Mechanical
Wiring Rules
DIN
2
4
3
I/O Bus
These modules are intended for installation within the UL Listed enclosure
model UL-ENCL for UL 294 and UL 1076.
I/O Modules connect in the following configurations:
Direct Connect
Direct Connect
Do not remotely ground any part of the input sensor wiring.
Max. Number of I/O Modules
Number of modules is limited to 32 per CPU but may
be reduced due to the capacity of the Power Supply**
Direct Connect
Power Supply
PS 120/240 AC 50-U
PS 120/240 AC 50 1
PS 120/240 AC 85-U
PS 120/240 AC 85
PS –48 DC 50
Remote grounds connected to the return terminal could make
the system operate incorrectly or damage the equipment.
Power Supply
The signal return is not true earth ground. It is an electronic
reference point necessary to interpret the sensor properly.
1
5
PANEL
For reliable operation, follow these wiring guidelines:
· Never lay wires across the surface of a printed circuit board.
· Wires should never be within 1 in. or 25 mm of any component
on a printed circuit board.
5
4
· Use shielded wire.
· Terminate the shield of the wires at one end of the run
only—preferably at the end where your I/O module is located.
· Be careful when stripping wire not to drop small pieces of wire
inside the cabinet.
· Don’t run your wiring in the same conduit with AC power.
· Don’t run your input wiring in the same conduit with your
output wiring.
3
2
1
+24 VDC
24 VDC RETURN
SHIELD
COMM B
COMM A
Caution
Do not externally ground any input signal. This may damage the unit.
Signal return terminals are not connected to earth ground.
Remote Cable
I/O
4
3
2
1
Technical Specifications
Digital Input/Output Module
Universal Input Module
+24 V Return
Contact
Closure
IN x
Reference
Resistor = OFF
DC Voltage
V
-
INx
Contact
Closure
RET
DIO-20
I/O x
Max DC Voltage:
GND
UI-8-10
UI-8-10-10V *
5V
10V
1
2
3
IN3 IN4 RET
4
5
6
IN5 IN6 RET
7
8
9
RET
Series-Parallel Circuits
INx
10 KW
IN7 IN8 RET
10
11
12
10 KW
10 KW
Contact
Closure
!
INx
10 KW
Contact
Closure
RET
IN1 IN2 RET
10 KW
RET
* Note: In the 10V mode the input impedance is
reduced to 4.4K. This may affect the performance
of the driving device.
GND
INx
Contact
Closure
10 KW
10K
LED
Indicator
RET
Parallel Circuits
+5V
I/O x
INx
Contact
Closure
GND
5V
Digital logic
Input
10 KW
RET
+
DM-20 to DIO-20
Power Connection
Normally Closed
I/O x
GND
24VDC @ .36 Amps
TO DI0-20
Reference
Resistor = ON
INx
Reference
Resistor = ON
Thermistor
Series Circuits
10 KW
Contact
Closure
DIO-20
+24 VDC
Cable Connector: ACC # 01-0010-840 (20 pcs.)
8858 ft. (2700 m) bus topology
1640 ft. (500 m) free topology
Normally Open
RET
I/O x
Connectors
2000 ft. (610 m)
IN x
10K
2
* Wattage does not include external devices
** 32 modules may require an auxiliary power source.
IN x
DM-20
1
1 The PS 120/240 AC 85-U model is only to be used for
UL294 applications.
Supervised Circuits
5V
Contact
Closure
Module
Power Req.
CPU (NetController)
10 W
UI-8-10 & UI-8-10-10V
0.7 W
DI-6 AC & DI-6 AC HV
0.7 W
DI-8; Digital Input Module
0.8 W
MI-6; MilliAmp Input Module
3.8 W
DM-20
0.5 W *
AO-4-8 & AO-4-8-O
3.8 W
DO-4-R & DO-4-R-O
2.8 W
DO-6-TR
1.1 W
LO-2 & LO-2-O
0.4 W
VT-1
1.5 W
AC-1
2.6 W *
AC-1A
2.0 W *
AC-1 Plus
2.2 W *
Max. Cable Lengths
COMM A&B Lines: Shielded, Twisted Pair
RS-485
Impedance= 100-120 W
FTT-10A
Low Capacitance
Power Lines:
Remote hookups require Listed UL294
UL1076 power limited power supply. Calculate
f
for maximum voltage drop of 2 VDC
UI-8-10 / UI-8-10-10V
Digital logic
Signal
Remote
Connect
Local & Remote Cable Information
120 W
EOL Resistor
DM-20
+ -
I/O
RS-485 Remote configuration (outside the Continuum enclosure) requires a
120 W resistor across pin 1 & 2 at the begining and at the end of the remote cable.
30-3001-716 Rev G.1
DM-20 to DIO-20
Data Connection
Local Cable
Remote Connection Line Termination
5
General Purpose I/O
I/O
I/O
Some modules include an integral ground clip. All modules include a screw
terminal connection for earth ground. It is important that this connection be
made as close to the module as possible.
DIO-20 Connections
I/O
Direct Connect
Module I/O Bus Pin-Out
Grounding the Modules
I/O Installation
CPU
Power Avail.
35 W
50 W
70 W
85 W
50 W
RET
Caution: Earth ground ( ) must be
connected to avoid module damage
DI-6 AC / DI-6-AC-HV
MI-6
DO-4-R / DO-4-R-O
VT-1
AC Digital Input Module
MilliAmp Input Module
Relay Output Module
Voice Telecom Module
Polarity
Independent
LOAD
Supply
AC
Signal
DC
Signal
IN x
24V
Loop-Powered
Sensor
IN x
INx
OUT x
Signal
Voltage Range:
LOAD
DI-6-AC
DI-6-AC-HV
Max Current:
20 mA
20-132 Vrms
90-250 Vrms
Voltage Supply to Sensor: 19 - 26V
Contact Rating:
DI-8
AO-4-8 / AO-4-8-O
DO-6-TR
Digital Input Module
Analog Output Module
Triac Output Module
Voltage Output
Digital logic
Signal
5A @ 240 VAC
5A @ 30 VDC
RJ-11
Telephone Line
+ ON
Current Output
Earth Ground
OUT 1
IN x
OUTx I
OUTx I
IN x
Contact
Closure
OUTx V
Device
Load
Resistance
RET
³ 2KW
Device
Load
Resistance
£ 650W
OUT x
LOAD
OUTx V
Common
FORM A
OUT 2
GND
GND
ON
Using Two Outputs to make
FORM K
IN1 IN2 RET
1
2
IN3 IN4 RET
3
4
5
6
IN5 IN6 RET
7
8
9
IN7 IN8 RET
10
11
12
Current Output:
0 - 20 mA
Output Rating:
24 VAC, 0.5 A (Cannot switch DC Loads)
Voltage Output:
0 - 10V
Minimum Load Current:
30 mA
LO-2 / LO-2-O
Lighting Output Module
For more information on these Andover Continuum products, see the I/O Systems
Reference, 30-3001-499, and the Power Supply Reference, 30-3001-702. For
documentation specific to Underwriters Laboratories (UL) evaluation, see the Note below.
Override Switch Connections
Module External Power Connections
28 VAC
Transformer
Momentary Switch
UL 916 Listed product for the United States and Canada, Open
Energy Management Equipment.
PWR
24-30 VAC
OFF
ON
RED
GND
UL 294 (Access Control System Unit Subassemblies for the
United States) and UL 1076 (Proprietary Burglar Alarm System
Unit Subassemblies for the United States) and C22.2 No.
205-M1983 (Signal Equipment for Canada)
BLK
This ground connection must be
the same as the ground
for the Continuum Power Supply
28 VDC (half-wave rectified AC)
to External Sensors
Output Rating:
OVERRIDE
Indicator
Lamp Load – 20 Amp Tungsten Filament @125 VAC
Resistive Load – 20 Amp Ballast @ 277 VAC (20 amp @347 VAC, Canada)
Motor Load – 0.5 Hp @ 110-125 VAC
0.5 HP @ 220-277 VAC (0.5 Hp @ 347 VAC, Canada)
YEL
WHT
28 VAC
RECT
RED (ON)
External Relay Assy. Connections
Note: Refer to the UL Listed Access Control/Proprietary Burglar Alarm System’s
installation manual (the UL294 Access Control and UL 1076 Proprietary Burglar Alarm
Systems Reference, 30-3001-504) for specific wiring, operation, and compatibility
information.
RED
BLK
(OFF)
BLK
OVERRIDE
Occupancy Sensor
YEL
WHT
(COM)
BLU
(POWER)
WHT
28 VAC
RECT.
Note: Only these products mentioned in this document are evaluated by UL for UL 294
and UL 1076 applications:
UI-8-10
UI -8-10-10V
DI-8 (UL294 only)
DO-4
© 2011 Schneider Electric All Rights Reserved.
Schneider Electric § One High St. § North Andover MA USA 01845