PROJECT DATA SAN JUAN COUNTY APPLICABLE CODES: 2009 INTERNATIONAL BUILDING CODE 2009 UNIFORM MECHANICAL CODE 2011 NATIONAL ELECTRICAL CODE 2009 INTERNATIONAL FIRE CODE 2009 UNIFORM PLUMBING CODE CABO/ANSI A 117.1-2009 2009 NEW MEXICO BUILDING CODE 2009 INTERNATIONAL EXISTING BUILDING CODE OCCUPANCY TYPE (PER SECTION 302): A3 CONSTRUCTION TYPE (PER TABLE 601): VB 4,181 S.F. 648 S.F. 5,289 S.F. OCCUPANT LOAD: DINING ROOM: KITCHEN: OFFICES: TOTAL: TITLE SHEET CIVIL SG-1 STRUCTURAL S1 FOUNDATION & ROOF FRAMING PLANS S2 GENERAL STRUCTURAL NOTES & DETAILS S3 FOUNDATION & ROOF FRAMING DETAILS 2,728 S.F. / 15 = 182 950 S.F. / 200 = 5 246 S.F. / 100 = 3 190 MECHANICAL M101 MECHANICAL FLOOR PLANS M601 MECHANICAL SCHEDULES & DETAILS P101 PLUMBING FLOOR PLANS P601 PLUMBING SCHEDULES & DETAILS PLUMBING FIXTURE REQUIREMENTS: (PER TABLE 2902.1) REQUIRED: PROVIDED: 1 W.C., 1 LAV PER SEX WOMEN: 2 W.C., 1 LAV MEN: 1 W.C., 1 LAV, 1 UR. PROPERTY OWNER: SAN JUAN COUNTY PROPERTY ADDRESS: 17 CR 6668 FRUITLAND, NM 87416 SITE GRADING PLAN ARCHITECTURAL C1 SITE IMPROVEMENT PLAN C2 SITE LANDSCAPING PLAN A1 DEMOLITION & FLOOR PLANS A2 BUILDING ELEVATIONS/SECTIONS A3 WALL SECTIONS A4 ROOF & REFLECTED CEILING PLANS A5 EQUIPMENT PLANS HC1 HANDICAP REQUIREMENTS LOWER VALLEY SENIOR CENTER MAX. ALLOWABLE SQUARE FOOTAGE 6,000 S.F. PER FLOOR: (PER TABLE 503) NOTE: THIS IS A LEVEL 2 ALTERATION PER SECTION 604.2.2.3, NO FIRE SPRINKLER SYSTEM IS REQUIRED BUILDING AREA: EXISTING: NEW: TOTAL: INDEX OF DRAWINGS ELECTRICAL E001 ELECTRICAL EP101 ELECTRICAL EL101 ELECTRICAL E501 ELECTRICAL E601 ELECTRICAL VICINITY MAP LEGENDS & GENERAL NOTES POWER PLANS LIGHTING PLANS RISERS & SCHEDULES SCHEDULES TO SHIPROCK HWY. 6 4 TO FARMING TO COUNTY COMMISSIONERS CHAIRMAN: SCOTT ECKSTEIN CR 6400 CR 6668 CR 6663 CR 6675 N COMMISSIONERS: GLOJEAN TODACHEENE MARGARET McDANIEL JACK FORTNER KEITH JOHNS CR 6100 PROJECT LOCATION COUNTY MANAGER: KIM CARPENTER BID #15-16-20 RODAHL & HUMMELL ARCHITECTURE, P.C. ARCHITECTURE 609 NORTH DUSTIN FARMINGTON, N.M. (505)326-6442 (505)325-1412 (PHONE) SET No. _____ N (FAX) 04.11.16 DATE: April 11, 2016 PROJ. No. 151120 N 04.11.16 RODAHL & HUMMELL ARCHITECTURE, P.C. N ARCHITECTURE 609 North Dustin Farmington, NM 87401 Phone: (505) 326-6442 LOWER VALLEY SENIOR CENTER FRUITLAND, NM SITE IMPROVEMENTS PLAN Checked: Date: Drawn: TEH 04.11.16 BTW Filename: 1120_SITE Project: 151120 Sheet: C1 Of: D E E A C C E E D E C B C C E E D E A A A E C D E C N A B 04.11.16 RODAHL & HUMMELL ARCHITECTURE, P.C. C D E ARCHITECTURE 609 North Dustin Farmington, NM 87401 Phone: (505) 326-6442 LOWER VALLEY SENIOR CENTER N FRUITLAND, NM SITE LANDSCAPING PLAN Checked: Date: Drawn: TEH 04.11.16 BTW Filename: 1120_LAND Project: 151120 Sheet: C2 Of: N N WAREWASH 04.11.16 RODAHL & HUMMELL ARCHITECTURE, P.C. ARCHITECTURE 609 North Dustin Farmington, NM 87401 Phone: (505) 326-6442 LOWER VALLEY SENIOR CENTER FRUITLAND, NM N DEMOLITION/FLOOR PLANS Checked: Date: Drawn: TEH 04.11.16 BTW Filename: 1120_FLOOR Project: 151120 Sheet: A1 Of: N COOLER/ FREEZER 04.11.16 WAREWASH RODAHL & HUMMELL ARCHITECTURE, P.C. ARCHITECTURE 609 North Dustin Farmington, NM 87401 Phone: (505) 326-6442 LOWER VALLEY SENIOR CENTER FRUITLAND, NM Filename: 1120_ELEV Project: 151120 Sheet: A2 BUILDING ELEVATIONS/SECTIONS Checked: Date: Drawn: TEH 04.11.16 Of: BTW N 04.11.16 RODAHL & HUMMELL ARCHITECTURE, P.C. ARCHITECTURE 609 North Dustin Farmington, NM 87401 Phone: (505) 326-6442 LOWER VALLEY SENIOR CENTER FRUITLAND, NM WALL SECTIONS Checked: Date: Drawn: TEH 04.11.16 BTW Filename: 1120_ELEV Project: 151120 Sheet: A3 Of: WAREWASH N N 04.11.16 RODAHL & HUMMELL ARCHITECTURE, P.C. ARCHITECTURE 609 North Dustin Farmington, NM 87401 Phone: (505) 326-6442 LOWER VALLEY SENIOR CENTER FRUITLAND, NM N ROOF & REF. CEILING PLANS Checked: Date: Drawn: TEH 04.11.16 BTW Filename: 1120_roof Project: 151120 Sheet: A4 Of: WAREWASH N N 04.11.16 RODAHL & HUMMELL ARCHITECTURE, P.C. ARCHITECTURE 609 North Dustin Farmington, NM 87401 Phone: (505) 326-6442 LOWER VALLEY SENIOR CENTER FRUITLAND, NM EQUIPMENT PLANS Checked: Date: Drawn: TEH 04.11.16 BTW Filename: 1120_EQU Project: 151120 Sheet: A5 Of: STATEMENT OF SPECIAL INSPECTIONS WOOD FRAMING AND SHEATHING CONCRETE AND REINFORCING GENERAL NOTES Per Chapter 17 of the 2006 International Building Code, it is required that special inspections be performed to verify that the materials and construction methods used in the construction of the project, as described in the construction documents, complies with these documents and applicable standards. The owner or the owner's agent shall be responsible for employing qualified third party inspectors for each of the building materials described in the table below. The materials shall be inspected at frequencies as listed in the table below, as required in the details and as required to verify compliance with the construction documents. If a condition in question arises, the special inspector shall request clarification from the Engineer of Record. 1. These notes do not represent all framing requirements. The builder shall do the work in a conscientious workmanlike fashion and conform to the requirements of the International Building Code. 2. Wood bearing on Concrete shall be pressure treated. 3. Wood sills shall be fastened to concrete or masonry with 5/8" diameter anchor bolts spaced at a maximum of 4'-0" o.c. unless detailed otherwise. There shall be at least 2 bolts per each wood member and bolts shall be located within 8" of each end of each member. The anchor bolts shall be embedded in the concrete 7 inches minimum UNO. 4. Structural lumber shall be grade stamped by a certified agency. Lumber shall be manufactured to S-Dry and seasoned for 60 days. 5. Lumber Species and Grades: (unless noted otherwise in the drawings) 1. Sill Plates: Hem-Fir #2 pressure treated or foundation grade redwood 2. Rafters and Joists: Hem-Fir #2 except for 2x12s which shall be Douglas Fir #2 3. Headers, Beams, Miscellaneous Framing : Hem-Fir #2 (UNO) 4. Blocking: Hem-Fir #2 5. Posts: Douglas-Fir #1 6. 4 x Beams: Douglas-Fir #2 7. 6 x Beams: Douglas-Fir #1 6. Fire-stop all stud walls with 2x lumber at each floor, at roof level and at 8'-0" o.c. max. in between floors and roof. 7. All joists, trusses and rafters shall have continuous 2x solid blocking provided between them at all bearing points. 8. Nails shall be box nails unless noted otherwise in the plans. Nails for exterior uses shall be galvanized. 9. All lag bolts shall be placed in sub-drilled holes. 10. Bolts shall be placed thru holes drilled 1/32" larger than the bolt diameter. 11. All bolts and lag bolts shall have flat washers under nut and bolt head. 12. Built-up wood members (multiple members assembled to form one member) shall be progressively fastened as follows: 1. 3-1/2" to 9'1/4" depth............2-10d @ 8"o.c., staggered 2. 9-1/4" to 11-1/4" depth.........3-16d @ 6"o.c. in 3 staggered ro 3. 11-1/4" to 18" depth..............2 rows of 1/2" diameter bolts @ 18" o.c., staggered. 13. When joists, rafters or trusses are @ 24" oc, they shall fall within 4" of a stud below. Studs shall be added as required. 14. Wall top plates shall be lapped 4'-0" minimum and nailed with 18-10d minimum. Top plates shall be lapped at all corners and nailed with 3-10d. 15. Wood connection hardware shall be fully fastened to wood members as required by hardware manufacturer. 16. Sheathing for roofs and walls shall be American Plywood Association (APA) stress rated sheathing. Sheathing Schedule (U.N.O. in plans): Min. Span Rating Floor Sheathing.................3/4" 48/24 Roof Sheathing.................5/8" 40/20 Wall Sheathing.................7/16" 24/16 Roof and floor sheathing shall be applied with long dimension perpendicular to framing and end joints shall be staggered 4'-0". Use plyclips with roof sheathing spans of 24" or more. Wall sheathing behind stucco shall be applied horizontally. All sheathing shall be rated Exposure 1 (and conform to NRB-108). See plans for fastening, blocking and other requirements. 17. Glue-Laminated Beams: Species..................Douglas Fir/Douglas Fir Fb..........................2400 psi, Combination 24F-V4 Fs...........................165 psi 18. Trusses shall be plant manufactured. The truss manufacturer shall provide shop drawings stamped by a Professional Engineer currently licensed in the state in which the trusses will be used. The trusses shall be specifically designed for all loads and conditions indicated in the plans. The shop drawings shall show all loads, design conditions and truss member design criteria. They shall be approved by the Engineer prior to fabrication. The minimum plate size shall be 2" x 4". All joints shall have plates of equal size applied to both sides. The truss manufacturer shall design, provide and show locations for all required bracing and bridging. All compression joints shall be butted tightly together or the plates shall be designed for 100% of the compression forces. Truss vertical deflection shall be limited to span length divided by 360 (L/360) under total load. 19. Wood Nailing Schedule: 1. Joists/Rafters to bearing plates...............................1-16d TN @ E.S. 2. Stud to sill plate.....................................................2-16d end nails 3. Blocking/Bridging to Rafters/Joists.........................3-16d @ E.E. 4. Top plates to Stud..................................................2-16d end nails 5. Double top/bottom Plates......................................10d @ 12" o.c. (staggered) 6. Multiple Studs...............................16 d @ 12" o.c. from ea. stud to the previous stud, staggered. 1. 1. In the absence of specific details refer to appropriate typical details or similar details for information. If any questions remain call the Engineer for clarification. 2. The plans and details in some areas represent assumptions made of existing conditions. The Contractor shall notify the Engineer immediately if conditions are found different from those assumed. The Engineer shall also be notified if field conditions necessitate changes from the plans. In either case detail changes may be required before work can proceed. 3. The plans shall not be scaled to obtain working dimensions. If dimensions are missing from the plans get clarification from the Architect or the Engineer. Cross-check all dimensions with the architectural plans. All layout dimensions shall be closed from both directions. 4. See architectural plans for all other non-structural information. 5. All openings or modifications to structure not shown on the structural plans shall be verified with the Engineer before doing the work. 6. The Contractor shall repair or replace all damaged materials. 7. The Contractor shall notify the Architect and Engineer of any discrepancies found in the contract documents ( plans and specifications ). Clarifications shall be received from the Architect or Engineer before proceeding with the work. The most restrictive condition shall govern when clarification is not obtained. 8. All mechanical unit weights shall be verified with loads shown on the structural drawings. Notify the Engineer, if weights are different than those shown or units are required where not shown on the structural drawings. 9. These plans represent a design for final in-place conditions. It shall be the Contractors' responsibility to account for all construction conditions, loads, sequences, temporary bracing requirements, all safety considerations, OSHA regulations, and all other applicable standards. 10. Construction shall follow the plans, details, notes and specifications. The Contractor shall be directly responsible for uncorrected errors or deviations from the plans without the Engineers approval. The Engineer will be available for considerations and repairs. Excessive repair detailing or revision to the contract documents shall be paid for by the Contractor. 11. Each sub-contractor shall inspect the conditions and work in place before they begin. Errors, problems and unacceptable conditions shall be repaired before beginning the new work. Beginning the new work shall be interpreted as acceptance of the previous work and conditions. 12. When shop drawings and product information are required for review by the Architect/Engineer, the Contractor shall allow 2 weeks for the review period. When shop drawings and product information are provided in large format (i.e. larger than 8 1/2" x 11"), one set of reproducibles shall be included with 3 sets of bluelines for mark-ups and stamping. The reproducibles will be returned to the Contractor to allow for his printing of as many sets of marked-up drawings as he shall require. The special inspector shall provide written reports of each material/activity inspected detailing the observations. The reports shall include, at a minimum, the time, date, and location on the project (described by areas, grids, materials, activity, etc.). Reports shall be organized in a numerical order for each material/activity. The report shall indicate if the inspection found the material/activity in conformance with the inspection documents or not. Non-conforming materials/activities shall be re-inspected after corrections have been made and followed by additional inspections and reporting until conformance is achieved. REQUIRED OBSERVATIONS The agreement for the design of these structural plans does not include a fee for construction observation or inspections of any kind to verify compliance. However, it is recommended that the owner/contractor contract with the Engineer or Architect or other qualified third party observer to make the following observations: 1. Exposed native soils shall be observed and approved by the Soils Engineer and the Engineer before placing structural fill or forming for concrete. 2. Material for structural backfill shall be observed and approved by the Soils Engineer before use. Structural backfill placement and compaction shall be observed, tested, and approved by the Soils Engineer before placing foundations. 3. Concrete reinforcing and formwork shall be observed and approved by the Engineer before placing concrete. 4. Framing shall be observed and approved by the Engineer before covering. 5. Shearwall construction and connections shall be observed and approved by the Engineer before covering. 6. Contractor shall provide 24 hour notice for observations. ABBREVIATIONS A.A. = Adhesive anchor A.B. = anchor bolt AB = post above ABC = aggregate base course ABV. = above ADJ = adjacent AGG = aggregate ARCHT = architect B.B. = bond beam B.F. = bottom of footing elev., or = backfill BLK = block BLDG = building BLKG. = blocking BM = beam BRG = bearing BTWN = between B.U. = built-up CJ = construction joint or, = contraction joint or CLG. = ceiling CMU = concrete masonry unit COL. = column CONC. = concrete CONN. = connection CONT. = continuous CONTR. = contractor C.P. = cripple post CTR. = center CTR'D = centered DAS = deformed anchor stud DBL.= double D.F. = Douglas Fir - Larch DIA. = diameter DL = dead load DTL. = detail DWG. = drawing DWL. = dowel EA = each EE = each end E.F. = each face E.J. = expansion joint ENGR. = engineer EQ. = equal E.S. = each side E.W. = each way EXP = expansion EXT = exterior FDN = foundation FF = finished floor elevation F.J. = floor joist FG = finished grade elevation F.O. = face of FOC = face of concrete FOS = face of stud FOM = face of masonry FRMG = framing F.S. = far side FTG. = footing GA = gage GALV = galvanized G.B. = Grade Beam GL = glue laminated beam GR. = grade HAS = headed anchor stud HDR. = header H.F. = Hem-fir HORIZ = horizontal H.S. = high strength INFO = information INT = interior JST. = joist JT. = joint KS = king stud LD = load LL = live load LLH = long leg horizontal LLV = long leg vertical LVL = laminated veneer lumber MAS = masonry MAT = material MAX = maximum M.B.M. = metal building mfr. Mfr. = manufacturer MIN = minimum NA = not applicable NLG = nailing N.S. = near side NTS = not to scale O/ = over O.C. = on center O.H. = opposite hand OPNG. = opening OSB = oriented strand board P/C = precast PL = plate PLYWD = plywood PNL = panel P.T. = pressure treated REINF. = reinforcing R.J. = roof joist SH/ = Simpson hardware SHT. = sheet SHTG. = sheathing SIM = similar SPA = space STL = steel SL = snow load S.O.G. = slab-on-grade S.S. = steel stud SW = shearwall T.B. = top of beam T.J. = top of joist T.L. = top of ledger T.M. = top of masonry TN = toe nail T.O. = top of T.O.C. = top of concrete T.O.S. = top of steel T.O.SHTG. = top of sheathing T.O.W. = top of wall T.P. = top of parapet T. PL = top of plate T.R. = threaded rod TS = trim studs or, = tube steel TYP = typical UNO = unless noted otherwise VERT = vertical WWF = welded wire fabric 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. Concrete shall b e made from an approved commercial mix of normal weight aggregates, potable water and Portland Cement ( type II ) meeting ASTM C150 specifications. Admixtures meeting ap propriate ASTM requirements may be used when approved by the Engineer. The Concrete shall have a minimum of 517 lb. of Portland Cement per yard and ha ve a maximum water to cementitious material ratio of 0.52. Fly ash meeting ASTM specifications maybe substituted for up to 25% of the Portland Cement in the mix designs at ratio of 1.0 lb. of fly ash for 1.0 lb. of Portland Cement. The proposed concrete mix designs shall be submitted to the Engineer for approval a minimum of 72 hours before delivery. Concrete shall achieve the following minimum compressive strengths ( f 'c ) in 28 days: footings and grade beams.................................................... 3000 psi interior slabs on grade........................................................... 3000 psi exterior slabs on grade.......................................................... 4000 psi Provide the following minimum thickness of concrete coverage around reinforcement: footings: to earth...................................3" to formed surfaces..................2" slabs: to earth...................................1" stemwalls and retaining walls: interior face............................3/4" exterior face...........................1 1/2" face exposed to earth.............2" Maximum allow able slump of concrete at the point of placement shall be 4" unless specifically ap proved otherwise by the Engineer and designed accordingly. All concrete (including slabs) shall be thoroughly consolidated by mechanical vibration. Reinforcing bars shall conform to ASTM A615. Reinforcing to be welded shall conform to ASTM A706: #3 to #5.......grade 40 ( U.N.O. ) #6 to #11.....grade 60 W elded W ire Fabric (WW F) shall conform to ASTM A18 5 and shall be provided in flat sheets. W WF in rolls shall not be used. WW F shall be chaired in place within 2" of the conc. final surface U.N.O. All reinforcing, anchorages and embedments shall be securely wired in place during concrete placement. Reinforcing shall not be heated to be bent. See typical details for reinforcing bending and splicing requirements. W elded W ire Fabric (when specified) shall be lapped a minimum of 1-1/2 wire spaces. Reinforcing shall be held above earth on concrete adobes, chairs or by suspension. Bars driven into the earth shall not be used to support reinforcing. All openings in slabs or walls shall be reinforced with a minimum of 2-#5 on 4 sides extending 2'-0" minimum beyond opening corners. Chamfer all exposed concrete edges unless detailed or noted otherwise. Openings in concrete shall be formed, cored or sawcut. Chipping and breaking out shall not be done unless specifically approved. Concrete exposed to freezing environment either during construction or in place shall be air entrained. Air entrainment of the mix shall be 4% minimum to 8% maximum based on volume. Typical slab on grade unless noted otherwise: 4 1/2" min. thick concrete with #4 at 24" o.c. each way chaired to be in the center of slab thickness. Place over a minimum of 4" of aggregate base course compacted to 95%.. All concrete slabs shall have contraction joints provided in the slabs according to the placement shown in plan or at approximately 15 feet on center each way if not indicated otherwise. The joints shall be made according to the typical details. Concrete Curing: Final concrete quality is highly dependant on curing. Inadequate curing can cause excessive shrinkage, cracking, low strength, slab curling and other detrimental effects. Concrete shall be cured as follows: slabs shall be moist cured with water and an impermeable barrier or with a water saturated cover. No portion of the slab shall be allowed to dry for 7 days. Other concrete shall be moist cured or cured with a curing compound conforming to ASTM C309 applied immediately after formwork is removed. Special protection measures shall be provided during windy and or hot we ather. Provide special inspection of epoxy anchors per 2009 IBC. MANFACTURED COMPOSITE JOIST PRODUCTS 1. Joists shall have current ICBO approvals. 2. Joist substitutions shall be approved by the Engineer and shall provide equivalent performance characteristics of those specified. Substitutions shall adequately support all design loads in all conditions. 3. Nail each joist to bearing plate with 3-10d box nails. 4. Metal hangers for floor joists shall have a bead of construction adhesive applied to the points of contact with the joist immediately before the joists are installed in the hanger. 5. Joist flanges shall not be cut between joist ends. Joist webs may only be penetrated according to manufacturer requirements and Engineers approval. 6. Joist manufacturer shall provide all joist blocking and shaped bearing plates. 7. Web fillers and stiffeners shall be of APA rated sheathing in a thickness equal to the offset distance from the joist web to the outside of the flanges. Hold the top of the filler/stiffener 1/8" below the bottom of the top flange and set tight to the top of the bottom flange. Fasten to the joist web with a minimum of 4-8d nails unless detailed otherwise. Apply to both sides of the web unless detailed otherwise. Length of filler/stiffener shall be as detailed or otherwise as required for the intent of the application. If the filler/ stiffener length is greater than 8", fasten to joist web with 2-8d at 12" on center. 8. Joists shall be maintained in a dry condition and stored off of the ground. 9. Joists shall be stored, handled, shipped and erected according to manufacturers requirements. Joists shall not be handled such that they will be allowed to bend in their weak direction. Damaged products shall not be used in the work. 10. Joist uses, details, sizes or spacings other than those shown on the plans shall not be allowed without specific approval and a stamped design/shop drawings from a registered Engineer licensed in the State of the product's use. 11. Check and verify all joist bearing elevations with Structural and Architectural drawings before installing joists. Notify Designer immediately of problems or discrepancies. Do not proceed without direction from Designer or Engineer. DESIGN CRITERIA 1. 2. 3. SPECIALTY CONNECTIONS / ANCHORAGES / FASTENERS 1. 2. 3. 4. 1. 2. 3. 4. 5. 6. 7. LAMINATED VENEER LUMBER (LVL) Framing of LVL shall be of sizes, numbers and lengths as required in plans. LVL provided shall have current ICBO approvals. Minimum bearing length shall be 3" U.N.O. Built-up member assembly: 2 Members (less than 14" deep)...........3 rows of 16d @ 12"oc from one side 2 Members (14" or deeper)..................3 rows of 16d @ 12"oc from one side 3 Members (less than 14" deep)...........3 rows of 16d @ 8" oc from each side 3 Members (14" or deeper)..................3 rows of 16d @ 6"oc from each side 4 Members (all)....................................2 rows of 1/2" diameter thru bolts @ 24" oc note: Nails shall be 16d common. Nails and bolts shall be staggered from adjacent rows 5. Design Properties (minimums): Fb = 2600 psi Fv = 220 psi E = 1,800,000 psi 6. LVL shall be maintained in a dry condition and stored off of the ground. Do not remove protective wrappings until ready for use. Expansion bolts, adhesive anchors, shotpins, headed anchor studs (HAS), self-tapping screws and other proprietary devices shall have ICBO approvals. These approvals along with load capacities and use information shall be submitted to the Engineer when materials other than those specified are proposed. Devices shall be used in full accordance with manufacturer's requirements. Headed anchor studs shall be welded all around the base of the stud with a 5/16" fillet unless noted otherwise. Stud guns may be used provided the attachment will develop the strength of the stud. Typical acceptable anchors (when called out in plans) unless noted otherwise: Expansion Bolts: 5/8" diameter by Hilti or Redhead with a minimum embedment of 4" Shotpins: 0.145" diameter minimum by Hilti or Ramset with 1" minimum embedment in concrete and a minimum safe working load in shear of 200 lb. Headed Anchor Studs: 1/2" diameter x 6" long by Nelson Stud Adhesive Anchors: Hilti HIT or HVA system sized for bolts required Self-Tapping Screw s: #10 TEK screws E ARTHWORK FOR FOUNDATIONS 8. 9. 1. 2. 3. 4. Superimposed Design Loads: Roof DL = 20 psf Roof Snow Load = 25 psf (base) Applicable Building Code = 2009 International Building Code W ind Load: a)basic wind speed........................90 mph (3 sec. gust) b)exposure category......................'B' c)importance factor(Iw)..................1.0 Seismic Load: a)Occupancy Category.................................II b)Site Class..................................................C c)Short Period Spectral response (Ss).........16% g d)importance factor(Ie)..................................1.0 10. 11. 12. 13. 14. 15. 16. 17. WOOD ROOF DECK 18. 1. Roof sheathing shall be 5/8" APA stress rated sheathing with a minimum span rating of 40/20. Sheathing shall have an Exposure 1 rating. Sheathing shall be laid out with the long dimension perpendicular to the framing. Stagger the ends of the sheets 4'-0" in each consecutive row of sheathing. Layout sheathing so the smallest pieces make two continuous spans. Provide plyclips at midspan or edge blocking when the framing is spaced at more than 24" oc. Provide 1/8" joint between all sheets at edges. Nail sheathing to all supports with 10d box nails at 5" oc at all sheet edges and 10" oc in the field of each sheet. 2. Verify framing space ventilation before beginning sheathing. Correct if necessary before beginning sheathing. 3. Fasteners other than those described may be used if approved by the Engineer (such as staples). Contact the Engineer for equivalent fastener schedule. 19. 20. The foundation des igns are based on a Geotec tnical In vestigation by Geomat Inc ., report #152-2408, dated Dec ember 9, 2015. Allowable s oil bearing pressure s truc tural back fill: 2500 psf @ 2'-6" em bedment All foundations shall bear entirely on s truc tural bac k fill over scarified & re-c om pacted native soils. S ee typical minimum earthwork detail A/S 1 for additional inform ation. All foundations shall bear entirely on 24" min. of structural fill ove r 8" o f nati ve soils that have been s carified and re-c ompacted @ plus / minus 3% of optim um moisture content. See m inim um ea rthw ork detail A/S1 for spec ifics . U nless noted otherwis e ex terior footings shall bear a m inim um of 30" below lowest adjacent grade an d interior footings shall have a minimum embedm e nt of 18". All earthwork cuts and fills shall be m ade in level b enches . All struc tural back fill m aterials shall be appro ved by the Soils E ngineer. Unless n oted otherwise, s tructural (or engineered) bac kfill shall be g ranular non-ex pans ive material m eeting the following minimum c riteria: no more than 5% s hall pass a 200 sc reen, 1 00 % shall pas s a 6 inch scree n, and the material shall be well graded unless it is sand or 3/4 inch washed gravel. Structural back fill s hall be moisture c onditioned, placed in thin lifts an d m echanically com pacted. Lifts s hall not ex ceed 8" in depth and shall be of de pths c om patible with the capa bilities of the machinery used. Back fill shall be uniformly moisture controlled to maintain spec ified compaction densities. U nless noted otherwis e all backfill s hall be compac ted to a minimum of 95% of the m aximum de nsity as d etermined by ASTM m ethod D698. All com pac tion densities noted in the plans are relative to max imum dens ity per AS TM D698 at optimum m oisture content unless noted othe rwise. Found ations s hall be c ons truc ted of c onc rete c ast in secure formwork . Co ncrete may be cas t in trenc hes agains t stable earth banks when a pproved by the Enginee r. R einforc em ent for concrete found ations s hall be supported 3" minimum from ea rth on all sides . R einforc em ent shall not be sup ported on bars driven into the earth. It shall be s upported on a pproved c hairs or adobes or s uspen ded from above. Found ations s hall not be placed on froz en ea rth or uns table conditions . Frozen earth shall be thawe d an d re -com pac ted before placing foundations. A ll s oft materials disc overed s hall be o ver-excavated as directed by the Soils E ngineer and replaced with com pacted enginee red m aterial. Geotex tile fabric s hall be pro vided for stabilization wh en c onditions dictate. W ater shall not be allowed from any s ource to ac cumulate in excavations . The C ontractor shall provide drainage to pre vent run-off water from entering ex ca vations and de-w atering when nec ess ary. If water does ac cumulate in the excavations and causes additional ea rthw ork , the additional work s hall be paid for by the contractor. The Contractor shall be responsible for s afely retaining all earth em bankm ents. Exterior grades adjacent s tructures s hall slope away from the s tructure on all sides at a minimum s lope 3% for 10 feet. A positive water flow s hall be p rovided fo r all loc ations to natural water cours es. Pro vide swales w here neces sary . No ponding of water shall b e allowed. Planters shall not be adjac ent structure exc ept when a des ign is s pecifically pro vided. R oof drains shall not empty onto exterior grade within fi ve feet of the fou ndations . S plash block s, leaders , concrete swales , or other m ea ns shall be used to direct water away from the structure for at leas t 5'-0" from the structure. All bac k fill at retaining walls shall be granular, free-draining, non-ex pansive m aterial c om pacted to 95% . Slabs shall be in place before walls are back filled. D eep rooted veg etation s hall not be placed clos er than 8-0" to the structure. Back fill shall be tested for com pac tion. M aterial failing the tes ts s hall be re-c ompac ted and then retested. Failing tes ts s hall be paid for by the earthwork c ontractor. One compaction test shall be provided for e very 32 c ubic yards of b ack fill material. C om paction densities s hall also be made under all found ations where the n ative earth is s carified a nd re-compacted. One compaction test s hall be made for every 50 linear feet of footing. D eviations from this s chedule shall require the approval of the Engineer. KEYED NOTES ENTRY 109 23.02 WOMEN 105 STORAGE 110 23.01 MEN 106 T 23.03 OFFICE 111 DINING ROOM 107 OFFICE 108 23.01 THROUGH THE WALL AC UNIT TO REMAIN. NO WORK. 23.02 REMOVE AND DISPOSE OF GAS FIRED UNIT HEATER AND RELATED CONTROLS, FLUE, HANGERS, GAS PIPING. REMOVE EXPOSED GAS PIPING. CAP BEHIND FINISHED SURFACES. ABANDON ALL INACCESSIBLE PIPING. SEE ARCHITECT FOR ROOF PATCH AND REPAIR REQUIREMENTS. 23.03 REMOVE AND DISPOSE OF EVAPORATIVE COOLER. REMOVE ALL WATER PIPING DOWN TO HOSE BIBB ON THE EAST SIDE OF BUILDING. CAP DUCT OPENING AND STUFF VOID WITH INSULATION. 23.04 REMOVE AND DISPOSE OF WALL FURNACE LOCATED IN THE UPSTAIRS STORAGE ROOM. REMOVE FLUE. SEE ARCHITECT FOR ROOF PATCH AND REPAIR REQUIREMENTS. 23.05 REMOVE FLUE. SEE ARCHITECT FOR ROOF PATCH AND REPAIR REQUIREMENTS. 23.06 ROOF EXHAUSTER AND RELATED TYPE II HOOD TO BE RELOCATED. SEE ARCHITECTURAL PLANS FOR NEW LOCATION. RELOCATE WALL SWITCH TO NEW WALL SURFACE. 23.07 ROOF EXHAUSTER AND RELATED TYPE I HOOD TO BE RELOCATED. SEE ARCHITECTURAL PLANS FOR NEW LOCATION. RELOCATE WALL SWITCH TO NEW WALL SURFACE. RELOCATE FIRE SUPPRESSION SYSTEM TO NEW WALL SURFACE. ADJUST ALL PIPING TO ACCOMMODATE NEW LOCATION/CONFIGURATION. WRAP NEW 16G. DUCT WITH 1 HOUR RATED FIRE WRAP. 23.08 ROOFTOP UNIT TO REMAIN. PROVIDE NEW GAS CONNECTION. SEE PROPOSED PLAN FOR NEW DUCTWORK ADDITION. 23.09 REMOVE 14"x14" COMBUSTION AIR WALL LOUVERS, SEE ARCHITECTURAL DRAWINGS FOR PATCH AND/OR REPAIR REQUIREMENTS. COMBUSTION AIR TO BE PROVIDED THROUGH THE ROOF. 23.10 RELOCATE HEATCRAFT MODEL# CHT009X68BFMT SERIAL# T13L05266 CONDENSING UNIT TO NEW ROOF ABOVE. EXTEND ALL PIPING ACCORDINGLY. 23.11 RELOCATE HEATCRAFT MODEL# CHT014L6BF SERIAL# T13J17429 CONDENSING UNIT TO NEW ROOF ABOVE. EXTEND ALL PIPING ACCORDINGLY. 23.12 ROOF EXHAUSTER TO REMAIN. NO WORK. 23.13 SIDEWALL SUPPLY GRILLE TO DISTRIBUTE AIR TO THE ATTIC. 23.14 4" DIA. DRYER DUCT TO WALL CAP WITH BACKDRAFT DAMPER. 23.15 CAP DRYER DUCT ON ROOF. 23.04 STORAGE 112 T 23.02 23.05 23.15 WAREWASH 114 23.08 23.12 EF2 R(E) 23.06 KITCHEN 104 OFFICE 113 23.07 EF3 EF1 23.10 23.09 COOLER/ FREEZER 115 23.11 1 MECHANICAL DEMOLITION PLAN 1/8" = 1'-0" ENTRY 109 STORAGE 110 CX1 CX2 A6 65CFM 10"ø T DINING ROOM 107 10"ø 10"ø 8"ø 12"x18" 6"ø 10"ø STORAGE A6 112 23.13 10"ø 6"ø C12"x6" 200CFM 12"x18" A6 75CFM A10 300CFM TYP.-12 10"ø 10"ø B2 OFFICE 108 18"x18" 60CFM B2 6"ø 18"x18" T A6 135CFM R2 R3 T 6"ø COMPUTER 101 10"ø 18"x12" R1 10"ø WAREWASH 114 R(E) A10 363CFM A6 89CFM OFFICE 113 A8 110CFM A8 100CFM 6"ø OFFICE 111 12"x12" 12"x12" 6"ø MEN 106 WOMEN 105 Stair 2 10"ø 10"ø 10"ø KITCHEN 104 B2 B2 COOLER/ FREEZER 115 A6 66CFM VEST 103 23.14 10"x10" 18"x12" A10 363CFM TYP.-2 03/31/2016 RODAHL & HUMMELL ARCHITECTURE, P.C. GAME ROOM 100 ARCHITECTURE 609 North Dustin Farmington, NM 87401 Phone: (505) 326-6442 LOWER VALLEY SENIOR CENTER R.R. 102 CX3 FRUITLAND, NM 2 MECHANICAL PLAN MECHANICAL FLOOR PLANS Drawn: 1/8" = 1'-0" DS Checked: TC Date: 2016-04-04 Filename: Project: 1538 Sheet: M101 Of: EF# SEE STRUCTURAL DRAWINGS FOR JOIST CONFIGURATION MECHANICAL GENERAL NOTES BREATHER TUBE EXISTING CURB 1. HANGERS WITH VIBRATION ISOLATORS FLEX CONNECTION, TYPICAL 6" CLEARANCE TO NONCOMBUSTIBLES 18" CLEARANCE TO COMBUSTIBLES ½" HANGER ROD PER MANUFACTURER'S RECOMMENDATIONS CX# 6"∅ FLASH PER ROOFING MANUFACTURER'S RECOMMENDATIONS. REFER TO ARCH. DRAWINGS FOR ROOF CONSTRUCTION. WALL CAP PAINT PER ARCHITECT SEE ARCHITECTURAL DRAWINGS FOR WALL TYPE INTEGRAL GRILLE HORIZONTAL DISCHARGE FAN SEE ARCHITECTURAL CEILING TYPE 2. 3. VIBRATIONALLY ISOLATE ALL EQUIPMENT AND PIPING FROM THE BUILDING STRUCTURE. COORDINATE TO ASSURE THAT AS QUIET AN OPERATING SYSTEM AS POSSIBLE IS INSTALLED. NONCOMBUSTIBLE WALL STRUCTURE WITH CLEANABLE, NONABSORBENT SURFACE EXTENDING 18" MIN. IN ALL DIRECTIONS FROM HOOD 4. VERIFY THAT DIFFUSERS, REGISTERS, GRILLES, DUCTWORK AND ALL EQUIPMENT SPECIFIED IS CORRECT FOR FIELD INSTALLATION BEFORE ORDERING OR FABRICATING. PROVIDE A WRITTEN REQUEST FOR INFORMATION TO THE ENGINEER FOR A RULING ON HOW TO PROCEED IF CONDITIONS EXIST THAT WILL NOT ALLOW FOR THE INSTALLATION OF THE EQUIPMENT SPECIFIED. 5. PROVIDE ALL DUCTWORK CONNECTIONS AND TRANSITIONS AT GRILLES, DIFFUSERS, REGISTERS, FILTERS, COILS, AND OTHER LOCATIONS WHERE REQUIRED. CONSTRUCT ALL TRANSITIONS AND CONNECTIONS ACCORDING TO SMACNA STANDARDS. 6. PROVIDE AND INSTALL DAMPERS IN THE BRANCH DUCTS, NEAR THE MAIN, SERVING DIFFUSERS AND GRILLES TO ALLOW PLUS OR MINUS 10% OF THE CFM REQUIRED FROM EACH DIFFUSER AND REGISTER AS LISTED ON THE PLANS. 7. TESTING AND BALANCING AGENCY: PROVIDE AND INSTALL SHEAVES AND ALL EQUIPMENT NECESSARY TO PROVIDE PLUS OR MINUS 10% OF THE CFM REQUIRED FROM EACH DIFFUSER AND REGISTER. 8. PROVIDE AND INSTALL ALL MECHANICAL EQUIPMENT, TRANSFORMERS, RELAYS, AND OTHER ELEMENTS NECESSARY FOR A COMPLETE OPERATING SYSTEM. COMPLETE ALL 24 VOLT CONTROL WIRING AND EQUIPMENT TO THE ABOVE. ALL LINE VOLTAGE WIRING TO THE ABOVE SHALL BE COMPLETED BY THE ELECTRICAL CONTRACTOR. REFER TO COORDINATION SCHEDULE ON ELECTRICAL DRAWINGS. EXISTING HOOD 3" STAINLESS STEEL BACK PLATE. CEILING EXHAUSTER DETAIL SCALE: NTS D3 KITCHEN EXHAUST DETAIL SCALE: NTS M066 R3 R2 ECONOMIZER SIMILAR M101 NOTE: ALL NOTES ARE TYPICAL FOR ALL UNITS HAIL GUARD GAS CONNECTION PROVIDE GAS VALVE, DRIP LEG AND UNION PRIOR TO CONNECTION. RELIEF AIR 9. TRAP CONDENSATE PER MANUFACTURER'S RECOMMENDATIONS. PIPE TO NEAREST ROOF DRAIN RETURN LAYOUT AND INSTALL COMPLETE AND FUNCTIONAL MECHANICAL SYSTEMS, INCLUDING TEMPORARY CUTOFF OF EXISTING UTILITIES. PERFORM ALL CUTTING, PATCHING, AND REPAIR ASSOCIATED WITH INSTALLING THE SYSTEMS. 16 GAUGE WELDED DUCT IN 3M FIRE BARRIER GREASE & AIR DUCT WRAP 4'-0" ABOVE COOKING SURFACE MAXIMUM SEE MANUFACTURER FOR RECOMMENDED HEIGHTS D2 PROVIDE AND INSTALL ALL MATERIAL AND EQUIPMENT AS REQUIRED BY UPC, UMC, NFPA, LIFE SAFETY CODE, GAS CODE, AND ALL OTHER LOCAL CODES AND ORDINANCES THAT APPLY. WHERE THERE IS A DISCREPANCY BETWEEN THE CODES OR ORDINANCES AND THE DRAWINGS, THE MORE STRINGENT APPLICATION SHALL APPLY. R1 INSULATED ROOF CURB TO MATCH ROOF SLOPE ALTER DIMENSIONS OF THE DUCTWORK IN THE CEILING SPACE FROM SIZES INDICATED ON THE DRAWINGS AT SPECIFIC LOCATIONS WHEN NECESSARY TO FIT THE DUCTWORK IN THE SPACE PROVIDED. REROUTE DUCTWORK IN CEILING SPACE TO AVOID OTHER MECHANICAL EQUIPMENT, LIGHT FIXTURES, ETC. MAINTAIN THE SAME FREE AREA AND SUBMIT PROPOSED CHANGES TO THE ENGINEER FOR APPROVAL. BE RESPONSIBLE FOR VERIFYING SPACE LIMITATIONS BEFORE DUCTWORK FABRICATION AND MAKE CHANGES ACCORDINGLY. PROVIDE ALL NECESSARY TRANSITIONS. 10. COORDINATE ALL PROPOSED ROOF PENETRATIONS WITH EXISTING WARRANTEE HOLDER AND RELOCATE IF NECESSARY. SUPPLY 11. PROVIDE ONE UNION AT ALL VALVES OR SUITABLE MEANS OF REMOVAL WITHOUT PIPE CUTTING ON SCREWED PIPING. UNIONS REQUIRED ON COPPER PIPING AT EQUIPMENT CONNECTION. LAY-IN CEILING T.O. > 111'-4" RETURN 24"x24" TYPE "B" RETURN GRILLE MECHANICAL SCHEDULE # R(e) EXISTING ROOFTOP UNIT: SHOWN FOR REFERENCE. "CARRIER" MODEL 48TCEA04A2A3A0A0A0 SERIAL#0910G40130 UNIT CFM R(e) 1200 HTG COOL MBH TONS IN 3.0 115 OSA CFM 0 MCA 29.1 SUPPLY RETURN MOCP (W"xH") (W"xH") SEER MANUF. DATE 45.0 17"x12" 11"x26" 13 2010 R1R3 ROOFTOP UNIT: 13 SEER, GAS-FIRED, ELECTRIC R-410A REFRIGERATION, DOWN DISCHARGE PACKAGED ROOFTOP UNIT. FILTERS: ASHRAE 25% DISPOSABLE. COMPRESSORS: DIRECT DRIVE, HERMETIC RECIPROCATING WITH CRANKCASE HEATER, TEMPERATURE AND CURRENT OVERLOAD PROTECTION AND SPRING ISOLATION. EVAPORATOR COILS: INTERNALLY FINNED COPPER TUBES BONDED TO ALUMINUM PLATE. OUTDOOR FANS: DIRECT DRIVE, PERMANENTLY LUBRICATED. INDOOR FAN: BELT DRIVE. NATURAL GAS HEATING SECTION: DRUM AND TUBE TYPE WITH FORCED COMBUSTION. INTERNAL SPRING ISOLATORS. DISCONNECT SWITCH. POWERED CONVENIENCE OUTELT, HIGH ALTITUDE KIT FOR 6000 FEET ABOVE SEA LEVEL. ACCESSORIES: HINGED ACCESS PANELS, DB ECONOMIZER, CO2 SENSOR &CONTROL, 100% BAROMETRIC RELIEF, ROOF CURB TO MATCH ROOF SLOPE, HAIL GUARD, PROGRAMMABLE THERMOSTAT. AMBIENT CONDITIONS = 89°F/59°F. ENTERING AIR = 80°F/60°F. HEATING MBH = INPUT. ELEC.=240V/1∅. "CARRIER" MODELS LISTED HEAT WT. COOL MBH OSA SUPPLY RETURN LBS. MCA MOCP (W"xH") (W"xH") UNIT CFM ESP MBH INPUT CFM MODEL R1 1434 0.50" 33.2 90 78 48KCF04 730 30 45 18"x12" 26"x11" 120 624 48KCF06E 836 41 60 18"x12" 26"x11" R2 2000 0.75" 50.0 48KCF06E 836 41 18"x12" 26"x11" R3 2000 0.75" 50.0 120 624 60 A CEILING DIFFUSER: 4-WAY ADJUSTABLE VERTICAL/HORIZONTAL THROW STEEL 24"x24" FACE UNLESS OTHERWISE INDICATED ON PLAN, SEE PLAN FOR NECK SIZE, CFM AND CEILING TYPE. NC < 30. "KRUEGER" MODEL 1450 A CEILING RETURN GRILLE: EGG-CRATE STYLE, 24"x24" FACE UNLESS OTHERWISE INDICATED ON PLAN. SEE PLAN FOR NECK SIZE, CFM AND CEILING TYPE. PROVIDE OBD WHEN GRILLE IS USED FOR EXHAUST. NC<30. "KRUEGER" MODEL EGC-5 B C SIDEWALL SUPPLY GRILLE: STEEL FRAME, HORIZONTAL DEFLECTION VANES WITH OBD, SEE PLAN FOR SIZE AND CFM. FIELD PAINT PER ARCHITECT. NC < 30. "KRUEGER" MODEL 880-H CX1CX2 CEILING EXHAUSTER: DIRECT DRIVE CEILING MOUNTED EXHAUSTER WITH BACKDRAFT DAMPER, VIBRATION ISOLATOR KIT, INTEGRAL GRILLE, OCCUPANCY SENSOR AND BIRDSCREEN. 120 V/1∅ "COOK" ESP ("WC) WATTS ACCESSORIES CONTROLLED BY UNIT MODEL CFM CX1 GC320 150 0.25" 53 WALL CAP OCCUPANCY SENSOR CX2 GC320 150 0.25" 53 WALL CAP OCCUPANCY SENSOR EF1EF3 EXISTING ROOF MOUNTED EXHAUSTER: SHOWN FOR REFERENCE UNIT EF1 EF2 EF3 MODEL GREENHECK GREENHECK FANTECH MODEL CUBE140-7C CUE100C 5DDD10AA SERIAL# 91E02036 91E02037 NA ELEC. 115V/1∅ 115V/1∅ 115V/1∅ AMPS NA NA 2.3 CONTROLLED BY WALL SWITCH WALL SWITCH WALL SWITCH 12. INSTALL SMOKE DETECTORS AND EQUIPMENT REQUIRED BY THE NFPA IN THE SUPPLY AND RETURN DUCT MAINS OF THE AIR HANDLING EQUIPMENT. SMOKE DETECTORS ARE PROVIDED BY THE ELECTRICAL CONTRACTOR. SUPPLY 13. PROVIDE TURNING VANES IN ALL RECTANGULAR DUCTWORK AT ELBOWS AND TEES WHETHER SHOWN ON THE PLANS OR NOT. THE ONLY EXCEPTION IS RETURN AIR TRANSFER DUCTS BETWEEN ROOMS. C2 ROOFTOP UNIT DETAIL 14. FIELD VERIFY THAT ALL NEW DUCTWORK CAN FIT WITHIN THE SPACE PROVIDED PRIOR TO FABRICATING ANY NEW DUCTWORK. EXISTING DUCTWORK SHOWN IS FROM ORIGINAL AS-BUILT DRAWINGS AND NOT ALL CONFIGURATIONS HAVE BEEN VERIFIED. SCALE: NTS HANGER ROD SIZE: TYPE "B" ¼" TYPE "C" ¼" TYPE "D" 3/8" SECURE TO STRUCTURE ABOVE AS RECOMMENDED BY SMACNA. 1"x16 GA. GALV. METAL STRAP DOUBLE-NUT & WASHER @ END OF ROD SHEET METAL SCREW RIVET OR BOLT TO BOTH SIDES OF DUCT. MAX. SIDE MAX. SIDE FOR BRACING ANGLES - SEE NOTES DUCT SCHEDULE DUCT DIMENSIONS TYPE INCHES HANGER UP THRU 14 20 32 44 56 62 86 OVER 12 18 30 42 54 60 84 96 96 15. ALL PLENUM INSTALLED MATERIALS MUST BE PLENUM RATED OR WRAPPED IN A LISTED SYSTEM TO ACHIEVE A VALUE LOWER THAN 25 FLAME SPREAD AND 50 SMOKE DEVELOPMENT RATING. A A A/B B B B C C D TYPE "A" 8 FT. MAX. HANGER SPACING ALSO PROVIDE 3 HANGERS AT EACH TAKE-OFF OR BRANCH TYPE "B", "C" & "D" 8 FT. MAX. HANGER SPACING. NOTES: 1. FOR SEVERAL DUCTS ON ONE HANGER TYPE "B"-"C" OR "D" MAY BE USED. SIZE OF HANGER WILL BE SELECTED ON THE SUM OF DUCT WIDTHS EQUAL TO MAX. WIDTH OF DUCT SCHEDULE. 2. SCHEDULE FOR ANGLES FOR BRACING: TYPE "B" 1½"x1½"x1/8" ANGLE MAX. SPACING 8'-0" CENTERS; TYPE "C" 1½"x1½"x3/16" ANGLE MAX. SPACING 8'-0" CENTERS; TYPE "D" 2"x2"x¼" MAX. SPACING 4'-0" CENTERS. B2 DUCT HANGER DETAIL SCALE: NTS M088 MECHANICAL SYMBOLS LEGEND INSULATE ALL BRANCH DUCT AND COVER CONNECTIONS WITH DUCT WRAP. 1"x18 GAGE SHEETMETAL SUPPORT STRAP. ATTACH TO STRUCTURE ABOVE. 10' O.C. MINIMUM HANGER STRAPS NO POP RIVETS ALLOWED. VOLUME DAMPER #10 x 3/4" SELF TAPPING CADIUM PLATED SCREWS TO ANCHOR STRAPS TO DUCT. (TYPICAL) V/D INSULATED FLEX DUCT SHEETMETAL SCREWS. NO SAGS OR SHARP TURNS MAX RUN LIMITED TO 4 FEET STRETCH DUCT RUN FOR SMOOTH INTERIOR. A6 100CFM CEILING DIFFUSER DESIGNATION = TYPE "A" WITH A 6" DIAMETER NECK AT CFM SHOWN UNION B1 CEILING RETURN GRILLE DESIGNATION = TYPE "B" AT 1'X1' GAS COCK B2 CEILING RETURN GRILLE DESIGNATION = TYPE "B" AT 2'X2' THERMOMETER C16"x16" 100CFM SIDEWALL DIFFUSER DESIGNATION = TYPE "C" WITH A 16"x16" FACE AT CFM SHOWN CHECK VALVE UNIT DESIGNATION 1 23.01 USE ADJUSTABLE ROUND SHEETMETAL DUCT ELBOW WHERE AN IMMEDIATE TURN FROM DIFFUSER. DIFFUSER WATER HAMMER ARRESTER GATE VALVE OS&Y PLUG, CIRCUIT SETTER OR GAUGE COCK ROUND RIGID DUCT. SEE PLANS FOR SIZES FACTORY FABRICATED ROUND TO RECTANGULAR OR SQUARE ADAPTER. SEE DIFFUSER SCHEDULE. 2-WAY VALVE RETURN GRILLE 3-WAY VALVE BACKFLOW PREVENTER RELIEF VALVE FLEX DUCT SIDEWALL SUPPLY BUTTERFLY VALVE BALL VALVE MOTORIZED, FIRE, FIRE/SMOKE VOLUME DAMPER T TYPICAL DIFFUSER CONNECTION DETAIL R CO 2 SCALE: NTS M092 H THERMOSTAT, REMOTE SENSOR OR HUMIDISTAT CARBON DIOXIDE SENSOR NOTE: SYMBOLS ILLUSTRATED ABOVE MAY NOT APPEAR ON THE PLANS RODAHL & HUMMELL ARCHITECTURE, P.C. REDUCED PRESSURE BACKFLOW PREVENTER SUPPLY DIFFUSER SIDEWALL RETURN A2 PRV KEYED NOTE DESIGNATION PRESSURE GAUGE STAINLESS STEEL ADJUSTABLE ADJUSTABLE DUCT BAND. (TYPICAL) 03/31/2016 SOLENOID 10"x10" CLEAR INSIDE DUCT DIMENSION (NEW) ARCHITECTURE LOWER VALLEY SENIOR CENTER GLOBE VALVE FRUITLAND, NM STRAINER STRAINER WITH DRAIN VALVE 609 North Dustin Farmington, NM 87401 Phone: (505) 326-6442 MECHANICAL SCHEDULE, DETAILS & NOTES Drawn: Author Checked: Checker Date: 2016-04-04 Filename: Project: 1538 Sheet: M601 Of: KEYED NOTES (E)SS 22.01 REMOVE (E)PLUMBING FIXTURE. SEE NEW WORK PLAN FOR REPLACEMENT. 22.02 REMOVE (E)PLUMBING FIXTURE. CAP WATER, WASTE AND VENT BEHIND FINISHED SURFACE. 22.03 REMOVE/RELOCATE (E)HAND SINK. SEE NEW WORK PLAN. 22.04 REMOVE/RELOCATE (E)2-COMPARTMENT SINK AND GREASE TRAP. SEE NEW WORK PLAN. 22.06 3/4"CW, 3/4"HW DROP TO PREP SINK. OFFSET 1/2"CW., 1/2"HW TO HAND SINK. 22.09 3"W DOWN, 2"V RISE FROM FLOOR SINK. 22.10 1-1/2"W DOWN, 1-1/2"V RISE FROM LAVATORY/RELOCATED HAND SINK. 22.11 CONNECT NEW PLUMBING FIXTURE TO (E)ROUGH-IN. 22.12 3"SS DOWN, 2"V RISE AND 3/4"CW ROUGH-IN FOR NEW WATER CLOSET. 22.15 REMOVE (E)CW, HW AND GAS DROPS TO ABOVE CEILING. SEE NEW WORK PLAN FOR NEW CONNECTION. 22.16 REMOVE (E)IW AND GAS PIPING. 22.17 REMOVE (E)UNDERGROUND GAS PIPING BELOW FOOTPRINT OF NEW ADDITION. 22.18 REMOVE (E)GAS RISER AND ALL PIPING ON ROOF. SEE PLAN BELOW FOR REPLACEMENT. 22.19 (E)FLOOR DRAIN TO REMAIN. SEE NEW WORK PLAN FOR REFURBISHMENT. 22.20 REMOVE (E)1" ABANDONED GAS SERVICE LINE ENTIRELY. COORDINATE WALL PATCH WITH GENERAL CONTRACTOR. 22.21 DISCONNECT/REMOVE GAS FROM (E)(R) KITCHEN EQUIPMENT. SEE NEW WORK PLAN NEW CONNECTION. 22.22 REMOVE (E)HOSE BIBB. REMOVE AND CAP CW INSIDE EXTERIOR WALL OR AS INDICATED.. 22.23 REMOVE GAS SUPPLY AND PIPING TO UNIT HEATER COMPLETELY. 22.24 MAKE NEW 2"G CONNECTION TO (E)2"G ON ROOF AND EXTEND AS INDICATED. 22.26 MAKE NEW 2"G CONNECTION TO UNDERGROUND GAS LINE AND EXTEND TO NEW RISER LOCATION. 22.27 PROVIDE AND SECURE NEW STRAINER TO EXISTING FLOOR DRAIN/SINK FLUSH WITH FINISHED FLOOR AND INSTALL NEW TRAP GUARD. COORDINATE FLOOR PATCH WITH GENERAL CONTRACTOR. FIELD VERIFY EXACT REQUIREMENTS. 22.28 REMOVE WASHER/DRYER ROUGH-INS. CAP LINES ABOVE CEILING OR BEHIND FINISHED SURFACE. COORDINATE PATCHWORK WITH GENERAL CONTRACTOR. 22.29 1-1/2"G DROP IN WALL. MAKE 1-1/4"G CONNECTION TO GAS RANGE AND 3/4"G CONNECTION TO COMBI-OVEN. SEE GAS CONNECTION DETAIL. 22.30 NEW 1-1/2"CW CONNECTION TO (E)1-1/2"CW ABOVE CEILING. 22.31 1-1/2"CW DROP TO NEW WATER ENTRY WITH BFP WALL MOUNTED AT 24" ABOVE FINISHED FLOOR. FIELD VERIFY EXACT CONDITIONS. SEE DETAIL. 22.32 1"G DOWN THROUGH ROOF. MAKE NEW GAS ONNECTION TO WATER HEATER. SEE GAS CONNECTION DETAIL. 22.33 INSTALL NEW CHECK VALVE AND EXPANSION TANK (XT) ON 1"CW TO WATER HEATER. FIELD VERIFY EXACT CONDITIONS. 22.37 EXTEND 1"G AND MAKE NEW CONNECTION TO ROOFTOP UNIT. SEE GAS CONNECTION DETAIL. FIELD VERIFY EXACT CONDITIONS. 22.38 NEW GAS PIPE ON ROOF. SUPPORT WITH 5" HIGH B-LINE DURA-BLOK DB10 OR EQUAL AT 8' CENTERS MAXIMUM. 22.39 DISCONNECT BRANCH PIPING AND REMOVE CW MAIN LINE. SEE PLAN BELOW FOR REPLACEMENT. 22.41 RECONNECT (E)BRANCH CW PIPING TO NEW CW MAIN LINE. FIELD VERIFY EXACT CONDITIONS. 22.42 REINSTALL EXISTING ELECTRIC WATER COOLER OVER (E)ROUGH-IN. 22.43 3/4"CW, 3/4"HW DROP, 2"W DOWN AND 2"V RISE FROM WASHER BOX (WB). SEE DETAIL. 22.44 NEW 3/4"CW, 3/4"HW CONNECTION TO NEW/EXISTING LINES. 22.45 OFFSET 1"G TO SLOPED ROOF. FIELD VERIFY EXACT REQUIREMENTS. 22.46 EXTEND 3/4"CW TO HOSE BIBB MOUNTED AT 24"ABOVE GRADE. 22.47 NEW 3"SS CONNECTION TO (E)4"SS. FIELD VERIFY EXACT CONDITIONS. 22.48 LOCATE NEAREST 2' OR LARGER VENT THROUGH ROOF AND MAKE NEW 2"V CONNECTION. 22.49 NEW TWO-WAY CLEANOUT TO GRADE. SEE DETAIL. 22.50 REMOVE EXISTING HOSE BIBB AND CW SUPPLY. CAP LINE AT MAIN. (E)SS 22.02 22.01 Stair 2 STORAGE 110 MEN 106 22.01 22.23 WOMEN 105 22.01 22.01 22.01 OFFICE 111 DINING ROOM 107 22.01 22.23 STORAGE 112 OFFICE 108 22.28 22.23 WCO 22.18 22.50 22.39 (E)G 22.39 (E)4"SS (E)4"SS KITCHEN 104 OFFICE 113 22.21 22.22 COMPUTER 101 22.19 (E)G 22.03 22.17 22.17 (E)G GAME ROOM 100 22.18 22.18 22.16 22.15 (E)G 22.17 VEST 103 22.04 COOLER/ FREEZER 115 1 22.20 (E)G 22.39 R.R. 102 PLUMBING DEMOLITION PLAN 1/8" = 1'-0" (E)SS (E)SS ENTRY 109 22.32 22.12 FPHB 22.47 22.11 2"G U L TMV (E)EWC DINING ROOM 107 2"V FCO 22.11 (R) H.SK. XT 22.09 FS 22.31 BFP PRV WB VEST 103 22.10 22.42 FS BV 22.43 2"V MEN 106 22.44 L TMV 22.38 22.48 2"G 22.11 OFFICE 111 WOMEN 105 22.27 1-1/2"G 22.27 WC 3/4"CW WC 22.33 1-1/2"G 3/4"CW 3/4"HW WC 3/4"HW STORAGE 110 2"G 2"G 22.09 22.24 FPHB 22.37 22.37 L TMV 2"VTR COOLER/ FREEZER 115 1"G 1"G 1"G 22.06 R.R. 102 WC 22.37 22.30 22.45 22.38 22.46 FPHB 22.32 BV 1-1/4"G DCO (E)4"SS (E4")SS OFFICE 113 4"SS 22.49 KITCHEN 104 (E)4"SS COMPUTER 101 1"G 22.37 22.38 22.38 2"G GAME ROOM 100 RODAHL & HUMMELL ARCHITECTURE, P.C. 1/4" = 1'-0" 22.26 ARCHITECTURE 2"G 22.29 (E)2 1-1/2"G COOLER/ FREEZER 115 4"SS PLUMBING FLOOR PLAN 1/8" = 1'-0" 03/31/2016 2"G VEST 103 GCO GCO 3 ENLARGED PLUMBING PLAN 22.38 22.44 4" SS FOR CONTINUATION SEE 1/8"PLAN 1-1/2"G 22.27 2 FOR CONTINUATION SEE 1/8"PLAN 22.45 WAREWASH 114 22.12 1"G 22.41 22.10 3"SS OFFICE 108 3"SS STORAGE 112 3 P101 R.R. 102 "G 609 North Dustin Farmington, NM 87401 Phone: (505) 326-6442 LOWER VALLEY SENIOR CENTER FRUITLAND, NM 4"SS GCO PLUMBING FLOOR PLANS Drawn: Author Checked: Checker Date: 2016-04-04 Filename: Project: 1538 Sheet: P101 Of: PLUMBING SYMBOLS LEGEND 1-12/" CW TO BUILDING SYMBOL DESCRIPTION SCHEDULE WC FLUSH TANK WATER CLOSET: A.D.A COMPLIANT, 1.28 GPF FLOOR MOUNTED VITREOUS CHINA, SIPHON JET FLUSHING, ELONGATED FRONT TOILET, EVERCLEAN SURFACE. COMPLETE WITH OPEN FRONT SEAT LESS COVER AND BOLT CAPS. FLUSH LEVER OPPOSITE SIDEWALL. "AMERICAN STANDARD" CADET MODEL 3339.128. WASTE = 3", VENT = 2", CW = 3/4" U URINAL: A.D.A. COMPLIANT, VITREOUS CHINA W/ WASHOUT ACTION, 3/4" TOP SPUD INLET 2 IN. OUTLET, ADJUSTABLE FLOOR SUPPORTED WALL CARRIER, "AMERICAN STANDARD" 6045.013.002 1.0 PINT MANUAL FLUSH VALVE. "AMERICAN STANDARD" WASHBROOK MODEL 6590.125 WASTE = 2 IN., VENT = 1-1/2 IN., CW = 1 IN. L LAVATORY: A.D.A. COMPLIANT, COUNTERTOP, VITREOUS CHINA,, 4" FAUCET CENTERS, CHROME PLATED GRID DRAIN, OFFSET TAILPIECE "TRUE-BRO" LAV GUARD "AMERICAN STANDARD" 7385.003 SINGLE LEVER CHROME PLATED FAUCET LESS POP-UP DRAIN, 1.5 GPM AERATOR. "AMERICAN STANDARD" AQUALYN 0476.028 WASTE = 2 IN., VENT = 1 - 1/2 IN., CW = 1/2 IN. HW = 1/2" UNIT DESIGNATION KEYED NOTE PRESSURE REDUCING VALVE (SET @ 50PSI) W/ INTEGRAL STRAINER 1-1/2" POINT OF CONNECTION PRESSURE GAUGE, TYP VENT COLD WATER (CW) HOT WATER SUPPLY (140°F) (HW) HOT WATER RETURN (HWR) GAS (6.5"w.c.) G TO MOP SINK EWC1 SANITARY WASTE (ABOVE FLOOR) BACKFLOW PREVENTER (BFP) C1 SS SANITARY WASTE (SS) (BELOW FLOOR) GAS COCK WATER ENTRY ASSEMBLY BALL VALVE BFP1 BACKFLOW PREVENTER: SEE PLAN FOR SIZE, LEAD FREE, BRONZE BODY WITH STAINLESS STEEL SPRINGS, REDUCED PRESSURE BACKFLOW PREVENTER COMPLETE WITH TWO "Y" PATTERN CHECK VALVES AND ONE HYDRAULICALLY DEPENDENT DIFFERENTIAL RELIEF VALVE. PROVIDE BALL SHUT OFF VALVES AND DRAIN KIT. ASSE STANDARD 1013. "FEBCO" MODEL LF825Y STRAINER CO INTERIOR FLOOR CLEAN OUT: CAST IRON CLEAN OUT WITH THREADED ADJUSTABLE HOUSING, SV HUB OUTLET, FLANGED FERRULE WITH PLUG AND ROUND SCORIATED POLISHED BRONZE SECURED TOP. "ZURN" MODEL ZB-1400- (VERIFY SURFACE TYPE) FD FLOOR DRAIN: CAST IRON FLOOR DRAIN WITH TRAP GUARD, VANDAL PROOF SECURED TOP, NICKEL BRONZE STRAINER. EXTENSION ADAPTER MAY BE REQUIRED, CONTRACTOR TO VERIFY AND INCLUDE IF NECESSARY. "ZURN" MODEL Z-415 W/ TYPE B STRAINER WASTE = 2 IN., VENT = 2 IN. CHECK VALVE SCALE: N.T.S. RELIEF VALVE TERMINATE WITH VENT CAP (VC) UNION WATER HAMMER ARRESTER SOLENOID RUBBER BOOT PRV 12" MIN. SEAL WATERTIGHT BACKFLOW PREVENTER ROOFING OVER BASE VENT THRU ROOF FPHB HOSE BIBB: FREEZELESS, AUTOMATIC DRAINING, WALL HYDRANT: BRASS WITH POLISHED CHROME PLEATED CASTING, KEY OPERATED, AND CHROME PLATE VACUUM BREAKER, 3/4" FPT, MIN. 16" LENGTH "WOODFORD" MODEL 67-3/4 IN DOUBLE CLEAN OUT PRV FLOOR SINK SEE ARCH. DWG's FOR ROOF CONST. 8" MIN. DCO CO CONTINUOUS RUBBER BOOT INCREASE TO NEXT LARGER PIPE SIZE (EXCEPT 4") VENT, REQUIRED SIZE B1 CLEAN OUT SCALE: N.T.S. P40 PRESSURE REDUCING VALVE: LEAD FREE BRONZE BODY, 300 PSI INLET RATING, SET TO 60PSI OUTLET PRESSURE, ASSE 1003 CERTIFIED, NSF CERTIFIED. "WATTS" SERIES LFX65B TMV THERMOSTATIC MIXING VALVE: 1/ "-1" (SEE PLAN FOR SIZE)ASSE 1070 AND 1017, 2 POINT-OF-USE MIXING VALVE. SET AT 105°F. COLD WATER 50°F.; HOT WATER 140°F.; MODEL MVB XT "APOLLO" EXPANSION TANK: POTABLE WATER USE, 175 MAX. WORKING PRESSURE, 2.0 M METER (E) (EXISTING) IW INDIRECT WASTE GC GENERAL CONTRACTOR GALLONS TOTAL VOLUME, 40 PSIG FACTORY PRECHARGE. "AMTROL" MODEL ST-5C PC PLUMBING CONTRACTOR TYP TYPICAL VENT THRU ROOF DETAIL ELECTRIC WATER COOLER: A.D.A. COMPLIANT WATER COOLER WITH STRAINER, ANGLE STOPS, TRAPS, FRONT PUSH-BAR AND WALL HANGERS. 8.0GPH, GRAY GRANITE VINYL CLAD STEEL ELEC = 120V/1PH/3.2 FLA "ELKAY" MODEL LZSG8 WASTE = 2", VENT = 1-1/2" CW = 1/2" WB WASHER BOX: WHITE POWDER COATED METAL WASHER BOX WITH QUARTER TURN VALVES AND WATTER HAMMER ARRESTORS "GUY GRAY" MODEL 82158 WASTE = 2 IN.; VENT = 2 IN.; CW = 3/4 IN.; HW = 3/4 IN. WCO WALL CLEANOUT: BRASS PLUG WITH ROUND STAINLESS STEEL SECURED ACCESS COVER, SEE PLAN FOR SIZE. "ZURN" MODEL Z-1468 NOTE: SYMBOLS ILLUSTRATED ABOVE MAY NOT APPEAR ON THE PLANS PLUMBING GENERAL NOTES CLEANOUT TEE (E)(R) 2-COMPARTMENT PREP SINK 1. COMPLETE ALL WORK IN FULL COMPLIANCE WITH THE UMC, UPC,IBC, LIFE SAFETY CODE, N.F.P.A. AND ALL LOCAL CODES AND ORDINANCES. 2. CAREFULLY LAYOUT AND INSTALL THE PLUMBING SYSTEMS INCLUDING ALL COORDINATION WITH MECHANICAL EQUIPMENT, DUCTWORK, ELECTRICAL EQUIPMENT AND ANY OTHER EQUIPMENT THAT MAY REQUIRE COORDINATION EFFORTS. COORDINATE TEMPORARY CUT-OFF OF WATER AND SEWER WITH UTILITY PROVIDERS. PERFORM ALL NECESSARY TRENCHING, BACK FILLING, CUTTING, PATCHING, REPAIRING, ETC. ASSOCIATED WITH THE INSTALLATION OF THE PLUMBING SYSTEM SHOWN ON THE PLANS AND DESCRIBED IN THE SPECIFICATIONS. 3. VERIFY ALL INVERTS BEFORE ROUTING ANY AND ALL PIPING. NO COMPENSATION WILL BE MADE FOR THE CONTRACTOR'S FAILURE TO COORDINATE WORK WITH SITE CONDITIONS. BECOME TOTALLY FAMILIAR WITH ALL ASPECTS OF THE WORK AND ALL CONSTRAINTS AND LIMITATIONS OF THE WORK REQUIRED. 4. ROUTE PIPING AS NEARLY AS POSSIBLE TO THE ROUTING INDICATED ON THE PLANS, BUT MAKE MINOR CHANGES IN ROUTING TO ACCOMMODATE THE CONDITIONS AT THE SITE. DO NOT UNDERTAKE MAJOR REROUTING OF PIPING WITHOUT WRITTEN APPROVAL FROM ENGINEER. MAKE ALL REQUIRED TRANSITIONS, OFFSETS, MINOR RE-LOCATIONS, AND ALL ASSOCIATED FITTINGS, PIPING, AND EQUIPMENT TO INSTALL A COMPLETE AND OPERATIONAL SYSTEM. 5. THE PROXIMITY OF WATER AND SEWER LINES SHALL BE AS FOLLOWS, UNLESS WRITTEN APPROVAL FROM THE STATE HEALTH DEPARTMENT SPECIFIES DIFFERENT CONDITIONS: WHENEVER POSSIBLE, IT IS DESIRABLE TO LAY PARALLEL WATER AND SEWER LINES AT LEAST TEN FEET APART HORIZONTALLY, AND THE WATER LINE SHOULD BE AT A HIGHER ELEVATION THAN THE SEWER LINE. IF THIS IS NOT POSSIBLE, SEPARATE TRENCHES WILL BE REQUIRED IN ALL CASES (THIS SHALL BE EFFECTIVE EVEN THOUGH ONE LINE HAS BEEN INSTALLED PRIOR TO THE OTHER), AND THE WATER LINE SHALL BE AT LEAST ONE FOOT ABOVE THE SEWER LINE. WHERE LINES INTERSECT THE WATER LINE SHALL BE SLEEVED FOR TEN FEET ON EACH SIDE OF THE INTERSECTION. 6. ALL CONTRACTORS BIDDING ON THIS PROJECT ARE CAUTIONED TO VISIT THE SITE AND MAKE ALL NECESSARY INQUIRIES TO DETERMINE THE EXISTING CONDITIONS PRIOR TO SUBMITTING THEIR BIDS. NO SUBSEQUENT ALLOWANCE WILL BE MADE TO COMPENSATE FOR LACK OF PRE-BID INSPECTIONS BY THE SUCCESSFUL CONTRACTOR. ANY LINES ENCOUNTERED WHICH MAY INTERFERE WITH NEW CONSTRUCTION SHALL BE RELOCATED IF ACTIVE AND ABANDONED IF INACTIVE BY THIS CONTRACTOR UNDER THIS CONTRACT BY FIRST CONTACTING THE ARCHITECT FOR A RULING AS TO THEIR REMOVAL, RELOCATION, ETC. 7. PROVIDE ACCESS PANELS TO ALL INACCESSIBLE PLUMBING EQUIPMENT. 8. INSULATE ALL NEWLY INSTALLED PIPING (DOMESTIC HOT, COLD, AND RECIRC. WATER) IN THE BUILDING. LABEL PIPE WITH FLUID TYPE AND FLOW DIRECTION. 9. PROVIDE WALL CLEANOUTS AT ALL URINALS, SINKS AND LAVATORIES. STAINLESS STEEL ACCESS COVER W/ COUNTERSUNK SCREW TWIST HANDLE DRAIN (TYP. 3) 2"INDIRECT WASTE FINISHED WALL (E)(R) GREASE TRAP FLOOR SINK, SEE SCHEDULE B2 PREP SINK DETAIL WALL CLEANOUT DETAIL B3 SCALE: N.T.S. SCALE: N.T.S. P41 1-1/2" MIN. PROVIDE GAS PRESSURE REGULATOR (WHERE REQUIRED) VENTED TO OUTDOORS WHEN LOCATED INSIDE #3 REBAR GAS COCK #3 BRAZED TO C.I., (TYP) 3000 PSI CONCRETE 1" CHAMFER GAS CONNECTOR OR RIGID PIPE 18" MIN 24" MIN IRON FERRULE W/BRASS C. S. SCREW PLUG (TYP). MIN 6" FINISHED GRADE SOIL PIPE RISER (TYP). 11. PRESSURE TEST, FLUSH AND DISINFECT ALL DOMESTIC WATER PIPING PER CHAPTER 6 OF THE PLUMBING CODE PRIOR TO CALLING FOR FINAL INSPECTION. TWO-WAY CLEANOUT 12. TERMINATE ALL PLUMBING VENTS NOT LESS THAN 25' FROM ANY VENTILATION AIR INTAKES. COORDINATE WITH MECHANICAL CONTRACTOR AND MECHANICAL DWGS. TERMINATE WITH VENT CAP (VC). MAIN A3 GAS CONNECTION DETAIL SCALE: N.T.S. RODAHL & HUMMELL ARCHITECTURE, P.C. 10. PERFORM PRESSURE TEST OF WASTE/VENT LINE PER CODE. COMPLETE A SUCCESSFUL TEST PRIOR TO COVERING THE WORK. MIN. 6" DIRT LEG UNION 03/31/2016 C1 ARCHITECTURE 609 North Dustin Farmington, NM 87401 Phone: (505) 326-6442 LOWER VALLEY SENIOR CENTER DOUBLE CLEANOUT TO GRADE FRUITLAND, NM SCALE: N.T.S. PLUMBING SCHEDULE AND DETAILS P04 Drawn: Author Checked: Checker Date: 2016-04-04 Filename: Project: 1538 Sheet: P601 Of: ELECTRICAL SYMBOLS LEGEND FIRE ALARM SWITCHING LIGHTING RECTANGULAR FIXTURE, CEILING MOUNTED (DIMENSIONS AS SHOWN) A A A B C A A A A A-E 3. NOTIFY THE ENGINEER IN WRITING IF DISCREPANCIES BETWEEN CONTRACT DOCUMENTS AND ANY ASSOCIATED LEGAL OR SAFETY REQUIREMENTS ARE DETECTED. THE ENGINEER WILL MODIFY THE CONTRACT DOCUMENTS ACCORDINGLY. IF THE CONTRACTOR PROCEEDS W/ ANY WORK WHICH IS IN VARIANCE OF KNOWN LEGAL OR SAFETY REQUIREMENTS, THE CONTRACTOR WILL ASSUME RESPONSIBILITY FOR THIS WORK AND WILL PROMPTLY CORRECT THE WORK, WHEN NOTIFIED WITHOUT ADDITIONAL COST TO THE OWNER. 4. FIELD VERIFY EXISTING CONDITIONS PRIOR TO COMMENCING WORK. NOTIFY THE ENGINEER OF ANY DISCREPANCIES BEFORE PROCEEDING. NO CLAIM FOR ADDITIONAL COST OR TIME EXTENSION WILL BE ALLOWED WITHOUT PROPER NOTICE PLUS PRIOR DETERMINATION OF TIME AND COST TO THE OWNER. 5. CLEAN THE ENTIRE ELECTRICAL SYSTEM AFTER COMPLETION OF THE INSTALLATION. REMOVE ALL FOREIGN MATTER, PAINT, OR DIRT, GREASE, UNNEEDED LABELS OR STICKERS FROM FIXTURES AND EQUIPMENT. REMOVE ALL RUBBISH AND DEBRIS ACCUMULATED DURING INSTALLATION FOR THE PREMISES. WALL OCCUPANCY SENSOR (ARROWS INDICATE VIEW) 6. COORDINATE ALL PHASES OF THE ELECTRICAL WORK WITH THE ARCHITECT AND GENERAL CONTRACTOR. PERFORM WORK TO CAUSE AS LITTLE INCONVENIENCE AS POSSIBLE TO THE OWNER. POWER OUTLETS 7. OBTAIN, FROM SYSTEM SUPPLIERS, ALL WIRING DIAGRAMS FOR ALL EQUIPMENT, PRIOR TO ANY ROUGH-IN, TO ASSURE THAT PROPER ELECTRICAL CHARACTERISTICS ARE PROVIDED, ANY INCORRECT WIRING OR DEVICES INSTALLED BY ELECTRICAL CONTRACTOR WITHOUT THE WIRING DIAGRAM SHALL BE CORRECTED AT ELECTRICAL CONTRACTOR'S EXPENSE. 8. VERIFY ELECTRICAL DEVICE LOCATIONS WITH ARCHITECTURAL CASE WORK DETAILS PRIOR TO ANY ROUGH-IN. 9. VERIFY FINAL LOCATIONS OF ALL SINKS WITH THE PLUMBING CONTRACTOR PRIOR TO ROUGH-IN. ANY ELECTRICAL DEVICES LOCATED ABOVE COUNTER AND BEHIND FINAL SINK LOCATIONS WILL BE SHIFTED A MINIMUM OF 8'' TO EITHER SIDE OF SINK. ANY ELECTRICAL DEVICES LEFT BEHIND SINK AT TIME OF FINAL ELECTRICAL WALK THROUGH WILL BE RELOCATED AT ELECTRICAL CONTRACTOR'S EXPENSE. 10. PRIOR TO INSTALLATION, THE OWNER RESERVES THE RIGHT TO RELOCATE ANY ELECTRICAL DEVICE, UP TO A DISTANCE OF 12", WITHOUT ADDITIONAL CHARGE. 11. FIELD VERIFY AND COORDINATE THE EXACT LOCATION OF ALL SYSTEMS AND EQUIPMENT WITH ALL TRADES PRIOR TO INSTALLATION. WHERE EXACT LOCATIONS ARE NECESSARY, THEY ARE DIMENSIONED ON THESE DRAWINGS. WHERE THERE IS A QUESTION OF ADEQUATE CLEARANCE OR COORDINATION BETWEEN TRADES, THIS CONTRACTOR WILL PREPARE AS BUILT DRAWINGS FOR ENGINEERS REVIEW. 12. CONTACT UTILITY COMPANIES (POWER, GAS, WATER, SEWER, TELEPHONE, CABLE TV., ETC.) PRIOR TO TRENCHING IN ORDER TO IDENTIFY UNDERGROUND UTILITIES. CONTRACTOR SHALL LOCATE SECONDARY SERVICE FEEDERS, UNDER- GROUND ELECTRICAL BRANCH CIRCUITS, SPRINKLER LINES, ETC., PRIOR TO TRENCHING. ANY CUT DAMAGED UNDER- GROUND UTILITIES SHALL REPAIRED OR REPLACED AT CONTRACTOR'S EXPENSE. 13. UTILIZE COPPER CONDUCTORS, RATED FOR 600 VOLTS, TYPE THHN/THWN INSULATION, UNLESS OTHERWISE INDICATED. MINIMUM WIRE SIZE #12 AWG AND STRANDED FOR #8 AWG OR LARGER, RUN WIRING IN CONDUIT AND PROVIDE WIRE TYPE EQUIPMENT GROUND, UNLESS OTHERWISE NOTED (INCLUDING LOW VOLTAGE WIRING). 14. UTILIZE 1/2 INCH E.M.T. CONDUIT MINIMUM. WHERE REQUIRED TO PROTECT FROM PHYSICAL DAMAGE, USE RIGID OR IMC TYPE CONDUIT. RUN CONDUIT CONCEALED UNLESS OTHERWISE SHOWN ON THE DRAWINGS. USE FLEXIBLE METALLIC CONDUIT WHERE NEEDED. PROVIDE EXPANSION FITTINGS FOR CONDUIT CROSSING EXPANSION JOINTS. 15. SUPPORT ALL CONDUIT INDEPENDENTLY FROM THE BUILDING STRUCTURE. DO NOT SUPPORT FROM VENTILATION DUCTS, MECHANICAL PIPING, SUSPENDED CEILING GRIDS, OR THEIR HANGERS. USE ONLY ACCEPTABLE METHODS OF SUPPORT. 16. TERMINATING & SPLICING: MAKE ALL JOINTS & SPLICES IN BRANCH CIRCUIT WIRING, #10 AWG & SMALLER, W/ AN APPROVED SOLDER LESS TOOL OR TWIST ON CONNECTORS. #8 AWG AND LARGER USE HIGH COMPRESSION BARREL SPLICES WITH SHRINK WRAP AND MANUFACTURER'S COMPATIBLE CONNECTORS IN GUTTERS, AND SIMILAR LOCATIONS; BUT NOT ALLOWED IN RACEWAYS. LEAVE SUFFICIENT SLACK TO PERMIT 2 OR MORE SPLICES OR JOINTS TO BE REMADE IN CASE OF FAULT. 17. EMT CONDUIT FITTINGS: IN DRY LOCATIONS USE STEEL SET SCREW TYPE OR "REGAL" DIE CAST SET SCREW COUPLINGS AND CONNECTORS. DIE CAST FITTINGS WILL NOT BE USED ON THIS PROJECT. DAMP/ WET LOCATIONS: USE STEEL COMPRESSION GLAND TYPE COUPLER AND CONNECTIONS. 18. SURFACE RACEWAY: WHEREVER CONCEALED CONDUIT IN FINISHED AREAS IS NOT POSSIBLE, INSTALL SURFACE MOUNTED RACEWAYS EQUAL TO WIREMOLD. RUN SURFACE RACEWAYS IN CORNER OF WALL AND CEILING. ALL RACEWAYS THAT ARE EXPOSED WILL REQUIRE ARCHITECT'S/ ENGINEER'S APPROVAL PRIOR TO ROUGH-IN. COLOR BY ARCHITECT. 19. TYPE NM (ROMEX CABLE) AND NMC CABLE WILL NOT BE ALLOWED ON THIS PROJECT. ANN FA ANNUNCIATOR 20A, 3-WAY TOGGLE SWITCH FA ADA HORN/STROBE. V=VOICE/STROBE S3 S4 SK F FA CEILING MOUNTED FA HORN/STROBE SN 20A, NETWORKED SWITCH SD DIMMER SWITCH F FA ADA STROBE F DOT SYMBOL ADDITION INDICATES PENDANT MOUNTING BOX SYMBOL ADDITION INDICATES FLOOR OR IN-GROUND MOUNTING V F FA CEILING MOUNTED FA STROBE F FA FIRE ALARM PULL STATION F/S FA FIRE/SMOKE DAMPER RI FA REMOTE INDICATOR FS FA FLOW SWITCH TS FA TAMPER SWITCH 20A, 4-WAY TOGGLE SWITCH 20A, 1 POLE KEY OPERATED SWITCH PUSHBUTTON SWITCH TC TIME CLOCK SWITCH PH PHOTOSENSOR RC ROOM CONTROLLER (ABOVE CEILING) CEILING OCCUPANCY SENSOR (ARROWS INDICATE VIEW) FA GAS DETECTOR HALF FILLED SYMBOL INDICATES EMERGENCY VERSION FA SMOKE DETECTOR EXIT SIGNS (FILL INDICATES NUMBER OF FACES) WITH LIGHTS PERFORM ALL ELECTRICAL WORK IN A NEAT AND WORKMANLIKE MANNER IN FULL COMPLIANCE WITH ALL APPLICABLE, ADOPTED, CODES; INCLUDING, BUT NOT LIMITED TO THE NATIONAL ELECTRICAL CODE (NEC), UBC, IBC, NFPA, AND ADA. ALL LOCAL AND STATE REQUIREMENTS WILL BE OBSERVED DURING THE PERFORMANCE OF THIS WORK. 20A, 1 POLE TOGGLE SWITCH ARM SYMBOL ADDITION INDICATES WALL MOUNTING A-E 2. S POLE MOUNTED FIXTURE (HEADS NOT TO SCALE) A A PROVIDE, INSTALL, AND COORDINATE ALL WORK INDICATED BY THESE DRAWINGS. THIS CONSISTS OF FURNISHING ALL LABOR, EQUIPMENT, SUPPLIES AND MATERIALS IN ADDITION TO PERFORMING ALL OPERATIONS INCLUDING CUTTING, CHANNELING & UNDERGROUND TRENCHING, BACK FILL & TAMPING NECESSARY FOR THE INSTALLATION OF COMPLETE POWER, LIGHTING, OR OTHER SYSTEMS AS SHOWN. FIRE ALARM (FA) CONTROL PANEL TRACK LIGHTING (LENGTH AS SHOWN, HEADS NOT TO SCALE) A 1. FACP ROUND FIXTURE, CEILING MOUNTED (DIMENSIONS AS SHOWN) DS WITH DOUBLE ARROW FACE FA HEAT DETECTOR 20A, 120V, DUPLEX RECEPTACLE FA DUCT SMOKE DETECTOR 20A, 120V, FOURPLEX RECEPTACLE 2P-4W RECEPTACLE (SEE PANEL SCHEDULE FOR DETAILS) NOTES: 1. Lower case letters after a comma in the fixture designation indicate switching. For example, "A3, b" indicates a type A3 fixture controlled by switch b. 2. A fixture designation ending in "-E" indicates an emergency fixture, even where the fixture symbol may too small to show a half fill clearly. 3. Dimensions and mounting heights in the lighting fixture schedule supercede information implied by these symbols. Symbols are for general reference only. POWER DISTRIBUTION SURFACE MOUNTED ELECTRICAL PLUG-IN RACEWAY G 20A, 120V - GROUND FAULT PROTECTED (AT RECEPT. OR BREAKER, AS REQUIRED FOR ACCESSIBILITY) WP 20A, 120V - WEATHERPROOF IN USE COVER GROUND FAULT PROTECTED (AT RECEPT. OR BREAKER, AS REQUIRED FOR ACCESSIBILITY) 20A, 120V, DUPLEX RECEPTACLE, HALF SWITCHED DISCONNECT SWITCH COMMUNICATIONS 2P S SPECIAL RECEPTACLE 20A FRACTIONAL HORSEPOWER DISCONNECT SWITCH WITH THERMAL OVERLOAD PROTECTION. 2P = 2 POLE T DATA OUTLET DATA OUTLET, ABOVE COUNTER CEILING MOUNTED DUPLEX RECEPTACLE, 20A, 120V FLOOR MOUNTED DUPLEX RECEPTACLE, 20A, 120V MOTOR OR EXHAUST FAN SIMPLEX TYPE RECEPTACLE CONTROL STATION 20A, 120V, DUPLEX RECEPTACLE, ABOVE COUNTER ANALOG PHONE OUTLET M METER COMBINATION DATA & ANALOG PHONE OUTLET R RELAY COMBINATION DATA & ANALOG PHONE OUTLET, ABOVE COUNTER G GROUND CONNECTION ANALOG PHONE OUTLET, ABOVE COUNTER BOX INDICATES FLUSH MOUNTING IN FLOOR CIRCLE INDICATES FLUSH MOUNTING IN CEILING 3 SUBSCRIPT INDICATES QUANTITY OF PORTS (IF MORE THAN 1) 4 M M M MICROPHONE: CEILING, WALL AND FLOOR MOUNTED RESPECTIVELY S S S SPEAKER: CEILING, WALL AND FLOOR MOUNTED RESPECTIVELY J DOOR CONTROLS THERMOSTAT OUTLET BOX: SINGLE GANG BACK BOX, PLASTER RING (UNLESS OTHERWISE NOTED) 1/2''CONDUIT AND PULL CORD TO MECH UNIT T 2 J J JUNCTION BOX, CEILING, WALL AND FLOOR MOUNTED RESPECTIVELY BRANCH CIRCUIT PANEL BOARD, SEE SCHEDULE FOR MOUNTING T AO AUTOMATIC DOOR OPENER DH MAGNETIC DOOR HOLDER PS DOOR POSITION SWITCH EL ELECTRIC LOCK/STRIKE KP KEY PAD KC KEY CARD READER PAD MOUNT TRANSFORMER ABBREVIATIONS WALL MOUNTED HORN/SPEAKER T WALL MOUNT TRANSFORMER WIRELESS ACCESS POINT WAP SURGE PROTECTION DEVICE TVSS B BELL C CLOCK OUTLET, SINGLE RECEPTACLE WITH BRACKET & CLOCK C/S COMBINATION CLOCK & SPEAKER WALL MOUNTED TV TELEVISION OUTLET GROUND CONDUIT STUB-OUT LIGHTNING/SURGE ARRESTOR LA S IC INTERCOM CONTROL SWITCH S IV INTERCOM VOLUME CONTROL C1D1 RATED SEALS SECURITY SYSTEM INFRARED MOTION SENSOR SITE PLAN SECURITY SYSTEM CAMERA OR PULL CORD, WALL MOUNTED NP PULL CORD, CEILING MOUNTED NB CALL BUTTON NL INDICATOR LIGHT NC CONTROL STATION UGP UNDERGROUND ELECTRICAL PRIMARY FEEDER UGE UNDERGROUND ELECTRICAL FEEDER UGC UNDERGROUND COMMUNICATIONS OHE OVERHEAD ELECTRICAL FEEDER OHP NURSE CALL NP OVERHEAD ELECTRICAL PRIMARY FEEDER TV UNDERGROUND TELEVISION CABLE T UNDERGROUND TELEPHONE CABLE MOUNTING WALL MOUNTED F PNL CB E D H J G S C DS 48'' C B F MOUNTING HEIGHTS A 90'' TO TOP AND NOT LESS THAN 6'' BELOW FINISHED CEILING WHERE REQUIRED 80'' TO BOTTOM AND NOT GREATER THAN 96'' TO BOTTOM B TV T KEY F F TV NOT TO SCALE NOTES: 1. VERIFY ALL MOUNTING HEIGHTS WITH ARCHITECT PRIOR TO ROUGH-IN. 2. DIMENSIONS ARE TO TOP OF DEVICE WITH TRIM. ADJUST BACK BOX LOCATION AS REQUIRED. C 6'-0'' D 48'' TO TOP AFF E 20'' TO TOP AFF F 3'' G 6''AC H 5'-0'' TO HANDLE J 6'-6''MAX 3. ALL MOUNTING HEIGHTS SHALL CONFORM TO THE LATEST EDITION OF THE AMERICANS WITH DISABILITIES ACT. (ADA) LINETYPES SOLID BLACK INDICATES NEW DEVICE F GRAY INDICATES EXISTING DEVICE TO REMAIN DASHED INDICATES EXISTING DEVICE TO BE DEMOLISHED F R R R AC AFF ABOVE COUNTER ABOVE FINISHED FLOOR 20. AFG ARCH BC ABOVE FINISHED GRADE ARCHITECTURAL BELOW COUNTER FEEDER RACEWAY: IN ADDITION TO RACEWAY BONDING REQUIRED BY CODE & OUTLET BOX BONDING JUMPERS, A SEPARATE, INSULATED, GREEN EQUIPMENT GROUND CONDUCTOR. TERMINATE EACH END ON SUITABLE LUG, BUS, OR BUSHING. 21. C CONDUIT ELECTRONIC/ COMPUTER EQUIPMENT AND SPECIAL EQUIPMENT BRANCH CIRCUITS: IN ADDITION TO RACEWAY BONDING REQUIRED BY CODE AND OUTLET BOX BONDING JUMPERS, INSTALL A SEPARATE, INSULATED, GREEN EQUIPMENT GROUND CONDUCTOR WITHIN BRANCH CIRCUIT RACEWAY. TERMINATE EACH END ON SUITABLE LUG, BUS, OR BUSHING. EC ELEC EMT ELECTRICAL CONTRACTOR ELECTRICAL ELECTRICAL METALLIC TUBING 22. MAINTAIN A MINIMUM OF 24 INCH SEPARATION BETWEEN POWER CONDUITS AND SIGNAL CONDUITS. ROUTE CONDUITS SO AS NOT CROSS EACH OTHER. GC GEC GRC GENERAL CONTRACTOR GROUND ELECTRODE CONDUCTOR GALVANIZED RIGID CONDUIT 23. PROVIDE WIRING DEVICES RATED FOR THE GIVEN APPLICATION AS REQUIRED BY CODE. 24. INSTALL EXTERIOR WIRING IN CONDUIT. UTILIZE WEATHERPROOF FITTINGS AND WEATHERPROOF BOXES/ COVERS. 25. GRD GROUND SIZE ALL BOXES AND ENCLOSURES PER THE NATIONAL ELECTRICAL CODE. WORKING SPACE FOR ELECTRICAL INSTALLATION SHALL BE IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE ARTICLE 110. GFI GROUND FAULT INTERRUPTER 26. IG ISOLATED GROUND IMC INTERMEDIATE METALLIC CONDUIT LA LIGHTNING ARRESTOR MC MECHANICAL CONTRACTOR PROVIDE A 20 AMP, 120 VOLT, RECEPTACLE OUTLET INSTALLED AT AN ACCESSIBLE LOCATION FOR THE SERVICING OF HEATING, AIR CONDITIONING, AND REFRIGERATION EQUIPMENT OF ROOF TOPS, ATTICS, AND CRAWL SPACES PER NEC 210-63. LOCATE THE RECEPTACLE ON THE SAME LEVEL AND WITHIN 25' OF THE EQUIPMENT. INSTALL A GFCI RECEPTACLE AT ROOF TOP LOCATIONS WITH CAST BOX, WEATHERPROOF COVER PLATE, AND MOUNT ONTO A THREADED IMC CONDUIT SECURELY FASTENED IN PLACE IN ACCORDANCE WITH NEC 314-23. MECH MECHANICAL 27. NIC NOT IN CONTRACT INSTALL AT LEAST ONE WALL SWITCH-CONTROLLED LIGHTING OUTLET AT OR NEAR EQUIPMENT REQUIRING SERVICING SUCH AS HEATING, AIR CONDITIONING, AND REFRIGERATION EQUIPMENT IN ATTIC OR UNDERFLOOR SPACES PER NEC 210-70. LOCATE SWITCH AT POINT OF ENTRY TO THE ATTIC OR UNDERFLOOR SPACE. NTS NOT TO SCALE 28. BRANCH CIRCUITS: UTILIZE #10 AWG CONDUCTORS ON ALL RUNS OVER 100'-0". OHE OVERHEAD ELECTRICAL FEEDER OHP OVERHEAD PRIMARY FEEDER 29. PHASE PROTECTION: INSTALL PHASE PROTECTION ON ALL NEW 3 PHASE MOTORS 1HP AND ABOVE AND ALL 3PH AIR HANDLING UNITS. MANUFACTURED BY CUTLER HAMMER D65 OR SQUARE D MPS. OHS OVERHEAD SECONDARY FEEDER PVC POLYVINYL CHLORIDE 30. PLMBG PLUMBING MULTIPLE PHASE HOME RUNS MAY SHARE A COMMON NEUTRAL EXCEPT WHEN A DIMMER/ DIMMING SYSTEM IS USED, & WHEN ELECTRONIC/ COMPUTER EQUIPMENT CONNECTIONS ARE REQUIRED. VERIFY W/ ENGINEER PRIOR TO ROUGH-IN. PNL PANEL 31. RTU ROOFTOP UNIT PROVIDE ACCESS PANELS WITHIN THE ELECTRICAL BID. TURN OVER TO THE APPROPRIATE TRADE FOR INSTALLATION. REFER TO ARCHITECTURAL SPECIFICATION SECTIONS. TVSS TRANSIENT VOLTAGE SURGE SUPPRESSER 32. UG UNDERGROUND UGE UNDERGROUND ELECTRICAL FEEDER UGP UNDERGROUND PRIMARY FEEDER COORDINATE SHORT CIRCUIT RATING OF PANELBOARDS AND OVER-CURRENT PROTECTION WITH UPSTREAM OVER- CURRENT PROTECTION AND AVAILABLE SCA. PROPERLY IDENTIFY ALL PANELBOARDS W/ LAMINATE LABEL & TYPE ALL PANEL SCHEDULES. INSTALL PANELBOARDS AS INDICATED ON DRAWINGS AND SCHEDULES. PROVIDE CIRCUIT BREAKERS AS REQUIRED. USE "HACR" BREAKERS FOR HEATING /AIR CONDITIONING LOADS, PROVIDE GROUND-FAULT CIRCUIT-INTERRUPTER BREAKERS AS REQUIRED. PROVIDE A GROUND BAR KIT WITHIN EACH DISTRIBUTION PANEL, BRANCH CIRCUIT PANEL, AND LOAD CENTER. UPS UN INTERRUPT ABLE POWER SUPPLY 33. WP WEATHERPROOF INSTALL METERING AND ELECTRICAL SERVICE ENTRANCE EQUIPMENT IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL ELECTRIC UTILITY SYSTEM STANDARDS. XFMR TRANSFORMER 34. EXTEND ALL CONDUIT AND CONDUCTORS, INSTALL ELECTRICAL EQUIPMENT AS NECESSARY, AND MAKE ALL FINAL CONNECTIONS TO MECHANICAL AND OWNER FURNISHED EQUIPMENT. LEAVE ALL EQUIPMENT IN OPERABLE CONDITION WITH APPROPRIATE OVERLOAD AND SERVICE DISCONNECT PROTECTION AS REQUIRED BY THE APPLICABLE CODES. FOLLOW MANUFACTURERS INSTALLATION GUIDELINES WHERE APPLICABLE. 35. COORDINATE WITH THE MECHANICAL /PLUMBING /CONTROLS CONTRACTOR TO INSURE THAT ALL REQUIRED COMPONENTS OF CONTROL WORK ARE INCLUDED AND FULLY UNDERSTOOD. NO ADDITIONAL COST SHALL ACCRUE TO THE OWNER AS A RESULT OF LACK OF SUCH COORDINATION. REFER TO THE ELECTRICAL CONNECTION SCHEDULE FOR MECHANICAL EQUIPMENT AND THE MECHANICAL-ELECTRICAL RESPONSIBILITY TABLE. 36. CEILING PENETRATIONS IN FIRE RATED CEILINGS SHALL CONFORM TO THE REQUIREMENTS OF IBC SECTION 712. IF AGGREGATE PENETRATION AREA (DETERMINE AGGREGATE AREA FOR ALL DISCIPLINES PENETRATING CEILING AREA) EXCEEDS AREA ALLOWED, THE ELECTRICAL CONTRACTOR SHALL INCLUDE, AS REQUIRED, A FIRE RATED ENCLOSURE FOR EACH FIXTURE IN THAT AREA. LIGHTING FIXTURE TYPE MAY REQUIRE ''IC'' RATING. CONSULT ARCH. FOR DETAILS. GENERAL NOTES 26.## KEYED NOTE M ## MECHANICAL EQUIPMENT IDENTIFICATION K# KITCHEN EQUIPMENT IDENTIFICATION 03/31/2016 RODAHL & HUMMELL ARCHITECTURE, P.C. GENERAL DEMOLITION NOTES 1. F F GENERAL ELECTRICAL NOTES 2. IF CONCEALED OR UNKNOWN CONDITIONS ARE UNCOVERED AND ARE AT A VARIANCE WITH CONDITIONS SHOWN IN THE CONTRACT DOCUMENTS OR OF AN UNUSUAL NATURE NOT ORDINARILY ENCOUNTERED IN WORK OF THIS KIND, NOTICE MUST BE GIVEN TO THE ENGINEER BEFORE PROCEEDING WITH ANY ADDITIONAL WORK. NO CLAIM FOR ADDITIONAL COST OR TIME EXTENSION WILL BE ALLOWED WITHOUT PROPER NOTICE, PRIOR DETERMINATION OF COST OR TIME, AND EXPENSE TO THE OWNER. THE DEMOLITION PLAN SHALL BE USED AS A SCHEMATIC GUIDE TO DEMOLITION ONLY. ADDITIONAL DEMOLITION MAY BE REQUIRED TO COMPLETE THE NEW CONSTRUCTION/ REMODELING AS INDICATED ON THE DRAWINGS. ITEMS OF DEMOLITION WORK NOT SPECIFICALLY INDICATED BUT REQUIRED TO COMPLETE THE PROJECT WORK SHALL BE INCLUDED IN THE CONTRACT SUM. DASHED WITH "R" INDICATES EXISTING DEVICE TO BE RELOCATED 3. DAMAGE ON THE CONSTRUCTION SITE CAUSED BY THE CONTRACTOR OR A PARTY TO THE CONTRACTOR DURING THE DEMOLITION OF CONSTRUCTION PHASE SHALL BE REPAIRED PRIOR TO CONTRACT DATE OF SUBSTANTIAL COMPLETION AT NO ADDITIONAL EXPENSE TO THE OWNER. 4. ALL EXISTING REMOVED EQUIPMENT WILL BE STOCKPILED AT THE SITE UNTIL AN INSPECTION BY THE OWNER'S REPRESENTATIVE WILL DETERMINE WHAT WILL BE SALVAGED, ALL EQUIPMENT NOT SALVAGED OR RETAINED BY THE CONTRACTOR FOR REUSE WILL BE HAULED OFF THE SITE BY THIS CONTRACTOR. THE STOCK PILE AREA WILL BE DETERMINED BY THE ARCHITECT AND OWNER. REFER TO ELECTRICAL SPECIFICATIONS SECTION 16060 - ''ELECTRICAL DEMOLITION FOR REMODELING''. 5. VERIFY THAT ALL ELECTRICAL EQUIPMENT TO REMAIN OR BE RELOCATED AND REUSED ARE IN WORKING ORDER PRIOR TO ANY DEMOLITION WORK. IF THE EXISTING MATERIAL IS FOUND TO BE INOPERABLE, CONTRACTOR SHALL INFORM THE OWNER ONCE ANY DEMOLITION WORK HAS BEGUN, ANY INOPERABLE OR DAMAGED MATERIAL SHALL BE REPAIRED OR REPLACED AT THE CONTRACTOR'S EXPENSE. ARCHITECTURE 609 North Dustin Farmington, NM 87401 Phone: (505) 326-6442 LOWER VALLEY SENIOR CENTER FRUITLAND, NM NOTE: SOME OF THE SYMBOLS SHOWN MAY NOT APPEAR ON ALL DOCUMENTS OR PLANS. ELECTRICAL LEGEND AND GEN. NOTES Drawn: NB Checked: JL Date: 2016-04-04 Filename: Project: 1538 Sheet: E001 Of: KEYED NOTES 26.01 26.02 26.03 26.04 26.05 26.06 26.07 26.08 26.09 26.05 26.11 26.10 26.11 26.10 26.08 26.07 26.13 XEWC 26.16 26.19 26.24 26.13 26.13 26.13 26.22 26.24 EXISTING ROOF EXHAUSTER AND RELATED HOOD TO BE RELOCATED. SEE ARCHITECTURAL PLANS FOR NEW LOCATION. EXTEND CONDUCTORS AND CONDUIT AS NECESSARY. PROVIDE CONDUCTORS AND CONDUIT FROM RELOCATED HOOD TO RELOCATED WALL SWITCH AS NECESSARY. ROOF EXHAUSTER TO REMAIN. NO WORK. RELOCATE HEATCRAFT MODEL# CHT009X68BFMT SERIAL #T13L05266 CONDENSING UNIT TO NEW ROOF ABOVE. EXTEND CONDUCTORS AND CONDUIT AS NECCESSARY. ROUTE NEW (2) #12 AND #12 G IN 1/2" C DOWN THTOURHG ROOF. RECONNECT EXISTING EVAPORATOR. RELOCATE HEATCRAFT MODEL# CHT014L6BF SERIAL# T13J17429 CONDENSING UNIT TO NEW ROOF ABOVE. EXTEND CONDUCTORS AND CONDUIT AS NECESSARY. GAS FIRED UNIT HEATER TO BE REMOVED BY MECHANICAL CONTRACTOR. REMOVE CONDUIT AND CONDUCTORS BACK TO PANEL. ROOFTOP UNIT TO REMAIN. NO WORK. THROUGH THE WALL AC UNIT TO REMAIN. NO WORK. EVAPORATIVE COOLER TO BE REMOVED BY MECHANICAL CONTRACTOR. REMOVE ALL CONDUIT AND CONDUCTORS BACK TO PANEL. REMOVE SWITCH AND PROVIDE AND INSTALL J-BOX COVER AT LOCATION OF REMOVED SWITCH. WALL FURNACE LOCATED IN UPSTAIRS STORAGE ROOM TO BE REMOVED BY MECHANICAL CONTRACTOR. REMOVE ALL CONDUIT AND CONDUCTORS BACK TO PANEL. EXISTING INSTANT ELECTRIC WATER HEATER (UNDER COUNTER, 240V) TO REMAIN. EXISTING OUTLET TO BE RELOCATED. EXTEND CONDUIT AND CONDUCTORS TO NEW LOCATION SHOWN ON NEW POWER PLAN. REMOVE AND DISPOSE OF CEILING FAN, TYPICAL ALL. REMOVE CONDUIT AND CONDUCTORS BACK TO PANEL. REMOVE CONDUCTORS AND CONDUIT BACK TO WALL SWITCH. PROVIDE AND INSTALL J-BOX COVER AT LOCATION OF REMOVED SWITCH. ALL EXISTING RECEPTACLES AND DATA DEVICES IN THIS ROOM ARE TO REMAIN. ALL KITCHEN EQUIPMENT SHOWN ON THIS DRAWING IS EXISTING TO BE RELOCATED. EXTEND ORIGINAL CIRCUIT AS NEEDED AND RECONNECT. SEE KITCHEN EQUIPMENT SCHEDULE FOR EQUIPMENT DETAILS. RELOCATED EXISTING OUTLET. RECONNECT TO EXISTING CIRCUIT. RE-ROUTE CONDUCTORS IN WALL. EXISTING ELECTRIC WATER COOLER TO BE REMOVED AND REINSTALLED IN SAME LOCATION ON NEW WALL SURFACE. 26.09 26.05 KD KD 26.02 26.06 26.01 XEF3 J 26.01 XEF1 J J J J KG KS KH G KO KH 26.03 XC1 26.04 XC2 1 POWER DEMOLITION PLAN 1/8" = 1'-0" CX2 CX1 WP 26.16 26.16 STORAGE 110 PANEL B 26.16 26.16 OFFICE 111 DINING ROOM 107 26.16 MEN 106 26.22 26.24 MDP - 9,11 XEWC 26.16 MDP - 5,7 26.16 OFFICE 108 STORAGE 112 R3 R2 PANEL A 26.06 WAREWASH 114 A-8 A-6 R1 A-7 2 2 XR1 2 26.02 2 26.16 G KH J 26.03 KG XEF1 J KS 26.01 26.19 XEF3 J KO J 26.19 J 26.01 PANEL MDP A-4 03/31/2016 GAME ROOM 100 RODAHL & HUMMELL ARCHITECTURE, P.C. 2 COMPUTER 101 KITCHEN 104 A - 10 MDP - 1,3 2 OFFICE 113 A-2 2 26.07 G WOMEN 105 A-9 G TO LIGHTING CIRCUIT VEST KW 103 KD 26.19 XC1 COOLER/ FREEZER 115 XC2 26.04 CX3 R.R. 102 TO LIGHTING CIRCUIT ARCHITECTURE LOWER VALLEY SENIOR CENTER FRUITLAND, NM KH 2 POWER PLAN 1/8" = 1'-0" 609 North Dustin Farmington, NM 87401 Phone: (505) 326-6442 ELECTRICAL POWER PLANS Drawn: NB/AW Checked: JL Date: 2016-04-04 Filename: Project: 1538 Sheet: EP101 Of: KEYED NOTES 26.08 26.12 X6 X6 26.14 X3 26.14 X3 PANEL B 26.23 26.25 26.08 a bc d X3 26.17 26.17 TO REMAIN X1 X1 X1 X1 X1 X1 X1 X1 X1 X1 X1 X1 X1 X1 26.26 X4 X4 EVAPORATIVE COOLER TO BE REMOVED BY MECHANICAL CONTRACTOR. REMOVE ALL CONDUIT AND CONDUCTORS BACK TO PANEL. REMOVE SWITCH AND PROVIDE AND INSTALL J-BOX COVER AT LOCATION OF REMOVED SWITCH. EXISTING SWITCH TO BE REMOVED. PATCH AND REPAIR. NEW SWITCH TO BE PROVIDED AFTER NEW DOOR IS INSTALLED PER NEW LIGHTING PLAN. EXISTING SWITCHES SERVING ENTRYWAY AND EXTERIOR LIGHTING TO BE REMOVED. ENTRYWAY TO BE CONTROLLED BY OCCUPANCY SENSOR, EXTERIOR LIGHTING TO BE CONTROLLED BY INTEGRAL PHOTOCELL. REPLACE FOUR SWITCHES CONTROLLING LIGHTING IN THIS ROOM WITH LOW VOLTAGE DIMMERS. CONNECT DIMMERS AND OCCUPANCY SENSORS TO LOCAL ROOM CONTROLLER WITH CAT5 CABLE. PROVIDE SWITCH FOR MANUAL OVERRIDE OF NEW CEILING OCCUPANCY SENSOR. PROVIDE QUANTITY OF OCCUPANCY SENSORS REQUIRED FOR FULL COVERAGE ACCORDING TO MANUFACTURER'S SPECIFICATIONS. TEST AND ADJUST AS NEEDED FOR PROPER FUNCTION. TYPICAL ALL OCCUPANCY SENSORS. EXISTING MANUAL CONTROLS IN KITCHEN TO REMAIN. ADD NEW FIXTURES TO EXISTING SINGLE CONTROL ZONE. X4 X4 26.12 26.12 X2 X5 X2 X5 X5 3 X1 X1 X1 X1 X1 X1 3 X1 X3 X3 X3 X3 X3 X3 X1 X1 X1 X1 X1 X1 X1 X7 a X7 X2 b c PANEL A X6 X2 X2 X2 X2 X2 X2 X2 X2 X4 COOLER PANEL MDP FREEZER 1 LIGHTING DEMOLITION PLAN 1/8" = 1'-0" F F ENTRY 109 C 26.17 EL STORAGE 110 C DDDD a b c d D6 D6 C AV, a AV, a AV, b AV, b AV, c AV, c AV, d AV, d WOMEN 105 PANEL B OFFICE 111 AM 26.23 26.17 D6 D6 MEN 106 26.23 RC EL AV, d Panel B AV, a AV, a AV, b AV, b AV, c AV, c AV, d EL Panel B AM AM G AM 26.25 Panel B STORAGE 112 26.25 Panel B Panel B C C C AV, a AV, a AV, b AV, b AV, c AV, c AV, d EL X7 26.26 B2 PANEL A B2 B1 B2 WAREWASH 114 OFFICE 113 AM A-5 B2 PANEL MDP B2 EL COMPUTER 101 AM B1 B2 B1 B1 B1 AM GAME ROOM AM 100 AM D12 03/31/2016 AM B1 VEST 103 B1 C B1 KITCHEN 104 (EXISTING) C 26.23 Panel B D12 G C 26.23 AV, d X7 B2 OFFICE 108 26.23 Panel B AM AM RODAHL & HUMMELL ARCHITECTURE, P.C. AM C ARCHITECTURE COOLER/ FREEZER 115 R.R. 102 D6 609 North Dustin Farmington, NM 87401 Phone: (505) 326-6442 LOWER VALLEY SENIOR CENTER FRUITLAND, NM 2 LIGHTING PLAN 1/8" = 1'-0" ELECTRICAL LIGHTING PLANS Drawn: NB/AW Checked: JL Date: 2016-04-04 Filename: Project: 1538 Sheet: EL101 Of: LOAD SUMMARY: MDP 28.75 DEMAND LOAD (KVA) ITEM ADDED REMOVED LIGHTING (125%) 1.00 -1.1 LIGHTING (125%) ADDED REMOVED 4.95 -6.14 ADDED REMOVED PANEL A CHANGE 11.86 -11.9 MISC. POWER (100%) 5.76 0 MISC. POWER (100%) 0 0 MECHANICAL (125%) 26.88 0 MECHANICAL (100%) 0.05 0 MECHANICAL (100%) 0.10 -4.66 PANEL B CHANGE 55.59 KVA 231.6 AMPS @ 240V, 1 PH -5.75 KVA -0.2 AMPS -24.0 AMPS NET CHANGE: @ 240V, 1 PH 400 AMPS @ 240V, 1 PH Circuit Description R1 -R2 -R3 -PANEL A -Space Space Trip 45 -60 -60 -250 ---- Poles 2 -2 -2 -2 ---- 3600 A.I.C. Rating: 22,000 Mains Type: MCB Mains Rating: 400 A B 1350 4920 1400 4920 0 0 0 3600 1350 4920 1400 4920 0 0 0 0 0 0 0 Poles 2 -2 -1 1 ----- Trip 20 -25 -20 20 ----- Circuit Description XC1 -XC2 -FREEZER LIGHTS / DOOR COOLER LIGHTS / COIL Space Space Space Space CKT 2 4 6 8 10 12 14 16 18 20 RISER LEGEND BUILDING 4 4 1 5 5 PANEL MDP PANEL A PANEL B NEW OR MODIFIED IN THIS PROJECT EXISTING TO REMAIN EXISTING TO BE DEMOLISHED MLO - 240V 400A MCB NEW RTU NEW RTU NEW RTU 240V SINGLE PHASE MCB - 240V M RISER GENERAL NOTES EXIST COMP. 1. ALL UNDERGROUND CONDUIT TO BE SCHEDULE 80 PVC. EXIST COMP. 2. ALL EXPOSED EXTERIOR CONDUIT TO BE RIGID STEEL. 3. THIS DIAGRAM IS SCHEMATIC, AND NOT INTENDED TO SPECIFY CONDUIT ROUTING OR FEED SIDE OF PANELS. 4. WHERE ALUMINUM FEEDERS ARE SPECIFIED, VERIFY THAT ASSOCIATED PANELS ARE RATED FOR ALUMINUM CONDUCTORS. 5. TERMINAL SCREWS ON ALL ALUMINUM FEEDERS SHALL BE TORQUED TO CONDUCTOR MANUFACTURER'S SPECIFICATIONS AT CONSTRUCTION, AND RE-TORQUED 90 DAYS AFTER COMMISSIONING. # 1/0 CU NEUT BUS GRND BUS # 1/0 CU # 3 # 1/0 CU 20 '-0 " RISER KEYED NOTES 20' LOOP 30" BELOW GRADE 20'-0" 2 SETS OF (3) # 4/0 AL IN 2" COND. 2 0" 0'- (3) 3/4" X 10' COPPER CLAD STEEL GROUND RODS NEW ELECTRICAL RISER DIAGRAM 1. REPLACE EXISTING FEED-THROUGH MDP WITH NEW MDP WITH SUBFEED BREAKER. SEE PANEL SCHEDULE FOR DETAILS. 2. EXISTING MDP IS GROUNDED THROUGH METER. REPLACE GROUNDING ELECTRODE AS SHOWN. 3. THE UNDERGROUND PORTION OF THE SERVICE LATERAL PASSES BENEATH A BUILDING ADDITION TO BE CONSTRUCTED IN THIS PROJECT. COORDINATE WITH UTILITY TO REPLACE SERVICE CONDUCTORS WITH LARGER SIZE AS SHOWN. ROUTE AROUND BUILDING ADDITION. 4. THE UTILITY TRANSFORMER AND METER WILL NEED TO BE REPLACED AS A RESULT OF THIS PROJECT. COORDINATE WITH UTILITY. 5. THIS PANEL IS EXISTING TO REMAIN. SEE PLANS AND LOAD SUMMARY FOR BRANCH CIRCUIT CHANGES. BUILDING 4 4 1 5 5 PANEL MDP PANEL A PANEL B M 300A MCB EXIST COMP. EXIST COMP. 240V SINGLE PHASE SERVICE CAPACITY: NET CHANGE: A CKT 1 3 5 7 9 11 13 15 17 19 -10.8 -0.04 KVA Volts: 120/240 Single Phases: 1 Wires: 3 Notes: LOADS ONLY SHOWN FOR NEW CIRCUITS ON THIS SCHEDULE. SEE LOAD SUMMARIES FOR EXISTING DEMAND AND NEW TOTAL. 3 2 NEUT BUS MLO - 240V NEW SERVICE TOTAL: 5.05 PANEL MDP Location: EXTERIOR Supply From: Mounting: Surface Enclosure: 3R DEMAND LOAD (KVA) ITEM DEMAND LOAD (KVA) ITEM NEW LOAD SUMMARY: PANEL B (3) 250 MCM CU + #2 CU GRND. IN 2.5" COND. MCB - 240V EXISTING MAX DEMAND: (PER UTIL, 125%) LOAD SUMMARY: PANEL A (3) #2 CU + #8 CU GRND. IN 1.25" COND. 03/31/2016 GRND BUS RODAHL & HUMMELL ARCHITECTURE, P.C. ARCHITECTURE (3) 250 MCM CU IN 2.5" CONDUIT 609 North Dustin Farmington, NM 87401 Phone: (505) 326-6442 LOWER VALLEY SENIOR CENTER FRUITLAND, NM EXISTING ELECTRICAL RISER DIAGRAM ELECTRICAL RISER AND SCHEDULES Drawn: AW Checked: JL Date: 2016-04-04 Filename: Project: 1538 Sheet: E501 Of: KITCHEN EQUIPMENT CONNECTION SCHEDULE NM 2 CUMULATIVE VOLTAGE DROP 13400 Segment Voltage Drop at the secondary of the utility transformer FAULT CURRENT Motor Contribution M f Conductor Reactance (X) Conductor Resistance (R) Length (L) 1 L-L Volts (E) 1 'C' value 2 MDP Wire/Bus 0 Conduit Type Source (Point) 1 Source Isc Phase 1 SERVICE Point Description SHORT CIRCUIT & VOLTAGE DROP CALCULATIONS 13400 - - 9973 1.1% 1.1% Set(s) 4/0 AL 11174 240 80 of 0.0001 0.000041 0.400 0.714 0.00005 0.000052 0.076 0.930 9272 0.2% 1.3% 0.0002 0.000057 0.654 0.605 5605 0.7% 2.0% 3 PANEL A 1 2 9973 M Set(s) 1 250 CU 16483 240 15 of 4 PANEL B 1 3 9272 M 1 Set(s) 2 of CU 5906 240 50 NOTES TO THE CONTRACTOR: 100 LEGEND: 1. THE DISTANCES SHOWN ARE FOR CALCULATION PURPOSES ONLY. THEY SHALL NOT BE USED FOR CONTRACTOR TAKEOFFS, NOR FOR BIDDING. 2. CONTRACTOR SHALL NOTIFY ENGINEER OF ANY FIELD CONDITION THAT RESULTS IN A CHANGE OF 10% OR GREATER CIRCUIT DISTANCE CALCULATIONS ARE BASED ON THE "POINT-BY-POINT" METHOD: NM = NON-MAGNETIC CONDUIT M = MAGNETIC CONDUIT FB = FEEDER BUSWAY PB = PLUG-IN BUSWAY XFMR = TRANSFORMER L= I= Isca (1) = SHORT CIRCUIT CURRENT AT FAULT POINT #1 Isca (2) = SHORT CIRCUIT CURRENT AT FAULT POINT #2 Isca (2) = Isca (1) x M(1) M = 1/(1+f) FEEDER: 'f (3Ø) = 1.732 x L x Isca CxE XFMR: 'f (3Ø) = IP(sca)x Vp x 1.73 x %Z 100,000 x kVA FEEDER: 'f (1Ø) = 2 x L x Isca CxE XFMR: 'f (1Ø) = IP(sca)x Vp x %Z 100,000 x kVA ISsca = Vp x M x IP(sca) Vs LENGTH OF CIRCUIT TO THE FAULT IN FT (1 WAY). AVAILABLE SHORT-CIRCUIT CURRENT IN AMPS AT THE BEGINNING OF THE CIRCUIT. C = 'C' FACTOR CONSTANT FROM THE TABLE OF 'C' VALUES FOR THE CONDUCTORS. E = LINE-TO-LINE OR LINE-TO NEUTRAL VOLTAGE. IP = PRIMARY SHORT CIRCUIT CURRENT IS = IS = SECONDARY SHORT CIRCUIT CURRENT Vs = SECONDARY VOLTAGE Vp = PRIMARY VOLTAGE TYPE KD KG KH KO KS KW QUANTITY 1 1 2 1 1 1 DESCRIPTION EXISTING STACKED DRYER, 240V GARBAGE DISPOSAL, 3/4 HP, 240V GREASE HOOD, 120V CONVECTION OVEN, GAS FIRED, 1/2 HP FAN, 120V STOVE / OVEN COMBO, GAS FIRED , 120V CONTROLS EXISTING STACKED CLOTHES WASHER, 120V CB SIZE 30 A 20 A 20 A 20 A 20 A 20 A SHUNT TRIP CB REQ. No No No Yes Yes No CONDUCTORS # 10 CU + #10 CU GROUND # 12 CU + #12 CU GROUND # 12 CU + #12 CU GROUND # 12 CU + #12 CU GROUND # 12 CU + #12 CU GROUND # 12 CU + #12 CU GROUND NOTES TO BE RELOCATED TO BE RELOCATED TO BE RELOCATED TO BE RELOCATED, REPLACE CB WITH SHUNT TRIP AND CONNECT TO ANSUL SYS TO BE RELOCATED, REPLACE CB WITH SHUNT TRIP AND CONNECT TO ANSUL SYS TO BE RELOCATED MECHANICAL EQUIPMENT CONNECTION SCHEDULE TYPE CX1 CX2 CX3 R1 R2 R3 XC1 XC2 XEF1 XEF3 XEWC DESCRIPTION NEW CEILING EXHAUSTER NEW CEILING EXHAUSTER NEW CEILING EXHAUSTER NEW ROOFTOP UNIT NEW ROOFTOP UNIT NEW ROOFTOP UNIT EXISTING COOLER CONDENSER EXISTING FREEZER CONDENSER EXISTING ROOF EXHAUSTER, 3/4 HP EXISTING ROOF EXHAUSTER EXISTING WATER COOLER ELECTRICAL 120 V/1-53 VA 120 V/1-53 VA 120 V/1-53 VA 240 V/2-7200 VA 240 V/2-9840 VA 240 V/2-9840 VA 240 V/2-2700 VA 240 V/2-2800 VA 120 V/1-1330 VA 120 V/1-276 VA 120 V/1-1400 VA CB AT PANEL 15 A 15 A 15 A 45 A 60 A 60 A 20 A 25 A 20 A 15 A 20 A DISC. AT UNIT SWITCH SWITCH SWITCH INCL. INCL. INCL. RELOCATE RELOCATE REPLACE REPLACE CORD/PLUG CONDUCTORS # 12 CU + #12 CU GROUND # 12 CU + #12 CU GROUND # 12 CU + #12 CU GROUND # 8 CU + # 10 CU GROUND # 6 CU + # 10 CU GROUND # 6 CU + # 10 CU GROUND # 10 CU + #10 CU GROUND # 10 CU + #10 CU GROUND # 12 CU + #12 CU GROUND # 12 CU + #12 CU GROUND # 12 CU + #12 CU GROUND NOTES CONTROL VIA SECOND RELAY IN OCCUPANCY SENSOR CONTROL VIA SECOND RELAY IN OCCUPANCY SENSOR CONTROL VIA SECOND RELAY IN OCCUPANCY SENSOR CONNECT INTEGRAL CONVENIENCE RECEPT. CONNECT INTEGRAL CONVENIENCE RECEPT. CONNECT INTEGRAL CONVENIENCE RECEPT. TO BE RELOCATED TO BE RELOCATED TO BE RELOCATED TO BE RELOCATED TO BE RECONNECTED IN SAME LOCATION LIGHTING FIXTURE SCHEDULE TYPE AM AV B1 B2 C D6 D12 EL F G X1 X2 X3 X4 X5 X6 X7 DESCRIPTION 2X4 VOLUMETRIC TROFFER, MEDIUM OUTPUT 2X4 VOLUMETRIC TROFFER, VERY HIGH OUTPUT, DIMMING 1X4 KITCHEN TROFFER, SMOOTH LENS, GASKETED 2X4 KITCHEN TROFFER, SMOOTH LENS, GASKETED LINEAR WRAP LENS DIRECT-INDIRECT, 6 FOOT, VERTICAL FACE DIRECT-INDIRECT, 12 FOOT, ANGLED FOR UPLIGHT EXIT SIGN WITH LIGHTS EXTERIOR - FULL CUTOFF SCONCE WITH BATTERY AND PHOTOCELL EXTERIOR - SQUARE DOME WITH BATTERY AND PHOTOCELL EXISTING TROFFER EXISTING TROFFER EXISTING LINEAR LENSED EXISTING LINEAR LENSED EXISTING DOME LENS EXISTING EXTERIOR WALLPACK EXISTING EMERGENCY LIGHT MOUNTING RECESSED RECESSED RECESSED RECESSED SURFACE WALL WALL UNIVERSAL WALL SURFACE RECESSED RECESSED SURFACE WALL SURFACE WALL WALL LAMP LED LED LED LED LED LED LED LED LED LED (4) T-12 (3) T-5 (2) T-5 (2) T8 INCAND. INCAND. LED ELECTRICAL 120 V/1-40 VA 120 V/1-65 VA 120 V/1-39 VA 120 V/1-45 VA 120 V/1-48 VA 120 V/1-60 VA 120 V/1-110 VA 120 V/1-3 VA 120 V/1-26 VA 120 V/1-22 VA 120 V/1-128 VA 120 V/1-84 VA 120 V/1-56 VA 120 V/1-64 VA 120 V/1-60 VA 120 V/1-60 VA 120 V/1-0 VA MAKE COLUMBIA COLUMBIA COLUMBIA COLUMBIA COLUMBIA FINELITE FINELITE COMPASS KENALL KENALL EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING MODEL LCAT24-35MLG-EDU LCAT24-35VLG-EDU LJT14-35MLG-FSA19INVERTED-EU-G3 LJT24-35MLG-FSA19INVERTED-EU-G3 LAW4-35ML-EU S17-LED-VCF-PF-6-HO-35-SC-120 S17-LED-ACF-PF-12-HO-35-SC-120 CCR FN15NL-4-7-DB-26L40K-120-LEL-BPC MS11FL-PP-DB-20L35K-DCC-120-LEL-BPC 03/31/2016 RODAHL & HUMMELL ARCHITECTURE, P.C. ARCHITECTURE 609 North Dustin Farmington, NM 87401 Phone: (505) 326-6442 LOWER VALLEY SENIOR CENTER FRUITLAND, NM ELECTRICAL SCHEDULES Drawn: AW Checked: JL Date: 2016-04-04 Filename: Project: 1538 Sheet: E601 Of: