIGURE D.38
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
567
APPENDIX D
12"
N.W. STAIR
NO ROOF ACCESS
20
14"
B2 THRU 24
BRAILLE SHALL BE GRADE 2 TYPE,
INDICATING STAIRWELL LOCATION AND
FLOOR NUMBER.
(EXAMPLE: N.W. STAIRWELL FLOOR 20)
1.25" (1¼") LETTERING, ¼" STROKE
1" LETTERING, 3/16" STROKE
5" LETTERING, 7/8" STROKE
1" LETTERING, 3/16" STROKE
1" LETTERING, 3/16" STROKE
NUMBERS SHALL BE RAISED A
MINIMUM OF 1 32 ", UPPER CASE,
SANS SERIF TYPE FONT.
ADA DISCLAIMER
THE INFORMATION PROVIDED ON THE BOTTOM 2" PORTION OF THIS
SIGN IS ONLY INTENDED TO AID PEOPLE WITH VISUAL IMPAIRMENTS
EXITING THE BUILDING. THE BRAILLE AND RAISED #'S INDICATING
THE BRAILLE AND RAISE NUMBERS
SHALL BE PLACED NO MORE THAN 2"
APART AND SHALL BE CENTERED ON
THE SIGN.
STAIRWELL LOCATION AND FLOOR # MEETS ADA REQUIREMENTS
FOR DIRECTIONAL SIGNAGE. ADDITIONAL INFORMATION DISPLAYED
ON THE SIGN IS INTENDED FOR F.D. USE ONLY.
SEE DETAIL
ABOVE
N.W. STAIR
NO ROOF ACCESS
20
B2 THRU 24
5 FT
FROM GRADE
TO CENTER OF SIGN
NOTES:
1. THE SIGN FACE SHALL BE 12" X 14" AND FABRICATED FROM .080
ALUMINUM SHEET WITH 1½" RADIUS CORNERS.
2.
FONT STYLE USED IS HANDEL GOTHIC BT CAPITAL FONTS
3.
THE SIGN FACE SHALL HAVE A WHITE 3M DIAMOND GRADE REFLECTIVE
SHEETING (DG³4090 SERIES OR EQUIVALENT) APPLIED AS A
BACKGROUND TO THE ALUMINUM PLATES.
4. LETTERING / GRAPHICS SHALL BE HIGH PERFORMANCE, NON-REFLECTIVE,
CUTTABLE VINYL (3M 7725 SERIES) INVERSE CUT TO ALLOW WHITE
REFLECTIVE BACKGROUND TO SHOW THROUGH.
5.
ALL SIGN IMAGING SHALL BE IN COMPLIANCE WITH THE REFLECTIVE
SHEETING MANUFACTURES MATCH COMPONENT SYSTEM.
7.
REQUIRES PRE-APPROVAL BY A FIRE CODE OFFICIAL. 602-262-6771
STAIRWELL MARKING DETAIL
FIGURE D.39
568
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
APPENDIX D
12” x 12”
Hazardous Materials Identification
(Fire Diamond)
Occupancy Name:
Occupancy Address:
NUMBER SYSTEM
3
2
4 - SEVERE DANGER
4
OXY
3 - HIGH DANGER
TOP
Number in this space
shall be RED
2 - MODERATE DANGER
1 - SLIGHT HAZARD
0 - NO HAZARD
EXAMPLE
Number in this space
shall be YELLOW
with a black outline
Number in this space
shall be BLUE
Letters in this space
shall be BLACK
(White Special Hazard Box)
SPECIFICATIONS:
The sign plate shall be a 12” square with a thickness of .080 aluminum construction.
Radius Corners
The sign face shall have a white reflective vinyl background.
Font style used - Numbers: Helvetica Bold Extended, Letters: Helvetica Blk BT.
Numbers shall be a minimum of 3½” high with 11/16” stroke width.
Lettering for White Special Hazard Box:
One Line
1 3/4” high w/ 9/16” stroke width.
Two Lines
1 3/8” high w/ 7/16” stroke width.
Three Lines
1¼” high w/ 3/8” stroke width.
Numbers and Letters arranged by color as shown above.
Sign shall be posted at location as approved by the City of Phoenix Fire Department.
Fire Prevention - HazMat
(602)262-6771
FIGURE D.40
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
569
570
WATER LINE
WL
Rev. 02/2013
REQUIRED BY NFPA 24. 7.1.1.1
REQUIRED BY STATE
PLUMBING CODE
NFPA 13.8.1.6.1.1
13.8.1
WATER LINE
STREET
F.L.
FIGURE D.41
N.T.S.
FIGURE P507.7a
REQUIRED
NFPA 13-6.7.1.3
OS&Y A/S CONTROL VALVE
HYDRANT
FIRE DEPT. CONNECTION
POST INDICATOR VALVE
SECTIONAL VALVE OR CONTROL VALVE
BACK FLOW ASSEMBLY
A/S RISER
FIRELANE
FL
REQUIRED BY STATE
PLUMBING CODE
NFPA 13.8.1.6.1.1
REQUIRED 24.6.1.5
APPENDIX D
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
F.L.
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
WATER LINE
WL
F.L.
BY P508.3
WATER LINE
Rev. 02/2013
OS&Y A/S CONTROL VALVE
HYDRANT
FIRE DEPT. CONNECTION
POST INDICATOR VALVE
FIGURE D.42
SECTIONAL VALVE OR CONTROL VALVE
BACK FLOW ASSEMBLY
A/S RISER
FIRELANE
FL
REQUIRED BY NFPA 24.7.1.1.1
NON-INDICATIONG VALVE
PERMITTED BY 13.8.17.3.3
REQUIRED BY STATE
PLUMBING CODE
NFPA 13.15.1.8.3
WL
STREET
N.T.S.
FIGURE 507.7b
REQUIRED BY STATE
PLUMBING CODE
NFPA 13.8.1.1.2.5
WL
REQUIRED 24.6.1.5
APPENDIX D
571
WATER LINE
WL
Rev. 02/2013
STREET
OS&Y A/S CONTROL VALVE
HYDRANT
FIRE DEPT. CONNECTION
POST INDICATOR VALVE
SECTIONAL VALVE OR CONTROL VALVE
BACK FLOW ASSEMBLY
A/S RISER
FIRELANE
WATER LINE
572
FIGURE D.43
P508.3
WATER LINE
STREET
N.T.S.
FIGURE 507.7c
P508.3
F.L.
FL
2
2
40 FT FROM BUIL
24.6.3.3.1
REQUIRED BY 24.6.3.1
APPENDIX D
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
WATER LINE
WL
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS
Rev.02/2013
OS&Y A/S CONTROL VALVE
HYDRANT
FIRE DEPT. CONNECTION
POST INDICATOR VALVE
N.T.S.
FIGURE D.44
WATER LINE
STREET
13.8.16.1.1.3.2
FL
NO VALVES IN F.D.C. LINE 24.6.2.2
FIGURE 507.7d
SECTIONAL VALVE OR CONTROL VALVE
BACK FLOW ASSEMBLY
A/S RISER
FIRELANE
FL
APPENDIX D
573
574
2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS