ARCHITECTURE CONSTRUCTION MANAGEMENT DEVELOPMENT ELECTRICAL IDENTIFICATION DUPLEX RECEPTACLE PLATE STANDARD TOGGLE SWITCH PLATE FRONT SYMBOL FRONT REAR SIDE OF PLATE REAR SIDE OF PLATE N-2 N-5 LABEL CKT. NO. OF EACH DEVICE ON REAR SIDE OF COVER PLATE. USE PERMANANT MARKER PEN, BRADY MARKING SYSTEM OR OTHER METHOD APPROVED BY THE ENGINEER LABEL COVERS WITH CKT.'S CONTAINED WITHIN. USE PERMANANT MARKER PEN OR OTHER APPROVED METHOD. JUNCTION BOXES (EXPOSED OR CONCEALED ABOVE ACCESSIBLE CEILING) CKT.S LP4-13,15,17 ELECTRICAL SYMBOL LEGEND DESCRIPTION NOTES DESCRIPTION NOTES S S3 S4 SD SINGLE POLE SWITCH, (LEVITON #CSBI-20-W) MOUNT @ 44" A.F.F. TO BOTTOM OF BOX, UON DUPLEX OUTLET - 20 AMP (LEVITON #BR20-W) MOUNT @ 16" A.F.F. TO BOTTOM OF BOX, UON THREE-WAY SWITCH, (LEVITON #CSB3-20-W) MOUNT @ 44" A.F.F. TO BOTTOM OF BOX, UON MOUNT @ 44" A.F.F. TO BOTTOM OF BOX, UON GFCI WEATHER-RESISTANT DUPLEX OUTLET - (LEVITON #7899-T-W) w/ WHILE-IN-USE COVER (LEVITON #5977-DGY) MOUNT @ 24" A.F.F. TO BOTTOM OF BOX, UON FOUR-WAY SWITCH, (LEVITON #CSB4-20-W) DIMMER SWITCH (FIELD VERIFY w/ LOAD) MOUNT @ 44" A.F.F. TO BOTTOM OF BOX, UON DUPLEX OUTLET - GROUND FAULT (LEVITON #8899-W) MOUNT @ 16" A.F.F. TO BOTTOM OF BOX, UON S 3D SS S SF THREE-WAY DIMMER SWITCH (FIELD VERIFY w/ LOAD) MOUNT @ 44" A.F.F. TO BOTTOM OF BOX, UON GFCI DEAD-FRONT DUPLEX OUTLET - (P&S #2085W) MOUNT @ 42" A.F.F. TO BOTTOM OF BOX, UON PASSIVE INFRARED OCCUPANCY SENSOR SWITCH, MOUNT @ 44" A.F.F. TO BOTTOM OF BOX, UON DUAL-RELAY MULTI-TECHNOLOGY OCCUPANCY SENSOR WALL SWITCH, (LEVITON #OSSMD-FT*) MOUNT @ 44" A.F.F. TO BOTTOM OF BOX, UON - CONNECT EXHAUST FANS TO DELAYED-OFF ON SECOND RELAY. 250V OUTLET, VERIFY WITH EQUIPMENT SPECIFICATIONS MOUNT @ 48" A.F.F. TO BOTTOM OF BOX, UON SINGLE-PHASE SPECIAL PURPOSE OUTLET, AS NOTED REFER TO SHOP DRAWINGS FOR CONNECTION REQUIRE. ROUND FIXTURE SEE LIGHTING FIXTURE SCHEDULE FOR TYPES 2'x4' FIXTURE SEE LIGHTING FIXTURE SCHEDULE FOR TYPES 2'x2' FIXTURE SEE LIGHTING FIXTURE SCHEDULE FOR TYPES 1'x4' FIXTURE SEE LIGHTING FIXTURE SCHEDULE FOR TYPES WALL MOUNTED FIXTURE SEE LIGHTING FIXTURE SCHEDULE FOR TYPES 4' LINEAR FIXTURE SEE LIGHTING FIXTURE SCHEDULE FOR TYPES JUNCTION BOX WITH BLANK COVER UNIVERSAL EXIT SIGN w/ DIRECTIONAL ARROWS AS REQUIRED. SEE LIGHTING FIXTURE SCHEDULE FOR TYPES LIGHTING/BRANCH CIRCUIT PANELS REFER TO SPEC'S, AND ONE-LINE DIAGRAM. DOUBLE HEADED EMERGENCY LIGHT FIXTURE SEE LIGHTING FIXTURE SCHEDULE FOR TYPES LOW VOLTAGE DATA OUTLET REMOTE EMERGENCY LIGHT FIXTURE SEE LIGHTING FIXTURE SCHEDULE FOR TYPES E.C. TO PROVIDE AND INSTALL 4" SQ. x 2-1/8" DEEP BOX WITH 2" DEEP PLASTER RING AND 1" CONDUIT STUBBED ABOVE NEAREST ACCESSIBLE CEILING. AC ABOVE COUNTER CEILING MNTD. OCCUPANCY SENSOR SEE LIGHTING FIXTURE SCHEDULE FOR TYPES AFF ABOVE FINISHED FLOOR SWITCHPACK LIGHTING CONTROL (COOPER #SP20-MV) CONNECT TO OCC. SENSORS (PER MANUFACTURER) EC ELECTRICAL CONTRACTOR 120V PHOTOCELL CONNECT IN SERIES WITH TIMER AS REQ'D. EGC EQUIPMENT GROUNDING CONDUCTOR EXT'G DOOR BELL EXT'G EXISTING FIELD VERIFY GEC GROUNDING ELECTRODE CONDUCTOR EXT'G SURFACE MNTD RACEWAY OR PLUGSTRIP FIELD VERIFY SM SURFACE MOUNTED EXT'G PLYWOOD BACKWOOD FIELD VERIFY UON UNLESS OTHERWISE NOTED VIF VERIFY IN THE FIELD xR EXISTING TO BE RELOCATED 1-21 CIRCUIT FROM PANEL 1, CIRCUIT 21 LABEL EXAMPLES: ----------"FIRE ALARM-ZONES 2&3" "P.A. ZONES 4,5,&6" "DATA CIRCUITS A&B" "EXIT SIGNS-EMI&2" "EMERG. CKTS. BPEM-3,4" FOR J.B.'S CONTAINING OTHER THAN POWER OR LIGHTING CKT.'S LABEL COVERS INDICATING SYSTEM TYPE AND ZONES. SYMBOL LOW VOLTAGE DATA OUTLET DETAIL THE DESIGN GROUP SINGLE-PHASE MOTOR, AS SPECIFIED SINGLE-PHASE FUSED OR NON-FUSED DISCONNECT SINGLE-PHASE MANUAL STARTER OR COMB. DISC./STR. SM MOTOR TOGGLE SWITCH WITH THERMAL OVERLOAD AND LOCKOUT SQUARE D #CLASS 2510 FGJ5P (SINGLE POLE) 1104 S. MITCHELL ST. CADILLAC, MICHIGAN 49601 (231) 779-4002 (231) 779-4022 FAX GENERAL ELECTRICAL SPECIFICATIONS NO SCALE 1. 2. ELECTRICAL WORK SHALL COMPLY WITH THE LATEST ENFORCEABLE EDITION OF THE N.E.C., LOCAL AND STATE CODES, ORDINANCES, REGULATIONS, INCLUDING THE OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA), AND ADA GUIDELINES WITH THE LOCAL CODE AUTHORITIES HAVING JURISDICTION. 15. WITHIN THIRTY (30) DAYS AFTER THE ELECTRICAL CONTRACTOR HAS BEEN NOTIFIED TO PROCEED WITH THE WORK, HE SHALL SUBMIT TO THE ARCHITECT/ENGINEER EIGHT (8) PRINTED HARD COPIES OR ONE (1) ELECTRONIC COPY IN PDF FORMAT OF EACH OF THE FOLLOWING DRAWINGS AND DATA SHEETS FOR REVIEW. ALL EQUIPMENT FOR WHICH SHOP DRAWINGS ARE BEING SUBMITTED SHALL NOT BE ORDERED UNTIL APPROVED DRAWINGS HAVE BEEN RETURNED. SUCH SUBMITTALS SHALL INCLUDE: * ELECTRICAL DISTRIBUTION EQUIPMENT, INCLUDING CIRCUIT BREAKERS AND DISCONNECTS. * LIGHT FIXTURES, LIGHTING CONTROLS, AND LAMPS * WIRING DEVICES, INCLUDING SWITCHES, RECEPTACLES, ETC. 3. 16. ELECTRICAL MATERIALS SHALL BE NEW, AND BEAR THE "UL" LABEL OR LISTING. 1" CONN. & BUSHING ON STUB-OUTS CEILING PRIOR TO SUBMITTING A PROPOSAL, BIDDER SHALL HAVE VISITED THE CONSTRUCTION SITE. HE SHALL BE FAMILIAR WITH THE EXISTING CONDITIONS UNDER WHICH HE WILL HAVE TO OPERATE AND WHICH WILL IN ANY WAY AFFECT THE WORK UNDER THIS CONTRACT. NO SUBSEQUENT ALLOWANCE WILL BE MADE IN THIS CONNECTION ON BEHALF OF THE CONTRACTOR FOR ANY ERROR OR NEGLIGENCE ON HIS PART. 1" EMT 4" SQ. x 2 1/2" DEEP BOX W/ 1-GANG 2" DEEP PLASTER RING WITH BLANK S.G. WALL PLATES (TYPICAL OF EACH) 4. THE CONTRACTOR SHALL EMPLOY QUALIFIED AND EXPERIENCED WORKMEN FOR THIS WORK. 5. ELECTRICAL CONTRACTOR SHALL GUARANTEE ALL WORK INSTALLED UNDER HIS CONTRACT TO BE FREE FROM DEFECTIVE WORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE YEAR AFTER THE ACCEPTANCE OF THE BUILDING BY THE OWNER. SHOULD DEFECTS OCCUR WITHIN THIS PERIOD, REPAIR AND/OR REPLACE DEFECTIVE ITEMS AT NO EXPENSE TO THE OWNER. 18" AFF FLOOR ELECTRICAL CONTRACTOR SHALL OBTAIN ALL PERMITS, PAY ALL FEES, AND ARRANGE FOR ALL INSPECTIONS FOR HIS WORK. AT THE COMPLETION OF ELECTRICAL WORK, THE ELECTRICAL CONTRACTOR SHALL FURNISH THE OWNER WITH ALL CERTIFICATES OF FINAL INSPECTION AND APPROVALS. 6. THE ELECTRICAL CONTRACTOR SHALL PROVIDE A MINIMUM OF TWO (2) HOURS OF TRAINING AS NECESSARY TO THE OWNER ON THE LIGHTING CONTROLS, AND ALL OTHER ELECTRICAL EQUIPMENT AND/OR DEVICES. 7. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL OPERATING AND MAINTENANCE INSTRUCTION MANUALS, CERTIFICATES OF INSPECTION, TEST REPORTS, SPARE PARTS, AND RECORD DRAWINGS (AS-BUILTS) TO THE OWNER PRIOR TO CLOSEOUT. FINAL PAYMENT WILL ONLY BE MADE AFTER THE FINAL PUNCH LIST COMPLETION AND RECEIPT OF THE ABOVE CLOSEOUT DOCUMENTATION. 8. 9. ELECTRICAL CONTRACTOR SHALL COORDINATE LOCATIONS OF HIS EQUIPMENT AND WORK WITH OTHER BUILDING TRADES TO AVOID ANY INTERFERENCES BETWEEN HIS WORK AND THE WORK OF OTHER BUILDING TRADES. IF ANY DISCREPANCIES OCCUR, CONSULT WITH THE ARCHITECT, ENGINEER AND/OR OWNER BEFORE CONTINUING. THE CONTRACTOR SHALL BE HELD FULLY RESPONSIBLE FOR THE PROPER RESTORATION OF ALL EXISTING SURFACES REQUIRING PATCHING, PLASTERING, PAINTING AND/OR REPAIR DUE TO THE INSTALLATION OF ELECTRICAL WORK UNDER THE TERMS OF THIS SPECIFICATION. CLOSE ALL OPENINGS, REPAIR ALL SURFACES, ETC. AS REQUIRED. 10. CUTTING AND/OR PATCHING THAT MAY BE REQUIRED FOR THE INSTALLATION OF THE ELECTRICAL SYSTEM(S) SHALL BE DONE AND/OR REPAIRED BY THE ELECTRICAL CONTRACTOR. NO CUTTING OF THE BUILDING STRUCTURAL SYSTEM SHALL BE DONE WITHOUT THE WRITTEN CONSENT OF THE ARCHITECT. 11. THE ELECTRICAL CONTRACTOR SHALL PERIODICALLY REMOVE FROM THE SITE ALL DEBRIS AND RUBBISH ACCUMULATING AS A RESULT OF THE ELECTRICAL INSTALLATION. UPON COMPLETION OF THE PROJECT, HE SHALL DISPOSE OF ALL DEBRIS AND RUBBISH AND SHALL LEAVE ALL AREAS CLEAN. THE INTERIORS OF ALL CABINETS, PULL BOXES, AND EQUIPMENT ENCLOSURES SHALL BE FREE OF ANY DEBRIS. 12. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND SHALL WORK WITH EXISTING SYSTEMS IN AN "AS FOUND" CONDITION. 13. DRAWINGS ARE DIAGRAMMATIC ONLY AND SHOW OBSERVATIONS FROM CASUAL FIELD INVESTIGATIONS AND EXISTING DRAWINGS. FIELD VERIFY ALL EXISTING CONDITIONS, DIMENSIONS AND MOUNTING LOCATIONS. NOTIFY ENGINEER IF ANY DISCREPANCIES ARE FOUND THAT AFFECT THE WORK TO BE PERFORMED, PRIOR TO PROCEEDING. 14. ELECTRICAL JOINTS WILL BE PERMITTED ONLY IN JUNCTION AND OUTLET BOXES. ALL JOINTS SHALL BE FIRMLY BONDED TOGETHER AND TAPED OR SHALL BE MADE WITH MECHANICAL CONNECTORS. 17. OR "THWN-2" AND INSTALLED IN EMT, FOR INDOOR USE, AND SCHEDULE 40 PVC OR RMC FOR OUTDOOR USE, MINIMUM SIZE 1/2", OR "MC" OR "AC" CABLE (10 FT. MAXIMUM UNLESS OTHERWISE APPROVED BY THE ARCHITECT,/ENGINEER/OWNER), UNLESS OTHERWISE NOTED OR REQUIRED BY CODE. INTERIOR MOTOR CONNECTIONS SHALL BE TYPE "MC" OR "AC" CABLE OR LIQUID TITE FLEXIBLE CONDUIT (BOTH WITH A 6FT. MAXIMUM LENGTH). ALL WIRE AND CABLE SHALL BE NEW AND SHALL BE DELIVERED TO PROJECT IN UNBROKEN AND UNDAMAGED CARTONS AND/OR REELS. 18. FUSES SHALL BE "UL" LISTED, DUAL-ELEMENT AS MANUFACTURED BY BUSSMAN CO., OR APPROVED EQUAL (200,000 AIC). 19. SWITCHES SHALL BE RATED 20A, 120/277V, COMMERCIAL SPECIFICATION GRADE, SINGLE, DOUBLE-POLE, THREE-WAY, ETC. AS INDICATED, AND EQUAL TO HUBBELL, GE, LEVITON, COOPER, ARROW-HART OR P&S. 20. RECEPTACLES SHALL BE RATED 20A, 125AMP, COMMERCIAL GRADE GROUNDED TYPE (NEMA 5-20R), EQUAL TO HUBBELL, GE, LEVITON, COOPER, ARROW-HART OR P&S. 21. PLATES FOR SWITCHES AND RECEPTACLES SHALL BE PLASTIC OR SIMILAR. COORDINATE ALL FINISH COLORS WITH OWNER/ARCHITECT TO MATCH ASSOCIATED DEVICES. 22. THE AUTOMATIC OCCUPANCY SENSORS SHALL BE FIELD ORIENTATED TO MAXIMIZE SENSING COVERAGE. E.C. SHALL ADJUST AUTOMATIC OFF DELAY SETTINGS PER THE OWNERS SPECIFICATIONS. E.C. SHALL TRAIN THE OWNER ON HOW TO ADJUST THE DELAY SETTINGS. OCCUPANCY SENSORS SHALL BE AS SPECIFIED BY COOPER OR EQUAL BY LEVITON, HBA, SENSOR SWITCH, OR WATTSTOPPER 23. FLUORESCENT FIXTURE BALLAST VOLTAGE RATING SHALL BE AS NOTED, NON-PCB, HIGH POWER FACTOR, ENERGY SAVING, CLASS P, "A" SOUND RATED, PROGRAM RAPID START MINIMUM 100,000 CYCLES. 24. LAMPS - ALL LAMPS SHALL BE CLASSIFIED "ENERGY SAVING". PROVIDE A MINIMUM OF 3% OR TWO (2), WHICHEVER IS GREATER, SPARE OF EACH TYPE OF LAMP TO THE OWNER AT PROJECT CLOSEOUT. LAMPS 25. INTEGRAL EMERGENCY BATTERIES AND REMOTE EMERGENCY MINI-INVERTERS SHALL PROVIDE A MINIMUM OF 90 MINUTES OF RUN-TIME FOR LAMPS AS SHOWN. BY COOPER, LVS, IOTA, BODINE, OR SIMILAR. 26. ALL LIGHT FIXTURES HAVE BEEN SELECTED BY THE ARCHITECT/ENGINEER FOR THE BASIS OF DESIGN AND APPEARANCE. SUBMIT ALL PROPOSED VOLUNTARY ALTERNATE LIGHT FIXTURES A MINIMUM OF TEN (10) WORKING DAYS PRIOR TO BIDS BEING DUE. 27. PROJECT HAS BEEN DESIGNED TO COMPLY WITH AUTOMATIC LIGHTING SHUTOFF REQUIREMENTS OF ADOPTED ENERGY CODE (ASHRAE 90.1-2007). INTERIOR AND EXTERIOR LIGHTING COMPLIANCE DOCUMENTATION CAN BE PROVIDED BY THE ENGINEER UPON REQUEST. 30. FEEDER AND BRANCH CIRCUIT BREAKERS SHALL BE COMPATIBLE (VOLTAGE, AIC RATING, MANUFACTURER, ETC.) WITH THE EXISTING PANELBOARDS THAT THEY ARE MOUNTED IN. 31. FIRE CAULKING REQUIRED WHERE ANY PENETRATIONS ARE MADE THROUGH FIRE RATED WALLS, BY. E.C. 32. PROVIDE AN UPDATED, ACCURATE AND TYPED PANEL SCHEDULE FOR ALL NEW AND EXISTING ELECTRICAL PANELS THAT ARE AFFECTED BY THE WORK IN THIS PROJECT. DOCUMENT ALL CHANGES ON FINAL AS-BUILT DRAWINGS AS REQUIRED. VERIFY ALL EXISTING LOADS AND WIRING - NOTIFY THE ARCHTIECT/ENGINEER IF EXISTING CONDITIONS ARE FOUND THAT VIOLATE INSTALLATION OR SAFETY CODES. 33. ALL NEW EQUIPMENT (DISCONNECTS, VARIABLE FREQUENCY DRIVES (VFD), ETC.) SHALL BE IDENTIFIED WITH TYPED LABELS. 34. UNDERGROUND CONDUIT TO BE SCHEDULE 40 PVC, UNLESS OTHERWISE REQUIRED BY CODE. 35. ELECTRICAL CONTRACTOR SHALL VERIFY EXACT ELECTRIC UTILITY COMPANIES SERVICE POINTS AND PRIMARY SERVICE CONDUIT, ROUTING, AND SIZE WITH UTILITY COMPANY SERVICE PANNERS/ENGINEERS PRIOR TO BEGINNING WORK. 36. THE ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL A BOX AND RACEWAY SYSTEM FOR THE LOW-VOLTAGE CABLING SYSTEMS (TELEPHONE, DATA, TELEVISION, SOUND, ETC.) THAT ARE BEING PROVIDED BY THE OWNER. THESE DRAWINGS ARE DIAGRAMMATICAL AND THE LOCATIONS AND REQUIREMENTS SHALL BE COORDINATED WITH THE OWNER/OWNER'S CONTRACTORS IN THE FIELD. PROVIDE AND INSTALL RACEWAY SLEEVES THRU FLOORS, FIRE WALLS, AND NON-ACCESSIBLE CEILINGS AS REQUIRED. 37. ALL NEW BRANCH WIRING SHALL BE COLOR CODED BY THE FOLLOWING VOLTAGE SYSTEMS AND LABELED AT THEIR SOURCE PER 2011 NEC SECTION #210.5: NEUTRAL - WHITE E.G.C. - GREEN 38. EXISTING ELECTRICAL WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO OPERATING CONDITION AS REQUIRED AND/OR DIRECTED. WHERE REQUIRED, SHOWN, AND/OR DIRECTED, OUTLETS AND CONDUIT RUNS SHALL BE RELOCATED. IN SOME CASES IT MAY BE NECESSARY TO EXTEND CONDUITS AND PULL IN NEW WIRING, INSTALL JUNCTION BOXES, AND SPLICE IN NEW WIRING, OR REPLACE OLD WIRING WITH NEW. 39. WHERE EXISTING WIRE, CONDUIT, AND OUTLET BOXES ARE NO LONGER USED, REMOVE EXISTING WIRE BACK THE POWER SOURCE AND PROVIDE BLANK COVER PLATES ON EMPTY GANG BOXES. ALL EXPOSED CONDUIT AND SURFACE MOUNTED RACEWAY THAT HAS BEEN ABANDONED SHALL BE REMOVED. WHERE IT IS IMPOSSIBLE TO REMOVE, THE CONDUIT SHALL SHALL BE CUT OFF AND CAPPED/PLUGGED. 40. COORDINATE WITH THE OWNER AND THE UTILITY COMPANY TO APPLY FOR AVAILABLE ENERGY INCENTIVES OFFERED BY THE UTILITY. 41. ELECTRICAL CONTRACTOR SHALL SUBMIT SEPARATE LINE ITEM PRICING ON ALL BID ALTERNATES AS DESCRIBED ON THE DRAWINGS AND IN THE SPECIFICATIONS. REFERENCE THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR MORE DETAILS AND LIST OF ADD ALTERNATES. ARCHITECT OF RECORD: D. DeKryger DRAWN BY: B. Reinhardt DATE ISSUED: July 31, 2015 Construction Drawings 28. DISCONNECT SWITCHES SHALL BE RATED 250V, OR 600V, FUSED OR NON-FUSED AS NOTED, HEAVY-DUTY, NEMA-1, FOR INDOOR USE, AND NEMA-3R FOR OUTDOOR USE BY SQUARE D OR SIMILAR. 29. SINGLE PHASE MOTOR STARTERS SHALL HAVE MANUAL TOGGLE SWITCH WITH THERMAL OVERLOADS AND PILOT LIGHT, SURFACE OR FLUSH MOUNTED AS NOTED BY SQUARE D CLASS 2510 OR SIMILAR. SHEET NUMBER: E2.0 PROJECT NUMBER: 15121