Mechanical Wiring Rules DIN 2 4 3 I/O Bus These modules are intended for installation within the UL Listed enclosure model UL-ENCL for UL 294 and UL 1076. I/O Modules connect in the following configurations: Direct Connect Direct Connect Do not remotely ground any part of the input sensor wiring. Max. Number of I/O Modules Number of modules is limited to 32 per CPU but may be reduced due to the capacity of the Power Supply** Direct Connect Power Supply PS 120/240 AC 50-U PS 120/240 AC 50 1 PS 120/240 AC 85-U PS 120/240 AC 85 PS 48 DC 50 Remote grounds connected to the return terminal could make the system operate incorrectly or damage the equipment. Power Supply The signal return is not true earth ground. It is an electronic reference point necessary to interpret the sensor properly. 1 5 PANEL For reliable operation, follow these wiring guidelines: · Never lay wires across the surface of a printed circuit board. · Wires should never be within 1 in. or 25 mm of any component on a printed circuit board. 5 4 · Use shielded wire. · Terminate the shield of the wires at one end of the run onlypreferably at the end where your I/O module is located. · Be careful when stripping wire not to drop small pieces of wire inside the cabinet. · Dont run your wiring in the same conduit with AC power. · Dont run your input wiring in the same conduit with your output wiring. 3 2 1 +24 VDC 24 VDC RETURN SHIELD COMM B COMM A Caution Do not externally ground any input signal. This may damage the unit. Signal return terminals are not connected to earth ground. Remote Cable I/O 4 3 2 1 Technical Specifications Digital Input/Output Module Universal Input Module +24 V Return Contact Closure IN x Reference Resistor = OFF DC Voltage V - INx Contact Closure RET DIO-20 I/O x Max DC Voltage: GND UI-8-10 UI-8-10-10V * 5V 10V 1 2 3 IN3 IN4 RET 4 5 6 IN5 IN6 RET 7 8 9 RET Series-Parallel Circuits INx 10 KW IN7 IN8 RET 10 11 12 10 KW 10 KW Contact Closure ! INx 10 KW Contact Closure RET IN1 IN2 RET 10 KW RET * Note: In the 10V mode the input impedance is reduced to 4.4K. This may affect the performance of the driving device. GND INx Contact Closure 10 KW 10K LED Indicator RET Parallel Circuits +5V I/O x INx Contact Closure GND 5V Digital logic Input 10 KW RET + DM-20 to DIO-20 Power Connection Normally Closed I/O x GND 24VDC @ .36 Amps TO DI0-20 Reference Resistor = ON INx Reference Resistor = ON Thermistor Series Circuits 10 KW Contact Closure DIO-20 +24 VDC Cable Connector: ACC # 01-0010-840 (20 pcs.) 8858 ft. (2700 m) bus topology 1640 ft. (500 m) free topology Normally Open RET I/O x Connectors 2000 ft. (610 m) IN x 10K 2 * Wattage does not include external devices ** 32 modules may require an auxiliary power source. IN x DM-20 1 1 The PS 120/240 AC 85-U model is only to be used for UL294 applications. Supervised Circuits 5V Contact Closure Module Power Req. CPU (NetController) 10 W UI-8-10 & UI-8-10-10V 0.7 W DI-6 AC & DI-6 AC HV 0.7 W DI-8; Digital Input Module 0.8 W MI-6; MilliAmp Input Module 3.8 W DM-20 0.5 W * AO-4-8 & AO-4-8-O 3.8 W DO-4-R & DO-4-R-O 2.8 W DO-6-TR 1.1 W LO-2 & LO-2-O 0.4 W VT-1 1.5 W AC-1 2.6 W * AC-1A 2.0 W * AC-1 Plus 2.2 W * Max. Cable Lengths COMM A&B Lines: Shielded, Twisted Pair RS-485 Impedance= 100-120 W FTT-10A Low Capacitance Power Lines: Remote hookups require Listed UL294 UL1076 power limited power supply. Calculate f for maximum voltage drop of 2 VDC UI-8-10 / UI-8-10-10V Digital logic Signal Remote Connect Local & Remote Cable Information 120 W EOL Resistor DM-20 + - I/O RS-485 Remote configuration (outside the Continuum enclosure) requires a 120 W resistor across pin 1 & 2 at the begining and at the end of the remote cable. 30-3001-716 Rev G.1 DM-20 to DIO-20 Data Connection Local Cable Remote Connection Line Termination 5 General Purpose I/O I/O I/O Some modules include an integral ground clip. All modules include a screw terminal connection for earth ground. It is important that this connection be made as close to the module as possible. DIO-20 Connections I/O Direct Connect Module I/O Bus Pin-Out Grounding the Modules I/O Installation CPU Power Avail. 35 W 50 W 70 W 85 W 50 W RET Caution: Earth ground ( ) must be connected to avoid module damage DI-6 AC / DI-6-AC-HV MI-6 DO-4-R / DO-4-R-O VT-1 AC Digital Input Module MilliAmp Input Module Relay Output Module Voice Telecom Module Polarity Independent LOAD Supply AC Signal DC Signal IN x 24V Loop-Powered Sensor IN x INx OUT x Signal Voltage Range: LOAD DI-6-AC DI-6-AC-HV Max Current: 20 mA 20-132 Vrms 90-250 Vrms Voltage Supply to Sensor: 19 - 26V Contact Rating: DI-8 AO-4-8 / AO-4-8-O DO-6-TR Digital Input Module Analog Output Module Triac Output Module Voltage Output Digital logic Signal 5A @ 240 VAC 5A @ 30 VDC RJ-11 Telephone Line + ON Current Output Earth Ground OUT 1 IN x OUTx I OUTx I IN x Contact Closure OUTx V Device Load Resistance RET ³ 2KW Device Load Resistance £ 650W OUT x LOAD OUTx V Common FORM A OUT 2 GND GND ON Using Two Outputs to make FORM K IN1 IN2 RET 1 2 IN3 IN4 RET 3 4 5 6 IN5 IN6 RET 7 8 9 IN7 IN8 RET 10 11 12 Current Output: 0 - 20 mA Output Rating: 24 VAC, 0.5 A (Cannot switch DC Loads) Voltage Output: 0 - 10V Minimum Load Current: 30 mA LO-2 / LO-2-O Lighting Output Module For more information on these Andover Continuum products, see the I/O Systems Reference, 30-3001-499, and the Power Supply Reference, 30-3001-702. For documentation specific to Underwriters Laboratories (UL) evaluation, see the Note below. Override Switch Connections Module External Power Connections 28 VAC Transformer Momentary Switch UL 916 Listed product for the United States and Canada, Open Energy Management Equipment. PWR 24-30 VAC OFF ON RED GND UL 294 (Access Control System Unit Subassemblies for the United States) and UL 1076 (Proprietary Burglar Alarm System Unit Subassemblies for the United States) and C22.2 No. 205-M1983 (Signal Equipment for Canada) BLK This ground connection must be the same as the ground for the Continuum Power Supply 28 VDC (half-wave rectified AC) to External Sensors Output Rating: OVERRIDE Indicator Lamp Load 20 Amp Tungsten Filament @125 VAC Resistive Load 20 Amp Ballast @ 277 VAC (20 amp @347 VAC, Canada) Motor Load 0.5 Hp @ 110-125 VAC 0.5 HP @ 220-277 VAC (0.5 Hp @ 347 VAC, Canada) YEL WHT 28 VAC RECT RED (ON) External Relay Assy. Connections Note: Refer to the UL Listed Access Control/Proprietary Burglar Alarm Systems installation manual (the UL294 Access Control and UL 1076 Proprietary Burglar Alarm Systems Reference, 30-3001-504) for specific wiring, operation, and compatibility information. RED BLK (OFF) BLK OVERRIDE Occupancy Sensor YEL WHT (COM) BLU (POWER) WHT 28 VAC RECT. Note: Only these products mentioned in this document are evaluated by UL for UL 294 and UL 1076 applications: UI-8-10 UI -8-10-10V DI-8 (UL294 only) DO-4 © 2011 Schneider Electric All Rights Reserved. Schneider Electric § One High St. § North Andover MA USA 01845