RATED VOLTAGE APPLICATION CONSTRUCTION Plastic

MCMK

Plastic-sheathed screen-protected 1 kV power cable

RATED VOLTAGE

Uo/U = 0,6/1 kV, Um = 1,2 kV

APPLICATION

For fixed installation indoors, outdoors and underground; as well as in building structures e.g. directly in concrete (but not in sliding joints).

Not for installations subject to severe electrical interference.

For EMC-applications see cable type MCCMK.

And if there is need for low smoke halogen-free power cable, see cable types MCMK-LSZH and XCMK-HF.

Highest permissible conductor temperature:

• continuous operation

• short circuit (duration up to 5 s)

70 °C

160 °C

Lowest recommended temperature during laying: -15 °C

CONSTRUCTION

Conductor 1,5-6 mm²: solid annealed copper wire

10-16 mm²: stranded annealed copper wire

25-240 mm²: sector shaped annealed copper wire

Insulation Lead-free PVC compound

Laying up Insulated conductors stranded together

Filling sheath 1,5-16 mm²: Lead-free filling compound

PE-conductor Copper wire layer and copper wires/tape binding

Outer sheath Black lead-free PVC compound

IDENTIFICATION OF CORES

Colours of inner cores:

2-cores

3-cores

4-cores

Blue, brown

Brown, black, grey

Blue, brown, black, grey

STANDARDS

SFS 4880

HD 603-3F

IEC 60502-1

1,5-240 mm²: IEC / EN 60332-1

25-240 mm²: IEC / EN 60332-3

CERTIFICATES, APPROVALS

(SGS Fimko)

The cable does not contain any substances on the

REACH/SVHC -list.

All substances of the cable meet the requirements of RoHS directive.

CUSTOMS CODE

8554 49 91

23.07.2014 © Prysmian Group. All rights reserved.

All sizes and values without tolerances are reference values. Specifications are for product as supplied by Prysmian Group; any modification or alteration afterwards of product may give different result.

The information contained within this document must not be copied, reprinted or reproduced in any form, either wholly or in part, without the written consent of Prysmian Group. The information is believed  to be  correct at the time of issue. Prysmian Group reserves the right to amend this specification without notice.

This specification is not contractually valid unless specifically authorised by Prysmian Group.

1 kV power cables

MCMK 3- and 4-cores

PROPERTIES

PRODUCT NAME

STK-code and drum

STK-code and spool

STK-code and coil

CONSTRUCTION DATA (1)

Diameter over cable

Weight mm kg/km

MECHANICAL DATA (2)

Minimum permissible bending radius during laying

Minimum permissible bending radius at final installation (3)

Maximum permissible pulling force with a pulling eye

ELECTRICAL DATA (2)

Maximum DC resistance of phase and neutral conductor.

AC resistance of phase and neutral conductor (1)

Maximum DC resistance of

PE-conductor

Inductance (1) conductor 20 °C conductor 70 °C conductor 20 °C m m kN

Ω/km

Ω/km

Ω/km mH/km

Operating capacitance (1)

CURRENT RATINGS (2)

µF/km

In ground

In free air (6) conductor 70 °C conductor 70 °C

SHORT CIRCUIT CURRENTS (2)

Maximum permissible short circuit current for one second phase conductor (4)

PE-conductor (5)

A

A kA kA

MCMK

2x1,5/1,5

1 kV

MCMK

2x2,5/2,5

1 kV

K8/1000

0602122

PK200

0602111

R100

0602112

K8/1000

0602123

PK150

0602114

R100

0602113

MCMK

2x6/6

1 kV

K8/500

0602125

12

170

0,15

0,10

0,15

12,1

14,5

12,1

0,34

0,25

26

15

0,18

0,24

13

220

0,16

0,11

0,25

7,41

8,87

7,41

0,32

0,30

35

20

0,30

0,42

17

400

0,20

0,14

0,60

3,08

3,69

3,08

0,30

0,35

57

34

0,70

1,0

MCMK

2x10/10

RM 1 kV

K9/500

0602126

MCMK

3x1,5/1,5

1 kV

K8/1000

0602152

MCMK

3x2,5/2,5

1 kV

K8/1000

0602153

MCMK

3x6/6

1 kV

K8/500

0602155

MCMK

3x10/10

RM 1 kV

K9/500

0602156

MCMK

3x16/16

RM 1 kV

K11/500

0602157

20

610

0,24

0,17

1,0

1,83

2,19

1,83

0,28

0,40

77

67

1,1

1,7

R100

0600122

12

190

0,15

0,10

0,22

12,1

14,5

12,1

0,34

0,25

26

14

0,18

0,24

R100

0600123

13

250

0,16

0,11

0,37

7,41

8,87

7,41

0,32

0,30

35

19

0,30

0,42

17

470

0,20

0,14

0,90

3,08

3,69

3,08

0,30

0,35

57

31

0,70

1,0

20

710

0,24

0,17

1,5

1,83

2,19

1,83

0,28

0,40

77

63

1,1

1,7

23

1000

0,28

0,19

2,4

1,15

1,38

1,15

0,26

0,40

100

85

1,8

2,6

(2) See the basic assumptions at general information of products.

(3) Final installation with careful single bending into final position.

(4) Initial temperature of conductor before short circuit 70°C, final temperature of conductor after short circuit 160°C.

(5) Initial temperature of PE conductor before short circuit 65°C, final temperature of PE conductor after short circuit maximum 250°C.

(6) Current ratings of 1,5-6 mm

2

conductors allows surface mounting, installation in ducts and in short leading-throughs.

23.07.2014 © Prysmian Group. All rights reserved.

All sizes and values without tolerances are reference values. Specifications are for product as supplied by Prysmian Group; any modification or alteration afterwards of product may give different result.

The information contained within this document must not be copied, reprinted or reproduced in any form, either wholly or in part, without the written consent of Prysmian Group. The information is believed  to be  correct at the time of issue. Prysmian

Group reserves the right to amend this specification without notice. This specification is not contractually valid unless specifically authorised by Prysmian Group.

1 kV power cables

MCMK 5-cores

PROPERTIES

PRODUCT NAME

STK-code and drum

STK-code and spool

STK-code ja coil

CONSTRUCTION DATA (1)

Diameter over cable

Weight

MECHANICAL DATA (2)

Minimum permissible bending radius during laying

Minimum permissible bending radius at final installation (3) mm kg/km

Maximum permissible pulling force with a pulling eye kN

ELECTRICAL DATA (2)

Maximum DC resistance of phase and neutral conductor.

AC resistance of phase and neutral conductor (1)

Maximum DC resistance of PE conductor

Inductance (1)

Operating capacitance (1)

CURRENT RATINGS (2)

In ground

In free air (6)

SHORT CIRCUIT CURRENTS (2)

Maximum permissible short circuit current for one second conductor 20 °C conductor 70 °C conductor 20 °C conductor 70 °C conductor 70 °C phase conductor (4)

PE-conductor (5)

Ω/km

Ω/km

Ω/km mH/km

µF/km kA kA

A

A m m

MCMK

4x1,5/1,5

1 kV

K8/1000

0602172

PK150

0602131

R100

0602192

13

220

0,16

0,11

0,30

26

14

0,18

0,24

12,1

14,5

12,1

0,34

0,25

MCMK

4x2,5/2,5

1 kV

K9/1000

0602143

PK150

0602144

R100

0602193

14

290

0,17

0,12

0,50

35

19

0,30

0,42

7,41

8,87

7,41

0,32

0,30

MCMK

4x6/6

1 kV

K8/500

0602145

K6M/200

0602142

19

550

0,23

0,16

1,2

57

31

0,70

1,0

3,08

3,69

3,08

0,30

0,35

MCMK

4x10/10

RM 1 kV

K11/500

0602146

K7/200

0602100

22

840

0,26

0,18

2,0

77

63

1,1

1,7

1,83

2,19

1,83

0,28

0,40

MCMK

4x16/16

RM 1 kV

K11/500

0602147

25

1200

0,30

0,21

3,2

100

85

1,8

2,6

1,15

1,38

1,15

0,26

0,40

(2) See the basic assumptions at general information of products.

(3) Final installation with careful single bending into final position.

(4) Initial temperature of conductor before short circuit 70°C, final temperature of conductor after short circuit 160°C.

(5) Initial temperature of PE conductor before short circuit 65°C, final temperature of PE conductor after short circuit maximum 250°C.

(6) Current ratings of 1,5-6 mm

2

conductors allows surface mounting, installation in ducts and in short leading-throughs.

23.07.2014 © Prysmian Group. All rights reserved.

All sizes and values without tolerances are reference values. Specifications are for product as supplied by Prysmian Group; any modification or alteration afterwards of product may give different result.

The information contained within this document must not be copied, reprinted or reproduced in any form, either wholly or in part, without the written consent of Prysmian Group. The information is believed  to be  correct at the time of issue. Prysmian Group reserves the right to amend this specification without notice.

This specification is not contractually valid unless specifically authorised by Prysmian Group.

1 kV power cables

MCMK 3½-cores

PROPERTIES

PRODUCT NAME

MCMK

3x25/16

AN 1 kV

MCMK

3x35/16

AN 1 kV

MCMK

3x50/25

AN 1 kV

MCMK

3x70/35

AN 1 kV

MCMK

3x95/50

AN 1 kV

MCMK

3x120/70

AN 1 kV

MCMK

3x150/70

AN 1 kV

MCMK

3x185/95

AN 1 kV

MCMK

3x240/120

AN 1 kV

STK-code

CONSTRUCTION DATA (1)

Diameter over cable

0602158

Weight copper cable mm kg/km kg/km

22

800

1100

DELIVERY DATA

Standard delivery lenght

Standard delivery drum m 500

K11

Weight (1)

MECHANICAL DATA (2) cable+drum kg 605

Minimum permissible bending radius during laying

Minimum permissible bending radius at final installation (3)

Maximum permissible pulling force with a pulling grip

Maximum permissible pulling force with a pulling eye

ELECTRICAL DATA (2)

Maximum DC resistance of phase conductor

AC resistance of phase and neutral conductor (1)

Maximum DC resistance of PE conductor

Inductance (1) conductor 20 °C conductor 70 °C conductor 20 °C m m kN kN

Ω/km

Ω/km

Ω/km mH/km

0,27

0,19

1,1

7,5

0,727

0,87

1,15

0,26

µF/km 0,45 Operating capacitance (1)

CURRENT RATINGS (2)

In ground

In free air conductor 70 °C conductor 70 °C

SHORT CIRCUIT CURRENTS (2)

Maximum permissible short circuit current for one second phase conductor (4)

PE-conductor (5)

A

A kA kA

130

107

2,8

2,6

0602159 0602160 0602161 0602162 0602163

24

1050

1400

500

K11

755

0,29

0,21

1,5

10,5

0,524

0,63

1,15

0,26

0,55

160

135

4,0

2,6

28

1460

1950

500

K12

1065

0,34

0,24

2,2

15,0

0,387

0,47

0,727

0,25

0,60

190

160

5,7

4,4

31

2090

2650

500

K14

1440

0,38

0,26

3,1

20,0

0,268

0,32

0,524

0,24

0,65

240

200

8,0

5,7

36

2900

3650

500

K16

2020

0,44

0,30

4,2

20,0

0,193

0,23

0,387

0,24

0,75

285

245

10,9

7,2

38

3730

4550

500

K18

2505

0,46

0,32

5,4

20,0

0,153

0,19

0,268

0,23

0,80

325

280

13,7

10,4

0602164

42

4460

5450

500

K18

2955

0,51

0,35

6,7

20,0

0,124

0,15

0,268

0,23

0,80

370

320

17,2

10,4

0602165

47

5620

6900

500

K20

3790

0,57

0,40

8,3

20,0

0,0991

0,12

0,193

0,23

0,85

420

365

21,2

13,4

0602166

53

7350

8900

500

K24

4900

0,64

0,45

8,5

20,0

0,0754

0,097

0,153

0,23

0,85

480

425

27,5

16,6

(2) See the basic assumptions at general information of products.

(3) Final installation with careful single bending into final position.

(4) Initial temperature of conductor before short circuit 70°C, final temperature of conductor after short circuit 160°C.

(5) Initial temperature of PE conductor before short circuit 65°C, final temperature of PE conductor after short circuit maximum 250°C.

23.07.2014 © Prysmian Group. All rights reserved.

All sizes and values without tolerances are reference values. Specifications are for product as supplied by Prysmian Group; any modification or alteration afterwards of product may give different result.

The information contained within this document must not be copied, reprinted or reproduced in any form, either wholly or in part, without the written consent of Prysmian Group. The information is believed  to be  correct at the time of issue. Prysmian

Group reserves the right to amend this specification without notice. This specification is not contractually valid unless specifically authorised by Prysmian Group.

1 kV power cables

MCMK 4½-cores

PROPERTIES

PRODUCT NAME

MCMK

4x25/16

AN 1 kV

MCMK

4x35/16

AN 1 kV

MCMK

4x50/25

AN 1 kV

MCMK

4x70/35

AN 1 kV

MCMK

4x95/50

AN 1 kV

MCMK

4x120/70

AN 1 kV

MCMK

4x150/70

AN 1 kV

MCMK

4x185/95

AN 1 kV

MCMK

4x240/120

AN 1 kV

STK-code

CONSTRUCTION DATA (1)

Diameter over cable

0601858 0601859 0601860 0601861 0601862

Weight copper cable mm kg/km kg/km

24

1020

1400

DELIVERY DATA

Standard delivery lenght

Standard delivery drum m 500

K11

Weight (1)

MECHANICAL DATA (2) cable+drum kg 755

Minimum permissible bending radius during laying

Minimum permissible bending radius at final installation (3)

Maximum permissible pulling force with a pulling grip

Maximum permissible pulling force with a pulling eye

ELECTRICAL DATA (2)

Maximum DC resistance of phase and neutral conductor.

AC resistance of phase and neutral conductor (1)

Maximum DC resistance of

PE-conductor

Inductance (1) conductor 20 °C conductor 70 °C conductor 20 °C m m kN kN

Ω/km

Ω/km

Ω/km mH/km

0,29

0,20

1,5

10,0

0,727

0,87

1,15

0,28

0,45 Operating capacitance (1)

CURRENT RATINGS (2)

In ground

In free air conductor 70 °C conductor 70 °C

SHORT CIRCUIT CURRENTS (2)

Maximum permissible short circuit current for one second phase and neutral conductor (4)

PE-conductor (5)

µF/km kA kA

A

A

130

107

2,8

2,6

26

1350

1800

500

K12

990

0,32

0,22

2,1

14,0

0,524

0,63

1,15

0,27

0,45

160

135

4,0

2,6

32

1870

2500

500

K14

1365

0,39

0,28

3,0

20,0

0,387

0,46

0,727

0,27

0,50

190

160

5,7

4,4

35

2690

3400

500

K16

1895

0,42

0,30

4,2

20,0

0,268

0,32

0,524

0,26

0,55

240

200

8,0

5,7

40

3730

4650

500

K18

2555

0,48

0,34

5,7

20,0

0,193

0,23

0,387

0,26

0,65

285

245

10,9

7,2

0601863

43

4780

5800

500

K20

3240

0,52

0,36

7,2

20,0

0,153

0,19

0,268

0,26

0,70

325

280

13,7

10,4

0601864

48

5750

7050

500

K22

3935

0,58

0,40

8,5

20,0

0,124

0,15

0,268

0,26

0,70

370

320

17,2

10,4

0601865

54

7220

8850

500

K24

4875

0,65

0,46

8,5

20,0

0,0991

0,12

0,193

0,26

0,75

420

365

21,2

13,4

0601866

60

9440

11400

500

K24

6150

0,72

0,51

8,5

20,0

0,0754

0,097

0,153

0,26

0,80

480

425

27,5

16,6

(2) See the basic assumptions at general information of products.

(3) Final installation with careful single bending into final position.

(4) Initial temperature of conductor before short circuit 70°C, final temperature of conductor after short circuit 160°C.

(5) Initial temperature of PE conductor before short circuit 65°C, final temperature of PE conductor after short circuit maximum 250°C.

23.07.2014 © Prysmian Group. All rights reserved.

All sizes and values without tolerances are reference values. Specifications are for product as supplied by Prysmian Group; any modification or alteration afterwards of product may give different result.

The information contained within this document must not be copied, reprinted or reproduced in any form, either wholly or in part, without the written consent of Prysmian Group. The information is believed  to be  correct at the time of issue. Prysmian Group reserves the right to amend this specification without notice.

This specification is not contractually valid unless specifically authorised by Prysmian Group.