Power supply unit type MNG: D 7835

advertisement
Power supply unit type MNG 2,5-230/24 and MNG 5-230/24
generating a supply voltage of 24 VDC from mains 230 VAC
1.
General information
The power supply units type MNG generate a supply voltage of 24
VDC from mains 230 VAC for solenoid actuated hydraulic valves or
electronic amplifiers connected to proportional solenoids. A safety
transformer conforming EN 60 742 (DIN VDE 0551) supplies a
smoothed DC voltage with either max. 2,5 or 5 A. The load curve (I-U)
conforms the standard DIN 19 240.
The power supply units feature
- CE approval
- UL and CSA approval
- SEE (Luxembourg) approval
- Protection against electric shock conforming VBG 4
- Fulfill the German Standard DIN VDE 0106 T 101 (save separation)
1.1.
Circuitry
Inlet
4 A slow blow /
(10 A slow blow)
Outlet
(Figures in brackets apply to MNG 5-230/24)
2.
Available versions, order coding
2.1.
Type coding
MNG .. - 230/ 24
Modular power supply unit
Primary/ secondary
nominal voltage
Max. load current
2,5 = 2.5 A
5=5A
2.2.
Technical data
2.2.1.
General parameter
Nomenclature
Power supply unit for smoothed direct current supply
Version
Compact design, connection via solderless lugs
Connection leads
4 mm2 max
Fastening
Via snap-on foot fastening (scope of delivery) on 35 mm
carrier rails conforming EN 50 022 or via screws at
key shaped or oblong holes
Installed position
Any, up to 80% load
Hanging on vertical mounting area, when fully loaded
Mass (weight)
1.7 kg (MNG 2,5-230/24)
3 kg (MNG 5-230/24)
Protection class DIN VDE 0470
EN 60529 and C.E.I. 529
IP 20
Ambient temperature
-20° ... +55°C
HAWE HYDRAULIK SE
STREITFELDSTR. 25 • 81673 MÜNCHEN
© 1995 by HAWE Hydraulik
D 7835
Power supply unit
July 2001-01
5
D 7835 page 2
2.2.2.
Electrical parameters
MNG 2,5-230/24
Supply voltage
UB
Frequency
Nom. supply voltage
(load 50% and mains 230 VAC)
Max. ripple factor
f
w
Installed smoothing capacitor
Max. supply current
C
IA
Secondary side fuse (DIN 72581)
Recommended primary side fuse
Test voltage connected between
primary and secondary coil
4700 µF
2,5 A
2x4700 µF
5A
4A
0,5 A
U
time-laged
time-laged
10 A
1A
conf. VDE 0551, EN 60742 and IEC 742
(Safety transformer)
I
E 181 433(N)
L 9541198-01
Safety class
UL and CSA approval certificate No.
SEE approval certificate No.
2.2.3.
MNG 5-230/24
230 VDC (±10%)
tappings for +5 and -5% are provided
50 - 60 Hz
24 VDC
(The limits of DIN 19240 are maintained)
5% (residual ripple)
Limits for 24 V power supplies conforming DIN 19240 / IEC 38
"Periphery interfaces of electronic controls / power supply and binary interfaces"
Ripple factor (ripple)
w
≤ 5% at max. load secondary side IA
Upper limits for DC-voltage (for mains supply +6% and no load on the secondary side):
Upper peak figure
U
≤ 30,2 VS
Calculated average figure 1)
UB
28,8 V
Lower limits for DC-voltage (for mains supply -10% and full load on the secondary side):
Calculated average figure
UB
20,4 V
Lower peak figure
U
≥ 18,8 VS
1)
3.
The calculated average figure may rise up to the peak figure, when connected to a capacitor
Unit dimensions
Nom. voltage, nom. current,
nom. frequency, standards, and
approval labels are printed here
Mounting holes
All dimensions in mm, subject to change without notice !
Illustration: Hanging on vertical mounting area (preferred installation)
A snap-on foot fastening is scope of delivery, suited for 35 mm carrier rails conforming EN 50 022.
MN25-230/24
MN 5-230/24
4.
A
53,3
75,5
B
56
84
C
4,5
5,5
D
80
92
E
115
132
F
78
96
G
9,5
11,5
Notes for installation
The power supply unit should be safeguarded against short-cuts on the primary side (recom. Fuse, see 2.2.2.). This safeguard must
be certified as well for all applications, where UL or CSA standards do apply. The GND-terminal of the secondary coil may be
connected to the protective terminal acc. to DIN VDE 0113 and DIN EN 60204. Observe information on installed position and max. in
sect. 2.2.1 !