Power supply unit type MNG 2,5-230/24 and MNG 5-230/24 generating a supply voltage of 24 VDC from mains 230 VAC 1. General information The power supply units type MNG generate a supply voltage of 24 VDC from mains 230 VAC for solenoid actuated hydraulic valves or electronic amplifiers connected to proportional solenoids. A safety transformer conforming EN 60 742 (DIN VDE 0551) supplies a smoothed DC voltage with either max. 2,5 or 5 A. The load curve (I-U) conforms the standard DIN 19 240. The power supply units feature - CE approval - UL and CSA approval - SEE (Luxembourg) approval - Protection against electric shock conforming VBG 4 - Fulfill the German Standard DIN VDE 0106 T 101 (save separation) 1.1. Circuitry Inlet 4 A slow blow / (10 A slow blow) Outlet (Figures in brackets apply to MNG 5-230/24) 2. Available versions, order coding 2.1. Type coding MNG .. - 230/ 24 Modular power supply unit Primary/ secondary nominal voltage Max. load current 2,5 = 2.5 A 5=5A 2.2. Technical data 2.2.1. General parameter Nomenclature Power supply unit for smoothed direct current supply Version Compact design, connection via solderless lugs Connection leads 4 mm2 max Fastening Via snap-on foot fastening (scope of delivery) on 35 mm carrier rails conforming EN 50 022 or via screws at key shaped or oblong holes Installed position Any, up to 80% load Hanging on vertical mounting area, when fully loaded Mass (weight) 1.7 kg (MNG 2,5-230/24) 3 kg (MNG 5-230/24) Protection class DIN VDE 0470 EN 60529 and C.E.I. 529 IP 20 Ambient temperature -20° ... +55°C HAWE HYDRAULIK SE STREITFELDSTR. 25 • 81673 MÜNCHEN © 1995 by HAWE Hydraulik D 7835 Power supply unit July 2001-01 5 D 7835 page 2 2.2.2. Electrical parameters MNG 2,5-230/24 Supply voltage UB Frequency Nom. supply voltage (load 50% and mains 230 VAC) Max. ripple factor f w Installed smoothing capacitor Max. supply current C IA Secondary side fuse (DIN 72581) Recommended primary side fuse Test voltage connected between primary and secondary coil 4700 µF 2,5 A 2x4700 µF 5A 4A 0,5 A U time-laged time-laged 10 A 1A conf. VDE 0551, EN 60742 and IEC 742 (Safety transformer) I E 181 433(N) L 9541198-01 Safety class UL and CSA approval certificate No. SEE approval certificate No. 2.2.3. MNG 5-230/24 230 VDC (±10%) tappings for +5 and -5% are provided 50 - 60 Hz 24 VDC (The limits of DIN 19240 are maintained) 5% (residual ripple) Limits for 24 V power supplies conforming DIN 19240 / IEC 38 "Periphery interfaces of electronic controls / power supply and binary interfaces" Ripple factor (ripple) w ≤ 5% at max. load secondary side IA Upper limits for DC-voltage (for mains supply +6% and no load on the secondary side): Upper peak figure U ≤ 30,2 VS Calculated average figure 1) UB 28,8 V Lower limits for DC-voltage (for mains supply -10% and full load on the secondary side): Calculated average figure UB 20,4 V Lower peak figure U ≥ 18,8 VS 1) 3. The calculated average figure may rise up to the peak figure, when connected to a capacitor Unit dimensions Nom. voltage, nom. current, nom. frequency, standards, and approval labels are printed here Mounting holes All dimensions in mm, subject to change without notice ! Illustration: Hanging on vertical mounting area (preferred installation) A snap-on foot fastening is scope of delivery, suited for 35 mm carrier rails conforming EN 50 022. MN25-230/24 MN 5-230/24 4. A 53,3 75,5 B 56 84 C 4,5 5,5 D 80 92 E 115 132 F 78 96 G 9,5 11,5 Notes for installation The power supply unit should be safeguarded against short-cuts on the primary side (recom. Fuse, see 2.2.2.). This safeguard must be certified as well for all applications, where UL or CSA standards do apply. The GND-terminal of the secondary coil may be connected to the protective terminal acc. to DIN VDE 0113 and DIN EN 60204. Observe information on installed position and max. in sect. 2.2.1 !