POWER-ZONE® III Series 2 Low Voltage Metal-Enclosed Drawout Switchgear Class 6035 CONTENTS Description Page Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Application and General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Technical Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Suggested Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Product Description General POWER-ZONE® III Series 2, low voltage metal-enclosed drawout switchgear is premium distribution equipment designed to offer the user many operational security features: minimum down-time, system selectivity, ease of maintenance, and large functional capacity. The Types DSII (not fusible) and DSLII (fused) low voltage power circuit breakers are the primary components of POWER-ZONE III switchgear. These circuit breakers employ a solid state tripping device offering the latest in circuit protection. Functional and operational advantages are: Operational Security Features – Compartmentalized and barriered construction per ANSI C37.20.1. Dual steel-front barriers: one as the full cell door covering the circuit breaker manual operation controls and one as the front of the circuit breaker element covering the circuit breaker mechanism. Minimum Down-Time – Drawout construction allows quick and simple replacement of breaker elements. If an emergency occurs, breakers may be removed from low-priority circuits and re-installed to serve high-priority circuits. Ease of Maintenance – Circuit breakers are simple to inspect, adjust, and replace. They can be withdrawn from their compartments for convenient maintenance or inspection. Functional Capacity – Large frame sizes and high withstand rating make the DSII and DSLII low voltage circuit breakers ideal for application on today’s high capacity distribution systems. System Selectivity – The solid state trip devices provided on each DSII and DSLII low voltage power breaker are field adjustable, enabling the user to attain optimum selectivity and coordination. UL® Listing – POWER-ZONE III Series 2 switchgear can be designed and engineered to comply with UL requirements. As an option, DSII and DSLII power circuit breakers are available with a UL listing. Where UL coverage exists for all component material, parts and devices in a switchgear section, a UL label can be affixed. For Additional Information – POWER-ZONE III Series 2 switchgear is described in general but brief terms here. More detailed and comprehensive data is also available from your local Square D sales office. 1 11/98 © 1998 Square D All Rights Reserved Application and General Information Ratings: Main Bus – 5000 A maximum 120/208 to 600 Vac, 1∅3W, or 3∅4W. Available Breakers: DSII, DSLII-308, DSII-508, DSII-608 DSII, DSLII-516, DSII-616 DSII-620 DSII, DSLII-632 DSII, DSLII-840 DSII-850 (Forced air cooled) 800 A Frame 1600 A Frame 2000 A Frame 3200 A Frame 4000 A Frame 5000 A Frame Applicable Standards: Circuit Breakers: Structures: NEMA SG3 ANSI C37.13 ANSI C37.16 UL 1066 (Optional) NEMA SG5 ANSI C37.20.1 ANSI C37.51 UL 1558 (Optional) Features: • • • • • • Totally enclosed, dead front, free standing Front and rear alignment Covers installed with single tool, slotted hex-head screws Removable top plate, rear panel, and side panel Corrosion-resistant finish Single or multiple mains — — — — — Individually mounted drawout circuit breakers ANSI-rated low voltage power circuit breaker Front accessible, rear connected 100% rated, two-step stored energy circuit breakers 800–5000 A frame • Feeders — — — — — • • • • • • • • • Individually mounted drawout circuit breakers ANSI-rated low voltage power circuit breaker Front accessible, rear connected 100% rated, two-step stored energy circuit breakers 800–4000 A frame Structures are compartmentalized and barriered per ANSI C37.20.1 Provision for future extension Increased mounting space within main and feeder sections Bolted copper bus provided as standard up to 5000 A maximum Dual steel-front barriers – the compartment door and the circuit breaker front panel Ground bus with lugs Shipment as separate switchgear section or up to a maximum of four sections Removable lifting straps Interrupting rating – 30 kA to 85 kA at 480 Vac (200 kA, when fused) 2 © 1998 Square D All Rights Reserved 11/98 Application and General Information Indoor Enclosures Compartmentalized construction: POWER-ZONE III Series 2 low voltage drawout switchgear offers high reliability through compartmentalized construction. The three compartments are: • Circuit breaker or instrument compartment. • Bus compartment. • Cable compartment. Isolation between the bus and cable compartments and/or between adjacent bays is available through optional vertical barriers. NOTE: If incoming conductors are considered to be “Service Conductors,” then barriers as outlined in National Electrical Code® (NEC), Article 384-3 must be specified. The optional neutral bus is located on the innermost portion of the cable compartment, thereby allowing easy access to line and load connectors. Bus Riser Instrument or Circuit Breaker Compartment Bus Compartment N (Optional) Circuit Breaker Compartments A∅ Cable Compartment B∅ C∅ 6035-98140 Figure 1: Side View Illustration of Typical Switchgear Outdoor Enclosures POWER-ZONE III switchgear is available in a walk-in POWER ZONE® center enclosure for outdoor installation. A non-walk-in enclosure is also available. Both enclosures are NEMA Type 3R as standard. Non-walk-in enclosures are equipped with: • • • • • Strip heaters in breaker cells and bus compartment Front and rear lockable equipment doors with three point latching and filtered openings for ventilation Removable gasketed steel cover plates over conduit entrance One-piece construction for ease of installation Options Available: — — — — Mobile floor crane to handle breaker Top entry/exit for incoming and outgoing cables Capability for future expansion Interior and exterior lighting and convenience outlets 3 11/98 © 1998 Square D All Rights Reserved Application and General Information 6052-88200A Figure 2: POWER ZONE™ Center – Walk-In Enclosure The POWER ZONE center–walk-in enclosure is equipped with the following standard features: • • • • • • • • • Front aisle with steel entrance door equipped with panic hardware Lockable rear equipment doors hinged with 3-point latching and filtered openings for air intake Interior fluorescent lighting Three-way light switch and convenience outlets located near the entrance door Strip heaters in breaker cells and bus compartment Overhead breaker lifting device (Traveling Lifter Assembly) Removable gasketed steel cover plates over conduit entrance One-piece construction for ease of installation Options available: — — — — — — — — Extended aisle for additional work space Exhaust fan ventilation/Inside temperature control Exterior lighting Inside emergency lighting Wall-mounted ac distribution panel Top entry/exit for incoming and outgoing cables Capability for future expansion Modified NEMA Types: NEMA Type 4 and NEMA Type 4X NEMA Type 7 and NEMA Type 9 for use in hazardous areas 4 © 1998 Square D All Rights Reserved 11/98 Application and General Information POWER-ZONE III Series 2 switchgear uses the Type DSII low-voltage power circuit breaker. This circuit breaker is available in six basic frame sizes that are tabulated along with their respective interrupting capacities on page 14. The breaker overcurrent protection consists of a solid-state, microprocessor-based trip device that requires no external power source. The complete tripping system has three basic components: the molded sensors, the trip device (with rating plug), and the trip actuator. The microprocessor-based trip unit uses RMS current level sensing. Each pole of the circuit breaker is equipped with a molded sensor located on the bottom rear main disconnect contacts. These sensors produce an output proportional to the load current. The output is fed into the trip device, which has the intelligence and energy to operate the trip actuator when required. The trip actuator receives the tripping pulse (from the microprocessor-based trip unit) and mechanically trips the circuit breaker. Type DSII circuit breakers are equipped with the controls (see Figure 4 on page 6). All circuit breakers are fully stored energy devices with a two-step operating mechanism. A spring charging handle charges the mechanism and the circuit breaker contacts are closed by pushing the “Push To Close” button, which is located on the face of the circuit breaker. Electrically operated circuit breakers have a motor to charge the stored energy mechanism, electric close feature, and electric open feature. (Optional) POWERLOGIC® DIGITRIP® RMS 810D RMS Sensing with current and energy displays Values PowerLogic DIGITAL PROTECTION Digitrip RMS 810D D86LSIGA kA Demand IA Peak-MW IB Present-MW IC Energy-MWh Reset Step IG Long Delay Setting (Ir) 1.0 x In = Ir Long Delay Time 24 Sec. At 6 x Ir Digitrip RMS Rating Plug For Use in DS Breakers Only Cat. Must Use With Sensor Rated In (Rated I) = Hz Only Rating plug S1-8 S2-10 M1-8 M2-12 Battery Check Hinge Down to Replace Battery Short Delay Setting 2 x Ir Molded sensor Gnd. Fault Setting K x In Breaker Trips At 6T & GFT Test Amps 6T In Short Delay Time .3 Sec. 2 *=I t Trip actuator Test Gnd. Fault Time .3 Sec. Inst. Setting 2 x In Trip Reset Unit Status Gnd. Inst. NP7829C14H41 6035-98142 Figure 3: Tripping System 5 11/98 © 1998 Square D All Rights Reserved Application and General Information DIGITRIP Microprocessor-Based Trip Device (optional POWERLOGIC 810DTrip Unit illustrated) Nameplate Access shutter to hex shaft (for breaker removal) Spring charging handle Drawout unit position indicator Operations counter (optional) Open-Close indicator Padlock plate Trip plate Close bar Overcurrent trip switch reset (optional) Spring charge indicator 6035-9818 Figure 4: Standard DSII Circuit Breaker DSII circuit breakers are manufactured to Square D company specifications and are fully warranted and backed by Square D, its sales and technical service personnel. NOTE: Square D DSII and DSLII circuit breakers are NOT interchangeable with Cutler-Hammer DSII and DSLII circuit breakers. 6 © 1998 Square D All Rights Reserved 11/98 Application and General Information DIGITRIP® RMS 510 (Standard trip unit) NOTE: Detailed information on features and operations on the DIGITRIP RMS 510, 610 and POWERLOGIC® 810D trip units can be found in Instruction Bulletin 6035-510 DIGITRIP RMS Trip Units. Standard trip features include: • • • • • • RMS sensing Integral trip unit testing Unit status indicator Adjustable long delay and ampere setting Local mode of trip indicators Rating plug Optional features include: • • • • Adjustable short time delay and pickup Adjustable ground fault delay and pickup Selectable I2t on short time and ground fault Zone selective interlocking (only with other DSII breakers equipped with DIGITRIP trip units.) DIGITRIP RMS 610 and the POWERLOGIC DIGITRIP RMS 810D are optional. DIGITRIP RMS 610 (Optional) Standard trip features include: • All features of the RMS 510 • Local four-digit alphanumeric display — Amperes — Mode of trip — Service trip messages • Local hi-load indication • Remote signal contacts for hi-load and mode of trip (via the auxiliary trip relay-ATR) POWERLOGIC DIGITRIP RMS 810D (Optional) Standard trip features include: • All features of the RMS 510 and RMS 610 • Energy and power monitoring — — — — — — — Peak demand➀ Present demand➀ Energy consumption➀ Amperes Energy and demand information Remote breaker operation Service and trip messages • Direct communications link to the Square D POWERLOGIC Power Monitoring and Control System ➀ Energy and demand are calculated in conjunction with a built-in potential transformer module. 7 11/98 © 1998 Square D All Rights Reserved Application and General Information POWER-ZONE III Series 2 low voltage drawout switchgear is available with the Square D POWERLOGIC circuit monitoring metering, data acquisition, and control system. Basic circuit information, such as amperes and energy consumption, as well as circuit breaker remote operation, can be accomplished using the POWERLOGIC DIGITRIP 810D trip unit. For more sophisticated metering, power quality monitoring, data acquisition, and control, POWERLOGIC circuit monitors should also be considered. POWERLOGIC circuit monitors replace a variety of discrete meters, transducers, and other components. POWERLOGIC circuit monitors perform these functions: • • • • • • • • • • • 6035-98143 Figure 5: POWER-ZONE III Series 2 LV Drawout Switchgear with POWERLOGIC Circuit Monitors Meters Amperes, Volts Frequency Watts Thermal Demand Vars Watthour with Demand Kilovolt-ampere Varhours Power Factor Waveform capture Records data Industry standard RS-485 data communications allow the POWERLOGIC system to replace multiple transducers, analog wires, and analog-to-digital conversion equipment. Extensive information can be transmitted over a single communications cable to a POWERLOGIC system display, a personal computer, programmable logic controller, or other host system. In addition to its metering capabilities, the POWERLOGIC system is available with optional status inputs and relay outputs for monitoring discrete contacts and remote control of devices via the data communications channel. A POWERLOGIC circuit monitor, equipped with a “waveform capture” function, offers a highly accurate class of circuit information, not presently available on the built in trip unit devices. Comprehensive profiles of current and voltage waveforms, suitable for harmonics studies and other power quality analyses, are reported on user-command. For additional information regarding POWERLOGIC systems consult your local Square D sales office. 8 © 1998 Square D All Rights Reserved 11/98 Application and General Information The main disconnecting contacts on the rear of the circuit breaker are spring loaded and self-aligning to ensure positive electrical contact when the circuit breaker is in the connected position. These contacts are designed so the pressure at the point of contact on the stationary stud becomes greater under short circuit conditions. The secondary disconnecting contacts are also located on the rear of the circuit breaker element and are used for connecting the accessories to the control power source or other control circuits. These contacts are in the “make” position when the element is in the “Connected” and “Test” positions. See photo below. Interphase barriers Secondary disconnecting contacts Levering Arm Main disconnecting contacts 6035-9815 Figure 6: Rear View of DSII Circuit Breaker Element Circuit breakers of like frame sizes and interrupting ratings are interchangeable as standard. 9 11/98 © 1998 Square D All Rights Reserved Application and General Information POWER-ZONE III Switchgear is also available with fused power circuit breakers. Fused circuit breakers have a short circuit interrupting fusing of 200,000 A symmetrical. The circuit breaker element, including the microprocessor-based tripping system, is identical to that of a non-fusible circuit breaker except for the addition of the fuses and other circuitry necessary for the proper functioning of the fuse protection system. Current limiting fuses are available on the 800 A, 1600 A, 3200 A, and 4000 A frame power circuit breakers. The current limiting fuses are mounted integrally on the rear of the circuit breaker element for the 800 A and 1600 A frame sizes and are mounted on a separate drawout truck for the 3200 A and 4000 A frame sizes. When fuses are mounted on a separate fuse truck, the drawout mechanisms are mechanically key interlocked with the circuit breaker element. The Square D 3200 A and 4000 A fused circuit breaker design permits mounting both the fuse drawout truck and circuit breaker element in the same vertical section (see Figure 7.) All versions of the fused circuit breaker are equipped with blown fuse indication and anti-single phasing as standard. Fused circuit breakers of like frame sizes are interchangeable as standard. 6035-9801 Figure 7: Two Bay POWER-ZONE III Series 2 Switchgear with DSLII 840 Shown with Optional Lifter Assembly 10 © 1998 Square D All Rights Reserved 11/98 Application and General Information Blown fuse indicators (standard) 6035-9816 Figure 8: Front View of DSLII Circuit Breaker Fuses 6035-98123 Figure 9: Rear View of DSLII Circuit Breaker Equipped with Integral Current Limiting Fuses 11 11/98 © 1998 Square D All Rights Reserved Application and General Information Test and Maintenance Option All Type DSII and DSLII power circuit breakers equipped with microprocessor-based trip devices have a built-in test feature, as well as plug-in type test facilities that enable the user to test all tripping functions. The DSII circuit breaker test cart provides mobility for moving circuit breakers to the test area, a convenient height for visual inspection of circuit breakers, contacts for testing all secondary control functions, means for verification of mechanical operation, and a test equipment shelf for mounting the test kit. Secondary Control Contacts Stationary Contacts - Line Side Stationary Contacts - Load Side Circuit Breaker Cradle Electrical Operation Control Panel Storage Shelf for Test Equipment 6035-8726 Figure 10: Test Cart 12 © 1998 Square D All Rights Reserved 11/98 Application and General Information Miscellaneous Circuit Breaker Options and Accessories • DIGITRIP 610 and POWERLOGIC 810D trip units • Shunt trip for manually operated circuit breakers • Auxiliary switch with four 10 A contacts. A maximum of ten 10 A contacts can be supplied per circuit breaker. • Cell switch with 6 Form “A” and 6 Form “B”. Operates when circuit breaker is drawn from connected to test position. • Undervoltage trip–instantaneous or time delay type. Trips the circuit breaker on 30-60% undervoltage. • Overcurrent trip switch operates and latches when circuit breaker is automatically tripped on overload or fault conditions. • Electric lockout for manually operated circuit breakers • Electric close release for manually operated circuit breakers • Key interlocks • Operations counter • AC capacitor trip • Integral ground fault sensing • Insulated switchgear bussing • UL Label A rail-mounted traveling type circuit breaker lifting device is optionally available with indoor type switchgear. It is supplied as standard with outdoor walk-in enclosures. 6035-98134a Figure 11: Circuit Breaker Lifting Device 13 11/98 © 1998 Square D All Rights Reserved Technical Overview Ratings 6035-98135 Interrupting Ratings of Type DSII Circuit Breaker (RMS Symmetrical Amperes) Trip Current Range Circuit Breaker Type With Instantaneous Trip 50-800 50-800 50-800 50-1600 50-1600 50-2000 800-3200 1000-4000 1600-5000 DSII-308 DSII-508 DSII-608 DSII-516 DSII-616 DSII-620 DSII-632 DSII-840 DSII-850➀ 50-800 50-1600 800-3200 1000-4000 DSLII-308 DSLII-516 DSLII-632 DSLII-840 With Short Delay Trip 208-240V 480V 600V 208-240V 480V 600V 42,000 65,000 65,000 65,000 65,000 65,000 85,000 130,000 130,000 30,000 50,000 65,000 50,000 65,000 65,000 65,000 85,000 85,000 30,000 42,000 50,000 42,000 50,000 50,000 65,000 85,000 85,000 30,000 50,000 65,000 50,000 65,000 65,000 65,000 85,000 85,000 30,000 50,000 65,000 50,000 65,000 65,000 65,000 85,000 85,000 30,000 42,000 50,000 42,000 50,000 50,000 65,000 85,000 85,000 All Ranges: 200,000 Available Sensors Available Rating Plugs Circuit Breaker Type Sensor Rating (Amperes) DSII-308, DSLII-308, DSII-508, DSII-608 DSII-516, DSLII-516, DSII-616 Sensor Rating Amperes Plug Rating in Amperes 200, 300, 400, 600, 800 200 100, 200 200, 300, 400, 600, 800, 1200, 1600 300 200, 250, 300 DSII-620 200, 300, 400, 600, 800, 1200, 1600, 2000 400 200, 250, 300, 400 DSII-632 2400, 3200 600 300, 400, 600 DSII-840 4000 800 400, 600, 800 DSII-850➀ 5000 1200 600, 800, 1000, 1200 ➀ DSII-850 - Forced air cooled. 1600 800, 1000, 1200, 1600 2000 1000, 1200, 1600, 2000 2400 1600, 2000, 2400 3200 1600, 2000, 2400, 3000, 3200 4000 2000, 2400, 3200, 4000 5000 3200, 4000, 5000 Digitrip RMS Adjustable Trip Settings Time/Current Characteristic ➀ Pick-Up Setting Pick-Up Point ➀ Time Band, Seconds 2, 4, 7, 10, 12, 15, 20, 24 (at 6 times pick-up value) Long Delay 0.5, 0.6, 0.7, 0.8, 0.85, 0.9, 0.95, 1.0 In Times Long Delay Setting Instantaneous 2, 2.5, 3, 4, 5, 6 M1=8, M2=12 In Times Instantaneous Setting Short Delay 2, 2.5, 3, 4, 5, 6 S1=8, S2=10 Ir Times Short Delay Setting 0.1, 0.2, 0.3, 0.4, 0.5 (Flat Response) 0.1*, 0.3*, 0.5 *(I2t Response) Ground Fault A (.25), B (.3), C (.35), D (.4), E (.5), F (.6), H (.75), K (1.0) (1200A Max.) In Times Ground Fault Setting 0.1, 0.2, 0.3, 0.4, 0.5 (Flat Response) 0.1*, 0.3*, 0.5 *(I2t Response) In = Rating Plug Valve Ir = Long Delay Pickup Setting X In 14 © 1998 Square D All Rights Reserved 11/98 Technical Overview 1000 900 800 1000 900 800 700 700 Available long delay (Ir) settings .5, .6, .7, .8, .85, .9, .95, or 1 x In = Ir 600 500 400 400 300 300 200 200 Maximum total clearing time 150 150 100 90 80 100 90 80 70 70 60 60 50 50 40 40 30 30 Minimum total clearing time ➀ The Rating Plug is for 50 and 60 Hz applications. ➁ Curves apply from -20 °C to +55 °C ambient. Temperatures above 95 °C cause automatic trip. ➂ With zone interlocking on short delay utilized and no restraining signal, the minimum time band SDM applies – regardless of setting. ➃ Long Time Memory function automatically shortens long delay time as overload conditions recur. 800 900 1000 700 600 500 400 3 4 2 2 2 2 1.5 1 .9 .8 2 10 S2 5 3 1.5 Available short delay settings 2, 2.5, 3, 4, 5, 6, S1(8) or S2(10) x Ir Time in seconds 6 300 4 4 200 5 150 6 80 90 100 7 70 15 Available long 10 delay 9 time 8 settings 7 shown 6 @ 6 x Ir ➃ 5 2, 4, 7, 10, 12, 4 15, 20, 24 7 2.5 Notes: 20 24 10 9 8 3 Tolerances ➁ LDS Range = 90% to 110% of setting LDT Range = 67% to 100% of setting shown at 6 x Ir SDS Range = 90% to 110% of setting 60 15 100, 200 200, 250, 300 200, 250, 300, 400 300, 400, 600 400, 600, 800 600, 800, 1000, 1200 800, 1000, 1200, 1600 1000, 1200, 1600, 2000 1600, 2000, 2400 1600, 2000, 2400, 3000, 3200 2000, 2400, 3200, 4000 3200, 4000, 5000 50 20 ➀ Plug Rating in Amperes (In) 200 300 400 600 800 1200 1600 2000 2400 3200 4000 5000 40 500 Sensor Rating Amperes 30 600 Time in seconds 20 15 8 9 10 7 6 5 4 3 Available DIGITRIP RMS Rating Plugs Marked 50/60 Hz 2 1.5 .8 .9 1 .7 .6 .5 .4 .3 .2 .15 .08 .09 .1 .07 .06 .05 Current in multiples of the long delay setting Ir 1 .9 .8 .7 .7 .6 .5 .6 6 4 2.5 8 S1 .5* ➂ .4 .5 ➂ .5 .4 .4 ➂ .3 .3* ➂ Available flat response short delay time settings .1, .2, .3, .4, .5 second .3 ➂ .2 .3 .2 .2 ➂ .15 .15 .1 .09 .08 .1* ➂ Available I2t shape on short delay time settings indicated by * .07 .06 .05 SDM Application determines end of curve .1 ➂ .1 .09 .08 .07 .06 .05 .04 .04 .03 .03 Current in multiples of the long delay setting Ir 800 900 1000 700 600 500 400 300 200 150 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 20 1.5 15 8 9 10 7 6 5 4 .01 3 .01 2 .015 .06 .02 .05 .02 .015 44024-431-R1 Figure 12: Typical Long Delay and Short Delay Time-Phase Current Characteristic Curve (LS) for Types DSII and DSLII Circuit Breakers with DIGITRIP RMS 510/610/POWERLOGIC 810D 15 11/98 © 1998 Square D All Rights Reserved Technical Overview 20 15 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 .4 .3 .2 .15 .08 .09 .1 .07 .06 .05 Current in multiples of plug rating In Available DIGITRIP RMS Rating Plugs Marked 50/60 Hz 1000 900 800 1000 900 800 700 700 600 600 500 500 400 400 300 300 200 200 150 150 Sensor Rating Amperes ➀ Plug Rating in Amperes (In) 200 300 400 600 800 1200 1600 2000 2400 3200 4000 5000 100, 200 200, 250, 300 200, 250, 300, 400 300, 400, 600 400, 600, 800 600, 800, 1000, 1200 800, 1000, 1200, 1600 1000, 1200, 1600, 2000 1600, 2000, 2400 1600, 2000, 2400, 3000, 3200 2000, 2400, 3200, 4000 3200, 4000, 5000 Tolerances ➁ INST Range = 90% to 110% of setting 7 6 6 5 5 4 4 800 900 1000 7 700 10 9 8 600 10 9 8 500 15 400 20 15 300 20 200 30 150 40 30 80 90 100 50 40 70 60 50 60 70 60 50 70 ➀ The Rating Plug is for 50 and 60 Hz applications. ➁ Curves apply from -20 °C to +55 °C ambient. Temperatures above 95 °C cause automatic trip. 40 100 90 80 30 100 90 80 3 3 2 2 1.5 1.5 1 .9 .8 .7 .7 Available instantaneous settings 2, 2.5, 3, 4, 5, 6, M1(8) or M2(12) x In .6 1 .9 .8 5 3 2 Time in seconds Time in seconds Notes: 2.5 4 .6 6 .5 .5 8 M1 .4 .4 .3 .3 .2 .2 12 .15 .15 M2 .1 .09 .08 .1 .09 .08 .07 .07 .06 .06 .05 .05 .04 .04 Application determines end of curve .03 .03 Current in multiples of plug rating In 800 900 1000 700 600 500 400 300 200 150 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 .4 .3 .2 .15 .01 .08 .09 .1 .01 .07 .015 .06 .02 .05 .02 .015 44024-430-R1 Figure 13: Typical Instantaneous Time-Phase Current Characteristic Curve (I) for Types DSII and DSLII Circuit Breakers with DIGITRIP RMS 510/610/POWERLOGIC 810D 16 © 1998 Square D All Rights Reserved 11/98 Technical Overview Ground Fault Settings (Amperes) ➀ ➂ ➃ 8 9 10 1000 900 800 1000 900 800 700 700 600 A 500 Available ground fault settings (typical). For exact values and tolerances of letter codes, see chart. K 400 300 Code A➁ B➁ C➁ D➁ 100 25 30 35 40 600 200 50 60 70 80 100 120 150 200 500 250 63 75 88 100 125 150 188 250 400 300 75 90 105 120 150 180 225 300 400 100 120 140 160 200 240 300 400 600 150 180 210 240 300 360 450 600 800 200 240 280 320 400 480 600 800 1000 250 300 350 400 500 600 750 1000 1200 300 360 420 480 600 720 900 1200 1600 400 480 560 640 800 960 1200 1200 2000 500 600 700 800 1000 1200 1200 1200 2400 600 720 840 960 1200 1200 1200 1200 3200 800 960 1120 1200 1200 1200 1200 1200 4000 1000 1200 1200 1200 1200 1200 1200 1200 5000 1200 1200 1200 1200 1200 1200 1200 1200 In plug ratings available 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 .4 .3 .2 .15 .08 .09 .1 .07 .06 .05 Current in multiples of plug rating In RATING In CURRENT IN MULTIPLES OF PLUG 300 200 200 150 150 100 90 80 100 90 80 70 70 60 60 50 50 40 40 E F 50 60 H K 75 100 8 9 10 7 4 6 5 4 5 5 ➄ Curves apply from -20 °C to +55 °C ambient; temperatures above 95 °C cause automatic trip. ➅ With zone interlocking on ground fault utilized and no restraining signal, the minimum time band GDM applies – regardless of setting. 4 6 3 7 6 ➃ All tabulated values are based on the use of a residual sensing scheme with the same rated current sensor in all phase and neutral conductors. 2 7 ➂ The Rating Plug is for 50 and 60 Hz applications. 1.5 10 9 8 .8 .9 1 10 9 8 .7 15 .6 15 ➁ For Testing Purposes Only: When using an external single phase current source to check low level ground fault current settings, it is advisable to use the Auxiliary Power Module (APM). See TEST PROCEDURES in Instruction Leaflet. .5 20 .4 20 ➀ Except as noted, tolerances on current levels are ±10% of values shown in chart. .3 30 .2 30 3 3 D 2 2 B 1.5 1 .9 .8 1.5 I2t shape for ground fault time delay settings indicated by * A TIME INinSECONDS Time seconds TIME INseconds SECONDS Time in Notes: 1 .9 .8 .7 .7 .6 .6 .5 .5 .5 ➅ .5 ➅ .4 .4 .4 ➅ .3 .3 .2 .2 ➅ ➅ Available ground fault time delay settings flat response Available ground fault time delay settings I2t shape .3* ➅ .3 .2 .15 .15 GDM .1 .09 .08 .1 .1* ➅ .1 .09 .08 ➅ .07 .07 .06 .06 .05 .05 .04 .04 .03 .03 CURRENT IN MULTIPLES OF PLUG RATING In Current in multiples of plug rating In 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 .4 .3 .2 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 .4 .3 .2 .15 .01 .08 .09 .1 .01 .07 .015 .06 .02 .05 .02 .015 44024-432-R1 Figure 14: Typical Ground Fault/Protection Time-Phase Current Characteristic Curve (G) for Types DSII and DSLII Circuit Breakers with DIGITRIP RMS 510/610/POWERLOGIC 810D 17 11/98 © 1998 Square D All Rights Reserved Technical Overview DSL circuit breakers are equipped with limiters having characteristics as illustrated in curves A (Figure 15 on page 19) through E (Figure 20 on page 24). Fuse limiters are used where fault currents exceed the interrupting capacity of the circuit breaker alone. The let-through and I2T characteristics of the limiters are coordinated with the circuit breaker elements to allow safe application on circuits that have available fault currents up to 200,000 RMS symmetrical amperes. Selection of the proper limiter size depends upon whether the function of the limiter is to protect downstream equipment or to protect the circuit breaker. If downstream equipment protection is the main criterion, the smallest available limiter should be selected. Due to coordination problems, selection of certain small limiters may cause nuisance blowing on overloads or low-level short circuits. For protection of the circuit breaker only, the largest available limiter should be selected. The table below lists available limiter ratings for DSLII-308 and DSLII-516 circuit breakers. Circuit Breaker Type Sensor Rating Amperes DSLII-308 Limiter Rating, Amperes Minimum • Recommended ➁ Maximum ➂ 50 or 100 150 1200 2000 DSLII-308 150 200 1200 2000 DSLII-308 200 250 1200 2000 DSLII-308 300 400 1200 2000 DSLII-308 400 600 1200 2000 DSLII-308 600 800 1200 2000 DSLII-308 800 1200 1200 2000 DSLII-516 600 800 2000 3000 DSLII-516 800 1000 2000 3000 DSLII-516 1200 2000 2500 3000 DSLII-516 1600 3000 3000 3000 • For use only when protection of downstream equipment is required. Not completely coordinated with circuit breaker to avoid nuisance blowing. ➁ Lowest rating that can be coordinated with circuit breaker to minimize nuisance blowing. ➂ Highest available ratings, for protection of circuit breaker only. Limiters are mounted in separate trucks for the DSLII-632 and DSLII-840 circuit breakers. Three sizes, 2500, 3000, and 4000 A capacity, are available for DSLII-632. Four sizes, 2500, 3000, 4000, and 5000 A capacity, are available for DSLII-840. 18 © 1998 Square D All Rights Reserved 11/98 Technical Overview Curve A 8000 9000 10000 7000 6000 5000 4000 3000 2000 800 900 1000 700 600 500 400 300 200 80 90 100 70 60 50 40 30 20 8 9 10 7 1000 900 800 1000 900 800 700 700 600 600 500 500 400 400 300 300 200 200 1600 2000 1200 800 600 400 300 250 200 150 LIMITER AMPERE RATING 100 90 80 100 90 80 70 70 60 60 50 50 .05 .04 .04 .03 .03 .02 .02 .01 .01 8000 9000 10000 .06 .05 7000 .07 .06 6000 .1 .09 .08 .07 5000 .1 .09 .08 4000 .2 3000 .2 2000 .3 800 900 1000 .4 .3 700 .5 .4 600 .6 .5 500 .7 .6 400 .7 300 1 .9 .8 200 1 .9 .8 80 90 100 2 70 2 60 3 50 4 3 40 5 4 30 6 5 20 7 6 8 9 10 7 7 10 9 8 6 10 9 8 5 20 4 20 3 30 2 40 30 1 40 TIME IN SECONDS TIME IN SECONDS 6 5 4 3 2 1 SCALE X 100 = CURRENT IN AMPERES SCALE X 100 = CURRENT IN AMPERES 44025-793-R1 Figure 15: Type DSLII-308 Limiters: Average Melting Time and Current Characteristics 19 11/98 © 1998 Square D All Rights Reserved Technical Overview Curve B 400,000 300,000 200,000 1600 1200 80,000 800 70,000 60,000 E C 600 U 50,000 D O 40,000 N PR A IT C 400 U C 30,000 300 IR T C 250 EN 200 150 R R 20,000 U K AMPERE RATING MAXIMUM PEAK LET-THROUGH CURRENT (AMPERES) 2000 100,000 90,000 C A M PE U M XI A M 10,000 9000 8000 7000 6000 5000 4000 3000 2000 200,000 90,000 100,000 80,000 70,000 60,000 50,000 40,000 30,000 20,000 9000 10,000 8000 7000 6000 5000 4000 3000 2000 1000 1000 AVAILABLE CURRENT (RMS SYMMETRICAL AMPERES) 44025-796-R1 Figure 16: Type DSLII-308 Limiters: Let-through Characteristics 20 © 1998 Square D All Rights Reserved 11/98 Technical Overview Curve C 8000 9000 10000 7000 6000 5000 4000 3000 2000 800 900 1000 700 600 500 400 300 200 80 90 100 70 60 50 40 30 20 8 9 10 7 6 5 4 3 2 1 SCALE X 100 = CURRENT IN AMPERES 1000 900 800 1000 900 800 700 700 600 600 500 500 400 400 300 300 200 200 3000 2000 2500 1600 1200 1000 100 90 80 100 90 80 70 70 60 60 50 50 .03 .02 .02 .01 .01 8000 9000 10000 .04 .03 7000 .05 .04 6000 .06 .05 5000 .07 .06 4000 .1 .09 .08 .07 3000 .1 .09 .08 2000 .2 800 900 1000 .2 700 .3 600 .4 .3 500 .5 .4 400 .6 .5 300 .7 .6 200 1 .9 .8 .7 80 90 100 1 .9 .8 70 2 60 2 50 3 40 4 3 30 5 4 20 6 5 8 9 10 7 6 7 10 9 8 7 6 10 9 8 5 20 4 20 3 30 2 40 30 1 40 TIME IN SECONDS TIME IN SECONDS 800 LIMITER AMPERE RATING SCALE X 100 = CURRENT IN AMPERES 44025-794-R2 Figure 17: Type DSLII-516 Limiters: Average Melting Time and Current Characteristics 21 11/98 © 1998 Square D All Rights Reserved Technical Overview Curve D 400,000 300,000 200,000 2500 2000 MAXIMUM PEAK LET-THROUGH CURRENT (AMPERES) 1600 100,000 90,000 1200 80,000 1000 70,000 800 AMPERE RATING 3000 60,000 E C U 50,000 D O 40,000 N PR A IT C U C 30,000 IR T C EN R R 20,000 U K C A M PE U M XI A M 10,000 9000 8000 7000 6000 5000 4000 3000 2000 AVAILABLE CURRENT (RMS SYMMETRICAL AMPERES) 200,000 80,000 90,000 100,000 70,000 60,000 50,000 40,000 30,000 20,000 9000 10,000 8000 7000 6000 5000 4000 3000 2000 1000 1000 44025-797-R1 Figure 18: Type DSLII-516 Limiters: Let-through Characteristics 22 © 1998 Square D All Rights Reserved 11/98 Technical Overview Curve E 1000 900 800 8000 9000 10000 7000 6000 5000 4000 3000 2000 800 900 1000 700 600 500 400 300 200 80 90 100 70 60 50 40 30 20 8 9 10 7 6 5 4 3 2 1 SCALE X 100 = CURRENT IN AMPERES 1000 900 800 5000 600 4000 2500 3000 LIMITER AMPERE RATING 700 700 600 500 500 400 400 300 300 200 200 100 90 80 100 90 80 70 70 60 60 50 50 40 40 30 30 20 20 10 9 8 10 9 8 7 .01 8000 9000 10000 .01 7000 .02 6000 .02 5000 .03 4000 .04 .03 3000 .05 .04 2000 .06 .05 800 900 1000 .07 .06 700 .07 600 .1 .09 .08 500 .1 .09 .08 400 .2 300 .2 200 .3 80 90 100 .4 .3 70 .5 .4 60 .6 .5 50 .7 .6 40 1 .9 .8 .7 30 1 .9 .8 20 2 8 9 10 2 7 3 6 3 5 4 4 4 3 5 2 6 5 1 6 TIME IN SECONDS TIME IN SECONDS 7 SCALE X 100 = CURRENT IN AMPERES 44025-795-R2 Figure 19: Types DSLII-632 and DSLII-840 Limiters: Average Melting Time and Current Characteristics 23 11/98 © 1998 Square D All Rights Reserved Technical Overview Curve F 400,000 5000 300,000 4000 200,000 MAXIMUM PEAK LET-THROUGH CURRENT (AMPERES) 2500 100,000 90,000 80,000 70,000 AMPERE RATING 3000 60,000 E C U 50,000 D O 40,000 N PR A IT C U C 30,000 IR T C EN R R 20,000 U K C EA M P U M XI A M 10,000 9000 8000 7000 6000 5000 4000 3000 2000 200,000 90,000 100,000 80,000 70,000 60,000 50,000 40,000 30,000 20,000 9000 10,000 8000 7000 6000 5000 4000 3000 2000 1000 1000 AVAILABLE CURRENT (RMS SYMMETRICAL AMPERES) 44025-798-R2 Figure 20: Types DSLII-632 and DSLII-840 Limiters: Let-through Characteristics 24 © 1998 Square D All Rights Reserved 11/98 Technical Overview Application of Type DSII Air Circuit Breakers With Standard Three-Phase Transformers–Fluid Filled and Ventilated Dry Types Transformer Base (100%) Rating kVA and Percent Impedance Amperes ➀ Secondary Short-Circuit Currents RMS Symmetrical Amperes Max. Short Circuit kVA Available from Primary System Through Transformer Only Motor Contribution Combined 1700 16600 17400 17700 18000 18200 18400 2800 25900 28000 28800 29500 30000 30600 4200 32900 36200 37500 38600 39400 40400 5600 41500 46800 48900 50800 52300 53900 2900 15800 16500 16800 17000 17200 17300 4800 24800 26700 27300 27900 28400 28900 7200 32100 35000 36100 37000 37800 38600 9600 40600 45200 47100 48700 50000 51400 Minimum Size Circuit Breakers for Selective Trip Systems Main Feeder Circuit Circuit Breaker Breaker Short Short Delay Trip Delay Trip Feeder Circuit Breaker Instantaneous Trip 208 V Three-Phase – 50% Motor Load 300 5.0% 500 5.0% 750 5.75% 1000 5.75% 833 50000 100000 150000 250000 500000 Unlimited 14900 15700 16000 16300 16500 16700 1389 50000 100000 150000 250000 500000 Unlimited 23100 25200 26000 26700 27200 27800 2083 50000 100000 150000 250000 500000 Unlimited 28700 32000 33300 34400 35200 36200 2778 50000 100000 150000 250000 500000 Unlimited 35900 41200 43300 45200 46700 48300 DSII-516 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-516 ➁ DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-508 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-632 DSII-508 DSII-508 DSII-508 DSII-508 DSII-508 DSII-508 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-632 ➁ DSII-508 DSII-508 DSII-508 DSII-608 DSII-608 DSII-608 DSII-308 DSII-508 DSII-508 DSII-508 DSII-508 DSII-508 DSII-308 ➁ DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-516 ➁ DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-620 ➁ DSII-508 DSII-508 DSII-508 DSII-508 DSII-508 DSII-508 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-632 ➁ DSII-508 DSII-508 DSII-508 DSII-508 DSII-508 DSII-608 DSII-308 DSII-508 DSII-508 DSII-508 DSII-508 DSII-508 240 V Three-Phase – 100% Motor Load 300 5.0% 500 5.0% 750 5.75% 1000 5.75% ➀ ➁ 722 50000 100000 150000 250000 500000 Unlimited 12900 13600 13900 14100 14300 14400 1203 50000 100000 150000 250000 500000 Unlimited 20000 21900 22500 23100 23600 24100 1804 50000 100000 150000 250000 500000 Unlimited 24800 27800 28900 29800 30600 31400 2406 50000 100000 150000 250000 500000 Unlimited 31000 35600 37500 39100 40400 41800 At transformer self-cooled rating. Next larger frame size main circuit breaker may be required for 55/65 °C rise and/or forced air-cooled (FA) transformer. Check Transformer Secondary Ampere Rating. 25 11/98 © 1998 Square D All Rights Reserved Technical Overview Application of Type DSII Air Circuit Breakers With Standard Three-Phase Transformers Fluid Filled and Ventilated Dry Types Transformer Base (100%) Rating kVA and Percent Impedance Amperes ➀ Secondary Short-Circuit Currents RMS Symmetrical Amperes Max. Short Circuit kVA Available from Primary System Through Transformer Only Motor Contribution Combined 2400 12400 13300 13700 14000 14200 14400 3600 16000 17500 18000 18500 18900 19300 4800 20300 22600 23500 24400 25000 25700 7200 27800 32100 33900 35600 37000 38600 9600 34300 40600 43600 46300 48700 51400 12000 40000 48500 52500 56600 60100 64300 14000 44700 55200 60600 65900 70800 76800 18000 52000 65500 72700 80200 87400 96500 Minimum Size Circuit Breakers for Selective Trip Systems Feeder Main Circuit Breaker Circuit Breaker Short Delay Short Delay Trip Trip Feeder Circuit Breaker Instantaneous Trip 480 V Three-Phase – 100% Motor Load 500 5.0% 750 5.75% 1000 5.75% 1500 5.75% 2000 5.75% 2500 5.75% 3000 5.75% 3750 5.75% ➀ ➁ 601 50000 100000 150000 250000 500000 Unlimited 10000 10900 11300 11600 11800 12000 902 50000 100000 150000 250000 500000 Unlimited 12400 13900 14400 14900 15300 15700 1203 50000 100000 150000 250000 500000 Unlimited 15500 17800 18700 19600 30200 20900 1804 50000 100000 150000 250000 500000 Unlimited 20600 24900 26700 28400 29800 31400 2406 50000 100000 150000 250000 500000 Unlimited 24700 31000 34000 36700 39100 41800 3008 50000 100000 150000 250000 500000 Unlimited 28000 36500 40500 44600 48100 52300 3609 50000 100000 150000 250000 500000 Unlimited 30700 41200 46600 51900 56800 62800 4511 50000 100000 150000 250000 500000 Unlimited 34000 47500 54700 62200 69400 78500 DSII-308 ➁ DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-516 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-516 ➁ DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-620 ➁ DSII-308 DSII-508 DSII-508 DSII-508 DSII-508 DSII-508 DSII-308 DSII-508 DSII-508 DSII-508 DSII-508 DSII-508 DSII-632 ➁ DSII-508 DSII-508 DSII-508 DSII-508 DSII-508 DSII-608 DSII-508 DSII-508 DSII-508 DSII-508 DSII-508 DSII-608 DSII-632 ➁ DSII-508 DSII-508 DSII-608 DSII-608 DSII-608 DSII-608 DSII-508 DSII-508 DSII-608 DSII-608 DSII-608 DSII-608 DSII 840 ➁ DSII-508 DSII-608 DSII-608 DSLII-308 DSLII-308 DSLII-308 DSII-508 DSII-608 DSII-608 DSLII-308 DSLII-308 DSLII-308 DSII-850 DSII-608 DSLII-308 DSLII-308 DSLII-308 DSLII-308 DSLII-308 DSII-608 DSLII-308 DSLII-308 DSLII-308 DSLII-308 DSLII-308 At transformer self-cooled rating. Next larger frame size main circuit breaker may be required for 55/65 °C rise and/or forced air-cooled (FA) transformer. Check Transformer Secondary Ampere Rating. 26 © 1998 Square D All Rights Reserved 11/98 Technical Overview Application of Type DSII Air Circuit Breakers With Standard Three-Phase Transformers Fluid filled and Ventilated Dry Types Transformer Base (100%) Rating kVA and Percent Impedance Amperes ➀ Secondary Short-Circuit Currents RMS Symmetrical Amperes Max. Short Circuit kVA Available from Primary System Through Transformer Only Motor Contribution Combined 1900 9900 10600 10900 11200 11300 11500 2900 12900 14000 14500 14800 15100 15500 3900 16300 18200 18900 19500 30100 20600 5800 22300 25800 27200 28500 29700 30900 7700 27400 32500 34900 37100 39000 41200 9600 32000 38800 42000 45200 48100 51400 11500 36100 44500 48800 53000 57000 61700 14400 41600 52400 58100 64200 69900 77200 Minimum Size Circuit Breakers for Selective Trip Systems Main Feeder Circuit Circuit Breaker Breaker Short Short Delay Trip Delay Trip Feeder Circuit Breaker Instantaneous Trip 600 V Three-Phase – 100% Motor Load 500 5.0% 750 5.75% 1000 5.75% 1500 5.75% 2000 5.75% 2500 5.75% 3000 5.75% 3750 5.75% ➀ ➁ 481 50000 100000 150000 250000 500000 Unlimited 8000 8700 9000 9300 9400 9600 722 50000 100000 150000 250000 500000 Unlimited 10000 11100 11600 11900 12200 12600 962 50000 100000 150000 250000 500000 Unlimited 12400 14300 15000 15600 16200 16700 1443 50000 100000 150000 250000 500000 Unlimited 16500 20000 21400 22700 23900 25100 1924 50000 100000 150000 250000 500000 Unlimited 19700 24800 27200 29400 31300 33500 2406 50000 100000 150000 250000 500000 Unlimited 22400 29200 32400 35600 38500 41800 2886 50000 100000 150000 250000 500000 Unlimited 24600 33000 37300 41500 45500 50200 3608 50000 100000 150000 250000 500000 Unlimited 27200 38000 43700 49800 55500 62800 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSLII-308 ➁ DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-516 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSLII-516➁ DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-508 DSII-308 DSII-308 DSII-308 DSII-308 DSII-308 DSII-508 DSII-602 ➁ DSII-308 DSII-508 DSII-508 DSII-508 DSII-508 DSII-508 DSII-308 DSII-508 DSII-508 DSII-508 DSII-508 DSII-508 DSII-632 ➁ DSII-508 DSII-508 DSII-508 DSII-608 DSII-608 DSLII-308 DSII-508 DSII-508 DSII-508 DSII-608 DSII-608 DSLII-308 DSII-632 ➁ DSII-508 DSII-608 DSII-608 DSLII-308 DSLII-308 DSLII-308 DSII-508 DSII-608 DSII-608 DSLII-308 DSLII-308 DSLII-308 DSII-840 ➁ DSII-508 DSLII-308 DSLII-308 DSLII-308 DSLII-308 DSLII-308 DSII-508 DSLII-308 DSLII-308 DSLII-308 DSLII-308 DSLII-308 At transformer self-cooled rating. Next larger frame size main circuit breaker may be required for 55/65 °C rise and/or forced air-cooled (FA) transformer. Check Transformer Secondary Ampere Rating. 27 11/98 © 1998 Square D All Rights Reserved Dimensions Layout Approximate Dimensions–Not for Construction Top conduit entrance 29.0 737 17.0 432 F 2.5 64 D 2.5 64 2.5 64 F 2.5 64 2.5 64 Front 2.5 64 2.5 64 5.5 140 2.5 64 Front Figure 2 Tie Section Figure 4 Instrument or Blank Panel DSII-308 Or for DSII-508 Blank DSII-608 DSLII-308 DSII-516 DSII-616 DSLII-516 Front elevations B Auxiliary Section A DSII-516 DSII-616 DSLII-516 DSII-620 Main 91.50 2324 DSII-308 Or for DSII-508 Blank DSII-608 DSLII-308 DSII-516 DSII-616 DSLII-516 DSII-308 Or for DSII-508 Blank DSII-608 DSLII-308 DSII-516 DSII-616 DSLII-516 DSII-308 Or for DSII-508 Blank DSII-608 DSLII-308 DSII-516 DSII-616 DSLII-516 22.0 559 22.0 559 C D 22.0 559 17.0 432 29.0 737 17.0 432 2.5 64 Front 2.5 64 3.5 89 H 2.5 64 2.5 64 Front B DSII-308 Or for DSII-508 Blank DSII-608 DSLII-308 DSII-516 DSII-616 DSLII-516 34.0 864 89 B DSII-308 Or for DSII-508 Blank DSII-608 DSLII-308 DSII-516 DSII-616 DSLII-516 22.0 559 3.5 A Tie DSII-308 DSII-508 DSII-608 DSLII-308 DSII-516 DSII-616 DSLII-516 DSII-308 Or for DSII-508 Blank DSII-608 DSLII-308 DSII-516 DSII-616 DSLII-516 C H 2.5 64 Front A Auxiliary Section 2.5 64 Transformer Conn. Section Figure 3 DSII-308 Or for DSII-508 Blank DSII-608 DSLII-308 DSII-516 DSII-616 DSLII-516 Transition or 2.5 64 F Front DSII-308 Or for DSII-508 Blank DSII-608 DSLII-308 DSII-516 DSII-616 DSLII-516 Transition or 2.5 64 F 8.0 203 2.5 64 Figure 1A 17.0 432 2.5 64 F Front Figure 1 17.0 432 17.0 432 D D 17.0 432 3.5 89 H C 2.5 64 17.0 432 3.5 89 H 2.5 64 89 2.5 64 2.5 64 Front 3.5 H 2.5 64 Front 2.5 64 Front Bottom conduit entrance 6035-10 28 © 1998 Square D All Rights Reserved 11/98 Dimensions Layout Approximate Dimensions–Not for Construction Top conduit entrance 17.0 432 17.0 432 F 2.5 64 2.5 64 2.5 64 5.5 140 17.0 432 2.5 64 F 2.5 64 17.0 432 17.0 432 2.5 64 F 8.0 203 2.5 64 2.5 64 2.5 64 F 2.5 64 2.5 64 5.5 140 2.5 64 F 2.5 64 2.5 64 Front Front Front Front Front Front Incoming Cable Section Figure 5 Transformer Conn. Section Figure 6 Tie Section Figure 7 Incoming Cable Section Figure 8 Transformer Conn. Section Figure 9 Incoming Cable Section Figure 10 Instrument or Blank Panel Instrument or Blank Panel Instrument or Blank Panel Instrument or Blank Panel DSLII-632 A A A A Front elevations 2.5 64 F 8.0 203 2.5 64 D 17.0 432 DSII-516 DSII-616 DSLII-516 DSII-620 Main Limiter Truck AB B DSII-308 Or for DSII-508 Blank DSII-608 DSLII-308 DSII-516 DSII-616 DSLII-516 DSII-632 Main 91.5 2324 DSII-632 Tie BC BC Feeder BC Feeder D D 22.0 559 22.0 559 17.0 432 17.0 432 H 2.5 64 3.5 89 2.5 64 17.0 432 2.5 64 Main Breaker Main Breaker CD CD 22.0 559 22.0 559 22.0 559 17.0 432 17.0 432 17.0 432 3.5 89 H 2.5 64 Circuit Breaker Element D 22.0 559 3.5 89 Circuit Breaker Element Feeder D H AB DSII-632 Main C DSII-308 Or for DSII-508 Blank DSII-608 DSLII-308 DSII-516 DSII-616 DSLII-516 2.5 64 DSLII-632 Limiter Truck 2.5 64 H 2.5 64 2.5 64 3.5 89 H 2.5 64 2.5 64 3.5 89 H 2.5 64 3.5 89 2.5 64 Bottom conduit entrance 6035-11 29 11/98 © 1998 Square D All Rights Reserved Dimensions Layout Approximate Dimensions–Not for Construction Top conduit entrance 29.0 737 29.0 737 F 8.0 203 5.5 140 2.5 64 D 2.5 64 29.0 737 2.5 64 F 2.5 64 29.0 737 2.5 64 F 2.5 64 2.5 64 F 8.0 203 5.5 140 2.5 64 2.5 64 2.5 64 29.0 737 2.5 64 2.5 64 F 2.5 64 2.5 64 2.5 64 Front Front Front Front Front Transformer Conn. Section Figure 11 Incoming Cable Section Figure 12 Tie Section Figure 13 Transformer Conn. Section Figure 14 Incoming Cable Section Figure 15 Instruments or Blank Panel Instruments or Blank Panel Instruments or Blank Panel DSLII-840 DSLII-840 Limiter Truck Limiter Truck A DSII-840 DSII-850 1 Main Front elevations DSII-840 DSII-850 1 Main BC Feeder 2 Feeder 2 D 2.5 64 2.5 64 2.5 64 Front Main Breaker CD Main Breaker CD 34.0 864 29.0 737 3.5 89 H 2.5 64 29.0 737 3.5 89 H 2.5 64 2.5 64 2.5 64 Front Circuit Breaker Element 34.0 864 29.0 737 3.5 89 H Circuit Breaker Element 34.0 864 29.0 737 3.5 89 AB D 34.0 864 29.0 737 AB BC Feeder 2 D A DSII-840 DSII-850 1 Tie BC 34.0 864 H A Front 3.5 89 H 2.5 64 2.5 64 Front 2.5 64 Front Bottom conduit entrance ➀ DS-850 - Forced air cooled. ➁ No feeder permitted with DS-850. 6035-12 30 © 1998 Square D All Rights Reserved 11/98 Dimensions Dimensions Indoor Construction Approximate Dimensions – Not for Construction Bus Size Circuit Breaker Type MM IN MM IN MM IN MM IN MM IN MM IN MM IN F H F H F H F H F H F H F H F H 55.13 1400 14.5 13.5 368 343 14.5 6.5 368 165 9.0 6.5 229 165 14.5 6.5 368 165 60.13 1527 19.5 18.5 495 470 19.5 11.5 495 292 14.0 11.5 356 292 19.5 11.5 495 292 72.13 1832 31.5 30.5 800 775 31.5 23.5 800 597 26.0 23.5 660 597 31.5 23.5 800 597 63.13 1604 14.5 13.5 368 343 14.5 6.5 368 165 9.0 6.5 229 165 14.5 6.5 368 165 68.13 1731 19.5 18.5 495 470 19.5 11.5 495 292 14.0 11.5 356 292 19.5 11.5 495 292 80.13 2035 31.5 30.5 800 775 31.5 23.5 800 597 26.0 23.5 660 597 31.5 23.5 800 597 55.13 1400 14.5 13.5 368 343 14.5 6.5 368 165 … … … … 14.5 6.5 368 165 60.13 1527 19.5 18.5 495 470 19.5 11.5 495 292 … … … … 19.5 11.5 495 292 72.13 1832 31.5 30.5 800 775 31.5 23.5 800 597 … … … … 31.5 23.5 800 597 63.13 1604 14.5 13.5 368 343 14.5 6.5 368 165 … … … … 14.5 6.5 368 165 DSLII 68.13 1731 19.5 18.5 495 470 19.5 11.5 495 292 … … … … 19.5 11.5 495 292 80.13 2035 31.5 30.5 800 775 31.5 23.5 800 597 … … … … 31.5 23.5 800 597 DSII/DSLII (Except DSII/ DSLII-840 63.13 1604 14.5 13.5 368 343a 14.5 6.5 368 165 … … … … … … … … 68.13 1731 19.5 18.5 495 470a 19.5 11.5 495 292 … … … … … … … … 80.13 2035 31.5 30.5 800 775a 31.5 23.5 800 597 … … … … … … … … DSII DSLII DSII 3200 A Circuit Breaker Type ➁,➂ ➁,➂,➃ Figure 6 Transformer Main Unit Figure 7 Tie Unit Figure 8 Cable-in Main IN MM IN MM IN MM IN MM IN MM F H F H F H F H F H F H F H F H 55.13 1400 14.5 6.5 368 165 … … … … … … … … … … … … 60.13 1527 19.5 11.5 495 292 … … … … … … … … … … … … 72.13 1832 31.5 23.5 800 597 … … … … … … … … … … … … 63.13 1604 14.5 6.5 368 165 … … … … … … … … … … … … 68.13 1731 19.5 11.5 495 292 … … … … … … … … … … … … 80.13 2035 31.5 23.5 800 597 … … … … … … … … … … … … 55.13 1400 … … … … 9.0 6.5 229 165 14.5 6.5 368 165 … 6.5 … 165 60.13 1527 … … … … 14.0 11.5 356 292 19.5 11.5 495 292 19.5 11.5 495 292 72.13 1832 … … … … 26.0 23.5 660 597 31.5 23.5 800 597 31.5 23.5 800 597 63.13 1604 … … … … … … … … 14.5 6.5 368 165 … … … … DSLII 68.13 1731 … … … … … … … … 19.5 11.5 495 292 … … … … 80.13 2035 … … … … … … … … 31.5 23.5 800 597 … … … … DSII/DSLII (Except DSII/ DSLII-840 63.13 1604 … … … … … … … … 14.5 6.5 368 165 … … … … 1600 A or 2000 A DSII 1600 A or 2000 A DSLII 3200 A DSII 3200 A ➅ Figure 5 Cable-in Main Section Depth D MM ➁,➂,➃ (See Notes) 4000 A 5000 A Figure 4 Tie Unit IN 3200 A Bus Size Figure 3 Transformer Main Unit MM 1600 A or 2000 A ➅ Figure 2 Incoming Unit/ 4 High for Unit Figure 1,1A Transition Aux. Unit IN 1600 A or 2000 A 4000 A 5000 A Section Depth D (See Notes) 68.13 1731 … … … … … … … … 19.5 11.5 495 292 … … … … 80.13 2035 … … … … … … … … 31.5 23.5 800 597 … … … … ➁,➃ ➁,➂ ➁,➂,➃ ➁,➂,➃ NOTE: Conduit areas are for mechanical connectors. For compression lug conduit area, consult your local Square D sales office. • Transformer or auxiliary Unit Fig. 1A only. ➁ Conduit area for bottom (H) increases by 7 in/177.8 mm when there is no circuit breaker in the bottom cell. ➂ When a bus duct is used in this unit the top entrance (F) is decreased, consult your local Square D sales office for area. ➃ Service entrance barrier and other barriers change conduit area, consult your local Square D sales office for area. ➄ This unit has a through bus connection. For a ‘CD’ feeder, consult your local Square D sales office. ➅ 5000 A applications, consult your local Square D sales office. 31 11/98 © 1998 Square D All Rights Reserved Dimensions Dimensions Indoor Construction Approximate Dimensions – Not for Construction Bus Size 3200 A ➅ IN 3200 A MM IN MM IN Figure 12 Cable-in Main MM IN MM MM F H F H F H F H F H F H F H F H 63.13 1604 9.0 8.75 229 222 … … … … … … … … … … … … 68.13 1731 14.0 13.75 356 349 19.5 13.75 495 349 … … … … … … … … 80.13 2035 26.0 25.75 660 654 19.0 25.75 483 654 … … … … … … … … DSII/ DSLII 63.13 1604 … … … … … … … … … 6.5 … 165 … … … … 840 68.13 1731 … … … … … … … … 6.5 11.5 165 292 19.5 11.5 495 292 DSII-850 80.13 2035 … … … … … … … … 18.5 23.5 470 597 31.5 23.5 800 597 DSLII ➂,➄ (See Notes) Bus Size Figure 11 Transformer Main Unit Figure 10 Cable-in Main IN 4000 A 5000 A Figure 9 Transformer Main Section Depth D Circuit Breaker Type Circuit Breaker Type DSLII ➂,➃ Figure 13 Tie Unit Section Depth D IN ➁,➂ ➁,➃ Figure 14 Transformer Main MM IN Figure 15 Cable-in Main MM IN MM IN MM F H F H F H F H F H F H 63.13 1604 … … … … … … … … … … … … … 68.13 1731 … … … … … … … … … … … 80.13 2035 … … … … … … … … … … … … DSII/DSLII 63.13 1604 14.5 6.5 368 165 … 8.5 … 216 … … … … 4000 A 840 68.13 1731 19.5 11.5 495 292 6.5 12.5 165 317 19.5 13.75 495 349 5000 A ➅ DSII-850 80.13 2035 31.5 23.5 800 597 18.5 24.5 470 622 19.0 17.75 483 451 ➁,➂,➃ (See Notes) ➂ ➂,➃ NOTE: Conduit areas are for mechanical connectors. For compression lug conduit area, consult your local Square D sales office. • Transformer or auxiliary Unit Fig. 1A only. ➁ Conduit area for bottom (H) increases by 7 in/177.8 mm when there is no circuit breaker in the bottom cell. ➂ When a bus duct is used in this unit the top entrance (F) is decreased, consult your local Square D sales office for area. ➃ Service entrance barrier and other barriers change conduit area, consult your local Square D sales office for area. ➄ This unit has a through bus connection. For a ‘CD’ feeder, consult your local Square D sales office. ➅ 5000 A applications, consult your local Square D sales office. Lb Kg Type of Device Lb Kg DSII-308 Circuit Breaker Type of Device 175 79.4 DSII-850 Circuit Breaker 405 184.1 DSII-508 Circuit Breaker 180 81.7 DSLII-308 Circuit Breaker 205 93.0 DSII-608 Circuit Breaker 180 81.7 DSLII-516 Circuit Breaker 255 115.7 DSII-516 Circuit Breaker 180 81.7 DSLII-632 Limiter Truck 325 147.4 DSII-616 Circuit Breaker 185 83.9 DSLII-840 Limiter Truck 430 195.0 DSII-620 Circuit Breaker 180 81.7 4-high unit without Circuit Breakers (22") 1600 725.8 DSII-632 Circuit Breaker 300 136.0 Unit without Circuit Breakers (34") 2600 1179.3 DSII-840 Circuit Breaker 405 184.1 Auxiliary unit without devices 500 226.8 Recommended Minimum Clearance: Front - 42" (1050 mm) Rear - 42" (1050 mm) Ref. NEC®, Article 110-16 32 © 1998 Square D All Rights Reserved 11/98 Suggested Specifications General The specifications and associated drawings describe the indoor low voltage metal-enclosed drawout switchgear assembly. The assembly is to be designed for use on a _____ volt, (single) (3) phase, _____ wire, 50/60 Hz system, with _____ amperes symmetrical fault current available. Equipment is to be complete from the incoming line connections to the outgoing feeder connections. Any items not specifically mentioned but obviously necessary for proper operation are implied in this description. The low voltage section shall be POWER-ZONE III Series 2 low voltage, metal-enclosed switchgear, as manufactured by the Square D company, or approved equal, designed, manufactured, and tested in accordance with applicable standards for power circuit breakers and metal-enclosed switchgear. Applicable Standards: Structures: Circuit Breakers: NEMA SG5 NEMA SG3 ANSI C37.20.1 ANSI C37.13 ANSI C37.51 ANSI C37.16 UL 1558 (Optional) UL 1066 (Optional) The enclosure shall be electro-deposition coated with medium gray ANSI #49 enamel applied over a rust inhibiting phosphate primer. (Equipment shall be equipped with Service Entrance Label) (and) (UL 1558 label for metal-enclosed low voltage power circuit breaker type switchgear assemblies when UL recognized components are specified.) Enclosure The enclosure and internal barriers shall be fabricated of steel members in accordance with NEMA and ANSI standards. Steel lifting straps are to be provided with each shipping group to lift the structure from the top with a crane. Supply a wooden skid to permit the use of pipe rollers for moving the switchgear to its final location in the building. All vertical sections shall be bolted together. Ventilation openings on the front of the switchgear breaker compartments are to be located in such a way as to preclude the possibility of metal objects being inserted through them and easily contacting energized parts. To barrier operator from escaping gases during an interruption, circuit breakers shall be supplied with a steel front plate when ventilation openings are on the front of the circuit breaker compartment door. The equipment shall be assembled, adjusted, and tested at the factory and shall be sectionalized, if required, for shipping as requested or approved. The largest section is not to exceed ___ inches wide, ___ inches deep, and ____ inches high to enable installation at the job site. The structure is to consist of three basic compartments from the front to the rear: the front circuit breaker compartment, the center bus compartment, and the rear cable compartment. Front Circuit Breaker Compartment The front circuit breaker compartment is to contain the drawout circuit breaker elements, each mounted in its own barriered cell. Fully prepared cells shall be equipped to accept circuit breaker drawout mechanism and contain all secondary and primary current-carrying parts. Future use cells shall contain current carrying parts only and shall be capable of being converted by authorized personnel to accept a drawout circuit breaker and control circuits. Provide each circuit breaker cell and fully prepared cell with a hinged door equipped with a flush handle and an external trip button. When equipped with a circuit breaker, a double steel barrier shall exist between operating personnel, the circuit breaker mechanism, and the live parts. Thus, the circuit breaker can be operated with the outer steel door open. If the circuit breaker protrudes through a hole in the circuit breaker compartment door, shutters shall be provided to shield live parts when the circuit breaker is out for service. Also, a steel plate shall be provided for the opening in the circuit breaker compartment door to preclude the possibility of foreign objects entering the circuit breaker cell when the circuit breaker is removed. 33 11/98 © 1998 Square D All Rights Reserved Suggested Specifications Center Bus Compartment The bus compartment is to contain the section riser and main cross bus, which is to be rated for a 65 °C temperature rise per ANSI standards. The main cross bus shall be rated for ___ continuous amperes. All main and riser bus shall be bolted copper and adequately braced so to be applied on a system capable of supplying RMS symmetrical amperes of short circuit current of 50 kA, (100 kA), (150 kA), (200 kA). All contact surfaces at bolted joints shall be fully silver plated and the joint bolts are to be of high strength grade 5 steel equipped with conical type spring washers. Riser bus shall meet industry standard phaseto-phase clearance without the use of insulated/isolated bus. All electrical clearances are to be for 600 Vac. (An isolated neutral bus is to be supplied rated at (50) – (100) percent of the phase current.) Rear Cable Compartment Size the cable compartment to accommodate all incoming and outgoing cable required within each vertical switchgear section. Cable lugs are to be mounted on the load side (or line side as applicable) run-back bus, which is extended into this compartment from the bus compartment. Run-back bus for main or feeder circuit breakers are to be insulated from the section riser and the cross bus. This compartment shall also contain a copper ground bus bolted directly to the switchgear frame. (Extend a neutral run-back into the cable compartment for connecting the neutral to the ground bus with a removable isolating link.) (Clamp-type cable lugs suitable for use with aluminum or copper cable are to be supplied as shown on the plans.) (Option 1) The center bus compartment containing the section riser bus and main cross bus shall be segregated from the rear cable compartment by means of grounded metal barriers. Using plastic covers over bus, in lieu of rear barriers, for this safety precaution is not acceptable. Circuit Breakers The circuit breakers shall be the drawout type, manually or electrically operated Type DSII (DSLII) as shown on the associated drawings or as listed in the equipment tabulation. The circuit breakers are to mount on a rigid self-aligning drawout mechanism with “connected”, “test”, “disconnected”, and “removed” positions. The front door shall be capable of being closed in the “connected”, “test”, or “disconnected” positions. Provide interlocks to ensure the circuit breaker is open before it can be moved from any position or when it is between positions. Include an interlock to discharge the stored energy spring before the circuit breaker element can be withdrawn from its cell. In the “test” and “connected” positions, provide a positive ground contact between the circuit breaker element and the structure. Circuit Breakers of like frame sizes shall be interchangeable as standard. No special structural bracing will be required. All circuit breaker operating mechanisms are to be fully stored energy devices with a two-step stored energy quick-make, quick-break. Actuation of the operating handle or an operation cycle of the circuit breaker motor is to charge the closing springs. Operation of a local “close” button is to close the circuit breaker contact. Closing of the circuit breaker contacts shall automatically charge the opening springs to ensure quick-break operation. Low voltage power circuit breaker arc chutes containing asbestos will by no means be accepted. (Circuit breakers of 5000 A frame size may be forced air cooled.) The circuit breaker trip device is to be of a microprocessor design, which requires no external power connections, and provided with an adjustable long-time delay, instantaneous (and short-time delay) over-current/short circuit protection. (Include ground fault tripping as an integral part of the microprocessor trip device.) Internal self-testing of the unit shall be provided. Indicators for overload, short circuit, and ground trip shall be provided. (Circuit breakers are to have UL label.) 34 © 1998 Square D All Rights Reserved 11/98 Suggested Specifications (The trip unit shall be capable of measuring AC phase currents, power, energy, trip level, and show cause of trip. The trip unit shall be able to communicate this information, as well as permit remote operation of the circuit breaker, via the Square D POWERLOGIC communications network.) Padlocking provisions shall be furnished to receive up to three padlocks when circuit breaker is in the open position, positively preventing unauthorized closing of the circuit breaker contacts. A manual trip button and position indicator shall be furnished on all circuit breakers. A “Push to Close” button shall be conveniently located on face of circuit breaker for easy access, thereby avoiding the need to reach behind or around other devices located on the face of the circuit breaker. (Include the following only when Type DSLII circuit breakers are specified:) (Circuit breakers shall be equipped with current limiters. Current limiters shall be integrally mounted on 800 A and 1600 A frame sizes and separately mounted on 3200 A and 4000 A frame sizes. Equip each circuit breaker with a blown limiter indicator visible from the front of the circuit breaker, and with an antisingle phase device that will trip the circuit breaker when any limiter blows and will prevent reclosing the circuit breaker on a single phase condition resulting from blown or missing limiters.) The following equipment shall be provided: (1)(2) _____ Type DSII-_____ main circuit breaker(s), _____ ampere frame, 3-pole, (manually) (electrically) operated. Long-time Trip rated _____ amperes. _____ Type DSII- _____ tie circuit breaker, _____ ampere frame, 3-pole, (manually) (electrically) operated. Long-time Trip rated _____ amperes. _____ Type DSII- _____ feeder circuit breaker(s), _____ ampere frame, 3-pole, (manually) (electrically) operated. Long-time Trip rated _____ amperes. _____ Type DSII- _____ feeder circuit breaker(s), _____ ampere frame, 3-pole, (manually) (electrically) operated. Long-time Trip rated _____ amperes. Metering Components Main Bus (1)(2) _____ POWERLOGIC (circuit monitor model _*_) (Power meter model _*_) ____ _____ Current transformer, suitable ratio. ____ _____ Potential transformer, suitable ratio. Feeder Circuits ____ _____ POWERLOGIC (circuit monitor model _*_) (Power meter model _*_) ____ _____ 2% ammeter and 3-phase selector switch with OFF position. ____ _____ Current transformer, suitable ratio. (Option 2) A portable testing device shall be provided. (Option 3) A top mounted traveling circuit breaker lifting device shall be provided. (__) Indicates a selection is to be made for quantity or applicability. * (A complete line of POWERLOGIC circuit monitors, power meters, and control systems is available for POWER-ZONE III switchgear. Consult your local Square D sales office.) 35 11/98 © 1998 Square D All Rights Reserved Suggested Specifications For further information about POWER-ZONE III Series 2 Switchgear, contact your local Square D field sales office. They are conveniently located in over 160 cities throughout the U.S. and abroad to serve you: or, write to LV Equipment Product Marketing Section, Square D Company, 1010 Airpark Center Drive, Nashville, TN 37217 36 © 1998 Square D All Rights Reserved 11/98 Trademark Acknowledgements Square D Company 1500 South University Blvd. Middletown, OH 45044 (513) 424-1601 www.squared.com The following trademarks or registered trademarks are the property of the indicated entities. American National Standards Institute ANSI Cutler-Hammer Corporation DIGITRIP National Fire Protection Association National Electrical Code, NEC National Electrical Manufacturers’ Association NEMA Square D Company SQUARE D, POWER-ZONE, POWERLOGIC, Underwriter’s Laboratories UL 6035CT9201 11/98 November 1998 © 1998 Square D All Rights Reserved. Replaces 6035CT9201 dated 7/94.