MCMK
Plastic-sheathed screen-protected 1 kV power cable
RATED VOLTAGE
Uo/U = 0,6/1 kV, Um = 1,2 kV
APPLICATION
For fixed installation indoors, outdoors and underground; as well as in building structures e.g. directly in concrete (but not in sliding joints).
Not for installations subject to severe electrical interference.
For EMC-applications see cable type MCCMK.
And if there is need for low smoke halogen-free power cable, see cable types MCMK-LSZH and XCMK-HF.
Highest permissible conductor temperature:
• continuous operation
• short circuit (duration up to 5 s)
70 °C
160 °C
Lowest recommended temperature during laying: -15 °C
CONSTRUCTION
Conductor 1,5-6 mm²: solid annealed copper wire
10-16 mm²: stranded annealed copper wire
25-240 mm²: sector shaped annealed copper wire
Insulation Lead-free PVC compound
Laying up Insulated conductors stranded together
Filling sheath 1,5-16 mm²: Lead-free filling compound
PE-conductor Copper wire layer and copper wires/tape binding
Outer sheath Black lead-free PVC compound
IDENTIFICATION OF CORES
Colours of inner cores:
2-cores
3-cores
4-cores
Blue, brown
Brown, black, grey
Blue, brown, black, grey
STANDARDS
SFS 4880
HD 603-3F
IEC 60502-1
1,5-240 mm²: IEC / EN 60332-1
25-240 mm²: IEC / EN 60332-3
CERTIFICATES, APPROVALS
(SGS Fimko)
The cable does not contain any substances on the
REACH/SVHC -list.
All substances of the cable meet the requirements of RoHS directive.
CUSTOMS CODE
8554 49 91
23.07.2014 © Prysmian Group. All rights reserved.
All sizes and values without tolerances are reference values. Specifications are for product as supplied by Prysmian Group; any modification or alteration afterwards of product may give different result.
The information contained within this document must not be copied, reprinted or reproduced in any form, either wholly or in part, without the written consent of Prysmian Group. The information is believed to be correct at the time of issue. Prysmian Group reserves the right to amend this specification without notice.
This specification is not contractually valid unless specifically authorised by Prysmian Group.
1 kV power cables
PROPERTIES
PRODUCT NAME
STK-code and drum
STK-code and spool
STK-code and coil
CONSTRUCTION DATA (1)
Diameter over cable
Weight mm kg/km
MECHANICAL DATA (2)
Minimum permissible bending radius during laying
Minimum permissible bending radius at final installation (3)
Maximum permissible pulling force with a pulling eye
ELECTRICAL DATA (2)
Maximum DC resistance of phase and neutral conductor.
AC resistance of phase and neutral conductor (1)
Maximum DC resistance of
PE-conductor
Inductance (1) conductor 20 °C conductor 70 °C conductor 20 °C m m kN
Ω/km
Ω/km
Ω/km mH/km
Operating capacitance (1)
CURRENT RATINGS (2)
µF/km
In ground
In free air (6) conductor 70 °C conductor 70 °C
SHORT CIRCUIT CURRENTS (2)
Maximum permissible short circuit current for one second phase conductor (4)
PE-conductor (5)
A
A kA kA
MCMK
2x1,5/1,5
1 kV
MCMK
2x2,5/2,5
1 kV
K8/1000
0602122
PK200
0602111
R100
0602112
K8/1000
0602123
PK150
0602114
R100
0602113
MCMK
2x6/6
1 kV
K8/500
0602125
12
170
0,15
0,10
0,15
12,1
14,5
12,1
0,34
0,25
26
15
0,18
0,24
13
220
0,16
0,11
0,25
7,41
8,87
7,41
0,32
0,30
35
20
0,30
0,42
17
400
0,20
0,14
0,60
3,08
3,69
3,08
0,30
0,35
57
34
0,70
1,0
MCMK
2x10/10
RM 1 kV
K9/500
0602126
MCMK
3x1,5/1,5
1 kV
K8/1000
0602152
MCMK
3x2,5/2,5
1 kV
K8/1000
0602153
MCMK
3x6/6
1 kV
K8/500
0602155
MCMK
3x10/10
RM 1 kV
K9/500
0602156
MCMK
3x16/16
RM 1 kV
K11/500
0602157
20
610
0,24
0,17
1,0
1,83
2,19
1,83
0,28
0,40
77
67
1,1
1,7
R100
0600122
12
190
0,15
0,10
0,22
12,1
14,5
12,1
0,34
0,25
26
14
0,18
0,24
R100
0600123
13
250
0,16
0,11
0,37
7,41
8,87
7,41
0,32
0,30
35
19
0,30
0,42
17
470
0,20
0,14
0,90
3,08
3,69
3,08
0,30
0,35
57
31
0,70
1,0
20
710
0,24
0,17
1,5
1,83
2,19
1,83
0,28
0,40
77
63
1,1
1,7
23
1000
0,28
0,19
2,4
1,15
1,38
1,15
0,26
0,40
100
85
1,8
2,6
(2) See the basic assumptions at general information of products.
(3) Final installation with careful single bending into final position.
(4) Initial temperature of conductor before short circuit 70°C, final temperature of conductor after short circuit 160°C.
(5) Initial temperature of PE conductor before short circuit 65°C, final temperature of PE conductor after short circuit maximum 250°C.
(6) Current ratings of 1,5-6 mm
2
conductors allows surface mounting, installation in ducts and in short leading-throughs.
23.07.2014 © Prysmian Group. All rights reserved.
All sizes and values without tolerances are reference values. Specifications are for product as supplied by Prysmian Group; any modification or alteration afterwards of product may give different result.
The information contained within this document must not be copied, reprinted or reproduced in any form, either wholly or in part, without the written consent of Prysmian Group. The information is believed to be correct at the time of issue. Prysmian
Group reserves the right to amend this specification without notice. This specification is not contractually valid unless specifically authorised by Prysmian Group.
1 kV power cables
PROPERTIES
PRODUCT NAME
STK-code and drum
STK-code and spool
STK-code ja coil
CONSTRUCTION DATA (1)
Diameter over cable
Weight
MECHANICAL DATA (2)
Minimum permissible bending radius during laying
Minimum permissible bending radius at final installation (3) mm kg/km
Maximum permissible pulling force with a pulling eye kN
ELECTRICAL DATA (2)
Maximum DC resistance of phase and neutral conductor.
AC resistance of phase and neutral conductor (1)
Maximum DC resistance of PE conductor
Inductance (1)
Operating capacitance (1)
CURRENT RATINGS (2)
In ground
In free air (6)
SHORT CIRCUIT CURRENTS (2)
Maximum permissible short circuit current for one second conductor 20 °C conductor 70 °C conductor 20 °C conductor 70 °C conductor 70 °C phase conductor (4)
PE-conductor (5)
Ω/km
Ω/km
Ω/km mH/km
µF/km kA kA
A
A m m
MCMK
4x1,5/1,5
1 kV
K8/1000
0602172
PK150
0602131
R100
0602192
13
220
0,16
0,11
0,30
26
14
0,18
0,24
12,1
14,5
12,1
0,34
0,25
MCMK
4x2,5/2,5
1 kV
K9/1000
0602143
PK150
0602144
R100
0602193
14
290
0,17
0,12
0,50
35
19
0,30
0,42
7,41
8,87
7,41
0,32
0,30
MCMK
4x6/6
1 kV
K8/500
0602145
K6M/200
0602142
19
550
0,23
0,16
1,2
57
31
0,70
1,0
3,08
3,69
3,08
0,30
0,35
MCMK
4x10/10
RM 1 kV
K11/500
0602146
K7/200
0602100
22
840
0,26
0,18
2,0
77
63
1,1
1,7
1,83
2,19
1,83
0,28
0,40
MCMK
4x16/16
RM 1 kV
K11/500
0602147
25
1200
0,30
0,21
3,2
100
85
1,8
2,6
1,15
1,38
1,15
0,26
0,40
(2) See the basic assumptions at general information of products.
(3) Final installation with careful single bending into final position.
(4) Initial temperature of conductor before short circuit 70°C, final temperature of conductor after short circuit 160°C.
(5) Initial temperature of PE conductor before short circuit 65°C, final temperature of PE conductor after short circuit maximum 250°C.
(6) Current ratings of 1,5-6 mm
2
conductors allows surface mounting, installation in ducts and in short leading-throughs.
23.07.2014 © Prysmian Group. All rights reserved.
All sizes and values without tolerances are reference values. Specifications are for product as supplied by Prysmian Group; any modification or alteration afterwards of product may give different result.
The information contained within this document must not be copied, reprinted or reproduced in any form, either wholly or in part, without the written consent of Prysmian Group. The information is believed to be correct at the time of issue. Prysmian Group reserves the right to amend this specification without notice.
This specification is not contractually valid unless specifically authorised by Prysmian Group.
1 kV power cables
PROPERTIES
PRODUCT NAME
MCMK
3x25/16
AN 1 kV
MCMK
3x35/16
AN 1 kV
MCMK
3x50/25
AN 1 kV
MCMK
3x70/35
AN 1 kV
MCMK
3x95/50
AN 1 kV
MCMK
3x120/70
AN 1 kV
MCMK
3x150/70
AN 1 kV
MCMK
3x185/95
AN 1 kV
MCMK
3x240/120
AN 1 kV
STK-code
CONSTRUCTION DATA (1)
Diameter over cable
0602158
Weight copper cable mm kg/km kg/km
22
800
1100
DELIVERY DATA
Standard delivery lenght
Standard delivery drum m 500
K11
Weight (1)
MECHANICAL DATA (2) cable+drum kg 605
Minimum permissible bending radius during laying
Minimum permissible bending radius at final installation (3)
Maximum permissible pulling force with a pulling grip
Maximum permissible pulling force with a pulling eye
ELECTRICAL DATA (2)
Maximum DC resistance of phase conductor
AC resistance of phase and neutral conductor (1)
Maximum DC resistance of PE conductor
Inductance (1) conductor 20 °C conductor 70 °C conductor 20 °C m m kN kN
Ω/km
Ω/km
Ω/km mH/km
0,27
0,19
1,1
7,5
0,727
0,87
1,15
0,26
µF/km 0,45 Operating capacitance (1)
CURRENT RATINGS (2)
In ground
In free air conductor 70 °C conductor 70 °C
SHORT CIRCUIT CURRENTS (2)
Maximum permissible short circuit current for one second phase conductor (4)
PE-conductor (5)
A
A kA kA
130
107
2,8
2,6
0602159 0602160 0602161 0602162 0602163
24
1050
1400
500
K11
755
0,29
0,21
1,5
10,5
0,524
0,63
1,15
0,26
0,55
160
135
4,0
2,6
28
1460
1950
500
K12
1065
0,34
0,24
2,2
15,0
0,387
0,47
0,727
0,25
0,60
190
160
5,7
4,4
31
2090
2650
500
K14
1440
0,38
0,26
3,1
20,0
0,268
0,32
0,524
0,24
0,65
240
200
8,0
5,7
36
2900
3650
500
K16
2020
0,44
0,30
4,2
20,0
0,193
0,23
0,387
0,24
0,75
285
245
10,9
7,2
38
3730
4550
500
K18
2505
0,46
0,32
5,4
20,0
0,153
0,19
0,268
0,23
0,80
325
280
13,7
10,4
0602164
42
4460
5450
500
K18
2955
0,51
0,35
6,7
20,0
0,124
0,15
0,268
0,23
0,80
370
320
17,2
10,4
0602165
47
5620
6900
500
K20
3790
0,57
0,40
8,3
20,0
0,0991
0,12
0,193
0,23
0,85
420
365
21,2
13,4
0602166
53
7350
8900
500
K24
4900
0,64
0,45
8,5
20,0
0,0754
0,097
0,153
0,23
0,85
480
425
27,5
16,6
(2) See the basic assumptions at general information of products.
(3) Final installation with careful single bending into final position.
(4) Initial temperature of conductor before short circuit 70°C, final temperature of conductor after short circuit 160°C.
(5) Initial temperature of PE conductor before short circuit 65°C, final temperature of PE conductor after short circuit maximum 250°C.
23.07.2014 © Prysmian Group. All rights reserved.
All sizes and values without tolerances are reference values. Specifications are for product as supplied by Prysmian Group; any modification or alteration afterwards of product may give different result.
The information contained within this document must not be copied, reprinted or reproduced in any form, either wholly or in part, without the written consent of Prysmian Group. The information is believed to be correct at the time of issue. Prysmian
Group reserves the right to amend this specification without notice. This specification is not contractually valid unless specifically authorised by Prysmian Group.
1 kV power cables
PROPERTIES
PRODUCT NAME
MCMK
4x25/16
AN 1 kV
MCMK
4x35/16
AN 1 kV
MCMK
4x50/25
AN 1 kV
MCMK
4x70/35
AN 1 kV
MCMK
4x95/50
AN 1 kV
MCMK
4x120/70
AN 1 kV
MCMK
4x150/70
AN 1 kV
MCMK
4x185/95
AN 1 kV
MCMK
4x240/120
AN 1 kV
STK-code
CONSTRUCTION DATA (1)
Diameter over cable
0601858 0601859 0601860 0601861 0601862
Weight copper cable mm kg/km kg/km
24
1020
1400
DELIVERY DATA
Standard delivery lenght
Standard delivery drum m 500
K11
Weight (1)
MECHANICAL DATA (2) cable+drum kg 755
Minimum permissible bending radius during laying
Minimum permissible bending radius at final installation (3)
Maximum permissible pulling force with a pulling grip
Maximum permissible pulling force with a pulling eye
ELECTRICAL DATA (2)
Maximum DC resistance of phase and neutral conductor.
AC resistance of phase and neutral conductor (1)
Maximum DC resistance of
PE-conductor
Inductance (1) conductor 20 °C conductor 70 °C conductor 20 °C m m kN kN
Ω/km
Ω/km
Ω/km mH/km
0,29
0,20
1,5
10,0
0,727
0,87
1,15
0,28
0,45 Operating capacitance (1)
CURRENT RATINGS (2)
In ground
In free air conductor 70 °C conductor 70 °C
SHORT CIRCUIT CURRENTS (2)
Maximum permissible short circuit current for one second phase and neutral conductor (4)
PE-conductor (5)
µF/km kA kA
A
A
130
107
2,8
2,6
26
1350
1800
500
K12
990
0,32
0,22
2,1
14,0
0,524
0,63
1,15
0,27
0,45
160
135
4,0
2,6
32
1870
2500
500
K14
1365
0,39
0,28
3,0
20,0
0,387
0,46
0,727
0,27
0,50
190
160
5,7
4,4
35
2690
3400
500
K16
1895
0,42
0,30
4,2
20,0
0,268
0,32
0,524
0,26
0,55
240
200
8,0
5,7
40
3730
4650
500
K18
2555
0,48
0,34
5,7
20,0
0,193
0,23
0,387
0,26
0,65
285
245
10,9
7,2
0601863
43
4780
5800
500
K20
3240
0,52
0,36
7,2
20,0
0,153
0,19
0,268
0,26
0,70
325
280
13,7
10,4
0601864
48
5750
7050
500
K22
3935
0,58
0,40
8,5
20,0
0,124
0,15
0,268
0,26
0,70
370
320
17,2
10,4
0601865
54
7220
8850
500
K24
4875
0,65
0,46
8,5
20,0
0,0991
0,12
0,193
0,26
0,75
420
365
21,2
13,4
0601866
60
9440
11400
500
K24
6150
0,72
0,51
8,5
20,0
0,0754
0,097
0,153
0,26
0,80
480
425
27,5
16,6
(2) See the basic assumptions at general information of products.
(3) Final installation with careful single bending into final position.
(4) Initial temperature of conductor before short circuit 70°C, final temperature of conductor after short circuit 160°C.
(5) Initial temperature of PE conductor before short circuit 65°C, final temperature of PE conductor after short circuit maximum 250°C.
23.07.2014 © Prysmian Group. All rights reserved.
All sizes and values without tolerances are reference values. Specifications are for product as supplied by Prysmian Group; any modification or alteration afterwards of product may give different result.
The information contained within this document must not be copied, reprinted or reproduced in any form, either wholly or in part, without the written consent of Prysmian Group. The information is believed to be correct at the time of issue. Prysmian Group reserves the right to amend this specification without notice.
This specification is not contractually valid unless specifically authorised by Prysmian Group.