Building Management

advertisement
Building Management
Installation, Operation, and Maintenance Manual
A0023368
October 2015 Rev. 1.04
WARNING!
Wiring of the Communication Module, Protonode, and associated devices may involve working inside
of a UL508A electrical panel. Proper precautions should be taken to reduce potential risk of shock.
Wiring should be performed by qualified personnel only.
Save these instructions. This document is the property of the owner of this equipment and is required
for future maintenance. Leave this document with the owner when installation and setup is complete.
NOTE: This document includes sections for two exclusive Building
Management Systems (BMS).
The first section, CASLink, is a proprietary building management system for
monitoring restaurant applications.
The second section, External BMS, includes information for all other
building management options. This includes BACnet MS/TP, BACnet IP,
and Lonworks integration.
Each respective section of the manual applies only to the Building
Management System type that it is covering.
2
TABLE OF CONTENTS
WARRANTY .............................................................................................................................. 4
CASLink ..................................................................................................................................... 5
Installation .............................................................................................................................. 5
Wiring ................................................................................................................................................... 5
Field Wiring Equipment to the CASLink Communication Module .................................................... 5
Obtaining a Valid Internet Connection ............................................................................................. 7
Confirming Internet Connection for CASLink ..................................................................................... 13
Module Activation and Registration .......................................................................................14
Registration .................................................................................................................................... 14
Initial Settings for a New Module in CASLink ..................................................................................... 17
Defining the Occupancy Schedule ................................................................................................. 17
Module Editor (Service or Admin Access Only) ............................................................................. 18
Defining Sensor Areas and Names ................................................................................................ 19
Defining and Customizing Alert Emails and Alarms ...................................................................... 21
Adding Custom Alarms .................................................................................................................. 22
Adding Custom Email Alert Events ................................................................................................ 24
End User Guide.....................................................................................................................26
Log In ............................................................................................................................................. 26
Main Page Navigation .................................................................................................................... 26
Monitoring ...................................................................................................................................... 27
Control ............................................................................................................................................ 33
EXTERNAL BMS ......................................................................................................................37
BACNET Option for DCV and SC Packages .........................................................................37
Installation .......................................................................................................................................... 37
Internal Configuration ......................................................................................................................... 38
Operation ............................................................................................................................................ 41
BACNET Object List for DCV Packages ........................................................................................ 41
BACNET Object List for SC Packages .......................................................................................... 44
Changing Network Number and Device Instance .......................................................................... 47
Changing the IP Address ............................................................................................................... 49
LonWorks Option for DCV and SC Packages........................................................................50
Installation .......................................................................................................................................... 50
Operation ............................................................................................................................................ 51
LonWorks SNVT List for DCV Packages ....................................................................................... 51
LonWorks SNVT List for SC Packages.......................................................................................... 54
Commissioning on a LonWorks Network ....................................................................................... 58
Appendix A............................................................................................................................59
Cradlepoint Cellular GPIO Power Pinout and Wiring Diagram ...................................................... 59
Appendix B............................................................................................................................60
Dismounting the Cradlepoint from the Control Box ....................................................................... 60
Appendix C ...........................................................................................................................62
Weak Signal Strength (Less than -99 dBm)................................................................................... 62
MAINTENANCE ....................................................................................................................63
Module Registration Parameter Documentation ................................................................................ 63
Factory Service Department ............................................................................................................... 63
3
WARRANTY
This equipment is warranted to be free from defects in materials and workmanship, under normal use and
service, for a period of 12 months from date of shipment. This warranty shall not apply if:
1. The equipment is not installed by a qualified installer per the MANUFACTURER’S installation
instructions shipped with the product,
2. The equipment is not installed in accordance with federal, state and local codes and regulations,
3. The equipment is misused or neglected,
4. The equipment is not operated within its published capacity,
5. The invoice is not paid within the terms of the sales agreement.
The MANUFACTURER shall not be liable for incidental and consequential losses and damages
potentially attributable to malfunctioning equipment. Should any part of the equipment prove to be
defective in material or workmanship within the 12-month warranty period, upon examination by the
MANUFACTURER, such part will be repaired or replaced by MANUFACTURER at no charge. The
BUYER shall pay all labor costs incurred in connection with such repair or replacement. Equipment shall
not be returned without MANUFACTURER’S prior authorization and all returned equipment shall be
shipped by the BUYER, freight prepaid to a destination determined by the MANUFACTURER.
4
CASLink
Installation
It is imperative that this unit is installed and operated with the designed electrical supply in accordance
with this manual. If there are any questions about any items, please call the Service Department at 1-866784-6900 for warranty and technical support issues.
Wiring
WARNING: Wiring should be performed by qualified personnel only. Most wiring related to the
CASLink Building Management System is low-voltage signal wiring. However, it is typically
installed near high-voltage wiring posing risk of shock. Proper precautions must be taken.
Field Wiring Equipment to the CASLink Communication Module
The Communication Module, PN:COMM01, is included in all CASlink equipped panels. It obtains jobsite
data from various hardware components. Each component is connected on one of two communication
lines, the Modbus Communication Network or the CORE Interlock Network. This communication wiring is
either RS-485 shielded twisted pair wiring (Figure 1), or RJ45 Cat-5 Ethernet wiring (Figure 2). Some
typical examples are shown.
Figure 1. RS-485 CORE Interlock Network Wiring (Typical, refer to actual schematic)
Figure 2. Cat-5 Modbus Network Wiring (Typical, refer to actual schematic)
Most communication wiring is completed at the factory, with the following instructions provided for those
items which are field wired. NOTE: There are only two network lines. All field wiring for the
Communication Module will use one of the two lines.
5
Remote Wall Mounted CORE and PCU CORE
Remote (Wall Mounted) CORE Hood and PCU CORE Fire Protection circuit boards transfer data to the
Communication Module through the CORE Interlock Network Only. This is typically shown as terminal
blocks ILA, ILB, and ILC in each respective panel.
1. Wire ILA, ILB, and ILC of the Master CORE circuit board to ILA, ILB, and ILC of the Hood Control
Panel housing the Communication Module (Figure 1).
2. If additional CORE boards are present (such as PCU CORE, 2nd Remote CORE, etc.) wire ILA,
ILB, ILC of those panels to ILA, ILB, ILC of the Master CORE panel. NOTE: Doing this will
force all CORE panels in the same fire group to activate simultaneously if a single panel
activates.
3. Confirm DIP switch settings on all CORE circuit boards vs. the current CORE Operation &
Installation Manual. See Table 1 for typical arrangements of 1 or 2 CORE panels. NOTE:
Improper DIP switch settings will result in failed communication with the Communication Module.
Power must be cycled to the CORE circuit board for new DIP switch settings to initiate.
4. For ECPM03 based Hood Control Panels with digital LCD Interface, a Cat-5 Ethernet cable must
be run from J3 of the ECPM03 board to J5 of the Master CORE board. An end-of-line resistor
plug (PN: EOL120A) must be installed in J6 of the CORE circuit board if it is the final component
in this Modbus Communication Loop.
Table 1. Typical CORE Dip Switch Arrangement
Only One CORE Panel on the Network
CORE Board #
Dip 1
Dip 2
Dip 3
1st (Master)
ON
OFF
OFF
Dip 4
OFF
Dip 5
ON
Dip 6
OFF
Dip 7
OFF
Dip 8
ON
Two CORE Panels on the Network
CORE Board #
Dip 1
Dip 2
1st (Master)
OFF
ON
nd
2 (Slave)
ON
OFF
Dip 4
OFF
OFF
Dip 5
ON
OFF
Dip 6
OFF
OFF
Dip 7
OFF
OFF
Dip 8
ON
ON
Dip 3
OFF
OFF
For 3 or more panels, refer to the CORE Operation & Installation Manual.
PCU Advanced Filter Monitoring Module with ECPM03
1. PCU Advanced Filter Monitoring Modules (AFM) are not fire related, and therefore connect to the
standard Modbus Network for communication. Each PCU AFM comes equipped, within its
control panel internal to the PCU, with a pair of RJ45 Cat-5 connection ports. Modbus wiring shall
be run from J3 of the ECPM03 circuit board associated with the Communication Module, to either
of the two RJ45 ports within the PCU AFM cabinet (Figure 2). Additional PCU AFM modules
should be wired on this same daisy chain loop with an end-of-line terminator at the final location.
Communication in this arrangement travels from the PCU AFM, through the ECPM03, and into
the Communication Module
6
Obtaining a Valid Internet Connection
A reliable internet connection is required for proper Communication Module data monitoring. This
connection preferably comes in the form of a hard-wired Cat-5 Ethernet connection directly from the
building’s Local Area Network. Alternatively a wireless cellular gateway can be used to connect the
module in the event that a Local Area Network connection is unavailable (NOTE: Cellular data charges
will apply).
Wiring to the Local Area Network (Direct Internet Connection)
1. The first step in connecting to the Local Area Network is to identify the closest permanent
Ethernet source location. The best sources are Ethernet Switches or Wireless Routers (Figure 3).
2. Connect the wire from the Ethernet port directly on the Communication Module to a spare port on
the Ethernet Switch or Wireless Router.
Figure 3. Wireless Router (left) or Ethernet Switch (right) Used for Hard-wired Connection
Utilizing an Optional Cellular Wireless Bridge (Cradlepoint IBR650E-VZ)
1. The Cradlepoint device will allow the Communication Module (PN: COMM01) to connect to a
cellular data network (Verizon Wireless). In order for the Cradlepoint to provide a valid data
connection, there must be a valid Verizon Wireless signal at the location of the installation.
2. The IBR650E will be mounted inside the control box with all the necessary wiring completed by
the manufacturer. Confirming cellular connection, installing the antennas, and ensuring that the
device is receiving a proper data signal in its final location are the last necessary steps.
3. Check to make sure the power cord is connected properly. If the device is wired incorrectly it will
not power up. See Appendix A for GPIO port labels and a wiring diagram. Next, confirm that an
Ethernet cable is connected from the leftmost Ethernet port on the Cradlepoint (labeled
“COMPUTERS or LOCAL DEVICES” in Figure 4) to the Ethernet port on the COMM01.
7
Figure 4. Bottom View and Labels
Figure 5. Top View and Labels
4. The unit’s default password should have been noted in the QC process. Login to the QC Module
and lookup the job you are servicing to obtain the default password. Once you find it, make a
note of it or write it down. If, for some reason, the password was not noted during the QC
process, you will need to remove the device to obtain it. The password is located on the label on
the back of the device (Figure 6). Refer to Appendix B to unscrew the device from the electrical
panel to reveal the password. While the device is unscrewed, write down the default password.
If you unscrewed the device to obtain the password, fasten it back to its original mounted position
before moving forward.
Figure 6. Default Password Located on Back Label
8
5. If present, remove the black hole plugs from the two leftmost holes on the top of the electrical
enclosure. Connect the two provided modem antennas (shown in Figure 7), which shipped loose
with the electrical panel, to the SMA connectors that are visible through the two leftmost holes on
the top of the control box.
Figure 7. Modem Antennas
6. Data Connection Confirmation
a. Temporarily remove the Ethernet cable from the leftmost Ethernet port (“COMPUTERS
or LOCAL DEVICES” in Figure 4) on the IBR650E. Plug one end of your own Ethernet
cable into the leftmost Ethernet port and the other end into an Ethernet port on your
computer.
b. Wait for your computer to recognize the Ethernet connection (approximately 1 minute).
c. Open an internet browser, type “192.168.0.1” into the address bar, and press “Enter” or
“Return”. A page similar to the one in Figure 8 will appear.
Figure 8. Cradlepoint Login Page
d. In the “Password” field type the default eight character password, which you wrote down
in Step 4 of this section. When finished, click “Login”.
9
e. The next page will look like the one in Figure 9. Ensure the device has an Internet
Connection by the presence of a green light next to “Internet Connections” on the top of
the page (shown by the yellow circle in Figure 9).
f. Once the device has established a connection or the page has been loaded for at least
one minute, the “Signal Strength” should be recorded in the SDV notes. Signal Strength
is a negative number with dBm as the unit and can be found at the location of the red box
in Figure 9. The closer the signal strength is to zero, the stronger the signal. If the signal
strength is below -99 dBm (e.g. -115 dBm), the Cradlepoint device is receiving an
extremely poor signal (see Appendix C for solutions).
Figure 9. Cradlepoint Internal Settings
g. Next, select “System Settings” in the top menu bar and click “Administration” from the
drop down menu. See Figure 10.
10
Figure 10. System Settings --> Administration
h. On the next page, click “Remote Management” from the menu on the left side of the
page. See Figure 11.
Figure 11. Remote Management Page 1
11
i.
On the page that appears, make sure the box next to “Allow Remote Web
Administration:” is checked (if it is not checked, then check it). Once completed, the
page should look like Figure 12. Click “Apply”. The warning box shown in Figure 13 will
appear, click “OK”. Allow the changes to take place and click “OK” if any more warning
boxes appear.
Figure 12. Remote Management Page 2
Figure 13. Remote Management Warning
j.
Lastly, logout of the Cradlepoint settings page by clicking “Logout” in the upper right
corner, close out of the web browser, and disconnect the Ethernet cable that was
connected to your computer. Plug the Ethernet cable from the Communication Module
back in as it was previously.
12
Confirming Internet Connection for CASLink
The Communication Module conveniently has three LED indicators under the clear cover to help
diagnose a proper internet connection.
The first is the Green LED, which signifies that a proper physical Ethernet connection has been made. It
does not confirm that a valid internet connection has been made.
The second is the Yellow LED, which signifies activity on the Ethernet port. The rate of flashing of the
Yellow LED will vary with activity level. If there is no activity, the connection to the Ethernet Switch or
Wireless Bridge is suspect. Yellow LED activity does not confirm that a valid internet connection
has been made.
The third is the Red LED. The table below should be used to diagnose flashes of the Red LED. One
short flash every 3 seconds is the only method to confirm that a valid connection has been made
to the CASLink servers. The Red LED takes approximately 10 seconds to begin flashing upon power
up. NOTE: Certain configuration changes on the module may require up to 10 minutes to take effect. If a
module local setting is modified, allow 10 minutes to update the red LED.
Table 2. Flash Codes for the On-Module Red LED Indicator
Number
of
Description
Flashes
1
Normal operation
2
Waiting for DHCP
3
Configuration Mode enabled
4
No CORE interlock network traffic detected
5
Communication with CAS servers not established
6
Unspecified fault
13
Notes
Normal Operation (1 short flash
every 3 seconds)
Check that the Switch or Bridge
is communicating and properly
configured.
This mode is enabled via DIP
Switch 3. In this mode, a web
server is enabled for
configuration changes to be
made. Turn off DIP Switch 3 to
remove this code.
Not present if CORE is not
configured on the module’s
internal server. If present, CORE
Interlock Network is miswired or
CORE board DIP switch settings
are incorrect.
Typically no internet or CASLink
server down.
Normally a flash CRC error.
Contact Service to order a
replacement.
Module Activation and Registration
Once a valid connection to the CASLink server has been established (one short flash on Red LED every
three seconds), proceed to activate the module through the CASLink Module Registration Wizard.
Registration
Each module is given a unique MAC Address and Authentication Key. These two items are located on a
label on the door of the Electrical Control Panel housing the module (Figure 14). Obtain this MAC
Address along with the Authentication Key, and proceed to the following URL in any standard web
browser on any device:
www.CASLink.com
Figure 14. Authorization Key and MAC Address on Panel Lid.
The homepage will be shown as below (Figure 15) on a tablet or computer.
Figure 15. CASLink Home Screen
14
STEP 1
Log In:
Log in to the website utilizing your NOLA
credentials. If you do not have NOLA credentials,
please contact your local service representative
for additional instructions.
Select “Register New Module” (circled to the right
in two places) to initiate the Module Registration
Wizard.
STEP 2
Enter Authentication
Information:
Enter the Authentication Key and
MAC Address. Obtain from label on
the door of the control panel (Figure
14). Select “NEXT”.
STEP 3
Create New User:
If you are properly logged in using
your NOLA credentials, Step 2 will
already be completed. Simply select
“NEXT”. If you are not logged in, you
will be prompted to enter a username
and password.
15
STEP 4
Location Information:
Enter a description of the location. This is
typically the name of the facility. Enter the
address. NOTE: Address information is used
throughout the website for analytics and
service linking. Once complete, select “NEXT”.
STEP 5
Service Region Selection:
Enter the nearest “Service Region”. They
are sorted by distance using the address
entered in Step 3. The system will
automatically select the nearest location.
Only adjust if necessary then select
“NEXT”.
STEP 6
Confirmation:
Verify all information was entered correctly.
Select “REGISTER”.
16
Initial Settings for a New Module in CASLink
Defining the Occupancy Schedule
The range and activation of most email alert events depend specifically on the occupied/unoccupied state
of the building. A simple example of this is the Fan Run Status Alert. If a fan is running during the
occupied period this is considered normal operation. However, if a fan is running during the unoccupied
period this is considered an alert condition.
As such, a properly defined Building Schedule is an extremely important item in the CASLink
monitoring setup procedure.
NOTE: A schedule must match the end-user’s building occupancy to prevent nuisance alert emails.
By default, all modules are preset with a 7:00 AM – 10:00 PM schedule. To modify the
Occupied/Unoccupied Schedule follow the steps below:
a) Enter the settings area by selecting the “Settings” icon.
b) Select the “Occupancy” icon to access the Occupancy Editor (Figure 16)
c) Click or press (touchscreen) and drag over the desired occupancy ranges.
a. If starting on an empty time block, all blocks will be filled when the cursor is released.
b. If starting on a filled time block, all blocks will be emptied when the cursor is released.
c. Each block represents 15 minutes of time.
d) Confirm that the text version of the schedule, shown below the Schedule Editor itself, matches
what is expected.
e) Select “SAVE” to complete the Occupancy Editor.
f) Select “ROLLBACK” only if trying to revert to the previously saved schedule.
Figure 16. Occupancy Editor
17
Module Editor (Service or Admin Access Only)
By default, upon completion of the Module Registration Process, each module is given a standard predefined set of Alert Ranges, Sensor Names, Areas, and Email Events. All of this information should be
tailored to suit the specific needs of the customer.
To access the Module Editor, login in using Employee Credentials (NOLA credentials). If you are not a
CaptiveAire employee and don’t have NOLA credentials, contact your service or sales region for
documentation. If the Module Registration Process was just completed, you should already be signed in.
Upon logging in, a Select Module pop-up window will be present. Select the specific module by searching
for the name, address, or the MAC address.
Once a specific module is found, the Module Editor can be accessed by selecting the “Pencil” icon in the
module search results pop-up window, or alternatively by opening the “Location” drop down menu after
loading the module and selecting the module’s Mac Address (Figure 17). Most installations will only have
one MAC Address listed in this drop down menu. If there is more than one module at the location, each
module has to be edited individually. However, the data from the modules will be presented as one
location to the end user.
Figure 17. Accessing Module Editor via Location Menu
18
Once in the Module Editor, the following actions can be taken.
Defining Sensor Areas and Names
Specific sensors are not given an area and name by default, but instead follow the area and naming
convention of the hardware that they originate from. For example, the CORE Fire Protection Fire Active
Sensor is automatically placed into the Kitchen Area because the CORE board is located in the Kitchen
Area by default.
Additional sensor areas and names can be defined by the following procedure:
1. Select the sensor (or entire hardware component) that needs a new area defined. Sensor areas
can be defined by their hardware area (if no specific sensor area is defined) or individually. They
are not required to be in the same area as their hardware component.
2. To edit the entire hardware location and name (tag), select the entire hardware component from
the hardware tree, select edit, type in or select the new name and area, and select “Update” to
save your changes (Figure 18).
Figure 18. Editing a Complete Hardware Name and Area
3. To edit a specific sensor location and name (tag), select the specific sensor under the hardware
tree, select edit, type in or select the new name and area, and select “Update” to save your
changes (Figure 19).
NOTE: Sensors can be placed in areas separate from their hardware location. For example, a
temperature sensor could be mounted in a back kitchen, while the hood control panel is mounted in the
front kitchen. For this reason, it is extremely important during startup to properly label the sensors so that
each can be defined without on-site knowledge.
19
Proper sensor naming convention should indicate the sensor type and the component it is associated with
(hood #1, exhaust fan #4, etc.). Appliance type, if available, can be valuable as well.
An example of a properly named sensor would be “Hood #1 (Fryer) Duct Temp”.
An example of a poorly named sensor would be “Duct Temp #1”.
Figure 19. Editing a Specific Sensor Name and Area
4. After all sensors have been appropriately named and correspond to appropriate areas, proceed
to the home screen and confirm, via the “Sensors” icon, that the areas are defined, sensors are
where expected, and unnecessary areas are not present. Keep in mind that having too many
areas makes the navigation cumbersome. Simple and effective area naming is the best
approach.
20
Defining and Customizing Alert Emails and Alarms
Alarms are what drive the email and service notification portion of CASLink BMS.
By default, upon completion of the Module Registration Process, each module is given a standard predefined set of alarms and a pre-made email notification set.
NOTE: Pre-defined alarms cannot be changed. However, the email functions can be enabled/disabled.
By default, email notification is added to all sensors for warning conditions for the following users:
• The engineering sales office associated with the original design
• The service region selected during module registration.
Additional custom alerts (custom AV) or email notifications can be added to individual sensors or
parameters by following the instructions below. Valid reasons for setting up additional alerts would be to:
• Monitor a specific sensor for a suspect component.
• Define AV email activation setpoints that are more reactive than the standard setpoints.
• Monitor activation time by daily email for a component or sensor to watch for trends.
21
Adding Custom Alarms
NOTE: Adding a custom alarm variable does NOT automatically add the email link. See section below
titled “Adding Custom Email Alerts” to link the new alarm variable to email account(s).
To add a Custom Alarm Variable:
1. Select the specific sensor for the new alarm in the Module Editor (Figure 20).
Notice that alarms may already exist for that sensor. These are typically the default AV and cannot be
changed. They will show up under the “Default” heading, which can be collapsed via the adjacent arrow.
Figure 20. Adding Custom Alarms
2. Next, select the “Ranges & Alerts” tab in the lower window.
3. To add a new Alarm, select “Add Sensor Range” to open the Sensor Range Editor
4. In the Sensor Range Editor (Figure 21), adjust and enter the data as defined below.
22
Figure 21. The Alarm Variable Sensor Range Editor
Sensor: Confirm the appropriate sensor is selected.
Alert Level: This will dictate the alert severity level. Info, OK, Warning, and Alert are the available
options. “Info” should be used for standard data monitoring. “OK” is to confirm proper operational status.
“Warning” is used for moderate failure or data. “Alert” is used for severe failure or critical data.
Occupancy: This defines when the alert can be sent. Select “Occupied”, “Unoccupied”, or “Any”.
Refer to the Defining Occupancy Schedule portion of this document for further information.
Comparison: Defines the mathematical function used for the alert variable.
Minimum Value: Enter the minimum value for activating this alarm. NOTE: This does not apply to binary
data such as On/Off variables. If no minimum, select “None”.
Maximum Value: Enter the maximum value for activating this alarm. NOTE: This does not apply to binary
data such as On/Off variables). If no maximum, select “None”.
Hysteresis (min & max): Unless purposely defining for a specific purpose, set the hysteresis to “1” to
prevent cycling of the alert and unnecessary emails.
Delay Count: This determines how many data packets must come through the server continuously with
the fault active before considering it an active alert. A default of 30 is a wise choice. Some sensors, such
as building pressure, will fluctuate throughout the day and it is therefore wise to fine tune this number to
only activate on a true constant Failure Mode.
Can Repeat: If checked, the alert can repeat more than once for the same qualifying condition. This
should never be checked unless specifically required.
Can Snooze: If checked, this alert can be delayed by standard users in the “Alert” tabs of the website.
This feature is only available if the “Can Repeat” option is enabled.
Snooze Minutes: This is how long the snooze is effective for before the sensor can create an alert again.
23
Adding Custom Email Alert Events
To add a custom email alert event, first select the alarm variable in the Module Editor (default or custom
type are allowed) which is being used to activate the email. At the right end of the variable, there is a “b”
button.
1. Select the “Manage Alerts” button for that alarm (Figure 20 above).
2. Select the “Add Sensor Alert” button in the Sensor Alerts pop-up (Figure 22).
Figure 22. Adding Email Alerts
3. Enter a description of the alert event (Figure 23).
4. Add the email addresses as necessary.
5. Select all “Save” buttons when complete.
24
Figure 23. Alert Editor Window
6. The new alert event should now be shown in the Ranges & Alerts tab (Figure 24). Activation and
deactivation of the email alert event can be done via the checkbox. NOTE: This is a permanent
deactivation and should not be used when a snooze command will suffice.
Figure 24. Sensor Alerts Window After Email Has Been Added
25
End-User Guide
The alerts, zones, and customized events explained in the preceding sections should be set up by a
CaptiveAire service or sales representative. The end user (i.e. restaurant owner, manager, or employee)
can access CASLink by logging in with the account provided by CaptiveAire. The following sections
describe ways to access and interpret the information gathered through CASLink.
Log In
To log in, go to www.CASLink.com, and use the username and password provided by CaptiveAire.
Figure 25. CASLink Log-in Page
Main Page Navigation
Immediately after signing in, the main CASLink page will appear. There are multiple sections, each
highlighted either in green (if there are no alerts), yellow (if there are non-critical alerts), red (if there are
critical alerts that need immediate attention), or grey (if section is not available). The primary sections are:
1. Monitoring: Contains sensor values, alerts and graphs.
2. Control: Used to control certain functions/scheduling of events.
3. Analytics: Contains graphs and interpretations of sensor data.
4. Settings: Allows for occupancy schedule setup and location information changes (see Defining
the Occupancy Schedule section on Page 17).
26
Figure 26. CASLink Home Page
Figure 27. Indication of a Critical Alert in a Sensor Area
Monitoring
The monitoring section of CASLink shows all sensor areas that were setup for that specific location. To
view current sensor values, click on any of the sensor areas shown.
Figure 28. Sensor Areas Shown in the Monitoring Section
27
CORE Fire Protection
If there is one or multiple CORE fire systems (Hood or PCU) connected to a Communication Module, then
the following conditions can be monitored at all times:
1. Fire Status: Reports fire condition.
2. Wash Solenoid Malfunction: Alerts user if plenum and duct water system solenoid is
malfunctioning.
3. Appliance Solenoid Malfunction: Alerts user if appliance protection fire system solenoid is
malfunctioning.
4. Microcontroller Fault: Reports an alert if circuit board is malfunctioning.
5. Surfactant Pump Malfunction: Alerts if there is a problem with the surfactant pump.
6. Supervised Loop Issue: Reports issue with Pull/Push station and/or fire sensor connections.
7. Ground Fault: Reports issue with Pull/Push station and/or fire sensor connections.
8. Surfactant Low: Alerts when surfactant level is below 50%.
9. Battery Voltage Low: Alerts if backup battery voltage is low.
10. AC Power Failure: Alerts if there is a problem with feeding power line.
11. Door Panel Open: Triggers alarm if CORE door panel is opened when the system is armed.
12. Test Mode: Reports if CORE system is currently on Test Mode.
13. Network Communication Error: Reports an issue with the CORE interlock network.
14. Fire Suppression System Activated by Fire Sensor: Alerts user if CORE has activated based
on temperature readings.
15. Fire Suppression System Activated by Button: Alerts user if CORE has activated by push
station.
16. Gas Is On: Reports if the gas line to the appliances is open.
17. Successful Wash Has Not Occurred: Alerts user if a wash has not occurred in 24 hours.
18. Washing: Reports when hot water wash is active.
For further reference to these conditions, please consult the CORE Fire Protection manual.
Figure 29. CORE Monitoring Parameters and Alert Screen
28
Pollution Control Monitor
The following information can be monitored for a Pollution Control Unit - Advanced Filter Monitoring (PCU
AFM) System:
1. Clogged Filter: One or more filters in the unit need to be replaced.
2. Missing Filter: There are one or more filters missing in the unit.
3. Clogged Filter Shutdown: Unit shut down due to clogged filter condition.
4. Fully Clogged Unit: Unit is clogged.
5. Missing Door: One or more doors in the unit are missing.
6. Unit Needs Calibration: Perform calibration on the unit (see PCU AFM manual for reference).
7. Individual Pressure and Filter status (analog variables)
Figure 30. Monitoring Screen for PCU AFM
29
ECPM03 Hood Control Panel (SC and DCV)
The following information can be monitored for a Demand Control Ventilation connected to CASLink:
1. Temperature Sensors:
a. All room temperature sensors and duct sensors: Temperature on vertical axis, time
on horizontal axis
2. Make Up Air Units:
a. Speed: VFD frequency (DCV only)
b. Amperage: Current draw of the unit motor (DCV only)
c. Energy Usage: Power on the vertical axis, time on the horizontal axis (DCV only)
d. Fault State: Alerts if VFD is in fault state (DCV only)
e. Fan Status: Is MUA fan group on (both variants)
f. Fan On Reason: Why are fans on (both variants)
3. Exhaust Fan Units:
a. Speed: VFD frequency
b. Amperage: Current draw of the unit motor
c. Energy Usage: Power on the vertical axis, time on the horizontal axis
d. Fault State: Alerts if VFD is in fault state
e. Fan Status: Is Exhaust fan group on (both variants)
f. Fan On Reason: Why are fans on (both variants)
4. Hood Lighting State: Shows if hood lights are ON or OFF.
5. Wash Zone Status: Reports if one or more wash zones are currently active.
6. Alarms Active: Reports any active alarms on the ECPM03 system.
Figure 31. Hood Duct Temperature Obtained from DCV Panel
30
RTULink Control Board
The following RTU information can be monitored for every RTU that has an RTULink board installed in it.
1. Temperature Sensors:
a. Discharge Temperature
b. Return Temperature
c. Outside Air Temperature
d. Space Temperature (if installed)
2. Unit Activity:
a. Blower Status
b. Individual Cooling Stage Status
c. Individual Heating Stage Status
d. Unit Alarm Status
e. Cooling Setpoint (if in Full Control Mode)
f. Heating Setpoint (if in Full Control Mode)
3. Faults/Alarms: Reports any fault that is active on the RTULink control board or any fault that is
configured through CASLink
Figure 32. Cooling Setpoint Graph Obtained from RTULink Board
31
Navigating Sensor Data
All continuous time data (temperatures, fan speeds, energy usage, and amperage) will be shown in
graphs with time on the horizontal axis. The time frame viewable can be modified using the zoom
functions shown above the graph (Set View Range, Zoom Out, Reset Zoom). Graphs can also be
overlapped by dragging sensors from the menu on the left-hand side onto the body of any graph.
Zooming in on a selected area of the graph is accomplished by clicking on a start time and dragging the
mouse to an end time before releasing the click.
Figure 33. Overlapping Sensor Data on Same Plot
Figure 34. Set Range and Export Tabs Shown Above Graph
32
Any alerts for specific sensors can be viewed by clicking on the “Alerts” tab above the graphs. The data
tab will display the graphs again. The “Play Live” button will let you view data as it comes in (refreshed a
few times every minute). The “Export” button will allow you to download an excel file with sensor values
and times of occurrence.
Figure 35. Excel Sheet of Temperature Sensor Data Exported from CASLink
Control
The Control section of CASLink shows all sensor areas that have capability to be controlled through
CASLink UI. To view each piece of hardware that has control capabilities, click on the “Control” icon from
the home page.
33
RTULink Control Board
If the RTULink board is in Full Control or External Control Mode, it is capable of being controlled through
CASLink. The Full Control Mode offers the highest level of control, allowing setpoints and settings of each
RTU to be changed and controlled through CASLink. External Control Mode offers limited control of each
RTU, with the majority of the operation still being controlled by an external thermostat. The Passthrough
Control Mode offers no control capability and, as a result, the CASLink Controls interface will not be
accessible.
Each RTULink board will have a dashboard that appears in the Controls area. The color of each
individual dashboard indicates the current operation of the unit. A dashboard with a blue background
means the unit is cooling and a dashboard with a red background indicates a unit is heating.
In Figure 36:
• The yellow box shows the heating setpoint (to the right of the red bubble), the cooling setpoint (to
the right of the blue bubble), and the Blower Mode (a rotating fan means the blower is in ON
Mode and the absence of a fan means the blower is in AUTO Mode).
• The red box indicates the spot on the dashboard where the space, return, outside, and discharge
temperatures are displayed.
• The green box indicates the status of certain unit options. For example, if the emergency heat is
ON or OFF, if the economizer is allowed, if the unit is in an occupied or unoccupied state, etc.
Figure 36. RTULink Dashboard
The three links at the bottom of the RTULink dashboard are Schedule, Thermostat, and Settings.
Schedule
The scheduling UI is where the 7-day schedule is set for each board. Click and drag over an area of the
schedule and release the click to highlight an area of the scheduler (press, drag and release for a
touchscreen). Once an area has been highlighted, a popup will ask to create a new setpoint or to use an
existing setpoint. An example of this popup can be seen in Figure 37. If no setpoints have ever been
created, it will only give the option to create a new one.
Figure 37. Setpoint Popup
The Setpoint Editor has the following information and editable points. NOTE: The selections that are
available in the Setpoint Editor are based on the control mode that the RTULink is in. As mentioned
earlier, Full Control offers the highest level of control, so all points listed below will be shown. However, all
of the points may not be shown when in External Control Mode.
• The time block that is being edited.
• The operational mode (Heat/Cool, Heat only, Cool only, etc).
34
•
•
•
Occupied/unoccupied setting. This controls whether certain features will be enabled such
as CO2 based DCV, economizer, discharge tempering, etc.
Blower Mode. This is a separate setting from the Occupied/Unoccupied Mode and
controls the status of the blower (AUTO or ON).
Cooling and heating setpoints.
Figure 38. RTULink Set Point Editor
Thermostat
The thermostat UI provides temporary override of the schedule. This is intended to make small
adjustments to the schedule without writing over it. The Thermostat Editor will look identical to the
Setpoint Editor except for the addition of the override time. The override time specifies the duration of
time, in minutes, that the schedule override will last for.
Figure 39. RTULink Thermostat Editor
35
Settings
The settings UI is where default board settings can be changed. NOTE: The selections that are available
in the Set Point Editor are based on the control mode that the RTULink is in. Only settings that apply to
the current control mode will be viewable and editable in this interface.
Figure 40. RTULink Settings Editor
36
EXTERNAL BMS
BACNET Option for DCV and SC Packages
Installation
BACNET IP or BACNET MS/TP compatibility can be implemented on CaptiveAire’s Demand Control
Ventilation (DCV) and Smart Controls (SC) packages through a Protocessor, which is a BTL listed
embedded gateway configured to give a Building Management System access to monitor and/or control a
list of BACNET objects. The Protocessor is mounted and factory pre-wired inside the Electrical Control
Panel. Field connections to the Building Management System are shown in Figure 41 and Figure 42.
Figure 41. BACNET IP Field Connection
37
Figure 42. BACNET MS/TP Field Connection
The Protocessor is pre-configured at the factory to use the field protocol of the Building Management
System in the specific jobsite. BACNET objects from CaptiveAire’s DCV and SC packages can only be
accessed through the specified port and protocol.
Internal Configuration
The Protocessor has two sets of DIP switches.
Figure 43. Protocessor DIP Switches and Functionality
The “A” Bank of DIP switches can be used to set the MAC Address of the Protocessor for BACNET
MS/TP networks (where A1 is the least significant digit and A8 is the most significant digit of an 8-digit
binary number).
38
Examples:
MAC Address = 3 = 00000011 implies A1=ON, A2=ON, A3=OFF, A4=OFF, A5=OFF, A6=OFF, A7=OFF,
A8=OFF
MAC Address = 4 = 00000100 implies A1=OFF, A2=OFF, A3=ON, A4=OFF, A5=OFF, A6=OFF,
A7=OFF, A8=OFF
MAC Address = 5 = 00000101 implies A1=ON, A2=OFF, A3=ON, A4=OFF, A5=OFF, A6=OFF, A7=OFF,
A8=OFF
The MAC Address must be set between 0 and 127 so that the BMS can detect the Protocessor via
BACNET auto discovery. The default MAC address from the factory is 03. A list of “A” Bank DIP switch
settings for MAC Addresses from 0 to 127 are shown in Figure 44.
Figure 44. DIP Switch Settings for MAC Addresses Ranging from 0 to 127
The “B” Bank of DIP switches is used to set the baud rate if using BACNET MS/TP as the field protocol.
The default baud rate from the factory is 38400.
39
Figure 45. DIP Switch Settings for BACNET MS/TP Baud Rates
If the RS485 field output is used (for BACNET MS/TP), the Protocessor is also equipped with an End of
Line (EOL) Termination Switch that can be used if the Protocessor is the last device on the trunk. The
default EOL switch position is OFF, and it can be seen at the bottom right-hand corner of Figure 43
(labeled “End of Line termination switch”).
40
Operation
BACNET Object List for DCV Packages
The following list includes objects for all possible sensors in a DCV package. NOTE: Not all sensors
may be present on each package due to variations in software revision, options ordered, etc.
Table 3. BACNET Object List for DCV Packages
Object Name
Object Type
Object ID
Units
Description
Temperature Sensor 1
Analog Input
1
Deg_F
Temperature Reading Sensor 1, 1 decimal precision
Temperature Sensor 2
Analog Input
2
Deg_F
Temperature Reading Sensor 2
Temperature Sensor 3
Analog Input
3
Deg_F
Temperature Reading Sensor 3
Temperature Sensor 4
Analog Input
4
Deg_F
Temperature Reading Sensor 4
Temperature Sensor 5
Analog Input
5
Deg_F
Temperature Reading Sensor 5
Temperature Sensor 6
Analog Input
6
Deg_F
Temperature Reading Sensor 6
Temperature Sensor 7
Analog Input
7
Deg_F
Temperature Reading Sensor 7
Temperature Sensor 8
Analog Input
8
Deg_F
Temperature Reading Sensor 8
Temperature Sensor 9
Analog Input
9
Deg_F
Temperature Reading Sensor 9
Temperature Sensor 10
Analog Input
10
Deg_F
Temperature Reading Sensor 10
Temperature Sensor 11
Analog Input
11
Deg_F
Temperature Reading Sensor 11
Temperature Sensor 12
Analog Input
12
Deg_F
Temperature Reading Sensor 12
Temperature Sensor 13
Analog Input
13
Deg_F
Temperature Reading Sensor 13
Temperature Sensor 14
Analog Input
14
Deg_F
Temperature Reading Sensor 14
Temperature Sensor 15
Analog Input
15
Deg_F
Temperature Reading Sensor 15
Temperature Sensor 16
Analog Input
16
Deg_F
Temperature Reading Sensor 16
Temperature Sensor 17
Analog Input
17
Deg_F
Temperature Reading Sensor 17
Temperature Sensor 18
Analog Input
18
Deg_F
Temperature Reading Sensor 18
Temperature Sensor 19
Analog Input
19
Deg_F
Temperature Reading Sensor 19
Temperature Sensor 20
Analog Input
20
Deg_F
Temperature Reading Sensor 20
Temperature Sensor 21
Analog Input
21
Deg_F
Temperature Reading Sensor 21
Temperature Sensor 22
Analog Input
22
Deg_F
Temperature Reading Sensor 22
Temperature Sensor 23
Analog Input
23
Deg_F
Temperature Reading Sensor 23
Temperature Sensor 24
Analog Input
24
Deg_F
Temperature Reading Sensor 24
Temperature Sensor 25
Analog Input
25
Deg_F
Temperature Reading Sensor 25
Temperature Sensor 26
Analog Input
26
Deg_F
Temperature Reading Sensor 26
Temperature Sensor 27
Analog Input
27
Deg_F
Temperature Reading Sensor 27
Temperature Sensor 28
Analog Input
28
Deg_F
Temperature Reading Sensor 28
Temperature Sensor 29
Analog Input
29
Deg_F
Temperature Reading Sensor 29
Temperature Sensor 30
Analog Input
30
Deg_F
Temperature Reading Sensor 30
Temperature Sensor 31
Analog Input
31
Deg_F
Temperature Reading Sensor 31
Temperature Sensor 32
Analog Input
32
Deg_F
Temperature Reading Sensor 32
VFD Frequency Exhaust 1
Analog Input
33
Hz
VFD Frequency for Exhaust Fan 1, 1 decimal precision
VFD Frequency Exhaust 2
Analog Input
34
Hz
VFD Frequency for Exhaust Fan 2
41
VFD Frequency Exhaust 3
Analog Input
35
Hz
VFD Frequency for Exhaust Fan 3
VFD Frequency Exhaust 4
Analog Input
36
Hz
VFD Frequency for Exhaust Fan 4
VFD Frequency Exhaust 5
Analog Input
37
Hz
VFD Frequency for Exhaust Fan 5
VFD Frequency Exhaust 6
Analog Input
38
Hz
VFD Frequency for Exhaust Fan 6
VFD Frequency Exhaust 7
Analog Input
39
Hz
VFD Frequency for Exhaust Fan 7
VFD Frequency Exhaust 8
Analog Input
40
Hz
VFD Frequency for Exhaust Fan 8
VFD Frequency Supply 1
Analog Input
41
Hz
VFD Frequency for Supply Fan 1
VFD Frequency Supply 2
Analog Input
42
Hz
VFD Frequency for Supply Fan 2
VFD Amperage Exhaust 1
Analog Input
43
Amps
Amperage for Fan Exhaust 1, 1 decimal precision
VFD Amperage Exhaust 2
Analog Input
44
Amps
Amperage for Fan Exhaust 2
VFD Amperage Exhaust 3
Analog Input
45
Amps
Amperage for Fan Exhaust 3
VFD Amperage Exhaust 4
Analog Input
46
Amps
Amperage for Exhaust Fan 4
VFD Amperage Exhaust 5
Analog Input
47
Amps
Amperage for Exhaust Fan 5
VFD Amperage Exhaust 6
Analog Input
48
Amps
Amperage for Exhaust Fan 6
VFD Amperage Exhaust 7
Analog Input
49
Amps
Amperage for Exhaust Fan 7
VFD Amperage Exhaust 8
Analog Input
50
Amps
Amperage for Exhaust Fan 8
VFD Amperage Supply 1
Analog Input
51
Amps
Amperage for Supply Fan 1
VFD Amperage Supply 2
Analog Input
52
Amps
Amperage for Supply Fan 2
VFD Power Usage Exhaust 1
Analog Input
53
KW
KW for Exhaust Fan 1, 2 decimal precision
VFD Power Usage Exhaust 2
Analog Input
54
KW
KW for Exhaust Fan 2
VFD Power Usage Exhaust 3
Analog Input
55
KW
KW for Exhaust Fan 3
VFD Power Usage Exhaust 4
Analog Input
56
KW
KW for Exhaust Fan 4
VFD Power Usage Exhaust 5
Analog Input
57
KW
KW for Exhaust Fan 5
VFD Power Usage Exhaust 6
Analog Input
58
KW
KW for Exhaust Fan 6
VFD Power Usage Exhaust 7
Analog Input
59
KW
KW for Exhaust Fan 7
VFD Power Usage Exhaust 8
Analog Input
60
KW
KW for Exhaust Fan 8
VFD Power Usage Supply 1
Analog Input
61
KW
KW for Supply Fan 1
VFD Power Usage Supply 2
Analog Input
62
KW
KW for Supply Fan 2
VFD Fault Exhaust 1
Analog Input
63
No-Units
*Fault Code for VFD Exhaust Fan 1
VFD Fault Exhaust 2
Analog Input
64
No-Units
*Fault Code for VFD Exhaust Fan 2
VFD Fault Exhaust 3
Analog Input
65
No-Units
*Fault Code for VFD Exhaust Fan 3
VFD Fault Exhaust 4
Analog Input
66
No-Units
*Fault Code for VFD Exhaust Fan 4
VFD Fault Exhaust 5
Analog Input
67
No-Units
*Fault Code for VFD Exhaust Fan 5
VFD Fault Exhaust 6
Analog Input
68
No-Units
*Fault Code for VFD Exhaust Fan 6
VFD Fault Exhaust 7
Analog Input
69
No-Units
*Fault Code for VFD Exhaust Fan 7
VFD Fault Exhaust 8
Analog Input
70
No-Units
*Fault Code for VFD Exhaust Fan 8
VFD Fault Supply 1
Analog Input
71
No-Units
*Fault Code for VFD Supply Fan 1
VFD Fault Supply 2
Analog Input
72
No-Units
*Fault Code for VFD Supply Fan 2
Fans ON by Duct Temp
Binary Input
73
No-Units
Fan Status - ON due to Duct Stat Sensor Reading
Fans ON by Button
Binary Input
74
No-Units
Fan Status - ON due to Button Pressed
Fans ON by Interlock (IO1)
Binary Input
75
No-Units
Fan Status - ON due to Interlock
Fans ON by Fire Condition
Binary Input
76
No-Units
Fan Status - ON due to Fire Condition
Fans ON by BMS
Binary Input
77
No-Units
Fan Status - ON due to BMS command
42
Fans ON by Wash Cycle
Binary Input
78
No-Units
Fan Status - ON due to Wash Cycle
Fans ON by Proving
Binary Input
79
No-Units
Fan Status - ON due to Proving
Fans ON by CO Sensor
Binary Input
80
No-Units
Fan Status – ON due to CO Sensor value
Fans ON by Max Air
Binary Input
81
No-Units
Fan Status – ON due to Max Air Button
Fans ON by System Bypass
Binary Input
82
No-Units
Fan Status – ON due to System Bypass
Fire Alert
Binary Input
83
No-Units
*Alert – Fire Condition or circuit not wired properly
PCU Fault
Binary Input
84
No-Units
*Alert – PCU filters are clogged or missing
Proving Fault
Binary Input
85
No-Units
*Alert – Proving Interlock Error
Fuse F1 Blown
Binary Input
86
No-Units
*Alert – Replace Fuse F1 on ECPM03 Board
Lights Fault
Binary Input
87
No-Units
*Alert – Lights Switch and Power Status Mismatch
High Temperature Shut Down
Binary Input
88
No-Units
*Alert – Equipment shutdown due to high duct temp
Surfactant Low
Binary Input
89
No-Units
*Alert – Surfactant level is low
Modbus Comm Error
Binary Input
90
No-Units
*Alert – Network Component Not Responding
Temp Sensor Not Connected
Binary Input
91
No-Units
*Alert – Temp Sensor is disconnected
MUA 1 Interlock Error
Binary Input
92
No-Units
*Alert – Interlock Signal form MUA unit 1 not received
MUA 2 Interlock Error
Binary Input
93
No-Units
*Alert – Interlock Signal form MUA unit 2 not received
Kill Switch
Binary Input
94
No-Units
*Alert – Kill Switch Activated
Bad Temp Sensor
Binary Input
95
No-Units
*Alert – Temp Sensor is not working
High Level of CO
Binary Input
96
No-Units
*Alert – High Level of CO detected
Clog Percentage - PCUFMM 1 Filter 1
Analog Input
97
No-Units
Clog Percentage of Filter 1 in PCU 1
Clog Percentage - PCUFMM 1 Filter 2
Analog Input
98
No-Units
Clog Percentage of Filter 2 in PCU 1
Clog Percentage - PCUFMM 1 Filter 3
Analog Input
99
No-Units
Clog Percentage of Filter 3 in PCU 1
Clog Percentage - PCUFMM 1 Filter 4
Analog Input
100
No-Units
Clog Percentage of Filter 4 in PCU 1
Clog Percentage - PCUFMM 1 Filter 5
Analog Input
101
No-Units
Clog Percentage of Filter 5 in PCU 1
Clog Percentage - PCUFMM 2 Filter 1
Analog Input
102
No-Units
Clog Percentage of Filter 1 in PCU 2
Clog Percentage - PCUFMM 2 Filter 2
Analog Input
103
No-Units
Clog Percentage of Filter 2 in PCU 2
Clog Percentage - PCUFMM 2 Filter 3
Analog Input
104
No-Units
Clog Percentage of Filter 3 in PCU 2
Clog Percentage - PCUFMM 2 Filter 4
Analog Input
105
No-Units
Clog Percentage of Filter 4 in PCU 2
Clog Percentage - PCUFMM 2 Filter 5
Analog Input
106
No-Units
Clog Percentage of Filter 5 in PCU 2
Clog Percentage - PCUFMM 3 Filter 1
Analog Input
107
No-Units
Clog Percentage of Filter 1 in PCU 3
Clog Percentage - PCUFMM 3 Filter 2
Analog Input
108
No-Units
Clog Percentage of Filter 2 in PCU 3
Clog Percentage - PCUFMM 3 Filter 3
Analog Input
109
No-Units
Clog Percentage of Filter 3 in PCU 3
Clog Percentage - PCUFMM 3 Filter 4
Analog Input
110
No-Units
Clog Percentage of Filter 4 in PCU 3
Clog Percentage - PCUFMM 3 Filter 5
Analog Input
111
No-Units
Clog Percentage of Filter 5 in PCU 3
Internal Fault PCU 1
Binary Input
112
No-Units
*Internal Fault on Circuit Board – Alert PCU 1
Clogged Filter PCU 1
Binary Input
113
No-Units
*Clogged Filter – Alert PCU 1
Missing Filter PCU 1
Binary Input
114
No-Units
*Missing Filter – Alert PCU 1
72 Hour Clogged Filter PCU 1
Binary Input
115
No-Units
*Clogged Filter for 72 Hours – Alert PCU 1
Clogged PCU 1
Binary Input
116
No-Units
*Total Clogging – Alert PCU 1
Door Missing PCU 1
Binary Input
117
No-Units
*Door Missing – Alert PCU 1
Not Calibrated PCU 1
Binary Input
118
No-Units
*Calibration has not been performed – Alert PCU 1
24 Hour Clogged Filter PCU 1
Binary Input
119
No-Units
*Clogged Filter for 24 Hours – Alert PCU 1
No-Units
*Internal Fault on Circuit Board – Alert PCU 2
Internal Fault PCU 2
Binary Input
120
43
Clogged Filter PCU 2
Binary Input
121
No-Units
*Clogged Filter – Alert PCU 2
Missing Filter PCU 2
Binary Input
122
No-Units
*Missing Filter – Alert PCU 2
72 Hour Clogged Filter PCU 2
Binary Input
123
No-Units
*Clogged Filter for 72 Hours – Alert PCU 2
Clogged PCU 2
Binary Input
124
No-Units
*Total Clogging – Alert PCU 2
Door Missing PCU 2
Binary Input
125
No-Units
*Door Missing – Alert PCU 2
Not Calibrated PCU 2
Binary Input
126
No-Units
*Calibration has not been performed – Alert PCU 2
24 Hour Clogged Filter PCU 2
Binary Input
127
No-Units
*Clogged Filter for 24 Hours – Alert PCU 2
Internal Fault PCU 3
Binary Input
128
No-Units
*Internal Fault on Circuit Board – Alert PCU 3
Clogged Filter PCU 3
Binary Input
129
No-Units
*Clogged Filter – Alert PCU 3
Missing Filter PCU 3
Binary Input
130
No-Units
*Missing Filter – Alert PCU 3
72 Hour Clogged Filter PCU 3
Binary Input
131
No-Units
*Clogged Filter for 72 Hours – Alert PCU 3
Clogged PCU 3
Binary Input
132
No-Units
*Total Clogging – Alert PCU 3
Door Missing PCU 3
Binary Input
133
No-Units
*Door Missing – Alert PCU 3
Not Calibrated PCU 3
Binary Input
134
No-Units
*Calibration has not been performed – Alert PCU 3
24 Hour Clogged Filter PCU 3
Binary Input
135
No-Units
*Clogged Filter for 24 Hours – Alert PCU 3
PrepTimeButton
Binary Value
136
No-Units
Control - Initiate(1)/Terminate(0) Prep Time Mode
FansONButton
Binary Value
137
No-Units
Control - Turn Fans ON(1)/OFF(0)
WashButton
Binary Value
138
No-Units
Control - Initiate(1)/Terminate(0) Wash
LightsButton
Binary Value
139
No-Units
Control – Turn Hood Lights ON(1)/OFF(0)
Figure 46. Numerical Code and Corresponding Fault Associated with Object IDs 63-72
*Please refer to VFD manual for more information on VFD fault codes. Please refer to CAS DCV
manual for more information on alerts. Please refer to PCU Filtration manual for more information
on PCU Alerts.
BACNET Object List for SC Packages
The following list includes objects for all possible sensors in an SC package. Not all sensors may be
present on each package due to variations in software revision, options ordered, etc.
Table 4. BACNET Object List for SC Packages
Object Name
Object Type
Object ID
Units
Description
Temperature Sensor 1
Analog Input
1
Deg_F
Temperature Reading Sensor 1, 1 decimal precision
Temperature Sensor 2
Analog Input
2
Deg_F
Temperature Reading Sensor 2
Temperature Sensor 3
Analog Input
3
Deg_F
Temperature Reading Sensor 3
Temperature Sensor 4
Analog Input
4
Deg_F
Temperature Reading Sensor 4
Temperature Sensor 5
Analog Input
5
Deg_F
Temperature Reading Sensor 5
44
Temperature Sensor 6
Analog Input
6
Deg_F
Temperature Reading Sensor 6
Temperature Sensor 7
Analog Input
7
Deg_F
Temperature Reading Sensor 7
Temperature Sensor 8
Analog Input
8
Deg_F
Temperature Reading Sensor 8
Temperature Sensor 9
Analog Input
9
Deg_F
Temperature Reading Sensor 9
Temperature Sensor 10
Analog Input
10
Deg_F
Temperature Reading Sensor 10
Temperature Sensor 11
Analog Input
11
Deg_F
Temperature Reading Sensor 11
Temperature Sensor 12
Analog Input
12
Deg_F
Temperature Reading Sensor 12
Temperature Sensor 13
Analog Input
13
Deg_F
Temperature Reading Sensor 13
Temperature Sensor 14
Analog Input
14
Deg_F
Temperature Reading Sensor 14
Temperature Sensor 15
Analog Input
15
Deg_F
Temperature Reading Sensor 15
Temperature Sensor 16
Analog Input
16
Deg_F
Temperature Reading Sensor 16
Temperature Sensor 17
Analog Input
17
Deg_F
Temperature Reading Sensor 17
Temperature Sensor 18
Analog Input
18
Deg_F
Temperature Reading Sensor 18
Temperature Sensor 19
Analog Input
19
Deg_F
Temperature Reading Sensor 19
Temperature Sensor 20
Analog Input
20
Deg_F
Temperature Reading Sensor 20
Temperature Sensor 21
Analog Input
21
Deg_F
Temperature Reading Sensor 21
Temperature Sensor 22
Analog Input
22
Deg_F
Temperature Reading Sensor 22
Temperature Sensor 23
Analog Input
23
Deg_F
Temperature Reading Sensor 23
Temperature Sensor 24
Analog Input
24
Deg_F
Temperature Reading Sensor 24
Temperature Sensor 25
Analog Input
25
Deg_F
Temperature Reading Sensor 25
Temperature Sensor 26
Analog Input
26
Deg_F
Temperature Reading Sensor 26
Temperature Sensor 27
Analog Input
27
Deg_F
Temperature Reading Sensor 27
Temperature Sensor 28
Analog Input
28
Deg_F
Temperature Reading Sensor 28
Temperature Sensor 29
Analog Input
29
Deg_F
Temperature Reading Sensor 29
Temperature Sensor 30
Analog Input
30
Deg_F
Temperature Reading Sensor 30
Temperature Sensor 31
Analog Input
31
Deg_F
Temperature Reading Sensor 31
Temperature Sensor 32
Analog Input
32
Deg_F
Temperature Reading Sensor 32
Zone 1-Fans ON by Duct Temp
Binary Input
33
No-Units
Fan Status - ON due to Duct Stat Sensor Reading
Zone 1-Fans ON by Button
Binary Input
34
No-Units
Fan Status - ON due to Button Pressed
Zone 1-Fans ON by Interlock (IO1)
Binary Input
35
No-Units
Fan Status - ON due to Interlock
Zone 1-Fans ON by Fire Condition
Binary Input
36
No-Units
Fan Status - ON due to Fire Condition
Zone 1-Fans ON by BMS
Binary Input
37
No-Units
Fan Status - ON due to BMS command
Zone 1-Fans ON by Wash Cycle
Binary Input
38
No-Units
Fan Status - ON due to Wash Cycle
Zone 1-Fans ON by Proving
Binary Input
39
No-Units
Fan Status - ON due to Proving
Zone 1-Fans ON by CO Sensor
Binary Input
40
No-Units
Fan Status – ON due to CO Sensor
Zone 1-Fans ON by System Bypass
Binary Input
41
No-Units
Fan Status – ON due to System Bypass
Zone 2-Fans ON by Duct Temp
Binary Input
42
No-Units
Fan Status - ON due to Duct Stat Sensor Reading
Zone 2-Fans ON by Button
Binary Input
43
No-Units
Fan Status - ON due to Button Pressed
Zone 2-Fans ON by Interlock (IO1)
Binary Input
44
No-Units
Fan Status - ON due to Interlock
Zone 2-Fans ON by Fire Condition
Binary Input
45
No-Units
Fan Status - ON due to Fire Condition
Zone 2-Fans ON by BMS
Binary Input
46
No-Units
Fan Status - ON due to BMS command
Zone 2-Fans ON by Wash Cycle
Binary Input
47
No-Units
Fan Status - ON due to Wash Cycle
Zone 2-Fans ON by Proving
Binary Input
48
No-Units
Fan Status - ON due to Proving
45
Zone 2-Fans ON by CO Sensor
Binary Input
49
No-Units
Fan Status – ON due to CO Sensor
Zone 2-Fans ON by System Bypass
Binary Input
50
No-Units
Fan Status – ON due to System Bypass
Fire Alert
Binary Input
51
No-Units
*Alert – Fire Condition or circuit not wired properly
PCU Fault
Binary Input
52
No-Units
*Alert – PCU filters are clogged or missing
Proving Fault
Binary Input
53
No-Units
*Alert – Proving Interlock Error
Fuse F1 Blown
Binary Input
54
No-Units
*Alert – Replace Fuse F1 on ECPM03 Board
Lights Fault
Binary Input
55
No-Units
*Alert – Lights Switch and Power Status Mismatch
High Temperature Shut Down
Binary Input
56
No-Units
*Alert – Equipment shutdown due to high duct temp
Surfactant Low
Binary Input
57
No-Units
*Alert – Surfactant level is low
Modbus Comm Error
Binary Input
58
No-Units
*Alert – Network Component Not Responding
Temp Sensor Not Connected
Binary Input
59
No-Units
*Alert – Temp Sensor is disconnected
Zone 1- Fan Overload
Binary Input
60
No-Units
*Alert – Fan Overload Zone 1
Zone 2 - Fan Overload
Binary Input
61
No-Units
*Alert – Fan Overload Zone 2
Kill Switch
Binary Input
62
No-Units
*Alert – Kill Switch Activated
Bad Temp Sensor
Binary Input
63
No-Units
*Alert – Temp Sensor is malfunctioning
High Level of CO
Binary Input
64
No-Units
*Alert – High level of CO detected
Clog Percentage - PCUFMM 1 Filter 1
Analog Input
65
No-Units
Clog Percentage of Filter 1 in PCU 1
Clog Percentage - PCUFMM 1 Filter 2
Analog Input
66
No-Units
Clog Percentage of Filter 2 in PCU 1
Clog Percentage - PCUFMM 1 Filter 3
Analog Input
67
No-Units
Clog Percentage of Filter 3 in PCU 1
Clog Percentage - PCUFMM 1 Filter 4
Analog Input
68
No-Units
Clog Percentage of Filter 4 in PCU 1
Clog Percentage - PCUFMM 1 Filter 5
Analog Input
69
No-Units
Clog Percentage of Filter 5 in PCU 1
Clog Percentage - PCUFMM 2 Filter 1
Analog Input
70
No-Units
Clog Percentage of Filter 1 in PCU 2
Clog Percentage - PCUFMM 2 Filter 2
Analog Input
71
No-Units
Clog Percentage of Filter 2 in PCU 2
Clog Percentage - PCUFMM 2 Filter 3
Analog Input
72
No-Units
Clog Percentage of Filter 3 in PCU 2
Clog Percentage - PCUFMM 2 Filter 4
Analog Input
73
No-Units
Clog Percentage of Filter 4 in PCU 2
Clog Percentage - PCUFMM 2 Filter 5
Analog Input
74
No-Units
Clog Percentage of Filter 5 in PCU 2
Clog Percentage - PCUFMM 3 Filter 1
Analog Input
75
No-Units
Clog Percentage of Filter 1 in PCU 3
Clog Percentage - PCUFMM 3 Filter 2
Analog Input
76
No-Units
Clog Percentage of Filter 2 in PCU 3
Clog Percentage - PCUFMM 3 Filter 3
Analog Input
77
No-Units
Clog Percentage of Filter 3 in PCU 3
Clog Percentage - PCUFMM 3 Filter 4
Analog Input
78
No-Units
Clog Percentage of Filter 4 in PCU 3
Clog Percentage - PCUFMM 3 Filter 5
Analog Input
79
No-Units
Clog Percentage of Filter 5 in PCU 3
Internal Fault PCU 1
Binary Input
80
No-Units
*Internal Fault on Circuit Board – Alert PCU 1
Clogged Filter PCU 1
Binary Input
81
No-Units
*Clogged Filter – Alert PCU 1
Missing Filter PCU 1
Binary Input
82
No-Units
*Missing Filter – Alert PCU 1
72 Hour Clogged Filter PCU 1
Binary Input
83
No-Units
*Clogged Filter for 72 Hours – Alert PCU 1
Clogged PCU 1
Binary Input
84
No-Units
*Total Clogging – Alert PCU 1
Door Missing PCU 1
Binary Input
85
No-Units
*Door Missing – Alert PCU 1
Not Calibrated PCU 1
Binary Input
86
No-Units
*Calibration has not been performed – Alert PCU 1
24 Hour Clogged Filter PCU 1
Binary Input
87
No-Units
*Clogged Filter for 24 Hours – Alert PCU 1
Internal Fault PCU 2
Binary Input
88
No-Units
*Internal Fault on Circuit Board – Alert PCU 2
Clogged Filter PCU 2
Binary Input
89
No-Units
*Clogged Filter – Alert PCU 2
Missing Filter PCU 2
Binary Input
90
No-Units
*Missing Filter – Alert PCU 2
No-Units
*Clogged Filter for 72 Hours – Alert PCU 2
72 Hour Clogged Filter PCU 2
Binary Input
91
46
Clogged PCU 2
Binary Input
92
No-Units
*Total Clogging – Alert PCU 2
Door Missing PCU 2
Binary Input
93
No-Units
*Door Missing – Alert PCU 2
Not Calibrated PCU 2
Binary Input
94
No-Units
*Calibration has not been performed – Alert PCU 2
24 Hour Clogged Filter PCU 2
Binary Input
95
No-Units
*Clogged Filter for 24 Hours – Alert PCU 2
Internal Fault PCU 3
Binary Input
96
No-Units
*Internal Fault on Circuit Board – Alert PCU 3
Clogged Filter PCU 3
Binary Input
97
No-Units
*Clogged Filter – Alert PCU 3
Missing Filter PCU 3
Binary Input
98
No-Units
*Missing Filter – Alert PCU 3
72 Hour Clogged Filter PCU 3
Binary Input
99
No-Units
*Clogged Filter for 72 Hours – Alert PCU 3
Clogged PCU 3
Binary Input
100
No-Units
*Total Clogging – Alert PCU 3
Door Missing PCU 3
Binary Input
101
No-Units
*Door Missing – Alert PCU 3
Not Calibrated PCU 3
Binary Input
102
No-Units
*Calibration has not been performed – Alert PCU 3
24 Hour Clogged Filter PCU 3
Binary Input
103
No-Units
*Clogged Filter for 24 Hours – Alert PCU 3
Zone 1-FansONButton
Binary Value
104
No-Units
Control - Turn Fans ON(1)/OFF(0)
Zone 2-FansONButton
Binary Value
105
No-Units
Control - Turn Fans ON(1)/OFF(0)
WashButton
Binary Value
106
No-Units
**Control - Initiate(1)/Terminate(0) Wash
Zone 1-LightsButton
Binary Value
107
No-Units
Control – Turn Hood Lights ON(1)/OFF(0)
Zone 2-LightsButton
Binary Value
108
No-Units
Control – Turn Hood Lights ON(1)/OFF(0)
*Please refer to CAS Smart Controls manual for more information on alerts. Please refer to PCU
Filtration manual for more information on PCU Alerts.
**Command not available if there are multiple fan zones.
Building Management System fan commands will take precedence over direct commands made through
the HMI of the controls package. However, the highest precedence will always be given to emergency
conditions (i.e. Fire, High Temp Shutdown) and to temperature sensor readings (Duct Stat Override).
Fans: If the fans are turned ON by the BMS, they can only be turned OFF by an emergency condition
(i.e. Fire, High Temp Shutdown) or by the BMS. If fans are turned OFF by the BMS, they can always be
turned ON manually by the HMI or automatically through Duct Stat Override (temperature readings).
Lights: Lights can be turned ON and OFF by the BMS or by the HMI, meaning that they can override
each other. Lights will respond to any emergency conditions.
Wash: Wash cycles can be started/stopped by the BMS or the HMI, meaning that they can override each
other.
All commands are activated by writing a “1” onto the present value of the object. Likewise, all commands
are deactivated by writing a “0” onto the present value of the object. The FansONButton will only reflect
BMS commands, meaning that if the fan is turned ON by the HMI or automatically by the temperature
sensors, the FansONButton will remain as 0. On the other hand, the state of the lights and wash buttons
reflect either BMS commands or HMI commands. This implies that wash cycles and light commands
initiated by the BMS can be overridden by the HMI (local override) and vice versa.
Changing Network Number and Device Instance
Some applications may require that the Protocessor have a specific Network Number or Device Instance.
To change the Network Number or Device Instance, you must access the Web Configurator by
connecting a computer to the Ethernet port of the Protocessor. The computer used must be assigned a
static IP address of 192.168.1.xxx and a subnet mask of 255.255.255.0.
To access the Web Configurator, type the IP address of the Protocessor in the URL of any web browser.
The default IP address of the Protocessor is “192.168.1.24”. The window shown in Figure 46 should
47
appear. The “network_nr” field can be changed in order to apply a new network number. The default
network number for BACNET IP is 50. The network number for BACNET MS/TP is 0 (this is noneditable).
Similarly, changing the “node_offset” field will change the Device Instance. The Device Instance is
calculated by adding the “node_offset” and the Node ID (always 59 for DCV and SC Packages). The
default Device Instance is 50,059.
Figure 46. Configuration Parameters Page
If any changes are made, click the “Submit” button for each individual change. Once all changes
have been made, click “System Restart” at the bottom of the screen. NOTE: DO NOT CLICK “CLEAR
PROFILES AND RESTART”.
48
Changing the IP Address
Some BACNET IP applications may require changing the IP address of the Protocessor. In order to
change the IP address, go to the internal server by typing the default IP address of the Protocessor,
“192.168.1.24”, in the URL field of any web browser. The computer used must have a static IP address of
192.168.1.xxx. The window shown in “Error! Reference source not found.” appears. Click the
“Diagnostics and Debugging” button on the lower right corner.
Then, click “Setup” from the left-hand side menu, and select “Network Settings”. The window shown in
Figure 47 will appear. You can now modify the IP address to whatever is required in the application. Once
the IP address has been modified, click “Update IP Settings”.
Figure 47. Network Settings Page
After you have updated the IP settings, you will be prompted to restart the system. You can do so by
clicking the “System Restart” button at the bottom of the screen. Any time after this, you will have to type
the new IP address of the Protocessor on the URL to gain access to the Web Configurator.
49
LonWorks Option for DCV and SC Packages
Installation
LonWorks compatibility can be implemented on CaptiveAire’s Demand Control Ventilation (DCV) and
Smart Controls (SC) packages through the ProtoNode, a LonMark certified external gateway configured
to give a Building Management System access to monitor and/or control a list of network variables. The
ProtoNode is mounted and factory pre-wired inside the Electrical Control Panel. Field connections to the
Building Management System are shown in Figure 48.
Figure 48. LonWorks Field Connection
50
Operation
LonWorks SNVT List for DCV Packages
The following list includes network variable for all possible sensors in a DCV package. NOTE: Not all
sensors may be present on each package due to software revision, options ordered, etc.
Table 5. LonWorks SNVT List for DCV Packages
SNVT Name
SNVT Type
Description
SNVT Units
nvoTempSensor1
Index
0
SNVT_temp_f
Temperature Reading Sensor 1, 1 decimal precision
Deg_F
nvoTempSensor2
1
SNVT_temp_f
Temperature Reading Sensor 2
Deg_F
Deg_F
nvoTempSensor3
2
SNVT_temp_f
Temperature Reading Sensor 3
nvoTempSensor4
3
SNVT_temp_f
Temperature Reading Sensor 4
Deg_F
nvoTempSensor5
4
SNVT_temp_f
Temperature Reading Sensor 5
Deg_F
Deg_F
nvoTempSensor6
5
SNVT_temp_f
Temperature Reading Sensor 6
nvoTempSensor7
6
SNVT_temp_f
Temperature Reading Sensor 7
Deg_F
nvoTempSensor8
7
SNVT_temp_f
Temperature Reading Sensor 8
Deg_F
nvoTempSensor9
8
SNVT_temp_f
Temperature Reading Sensor 9
Deg_F
Deg_F
nvoTempSensor10
9
SNVT_temp_f
Temperature Reading Sensor 10
nvoTempSensor11
10
SNVT_temp_f
Temperature Reading Sensor 11
Deg_F
nvoTempSensor12
11
SNVT_temp_f
Temperature Reading Sensor 12
Deg_F
nvoTempSensor13
12
SNVT_temp_f
Temperature Reading Sensor 13
Deg_F
Deg_F
nvoTempSensor14
13
SNVT_temp_f
Temperature Reading Sensor 14
nvoTempSensor15
14
SNVT_temp_f
Temperature Reading Sensor 15
Deg_F
nvoTempSensor16
15
SNVT_temp_f
Temperature Reading Sensor 16
Deg_F
Deg_F
nvoTempSensor17
16
SNVT_temp_f
Temperature Reading Sensor 17
nvoTempSensor18
17
SNVT_temp_f
Temperature Reading Sensor 18
Deg_F
nvoTempSensor19
18
SNVT_temp_f
Temperature Reading Sensor 19
Deg_F
nvoTempSensor20
19
SNVT_temp_f
Temperature Reading Sensor 20
Deg_F
Deg_F
nvoTempSensor21
20
SNVT_temp_f
Temperature Reading Sensor 21
nvoTempSensor22
21
SNVT_temp_f
Temperature Reading Sensor 22
Deg_F
nvoTempSensor23
22
SNVT_temp_f
Temperature Reading Sensor 23
Deg_F
Deg_F
nvoTempSensor24
23
SNVT_temp_f
Temperature Reading Sensor 24
nvoTempSensor25
24
SNVT_temp_f
Temperature Reading Sensor 25
Deg_F
nvoTempSensor26
25
SNVT_temp_f
Temperature Reading Sensor 26
Deg_F
nvoTempSensor27
26
SNVT_temp_f
Temperature Reading Sensor 27
Deg_F
Deg_F
nvoTempSensor28
27
SNVT_temp_f
Temperature Reading Sensor 28
nvoTempSensor29
28
SNVT_temp_f
Temperature Reading Sensor 29
Deg_F
nvoTempSensor30
29
SNVT_temp_f
Temperature Reading Sensor 30
Deg_F
nvoTempSensor31
30
SNVT_temp_f
Temperature Reading Sensor 31
Deg_F
Deg_F
nvoTempSensor32
31
SNVT_temp_f
Temperature Reading Sensor 32
nvoFreq_Exh1
32
SNVT_freq_f
VFD Frequency for Exhaust Fan 1, 1 decimal precision
Hz
nvoFreq_Exh2
33
SNVT_freq_f
VFD Frequency for Exhaust Fan 2
Hz
Hz
Hz
nvoFreq_Exh3
34
SNVT_freq_f
VFD Frequency for Exhaust Fan 3
nvoFreq_Exh4
35
SNVT_freq_f
VFD Frequency for Exhaust Fan 4
51
nvoFreq_Exh5
36
SNVT_freq_f
VFD Frequency for Exhaust Fan 5
Hz
nvoFreq_Exh6
37
SNVT_freq_f
VFD Frequency for Exhaust Fan 6
Hz
Hz
nvoFreq_Exh7
38
SNVT_freq_f
VFD Frequency for Exhaust Fan 7
nvoFreq_Exh8
39
SNVT_freq_f
VFD Frequency for Exhaust Fan 8
Hz
nvoFreq_Sup1
40
SNVT_freq_f
VFD Frequency for Supply Fan 1
Hz
nvoFreq_Sup2
41
SNVT_freq_f
VFD Frequency for Supply Fan 2
Hz
Amps
nvoAmps_Exh1
42
SNVT_amp_f
Amperage for Fan Exhaust 1, 1 decimal precision
nvoAmps_Exh2
43
SNVT_amp_f
Amperage for Fan Exhaust 2
Amps
nvoAmps_Exh3
44
SNVT_amp_f
Amperage for Fan Exhaust 3
Amps
nvoAmps_Exh4
45
SNVT_amp_f
Amperage for Exhaust Fan 4
Amps
Amps
nvoAmps_Exh5
46
SNVT_amp_f
Amperage for Exhaust Fan 5
nvoAmps_Exh6
47
SNVT_amp_f
Amperage for Exhaust Fan 6
Amps
nvoAmps_Exh7
48
SNVT_amp_f
Amperage for Exhaust Fan 7
Amps
Amps
nvoAmps_Exh8
49
SNVT_amp_f
Amperage for Exhaust Fan 8
nvoAmps_Sup1
50
SNVT_amp_f
Amperage for Supply Fan 1
Amps
nvoAmps_Sup2
51
SNVT_amp_f
Amperage for Supply Fan 2
Amps
nvoKWs_Exh1
52
SNVT_count_f
KW for Exhaust Fan 1, 2 decimal precision
KW
KW
nvoKWs_Exh2
53
SNVT_count_f
KW for Exhaust Fan 2
nvoKWs_Exh3
54
SNVT_count_f
KW for Exhaust Fan 3
KW
nvoKWs_Exh4
55
SNVT_count_f
KW for Exhaust Fan 4
KW
KW
nvoKWs_Exh5
56
SNVT_count_f
KW for Exhaust Fan 5
nvoKWs_Exh6
57
SNVT_count_f
KW for Exhaust Fan 6
KW
nvoKWs_Exh7
58
SNVT_count_f
KW for Exhaust Fan 7
KW
nvoKWs_Exh8
59
SNVT_count_f
KW for Exhaust Fan 8
KW
KW
nvoKWs_Sup1
60
SNVT_count_f
KW for Supply Fan 1
nvoKWs_Sup2
61
SNVT_count_f
KW for Supply Fan 2
KW
nvoVFDFaultExh1
62
SNVT_count
*Fault Code for VFD Exhaust Fan 1
No-Units
nvoVFDFaultExh2
63
SNVT_count
*Fault Code for VFD Exhaust Fan 2
No-Units
No-Units
nvoVFDFaultExh3
64
SNVT_count
*Fault Code for VFD Exhaust Fan 3
nvoVFDFaultExh4
65
SNVT_count
*Fault Code for VFD Exhaust Fan 4
No-Units
nvoVFDFaultExh5
66
SNVT_count
*Fault Code for VFD Exhaust Fan 5
No-Units
No-Units
nvoVFDFaultExh6
67
SNVT_count
*Fault Code for VFD Exhaust Fan 6
nvoVFDFaultExh7
68
SNVT_count
*Fault Code for VFD Exhaust Fan 7
No-Units
nvoVFDFaultExh8
69
SNVT_count
*Fault Code for VFD Exhaust Fan 8
No-Units
nvoVFDFaultSup1
70
SNVT_count
*Fault Code for VFD Supply Fan 1
No-Units
No-Units
nvoVFDFaultSup2
71
SNVT_count
*Fault Code for VFD Supply Fan 2
nvoON_Duct_Temp
72
SNVT_count
Fan Status - ON due to Duct Stat Sensor Reading
No-Units
nvoON_Button
73
SNVT_count
Fan Status - ON due to Button Pressed
No-Units
nvoON_IO1
74
SNVT_count
Fan Status - ON due to Interlock
No-Units
No-Units
No-Units
nvoON_Fire
75
SNVT_count
Fan Status - ON due to Fire Condition
nvoON_BMS
76
SNVT_count
Fan Status - ON due to BMS command
nvoON_Wash
77
SNVT_count
Fan Status - ON due to Wash Cycle
No-Units
SNVT_count
Fan Status - ON due to Proving
No-Units
nvoON_Proving
78
52
nvoON_COSensor
79
SNVT_count
Fan Status – ON due to CO Sensor
No-Units
nvoON_MaxAir
80
SNVT_count
Fan Status – ON due to Max Air Button
No-Units
No-Units
nvoON_SysBypass
81
SNVT_count
Fan Status – ON due to System Bypass
nvoFireAlert
82
SNVT_count
*Alert – Fire Condition or circuit not wired properly
No-Units
nvoPCUFault
83
SNVT_count
*Alert – PCU filters are clogged or missing
No-Units
nvoProvingFault
84
SNVT_count
*Alert – Proving Interlock Error
No-Units
No-Units
nvoFuseF1Blown
85
SNVT_count
*Alert – Replace Fuse F1 on ECPM03 Board
nvoLightsFault
86
SNVT_count
*Alert – Lights Switch and Power Status Mismatch
No-Units
nvoHighTemp
87
SNVT_count
*Alert – Equipment shutdown due to high duct temp
No-Units
nvoSurfLow
88
SNVT_count
*Alert – Surfactant level is low
No-Units
No-Units
nvoModComError
89
SNVT_count
*Alert – Network Component Not Responding
nvoTempSensErr
90
SNVT_count
*Alert – Temp Sensor is disconnected
No-Units
nvoMUA1ILError
91
SNVT_count
*Alert – Interlock Signal form MUA unit 1 not received
No-Units
No-Units
nvoMUA2ILError
92
SNVT_count
*Alert – Interlock Signal form MUA unit 2 not received
nvoKillSwitch
93
SNVT_count
*Alert – Kill Switch Activated
No-Units
nvoBadTempSensor
94
SNVT_count
*Alert – Temp Sensor is malfunctioning
No-Units
nvoHighCOLevel
95
SNVT_count
*Alert – High level of CO detected
No-Units
No-Units
nvoPCUClgPcnt1_1
96
SNVT_count
Clog Percentage of Filter 1 in PCU 1
nvoPCUClgPcnt1_2
97
SNVT_count
Clog Percentage of Filter 2 in PCU 1
No-Units
nvoPCUClgPcnt1_3
98
SNVT_count
Clog Percentage of Filter 3 in PCU 1
No-Units
No-Units
nvoPCUClgPcnt1_4
99
SNVT_count
Clog Percentage of Filter 4 in PCU 1
nvoPCUClgPcnt1_5
100
SNVT_count
Clog Percentage of Filter 5 in PCU 1
No-Units
nvoPCUClgPcnt2_1
101
SNVT_count
Clog Percentage of Filter 1 in PCU 2
No-Units
nvoPCUClgPcnt2_2
102
SNVT_count
Clog Percentage of Filter 2 in PCU 2
No-Units
No-Units
nvoPCUClgPcnt2_3
103
SNVT_count
Clog Percentage of Filter 3 in PCU 2
nvoPCUClgPcnt2_4
104
SNVT_count
Clog Percentage of Filter 4 in PCU 2
No-Units
nvoPCUClgPcnt2_5
105
SNVT_count
Clog Percentage of Filter 5 in PCU 2
No-Units
nvoPCUClgPcnt3_1
106
SNVT_count
Clog Percentage of Filter 1 in PCU 3
No-Units
No-Units
nvoPCUClgPcnt3_2
107
SNVT_count
Clog Percentage of Filter 2 in PCU 3
nvoPCUClgPcnt3_3
108
SNVT_count
Clog Percentage of Filter 3 in PCU 3
No-Units
nvoPCUClgPcnt3_4
109
SNVT_count
Clog Percentage of Filter 4 in PCU 3
No-Units
No-Units
nvoPCUClgPcnt3_5
110
SNVT_count
Clog Percentage of Filter 5 in PCU 3
nvoIntFaultPCU1
111
SNVT_count
*Internal Fault on Circuit Board – Alert PCU 1
No-Units
nvoClogFiltPCU1
112
SNVT_count
*Clogged Filter – Alert PCU 1
No-Units
nvoMissFiltPCU1
113
SNVT_count
*Missing Filter – Alert PCU 1
No-Units
No-Units
nvo72hClogPCU1
114
SNVT_count
*Clogged Filter for 72 Hours – Alert PCU 1
nvoTotalClogPCU1
115
SNVT_count
*Total Clogging – Alert PCU 1
No-Units
nvoDoorMissPCU1
116
SNVT_count
*Door Missing – Alert PCU 1
No-Units
nvoNotCalibrPCU1
117
SNVT_count
*Calibration has not been performed – Alert PCU 1
No-Units
No-Units
nvo24hClogPCU1
118
SNVT_count
*Clogged Filter for 24 Hours – Alert PCU 1
nvoIntFaultPCU1
119
SNVT_count
*Internal Fault on Circuit Board – Alert PCU 2
No-Units
nvoClogFiltPCU1
120
SNVT_count
*Clogged Filter – Alert PCU 2
No-Units
SNVT_count
*Missing Filter – Alert PCU 2
No-Units
nvoMissFiltPCU1
121
53
nvo72hClogPCU1
122
SNVT_count
*Clogged Filter for 72 Hours – Alert PCU 2
No-Units
nvoTotalClogPCU1
123
SNVT_count
*Total Clogging – Alert PCU 2
No-Units
No-Units
nvoDoorMissPCU1
124
SNVT_count
*Door Missing – Alert PCU 2
nvoNotCalibrPCU1
125
SNVT_count
*Calibration has not been performed – Alert PCU 2
No-Units
nvo24hClogPCU1
126
SNVT_count
*Clogged Filter for 24 Hours – Alert PCU 2
No-Units
nvoIntFaultPCU1
127
SNVT_count
*Internal Fault on Circuit Board – Alert PCU 3
No-Units
No-Units
nvoClogFiltPCU1
128
SNVT_count
*Clogged Filter – Alert PCU 3
nvoMissFiltPCU1
129
SNVT_count
*Missing Filter – Alert PCU 3
No-Units
nvo72hClogPCU1
130
SNVT_count
*Clogged Filter for 72 Hours – Alert PCU 3
No-Units
nvoTotalClogPCU1
131
SNVT_count
*Total Clogging – Alert PCU 3
No-Units
No-Units
No-Units
nvoDoorMissPCU1
132
SNVT_count
*Door Missing – Alert PCU 3
nvoNotCalibrPCU1
133
SNVT_count
*Calibration has not been performed – Alert PCU 3
nvo24hClogPCU1
134
SNVT_count
*Clogged Filter for 24 Hours – Alert PCU 3
No-Units
No-Units
nvoPrepTimeB
135
SNVT_count
Monitor - Initiate(1)/Terminate(0) Prep Time Mode
nvoFansONB
136
SNVT_count
Monitor - Turn Fans ON(1)/OFF(0)
No-Units
nvoWashB
137
SNVT_count
Monitor - Initiate(1)/Terminate(0) Wash
No-Units
nvoLightsB
138
SNVT_count
Monitor – Turn Hood Lights ON(1)/OFF(0)
No-Units
No-Units
nviPrepTimeB
139
SNVT_count
Control - Initiate(1)/Terminate(0) Prep Time Mode
nviFansONB
140
SNVT_count
Control - Turn Fans ON(1)/OFF(0)
No-Units
nviWashB
141
SNVT_count
Control - Initiate(1)/Terminate(0) Wash
No-Units
SNVT_count
Control – Turn Hood Lights ON(1)/OFF(0)
No-Units
nviLightsB
142
Figure 49. Numerical Code and Corresponding Fault Associated with SNVT Indices 62-71
*Please refer to VFD manual for more information on VFD fault codes. Please refer to DCV manual
for more information on Alerts. Please refer to PCU Filtration manual for more information on PCU
Alerts.
LonWorks SNVT List for SC Packages
The following list includes network variable for all possible sensors in an SC package. NOTE: Not all
sensors may be present on each package due to software revision, options ordered, etc.
Table 6. LonWorks SNVT List for SC Packages
SNVT Name
Index
SNVT Type
Description
SNVT Units
Deg_F
nvoTempSensor1
0
SNVT_temp_f
Temperature Reading Sensor 1, 1 decimal precision
nvoTempSensor2
1
SNVT_temp_f
Temperature Reading Sensor 2
Deg_F
SNVT_temp_f
Temperature Reading Sensor 3
Deg_F
SNVT_temp_f
Temperature Reading Sensor 4
Deg_F
nvoTempSensor3
nvoTempSensor4
2
3
54
nvoTempSensor5
4
SNVT_temp_f
Temperature Reading Sensor 5
Deg_F
nvoTempSensor6
5
SNVT_temp_f
Temperature Reading Sensor 6
Deg_F
SNVT_temp_f
Temperature Reading Sensor 7
Deg_F
SNVT_temp_f
Temperature Reading Sensor 8
Deg_F
Deg_F
nvoTempSensor7
nvoTempSensor8
6
7
nvoTempSensor9
8
SNVT_temp_f
Temperature Reading Sensor 9
nvoTempSensor10
9
SNVT_temp_f
Temperature Reading Sensor 10
Deg_F
SNVT_temp_f
Temperature Reading Sensor 11
Deg_F
SNVT_temp_f
Temperature Reading Sensor 12
Deg_F
Deg_F
nvoTempSensor11
nvoTempSensor12
10
11
nvoTempSensor13
12
SNVT_temp_f
Temperature Reading Sensor 13
nvoTempSensor14
13
SNVT_temp_f
Temperature Reading Sensor 14
Deg_F
SNVT_temp_f
Temperature Reading Sensor 15
Deg_F
SNVT_temp_f
Temperature Reading Sensor 16
Deg_F
Deg_F
nvoTempSensor15
nvoTempSensor16
14
15
nvoTempSensor17
16
SNVT_temp_f
Temperature Reading Sensor 17
nvoTempSensor18
17
SNVT_temp_f
Temperature Reading Sensor 18
Deg_F
SNVT_temp_f
Temperature Reading Sensor 19
Deg_F
SNVT_temp_f
Temperature Reading Sensor 20
Deg_F
Deg_F
nvoTempSensor19
nvoTempSensor20
18
19
nvoTempSensor21
20
SNVT_temp_f
Temperature Reading Sensor 21
nvoTempSensor22
21
SNVT_temp_f
Temperature Reading Sensor 22
Deg_F
SNVT_temp_f
Temperature Reading Sensor 23
Deg_F
SNVT_temp_f
Temperature Reading Sensor 24
Deg_F
Deg_F
nvoTempSensor23
nvoTempSensor24
22
23
nvoTempSensor25
24
SNVT_temp_f
Temperature Reading Sensor 25
nvoTempSensor26
25
SNVT_temp_f
Temperature Reading Sensor 26
Deg_F
SNVT_temp_f
Temperature Reading Sensor 27
Deg_F
SNVT_temp_f
Temperature Reading Sensor 28
Deg_F
Deg_F
nvoTempSensor27
nvoTempSensor28
26
27
nvoTempSensor29
28
SNVT_temp_f
Temperature Reading Sensor 29
nvoTempSensor30
29
SNVT_temp_f
Temperature Reading Sensor 30
Deg_F
SNVT_temp_f
Temperature Reading Sensor 31
Deg_F
SNVT_temp_f
Temperature Reading Sensor 32
Deg_F
No-Units
nvoTempSensor31
nvoTempSensor32
30
31
nvoON_Duct_Temp1
32
SNVT_count
Fan Status Zone 1 - ON due to Duct Stat Sensor Reading
nvoON_Button1
33
SNVT_count
Fan Status Zone 1 - ON due to Button Pressed
No-Units
nvoON_IO11
34
SNVT_count
Fan Status Zone 1 - ON due to Interlock
No-Units
SNVT_count
Fan Status Zone 1 - ON due to Fire Condition
No-Units
No-Units
nvoON_Fire1
35
nvoON_BMS1
36
SNVT_count
Fan Status Zone 1 - ON due to BMS command
nvoON_Wash1
37
SNVT_count
Fan Status Zone 1 - ON due to Wash Cycle
No-Units
SNVT_count
Fan Status Zone 1 - ON due to Proving
No-Units
SNVT_count
Fan Status Zone 1 – ON due to CO Sensor
No-Units
No-Units
nvoON_Proving1
nvoON_COSensor1
38
39
nvoON_SysBypas1
40
SNVT_count
Fan Status Zone 1 – ON due to System Bypass
nvoON_Duct_Temp2
41
SNVT_count
Fan Status Zone 2 - ON due to Duct Stat Sensor Reading
No-Units
SNVT_count
Fan Status Zone 2 - ON due to Button Pressed
No-Units
SNVT_count
Fan Status Zone 2 - ON due to Interlock
No-Units
No-Units
nvoON_Button2
nvoON_IO12
42
43
nvoON_Fire2
44
SNVT_count
Fan Status Zone 2 - ON due to Fire Condition
nvoON_BMS2
45
SNVT_count
Fan Status Zone 2 - ON due to BMS command
No-Units
SNVT_count
Fan Status Zone 2 - ON due to Wash Cycle
No-Units
nvoON_Wash2
46
55
nvoON_Proving2
47
SNVT_count
Fan Status Zone 2 - ON due to Proving
No-Units
nvoON_COSensor2
48
SNVT_count
Fan Status Zone 2 – ON due to CO Sensor
No-Units
SNVT_count
Fan Status Zone 2 – ON due to System Bypass
No-Units
SNVT_count
*Alert – Fire Condition or circuit not wired properly
No-Units
No-Units
nvoON_SysBypas2
nvoFireAlert
49
50
nvoPCUFault
51
SNVT_count
*Alert – PCU filters are clogged or missing
nvoProvingFault
52
SNVT_count
*Alert – Proving Interlock Error
No-Units
SNVT_count
*Alert – Replace Fuse F1 on ECPM03 Board
No-Units
SNVT_count
*Alert – Lights Switch and Power Status Mismatch
No-Units
No-Units
nvoFuseF1Blown
nvoLightsFault
53
54
nvoHighTemp
55
SNVT_count
*Alert – Equipment shutdown due to high duct temp
nvoSurfLow
56
SNVT_count
*Alert – Surfactant level is low
No-Units
SNVT_count
*Alert – Network Component Not Responding
No-Units
SNVT_count
*Alert – Temp Sensor is disconnected
No-Units
No-Units
nvoModComError
nvoTempSensErr
57
58
nvoOverload1
59
SNVT_count
*Alert – Fan Overload Zone 1
nvoOverload2
60
SNVT_count
*Alert – Fan Overload Zone 2
No-Units
SNVT_count
*Alert – Kill Switch Activated
No-Units
SNVT_count
*Alert – Temp Sensor is malfunctioning
No-Units
No-Units
nvoKillSwitch
nvoBadTempSensor
61
62
nvoHighCOLevel
63
SNVT_count
*Alert – High level of CO detected
nvoPCUClgPcnt1_1
64
SNVT_count
Clog Percentage of Filter 1 in PCU 1
No-Units
SNVT_count
Clog Percentage of Filter 2 in PCU 1
No-Units
SNVT_count
Clog Percentage of Filter 3 in PCU 1
No-Units
No-Units
nvoPCUClgPcnt1_2
nvoPCUClgPcnt1_3
65
66
nvoPCUClgPcnt1_4
67
SNVT_count
Clog Percentage of Filter 4 in PCU 1
nvoPCUClgPcnt1_5
68
SNVT_count
Clog Percentage of Filter 5 in PCU 1
No-Units
SNVT_count
Clog Percentage of Filter 1 in PCU 2
No-Units
SNVT_count
Clog Percentage of Filter 2 in PCU 2
No-Units
No-Units
nvoPCUClgPcnt2_1
nvoPCUClgPcnt2_2
69
70
nvoPCUClgPcnt2_3
71
SNVT_count
Clog Percentage of Filter 3 in PCU 2
nvoPCUClgPcnt2_4
72
SNVT_count
Clog Percentage of Filter 4 in PCU 2
No-Units
SNVT_count
Clog Percentage of Filter 5 in PCU 2
No-Units
SNVT_count
Clog Percentage of Filter 1 in PCU 3
No-Units
No-Units
nvoPCUClgPcnt2_5
nvoPCUClgPcnt3_1
73
74
nvoPCUClgPcnt3_2
75
SNVT_count
Clog Percentage of Filter 2 in PCU 3
nvoPCUClgPcnt3_3
76
SNVT_count
Clog Percentage of Filter 3 in PCU 3
No-Units
SNVT_count
Clog Percentage of Filter 4 in PCU 3
No-Units
SNVT_count
Clog Percentage of Filter 5 in PCU 3
No-Units
No-Units
nvoPCUClgPcnt3_4
nvoPCUClgPcnt3_5
77
78
nvoIntFaultPCU1
79
SNVT_count
*Internal Fault on Circuit Board – Alert PCU 1
nvoClogFiltPCU1
80
SNVT_count
*Clogged Filter – Alert PCU 1
No-Units
SNVT_count
*Missing Filter – Alert PCU 1
No-Units
SNVT_count
*Clogged Filter for 72 Hours – Alert PCU 1
No-Units
No-Units
nvoMissFiltPCU1
nvo72hClogPCU1
81
82
nvoTotalClogPCU1
83
SNVT_count
*Total Clogging – Alert PCU 1
nvoDoorMissPCU1
84
SNVT_count
*Door Missing – Alert PCU 1
No-Units
SNVT_count
*Calibration has not been performed – Alert PCU 1
No-Units
SNVT_count
*Clogged Filter for 24 Hours – Alert PCU 1
No-Units
No-Units
nvoNotCalibrPCU1
nvo24hClogPCU1
85
86
nvoIntFaultPCU1
87
SNVT_count
*Internal Fault on Circuit Board – Alert PCU 2
nvoClogFiltPCU1
88
SNVT_count
*Clogged Filter – Alert PCU 2
No-Units
SNVT_count
*Missing Filter – Alert PCU 2
No-Units
nvoMissFiltPCU1
89
56
nvo72hClogPCU1
90
SNVT_count
*Clogged Filter for 72 Hours – Alert PCU 2
No-Units
nvoTotalClogPCU1
91
SNVT_count
*Total Clogging – Alert PCU 2
No-Units
SNVT_count
*Door Missing – Alert PCU 2
No-Units
SNVT_count
*Calibration has not been performed – Alert PCU 2
No-Units
No-Units
nvoDoorMissPCU1
nvoNotCalibrPCU1
92
93
nvo24hClogPCU1
94
SNVT_count
*Clogged Filter for 24 Hours – Alert PCU 2
nvoIntFaultPCU1
95
SNVT_count
*Internal Fault on Circuit Board – Alert PCU 3
No-Units
SNVT_count
*Clogged Filter – Alert PCU 3
No-Units
SNVT_count
*Missing Filter – Alert PCU 3
No-Units
No-Units
nvoClogFiltPCU1
nvoMissFiltPCU1
96
97
nvo72hClogPCU1
98
SNVT_count
*Clogged Filter for 72 Hours – Alert PCU 3
nvoTotalClogPCU1
99
SNVT_count
*Total Clogging – Alert PCU 3
No-Units
SNVT_count
*Door Missing – Alert PCU 3
No-Units
SNVT_count
*Calibration has not been performed – Alert PCU 3
No-Units
No-Units
nvoDoorMissPCU1
nvoNotCalibrPCU1
100
101
nvo24hClogPCU1
102
SNVT_count
*Clogged Filter for 24 Hours – Alert PCU 3
nvoFansONB1
103
SNVT_count
Monitor - Initiate(1)/Terminate(0) Prep Time Zone 1
No-Units
SNVT_count
Monitor - Initiate(1)/Terminate(0) Prep Time Zone 2
No-Units
SNVT_count
Monitor - Initiate(1)/Terminate(0) Wash
No-Units
No-Units
nvoFansONB2
nvoWashB
104
105
nvoLightsB1
106
SNVT_count
Monitor – Turn Hood Lights ON(1)/OFF(0) Zone 1
nvoLightsB2
107
SNVT_count
Monitor – Turn Hood Lights ON(1)/OFF(0) Zone 2
No-Units
SNVT_count
Control - Initiate(1)/Terminate(0) Prep Time Zone 1
No-Units
SNVT_count
Control - Initiate(1)/Terminate(0) Prep Time Zone 2
No-Units
No-Units
nviFansONB1
nviFansONB2
108
109
nviWashB
110
SNVT_count
**Control - Initiate(1)/Terminate(0) Wash
nviLightsB1
111
SNVT_count
Control – Turn Hood Lights ON(1)/OFF(0) Zone 1
No-Units
SNVT_count
Control – Turn Hood Lights ON(1)/OFF(0) Zone 2
No-Units
nviLightsB2
112
*Please refer to CAS Electrical Controls manual for more information on alerts. Please refer to
PCU Filtration manual for more information on PCU Alerts.
**Command not available if there are multiple fan zones.
Building Management System fan commands will take precedence over direct commands made through
the HMI of the controls package. However, the highest precedence will always be given to emergency
conditions (i.e. Fire, High Temp Shutdown) and to temperature sensor readings (Duct Stat Override).
Fans: If the fans are turned ON by the BMS, they can only be turned OFF by an emergency condition
(i.e. Fire, High Temp Shutdown) or by the BMS. If fans are turned OFF by the BMS, they can always be
turned ON manually by the HMI or automatically through Duct Stat Override (temperature readings).
Lights: Lights can be turned ON and OFF by the BMS or by the HMI, meaning that they can override
each other. Lights will respond to any emergency conditions.
Wash: Wash cycles can be started/stopped by the BMS or the HMI, meaning that they can override each
other.
All commands are activated by sending a “1” to network variable inputs. Likewise, all commands are
deactivated by sending a “0” to network variable inputs. All network variable inputs have corresponding
network variable outputs to monitor their current state. The FansONButton will only reflect BMS
commands, meaning that if the fan is turned ON by the HMI or automatically by the temperature sensors,
the FansONButton will remain as 0. On the other hand, the state of the lights and wash buttons reflect
either BMS commands or HMI commands. This implies that wash cycles and light commands initiated by
the BMS can be overridden by the HMI and vice versa.
57
Commissioning on a LonWorks Network
During the commissioning process by the LonWorks administrator (using a LonWorks Network
Management Tool), the user will be prompted to hit the Service Pin in the ProtoNode. This pin is located
in the front face, and it can be pressed by inserting a small screwdriver and tilting it towards the
LonWorks Port. The location of the Service Pin is shown in Figure 50.
Figure 50. Service Pin Location
.
If an XIF file is required, it can be obtained by following these steps:
1. Set your computer’s static IP address to “192.168.1.xxx” with a subnet mask of “255.255.255.0”.
2. Run a Cat-5 connection from the ProtoNode’s Ethernet port to your computer.
3. On any web browser’s URL field, type “192.168.1.24/fserver.xif”
The web browser should automatically download the fserver.xif file or let you save it on your computer.
Save it as “fserver.xif”.
58
Appendix A
Cradlepoint Cellular GPIO Power Pinout and Wiring Diagram
1. The Cradlepoint power connection is via a GPIO connector. The connector utilizes 4 pins. Only
two of them (pins 1 and 2 in Figure 51) are used to power the device. The wire with the white
stripe should be connected to the + terminal on the 12 VDC power supply and the black wire
should be connected to the - terminal on the 12VDC power supply.
Figure 51. Cradlepoint GPIO Connection
Figure 52. Cradlepoint Power Connection
59
Appendix B
Dismounting the Cradlepoint from the Control Box
1. In order to service or replace the Cradlepoint, you may need to remove it from its position inside
the control box. To do this, follow the steps below. The device should not be removed from its
mounting location inside the control box unless it is absolutely necessary.
a. To remove the Cradlepoint from the control box, first unscrew the antennas protruding
from the top of the box.
b. Next unscrew the four screws on the side of the box (Figure 53).
Figure 53. Cradlepoint Mounting Screws
c.
Once the four mounting screws are removed, make the necessary changes to the unit
and fasten the four screws back in place. At no point should the Cradlepoint be
removed/unclipped from the metal mount that it uses to attach to the box (Figure 54).
60
Figure 54. DO NOT REMOVE CRADLEPOINT FROM MOUNT
61
Appendix C
Weak Signal Strength (Less than -99 dBm)
1. Follow the beginning of the manual through Step 5d in order to access the Cradlepoint dashboard
page (Figure 4).
2. Adjust the antenna positions. The antennas have the ability to rotate 360 degrees and also have
the ability to bend at right angles. The antennas should not be lying flat on each other or touching
each other. After a small adjustment in antenna position is made, step away from the electrical
box and observe the signal strength to see if it has improved (a 15 second pause must occur
each time in order for the Cradlepoint dashboard to refresh).
3. If no improvement in signal strength results from adjusted antenna positions then an antenna with
a higher gain may be needed.
a. Once it is determined that a higher gain antenna will be needed, one can be ordered with
PN: Cellular_Antenna in NOLA or from your local service representative. Only one will be
needed per device as it replaces both regular modem antennas. To install, connect the
wire attached to the antenna to the SMA connector labeled “MAIN” in Figure 5. This will
be the antenna hole closest to the back of the control box. The antenna is magnetic so it
will mount on any flat metal surface (top of control enclosure, metal stud, etc.). Mount
antenna somewhere within reach of the wire length (20 ft.). Coil the extra cable up and
place neatly inside the control box away from high-voltage wiring.
4. Take new signal strength measurements. To do this, follow Step 6 in the section labeled Utilizing
a Cellular Wireless Bridge (Page 7).
a. If the poor signal strength persists with several different antenna locations tested, please
contact service@captiveaire.com.
62
MAINTENANCE
The CASLink Building Management System and Protocessor/ProtoNode Modules, by their very nature,
do not require physical maintenance unless a communication problem occurs.
If changes are made to the jobsite between standard 6-month checkup intervals for other equipment such
as the fans, fire system, etc., CASLink or Building Management Menus should be updated to reflect those
changes.
Please record the module Mac Address, BAUD rates, Authentication Key, End-User information and
module data in the start-up table, and present this manual to the end-user upon completion.
Module Registration Parameter Documentation
Record initial settings and upload settings to Service Job Notes using System Design Verification
Procedures.
Item
Data
MAC Address
Authentication Key
BAUD Rate
Device ID
End User Email
End User Name
End User Password
CAS Service Region
CAS Technician
Phone
Email
Factory Service Department
Phone: 1-866-784-6900
Fax: 1-919-554-9374
63
Download