ElectricalDesignGuideforthedevelopingworld Developed and Compiled by Andy Engebretson, P.E. Staff Engineer Engineering Ministries International With Contributions from Jim Cathey, Kirk Singleton, Ed Lobnitz, Ruedi Tobler, Bob Gresham, Bill Wright, Larry Bentley Revised November 2014 1. Table of Contents 2. Introduction ................................................................................................................................ 2 3. Questions To Consider Before & During an EMI Trip ..................................................................... 3 4. Typical Electrical Design ............................................................................................................... 4 4.1 Electrical Symbols ......................................................................................................................... 4 4.2 Single line Diagram ....................................................................................................................... 4 4.3 Electrical Load Study..................................................................................................................... 4 4.4 Site Electrical Plan and Panel Schedules ...................................................................................... 5 4.5 Building Wiring Diagrams ............................................................................................................. 7 4.6 Panel Schedules ............................................................................................................................ 7 4.7 Circuit Breaker and Wire Size Determination .............................................................................. 8 4.8 Voltage Drop Calculation .............................................................................................................. 8 4.9 Grounding and Bonding................................................................................................................ 9 4.10 Written Report ............................................................................................................................. 9 5. Solar Design .............................................................................................................................. 10 5.1 Solar Sizing Concepts .................................................................................................................. 10 5.2 Rough Cost for Solar Equipment ................................................................................................ 10 6. Hospital Electrical Design ........................................................................................................... 11 6.1 Equipment List ............................................................................................................................ 11 6.2 Equipment Frequency Considerations ....................................................................................... 11 6.3 Air Conditioning and Heating ..................................................................................................... 11 6.4 Code Requirements .................................................................................................................... 11 6.5 Transfer Switches ....................................................................................................................... 12 6.6 Other Systems ............................................................................................................................ 12 Reference Documents EMI Pre-Trip and During Trip Questions Electrical Voltage & Output Worldwide Standards EMI Diesel Generators Overview EMI Electrical Power Density and Load Demand Factors EMI Electrical Report Example EMI Site Electrical Load Study Example EMI Solar vs Generator vs Utility Cost Comparison EMI Wire Chart Ground Conductor Sizing Ground Rod Detail Grounding & Bonding Diagram World Solar Isolation Maps Reference Drawings Electrical Legend Electrical One-Line Diagram Generator Room Electrical Plans Panel Schedules - MDP, PPG, PPPH Panel Schedules - PPA, SPAG Electrical Site Plan Basement Lighting Wiring Diagram Basement Power Wiring Diagram Ground Floor Lighting Wiring Diagram Ground Floor Power Wiring Diagram EMI Electrical Design Guide 1 2. Introduction Electrical Engineers on an EMI trip can expect to encounter a variety of unique design challenges that will require creativity, flexibility and good engineering judgment. EMI projects are all different and it would be impossible to try and address every design challenge that could be encountered. Therefore, this design guide is created to give the designer an idea of the general format of an EMI electrical design. This design guide will provide a lot of helpful information, but the designer must do their own research prior to the trip and while on the field and use their best judgment based on the information gathered during the trip. Data collected in the field that is different from this design guide shall take priority so long as safety of the public is maintained. Numerous supplemental documents and drawings are referenced throughout this design guide (see ‘Reference Documents’ and ‘Reference Drawings’). Some countries have no established electrical code, so many of the design principles presented in this document are adapted from the NFPA 70 National Electrical Code and are believed to be in accordance with sound design. However, if there is any variance from any governing codes applicable to the site location, the governing codes take priority and the installation shall follow the latest edition of those codes regardless of any and all specifications explicitly or implicitly set forth in this document. EMI Electrical Design Guide 2 3. Questions To Consider Before & During an EMI Trip Prior to embarking on an EMI trip the electrical designer should become familiar with the resources in this design guide. The document labeled ‘EMI Pre-Trip and During-Trip Electrical Engineer Questions’ is a list of questions that will help the designer understand and gather the pertinent information prior to and during the time in-country. EMI Electrical Design Guide 3 4. Typical Electrical Design The example design in this design guide describes the basic elements of an EMI electrical design and includes drawings and calculations. 4.1 Electrical Symbols The drawing labeled ‘Electrical Legend’ shows the typical symbols that are used to represent electrical devices. This is not an exhaustive list, so the designer may need to research the appropriate symbol if it is not included on this drawing. Also, if the designer is able to acquire a local electrical drawing and the symbols are different than shown on the EMI drawing, the symbols on the local drawing should be used. 4.2 Single line Diagram The drawing labeled ‘Electrical Single line Diagram’ shows a typical graphical representation of an entire electrical system. A Single line is usually one of the first drawings created in a design as it captures the information on an existing system and helps the designer quickly see how a system can be modified. Power sources are shown at the top of the page and the loads are at the bottom. The two power sources in this example are the public utility and a backup generator. A manual transfer switch is used to transfer between the two sources. The public utility through a transformer is the primary power source for the site. The transformer is sized to accommodate the loads for the Phase 1 and Phase 2 buildings (see ‘EMI Site Electrical Load Study Example’ for a description of the loads). Although the generator is the backup power source for the entire site, it is only large enough to handle the Phase 1 loads. The client will need to upgrade the generator or select the loads for which the generator will provide backup power (up to 100kW) when Phase 2 is built. If the client had requested that only certain loads be included on the backup generator, separate circuits and panels would need to be designed for the loads on back-up power. Wire and breaker sizes to the Main Distribution Panel (MDP) and the main building panels (PPA and PPPH) are shown on the single line diagram. The panels and sub-panels in each building are labeled and shown in more detail on the ‘Wiring Diagram’ and ‘Panel Schedules’ drawings. 4.3 Electrical Load Study Early in the design cycle a site electrical load study should be created to give the designer and the client an idea of the overall size of the electrical system. The ‘EMI Electrical Load Study Example’ summarizes the loads for the facility being used as an example in this design guide. The design is separated into Phase 1 and Phase 2. Phase 1 includes the first two levels (basement and ground levels) of the accommodations building and all the site lighting and soccer field lights. Two additional floors will be added to the accommodations building in Phase 2. The general load for the building is calculated by multiplying the area of the building by the power density for lights and outlets for a particular facility (see ‘EMI Electrical Power Density and Load Demand Factors’ for power densities). These load densities are general guidelines and may not be appropriate in some countries. The designer should try to measure lighting densities for similar EMI Electrical Design Guide 4 facilities in the area and match the design to these. The “special loads” for each building are specified in the last column and are calculated by multiplying the number of “special loads” (indicated in parentheses) by their respective power consumption found in the ‘Device Power Consumption’ table at the bottom of the spreadsheet. The maximum demand is the sum of the “general” and “special loads”. Once all the loads have been calculated, a demand factor must be applied. Referring again to the ‘EMI Electrical Power Density and Load Demand Factors’, a 50% demand factor should be applied to all “general loads” over 3kVA (apply 75% for hospitals) and a 100% demand factor to “special loads”. In this example, a 75% demand factor is applied to the special loads because the client specified that no more than 75% of the air conditioners (which are classified as “special load” devices) would be used simultaneously. Pumps are listed below the demand factor and 100% of their load is added to the total demand. 4.4 Site Electrical Plan and Panel Schedules The drawing labeled ‘Site Electrical Plan’ shows all the main feeder cables and their routing on the site in addition to all the site lighting. The names and locations of the main panels (MDP, PPG, PPA and PPPH) are also specified on the ‘Site Electrical Plan’. The drawing labeled ‘Generator Room Electrical Plans’ is a basic layout for the generator building and shows the location of the MDP, PPG and Transfer Switch. The drawing labeled ‘Panel Schedules – MDP, PPG, PPPH’ shows the layout of the main distribution panel (MDP), the Generator power panel (PPG), and the pump house power panel (PPPH). The MDP specifies all the main breakers feeding the subpanels. Picture 1 shows an example of a main distribution panel layout. Figure 1: MDP Layout EMI Electrical Design Guide 5 PPG is a single phase panel schedule called a consumer unit (see Figure 2 below). Consumer units are common in countries that have had European influence. The breakers mount to a din rail and the main breaker feeds power to the branch circuit breakers through jumper wires or jumper bars. Figure 2: PPG PPPH is a three phase panel schedule. Picture 3 shows a three phase panel with the main breaker at the bottom of the panel. Three phase panels can either contain bus bar like the one below, or they may look more like the consumer unit with jumper wires or jumper bars connecting the main breaker to the branch circuit breakers. The load calculations for individual panels are described in section 4.6 ‘Panel Schedules’ Figure 3: PPPH EMI Electrical Design Guide 6 4.5 Building Wiring Diagrams The building wiring diagrams (see drawings ‘Wiring Diagram - Basement’ and ‘Wiring Diagram Ground Floor’) show the general location of all the electrical devices and how they are connected together. The home runs to the panel board are also shown on the wiring diagrams. Each floor plan will have two sheet of electrical wiring to avoid overcrowding the drawing. One sheet shows the lighting wiring and the second shows the power wiring. 4.6 Panel Schedules The drawing labeled ‘Panel Schedules - PPA, SPAG’ shows two typical three-phase panel schedules and PPG is a typical single-phase panel schedule. PPA is the main panel schedule for the building and is located in the Basement Worker’s Room. SPAG is the ground floor subpanel and is located in the ground floor janitor room as shown on the building wiring diagrams. At the top of the panel schedule all the pertinent information about the panel is displayed (Mark, Location, Main Breaker etc.). The middle of the panel is a graphical representation of the 3-Phase bus bars and their connection to each circuit breaker. Circuits #1, 3, 5 on panel PPA are shown with a line connecting them together to represent a 3-phase circuit breaker. The total power consumption of the 3-Phase loads is evenly distributed across the three phases. For example the total load on SPAG is 27.498kVA, or 9.166kVA per phase. The wire size, circuit breaker size (CB Trip), load size (Wattage) and a description of the equipment being served by that circuit are all shown on the panel layout. The load on each circuit is calculated by summing up the power consumption of all the electrical devices connected to that circuit. For example, circuit #2 on panel PPA is feeding two single phase air conditioners for the small classrooms in the basement of the Accommodations. Each air conditioner is rated at 1,232VA and they are connected to phase A, so 2,464VA is the value placed for phase A on circuit #2. PPA is a main panel with sub-panels connected to it so the total load on the panel is calculated in the table labeled ‘Electrical Calculations (Accommodations)’ (reference spreadsheet ‘Panel Schedules PPA, SPAG’). The general load is calculated by multiplying the area of the building (the basement and ground floors) by the power density for lights and outlets (reference ‘EMI Electrical Power Density and Load Demand Factors’). A 50% demand factor is then applied to the general load. The special loads are calculated and a 75% demand factor is applied to them. Usually special loads do not have a demand factor applied, but in this case the client specified that no more than 75% of the “special load” devices (primarily air conditioners) would be used simultaneously. The future loads are estimated and added to the general and special loads to get the net total. In order to find the main circuit breaker size for the panel, the current is calculated and multiplied by 1.25 in order to avoid nuisance tripping. The next standard breaker size is then selected as the main breaker for the panel. When significant loads will be added to a panel in the future, it is advisable to design panels, breakers and wire sizes for future loads so that panels, breakers and wires do not have to be replaced when future phases are added. The ‘Summary’ table shows the total load (kVA) and current (Amps) on each phase. The total load on the ‘Summary’ table will be larger than the ‘Electrical Calculations’ table because it does not include the demand factor. The primary purpose of the ‘Summary’ table is to ensure that each phase has a similar amount of load on it, thus creating a balanced load. EMI Electrical Design Guide 7 4.7 Circuit Breaker and Wire Size Determination In order to demonstrate how to determine the circuit breaker and wire sizes, circuit #2 on panel PPA will be used as an example. The total load for circuit #2 on panel PPA in the drawing labeled ‘Panel Schedules – PPA, SPAG’ is 2,464VA. The circuit breaker size and wire size can now be determined by calculating the maximum current through the circuit: Before selecting a breaker size, a safety factor of 25% should be applied to the maximum current to avoid nuisance tripping: The next standard breaker size larger than the final current calculated is then selected for the circuit. In this case a 15Amp breaker would suffice. Circuit breakers generally come in standard sizes, so during the trip the designer should determine the standard sizes available in the area. With the breaker size selected, the wire size for the circuit must now be determined by referencing the ‘EMI Wire Chart’. The circuit breaker is protecting the wire, so wire that is able to carry 15Amps of current or more should be used on this circuit. In this example, 2.5mm2 wire was selected because column 3 of the EMI Wire Chart shows that 2.5mm2 copper wire is capable of carrying 22 amps. The same calculation above can be followed for the three-phase loads except the voltage would be the phase to phase voltage (380V) and the current is calculated as follows: The remainder of the EMI Wire Chart is explained as follows: Column 1 shows the American Wire Gauge (AWG) sizes. Most countries use mm2 for wire sizes as shown in column 2. Column 3 shows the current rating of copper wire that has an insulation rating of 75℃ since this is the most commonly used wire internationally. Column 4 shows the current rating of aluminum wire with a 75℃ insulation rating. The resistance factor used to calculate voltage drop is listed in column 5 and the physical characteristics of the wire are shown in columns 6-10. 4.8 Voltage Drop Calculation Voltage drop must be calculated in situations where the circuit conductors span large distances. If the voltage drop is too great (greater than 4%), the conductor size must be increased to maintain the voltage and current between the points. The calculations for a single-phase circuit and a three-phase circuit are slightly different. Single-phase voltage drop calculation: D EMI Electrical Design Guide 8 D D% S RCE Three-phase voltage drop calculation: D D D% S VD VD% L R I VSOURCE RCE = Voltage drop in Volts = Percentage of voltage drop, but is commonly called “voltage drop” = One way length of the circuits feeder (in meters) = Resistance factor of the wire in ohms/kilometer (see EMI Wire Chart) = Current in Amps = Voltage of the circuit at the source of power (i.e. 110, 220, 380 V …) If we continue with the example above using circuit #2 in panel PPA on drawing ‘Panel Schedules PPA, SPAG’ and assume a distance of 40 meters from the panel to the air conditioners and a 2.5mm2 wire, the voltage drop would be: D% Since the voltage drop is less than 4% on this branch circuit the wire size chosen is adequate. 4.9 Grounding and Bonding The Reference Document ‘Ground Conductor Sizing’ shows the size of the ground conductor needed for the corresponding feeder conductors. The ‘Ground Rod Detail’ shows a typical ground rod installation, and the ‘Grounding & Bonding Diagram’ identifies the components of a grounded system. 4.10 Written Report The document ‘EMI Electrical Report Example’ is an example of the electrical section of an EMI report. Typically, the electrical section of the report is around 1-3 pages in length and should be a high-level summary of the designers intent. The report should not include technical details, but should only reference drawings and spreadsheets for the technical details. A copy of the EMI Site Electrical Load Study should also be included in the report as an Appendix. EMI Electrical Design Guide 9 5. Solar Design 5.1 Solar Sizing Concepts When sizing solar panels for a system, one must first determine the total system energy needs (Et = Watts x Time) per day. This energy must be harvested during the window of usable sunlight (about 7.5 hours at a latitude of less than +/-15 degrees). The Reference Document labeled ‘World Solar Insolation Maps’ shows the equivalent sun hours on the surface of the earth. The system efficiency is about 70%, so the solar panel wattage (P) is estimated as: P = Et / (7.5 x 0.7) Charge controllers must be sized to match the solar panel wattage, P. Inverters must be sized to match the maximum power demand expected at any point during the day. Batteries must be sized to store the total energy (Eb = watts x time) required outside the solar harvest window. Since a battery efficiency of about 80% is typical, and since a deep cycle battery can be safely cycled to about 50% depth of discharge (DOD) the battery bank W-h rating is estimated as: W-h = Eb / (0.8 x 0.5) A 100 A-h, 12V battery is a 1200 W-h battery. 5.2 Rough Cost for Solar Equipment The following table is a rough estimate of the cost of the equipment needed in a typical solar system (Year 2011 Values). These costs are for the USA, so 30% may need to be added in other countries. These costs should be checked with a local distributor while in country. Also add about 20% of system cost to cover solar panel mounts, battery racks, wiring and switch gear. Item Cost Solar panels 3500 $/kW Charge Controller 300 $/kW Inverter 800 $/kW Batteries 200 $/kW-h Many Ministries would like to know how much a solar system would cost compared to the utility or using a generator. The document called ‘EMI Solar vs Generator vs Utility Cost Comparison’ can be used to calculate a rough estimate of the initial and on-going cost of each system. The cells highlighted in yellow are the variables the designer must input for the specific project. The graph shows the cost of each system over 25 years. The steps in the solar cost graph represent the purchase of new batteries every 5 years. EMI Electrical Design Guide 10 6. Hospital Electrical Design 6.1 Equipment List A major part of hospital/clinic design deals with providing the correct voltage, phase, ampacity, frequency and location for each piece of equipment. An equipment list and specifications from the client is extremely important. This list usually requires some research, consulting and guessing by the owner but it must be part of the design and documentation. The equipment list is also needed by the other design team members for A/C requirements, plumbing requirements, architectural space needs, structural considerations, etc. Specialized equipment in hospitals and clinics is much more extensive than any other type of facility design. In addition to the equipment, special room layouts, lighting and accessories will be required. Equipment suppliers should be contacted for these special pieces of equipment and wiring layouts. Examples of equipment in this category are: CAT Scans, X-Rays, MRI’s, .R. Exam Lights, O.R. special equipment (ie. portable x-ray), Laboratory Equipment, and Intensive Care Suite special equipment (ie. monitoring equipment). 6.2 Equipment Frequency Considerations Equipment frequency (50Hz vs. 60Hz) must be clarified before design can proceed. Equipment is often donated from the US with 60Hz requirements but at the same time the client will also want to use local 50Hz equipment. If the utility service frequency is 50Hz, motor-driven 60Hz equipment will not work unless a 50 to 60Hz converter is used. The equipment list should indicate where the equipment is to be obtained to force a decision on frequency. In addition, equipment designed by the team must specify the correct frequency depending on where it will be purchased/donated. 6.3 Air Conditioning and Heating Air Conditioning and Heating are often the largest load requirement in a hospital or clinic, so it is important to determine which areas specifically will be air conditioned, heated and ventilated and what type of equipment will be used (window units, split systems, central systems, ceiling fans, etc.). 6.4 Code Requirements NEC (NFPA 70), Article 517 – Health Care Facilities should be reviewed before the site visit. It may not be possible, or desirable, to follow this code exactly, but it should be used as a basis of design. Any downgrades from the code should be discussed with the client. For instance, providing only one or two emergency branches instead of three may make sense for a small rural hospital, or the use of fewer outlets per patient bed may make sense if minimal patient support equipment will be available for plug-in. Another standard that should be reviewed prior to the site visit is NFPA 110 – Standard for Emergency and Standby Emergency Systems. When designing a generator for a site, this standard should be followed as much as possible. In addition, a wealth of information is available on the internet from generator manufactures regarding physical sizes, air supply requirement, clearances, heat dissipation, EMI Electrical Design Guide 11 etc. Caterpillar, Kohler and Cummins are all good sources. The generator voltage, phase and frequency must match the system design parameters. 6.5 Transfer Switches Transfer switches for a hospital should be of the automatic type in lieu of manual if the cost will allow. Upon loss of power, which may be quite often in some locations, a generator can start and be on-line within 10 seconds with an automatic transfer switch. This may be critical to some patients and medical procedures. In some cases the generator will need to be used as “Base Power” and the utility as backup due to totally unreliable utility power. In this case automatic switching will definitely be required. 6.6 Other Systems Several other systems may be requested by the client and will need to be addressed in some manner by the engineer. These include: automatic or manual fire alarm system; nurse call systems; security systems (usually cameras and door controls); data network and server systems; telecom systems; satellite transmitting and receiving systems; electronic record-keeping systems; exit lighting; doctor’s paging and others. Usually EMI Engineers do not have the time or, in some instances, the knowledge to design these types of systems, but if the client requests any of the systems, they should be dealt with in the project report in some manner. The most efficient way to handle these designs is to send the floor plans to a manufacturer’s representative and ask for a design layout and cost to include in the report (except possibly for the exit lighting which the engineer should be able to design). If a local manufacture’s representative can be found for any of these systems, they should be given preference to help and encouraged to be involved. Local service of these systems will be critical to their operational longevity. EMI Electrical Design Guide 12 Reference Documents EMI Pre-Trip and During-Trip Electrical Engineer Questions Table of Contents 1. Before Trip .............................................................................................................................. 2 1.1. Power Requirements ........................................................................................................ 2 1.2. Solar Data......................................................................................................................... 2 1.3. Wind Data ........................................................................................................................ 2 1.4. Equipment to Bring .......................................................................................................... 2 2. During Trip.............................................................................................................................. 2 2.1. Sites with Existing Electric Infrastructure ....................................................................... 2 2.2. Sites to Add Local Electric Service ................................................................................. 4 2.3. Sites to Add a Generator .................................................................................................. 5 2.4. Planned Electrical Load Information ............................................................................... 5 3. Project Specific Information .................................................................................................. 7 4. Alternative Energy System Planning .................................................................................... 7 4.1. Solar Question List .......................................................................................................... 7 2 1. Before Trip 1.1. Power Requirements Reference EMI Electrical Power Density and Load Demand Factors.doc as a guide for estimating the value for the total electric service power requirement for your project. 1.2. Solar Data Collect solar data for location (see World Solar Insolation Maps.pdf). 1.3. Wind Data Collect wind data for location 1.4. Equipment to Bring a) b) c) d) e) Multi-meter (if possible with min, max, and avg. recording capabilities) Amp-clamp Calipers to measure the diameter of a wire Multi-purpose tool (i.e. Leatherman) Camera to document transformers, generators, panel locations, etc. 2. During Trip Find out the cost of electricity per kW-hr. If you can get any costs per kW-hr for energy supplied from the local utility, this information might be useful if there is any need to make any kind of economic tradeoff comparison. 2.1. Sites with Existing Electric Infrastructure If there is any existing electrical infrastructure, the tedious task of documentation is necessary. a) A rough sketch of existing buildings is needed - not architectural quality. Show doors, but windows are not necessary. Only major room dimensions are needed to about 5% accuracy. Somewhere in each room sketch, jot down the number of lights with wattage, the number of outlets and the number of fans (if any). The locations of these items are not needed. b) If one of these buildings is a dining hall, document any electrical appliances in the dining hall - especially any fridges, freezers, electric water heaters, or electric stoves. 3 c) If there is an existing laundry area, document the number of electric washing machines, electric dryers and electric irons in use. d) If there are any air conditioning units, electric heating, bore-hole pumps or other electrical motor loads, record name plate data and document locations on the site. e) Indicate the locations of any power panels on the building sketches. Take a photograph of these panels. If the breaker ratings do not show clearly on the panel photos, record these values. Be sure to develop an identification scheme to associate the panel photos with the located building. f) Document the earthing (grounding) method for the main power panel. Earth rod? Wire size? Check on any panels beyond the main power panel to document how earthing is handled. g) Although this may be a challenge, documentation of the electrical distribution scheme for the existing buildings is needed. If an electrician familiar with the site can be found, he would be an invaluable friend who could make this task simple. A feed from the electric utility probably runs to a power panel in one of the buildings, and then is distributed from that panel to the other existing buildings. A crude sketch documenting the electrical feed entry point and its interconnection to buildings is the goal. h) Is the service drop overhead or underground? i) Information on the incoming electrical feed is needed. It probably runs to a transformer mounted in a pole along a road somewhere in the vicinity of the site. If at all possible, determine the rating (kVA) of that transformer. Also, try to determine the size of the electrical cable used for this feed. Make a reasonable estimate of the length of this cable run from the transformer to the site connected building. j) Ask the ministry to give you copies or allow you to photograph any electrical drawings that they have for the site. If you can obtain any such information, it would be of great value. k) If possible, a design goal should be to feed the existing electrical system from a panel that is part of the new electrical system design. l) If there is a generator, get complete nameplate data on it - voltage, kVA or kW rating, power factor, three-phase or single-phase and primary or standby rating. 4 m) If there is an existing bore-hole pump, try to get name plate data. 2.2. Sites to Add Local Electric Service If the site presently has no electrical service, but plans to request service, there are several issues to explore. a) Where is the closest utility power line? b) Where will the electrical service enter the site? c) Is a transformer already installed from which the service would be supplied? If it is already installed, obtain Voltage and kVA rating on the transformer. d) If there is no transformer, will the electric utility company pay for the new transformer and to run the lines to the property? i. If the ministry has to purchase the transformer, prices may range from $US 40-70 per kVA. (Year 2011 values). e) Will the ministry quickly need any preliminary electrical plan to initiate the application for electrical service? If so, determine the level of detail. f) Does the local utility just offer service to certain customers for certain hours during the day – in other words, rolling blackouts? g) Is the local utility supplied service single-phase or three-phase? Determine the voltage (see Electrical Voltages & Outlets Worldwide.pdf). h) Find out if the local utility has rules, limits, or price breaks on levels of service per service drop. It might be possible that multiple utility service drops are advisable. i) Are there any national or local electrical codes to be satisfied? Are there any government inspections to be made? If so on either count, find out all the information available about the processes. j) Is site electrical power distribution to be underground or overhead? k) If underground distribution is to be used, ask if they use metallic shielded cable or PVC conduit for direct burial. l) Find out what standard circuit breaker sizes are readily available. 5 2.3. Sites to Add a Generator a) Is there already a generator on the site? If so, record complete nameplate data and photo document the generator unit and the associated generator house. b) If a new generator is to be installed, identify a suitable spot for a generator house (see EMI Diesel Generators Overview.doc). Ideally it needs to be 200 ft or less from the most distant point of electric service to minimize voltage drop problems. The building would need truck access to deliver diesel fuel. Noise emissions are principally from one side of generator house, but it could be irritating to those on all sides if sound-proofing is not used. c) If the purpose of the generator is for backup power, will it be used for total site backup or will it be used for certain loads deemed to be critical loads? If the latter, get a clear definition of these critical loads. d) The cost of an installed generation will probably be in the range of US$ 250-400 per kW plus an additional US$ 5000 -10000 for control panels. (Year 2011 values) e) If any information on the cost of any recently delivered multi-kW diesel generator set in the area can be found, this would be good information to know. f) The fuel consumption for the diesel engine will be about 0.07 gallons per kW-hr. Thus, a 50 kW load for 12 hrs per day with $5 per gallon diesel fuel costs $210 per day. (Year 2011 values) g) In addition to fuel, the engine will require an oil change (maybe 2-3 gal) and a filter change each 100-150 hours of operation. A major engine overhaul will be required every 25-30,000 hours of operation. There will be other expenses for operating an engine – a mechanic on site would reduce these expenses. h) Will there be a person on site with primary responsibility to keep the generator and electric system properly functioning? 2.4. Planned Electrical Load Information a) Obtain best estimates of walled square footages for the purpose of electrical load planning. b) Local practice on illumination power density needs to be determined and compared to the EMI Electrical Power Density and Load Demand Factors.doc. Observe the installed lighting wattage and roughly measure the floor area to determine the W/sq-m illumination power density for some typical existing building in the site neighborhood that has a living or dining area. Similarly, determine the illumination power density for an office or library area. 6 c) What types of light bulbs will be used? Fluorescent tubes (length and wattage)? Compact fluorescent lights (wattage)? Incandescent bulbs (wattage)? d) Is there any air conditioning, electric heating (direct or furnace), or electric water heating planned? If so, document specific locations. Get best description possible of the power these devices consume. e) Is a kitchen planned? If so, get all the information possible on the electric appliances to be installed - quantities and sizes. f) Will there be any pumping loads for fresh water or for sewage treatment facilities? g) For a medical clinic, identify electrical medical equipment planned - especially such items as X-ray machines and sterilization equipment. h) If a water well is to be drilled on the site, find out the expected depth of the well, the height of the storage tank above the well head, and the total daily water usage anticipated for the purposes of sizing a pump. This information is needed to determine the power requirement for the pump. i) If laundry facilities are planned, document the number of any electric washing machines, electric dryers, or electric irons anticipated? j) If there are some administrative offices planned, identify anticipated types and quantities of the electrical office equipment - PCs, printers, copiers, etc. k) Determine the nature of desired security lighting around the site. Do they plan to use street lights? Do they want motion activated lights around the entrance areas of buildings? l) If you are able to talk with an electrician or electrical contractor, ask if they wire with Ring Circuits or with Radial Feeds in building wiring. Also, ask if they specify their electrical wiring by the standard European sq mm sizes? m) If possible, take some close-up photos of electrical plug receptacles (they may call them outlets). It would be nice to know their particular plug pattern. Although that information does not have to be specified on the wiring diagram, it is a clue as to how close to they hold to the British standard (see Electrical Voltages & Outlets Worldwide.pdf). n) If possible, take some close-up photos of power panels in the area, both three-phase and single-phase. Of special concern is the single-phase power panel. If there is British influence, they may use what is called a Consumer Unit – breakers mounted horizontally on a DIN rail. This information will allow use of the appropriate panel template in the design work. 7 o) Assuming that there is to be indoor bath rooms in the project, check on a couple of things that would be British practice related. i. Are the plug receptacles inside the bathroom required to be special receptacles called “Shaver Outlets” with transformer isolation? ii. Are lights in the bathroom required to be either controlled by a switch located outside the door or by an insulated pull-cord? 3. Project Specific Information All eMi projects are different, thus a general question list will not address all the issues. For example, there might be light manufacturing facilities, a hospital, or other operations that have electrical service requirements beyond the scope covered by this document. In such cases, the EE volunteer should do appropriate research in advance of the project trip to prepare questions to properly gather information for the design phase. 4. Alternative Energy System Planning Discussion might arise concerning the use of photovoltaic (PV) generation or wind generation for backup electrical power since these two methods have low operating costs. PV generation has a fairly prohibitive initial cost - say around US$ 6-7000 per KW (Year 2011 Values). Rarely will a site have the average wind speed to make wind generation feasible. Unless the trees list at about 15 degrees from withstanding sustained winds, wind generation probably will not be feasible. The annual average wind speed for the site should exceed 15 mph before wind generation should be considered. Since PV generation is the more common alternate energy consideration for eMi projects, the following planning guide may be found useful in explaining the costs associated with a solar system. If the ministry definitely wants a solar system, then the items on the Solar Question List should be addressed during the project trip. 4.1. Solar Question List a) Get a clear definition of the loads to be operated during the solar harvest window from about 8:30 am to 4 pm (the harvest window may be shorter for latitudes greater +/- 15 degrees). This is a power-time profile – specific loads and time of day for which each load exists (see World Solar Insolation Maps.pdf). b) Get a clear definition of the loads to be operated outside of the solar harvest window from about 4 pm to 8:30 am. This is a power-time profile – specific loads and time of day for which each load exists. c) Water pumps can be a challenge for operation on a solar system. The best approach will be to use a small DC pump especially designed for solar power operation and to operate the pump only during the solar harvest window. Otherwise, batteries will 8 have to be sized to handle the pump operation, thus significantly increasing the capital outlay. d) How would the ministry choose to handle cloudy days? If electrical service is to be provided on cloudy days, then sufficient batteries would have to be installed to provide the energy needs for the span of sunless days. Also, sufficient solar panels would have to be installed to harvest the extra energy to be stored. Provision for electric service for a single cloudy day could easily double the system cost; a twoconsecutive cloudy day contingency could easily triple the system costs, etc. e) Batteries have approximately a 5 year life, thus this ongoing operational cost should be understood. Also, battery terminals need to be cleaned about every 6 months. Battery voltages need to be checked periodically – say once per month. Panel tilt angles need to be seasonally adjusted for maximum efficiency. f) A location for solar panels must be identified wherein there will be no blockage of incident sunlight during the solar harvest window. Solar panels may need to be washed down after dusty conditions. Keeping the solar arrays near the Power Center is best as voltage drop in connection cabling can be a design issue. Magellan's Adaptor Plugs: Afghanistan Albania F D 220/50 D EA23MFG EA351D EA351D EA23MFG EA23MDG EA23MDG Algeria 220/50 Andorra Angola Antigua EA23MFG EA23MDG EA23MDG Argentina 220/50 220/50 230/60 110/60 220/50 Armenia Australia Austria Azerbaijan 220/50 240/50 220/50 220/50 Bahamas Bahrain 120/60 220/50 Bangladesh 220/50 Barbados Belarus Belgium Belize Benin 115/50 220/50 230/50 110/60 220/60 220/50 Bermuda 120/60 Bhutan 220/50 EA23MFG EA351D EA351D EA351D EA351C EA351A EA351E EA351D EA351D EA351E EA351D EA351D EA23MFG EA351A EA351C EA23MFG EA23MFG EA351D EA351C EA351A EA351A EA351D EA351D EA351A EA351C EA23MFG EA351D EA351C EA351A EA23MFG EA351C EA351D EA351A EA351D EA351D EA351C EA23MFG EA351A EA351D EA351C EA351D EA351D EA351C EA351D EA23MFG EA351D Bolivia Bosnia/Herzegovina Botswana Brazil 220/50 110/50 220/50 220/50 220/50 Brunei Bulgaria Burkina Faso Burma 110/60 220/60 240/50 220/50 220/50 220/50 Burundi 220/50 F D D D C A E D D E D D F A C F F D C A A D D A C F D C A F C D A D D C F A D C D D C D F D 1 EA23MCG EA23MAG EA23MEG EA23MDG EA23MDG EA23MEG EA23MDG EA23MDG EA23MFG EA23MAG EA23MCG EA23MFG EA23MFG EA23MDG EA23MCG EA23MAG EA23MDG EA23MDG EA23MAG EA23MCG EA23MFG EA23MDG EA23MCG EA23MAG EA23MFG EA23MCG EA23MDG EA23MAG EA23MDG EA23MCG EA23MFG EA23MAG EA23MDG EA23MCG EA23MDG EA23MDG EA23MCG EA23MDG EA23MFG EA23MDG Guyana 120/50 240/50 Haiti Honduras Hong Kong 110/60 110/60 230/50 Hungary Iceland India 220/50 220/50 230/50 Indonesia Iran Iraq 220/50 110/50 220/50 220/50 Ireland, Northern Ireland, Republic of Israel Italy 220/50 230/50 230/50 220/50 Ivory Coast Jamaica Japan Okinawa Prefectorate 220/50 110/50 100/60 100/60 Jordan 220/50 Kampuchea 220/50 110/60 Kazakhstan Kenya 220/50 220/50 Kiribati 220/50 110/60 220/50 110/60 110/60 220/60 240/50 1 1 1 1 1 Korea, Dem. 1 Korea, Rep. Kuwait 1 Kyrgyz Rep. Laos 220/50 220/50 Latvia 220/50 C A F A A C F D D F C D D EA351C EA351A EA23MFG EA351A EA351A EA351C EA23MFG EA351D EA351D EA23MFG EA351C EA351D EA351D D C D F C C D D EA351D EA351C EA351D EA23MFG EA351C EA351C EA351D EA351D D A A A E C D F D A C D C F E A D A A D C D F D A D D EA351D EA351A EA351A EA351A EA351E EA351C EA351D EA23MFG EA351D EA351A EA351C EA351D EA351C EA23MFG EA351E EA351A EA351D EA351A EA351A EA351D EA351C EA351D EA23MFG EA351D EA351A EA351D EA351D EA23MCG EA23MAG EA23MFG EA23MAG EA23MAG EA23MCG EA23MFG EA23MDG EA23MDG EA23MFG EA23MCG 1 EA23MDG 1 EA23MDG EA23MCG EA23MDG EA23MFG EA23MCG EA23MCG EA23MJG EA23MIG EA23MDG EA23MDG EA23MAG EA23MAG EA23MAG EA23MEG EA23MCG EA23MDG EA23MFG EA23MDG 1 EA23MCG EA23MDG EA23MCG EA23MFG EA23MEG EA23MAG EA23MDG EA23MAG EA23MAG EA23MDG EA23MCG EA23MDG EA23MFG EA23MDG EA23MAG EA23MDG EA23MDG 1 Poland Portugal 220/50 220/50 Puerto Rico Qatar 120/60 240/50 Romania Russia Rwanda St. Kitts-Nevis 220/50 220/50 220/50 220/60 St. Lucia St. Maarten St.Vincent/Grenadines 240/50 220/50 220/50 Samoa, American 120/60 220/50 Samoa, Western San Marino Sao Tome and Principe Saudi Arabia 220/50 220/50 220/50 110/60 220/50 Scotland Senegal 220/50 220/50 Serbia/Montenegro Seychelles 220/50 220/50 Sierra Leone 220/50 Singapore Slovak Republic Slovenia Solomon Islands Somalia South Africa, Republic of 230/50 220/50 220/50 220/50 220/50 220/50 Spain Sri Lanka 220/50 110/50 230/50 Sudan 240/50 Surinam Swaziland 120/60 220/50 Sweden 230/50 1 1 1 1 D D F A C F D D D C F C D C A A E D E D D A D C C D F EA351D EA351D EA23MFG EA351A EA351C EA23MFG EA351D EA351D EA351D EA351C EA23MFG EA351C EA351D EA351C EA351A EA351A EA351E EA351D EA351E EA351D EA351D EA351A EA351D EA351C EA351C EA351D EA23MFG D C F C F C D D E D H C D EA351D EA351C EA23MFG EA351C EA23MFG EA351C EA351D EA351D EA351E EA351D EA23MHG EA351C EA351D EA23MDG EA23MDG EA23MFG EA23MAG EA23MCG EA23MFG EA23MDG EA23MDG EA23MDG EA23MCG EA23MFG EA23MCG EA23MDG EA23MCG EA23MAG EA23MAG EA23MEG EA23MDG EA23MEG EA23MIG EA23MDG EA23MAG EA23MDG EA23MCG EA23MCG EA23MDG EA23MFG EA23MKG EA23MDG EA23MCG EA23MFG EA23MCG EA23MFG EA23MCG EA23MDG EA23MDG EA23MEG EA23MDG EA23MHG EA23MCG EA23MDG F D C D D H D D EA23MFG EA351D EA351C EA351D EA351D EA23MHG EA351D EA351D EA23MFG EA23MDG EA23MCG EA23MDG EA23MDG EA23MHG EA23MDG EA23MDG ot es N G ro u A nd da ed pt or s N G onro u A nd da ed pt or s Vo lta ge /F re So q ck et C ou n tr y N G onro u A nd da ed pt or s G ro un A d da ed pt or s N ot es Vo lta ge /F re So q ck et C ou n tr y Vo lta ge /F So re q ck et N G onro u A nd da ed pt or s G ro un A d da ed pt or s N ot es C ou n tr y Electrical Standards by Country: 1 1 1 1 1 1 1 1 1 1 Cambodia 220/50 D 110/60 A C Cameroon 220/50 D Canada 110/60 A Canary Islands 220/50 D Cape Verde,Republic of 220/50 D Cayman Islands 120/60 A Central African Republic220/50 D Chad 220/50 D F Chile 220/50 D China 220/50 E C D A Hong Kong Region 230/50 C F Colombia 110/60 A Comoros 220/50 D Congo 220/50 D Congo, Dem. Rep. 220/50 D Cook Islands 240/50 E Costa Rica 120/60 A Croatia 220/50 D EA351D EA351A EA351C EA351D EA351A EA351D EA351D EA351A EA351D EA351D EA23MFG EA351D EA351E EA351C EA351D EA351A EA351C EA23MFG EA351A EA351D EA351D EA351D EA351E EA351A EA351D Cuba A D C D D D C F A A D A D C D D D D F E D D D D A D C D D C D F C D D D EA351A EA351D EA351C EA351D EA351D EA351D EA351C EA23MFG EA351A EA351A EA351D EA351A EA351D EA351C EA351D EA351D EA351D EA351D EA23MFG EA351E EA351D EA351D EA351D EA351D EA351A EA351D EA351C EA351D EA351D EA351C EA351D EA23MFG EA351C EA351D EA351D EA351D EA351C EA351D EA23MFG EA351D EA351A EA351A EA351D EA351D Cyprus Czech Rep. Denmark Djibouti Dominica 110/60 220/60 220/50 220/50 230/50 220/50 230/50 Dominican Republic Ecuador Egypt El Salvador 110/60 120/60 220/50 115/60 England Equatorial Guinea Eritrea Estonia Ethiopia 220/50 220/50 220/50 220/50 220/50 Fiji Finland France French Guiana French Polynesia Gabon Gambia Georgia Germany Ghana 240/50 220/50 230/50 220/50 220/60 110/60 220/50 220/50 220/50 230/50 220/50 Gibraltar 240/50 Greece Greenland 220/50 220/50 Grenada 220/50 C D F 220/50 D 110/60 A 120/60 A 220/50 D 220/50 D Guadeloupe Guam Guatemala Guinea Guinea-Bissau EA23MDG EA23MCG EA23MDG EA23MAG EA23MDG EA23MDG EA23MAG EA23MDG EA23MDG EA23MFG EA23MIG EA23MEG EA23MCG EA23MDG EA23MCG EA23MFG EA23MAG EA23MDG EA23MDG EA23MDG EA23MEG EA23MAG EA23MDG EA23MAG EA23MIG EA23MCG EA23MDG EA23MKG EA23MDG EA23MCG EA23MFG EA23MAG EA23MAG EA23MDG EA23MAG EA23MDG EA23MCG EA23MDG EA23MIG EA23MDG EA23MIG EA23MFG EA23MEG EA23MDG EA23MDG EA23MDG EA23MDG EA23MAG EA23MDG EA23MCG EA23MDG EA23MDG EA23MCG EA23MDG EA23MFG EA23MCG EA23MDG EA23MDG EA23MDG EA23MKG EA23MCG EA23MDG EA23MFG EA23MDG EA23MAG EA23MAG EA23MDG EA23MDG 1 Lebanon 220/50 110/50 220/50 Lesotho 1 Liberia Liechtenstein Lithuania Luxembourg Macao 120/60 220/50 127/50 230/50 220/50 220/50 220/50 200/50 Macedonia Madagascar 220/50 220/50 Madeira 220/50 Malawi Malaysia Maldives 230/50 240/50 220/50 Libya 1 1 1 1 Mali Malta Martinique 220/50 220/50 220/50 Mauritania Mauritius 220/50 220/50 Mexico Micronesia Moldova Monaco 120/60 120/60 220/50 220/50 Mongolia Montserrat Morocco 220/50 230/60 220/50 Mozambique 220/50 Myanmar 220/50 1 1 1 1 1 1 1 1 Namibia 220/50 Nauru Nepal 220/50 220/50 Netherlands Neth. Antilles New Caledonia New Zealand Nicaragua Niger Nigeria 230/50 220/50 110/50 220/50 230/50 120/60 220/50 230/50 Norway Oman 230/50 240/50 Pakistan 230/50 Panama 120/60 1 Papua New Guinea Paraguay Peru 1 Philippines 240/50 220/50 110/60 220/60 220/60 1 1 1 D A H D C A D F D D D F C D D F F D C C F D A D C D F D C D A A D D F D A D F D H C D F D H E F D D D A D E A D C F D C D F D A E E D A D A D EA351D EA351A EA23MHG EA351D EA351C EA351A EA351D EA23MFG EA351D EA351D EA351D EA23MFG EA351C EA351D EA351D EA23MFG EA23MFG EA351D EA351C EA351C EA23MFG EA351D EA351A EA351D EA351C EA351D EA23MFG EA351D EA351C EA351D EA351A EA351A EA351D EA351D EA23MFG EA351D EA351A EA351D EA23MFG EA351D EA23MHG EA351C EA351D EA23MFG EA351D EA23MHG EA351E EA23MFG EA351D EA351D EA351D EA351A EA351D EA351E EA351A EA351D EA351C EA23MFG EA351D EA351C EA351D EA23MFG EA351D EA351A EA351E EA351E EA351D EA351A EA351D EA351A EA351D EA23MDG 1 Switzerland Syria Taiwan Tajikistan Tanzania 230/50 220/50 110/60 220/50 230/50 Thailand 220/50 Tibet 220/50 Togo Tonga 220/50 240/50 Trinidad & Tobago 110/60 220/50 Tunisia Turkey Turkmenistan 220/50 220/50 220/50 Turks & Caicos Islands Tuvalu Uganda 120/60 220/50 220/50 Ukraine United Arab Emirates 220/50 220/50 USA Uruguay 110/60 220/50 Uzbekistan Vanuatu 220/50 220/50 1 1 Venezuela Vietnam 120/60 220/50 110/60 1 Virgin Islands (British) 110/60 1 Virg. Isl.(US) Wales Yemen 110/60 220/50 220/50 Zambia 220/50 Zimbabwe 220/50 EA23MHG EA23MDG EA23MCG EA23MDG EA23MFG EA23MSG EA23MDG EA23MDG EA23MFG EA23MCG EA23MDG EA23MDG EA23MFG EA23MFG EA23MDG EA23MCG EA23MCG EA23MFG EA23MDG EA23MDG EA23MCG EA23MDG EA23MFG EA23MDG EA23MCG EA23MDG EA23MAG EA23MAG EA23MDG EA23MDG EA23MFG EA23MDG EA23MAG EA23MDG EA23MFG EA23MDG EA23MHG EA23MCG EA23MDG EA23MFG EA23MDG EA23MHG EA23MEG EA23MFG EA23MDG EA23MDG EA23MDG EA23MAG EA23MDG EA23MEG EA23MAG EA23MDG EA23MCG EA23MFG EA23MDG EA23MCG EA23MFG EA23MDG EA23MAG EA23MEG EA23MEG EA23MDG EA23MAG EA23MAG © 2008 Magellan's Travel Supplies. All Rights Reserved. 1 1 1 1 1 1 1 1 1 D D A D C F D A D E D E F D A C F D D D A A E C F D C F A E D D E C D A D A C A C A C C F A C D C F EA351D EA351D EA351A EA351D EA351C EA23MFG EA351D EA351A EA351D EA351E EA351D EA351E EA23MFG EA351D EA351A EA351C EA23MFG EA351D EA351D EA351D EA351A EA351A EA351E EA351C EA23MFG EA351D EA351C EA23MFG EA351A EA351E EA351D EA351D EA351E EA351C EA351D EA351A EA351D EA351A EA351C EA351A EA351C EA351A EA351C EA351C EA23MFG EA351A EA351C EA351D EA351C EA23MFG EA23MSG EA23MDG EA23MAG EA23MDG EA23MCG EA23MFG EA23MDG EA23MAG EA23MDG EA23MEG EA23MDG EA23MEG EA23MFG EA23MDG EA23MAG EA23MCG EA23MFG EA23MDG EA23MDG EA23MDG EA23MAG EA23MAG EA23MEG EA23MCG EA23MFG EA23MDG EA23MCG EA23MFG EA23MAG EA23MEG EA23MIG EA23MDG EA23MEG EA23MCG EA23MAG EA23MDG 1 1 1 1 1 1 1 1 1 1 EA23MCG EA23MAG EA23MCG EA23MAG EA23MCG EA23MCG EA23MFG EA23MCG 1 EA23MCG EA23MFG 1 1 Notes: In countries where multiple adaptors are listed, the most common configuration is listed first. Wise travelers prepare for all possibilities. (1) Not all electrical sockets in these countries provide grounding. 1 1 1 1 Please Note: Electrical adaptor plugs do not change voltage (e.g. from 220 volts to 110 volts for North American appliances). If your appliance is not designed to operate on 220 volt systems found overseas, you will need a step-down transformer. If your appliance has three pins we recommend that you use a grounded adaptor plug. Grounding helps protect you from shock if your appliance is damaged and an electrical short occurs. In areas where grounded sockets are not available you may choose to bypass the grounding pin and use your appliance without the protection of a grounded socket. EMI Diesel Generators Overview When considering a design where generators will be used a prime power for remote and small operations (<1MW) there are several factors that need to be considered and known. 1. Terminology: Technically “Generators” produce DC voltage and current, and “Alternators” produce AC voltages and current, the same that we see from utility sources. While there are design differences in the internal connections of the electrical side of things that make that difference, it is common practice to call the entire system of engine driven alternators as "generators", and we will use that term here. We will use the term “alternator” only to describe design issues that impact the electrical portion of the overall generating system. DC systems have current flowing in a single constant direction with typically steady voltages and are commonly seen in battery powered systems. AC systems have current directional flow alternating, typically many times a second; the voltage also varies in a sine wave pattern, from zero to a positive peak then back down to zero and down to a negative peak then rising back to zero in each cycle. Since the voltage is constantly varying, the output is rated by an “RMS” (root mean square) voltage that is a mathematical calculation of the sine wave that give the same power as a DC current at that same voltage would. Peak voltages are higher than the RMS value by a factor of about 1.41 (the square root of 2). So a 120 volt AC system will have peak voltages of about 170 volts, and 220 volt AC system peak voltages of about 308 volts. 2. Ratings: Generators are typically sold by KW capacity with a kVA rating also provided. Generator sets (Gensets) are typically rated for Prime or continuous duty rating and at higher rating for Standby or limited run hours. It is wise to buy the unit based on the lower kVA Prime or continuous duty rating if it is to take to place of utility power and run all day or over 12-14 hours a day. The KW capacity is controlled by available engine horsepower (work), while the alternator's winding kVA rating (current) is limited due to temperature rise from windings resistance. At higher altitude and hotter inlet air the engine will deliver less horsepower than at sea level and standard temperature. Likewise hotter ambient air will also limit the acceptable temperature of the windings in the alternator thus limiting kVA. Since almost all 3 phase generators are rated with a 0.8 power factor, expect to see typical ratings like 80KW / 100kVA. While power factor is more complicated than we will deal with here, it is the effect when the current flow of an AC system doesn’t match exactly the voltage sine wave. Incandescent lights and resistance heaters have a power factor of 1.0 and induction motors typically have power factors closer to 0.8, lagging while capacitive loads such as UPS input filters tend to have leading power factors. The voltage regulators in the alternators generally have problems responding to leading power factor loads and loads with very low leading power factors can result in loss of voltage stability. Using a generator to feed a normal mix of loads this is not a problem but if you are feeding loads where a UPS kVA rating is over about 50% of the load the generator will be carrying, special attention to getting an engineer’s review would be wise. At cooler temperatures and for short periods the genset can deliver slightly above its rating. This allows for motor starting loads and brief load transitions. How well it will perform during this overload varies with the ambient air temperature, amount of overload and duration. You are at the edge or outside the envelope here so anything you get be grateful for. Planning under normal conditions not to exceed 80% of the engines rating is wise. 3. Frequency: The frequency of the output voltage is directly related to the engine speed. Thus with typical 4 pole armatures, a 50Hz machine will run at 1500 RPM and a 60 Hz machine will run at 1800 RPM. Engine speed is controlled by the governor. If you are having frequency and engine speed problems that is where to look, not the alternator or voltage regulator. So, yes some 60 hertz machines can be dialed back to run at the lower speed, but you will lose some horsepower and torque, so it will not deliver full original KW/kVA ratings at the lower speed. Likewise, some 50Hz machines could be adjusted upward in speed to provide 60Hz, where they would have more available engine horsepower but also might have tendency for the engine to overheat if the radiator system was sized closely at the 50 Hz rating, likewise fuel consumption will increase. Other than motor loads, many loads such as lighting, resistance heaters (stove, ovens, toasters etc), and many electronic devices are not frequency sensitive, they can work on either 50 or 60 hertz. Check the nameplate of the device to be sure. 4. Voltage: The voltage regulator controls output voltage. Engine speed and operation would only impact voltage if the engine is at the end of its performance range and can't hold any more power OR if a large load is suddenly applied to the engine. This block loading (adding or removing a large say >=25% fraction of the generator's rating) will briefly impact both speed (frequency) and voltage output but in general the engine should recover within about 3-5 seconds. Try to specify permanent magnet excited alternators, if they are available, other types can, when out of service for some time, (maintenance issues) have to have the field windings 'flashed' to get the unit generating voltage again. While this is a fairly simple procedure, it is easy for the procedure to be forgotten or trained personnel to leave before it is needed again. Thus, getting written manufacturers troubleshooting and basic maintenance procedures should be a part of the purchase if at all possible. Some 277/480 VAC units could be dialed down at the voltage regulator to provide 230/416 or possibly 220/400 VAC power for overseas systems. If the voltage regulator won't adjust that low possibly a replacement one can be obtained that will allow for the lower voltage. 3 Phase alternators are available in 6 lead and 12 lead winding arrangements, the leads are typically marked T1- T12. The 12 lead machines can be connected to provide two or more voltage levels across the three phases (120/208 or 277/480VAC). 6 lead machines have the two ends of each of the three windings available to be connected as a delta or star (WYE) arrangement. Be sure the connection is made as needed to match the electrical system design you are working with. The delta arrangement has a single voltage between any two phase connections and such will give only a single voltage, 120, 208, 240, 400, 480. While a star or WYE connected arrangement ties one end of each phase winding to a common point and then grounds them. This provides two voltage ranges, with the phase to ground voltage 120 in a 120/208 system, 220 in a 220/400 system and 277 in a 277/480 system. While the phase to phase voltage gives the higher level in each of those pairings. If the machine is reconnectable there will be a diagram in the owner’s manual and often a wiring diagram on the alternator cover. Reconnecting to get a different voltage arrangement may require changes in the sensing leads landed on the voltage regulator, watch closely if you have to make a reconnection. 5. Single or 3 Phase: A single phase unit can be connected to a 3 phase panel with each of 3 single phases wired to each hot phase, but of course it will not support true 3 phase loads, still all those single phase loads can be powered. The KW and kVA ratings will still apply since the three connections each add load. It is possible to use a 3 phase unit and wire to a single phase panel but the windings in the alternator will be heating unevenly and you need to reduce the loading to 1/3 of kVA rating if you only connect 1 phase. If you connect 2 legs to a US standard 120/240 panel you can use about 2/3 of the kVA rating of the unit. 6. Fuel choices: Engine generators in smaller sizes are generally available in gasoline from under 1KW to about 150KW, with natural gas (propane) and diesel units available in the whole range of 201000+ KW. In most majority world settings, diesel is the best choice for the following reasons. Diesel is less flammable (listed as combustible) than gasoline. Liquid fuels are categorized based on flash point, the temperature where the fuel gives off enough vapor to ignite. Combustible fuels (kerosene, D-2, Jet A etc) have flashpoints above 100F, while flammable fuels gasoline, alcohol have flashpoints under 100F (~37.7C). Thus combustible fuels are safer to transport and store.Diesel fuel should not be stored or piped with galvanized iron pipe. Black iron pipe is fine and the interior is preserved by the oily nature of the fuel. Diesel tends to strip the zinc galvanizing off the pipe and it causes problems for the engine injectors. In general, diesel fuel stores pretty well, as least compared with gasoline, and so it is more widely available in the more rural areas. Exceptions to this would be areas served by small boats with gasoline outboard engines. Diesel engines are also generally considered longer lived and to require less maintenance since they do not have points, spark plugs and electric ignition systems. While natural gas and propane are also scarce in the more rural areas due to transportation issues, gaseous fueled engines also have slightly slower responses to varying loads, and require spark ignition systems. There are some dual fueled engine that use some diesel fuel as an ignition source and mix the intake air with gaseous fuel for the rest of the power requirements but these are generally larger than the sizes reviewed here. So in general, diesel is the preferred fuel for this application. Many diesel engines are rated by their manufacturers to run on alternate fuels. Some fuels have slighter lower energy per volume and so reduce the generator KW capacity, these rarely require more than 5-10% derate. The key issue is often the fuel pump needing a certain level of lubricity. Telephone companies in the US often operate diesel engine generators on K-1 kerosene and D-1 (lighter weight or winter diesel) since they are more stable in storage. Most diesel engine vendors also have recommendations on use of so called bio-diesel fuels, while long term storage of bio fuels is generally not recommended many engine vendors have approved these fuels for operation with little if any KW derating. Always check with the engine manufacturer for their recommendations. Likewise many diesel operators blend used and filtered motor oil back into diesel fuel at ratios under 10% of used motor oil with satisfactory results. Bio fuels are not recommended for longer term storage (.>~45 days) since they tend to degrade and or grow out microbial bugs. If bio fuels are to be used be sure there is no water contamination as any water (even in standard diesel fuel) increases fuel microbial growth that can lead to filter plugging and fuel deterioration. High storage temperatures are also very bad for bio-diesel blends. Higher ratio blends of bio-diesel also can have greater than 12% derate for horsepower and increased fuel quantity consumption values above 15%. If biodiesel fuels are to be used, seriously consider use of fuel stabilizers. Biodiesel blends may also tend to clean the tanks of any accumulations of sludge or other sediments and can result in more frequent filter plugging than straight diesel. If you are located in extremely cold climates be aware that diesel fuel has a paraffin point or cloud point, a temperature where small crystals of waxy particulate condense out of the fuel. To avoid plugging the fuel filter or even having the fuel gel in the tank, the fuel must be kept above the paraffin point temperature. Your local fuel supplier should be able to provide you info on the cloud point of their winter fuel. Be aware that fuel blends can change summer to winter, so take that info account. Underground storage is often recommended since it reduces the temperature swings of aboveground tanks and so reduces moisture condensation that mixes into the fuel and tends to promote microbial growth. A nearly full tank has less air space and so less moisture condensation problems, but a large tank reduces fuel turnover so there is a greater change of the fuel having some deterioration due to longer storage times. It is best to try to use the tank down to very low level before refueling, as just mixing a little fresh fuel into a near full tank gives a longer average life of the fuel being stored and so a higher risk of deterioration. Environmental concerns recommend enclosing the diesel storage tank with a secondary containment able to prevent release of the fuel into watercourses if the tank leaks or is spilled. Since water is heavier than diesel fuel, be sure and pump any water or sediment laden fuel off the bottom of the tank at least annually. You can use a rigid small diameter pipe to get the water or fuel off the bottom of the tank, if there is no sump drain. For the same reason, make sure the fuel pickup piping is installed at least a couple of inches (5cm) or so off the bottom of the tank, so any water isn’t picked up and distributed to the fuel injectors as they can be damaged by this. On larger tanks, the pickup point can be 4-6" off the bottom of cylindrical tanks. 7. Fuel Consumption: At least for planning and budgetary reasons, the designer needs to be aware of fuel consumption requirements. Until a specific generator is selected and purchased, how do you estimate fuel consumption and thus fuel storage requirements? Rule of thumb - For each 10KW of load being operated, a diesel generator will use about 1 GPH (~4 LPH) of diesel fuel. This gets somewhat better with larger engines fully loaded and a little worse with smaller engines or engines under small partial load, but gives you a starting point for planning purposes. Many larger capacity diesel engines have fuel return lines. Excess fuel is pumped by the fuel pump to the injector pump and circulates in the fuel rail, cooling the injectors, the fuel that isn't needed at the existing engine loading is returned via the fuel return line. Some manufacturers have optional fuel coolers, small radiators for this fuel to pass thru before it is returned to the fuel tank. For planning purposed only the fuel consumed by the engine per hour is needed, but be aware that the fuel returned to the tank will tend to warm the fuel up and thin it out somewhat. 8. Fuel Security: Security of your fuel supply is a critical item. Loss by theft is all too common and a source of unneeded expense. For critical applications (hospitals etc.) having a separate concealed reserve can be helpful not only for emergencies requiring more fuel consumption than normal but as a bridge to cover delays in fuel delivery, or in emergencies due to theft. Locking and frequent inventory of fuel storage by principals to verify that (even otherwise trusted) staff is faithfully managing the expensive fuel supply is a wise management control item. While this seems harsh, such measures can also serve to reduce temptations to divert what seems to be such a plentiful and valuable liquid commodity. Initial planning for fuel storage should take these measures into consideration. 9. Radiator Cooled units: The rule of thumb for radiator cooled units says you need at a clear open inlet area least 1 ½ to 2 times the area of the radiator. Since many units in majority world installations don't have enclosed engine rooms or ducted air exhaust and inlet, this may not impact your design. But it is wise to make arrangements so the air flow from the radiator is not easily recycled into the inlet side of the radiator. The effect of such re-circulated air is to reduce engine cooling capacity and if the hotter air is entrained into the diesel engine inlet filters, the reduced density gives the effect of higher altitude operation and reduces available engine horsepower and thus KW. Thus pay attention to prevailing wind directions, radiator discharge into prevailing winds should be avoided or else use scoops or diverters to direct off radiator air upwards or sideways to allow normal airflow to help dissipate radiator exhaust hot air plume. If you have use for large quantities of hot water (hospitals) consider design of a heat exchanger to use waste engine heat to provide domestic hot water. 10. Noise: Remember the noise factor when designing placement of a diesel generator. Will it need to run at nighttime? While voltage drop issues force the unit to be located close to higher amp draw uses, look at orientation of the unit to minimize noise impact to sensitive areas. Pointing the engine exhaust and radiator fan away from those areas is a basic starting point. Scoops to divert radiator exhaust upwards can make significant noise reduction, as can baffling of air inlets around the sides of the generator. 11. Operating an Engine genset at reduced loads: While diesel engines can and do operate in wide range of loads, be aware that prolonged use under about 30% of rated loading can result in "wet stacking" where the engine tends to ooze a black tarry viscous liquid that is a mix of unburned diesel fuel, soot and carbon particles. This can cause the engine problems over time and is cured by running the engine for several hours at higher loads (50-75% of rating), before the problem gets too serious. Wet stacking can reduce the ability of a generator to supply its full rated load and cause other maintenance issues, so don't oversize a generator if the future load growth is several years off. Better to buy a more closely right sized unit now and trade when the load exceeds 90% or so of rated capacity. This problem is common with the older 2 cycle designs from Detroit diesel. 12. Operational Issues: While operational costs will depend on the local staff skills of the facility, distance from a service provider and cost of parts for that brand of unit in the country where it is located. Preference should be given to using manufacturers with good support in the region or at least the country. Importing the "finest" make in the world into an area where parts are simply hard to get, or unobtainable will result in an out of service unit all too soon. Air freight and import duties for specially imported parts will cost more than similar parts that are imported in greater quantity due to wider use of that make and model of engine.Consider specifying a fuel/water separator unit, and provide for spare fuel, oil and air filters. Try to get manufacture’s training for the local service staff to at least be able to change oil and all filters. The recommended service intervals will depend on how clean the air is at the generator, wind blown dust and dirt will shorten service intervals and increase costs as air filters will have to be replace more often and oil changes made more frequently. Labor costs will of course vary so investigate those costs and make sure the owner is aware of them. EMI Electrical Power Density and Load Demand Factors For loads serviced by Electric Utility or Generator Churches, Auditoriums, Dining Halls, Large Open Spaces Illumination power density - 11 VA/m2 (1 VA/ft2) General Outlet Loads - No additional load added for outlets - AV and PA equipment are included in special loads Demand factor sizing - 50% for General loads when General loads are over 3kVA. If less than 3kVA use 100% - 100% for Special loads* Dwellings, Offices, Schools, Dormitories, Small Clinics Illumination power density - 11 VA/m2 (1 VA/ft2) General Outlet loads - 6 VA/m2 (0.56 VA/ft2) Demand factor sizing - 50% for General Loads when General loads are over 3kVA. If less than 3kVA use 100% - 100% for Special Loads* Hospitals, Large Clinics Illumination power density - 22 VA/m2 (2 VA/ft2) (Operating Rooms, Delivery Rooms, Other rooms needing more intense lighting) - 11 VA/m2 (1VA/ft2) (All other rooms needing normal lighting) General Outlet Loads - 180 VA/outlet Demand factor sizing - 75% for General Loads when General Loads are over 3kVA. If less than 3kVA use 100% - 100% for Special Loads* * For certain special loads, demand factors allowed by NEC or IEE Regulations may be appropriately applied. Note: Alternate energy systems must be handled by a more carefully formed power-time profile. EMI Electrical Report Example 1.1 Existing Electrical The existing site presently has a 100 kW, 50 Hz, 380/220 VAC generator that is being used to run the well pump. No utility electrical service comes onto the site; however, a three-phase distribution line does exist across the road on the south side of the property. There will be line and transformer expenses required to extend the electrical service onto the site. 1.2 Proposed Electrical System The national electric utility grid will be the primary source of power for the Site. The government utility will need to provide the site with high voltage power lines from the existing power lines across the street from the property (see drawing ‘Site Electrical Plan’). The ‘EMI Electrical Load Study Example’ shows the complete load planning for the site electrical grid – Phase 1 and Phase 2. A 150kVA transformer will be needed for all phases of this project, but a 100kVA transformer would be sufficient for the first phase. The 100kW generator will be used as a back-up for the site but it will not be able to power the whole site when the future phases are added. Loads will have to be reduced or the backup loads separated when the future phases are added. Air conditioners contribute to the majority of the electrical load on this site. The new generator building will be located relatively close to the accommodations as they have the largest power demands. The generator building is also centrally located on the site to minimize voltage drop concerns if future buildings are added in the agriculture area. In addition to housing the generator, the building will also contain the main distribution panel, and the manual transfer switch to select between the utility as the primary power source, and the generator as the backup power source (see drawing ‘Generator Room Electrical Plans’). The ‘Electrical One Line Diagram’ shows a drawing of the proposed site electrical system wherein cable sizes are specified and electrical panels and switch gear are identified. Since some electrical cable runs exceed 60 m in length, several cables have been sized larger than necessary based on ampacity to keep voltage drop within the standard practice of 4% or less. Also, all panels, breakers and cables have been sized to accommodate all future expansion on the conference facility, so that new cables and panels do not have to be installed when the buildings are expanded. The ‘Site Electrical Plan’ suggests a viable plan for buried distribution cable routing for the site. Electrical power panels are also associated with each building on this drawing. Perimeter security lights are activated by a switch in the generator room with power supplied from panel PPG. 1.2.1 Accommodations Drawings ‘Wiring Diagram - Basement’ and ‘Wiring Diagram - Ground Floor’ show the wiring diagrams for the accommodations. Electrical service to the building feeds through one main power panel located in the worker’s room in the basement - PPA. Subpanels, fed from this main power panel, are distributed to each floor to provide convenient access to breakers for isolation of building sectors. As floors are added to the building a sub-panel for that floor can easily be connected in to the main panel in the basement. The main panel has been sized to account for all the future floors of the accommodations building. Calculations for the electrical loads serviced by each main power panel are shown below the respective panel drawings. EMI Site Electrical Load Study Example PHASE 1 Load Description Accommodations (2 levels) Site Lighting Soccer Field Lights Qty 2 46 10 Area (m2) 528 VA/m2 VA/m2 General Special Maximum Phase Lights Outlets Load (VA) Loads (VA) Demand (VA) Currents 11 6 17952 40780 58732 89 4600 4600 7 2000 2000 3 Phase 1 Max Demand (VA) Demand Factor: 50% General Loads + 75% Special 40 hp Well Pump with 0.7 power factor(VA) 1 hp Filtration Pump (VA) 10 hp Booster Pump (VA) Total Phase 1 Demand (kVA) Area VA/m2 Special Loads *A/Cs (29), Washers(4) Dryers(4) *Site Lights (46) *Field Lights (10) 65332 44511 42629 1066 10657 99 PHASE 2 Load Description Qty 2 Accommodations (2 levels) 2 (m ) 528 VA/m2 General Special Maximum Phase Special Loads Lights Outlets Load (VA) Loads (VA) Demand (VA) Current (A) 11 6 17952 36696 54648 Phase 2 Max Demand (VA) Demand Factor: 50% General Load + 75% Special Total Future Phases Demand (kVA) *A/Cs (29) 54648 36498 36 SUMMARY Property Loads Qty Phase 1 1 Phase 2 1 *Device Power Consumption Device Power (VA) Freezer Microwave Oven Washing Machine Gas Dryer (motor) Electric Dryer Iron Coffee Maker PC Printer Copier Field Lights Site Lights Air Conditioner (Small) Air Conditioner (Medium) Air Conditioner (Large) Ceiling Fan Data Projector 200 750 500 400 5000 1000 500 280 150 750 200 100 1232 1716 2310 150 600 Total (kVA) 98.86 36.50 Loads Total (kVA) 135.36 Xfmer Size (kVA) 150.00 Power Percentage Used 90.2% EMI Solar vs. Generator vs. Utility Combined Equipment and Operation Cost Comparison (NOTE: Pump loads not included in study, thus annual energy costs are larger than values below.) Yellow-highlighted cells are input values In table below, enter estimated hourly power demand values for the site in W. Time of Day (am first row, pm second row) 12-1 1-2 2-3 3-4 4-5 5-6 6-7 7-8 8-9 (W) 500 5000 (W) 500 6000 (W) 500 6000 (W) 500 5000 (W) 500 5000 (W) 1500 3000 (W) 3000 3000 (W) 3000 1500 (W) 5000 1500 9-10 10-11 11-12 LOAD Total Site Hourly (AM) Power Demand (PM) Solar System Assumptions: Inverter efficiency (ηI )= 90% Charge Controller efficiency (ηC) = 95% Battery efficiency (ηB) = 80% Daily sunlight = (W) (W) (W) 5000 5000 5000 1000 500 500 Site Daily Energy Usage System efficiency (ηS) = 70% Depth of Battery Discharge (DOD) = 0.5 Battery replacement every 5 years 7 Generator Assumptions: Fuel usage rate = 0.07 gal/kW-h Diesel fuel price = 3.80 US$/gal Utility Assumptions Elect. Cost per kW-h Distance to Site Equipment costs: Solar Panels Charge Controller Inverter Batteries Generator Transformer Cost for 3-phase to site Generator replacement every 5 years 0.3 US$/kW-h 800 Meters 3500 300 800 200 300 US$/kW Cost = US$/kW Cost = US$/kW Cost = US$/kW-h Cost = US$/kVA Cost = Generator annual fuel cost = 35 US$/kVA Cost = 39 US$/meter Cost = Utility electricity usage annual cost = 48571 3068 5333 13000 2000 6602 233 31200 7446 US$ US$ US$ US$ US$ US$ US$ US$ US$ ENERGY (kW-h) 68.00 TOTAL CUMULATIVE COSTS of SOLAR, GENERATOR & UTILITY 250,000 COSTS (US$) 200,000 150,000 100,000 50,000 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 YEARS Solar Generator Utility EMI Wire Chart Adapted from NEC 2008 Table 310.16 & Ch 9 Table 8 Size AWG/kcmil Size mm2 18 16 1.5 14 2.5 12 4 10 6 8 10 6 16 4 25 3 2 35 1 50 1/O 2/O 70 3/O 95 4/O 120 250 300 350 150 185 400 240 500 300 600 Copper(THHW) Aluminum(THHW) Resistance Ampacities Ampacities Factor (Copper) Diameter (75 °C rating) (75 °C rating) ohm/km in. 6 12 15 20 22 25 29 35 40 50 56 65 73 85 97 100 115 118 130 146 150 175 180 200 217 230 250 255 285 310 320 335 372 380 418 420 20 24 30 33 40 44 50 56 65 73 75 90 92 100 116 120 135 139 155 169 180 200 205 230 250 258 270 303 310 339 340 27.70 17.30 15.05 10.70 8.99 6.73 5.69 4.226 3.696 2.653 2.251 1.671 1.425 1.053 0.874 0.833 0.661 0.635 0.524 0.435 0.415 0.329 0.315 0.261 0.229 0.205 0.180 0.175 0.146 0.125 0.118 0.1080 0.0906 0.0870 0.0738 0.0732 Area in2 0.046 0.058 0.002 0.003 0.073 0.004 0.092 0.006 0.116 0.011 0.146 0.017 0.184 0.027 0.232 0.042 0.26 0.292 0.053 0.067 0.332 0.087 0.372 0.418 0.109 0.137 0.47 0.173 0.528 0.219 0.575 0.63 0.681 0.26 0.312 0.364 0.728 0.416 0.813 0.519 0.893 0.626 Area Diameter cir. mil mm Area mm2 1620 2580 2960 4110 4934 6530 7894 10380 11840 16510 19740 26240 31580 41740 49340 52620 66360 69070 83690 98680 105600 133100 138100 167800 187500 211600 237800 250000 300000 350000 365100 400000 473600 500000 592100 600000 1.16 1.46 1.6 1.84 2.06 2.32 2.59 2.93 3.21 3.7 4.12 4.66 5.18 5.88 6.48 6.61 7.42 7.62 8.43 9.27 9.45 10.62 10.9 11.94 12.8 13.41 14.4 14.61 16 17.3 17.8 18.49 20.3 20.65 22.6 22.68 1.06 1.67 2.01 2.66 3.33 4.23 5.27 6.74 8.09 10.75 13.33 17.06 21.07 27.15 32.98 34.32 43.24 45.60 55.81 67.49 70.14 88.58 93.31 111.97 128.68 141.24 162.86 167.64 201.06 235.06 248.85 268.51 323.65 334.91 401.15 403.99 Minimum Size Equipment Grounding Conductors for Grounding Raceway and Equipment 1 Size of Grounding Electrode Conductor ‐ Rating or Setting of Automatic Overcurrent Device in Circuit Ahead of AWG or kcmil(mm2) Equipment, Conduit, etc., Not Exceeding Aluminum or ‐ (Amperes) Copper Copper‐Clad 15 20 30 40 60 100 200 300 400 500 600 800 1000 1200 1600 2000 2500 3000 4000 5000 6000 1 Referenced from NEC 2008 Table 250.122 14 (2.5) 12 (4) 10 (6) 10 (6) 10 (6) 8 (10) 6 (16) 4 (25) 3 (35) 2 (35) 1 (50) 1/0 (70) 2/0 (70) 3/0 (95) 4/0 (120) 250 (150) 350 (185) 400 (240) 500 (300) 700 800 12 (4) 10 (6) 8 (10) 8 (10) 8 (10) 6 (16) 4 (25) 2 (35) 1 (50) 1/0 (70) 2/0 (70) 3/0 (95) 4/0 (120) 250 (150) 350 (185) 400 (240) 600 600 800 1200 1200 Sun-Hour Map World Design Insolation Map Excel Sizing Form Solarex’s World Design Insolation map plots design insolation—to the extent it has been reliably recorded—on the surface of the earth. On this map, design insolation is expressed as the average value of the total solar energy received each day on an optimally tilted surface during the month with the lowest solar radiation. This worst-month data is commonly accepted as a valid solar energy index for designing systems which must support a load 12 months per year, rather than seasonally. The unit of measurement is kilowatt-hours/m²/day, often referred to as equivalent sun-hours, or ESH. The map presents color-coded areas of essentially equal insolation (see key at bottom right) in addition to point values recorded at selected monitoring stations. From the main map, you can access detailed insolation maps of any area by clicking on that area. Consult the Adobe Acrobat Reader Help menu for instructions on moving around on the map. Select the site design insolation from the map, and enter it on line 9 of the Array Sizing Procedure form. Particularly if the site is at a latitude higher than 45°, be aware that the ESH number represents average daily insolation during the worst month of the year. It is not indicative of how much solar energy is available during other months, which--particularly at high latitudes--may be substantial. Contact an authorized Solarex representative for assistance in designing systems for such sites. Reference Drawings