APPENDIX D FIRE DEPARTMENT DETAILS (Adopted for Reference Only) SECTION D101 GENERAL D101.1 Scope. The following pages provide common detail that the Phoenix Fire Department, Fire Prevention office have approved for both new and existing buildings located within the City of Phoenix. These details can be used by design professionals and contractors. These details can be modified and reviewed and approved. The CAD drawing for each of these details is available on our website at: www.phoenix.gov/fire/prevention. The remainder of this appendix is organized by components: Fire Protection Signage Details Fire Lane Signage Controlled Access Gates Hydrants Directories Stairways Hazmat Identification Section Valves 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 529 APPENDIX D FIRE DEPT. SPRINKLER RISER ROOM SIGN FIRE DEPT. 12" SPRINKLER RISER RM. 1½" LETTERING WITH .344 STROKE (BETWEEN 5/16" & 3/8") 12" NOTES: 1. THE SIGN FACE SHALL BE 12" X12" AND FABRICATED FROM .080 ALUMINUM SHEET WITH 1½" RADIUS CORNERS. 2. FONT STYLE USED IS HANDEL GOTHIC BT CAPITAL FONTS, ADDITIONAL KERNING BETWEEN LETTERS AS SHOWN. 3. THE SIGN FACE SHALL HAVE A WHITE 3M DIAMOND GRADE REFLECTIVE SHEETING (DG³4090 SERIES OR EQUIVALENT) APPLIED AS A BACKGROUND TO THE ALUMINUM PLATES. 4. LETTERING SHALL BE DONE ONE OF THE FOLLOWING WAYS: A. 3M SCOTCHLITE ACRYLIC, TRANSPARENT, ELECTRONIC CUTTABLE FILM (RED 1172 SERIES) INVERSE CUT TO ALLOW WHITE REFLECTIVE BACKGROUND TO SHOW THROUGH. B. SCREEN PRINTED USING 3M 880 +OR 880Ä00 SERIES TRAFFIC SIGN RED TRANSLUCENT INK. BOTH PROCESSES ( A OR B ) WILL ACCOMPLISH A RED FIELD WITH WHITE COPY. 5. ALL SIGN IMAGING SHALL BE IN COMPLIANCE WITH THE REFLECTIVE SHEETING MANUFACTURES MATCH COMPONENT SYSTEM. 6. REQUIRES PRE-APPROVAL BY A FIRE CODE OFFICIAL 602-262-6771. FIGURE D.1 530 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS APPENDIX D SPRINKLER CONNECTION SIGN DETAIL 12" 18" FIRE DEPT. 2“ RED LETTERING 3/8“ STROKE 2½“ LETTERING 5/8” STROKE ON WHITE REFLECTIVE BACKGROUND 150’ 2“ LETTERING 3/8” STROKE ON WHITE REFLECTIVE BACKGROUND BLDGS 4&5 RED ARROW SPRINKLER CONNECTION 1½“ RED LETTERING 3/8“ STROKE 5" NOTES: 1. THE SIGN PLATE SHALL BE 12” X 18” WITH A THICKNESS OF .080 ALUMINUM CONSTRUCTION AND 1½” RADIUS CORNERS. 2. SIGN FACE SHALL HAVE A WHITE REFLECTIVE BACKGROUND WITH RED LEGEND, USING THE STANDARD 3M SCOTCHLITE SIGN FACE NUMBER R7-32 OR EQUIVALENT, WITH RED SCREED PRINTED LETTERING AS SHOWN ABOVE. 3. INFORMATION LOCATED INSIDE RED ARROW WILL BE DETERMINED BY FIRE PREVENTION EMERGENCY ACCESS OFFICER. 4. REQUIRES PRE-APPROVAL BY FIRE CODE OFFICIAL. SPECIAL APPLICATION FIGURE D.2 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 531 APPENDIX D SPRINKLER CONTROL VALVE SIGN FOR ZONE APPLICATIONS 14" 9 2 16 " 14" SPRINKLER CONTROL VALVE FOR 1½" (1.5") LETTERING ZONE 3 2¼" (2.25) LETTERING SPRINKLER VALVE SIGN Serves Floors 1 thru 4 NOTES: 1. THE SIGN FACE SHALL BE 14" X14" AND FABRICATED FROM .080 ALUMINUM SHEET WITH 1½" RADIUS CORNERS. 2. FONT STYLE USED IS HANDEL GOTHIC BT CAPITAL FONTS. ADDITIONAL KERNING BETWEEN LETTERS AS SHOWN. 3. THE SIGN FACE SHALL HAVE A WHITE 3M DIAMOND GRADE REFLECTIVE SHEETING (DG³4090 SERIES OR EQUIVALENT) APPLIED AS A BACKGROUND TO THE ALUMINUM PLATES. 4. LETTERING SHALL BE DONE ONE OF THE FOLLOWING WAYS: A. 3M SCOTCHLITE ACRYLIC, TRANSPARENT, ELECTRONIC CUTTABLE FILM (RED 1172 SERIES) INVERSE CUT TO ALLOW WHITE REFLECTIVE BACKGROUND TO SHOW THROUGH. B. SCREEN PRINTED USING 3M 880 +OR 880Ä00 SERIES TRAFFIC SIGN RED TRANSLUCENT INK. BOTH PROCESSES ( A OR B ) WILL ACCOMPLISH A RED FIELD WITH WHITE COPY. 5. ALL SIGN IMAGING SHALL BE IN COMPLIANCE WITH THE REFLECTIVE SHEETING MANUFACTURES MATCH COMPONENT SYSTEM. 6. REQUIRES PRE-APPROVAL BY A FIRE CODE OFFICIAL. 602-262-6771 Special Application FIGURE D.3 532 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS APPENDIX D APPROVED PHOENIX FIRE DEPARTMENT SPRINKLER SIGNS Each fire department connection shall be identified by a permanent weather resistant sign. When the building system supplied by the FDC does not supply the entire building or supplies multiple buildings the sign shall identify the buildings or areas of the buildings supplied by the FDC. Fire department connections shall designate service design - for example, AUTOSPKR., STANDPIPE, and DRYSTANDPIPE. A sign shall also indicate the pressure required at the inlets to deliver the greatest systems demand if the system demand pressure is greater than 150 psi. 12" F.D.C. 3" X ½" LETTERING (TYPICAL FOR ALL SIGNS) 7 9 1 16 " X 32 " LETTERING F.D.C. 12" 3" X ½" LETTERING F.D.C. 7 9 1 16 " X 32 " LETTERING 3" X ½" LETTERING (TYPICAL FOR ALL SIGNS) F.D.C. 1 6" 5/1 11" 3" X ½" LETTERING 7 9 1 16 " X 32 " LETTERING F.D.C. 3" X ½" LETTERING 7 9 1 16 " X 32 " LETTERING 200 W. WASH 1" LETTERING WHITE REFLECTIVE BACKGROUND RED TRANSPARENT FILM CONSTRUCTION and INSTALLATION NOTES: 1. THE SIGN FACE SHALL BE 12" X12" AND FABRICATED FROM .080 ALUMINUM SHEET WITH 1½" RADIUS CORNERS. 2. FONT STYLE USED IS HANDEL GOTHIC BT CAPITAL FONTS 3. THE SIGN FACE SHALL HAVE A WHITE 3M DIAMOND GRADE REFLECTIVE SHEETING (DG³4090 SERIES OR EQUIVALENT) APPLIED AS A BACKGROUND TO THE ALUMINUM PLATES. 4. LETTERING / GRAPHICS SHALL BE DONE ONE OF THE FOLLOWING WAYS: A. 3M SCOTCHLITE ACRYLIC, TRANSPARENT, ELECTRONIC CUTTABLE FILM (RED 1172 SERIES) INVERSE CUT TO ALLOW WHITE REFLECTIVE BACKGROUND TO SHOW THROUGH. B. SCREEN PRINTED USING 3M 880 +OR 880Ä00 SERIES TRAFFIC SIGN RED TRANSLUCENT INK. BOTH PROCESSES ( A OR B ) WILL ACCOMPLISH A RED FIELD WITH WHITE COPY. ALL SIGN IMAGING SHALL BE IN COMPLIANCE WITH THE REFLECTIVE SHEETING MANUFACTURES MATCH COMPONENT SYSTEM. 5. 6. TO BE INSTALLED ON THE WALL 5 - 7 FEET ABOVE GRADE OVER F.D.C. INLET. 7. REQUIRES PRE-APPROVAL BY A FIRE CODE OFFICIAL. 602-262-6771 FIGURE D.4 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 533 APPENDIX D FIRE DEPT. COMMAND ROOM SIGN 12" COMMAND 1½" LETTERING WITH .344 STROKE (BETWEEN 5/16" & 3/8") CENTER 12" NOTES: 1. THE SIGN FACE SHALL BE 12" X12" AND FABRICATED FROM .080 ALUMINUM SHEET WITH 1½" RADIUS CORNERS. 2. FONT STYLE USED IS HANDEL GOTHIC BT CAPITAL FONTS 3. THE SIGN FACE SHALL HAVE A WHITE 3M DIAMOND GRADE REFLECTIVE SHEETING (DG³4090 SERIES OR EQUIVALENT) APPLIED AS A BACKGROUND TO THE ALUMINUM PLATES. 4. LETTERING SHALL BE DONE ONE OF THE FOLLOWING WAYS: A. 3M SCOTCHLITE ACRYLIC, TRANSPARENT, ELECTRONIC CUTTABLE FILM (RED 1172 SERIES) INVERSE CUT TO ALLOW WHITE REFLECTIVE BACKGROUND TO SHOW THROUGH. B. SCREEN PRINTED USING 3M 880+OR 880Ä00 SERIES TRAFFIC SIGN RED TRANSLUCENT INK. BOTH PROCESSES ( A OR B ) WILL ACCOMPLISH A RED FIELD WITH WHITE COPY. 5. ALL SIGN IMAGING SHALL BE IN COMPLIANCE WITH THE REFLECTIVE SHEETING MANUFACTURES MATCH COMPONENT SYSTEM. 6. REQUIRES PRE-APPROVAL BY A FIRE CODE OFFICIAL. 602-262-6771 FIGURE D.5 534 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS APPENDIX D RESIDENTIAL MULTIFAMILY BROWN OR GREEN F.D.C. SIGNS Each fire department connection shall be identified by a permanent weather resistant sign. When the building system supplied by the FDC does not supply the entire building or supplies multiple buildings the sign shall identify the buildings or areas of the buildings supplied by the FDC. Fire department connections shall designate service design - for example, AUTOSPKR., STANDPIPE, and DRYSTANDPIPE. A sign shall also indicate the pressure required at the inlets to deliver the greatest systems demand if the system demand pressure is greater than 150 psi. 12" F.D.C. 3" X ½" LETTERING (TYPICAL FOR ALL SIGNS) 7 9 1 16 " X 32 " LETTERING F.D.C. 12" 3" X ½" LETTERING F.D.C. 7 9 1 16 " X 32 " LETTERING 3" X ½" LETTERING (TYPICAL FOR ALL SIGNS) F.D.C. 1 6" 5/1 11" 3" X ½" LETTERING F.D.C. 7 9 1 16 " X 32 " LETTERING 3" X ½" LETTERING 7 9 1 16 " X 32 " LETTERING 200 W. WASH 1" LETTERING WHITE REFLECTIVE BACKGROUND BROWN OR GREEN TRANSPARENT FILM CONSTRUCTION and INSTALLATION NOTES: 1. THE SIGN FACE SHALL BE 12" X12" AND FABRICATED FROM .080 ALUMINUM SHEET WITH 1½" RADIUS CORNERS. 2. FONT STYLE USED IS HANDEL GOTHIC BT CAPITAL FONTS 3. THE SIGN FACE SHALL HAVE A WHITE 3M DIAMOND GRADE REFLECTIVE SHEETING (DG³4090 SERIES OR EQUIVALENT) APPLIED AS A BACKGROUND TO THE ALUMINUM PLATES. 4. LETTERING / GRAPHICS SHALL BE DONE ONE OF THE FOLLOWING WAYS: A. 3M SCOTCHLITE ACRYLIC, TRANSPARENT, ELECTRONIC CUTTABLE FILM (BROWN 1179 SERIES OR GREEN 1177 SERIES) INVERSE CUT TO ALLOW WHITE REFLECTIVE BACKGROUND TO SHOW THROUGH. B. SCREEN PRINTED USING 3M 880+OR 880Ä00 SERIES TRAFFIC SIGN BROWN TRANSLUCENT INK. BOTH PROCESSES ( A OR B ) WILL ACCOMPLISH A BROWN FIELD WITH WHITE COPY. ALL SIGN IMAGING SHALL BE IN COMPLIANCE WITH THE REFLECTIVE SHEETING MANUFACTURES MATCH COMPONENT SYSTEM. 5. 6. TO BE INSTALLED ON THE WALL 5 - 7 FEET ABOVE GRADE OVER F.D.C. INLET. 7. REQUIRES PRE-APPROVAL BY A FIRE CODE OFFICIAL. 602-262-6771 FIGURE D.6 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 535 APPENDIX D F.D.C. SIGN POST INSTALLATION DETAIL CARRIAGE BOLTS (TYPICAL 2 PLACES) BEND BOLT TO REDUCE TAMPERING 3" X ½" LETTERING (TYPICAL FOR ALL SIGNS) FIRE LANE SIGN MOUNTED WITH 2- ¼" CARRIAGE BOLTS 2- FLAT OR FENDER WASHERS 2-NUTS 3" X ½" LETTERING 1 7 16" X 9 32" LETTERING 3" X ½" LETTERING HEAVY DUTY "U" CHANNEL POST 2 LBS. PER FT. 5FT REQUIRED GRADE 18" CLASS 'A' CONCRETE FOOTING 12" DIA NOTES: 1. THE SIGN FACE SHALL BE 12" X 12" AND FABRICATED FROM .080 ALUMINUM SHEET WITH 1½" RADIUS CORNERS. 2. FONT STYLE USED IS HANDEL GOTHIC BT CAPITAL FONTS 3. THE SIGN FACE SHALL HAVE A WHITE 3M DIAMOND GRADE REFLECTIVE SHEETING (DG³4090 SERIES OR EQUIVALENT) APPLIED AS A BACKGROUND TO THE ALUMINUM PLATES. 4. LETTERING SHALL BE DONE ONE OF THE FOLLOWING WAYS: A. 3M SCOTCHLITE ACRYLIC, TRANSPARENT, ELECTRONIC CUTTABLE FILM (RED 1172 SERIES) INVERSE CUT TO ALLOW WHITE REFLECTIVE BACKGROUND TO SHOW THROUGH. B. SCREEN PRINTED USING 3M 880 +OR 880Ä00 SERIES TRAFFIC SIGN RED TRANSLUCENT INK. BOTH PROCESSES ( A OR B ) WILL ACCOMPLISH A RED FIELD WITH WHITE COPY. ALL SIGN IMAGING SHALL BE IN COMPLIANCE WITH THE REFLECTIVE SHEETING MANUFACTURES MATCH COMPONENT SYSTEM. 5. ARIZONA BLUE STAKE CALL TWO WORKING DAYS BEFORE YOU DIG (602) 263-1100 1-800-STAKE-IT 6. TO BE INSTALLED 5 FEET ABOVE GRADE, POST SHALL BE 12" TO 18" FROM BACK OF CURB OR BACK OF SIDEWALK AND MUST FACE THE ONCOMING TRAFFIC. 6. REQUIRES PRE-APPROVAL BY A FIRE CODE OFFICIAL. 602-262-6771 (OUTSIDE MARICOPA COUNTY) www.azbsinc.com FIGURE D.7 536 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 2" x ¼ " LETTERS 6. REQUIRES PRE-APPROVAL BY A FIRE CODE OFFICIAL. 602-262-6771 FIGURE D.8 6. INSTALLED KNOX KEY BOX MODEL 1658 NEXT TO LOCK ON FIRE DEPT. ACCESS DOOR. 5. ALL SIGN IMAGING SHALL BE IN COMPLIANCE WITH THE REFLECTIVE SHEETING MANUFACTURES MATCH COMPONENT SYSTEM. 4. LETTERING / GRAPHICS SHALL BE DONE ONE OF THE FOLLOWING WAYS: A. 3M SCOTCHLITE ACRYLIC, TRANSPARENT, ELECTRONIC CUTTABLE FILM (RED 1172 SERIES) INVERSE CUT TO ALLOW WHITE REFLECTIVE BACKGROUND TO SHOW THROUGH. B. SCREEN PRINTED USING 3M 880 +OR 880Ä00 SERIES TRAFFIC SIGN RED TRANSLUCENT INK. BOTH PROCESSES ( A OR B ) WILL ACCOMPLISH A RED FIELD WITH WHITE COPY. 3. THE SIGN FACE SHALL HAVE A WHITE 3M DIAMOND GRADE REFLECTIVE SHEETING (DG³4090 SERIES OR EQUIVALENT) APPLIED AS A BACKGROUND TO THE ALUMINUM PLATES. 2. FONT STYLE USED IS HANDEL GOTHIC BT CAPITAL FONTS NOTES: 1. THE SIGN FACE SHALL BE 12" X18" AND FABRICATED FROM .080 ALUMINUM SHEET WITH 1½" RADIUS CORNERS. 18" 12" KNOX KEY BOX 1658 WET STANDPIPE SIGN DETAIL APPENDIX D 537 APPENDIX D CONSTRUCTION ACCESS SIGN DURING CONSTRUCTION FIGURE D.9 538 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS APPENDIX D APPROVED PHOENIX FIRE DEPARTMENT FIRE LANE SIGNS 12" 12" 2" 18" 1½" P 3/4" 1¼" X 3/16" BLACK WHITE 8½" DIA. 2" 3/4" 1¼" X 3/16" RED 3/4" 4 1/16" 5" 1¼" X 3/16" 1¼" X 3/16" MOUNTING HOLES 1. THE SIGN PLATE SHALL BE A MINIMUM OF 12" X 18" WITH A THICKNESS OF .080 ALUMINUM CONSTRUCTION. 2. THE SIGN FACE SHALL HAVE A WHITE REFLECTIVE BACKGROUND WITH A RED LEGEND. USE THE STANDARD 3M SCOTCHLITE SIGN FACE NUMBER R7-32 OR EQUIVALENT, WITH RED SCREEN PRINTED LETTERING AS SHOWN ABOVE. 3. SPECIAL APPLICATION DETAILS MUST BE PRE-APPROVED BY A FIRE CODE OFFICIAL 602-262-6771 SPECIAL APPLICATION FIGURE D.10 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 539 APPENDIX D FIRE LANE SIGN POST AND INSTALLATION CARRIAGE BOLTS (TYPICAL 2 PLACES) BEND BOLT TO REDUCE TAMPERING 12" FIRE LANE SIGN MOUNTED WITH 2-CARRIAGE BOLTS 2-WASHERS 2-NUTS 18" HEAVY DUTY "U" CHANNEL POST 2 LBS. PER FT. (SEE DETAIL 1.4) 7 FT REQUIRED GRADE 18" CLASS 'A' CONCRETE FOOTING 12" DIA RECOMMEND THE FOLLOWING MATERIALS FOR INSTALLATION: 10 FT LONG U-CHANNEL GALVANIZED OR PAINTED POST FIRE SIGN (12" X 18") .080 ALUMINUM CONSTRUCTION WITH WHITE REFLECTIVE BACKGROUND AND RED SCREEN PRINTED LEGEND (SEE DETAIL 1.1) ¼" BOLTS & NUTS LARGE FLAT OR FENDER WASHERS ARIZONA BLUE STAKE CALL TWO WORKING DAYS BEFORE YOU DIG (602) 263-1100 1-800-STAKE-IT (OUTSIDE MARICOPA COUNTY) www.azbsinc.com SIGN MUST FACE THE ONCOMING TRAFFIC POST SHALL BE INSTALLED 12" TO 18" FROM BACK OF CURB OR BACK OF SIDEWALK FIRE DEPT. RECOMMENDS YOU BLUE STAKE BEFORE YOU DIG. FIGURE D.11 540 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS APPENDIX D APPROVED WALL MOUNT BRACKET FIRE LANE SIGN P P P 7 FT GRADE NOTES: 11 " 1716 1. SEE DETAIL FOR PROPER FIRE LANE PAINT STRIPING. 13 " 1116 1" SQUARE TUBING 2. THE SAME DISTANCES FOR SIGNAGE ON POSTS ALSO APPLIES TO THE WALL MOUNTED SIGNS. 3. FLAG MOUNT SIGNS MAY ONLY BE USED WHEN THERE IS NO ROOM FOR A POST. 20" 5/16"Ø HOLES (TYP. 4) 4. MUST BE PRE-APPROVED BY A FIRE CODE OFFICIAL 602-262-6771 3 16" THICK X 4" FLAT BAR BASE PLATE 4" FIGURE D.12 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 541 APPENDIX D FIRE LANE STRIPING FOR HYDRANTS R 4FT BACK OF CURB BLUE HYDRANT REFLECTOR 4" STEAMER CAP FIRE LANE RED CURB 8½' to 9' 8½' to 9' 16' TYPICAL LANDSCAPING ISLAND TYPICAL PARKING SPACE TYPICAL PARKING SPACE TYPICAL PARKING SPACE 4 FT CLEARANCE FOR FIRE FIGHTER ACCESS 8½' to 9' FIRE LANE RED CURB WHITE STENCIL SHALL BE CENTERED 15 FT 15 FT 1 FT TO 6 FT BACK OF CURB CURB SIDEWALK NOTES: TYPICAL PARALLEL PARKING STREET DETAIL FOR HYDRANT INSTALLATION FIGURE D.13 542 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS APPENDIX D ALTERNATIVE FIRE LANE MARKING SYSTEM SPECIAL APPLICATION DETAILS MUST BE PRE-APPROVED BY A FIRE CODE OFFICIAL 602-262-6771 FIRE LANE 8" WHITE THERMOPLASTIC STRIPING OR WHITE GLASS BEAD PAINT - APPLY 2 COATS 35 FT RADIUS FIRE LANE MIN. 45 FT CENTER TURNING RADIUS 55 FT RADIUS E AN EL FIR FIRE LANE LEGEND PLACED EVERY 100 FT 8" WHITE THERMOPLASTIC STRIPING FIRE LANE MIN. 45 FT CENTER TURNING RADIUS 100 FT LETTERS 24"HT. 4" STROKE USING HANDEL GOTHIC CAPTIAL LETTERS INSTALL PREFORMED PAVEMENT MARKINGS TYPE 1 (AZ. DOT. SECT. 705-705-2.01) FIRE LANE 12 FT - 3 IN 20 FT FIRE LANE 20 FT 21 FT- 4 IN MINIMUM WIDTH SPECIAL APPLICATION FIGURE D.14 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 543 APPENDIX D ALTERNATIVE FIRE LANE MARKING FOR HARD SURFACES ALTERNATIVE FIRE LANE MARKING FOR HARD SURFACES 100FT 50FT 50FT ON CENTER WAREHOUSE TYPICAL PERIMETER FIRE LANE MARKING SYSTEM BLUE HYDRANT MARKER PASSING AREA OR PULL OUT HYDRANT FIRE LANE SIGN FIRE LANE SIGN RED REFLECTIVE MARKER 100 FT FIRE DEPT. APPROVED PIPE GATE 20' WIDE DRIVEWAY 20FT PARKING LOT INSTALLATION INSTRUCTIONS for HARD SURFACES (Asphalt / Concrete): 3 TYPES OF ADHESIVE ARE ACCEPTABLE FOR INSTALLING RED & BLUE HYDRANT MARKERS A. WEDCO A-4036 EPOXY PART A RESIN PART B CATALYST B. THERMOSET EP-308 EPOXY RESIN PART 'A' EP-308 EPOXY HARDENER PART 'B' C. BITUMINOUS ADHESIVE NOTE: LIQUID NAILS TYPE ADHESIVE IS UNACCEPTABLE REFLECTOR REQUIREMENTS The adhesive shall be placed uniformly on the cleaned pavement surface in an amount sufficient to result in complete coverage of the area of contact of the markers, with no void present and with a slight excess after the markers have been placed. The markers shall be placed in position and pressure applied until firm contact is made with the pavement. The marker shall be protected against impact until the adhesive has set to the degree acceptable to the Engineer. SPECIAL APPLICATION DETAILS MUST BE PRE-APPROVED BY A FIRE CODE OFFICIAL 602-262-6771 FIGURE D.15 544 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS APPENDIX D ALTERNATIVE SURFACE INTERIOR FIRE LANE DETAIL LIGHTING FIXTURES TO BE OUTSIDE OF THE 20 FT CLEAR FIRE LANE STANDARD FIRE LANE SIGN AT TERMINATION POINT 8" RED REFLECTORS 2" ABOVE GRADE 10" GRASS, DECOMPOSED GRANITE OR PAVING SYSTEM CONCRETE CURB R 55 FT R 35 FT 8" WIDTH CURB SEE DETAIL 1 DECOMPOSED GRANITE OR APPROVES GRASS PAVING SYSTEM 20 FT RED REFLECTORS 25 FT ON CENTERS REMOVABLE FIRE LANE SIGN HYDRANT 3 TYPES OF ADHESIVE ARE ACCEPTABLE FOR INSTALLING RED MARKERS A. WEDCO A-4036 EPOXY PART A RESIN PART B CATALYST B. THERMOSET EP-308 EPOXY RESIN PART 'A' EP-308 EPOXY HARDENER PART 'B' C. BITUMINOUS ADHESIVE NOTE: LIQUID NAILS TYPE ADHESIVE IS UNACCEPTABLE REFLECTOR REQUIREMENTS The adhesive shall be placed uniformly on the cleaned pavement surface in an amount sufficient to result in complete coverage of the area of contact of the markers, with no void present and with a slight excess after the markers have been placed. The markers shall be placed in position and pressure applied until firm contact is made with the pavement. The marker shall be protected against impact until the adhesive has set to the degree acceptable to the Engineer. 20 FT MIN STANDARD FIRE 25 FT LANE SIGN RED MARKERS INSTALLATION INSTRUCTIONS: ALTERNATIVE SURFACE INTERIOR FIRE LANE N.T.S. 1. FIRE LANES SHALL HAVE A VERTICAL CLEARANCE OF NO LESS THAN 14 FT. AND A MIN. WIDTH OF 20 FT. 2. FULL 20 FT. FIRE LANE WIDTH SHALL BE CONSTRUCTED WITH A COMBINATION OF HARD SURFACE AND PRE-ENGINEERED PLASTIC PAVER SYSTEM AS APPROVED BY THE CITY. 3. FIRE LANE CAN MEANDER, BUT SHALL NOT EXCEED THE MIN. 45 FT CENTER LINE TURNING RADIUS. (35' RADIUS INSIDE / 55' RADIUS OUTSIDE) 4. AREAS OUTSIDE AND BETWEEN WALKS MUST BE DECOMPOSED GRANITE OR APPROVED GRASS PAVING SYSTEM IN THE FIRE LANE AREA. 5. REFER TO STANDARD ALTERNATIVE SURFACE FIRE APPARATUS ROAD STIPULATIONS PAGE AND PHOENIX FIRE CODE CHAPTER 9. FIGURE D.16 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 545 APPENDIX D INTERIOR FIRE LANE DETAIL 8" RED REFLECTORS 2" ABOVE GRADE STANDARD FIRE LANE SIGN TERMINATION POINT 20' MIN GRASS OR DECOMPOSED GRANITE 10" CONCRETE CURB RED REFLECTORS 25 FT ON CENTERS 4'-6" 4' 3' 4' 4'-6" LIGHTING TO BE OUTSIDE OF THE 20 FT CLEAR FIRE LANE 20' MIN. 25FT O.C RED REFLECTORS. REMOVABLE FIRE LANE SIGN COLLECTOR SIDEWALK INTERSECTING SIDEWALKS & CROSSOVERS CAN OCCUR AT ANY POINT AS NEEDED DECOMPOSED GRANITE OR APPROVED GRASS PAVING SYSTEM REMOVABLE FIRE LANE SIGN CONCRETE SIDEWALK RIBBONS; THICKNESS AS REQ'D. PER SOILS REPORT PEDESTRIAN SIDEWALK R=55' R=45' R=35' ROLLED CURB PAINTED RED 20' MIN STANDARD FIRE LANE SIGN 8" WIDTH CURB FROM DRIVEWAY TO BEGINNING OF DOUBLE SIDEWALK SEE DETAIL #2 4' 20' MIN DRIVEWAY WIDTH VARIES SIDEWALK SINGLE SIDEWALK RIBBON ONLY TO EXTEND TO CURB, IF NEEDED. (COLLECTOR SIDEWALK PARALLEL TO CURB PREFERRED, TO DISCOURAGE UNAUTHORIZED ACCESS. SEE DETAIL #1 ABOVE) 1. FIRE LANES SHALL HAVE A VERTICAL CLEARANCE OF NO LESS THAN 14 FT., AND A MIN. WIDTH OF 20 FT. 2. FULL 20 FT. FIRE LANE WIDTH SHALL BE CONSTRUCTED WITH A COMBINATION OF HARD SURFACE AND PRE-ENGINEERED PLASTIC PAVER SYSTEM AS APPROVED BY THE CITY. 3. FIRE LANE CAN MEANDER, BUT SHALL NOT EXCEED THE MIN. 45 FT CENTER LINE TURNING RADIUS. (35' RADIUS INSIDE / 55' RADIUS OUTSIDE) 4. AREAS OUTSIDE AND BETWEEN WALKS MUST BE DECOMPOSED GRANITE OR APPROVED GRASS PAVING SYSTEM IN THE FIRE LANE AREA. 5. REFER TO STANDARD ALTERNATIVE SURFACE FIRE APPARATUS ROAD STIPULATIONS PAGE AND PHOENIX FIRE CODE CHAPTER 9 6. RED MARKERS INSTALLATION INSTRUCTIONS: 3 TYPES OF ADHESIVE ARE ACCEPTABLE FOR INSTALLING RED MARKERS A. WEDCO A-4036 EPOXY PART A RESIN PART B CATALYST B. THERMOSET EP-308 EPOXY RESIN PART 'A' EP-308 EPOXY HARDENER PART 'B' C. BITUMINOUS ADHESIVE NOTE: LIQUID NAILS TYPE ADHESIVE IS UNACCEPTABLE REFLECTOR REQUIREMENTS The adhesive shall be placed uniformly on the cleaned pavement surface in an amount sufficient to result in complete coverage of the area of contact of the markers, with no void present and with a slight excess after the markers have been placed. The markers shall be placed in position and pressure applied until firm contact is made with the pavement. The marker shall be protected against impact until the adhesive has set to the degree acceptable to the Engineer. FIGURE D.17 546 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS APPENDIX D REMOVABLE FIRE LANE BOLLARD 4" 1 1/ 2 3/4" 4½" 1 1/2" 3" /4" 13 21 /2" 10" Ø8" 6" 5" Ø68 7" 10" 6" SQUARE TUBE X 4' - 10" L 3/16" WALL BOLLARD BOLLARDS SHALL BE PAINTED CHROME YELLOW BOLLARD SHALL BE 6" DIA. INSIDE X 6 5/8" DIA. OUTSIDE SCHEDULE 40 PIPE 2" X 4" SLOTTED HAND HOLE BOTH SIDES 3' 2" WIDE STEEL COLLAR WITH CUT OUT FOR 4" LOCKING L - BRACKET 7" SQ. TUBE X 2'-4" L X 3/8" WALL SLEEVE 4'-10" SLEEVE PIPE SHALL BE 6 7/8" DIA INSIDE X 8" DIA OUTSIDE SCHEDULE 160 PIPE GRADE ANGLE IRON STITCH WELD TO SLEEVE 2'-4" 2' 2'-6" 1' ARIZONA BLUE STAKE CALL TWO WORKING DAYS BEFORE YOU DIG (602) 263-1100 1'-6" 1-800-STAKE-IT (OUTSIDE MARICOPA COUNTY) www.azbsinc.com FIGURE D.18 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 547 APPENDIX D APPROVED PHOENIX FIRE DEPT. GATE ACCESS SIGN 8" 4" NOTES: 1. THE SIGN FACE SHALL BE 8" X 4" AND FABRICATED FROM .080 ALUMINUM SHEET WITH ½" RADIUS CORNERS. 2. LETTERS 1¼" X ¼"STROKE, FONT STYLE USED IS HANDEL GOTHIC BT CAPITAL FONTS. 3. THE SIGN FACE SHALL HAVE A WHITE 3M DIAMOND GRADE REFLECTIVE SHEETING (DG³4090 SERIES OR EQUIVALENT) APPLIED AS A BACKGROUND TO THE ALUMINUM PLATES. 4. LETTERING / GRAPHICS SHALL BE DONE ONE OF THE FOLLOWING WAYS: A. 3M SCOTCHLITE ACRYLIC, TRANSPARENT, ELECTRONIC CUTTABLE FILM (RED 1172 SERIES) INVERSE CUT TO ALLOW WHITE REFLECTIVE BACKGROUND TO SHOW THROUGH. B. SCREEN PRINTED USING 3M 880 OR 88000 SERIES TRAFFIC SIGN RED TRANSLUCENT INK. BOTH PROCESSES ( A OR B ) WILL ACCOMPLISH A RED FIELD WITH WHITE COPY. 5. ALL SIGN IMAGING SHALL BE IN COMPLIANCE WITH THE REFLECTIVE SHEETING MANUFACTURES MATCH COMPONENT SYSTEM. 6. REQUIRES PRE-APPROVAL BY A FIRE CODE OFFICIAL. 602-262-6771 FIGURE D.19 548 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS GCB GCB 20 FT 6 GCB SEE STROBE DETAIL ABOVE PROPERTY SIDE 2 GCB 20 FT GCB FIGURE D.20 KNOX KEY SWITCH FLUSH MOUNTED 6 5 2 SEE DETAIL BELOW 90° ELBOW 4 ELECTRICAL JUNCTION BOX WITH MODULE UNIT 4 TAMPER RESISTANT SCREWS 4" X 4" SQUARE METAL POST LOCK NUT STROBE DETECTOR 3 GATE CONTROLLER BOX (GCB) 6 KNOX KEY SWITCH OPEN Requires Permit THE MINIMUM OVERALL WIDTH OF GATE SHALL BE 20 FEET STREET SIDE THE MINIMUM OVERALL WIDTH OF GATE SHALL BE 20 FEET APPROVED EMERGENCY KEY SWITCH SHALL BE INSTALLED ON THE ENTRANCE AND EXIT SIDE OF EACH ACCESS GATE. ENTRANCE SWITCH SHALL BE LOCATED ABOVE THE RESIDENCE KEY PAD 5½ FT FROM GRADE. EXIT SWITCH SHALL BE RECESSED INTO THE 4" X 4" POST WITH THE DUAL DETECTORS AND POWER MODULE UNIT. 3 4" X 4" POST WITH SEE STROBE DETAIL PREEMPTION STROBE DETECTOR ELEVATION VIEW 6 F.D. ACCESS THE 4" X 4" SQUARE POST WITH DETECTOR AND POWER MODULE SHALL BE INSTALLED ON THE PROPERTY SIDE OF THE GATE. THE POWER MODULE SHALL BE MOUNTED IN AN ELECTRICAL JUNCTION BOX, UNDER THE DETECTORS ON THE SAME 4" X 4" METAL POST. 5 4 DETECTORS SHALL POINT TOWARD THE APPROACH PATH AND EXIT PATH OF THE EMERGENCY VEHICLES. DETECTORS MUST ACTIVATE WITHIN 150 FEET FROM GATE. DETECTORS SHALL BE MOUNTED 8 TO 10 FEET FROM GRADE ON A 4" X 4" METAL POST. DETECTORS SHALL BE ON SEPARATE POST, NOT ON GUIDE POST. 2 3 EACH AUTOMATIC GATE SHALL HAVE TOMAR MODEL 2795-2 DUAL HEAD UNIT. 1 NOTES: OPEN F.D. ACCESS 5½ FT 5 MODULE LOCATION GATE CONTROLLER BOX APPROVED AUTOMATIC VEHICLE ACCESS GATE PREEMPTION DETECTORS WITH KNOX KEY SWITCHES 6 FT 8 FT ELECTRIC LINES IN CONDUIT APPENDIX D 549 APPENDIX D ENTRANCE ISLAND DETAILS FOR COMMUNITIES WITHOUT AUTOMATIC GATES F.D. KNOX KEY SWITCH (PERMIT REQUIRED) ACCESS SIGN REQUIRES PERMIT SITE DIRECTORY (REQUIRES PRE-APPROVAL) TENANT KEY PAD BLDG 1 BLDG 5 1 2 4 5 7 8 # 0 3 6 9 * TENANT CARD ACCESS BLDG 2 BLDG 4 BLDG 3 24" MINIMUM GRADE / PAVEMENT 8" ACCESS SIGN F.D. ACCESS 4" F.D. ACCESS F.D. KNOX KEY SWITCH FOR SINGLE GATE APPLICATION MODEL #3502 FOR DOUBLE GATE APPLICATION SWITCH MODEL #3513 FLUSH MOUNT TO FACE PLATE F.D. KNOX KEY SWITCH TENANT KEY PAD 5½ FT TENANT KEY PAD SITE DIRECTORY GRADE / PAVEMENT NOTES: 1. MUST HAVE AN ORIGINAL ORDER FORM AND FIRE DEPT. GATE PERMIT TO PURCHASE KEY SWITCH. 2. ORDER FORMS FOR KNOX KEY SWITCHES ARE AVAILABLE THROUGH THE INSPECTORS IN FIRE PREVENTION. CALL 602-262-6771 FOR ORDER FORMS. Permit Required FIGURE D.21 550 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS APPENDIX D AUTOMATIC GATE ENTRANCE WITH 3 STROBE DETECTORS OFFICE BUILDING PROPERTY SIDE OF GATE PROPERTY SIDE OF GATE 65° 65° GU SH ARD AC K PREEMPTION POST W/ KEY SWITCH MINIMUM OVERALL WIDTH OF GATE SHALL BE 20 FEET 65° F.D KNOX KEY SWITCH TENANT KEY PAD OR CARD ACCESS SITE DIRECTORY 1. DETECTORS SHALL BE MOUNTED 8 TO 10 FEET FROM GRADE ON A 4" X 4" METAL POST. NO MIRRORS SHALL SUBSTITUTE THE REQUIREMENTS OF TWO DETECTORS PER GATE. 2. DETECTORS SHALL POINT TOWARD THE APPROACH PATH AND EXIT PATH OF THE EMERGENCY VEHICLES. DETECTORS MUST ACTIVATE 150 FEET FROM GATE. 3. THE POWER MODULE SHALL BE MOUNTED IN AN ELECTRICAL JUNCTION BOX, UNDER THE DETECTORS ON THE SAME 4" X 4" METAL POST. 4. THE 4" X 4" SQUARE POST WITH DETECTOR AND POWER MODULE SHALL BE INSTALLED ON THE PROPERTY SIDE OF THE GATE. ( NOT ON GUIDE POST ) 5. APPROVED EMERGENCY KEY SWITCH SHALL BE INSTALLED ON THE ENTRANCE AND EXIT SIDE OF EACH ACCESS GATE. ENTRANCE SWITCH SHALL BE LOCATED ABOVE THE RESIDENCE KEY PAD 5½ FT FROM GRADE. EXIT SWITCH SHALL BE LOCATED ON THE 4" X 4" POST WITH THE DUAL DETECTORS AND POWER MODULE UNIT. FIGURE D.22 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 551 APPENDIX D 3 TOMAR PREEMPTION DETECTORS MODEL 2795-3 65° 65° 65° 30° STROBE SWITCH DETECTOR MODEL 2795-3 TOMAR ELECTRONICS, INC. 2100 W. OBISPO AVE GILBERT, AZ 85233 30° NOTE: 3 HEADS ARE REQUIRED WITH 90° TURNING LAYOUTS FIGURE D.23 552 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS L. Hertz F. D. ACCESS 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS Requires Permit APPROVED FIRE DEPT. ACCESS SIGN WITH WHITE 3M DIAMOND GRADE DG³ BACKGROUND PLACED BACK TO BACK. LOCKING BAR LENGTH IS DETERMINED BY THE FRAME WIDTH AND THE GAP WIDTH BETWEEN THE 2 GATES. REMOVE ALL SHARP EDGES & ROUND ALL CORNERS. WELD MODIFIED L-BRACKET TO GATE FRAME. ROUND ALL EDGES. (TYPICAL 2 PLACES) THE MINIMUM OVERALL WIDTH OF THE GATE OPENING SHALL BE 20 FT. (LARGER IS BETTER). 6" RED PARKING LOT STRIPING AT THE LOCATIONS SHOWN ON CONCRETE CURBS AND APPLIED TO ASPHALT (SEE EMERGENCY ACCESS DETAIL 8.5) APPROVED FIRE LANE SIGNS WITH REFLECTIVE BACKGROUND, PLACED BACK TO BACK, AND FASTENED ON ALL 4 CORNERS. FIRE DEPT. PADLOCK SHALL BE ACCESSIBLE FROM BOTH SIDES OF GATE. ORDER FORMS FOR KNOX PADLOCKS ARE AVAILABLE THROUGH EITHER THE GATE INSPECTORS IN FIRE PREVENTION OR CALL F.P. 602-262-6771 FOR ORDER FORMS. PROPERTY OWNER / MANAGEMENT PADLOCK ROUND ALL EDGES FIGURE D.24 5/8" ° HOLE LOCKING BAR PICKETS 6" 10" LENGTH VARIES L-BRACKET WELDED TO GATE FRAME 11/16" 2" OWNERS PADLOCK 5/8" DIA. 2" F. D. ACCESS 2" SQUARE GATE FRAME 2" 2" SQUARE GATE FRAME MANUAL SWING GATE APPROVED SIGN, WITH REFLECTIVE BACKGROUND, TO IDENTIFY THE NAME OF THE APARTMENT COMPLEX AND THE LOCATION OF THE ACCESS ENTRANCE RED STRIPING FOR FIRE LANE SHALL BE ON BOTH SIDES OF GATE NAME OF APARTMENT BLDG ENTRANCE ON STREET NAME FIRE APPARATUS ACCESS GATE 4" KNOX PADLOCK LOCKING SYSTEM DETAIL F. D. ACCESS GAP ½" - 1" MIN FIRE DEPT. KNOX PADLOCK DUAL LOCKING SYSTEM 2" X ½" STEEL BAR ROUND ALL EDGES F. D. ACCESS 8" APPENDIX D 553 FNAME:CLF_GATE_DET.CDR CALL FIRE PREVENTION-ACCESS OFFICER FOR QUESTIONS OR ASSISTANCE (602)256-3382 OR (602)262-6771 5/8” DIA HOLE (TYP. 2 PLACE) plan view 4 4 LOCKING BAR 2” X LG VARIES X ½” bar detail 4 5 NOTES: FIGURE D.25 F. D. ACCESS DUAL LOCK HASP DETAIL FOR CHAIN LINK FENCES FIRE DEPT KNOX PADLOCK MANUAL CHAIN LINK SECURITY GATE DETAILS 7. FIRE DEPT. KNOX PADLOCK SHALL BE ACCESSIBLE FROM BOTH SIDES OF THE GATE. ORDER FORMS FOR KNOX PADLOCKS ARE AVAILABLE THROUGH GATE INSPECTORS IN FIRE PREVENTION. CALL 602-262-6771 FOR ORDER FORMS. 6. THE MINIMUM OVERALL WIDTH OF THE GATE OPENING SHALL BE 20 FT. 5. WELD MODIFIED L-BRACKET TO GATE FRAME. 4. LOCKING BAR LENGTH IS DETERMINED BY THE FRAME WIDTH AND GAP WIDTH BETWEEN THE 2 GATES. REMOVE ALL SHARP EDGES/ROUND ALL CORNERS. 3/4” DIA HOLE MIN, HOLE DIAMETER DETERMINED BY SIZE OF PADLOCK. 3. STRIPING SHALL BE PAINTED SAFETY RED. 6” WIDE HASH STRIPING APPROX. 4FT TO 6FT APART. (SEE DETAIL 8.5) 2. APPROVED FIRE DEPT. ACCESS SIGN W/ WHITE 3M DIAMOND GRADE D 3 REFLECTIVE BACKGROUND PLACED BACK TO BACK SEE IFC) 1. APPROVED FIRE LANE SIGNS WITH REFLECTIVE BACKGROUND, PLACED BACK TO BACK AND FASTENED ON ALL 4 CORNERS (SEE IFC) Requires P e r m i t l bracket DETAIL 2 PULL BAR PROPERTY MANAGEMENT PADLOCK TENSION BAR TENSION BAND 2” ROUND GATE POST BAR UNLOCKED DETAIL 5 2 5 L-BRACKET WELD TO GATE FRAME 2”ROUND GATE POST 3 2” X ½” STEEL LOCKING BAR MIN. 3/4” DIA HOLES (TYP BOTH SIDES) 2” ROUND GATE POST L-BRACKET WELDED TO FRAME OF GATE SEE DETAIL 2” 3” 6” 554 DUAL LOCK HASP DETAIL STREET SIDE 4 PROFILE VIEW STREET SIDE 1 APPENDIX D 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 36" 6" 2 3 P 5" HEAVY DUTY BARREL HINGES (TYPICAL 4 PLACES) G3 FIGURE D.26 Requires Permit 3" X 3" X .120 POST 7 FT W/ CAP APPROVED COLOR CHROME YELLOW 2" X 2" X .120 RAILS APPROVED COLOR CHROME YELLOW G2 POST GATE NOTES: NOTES: GATE MANUFACTURED IN 3 SIZES- 16 FT, 20 FT AND 24 FT. RECOMMENDED POSTS/GATE COLOR CHROME YELLOW SEE FIRE LANE STRIPING DETAILS. 18" F.D. ACCESS G1 ABOVE GRADE P 1 APPROVED FIRE DEPT. ACCESS SIGN WITH WHITE 3M DIAMOND GRADE DG³ BACKGROUND PLACED BACK TO BACK. 9 48" 36" LOCKING BAR LENGTH IS DETERMINED BY THE FRAME WIDTH AND THE GAP WIDTH BETWEEN THE 2 GATES. REMOVE ALL SHARP EDGES / ROUND ALL CORNERS. 8 4 WELD MODIFIED L-BRACKET TO GATE FRAME. ROUND ALL EDGES. (TYPICAL 2 PLACES) 7 4 THE MINIMUM OVERALL WIDTH OF THE GATE OPENING SHALL BE 20 FT. 6 4 FIRE LANE STRIPING SHALL BE PROVIDED AT EACH MANUAL GATE. SEE F.D. DETAIL 8.5 FOR STRIPING EXAMPLES. 5 G2 APPROVED FIRE LANE SIGNS WITH REFLECTIVE BACKGROUND, PLACED BACK TO BACK AND FASTENED ON ALL 4 CORNERS. ¼" X 1½" MOUNTING STRAPS. 4 20 FT MINIMUM OPENING 7 8 9 FIRE DEPT. PADLOCK SHALL BE ACCESSIBLE FROM BOTH SIDES OF GATE. ORDER FORMS FOR KNOX PADLOCKS ARE AVAILABLE THROUGH EITHER THE GATE INSPECTORS IN FIRE PREVENTION OR CALL 602-262-6771 FOR ORDER FORMS. 3 4 PROPERTY OWNER/MANAGEMENT PADLOCK 2 1 G1 G2 5/8" ° HOLE LOCKING BAR 8 5/8" DIA. 2" FIRE DEPT KNOX PADLOCK 9 2" SQUARE GATE FRAME REFER TO APPROVED PFD ACCESS DETAIL F.D. ACCESS 8" 4" ROUNDED L-BRACKET WELDED TO GATE FRAME G2 2" 8 2" x ½" STEEL BAR ROUND ALL EDGES 3 7 L-BRACKET WELDED TO GATE FRAME TOP OF GATE FRAME 8 6" ROUND ALL EDGES 2" LENGTH VARIES MANUAL POST VEHICLE SECURITY GATE G3 PROPERTY PADLOCK 2 MANAGEMENT 7 GATE FRAME G2 GATE FRAME G1 11/16" MIN. APPROVED SIGN, WITH REFLECTIVE BACKGROUND, TO IDENTIFY THE NAME OF THE APARTMENT COMPLEX AND THE LOCATION OF THE ACCESS ENTRANCE. ¼" X 1½" MOUNTING STRAPS. 2" 3" 6" GENERAL NOTES: APPENDIX D 555 4 REBAR ANGLE IRON 2'-6" 48" 12" 24" 10 36" 24" X 36" CONCRETE POST FOOTINGS 10 GRADE APPROVED FIRE DEPT. ACCESS SIGN WITH WHITE 3M DIAMOND GRADE DG³ BACKGROUND PLACED BACK TO BACK. 9 DRIVEWAY P 20 FT MINIMUM OPENING G3 G2 G1 STOP POST FIGURE D.27 Requires Permit SEALED 5" HEAVY DUTY BARREL HINGES (TYPICAL 2 PLACES) 2" GATE FRAME (SQUARE OR ROUND) 11 GAUGE APPROVED COLOR CHROME YELLOW 2 11/16" 6" MINIMUM POST (SQUARE OR ROUND) ROUND POST SCHEDULE 40, SQUARE POST ¼" STOCK. POST 7 FT W/ CAP APPROVED COLOR CHROME YELLOW POST GATE NOTES: NOTE: GATE MANUFACTURED IN 3 SIZES-16FT, 20 FT AND 24 FT. RECOMMENDED POSTS / GATE COLOR CHROME YELLOW. 4 1 4 LOCKING BAR LENGTH IS DETERMINED BY THE FRAME WIDTH AND THE GAP WIDTH BETWEEN THE 2 GATES. REMOVE ALL SHARP EDGES / ROUND ALL CORNERS. 8 36" WELD MODIFIED L-BRACKET TO GATE FRAME. ROUND ALL EDGES. (TYPICAL 2 PLACES) 7 F.D. ACCESS THE MINIMUM OVERALL WIDTH OF THE GATE OPENING SHALL BE 20 FT. 6 G2 FIRE LANE STRIPING SHALL BE PROVIDED AT EACH MANUAL GATE. SEE F.D. DETAIL 8.5 FOR STRIPING EXAMPLES. 5 9 APPROVED FIRE LANE SIGNS WITH REFLECTIVE BACKGROUND, PLACED BACK TO BACK AND FASTENED ON ALL 4 CORNERS. ¼" X 1½" MOUNTING STRAPS. 4 G3 FIRE DEPT. PADLOCK SHALL BE ACCESSIBLE FROM BOTH SIDES OF GATE. ORDER FORMS FOR KNOX PADLOCKS ARE AVAILABLE THROUGH THE GATE INSPECTORS IN FIRE PREVENTION, OR CALL 602-262-6771 FOR ORDER FORMS. 3 G1 PROPERTY OWNER/MANAGEMENT PADLOCK 2 PLAN VIEW 4 FIRE LANE SIGNS APPROVED SIGN, WITH REFLECTIVE BACKGROUND, TO IDENTIFY THE NAME OF THE APARTMENT COMPLEX AND THE LOCATION OF THE ACCESS ENTRANCE. ¼" X 1½" MOUNTING STRAPS. 1 MIN. HT FROM ABOVE GRADE TO TOP OF GATE 6" LENGTH VARIES 3 PROPERTY SIDE 2" 9 8 8" REFER TO APPROVED PFD ACCESS DETAIL F.D. ACCESS VARIES ROUNDED L-BRACKET WELDED TO FRAME OF GATE GATE FRAME G2 2" SQUARE 5/8" DIA. 2" 4" FIRE DEPT KNOX PADLOCK 8 2" x ½" STEEL BAR ROUND ALL EDGES 3 7 ROUNDED L-BRACKET WELDED TO GATE FRAME G2 G1 GATE FRAME SINGLE MANUAL SWING SECURITY GATE 8 SEE DETAIL 8 ROUND ALL EDGES 2" G2 PROPERTY MANAGEMENT 2 PADLOCK 7 MIN. GATE FRAME G2 2" 3" 556 6" GENERAL NOTES: APPENDIX D 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 1' 20' 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 20' 20' 20' MINIMUM RED FIRE LANE STRIPING MUST BE A MINIMUM OF ONE HALF THE DISTANCE OF AREA BEHIND GATE. 10' 20' MINIMUN FIGURE D.28 10' Requires Permit STRIPING SHALL BE PAINTED SAFETY RED. 6 INCHES WIDE HASH STRIPING RUNNING APPROX. 4 FT. TO 6 FT. APART. 20' MINIMUM 4'TO 6' FIRE LANE STRIPING DETAILS FOR MANUAL GATES APPENDIX D 557 APPENDIX D MANUAL GATE APPLICATION FIRE LANE AND DIRECTIONAL SIGN .080 Aluminum Sheet WHITE 3M 4090 Diamond Grade, DG3 Reflective Sheeting See Note 3 See Note 4 & 5 FIGURE D.29 558 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS APPENDIX D APPROVED PEDESTRAIN GATE REQUIREMENTS 4" X 4" SQUARE POST SELF LATCHING DEVICE 4" X 4" SQUARE POST 5 FT MINIMUM 4 FT WELD KNOX KEY BOX TO WROUGHT IRON FENCE OWNERS PADLOCK KNOX KEY BOX MODEL 1658 54" MIN. VERTICAL CLEARANCE SEE NOTE 4 GRADE 24" X 24" X 24" FOOTING (TYPICAL BOTH SIDES-2 PLACES) KEY TO LOCK MUST BE PLACED IN THE APPROVED FIRE DEPT. KEY BOX. KEY BOX MUST BE WELDED ONTO FENCE PICKET FACING STREET. THE MINIMUM OVERALL WIDTH OF THE GATE OPENING SHALL BE 4 FT. THE VERTICAL CLEARANCE MINIMUM OF 2" AND A MAXIMUM OF 4" REFER TO BUILDING CODE REQUIREMENTS. ALL DIMENSIONS MUST COMPLY WITH THE PHOENIX CODE. FIGURE D.30 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 559 APPENDIX D BARRIERS FOR SWIMMING POOLS SPAS & HOT TUBS TURN OPEN KNOX KEY SWITCH DETAIL FOR MAG LOCKING APPLICATIONS ON PEDESTRIAN GATES 4" X 4" SQUARE POST SELF LATCHING DEVICE 4" X 4" SQUARE POST KNOX KEY SWITCH PART # 3502 KNOX KEY SWITCH RECESSED IN 4" POST FOR FIRE DEPT. ACCESS OWNERS ACCESS CARD OR KEYPAD 4 FT 6" 10" 11" 5 FT MINIMUM 54" MIN. VERTICAL CLEARENCE SEE NOTE 4 MAGNETIC LOCKING DEVISED GRADE 24" X 24" X 24" FOOTING (TYPICAL BOTH SIDES-2 PLACES) KNOX KEY SWITCH ACCESSIBLE FROM BOTH SIDES OF GATE THE MINIMUM OVERALL WIDTH OF THE GATE OPENING SHALL BE 4 FT. THE VERTICAL CLEARANCE MINIMUM OF 2" AND A MAXIMUM OF 4" REFER TO BUILDING CODE REQUIREMENTS. ALL DIMENSIONS MUST COMPLY WITH THE UNIFORM BUILDING CODE FOR SPECIAL USE AND OCCUPANCY SECTION 419 THRU 421. FIGURE D.31 560 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS APPENDIX D HYDRANT COLORS FOR PRIVATE AND PUBLIC HI, I’M A PRIVATE HYDRANT COOL, I’M A PUBLIC HYDRANT NOTES: 2 PUBLIC HYDRANTS SHALL BE PAINTED WITH OSHA APPROVED FEDERAL YELLOW 2 PRIVATE HYDRANTS SHALL BE PAINTED WITH OSHA APPROVED FEDERAL YELLOW AND HAVE A WHITE REFLECTIVE BONNET FIGURE D.32 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 561 562 GRADE ELECTRICAL CONDUIT 110 VOLT ALUMINUM LIP ON OFF SWITCH FLUORESCENT FIXTURES (TYP. 3) CONCRETE MASONRY UNIT (CMU) EQUAL 48" 50" 64" EQUAL EQ EQ 48" 8" 8" 24" 50" REQUIRES PERMIT FIGURE D.33 NOTE: 1. SHOULD INCLUDE PHOTO CELL. 2. REFER TO ENTRANCE ISLAND DETAIL MORE FOR DIMENSION SPECIFICATIONS. 80" 96" TO POWER SUPPLY 8" 8" 80" 8" 80" 50" EQ 20" 10" 16" EQ GRADE ELECTRICAL CONDUIT 110 VOLT APPENDIX D 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS APPENDIX D CORRIDOR SPREAD PLATE SAMPLE 24" 1" TYP. 1" 22" 1" NUMBER SIZE (FOUR DIGIT PLATE) FOUR FLOORS 4" X 5/8" BRUSH STROKE 4 DIGIT NUMBERS - THOUSAND SERIES 2" 10" ¼" LINE NUMBER SIZE (FOUR DIGIT PLATE) THREE FLOORS 18" 4" X 5/8" BRUSH STROKE 4 DIGIT NUMBERS - THOUSAND SERIES 20" NUMBER SIZE (THREE DIGIT PLATE) THREE FLOORS 18" 4" X 5/8" BRUSH STROKE 3 DIGIT NUMBERS - HUNDREDS SERIES 101 - 199 NUMBER RANGE NOTE: 1. THE FONT USED IS SEAGULL MD. FONTS USED FOR ADDRESSING MUST BE LEGIBLE AND EASY TO READ. 2. THE USE OF DIFFERENT FONTS MUST BE PRE-APPROVED BY A FIRE CODE OFFICIAL. FIGURE D.34 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 563 APPENDIX D MULTI-FAMILY NUMBERING DETAIL FOR COMMUNITIES WITH LESS THAN 100 TOTAL UNITS PER FLOOR 3 18" BLDG. NUMBER 3" STROKE 7" X 1" 27.5" 7" LETTERS 1" STROKE 36" ALL NUMBERING IS GILL SANS FONT NOTE: 1. THE FONT USED IS SEAGULL MD. FONTS USED FOR ADDRESSING MUST BE LEGIBLE AND EASY TO READ. 2. THE USE OF DIFFERENT FONTS MUST BE PRE-APPROVED BY A FIRE CODE OFFICIAL. FIGURE D.35 564 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS APPENDIX D APARTMENT DIRECTIONAL SIGN .080 Aluminum Sheet WHITE 3M 4090 Diamond Grade, DG3 Reflective Sheeting See Note 3 See Note 4 & 5 FIGURE D.36 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 565 APPENDIX D PRIVATE COMMUNITY STREET SIGNS 24" 3¼" ( 3.25) LETTERING 9/16" STROKES 43 4" STREET SIGN 7" 10" 7" 2 1 5/8" (1.625) LETTERING 3/8" STROKES 6 3¼" (3.25) LETTERING 9/16" STROKES DEAD END STREET SIGN NOTES: 1. THE STREET SIGN PLATE SHALL BE 24" X 4 3 4 ", THE DEAD END STREET SIGN PLATE SHALL BE 24" X 8" BOTH ARE FABRICATED FROM .080 ALUMINUM SHEET. 2. FONTS USED FOR ADDRESSING MUST BE LEGIBLE AND EASY TO READ. 3. THE SIGN FACE SHALL HAVE A WHITE 3M DIAMOND GRADE REFLECTIVE SHEETING (DG³ 4090 SERIES OR EQUIVALENT) APPLIED AS A BACKGROUND TO THE ALUMINUM PLATES. 4. LETTERING / NUMBERING SHALL BE DARK CONTRASTING, 3M SCOTCHLITE ACRYLIC, TRANSPARENT, ELECTRONIC CUTTABLE FILM (3M 1170 SERIES) INVERSE CUT TO ALLOW WHITE REFLECTIVE BACKGROUND TO SHOW THROUGH. 5. ALL SIGN IMAGING SHALL BE IN COMPLIANCE WITH THE REFLECTIVE SHEETING MANUFACTURES MATCH COMPONENT SYSTEM. 6. TO FORM A GRAFFITI BARRIER 3M 1160 PROTECTION OVERLAY FILM MAYBE APPLIED OVER SIGN. 7. REQUIRES PRE-APPROVAL BY A FIRE CODE OFFICIAL. 602-262-6771 FIGURE D.37 566 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS APPENDIX D PRIMARY AND SECONDARY HIGHRISE STAIRWELL SIGNAGE 12" N.W. STAIR STANDPIPE 14" B PARKING B THRU 4 BRAILLE SHALL BE GRADE 2 TYPE, INDICATING STAIRWELL LOCATION AND FLOOR NUMBER. (EXAMPLE: N.E. STAIRWELL FLOOR 4) THE BRAILLE AND RAISE NUMBERS SHALL BE PLACED NO MORE THAN 2" APART AND SHALL BE CENTERED ON THE SIGN. N.E. STAIR NO STANDPIPE 2 B THRU 4 1¼" X ¼" LETTERING 1" X 3 16" LETTERING 5" X 7 8" LETTERING 1" X 3 16" LETTERING N.W. STAIR STANDPIPE 20 B THRU 24 1" X 3 16" LETTERING WITH ADA RAISED INFORMATION 1¼" X ¼" LETTERING 1" X 3 16" LETTERING 43 4 " X 7 8" LETTERING 1¼" X 3 16" LETTERING 1" X 3 16" LETTERING WITH ADA RAISED INFORMATION N.W. STAIR 1¼" X ¼" LETTERING 1 " LETTERING, 3/16" STROKE 5" LETTERING, 1¼" X 3 16" 7 8" STANDPIPE STROKE LETTERING 20 B THRU 24 1" LETTERING, 3 16" STROKE WITH ADA RAISED INFORMATION N.E. STAIR NO STANDPIPE 3 B THRU 4 S.E. STAIR 1¼" X ¼" LETTERING 1" LETTERING, 3/16" STROKE 43 4 " LETTERING, 1¼" X 3 16" 7 8" STROKE LETTERING NO STANDPIPE 4 B THRU 4 1" LETTERING, 3 16" STROKE WITH ADA RAISED INFORMATION ADA DISCLAIMER THE INFORMATION PROVIDED ON THE BOTTOM 2" PORTION OF THIS SIGN IS ONLY INTENDED TO AID PEOPLE WITH VISUAL IMPAIRMENTS EXITING THE BUILDING. THE BRAILLE AND RAISED #'S INDICATING STAIRWELL LOCATION AND FLOOR # MEETS ADA REQUIREMENTS FOR DIRECTIONAL SIGNAGE. ADDITIONAL INFORMATION DISPLAYED ON THE SIGN IS INTENDED FOR F.D. USE ONLY. NOTES: 1. THE SIGN FACE SHALL BE 12" X 14" AND FABRICATED FROM .080 ALUMINUM SHEET WITH 1½" RADIUS CORNERS. 2. FONT STYLE USED IS HANDEL GOTHIC BT CAPITAL FONTS 3. THE SIGN FACE SHALL HAVE A WHITE 3M DIAMOND GRADE REFLECTIVE SHEETING (DG³4090 SERIES OR EQUIVALENT) APPLIED AS A BACKGROUND TO THE ALUMINUM PLATES. 4. LETTERING / NUMBERING SHALL BE HIGH PERFORMANCE, NON-REFLECTIVE, CUTTABLE VINYL (3M 7725 SERIES) INVERSE CUT TO ALLOW WHITE REFLECTIVE BACKGROUND TO SHOW THROUGH. 5. ALL SIGN IMAGING SHALL BE IN COMPLIANCE WITH THE REFLECTIVE SHEETING MANUFACTURES MATCH COMPONENT SYSTEM. 6. TO FORM A GRAFFITI BARRIER 3M 1160 PROTECTION OVERLAY FILM MAYBE APPLIED OVER SIGN. 7. REQUIRES PRE-APPROVAL BY A FIRE CODE OFFICIAL. 602-262-6771 Special Application FIGURE D.38 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 567 APPENDIX D 12" N.W. STAIR NO ROOF ACCESS 20 14" B2 THRU 24 BRAILLE SHALL BE GRADE 2 TYPE, INDICATING STAIRWELL LOCATION AND FLOOR NUMBER. (EXAMPLE: N.W. STAIRWELL FLOOR 20) 1.25" (1¼") LETTERING, ¼" STROKE 1" LETTERING, 3/16" STROKE 5" LETTERING, 7/8" STROKE 1" LETTERING, 3/16" STROKE 1" LETTERING, 3/16" STROKE NUMBERS SHALL BE RAISED A MINIMUM OF 1 32 ", UPPER CASE, SANS SERIF TYPE FONT. ADA DISCLAIMER THE INFORMATION PROVIDED ON THE BOTTOM 2" PORTION OF THIS SIGN IS ONLY INTENDED TO AID PEOPLE WITH VISUAL IMPAIRMENTS EXITING THE BUILDING. THE BRAILLE AND RAISED #'S INDICATING THE BRAILLE AND RAISE NUMBERS SHALL BE PLACED NO MORE THAN 2" APART AND SHALL BE CENTERED ON THE SIGN. STAIRWELL LOCATION AND FLOOR # MEETS ADA REQUIREMENTS FOR DIRECTIONAL SIGNAGE. ADDITIONAL INFORMATION DISPLAYED ON THE SIGN IS INTENDED FOR F.D. USE ONLY. SEE DETAIL ABOVE N.W. STAIR NO ROOF ACCESS 20 B2 THRU 24 5 FT FROM GRADE TO CENTER OF SIGN NOTES: 1. THE SIGN FACE SHALL BE 12" X 14" AND FABRICATED FROM .080 ALUMINUM SHEET WITH 1½" RADIUS CORNERS. 2. FONT STYLE USED IS HANDEL GOTHIC BT CAPITAL FONTS 3. THE SIGN FACE SHALL HAVE A WHITE 3M DIAMOND GRADE REFLECTIVE SHEETING (DG³4090 SERIES OR EQUIVALENT) APPLIED AS A BACKGROUND TO THE ALUMINUM PLATES. 4. LETTERING / GRAPHICS SHALL BE HIGH PERFORMANCE, NON-REFLECTIVE, CUTTABLE VINYL (3M 7725 SERIES) INVERSE CUT TO ALLOW WHITE REFLECTIVE BACKGROUND TO SHOW THROUGH. 5. ALL SIGN IMAGING SHALL BE IN COMPLIANCE WITH THE REFLECTIVE SHEETING MANUFACTURES MATCH COMPONENT SYSTEM. 7. REQUIRES PRE-APPROVAL BY A FIRE CODE OFFICIAL. 602-262-6771 STAIRWELL MARKING DETAIL FIGURE D.39 568 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS APPENDIX D 12” x 12” Hazardous Materials Identification (Fire Diamond) Occupancy Name: Occupancy Address: NUMBER SYSTEM 3 2 4 - SEVERE DANGER 4 OXY 3 - HIGH DANGER TOP Number in this space shall be RED 2 - MODERATE DANGER 1 - SLIGHT HAZARD 0 - NO HAZARD EXAMPLE Number in this space shall be YELLOW with a black outline Number in this space shall be BLUE Letters in this space shall be BLACK (White Special Hazard Box) SPECIFICATIONS: The sign plate shall be a 12” square with a thickness of .080 aluminum construction. Radius Corners The sign face shall have a white reflective vinyl background. Font style used - Numbers: Helvetica Bold Extended, Letters: Helvetica Blk BT. Numbers shall be a minimum of 3½” high with 11/16” stroke width. Lettering for White Special Hazard Box: One Line 1 3/4” high w/ 9/16” stroke width. Two Lines 1 3/8” high w/ 7/16” stroke width. Three Lines 1¼” high w/ 3/8” stroke width. Numbers and Letters arranged by color as shown above. Sign shall be posted at location as approved by the City of Phoenix Fire Department. Fire Prevention - HazMat (602)262-6771 FIGURE D.40 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS 569 570 WATER LINE WL Rev. 02/2013 REQUIRED BY NFPA 24. 7.1.1.1 REQUIRED BY STATE PLUMBING CODE NFPA 13.8.1.6.1.1 13.8.1 WATER LINE STREET F.L. FIGURE D.41 N.T.S. FIGURE P507.7a REQUIRED NFPA 13-6.7.1.3 OS&Y A/S CONTROL VALVE HYDRANT FIRE DEPT. CONNECTION POST INDICATOR VALVE SECTIONAL VALVE OR CONTROL VALVE BACK FLOW ASSEMBLY A/S RISER FIRELANE FL REQUIRED BY STATE PLUMBING CODE NFPA 13.8.1.6.1.1 REQUIRED 24.6.1.5 APPENDIX D 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS F.L. 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS WATER LINE WL F.L. BY P508.3 WATER LINE Rev. 02/2013 OS&Y A/S CONTROL VALVE HYDRANT FIRE DEPT. CONNECTION POST INDICATOR VALVE FIGURE D.42 SECTIONAL VALVE OR CONTROL VALVE BACK FLOW ASSEMBLY A/S RISER FIRELANE FL REQUIRED BY NFPA 24.7.1.1.1 NON-INDICATIONG VALVE PERMITTED BY 13.8.17.3.3 REQUIRED BY STATE PLUMBING CODE NFPA 13.15.1.8.3 WL STREET N.T.S. FIGURE 507.7b REQUIRED BY STATE PLUMBING CODE NFPA 13.8.1.1.2.5 WL REQUIRED 24.6.1.5 APPENDIX D 571 WATER LINE WL Rev. 02/2013 STREET OS&Y A/S CONTROL VALVE HYDRANT FIRE DEPT. CONNECTION POST INDICATOR VALVE SECTIONAL VALVE OR CONTROL VALVE BACK FLOW ASSEMBLY A/S RISER FIRELANE WATER LINE 572 FIGURE D.43 P508.3 WATER LINE STREET N.T.S. FIGURE 507.7c P508.3 F.L. FL 2 2 40 FT FROM BUIL 24.6.3.3.1 REQUIRED BY 24.6.3.1 APPENDIX D 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS WATER LINE WL 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS Rev.02/2013 OS&Y A/S CONTROL VALVE HYDRANT FIRE DEPT. CONNECTION POST INDICATOR VALVE N.T.S. FIGURE D.44 WATER LINE STREET 13.8.16.1.1.3.2 FL NO VALVES IN F.D.C. LINE 24.6.2.2 FIGURE 507.7d SECTIONAL VALVE OR CONTROL VALVE BACK FLOW ASSEMBLY A/S RISER FIRELANE FL APPENDIX D 573 574 2012 INTERNATIONAL FIRE CODE WITH PHOENIX AMENDMENTS