INDUSTRY TOPICS TESTING ROTATING MACHINERY POLARIZATION/ DEPOLARIZATION CURRENT (PDC) B Y V I CK I WA R R E N , Iris Powe r LP The insulation resistance (IR) and polarization index (PI) tests [IEEE Std. 43-2000, ANSI/NETA ATS/MTS], should be done prior to application of any high voltage tests or return to service to assure that the winding is not wet or dirty enough to pose a risk of failure that might be averted by a cleaning and drying-out procedure. IR/PI is a useful indicator of contamination and moisture on the exposed insulation surfaces of a winding, especially when there are cracks or fissures in the insulation. These tests are easily done (see NETA World Winter 2011 and Spring 2012 issues). Since squirrel cage induction motor rotor windings are not insulated, these tests are not appropriate. Resistance testing is principally a pass/fail criterion and cannot be relied upon to predict the condition of the main insulation except when the insulation has already faulted. Experience has shown that IR/PI is a useful indicator of contamination and moisture on the exposed insulation surfaces of a winding, especially when there are cracks or fissures in the insulation. However, as discussed in IEEE 43, the IR/PI test does not seem to be sensitive to many other stator winding insulation problems such as: •Loose coils in the slot that lead to insulation abrasion •Delamination of the insulation due to operation at high temperature 94 • SPRING 2014 •Separation of the copper from the groundwall insulation due to load cycling • Deterioration of the stress relief coatings •Partial discharge (PD) between coils in different phases due to insufficient spacing in the endwindings AC tests, such as partial discharge (described in NETA World Winter/Spring 2013) are effective in finding these issues, but are cumbersome to do in an offline configuration due to the need of a large ac power supply; therefore, more sophisticated dc tests that some have proposed may detect more kinds of problems than the simple IR/PI test. Included in the NETA World Spring 2012 issue was a section about the dielectric response analysis (DRA) or polarization/depolarization current-measurement (PDC). This measures the charging and discharging currents of the winding insulation of stator or rotor winding. Reportedly, the results of the measurement provide information about the condition of machine insulation (cleanliness, humidity, ageing, corrosion, resin decomposition, and similar characteristics). TESTING ROTATING MACHINERY POLARIZATION/DEPOLARIZATION CURRENT (PDC) INDUSTRY TOPICS THEORY The new draft standard (IEEE Std. 43 draft revision 2012) has an annex that deals with additional information that can be obtained by applying a stable dc voltage to a complete stator winding or individual phases for 1000 to 2000 seconds and recording the polarizing current IP versus time. The voltage is then removed and the discharge current ID is monitored as a function of time using a suitable discharge circuit. When the voltage is removed, reverse current flows and the molecules in the insulation become disorientated and the space charge dissipates. This discharge current ID has two main components: a capacitive discharge current component, which decays nearly instantaneously, depending upon the discharge resistance; and the absorption discharge current, which will decay from a high initial value to nearly zero with the same characteristics as the initial charging current but with the opposite polarity. Normally, neither the surface leakage IL nor the conduction current IG affects the discharge current. Differences in the IP and ID [Figure 1] may indicate winding lack of curing, moisture absorption, surface contamination, damage to the voltage stress coatings, or severe thermal deterioration of the bulk of the insulation. Figure 1: Charging and Discharging Curves EXAMINATION OF THE PDC TEST Since the IEEE 43 standard suggests that the PDC test is valid for testing windings for thermal deterioration, tests were done on a motor stator rated 13.2 kV, 6000 HP known to be thermally aged, but clean and dry. Both the PDC test and the ac offline partial discharge test were done, as the latter has proven to be effective for evaluating insulation delamination. The stator had an asphaltic mica insulation system and was several decades old. The three Figure 2: PDC plot for A-phase with a 10 kV charge cycle (other phases were identical). The charge current is the upper line and the discharge current is the bottom line. The logarithmic vertical scale goes from 0.1 μA to 1000 μA and the horizontal axis ranges from 1 to 1000 seconds. TESTING ROTATING MACHINERY POLARIZATION/DEPOLARIZATION CURRENT (PDC) NETAWORLD • 95 INDUSTRY TOPICS phases in the stator could be isolated from each other to facilitate testing of each phase. Figure 3: LF PD plot for phase A, which had the highest PD at 8 kV. Note that the polarity of the PD plotted between 0 and 180 degrees has been inverted. The linear scale ranges from 0 to 11 nC. Figure 4: PD response from stator phase A, which had the highest PD at 8 kV. 96 • SPRING 2014 Polarization/Depolarization Test For these tests, a PDTech DRA 3 was used to record the polarizing and depolarizing dc currents. It applies a positive dc voltage to the test object at a selected voltage (usually 5 or 10 kV for these experiments) and for a selected time (usually 1000 s – about 16.7 minutes), while measuring the charging current. The dc supply is then removed from the test object and the test object is grounded. The discharge current-to-ground is then measured for the same amount of time. Software records these currents, inverts the discharge current, and displays both the charge and discharge currents in the same plot against time, with the plot time origin starting from either the start of the charge cycle, or the start of the discharge cycle (Fig. 2). The difference in the charge and absolute value of the discharge current can also be displayed. The instrument also calculates the IR and PI. All tests were done at 20°C. Partial Discharge Test Partial discharge tests were conducted using a conventional IEC 60270 PD detector, a PDTech DeltaMaxx, working in the low frequency (<3 MHz), broadband range. This instrument automatically converts the measured pulse magnitude in mV into pC, per the procedure in IEC 60270. The PD was also measured in the VHF range (30-300 MHz) range with an Iris Power TGA-B, more typically used for on-line PD monitoring. This device does not perform an automatic normalization, instead it reports the PD magnitudes in mV. The PD tests were performed at rated line-to-ground voltage, and the data was recorded after stabilization at the test voltage for 10 minutes. The low frequency (LF) and VHF phase-resolved PD plots for the worst phase (A-phase) are shown in Figures 3 and 4, respectively. TESTING ROTATING MACHINERY POLARIZATION/DEPOLARIZATION CURRENT (PDC) INDUSTRY TOPICS Table 1: Summary of Diagnostic Results for the Motor Stator Winding Test Configuration IR PI (GΩ) VHF PD (mV) LF PD (nC) DF (@2 kV) Tip-Up Qm+ Qm- Qm (%) (%) A 5.1 3.4 1066 888 9.7 4.7 0.79 B 5.2 3.4 275 330 3.7 4.6 0.73 C 5.0 3.4 433 440 2.9 4.8 0.80 Conclusion Table I shows a summary of the test results for each phase of the winding. PDC plots for each phase are shown in Fig. 2. When all three phases are super-imposed, all the charge currents and all the discharge currents overlap completely. It is clear from Table I that A phase has the highest PD in both frequency ranges. Since the positive and negative PD is about the same (within +/- 25%), then based on normal PD interpretation rules (see IEEE 1434 or IEC 60034-27), one suspects the PD is due to groundwall delamination, and when compared to the instrument manufacturer’s database would be ranked as Very High. PDC has been proposed as an off-line tool that can detect issues besides contamination and moisture absorption, such as something that can be used to confirm the diagnosis of insulation condition obtained from on-line PD testing, without having to use a large ac transformer to energize the winding for an off-line PD or tip-up test. The comparison tests described here did not produce consistent results. Clearly more tests are required to determine its efficacy. REF EREN C ES 1. IEEE, Recommended Practice for Testing Insulation Resistance of Rotating Machinery, IEEE std. 43-2000 2. ANSI/NETA, Standard for Acceptance Testing Specifications for Electrical Power Distribution Equipment and Systems, 2009 edition 3. ANSI/NETA, Standard for Maintenance Testing Specifications for Electrical Power Distribution Equipment and Systems, 2007 edition 4. Stone, G., and Sasic, M., Experience with DC PolarizationDepolarization Measurements on Stator Winding Insulation, Electrical Insulation Conference (EIC), Ottawa, Ontario, March 2014. 5. IEC 60034-27, “Off-line partial discharge measurements on the stator winding insulation of rotating electrical machines” Vicki Warren, Senior Product Engineer, Iris Power LP. Vicki is an electrical engineer with extensive experience in testing and maintenance of motor and generator windings. Prior to joining Iris in 1996, she worked for the U.S. Army Corps of Engineers for 13 years. While with the Corps, she was responsible for the testing and maintenance of hydrogenerator windings, switchgear, transformers, protection and control devices, development of SCADA software, and the installation of local area networks. At Iris, Vicki has been involved in using partial discharge testing to evaluate the condition of insulation systems used in medium- to high-voltage rotating machines, switchgear and transformers. Additionally, she has worked extensively in the development and design of new products used for condition monitoring of insulation systems, both periodical and continual. Vicki also actively participated in the development of multiple IEEE standards and guides and was Chair of the IEEE 432000 Working Group. TESTING ROTATING MACHINERY POLARIZATION/DEPOLARIZATION CURRENT (PDC) NETAWORLD • 97