HF-M Blue

advertisement
HF-M Blue
Electronic ballasts for f luorescent lamps
Product Description
• Compact light weight, high-frequency cold
• Fixing centers for mounting remain same as
equivalent electromagnetic ballasts
start CE compliant electronic ballasts for TL
(13-18W), TL5 (14-24W) and compact
Applications
fluorescent PL (10-28W) lamps.
• HF-M Blue ballasts are designed for areas
where the lighting is switched on and off
Features and Benefits
• Instant start flicker-free starting, ideal for
lighting applications with long burning hours
and infrequent switching for optimum lamp
infrequently
• HF-M Blue should not be used in combination with movement/ presence datection
• Typical areas of application in indoor
life. It is advisable to use HF-M Blue ballasts
residential situations indude living rooms
where the lighting is burning continuously for
kitchens (under cupboards), studies
at least 3 hours (3-8 switching per day), or in
(desktop), bedrooms, halls, staircases and
residential applications where the intensity of
garages
use is limited
• Energy savings of more than 25% (at equal
• Typical outdoor residential situations include
driveways, porches front doors and galleries
luminous flux) compared with electromag-
• Suitable for DC operations
netic gear
• For luminaires with protension class I and II
• Multi-lamp ballast one type can be used to
drive a single lamp of different types and
can meet EMC requirement if follow the
assembly instructions
wattages, e.g. a TL mini 13W, or a PL-S 11W
or a PL-C 10/13W or a PL-Q 16W or a TL5
Quality
HE 14W lamp can be connected to the
This implies optimum quality regarding
HF-M Blue 114 SH TL/ PL-S/ PL-C 220-240V
• System supplier
ballast
• Compact dimensions and low weight
As manufacturers of lamps and electronic
control gear, Philips makes sure that, from
compared to electromagnetic ballasts that
the earliest development stage, optimum
this design replaces
lamp/ballast performance is achieved.
Compliances and approvals
• RFI<300MHz
EN 55015 ed7.1
• Harmonics
IEC 61000-3-2
• Safety
IEC 61347-2-3
• Vibration & bump tests
IEC 68-2-6 FC
C1
ISO 9001
• Environmental standard
ISO 14001
• Certificates
KEMA-KEUR
A1
A1
B1
B1
D1
D1
A2
IEC 68-2-29 Eb
• Quality standard
C1
C2
A2
HF-M Blue LH
HF-M Blue SH
CE
Type
A1
A2
B1
C1
C2
D1
HF-M Blue 114 SH TL/PL-S/PL-C 220-240V
80
70
40
22
10
4.4
HF-M Blue 121 LH TL5 220-240V
187
176
22
22
-
4.4
HF-M Blue 124 LH TL/TL5/PL-L 220-240V
187
176
22
22
-
4.4
HF-M Blue 126 LH PL-Q/PL-C/PL-T 220-240V
144
132
22
22
-
4.4
HF-M Blue 124 SH TL/TL5/PL-L 220-240V
94
84
40
22
10
4.4
HF-M Blue 118 SH PL-C/PL-T 220-240V
80
70
40
22
10
4.4
Technical data
Type
Rated input
power (1)
HF-M Blue 114 SH TL/PL-S/PL-C 220-240V
11-14
Rated
Lamptype
Line
voltage
Line
Frequency
Battery
voltage
lamp
ignition
Mains
voltage
safety
(AC)
TL mini 13W; TL5 HE 14W; PL-S 11W; PL-C 10/13W; PL-Q 16W
220-240V
50/60Hz
194-254V
198-264V
(W)
HF-M Blue 121 LH TL5 220-240V
21
TL5 HE 21W
220-240V
50/60Hz
194-254V
198-264V
HF-M Blue 124 LH TL/TL5/PL-L 220-240V
17-23
TLD 15/18W; TL5 HO 24W; TL5C 22W; PL-L 18/24W
220-240V
50/60Hz
194-254V
198-264V
HF-M Blue 126 LH PL-Q/PL-C/PL-T 220-240V
21-24
PL-Q 28W; PL-C 26W; PL-T 26W
220-240V
50/60Hz
194-254V
198-264V
HF-M Blue 124 SH TL/TL5/PL-L 220-240V
17-23
TLD 15/18W; TL5 HO 24W; TL5C 22W; PL-L 18/24W
220-240V
50/60Hz
194-254V
198-264V
HF-M Blue 118 SH PL-C/PL-T 220-240V
18
PL-C 18W; PL-T 18W
220-240V
50/60Hz
194-254V
198-264V
(1) Depending on lamp combination
Type
Power Factor
Power
Maximum
Colour
Colour
Conn.type
Conn.type
100% output
losses
ighition
input
output
input
output
power
gear
time
terminals
terminals
terminals
terminals
HF-M Blue 114 SH TL/PL-S/PL-C 220-240V
0.6 - [nom]
1.7-2.3W
0.5 s [max]
Grey
Grey
Insert
Insert
HF-M Blue 121 LH TL5 220-240V
0.6 - [nom]
1.7-2.6W
0.5 s [max]
Grey
Grey
Insert
Insert
(1)
HF-M Blue 124 LH TL/TL5/PL-L 220-240V
0.6 - [nom]
2.5W
0.5 s [max]
Orange
Grey
Insert
Insert
HF-M Blue 126 LH PL-Q/PL-C/PL-T 220-240V
0.6 - [nom]
2.5-3.0W
0.5 s [max]
Blue
Grey
Insert
Insert
HF-M Blue 124 SH TL/TL5/PL-L 220-240V
0.6 - [nom]
1.7-2.6W
0.5 s [max]
Orange
Grey
Insert
Insert
HF-M Blue 118 SH PL-C/PL-T 220-240V
0.6 - [nom]
2.5W
0.5 s [max]
Orange
Grey
Insert
Insert
(1) Depending on lamp combination
Mains current
Type
Input current
A
HF-M Blue 114 SH TL/PL-S/PL-C 220-240V
0.09-0.12
Mains frequency
50/60 Hz
Power factor
0.6
Earth leakage current
NA
Ignition time
< 0.5 s
Over voltage protection
48 hrs at 276 V AC
HF-M Blue 124 LH TL/TL5/PL-L 220-240V
0.13-0.16
Dual fixture
NA
HF-M Blue 126 LH PL-Q/PL-C/PL-T 220-240V
0.15-0.18
Cable capacity
Max. 120 pF between lamp wires
HF-M Blue 124 SH TL/TL5/PL-L 220-240V
0.13-0.16
HF-M Blue 121 LH TL5 220-240V
0.15
HF-M Blue 118 SH PL-C/PL-T 220-240V
0.13
and earth
Automatic restart after
No, manual restart request
lamp replacement
Insulation resistance test
Inrush current
Type
500 V DC from
Line/Neutral to Earth
(not between Line and Neutral)
Max. quantity of ballast per
Miniature Circuit Breaker
16A
HF-M Blue 114 SH TL/PL-S/PL-C 220-240V
HF-M Blue 121 LH TL5 220-240V
100
60
HF-M Blue 124 LH TL/TL5/PL-L 220-240V
60
HF-M Blue 126 LH PL-Q/PL-C/PL-T 220-240V
60
HF-M Blue 124 SH TL/TL5/PL-L 220-240V
HF-M Blue 118 SH PL-C/PL-T 220-240V
60
100
Notes:
1. Ensure that the neutral is reconnected again after above mentioned
test is carried out and before the installation is put into operation.
Electrical installation notes
Mains operation
Rated mains voltage
220-240 V
With tolerances for safety +/- 10%
198-264 V
With tolerance for ignition & burning: +5%, -15%
184 - 253 V
Technical data for design and mounting HF-M Blue ballasts
Connector types:
in fixtures
Connection wiring is greatly simplified by the use of insert contacts with
Temperatures
push buttons.
Temperature range to ignite lamp
-10ºC to +40ºC
with ignition aid
Wire lenghts:
Max. Tcase
75ºC
After finishing system installation, please check carefully before you turn
the power on.
Lifetime of a ballast depends on the temperature of the ballast. This
1. Check whether lamp, ballast model and wiring are compatible
means there is a relation between the Tc point on the ballast and its
according to Philips HF-M Blue datasheet.
lifetime.
2. Keep wires to terminals 1, 2 short.
The HF-M Blue ballast has a specified lifetime of 30,000 hrs, with a
3. Mismatch of the ballast and lamp may lead to ballast failure.
maximum of 10% failures guaranteed, at a measured Tcase of 75°C .
Wire cross-section:
Independent lamp operation function
NA
Hum and noise level
On the mains side
0.5 ...1.5 mm2
On the lamp side
0.5 ...1.5 mm2
Strip length
7.5 - 8.5 mm
< 30dB at 1m distance
Permitted humidity is tested according to IEC 61347-2-3 par.11.
Note that no moisture or condensation may enter the ballast.
Notes:
1. Data is based on a mains supply with an impedance of 400mΩ, under
worst case conditions. With an impedance of 800mΩ the number of
ballasts can be increased by 10%.
2. Measurements will be verified in real installations; therefore data are
L
N
HF-M Blue
Ballast
subject to change.
1
2
3
4
3. In some cases the maximum number of ballasts is not determined
by the MCB but by the maximum electrical load of the lighting
installation.
4. Note that the maximum number of ballasts is given when these are
all switched on at the same moment, i.e. by a wall switch.
5. Measurements were carried out on single-pole MCB’s. For
multi-pole MCB’s, it is advised to reduce the number of ballasts by
20%.
Ordering and packing data
Type
Net weight
Qty bulk
Dimensions
Ordering Number
Gross weight
Pallet packing
per piece
packing
bulk packing
per carton box
kg
pcs
cm
kg
carton / ballast
pcs
HF-M Blue 114 SH TL /PL-S/PL-C 220-240V
0.048
50
21.5 x 17.5 x 13.0
9137 130 353
3.1
200/10000
HF-M Blue 121 LH TL5 220-240V
0.058
50
23.0 x 20.0 x 13.0
9137 130 352
3.6
200/10000
HF-M Blue 124 LH TL /TL5/PL-L 220-240V
0.058
50
23.0 x 20.0 x 13.0
9137 130 350
3.6
200/10000
HF-M Blue 126 LH PL-Q/PL-C/PL-T 220-240V
0.052
50
23.0 x 16.0 x 13.0
9137 130 354
3.3
240/12000
HF-M Blue 124 SH TL /TL5/PL-L 220-240V
0.052
50
21.1 x 19.8 x 13.0
9137 130 351
3.3
200/10000
HF-M Blue 118 SH PL-C/PL-T 220-240V
0.048
50
21.5 x 17.5 x 13.0
9137 130 349
3.1
200/10000
Download