ELECTRICAL SYMBOLS LEGEND
FIRE ALARM
SWITCHING
LIGHTING
RECTANGULAR FIXTURE, CEILING MOUNTED
(DIMENSIONS AS SHOWN)
A
FACP
FIRE ALARM (FA) CONTROL PANEL
ANN
FA ANNUNCIATOR
ROUND FIXTURE, CEILING MOUNTED
(DIMENSIONS AS SHOWN)
A
A
B
C
TRACK LIGHTING
(LENGTH AS SHOWN, HEADS NOT TO SCALE)
A
POLE MOUNTED FIXTURE
(HEADS NOT TO SCALE)
ARM SYMBOL ADDITION
INDICATES WALL MOUNTING
A
A
DOT SYMBOL ADDITION
INDICATES PENDANT MOUNTING
A
A
A
A-E
PERFORM ALL ELECTRICAL WORK IN A NEAT AND WORKMANLIKE MANNER IN FULL COMPLIANCE WITH ALL
APPLICABLE, ADOPTED, CODES; INCLUDING, BUT NOT LIMITED TO THE NATIONAL ELECTRICAL CODE (NEC),
UBC, IBC, NFPA, AND ADA. ALL LOCAL AND STATE REQUIREMENTS WILL BE OBSERVED DURING THE
PERFORMANCE OF THIS WORK.
3.
NOTIFY THE ENGINEER IN WRITING IF DISCREPANCIES BETWEEN CONTRACT DOCUMENTS AND ANY ASSOCIATED
LEGAL OR SAFETY REQUIREMENTS ARE DETECTED. THE ENGINEER WILL MODIFY THE CONTRACT DOCUMENTS
ACCORDINGLY. IF THE CONTRACTOR PROCEEDS W/ ANY WORK WHICH IS IN VARIANCE OF KNOWN LEGAL OR
SAFETY REQUIREMENTS, THE CONTRACTOR WILL ASSUME RESPONSIBILITY FOR THIS WORK AND WILL PROMPTLY
CORRECT THE WORK, WHEN NOTIFIED WITHOUT ADDITIONAL COST TO THE OWNER.
4.
FIELD VERIFY EXISTING CONDITIONS PRIOR TO COMMENCING WORK. NOTIFY THE ENGINEER OF ANY
DISCREPANCIES BEFORE PROCEEDING. NO CLAIM FOR ADDITIONAL COST OR TIME EXTENSION WILL BE ALLOWED
WITHOUT PROPER NOTICE PLUS PRIOR DETERMINATION OF TIME AND COST TO THE OWNER.
5.
CLEAN THE ENTIRE ELECTRICAL SYSTEM AFTER COMPLETION OF THE INSTALLATION. REMOVE ALL FOREIGN
MATTER, PAINT, OR DIRT, GREASE, UNNEEDED LABELS OR STICKERS FROM FIXTURES AND EQUIPMENT. REMOVE
ALL RUBBISH AND DEBRIS ACCUMULATED DURING INSTALLATION FOR THE PREMISES.
WALL OCCUPANCY SENSOR (ARROWS INDICATE VIEW)
6.
COORDINATE ALL PHASES OF THE ELECTRICAL WORK WITH THE ARCHITECT AND GENERAL CONTRACTOR.
PERFORM WORK TO CAUSE AS LITTLE INCONVENIENCE AS POSSIBLE TO THE OWNER.
POWER OUTLETS
7.
OBTAIN, FROM SYSTEM SUPPLIERS, ALL WIRING DIAGRAMS FOR ALL EQUIPMENT, PRIOR TO ANY ROUGH-IN, TO
ASSURE THAT PROPER ELECTRICAL CHARACTERISTICS ARE PROVIDED, ANY INCORRECT WIRING OR DEVICES
INSTALLED BY ELECTRICAL CONTRACTOR WITHOUT THE WIRING DIAGRAM SHALL BE CORRECTED AT ELECTRICAL
CONTRACTOR'S EXPENSE.
8.
VERIFY ELECTRICAL DEVICE LOCATIONS WITH ARCHITECTURAL CASE WORK DETAILS PRIOR TO ANY ROUGH-IN.
9.
VERIFY FINAL LOCATIONS OF ALL SINKS WITH THE PLUMBING CONTRACTOR PRIOR TO ROUGH-IN. ANY
ELECTRICAL DEVICES LOCATED ABOVE COUNTER AND BEHIND FINAL SINK LOCATIONS WILL BE SHIFTED A
MINIMUM OF 8'' TO EITHER SIDE OF SINK. ANY ELECTRICAL DEVICES LEFT BEHIND SINK AT TIME OF FINAL
ELECTRICAL WALK THROUGH WILL BE RELOCATED AT ELECTRICAL CONTRACTOR'S EXPENSE.
10.
PRIOR TO INSTALLATION, THE OWNER RESERVES THE RIGHT TO RELOCATE ANY ELECTRICAL DEVICE, UP TO A
DISTANCE OF 12", WITHOUT ADDITIONAL CHARGE.
11.
FIELD VERIFY AND COORDINATE THE EXACT LOCATION OF ALL SYSTEMS AND EQUIPMENT WITH ALL TRADES
PRIOR TO INSTALLATION. WHERE EXACT LOCATIONS ARE NECESSARY, THEY ARE DIMENSIONED ON THESE
DRAWINGS. WHERE THERE IS A QUESTION OF ADEQUATE CLEARANCE OR COORDINATION BETWEEN TRADES, THIS
CONTRACTOR WILL PREPARE AS BUILT DRAWINGS FOR ENGINEERS REVIEW.
12.
CONTACT UTILITY COMPANIES (POWER, GAS, WATER, SEWER, TELEPHONE, CABLE TV., ETC.) PRIOR TO
TRENCHING IN ORDER TO IDENTIFY UNDERGROUND UTILITIES. CONTRACTOR SHALL LOCATE SECONDARY SERVICE
FEEDERS, UNDER- GROUND ELECTRICAL BRANCH CIRCUITS, SPRINKLER LINES, ETC., PRIOR TO TRENCHING.
ANY CUT DAMAGED UNDER- GROUND UTILITIES SHALL REPAIRED OR REPLACED AT CONTRACTOR'S EXPENSE.
13.
UTILIZE COPPER CONDUCTORS, RATED FOR 600 VOLTS, TYPE THHN/THWN INSULATION, UNLESS OTHERWISE
INDICATED. MINIMUM WIRE SIZE #12 AWG AND STRANDED FOR #8 AWG OR LARGER, RUN WIRING IN CONDUIT
INCLUDING LOW VOLTAGE AND CONTROL WIRING, UNLESS OTHERWISE NOTED.
14.
UTILIZE 1/2 INCH E.M.T. CONDUIT MINIMUM. WHERE REQUIRED TO PROTECT FROM PHYSICAL DAMAGE, USE
RIGID OR IMC TYPE CONDUIT. RUN CONDUIT CONCEALED UNLESS OTHERWISE SHOWN ON THE DRAWINGS. USE
FLEXIBLE METALLIC CONDUIT WHERE NEEDED. PROVIDE EXPANSION FITTINGS FOR CONDUIT CROSSING
EXPANSION JOINTS.
15.
SUPPORT ALL CONDUIT INDEPENDENTLY FROM THE BUILDING STRUCTURE. DO NOT SUPPORT FROM VENTILATION
DUCTS, MECHANICAL PIPING, SUSPENDED CEILING GRIDS, OR THEIR HANGERS. USE ONLY ACCEPTABLE
METHODS OF SUPPORT.
16.
TERMINATING & SPLICING: MAKE ALL JOINTS & SPLICES IN BRANCH CIRCUIT WIRING, #10 AWG & SMALLER,
W/ AN APPROVED SOLDER LESS TOOL OR TWIST ON CONNECTORS. #8 AWG AND LARGER USE HIGH
COMPRESSION BARREL SPLICES WITH SHRINK WRAP AND MANUFACTURER'S COMPATIBLE CONNECTORS IN
GUTTERS, AND SIMILAR LOCATIONS; BUT NOT ALLOWED IN RACEWAYS. LEAVE SUFFICIENT SLACK TO PERMIT 2
OR MORE SPLICES OR JOINTS TO BE REMADE IN CASE OF FAULT.
17.
EMT CONDUIT FITTINGS: IN DRY LOCATIONS USE STEEL SET SCREW TYPE OR "REGAL" DIE CAST SET SCREW
COUPLINGS AND CONNECTORS. DIE CAST FITTINGS WILL NOT BE USED ON THIS PROJECT. DAMP/ WET
LOCATIONS: USE STEEL COMPRESSION GLAND TYPE COUPLER AND CONNECTIONS.
18.
SURFACE RACEWAY: WHEREVER CONCEALED CONDUIT IN FINISHED AREAS IS NOT POSSIBLE, INSTALL SURFACE
MOUNTED RACEWAYS EQUAL TO WIREMOLD. RUN SURFACE RACEWAYS IN CORNER OF WALL AND CEILING. ALL
RACEWAYS THAT ARE EXPOSED WILL REQUIRE ARCHITECT'S/ ENGINEER'S APPROVAL PRIOR TO ROUGH-IN.
COLOR BY ARCHITECT.
19.
TYPE NM (ROMEX CABLE) AND NMC CABLE WILL NOT BE ALLOWED ON THIS PROJECT.
F
FA CEILING MOUNTED FA HORN/STROBE
SN
20A, NETWORKED SWITCH
SD
DIMMER SWITCH
F
FA ADA STROBE
V
F
FA CEILING MOUNTED FA STROBE
F
FA FIRE ALARM PULL STATION
F/S
FA FIRE/SMOKE DAMPER
RI
FA REMOTE INDICATOR
FS
FA FLOW SWITCH
TS
FA TAMPER SWITCH
20A, 4-WAY TOGGLE SWITCH
20A, 1 POLE KEY OPERATED SWITCH
PUSHBUTTON SWITCH
TC
TIME CLOCK SWITCH
PH
PHOTOSENSOR
RC
ROOM CONTROLLER (ABOVE CEILING)
CEILING OCCUPANCY SENSOR (ARROWS INDICATE VIEW)
FA GAS DETECTOR
FA SMOKE DETECTOR
EXIT SIGNS
(FILL INDICATES NUMBER OF FACES)
WITH
LIGHTS
2.
20A, 3-WAY TOGGLE SWITCH
FA ADA HORN/STROBE. V=VOICE/STROBE
S3
S4
SK
HALF FILLED SYMBOL
INDICATES EMERGENCY VERSION
A-E
PROVIDE, INSTALL, AND COORDINATE ALL WORK INDICATED BY THESE DRAWINGS. THIS CONSISTS OF
FURNISHING ALL LABOR, EQUIPMENT, SUPPLIES AND MATERIALS IN ADDITION TO PERFORMING ALL OPERATIONS
INCLUDING CUTTING, CHANNELING & UNDERGROUND TRENCHING, BACK FILL & TAMPING NECESSARY FOR THE
INSTALLATION OF COMPLETE POWER, LIGHTING, OR OTHER SYSTEMS AS SHOWN.
20A, 1 POLE TOGGLE SWITCH
BOX SYMBOL ADDITION
INDICATES FLOOR OR IN-GROUND MOUNTING
A
1.
S
F
DS
WITH DOUBLE
ARROW FACE
FA HEAT DETECTOR
20A, 120V, DUPLEX RECEPTACLE
FA DUCT SMOKE DETECTOR
20A, 120V, FOURPLEX RECEPTACLE
2P-4W RECEPTACLE (SEE PANEL SCHEDULE FOR DETAILS)
NOTES:
1. Lower case letters after a comma in the fixture designation indicate switching. For
example, "A3, b" indicates a type A3 fixture controlled by switch b.
2. A fixture designation ending in "-E" indicates an emergency fixture, even where the
fixture symbol may too small to show a half fill clearly.
3. Dimensions and mounting heights in the lighting fixture schedule supercede
information implied by these symbols. Symbols are for general reference only.
POWER DISTRIBUTION
G
20A, 120V - GROUND FAULT PROTECTED (AT RECEPT.
OR BREAKER, AS REQUIRED FOR ACCESSIBILITY)
WP
20A, 120V - WEATHERPROOF IN USE COVER
GROUND FAULT PROTECTED (AT RECEPT.
OR BREAKER, AS REQUIRED FOR ACCESSIBILITY)
SURFACE MOUNTED ELECTRICAL PLUG-IN
RACEWAY
20A, 120V, DUPLEX RECEPTACLE, HALF SWITCHED
DISCONNECT SWITCH
COMMUNICATIONS
S
T
2P
SPECIAL RECEPTACLE
20A FRACTIONAL HORSEPOWER DISCONNECT
SWITCH WITH THERMAL OVERLOAD
PROTECTION. 2P = 2 POLE
DATA OUTLET
CEILING MOUNTED DUPLEX RECEPTACLE, 20A, 120V
FLOOR MOUNTED DUPLEX RECEPTACLE, 20A, 120V
MOTOR OR EXHAUST FAN
SIMPLEX TYPE RECEPTACLE
CONTROL STATION
20A, 120V, DUPLEX RECEPTACLE, ABOVE COUNTER
DATA OUTLET, ABOVE COUNTER
ANALOG PHONE OUTLET
M
METER
COMBINATION DATA & ANALOG PHONE OUTLET
R
RELAY
COMBINATION DATA & ANALOG PHONE OUTLET, ABOVE COUNTER
G
GROUND CONNECTION
ANALOG PHONE OUTLET, ABOVE COUNTER
BOX INDICATES FLUSH MOUNTING IN FLOOR
CIRCLE INDICATES FLUSH MOUNTING IN CEILING
3
SUBSCRIPT INDICATES QUANTITY OF PORTS (IF MORE THAN 1)
4
M
M
M
MICROPHONE:
CEILING, WALL AND FLOOR MOUNTED RESPECTIVELY
S
S
S
SPEAKER:
CEILING, WALL AND FLOOR MOUNTED RESPECTIVELY
J
DOOR CONTROLS
THERMOSTAT OUTLET BOX: SINGLE GANG
BACK BOX, PLASTER RING (UNLESS
OTHERWISE NOTED) 1/2''CONDUIT
AND PULL CORD TO MECH UNIT
T
2
J
J
JUNCTION BOX, CEILING, WALL AND
FLOOR MOUNTED RESPECTIVELY
BRANCH CIRCUIT PANEL BOARD,
SEE SCHEDULE FOR MOUNTING
T
AO
AUTOMATIC DOOR OPENER
DH
MAGNETIC DOOR HOLDER
PS
DOOR POSITION SWITCH
EL
ELECTRIC LOCK/STRIKE
KP
KEY PAD
KC
KEY CARD READER
PAD MOUNT TRANSFORMER
ABBREVIATIONS
WALL MOUNTED HORN/SPEAKER
T
WALL MOUNT TRANSFORMER
WIRELESS ACCESS POINT
WAP
SURGE PROTECTION DEVICE
TVSS
B
BELL
GROUND
C
CLOCK OUTLET, SINGLE RECEPTACLE WITH BRACKET & CLOCK
C/S
COMBINATION CLOCK & SPEAKER WALL MOUNTED
TV
TELEVISION OUTLET
CONDUIT STUB-OUT
LIGHTNING/SURGE ARRESTOR
LA
S IC
INTERCOM CONTROL SWITCH
S IV
INTERCOM VOLUME CONTROL
C1D1 RATED SEALS
SECURITY SYSTEM INFRARED MOTION SENSOR
SITE PLAN
SECURITY SYSTEM CAMERA
OR
NURSE CALL
NP
PULL CORD, CEILING MOUNTED
NB
CALL BUTTON
NL
INDICATOR LIGHT
NC
CONTROL STATION
UGP
UNDERGROUND ELECTRICAL PRIMARY FEEDER
UGE
UNDERGROUND ELECTRICAL FEEDER
UGC
UNDERGROUND COMMUNICATIONS
OHE
OVERHEAD ELECTRICAL FEEDER
OHP
PULL CORD, WALL MOUNTED
NP
OVERHEAD ELECTRICAL PRIMARY FEEDER
TV
UNDERGROUND TELEVISION CABLE
T
UNDERGROUND TELEPHONE CABLE
MOUNTING
WALL MOUNTED
KEY
MOUNTING HEIGHTS
A
90'' TO TOP AND NOT LESS THAN 6'' BELOW
FINISHED CEILING WHERE REQUIRED
80'' TO BOTTOM AND NOT GREATER THAN 96''
TO BOTTOM
F
F
F
B
TV
PNL
C
6'-0''
D
48'' TO TOP AFF
E
20'' TO TOP AFF
F
3''
CB
S C DS
48''
J
G
F
D
H
C
B
T
TV
E
GENERAL ELECTRICAL NOTES
NOT TO SCALE
NOTES:
1. VERIFY ALL MOUNTING HEIGHTS
WITH ARCHITECT PRIOR TO ROUGH-IN.
2. DIMENSIONS ARE TO TOP OF DEVICE WITH TRIM.
ADJUST BACK BOX LOCATION AS REQUIRED.
6''AC
H
5'-0'' TO HANDLE
J
6'-6''MAX
3. ALL MOUNTING HEIGHTS SHALL CONFORM TO THE LATEST
EDITION OF THE AMERICANS WITH DISABILITIES ACT. (ADA)
DASHED VERSION OF SYMBOL INDICATES EXISTING DEVICE.
TYPICAL OF ALL SYMBOLS SHOWN ABOVE.
F
"X"
EXISTING DEVICE TO REMAIN.
"XO"
EXISTING DEVICE REMOVED COMPLETELY.
EXISTING DEVICE TO BE RELOCATED TO NEW
POSITION.
"XRR"
"XR"
EXISTING RELOCATED DEVICE.
"XP"
EXISTING DEVICE, COVERPLATE AND CIRCUITING
REPLACE WITH NEW. REFER TO NEW POWER PLANS FOR NEW CIRCUITING.
ABOVE COUNTER
ABOVE FINISHED FLOOR
20.
AFG
ARCH
BC
ABOVE FINISHED GRADE
ARCHITECTURAL
BELOW COUNTER
FEEDER RACEWAY: IN ADDITION TO RACEWAY BONDING REQUIRED BY CODE & OUTLET BOX BONDING
JUMPERS, A SEPARATE, INSULATED, GREEN EQUIPMENT GROUND CONDUCTOR. TERMINATE EACH END ON
SUITABLE LUG, BUS, OR BUSHING.
21.
C
CONDUIT
ELECTRONIC/ COMPUTER EQUIPMENT AND SPECIAL EQUIPMENT BRANCH CIRCUITS: IN ADDITION TO RACEWAY
BONDING REQUIRED BY CODE AND OUTLET BOX BONDING JUMPERS, INSTALL A SEPARATE, INSULATED, GREEN
EQUIPMENT GROUND CONDUCTOR WITHIN BRANCH CIRCUIT RACEWAY. TERMINATE EACH END ON SUITABLE
LUG, BUS, OR BUSHING.
EC
ELEC
EMT
ELECTRICAL CONTRACTOR
ELECTRICAL
ELECTRICAL METALLIC TUBING
22.
MAINTAIN A MINIMUM OF 24 INCH SEPARATION BETWEEN POWER CONDUITS AND SIGNAL CONDUITS. ROUTE
CONDUITS SO AS NOT CROSS EACH OTHER.
GC
GEC
GRC
GENERAL CONTRACTOR
GROUND ELECTRODE CONDUCTOR
GALVANIZED RIGID CONDUIT
23.
PROVIDE WIRING DEVICES RATED FOR THE GIVEN APPLICATION AS REQUIRED BY CODE.
24.
INSTALL EXTERIOR WIRING IN CONDUIT. UTILIZE WEATHERPROOF FITTINGS AND WEATHERPROOF BOXES/ COVERS.
25.
GRD
GROUND
SIZE ALL BOXES AND ENCLOSURES PER THE NATIONAL ELECTRICAL CODE. WORKING SPACE FOR ELECTRICAL
INSTALLATION SHALL BE IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE ARTICLE 110.
GFI
GROUND FAULT INTERRUPTER
26.
IG
ISOLATED GROUND
IMC
INTERMEDIATE METALLIC CONDUIT
LA
LIGHTNING ARRESTOR
MC
MECHANICAL CONTRACTOR
PROVIDE A 20 AMP, 120 VOLT, RECEPTACLE OUTLET INSTALLED AT AN ACCESSIBLE LOCATION FOR THE
SERVICING OF HEATING, AIR CONDITIONING, AND REFRIGERATION EQUIPMENT OF ROOF TOPS, ATTICS, AND
CRAWL SPACES PER NEC 210-63. LOCATE THE RECEPTACLE ON THE SAME LEVEL AND WITHIN 25' OF THE
EQUIPMENT. INSTALL A GFCI RECEPTACLE AT ROOF TOP LOCATIONS WITH CAST BOX, WEATHERPROOF COVER
PLATE, AND MOUNT ONTO A THREADED IMC CONDUIT SECURELY FASTENED IN PLACE IN ACCORDANCE WITH
NEC 314-23.
MECH
MECHANICAL
27.
NIC
NOT IN CONTRACT
INSTALL AT LEAST ONE WALL SWITCH-CONTROLLED LIGHTING OUTLET AT OR NEAR EQUIPMENT REQUIRING
SERVICING SUCH AS HEATING, AIR CONDITIONING, AND REFRIGERATION EQUIPMENT IN ATTIC OR UNDERFLOOR
SPACES PER NEC 210-70. LOCATE SWITCH AT POINT OF ENTRY TO THE ATTIC OR UNDERFLOOR SPACE.
NTS
NOT TO SCALE
28.
BRANCH CIRCUITS: UTILIZE #10 AWG CONDUCTORS ON ALL RUNS OVER 100'-0".
OHE
OVERHEAD ELECTRICAL FEEDER
OHP
OVERHEAD PRIMARY FEEDER
29.
PHASE PROTECTION: INSTALL PHASE PROTECTION ON ALL NEW 3 PHASE MOTORS 1HP AND ABOVE AND ALL
3PH AIR HANDLING UNITS. MANUFACTURED BY CUTLER HAMMER D65 OR SQUARE D MPS.
OHS
OVERHEAD SECONDARY FEEDER
30.
PVC
POLYVINYL CHLORIDE
PLMBG
PLUMBING
MULTIPLE PHASE HOME RUNS MAY SHARE A COMMON NEUTRAL EXCEPT WHEN A DIMMER/ DIMMING SYSTEM IS
USED, & WHEN ELECTRONIC/ COMPUTER EQUIPMENT CONNECTIONS ARE REQUIRED. VERIFY W/ ENGINEER
PRIOR TO ROUGH-IN.
PNL
PANEL
31.
PROVIDE ACCESS PANELS WITHIN THE ELECTRICAL BID. TURN OVER TO THE APPROPRIATE TRADE FOR
INSTALLATION. REFER TO ARCHITECTURAL SPECIFICATION SECTIONS.
RTU
ROOFTOP UNIT
TVSS
TRANSIENT VOLTAGE SURGE SUPPRESSER
32.
UG
UNDERGROUND
UGE
UNDERGROUND ELECTRICAL FEEDER
UGP
UNDERGROUND PRIMARY FEEDER
COORDINATE SHORT CIRCUIT RATING OF PANELBOARDS AND OVER-CURRENT PROTECTION WITH UPSTREAM
OVER- CURRENT PROTECTION AND AVAILABLE SCA. PROPERLY IDENTIFY ALL PANELBOARDS W/ LAMINATE
LABEL & TYPE ALL PANEL SCHEDULES. INSTALL PANELBOARDS AS INDICATED ON DRAWINGS AND SCHEDULES.
PROVIDE CIRCUIT BREAKERS AS REQUIRED. USE "HACR" BREAKERS FOR HEATING /AIR CONDITIONING LOADS,
PROVIDE GROUND-FAULT CIRCUIT-INTERRUPTER BREAKERS AS REQUIRED. PROVIDE A GROUND BAR KIT WITHIN
EACH DISTRIBUTION PANEL, BRANCH CIRCUIT PANEL, AND LOAD CENTER.
UPS
UN INTERRUPT ABLE POWER SUPPLY
33.
WP
WEATHERPROOF
INSTALL METERING AND ELECTRICAL SERVICE ENTRANCE EQUIPMENT IN ACCORDANCE WITH THE NATIONAL
ELECTRICAL CODE AND LOCAL ELECTRIC UTILITY SYSTEM STANDARDS.
XFMR
TRANSFORMER
34.
EXTEND ALL CONDUIT AND CONDUCTORS, INSTALL ELECTRICAL EQUIPMENT AS NECESSARY, AND MAKE ALL
FINAL CONNECTIONS TO MECHANICAL AND OWNER FURNISHED EQUIPMENT. LEAVE ALL EQUIPMENT IN OPERABLE
CONDITION WITH APPROPRIATE OVERLOAD AND SERVICE DISCONNECT PROTECTION AS REQUIRED BY THE
APPLICABLE CODES. FOLLOW MANUFACTURERS INSTALLATION GUIDELINES WHERE APPLICABLE.
35.
COORDINATE WITH THE MECHANICAL /PLUMBING /CONTROLS CONTRACTOR TO INSURE THAT ALL REQUIRED
COMPONENTS OF CONTROL WORK ARE INCLUDED AND FULLY UNDERSTOOD. NO ADDITIONAL COST SHALL
ACCRUE TO THE OWNER AS A RESULT OF LACK OF SUCH COORDINATION. REFER TO THE ELECTRICAL
CONNECTION SCHEDULE FOR MECHANICAL EQUIPMENT AND THE MECHANICAL-ELECTRICAL RESPONSIBILITY
TABLE.
36.
CEILING PENETRATIONS IN FIRE RATED CEILINGS SHALL CONFORM TO THE REQUIREMENTS OF IBC SECTION
712. IF AGGREGATE PENETRATION AREA (DETERMINE AGGREGATE AREA FOR ALL DISCIPLINES PENETRATING
CEILING AREA) EXCEEDS AREA ALLOWED, THE ELECTRICAL CONTRACTOR SHALL INCLUDE, AS REQUIRED, A FIRE
RATED ENCLOSURE FOR EACH FIXTURE IN THAT AREA. LIGHTING FIXTURE TYPE MAY REQUIRE ''IC'' RATING.
CONSULT ARCH. FOR DETAILS.
GENERAL NOTES
26.##
G
DEMOLITION
AC
AFF
KEYED NOTE
- ##
MECHANICAL EQUIPMENT IDENTIFICATION
K#
KITCHEN EQUIPMENT IDENTIFICATION
RODAHL & HUMMELL
ARCHITECTURE, P.C.
GENERAL DEMOLITION NOTES
1.
2.
IF CONCEALED OR UNKNOWN CONDITIONS ARE UNCOVERED AND ARE AT A VARIANCE WITH CONDITIONS SHOWN
IN THE CONTRACT DOCUMENTS OR OF AN UNUSUAL NATURE NOT ORDINARILY ENCOUNTERED IN WORK OF
THIS KIND, NOTICE MUST BE GIVEN TO THE ENGINEER BEFORE PROCEEDING WITH ANY ADDITIONAL WORK. NO
CLAIM FOR ADDITIONAL COST OR TIME EXTENSION WILL BE ALLOWED WITHOUT PROPER NOTICE, PRIOR
DETERMINATION OF COST OR TIME, AND EXPENSE TO THE OWNER.
THE DEMOLITION PLAN SHALL BE USED AS A SCHEMATIC GUIDE TO DEMOLITION ONLY. ADDITIONAL DEMOLITION
MAY BE REQUIRED TO COMPLETE THE NEW CONSTRUCTION/ REMODELING AS INDICATED ON THE DRAWINGS.
ITEMS OF DEMOLITION WORK NOT SPECIFICALLY INDICATED BUT REQUIRED TO COMPLETE THE PROJECT WORK
SHALL BE INCLUDED IN THE CONTRACT SUM.
NOTE: SOME OF THE SYMBOLS SHOWN MAY NOT APPEAR ON ALL DOCUMENTS OR PLANS.
3.
DAMAGE ON THE CONSTRUCTION SITE CAUSED BY THE CONTRACTOR OR A PARTY TO THE CONTRACTOR
DURING THE DEMOLITION OF CONSTRUCTION PHASE SHALL BE REPAIRED PRIOR TO CONTRACT DATE OF
SUBSTANTIAL COMPLETION AT NO ADDITIONAL EXPENSE TO THE OWNER.
4.
ALL EXISTING REMOVED EQUIPMENT WILL BE STOCKPILED AT THE SITE UNTIL AN INSPECTION BY THE OWNER'S
REPRESENTATIVE WILL DETERMINE WHAT WILL BE SALVAGED, ALL EQUIPMENT NOT SALVAGED OR RETAINED BY
THE CONTRACTOR FOR REUSE WILL BE HAULED OFF THE SITE BY THIS CONTRACTOR. THE STOCK PILE AREA
WILL BE DETERMINED BY THE ARCHITECT AND OWNER. REFER TO ELECTRICAL SPECIFICATIONS SECTION 16060
- ''ELECTRICAL DEMOLITION FOR REMODELING''.
5.
VERIFY THAT ALL ELECTRICAL EQUIPMENT TO REMAIN OR BE RELOCATED AND REUSED ARE IN WORKING ORDER
PRIOR TO ANY DEMOLITION WORK. IF THE EXISTING MATERIAL IS FOUND TO BE INOPERABLE, CONTRACTOR
SHALL INFORM THE OWNER ONCE ANY DEMOLITION WORK HAS BEGUN, ANY INOPERABLE OR DAMAGED
MATERIAL SHALL BE REPAIRED OR REPLACED AT THE CONTRACTOR'S EXPENSE.
ARCHITECTURE
609 North Dustin
Farmington, NM 87401
Phone: (505) 326-6442
VALLEY #1
FIRE STATION
KIRTLAND, NM
ELECTRICAL LEGEND
Checked: Date:
Drawn:
AW
JL
12-09-15
Filename:
1526.rvt
Project:
1526
Sheet:
E1
Of: 8
KEYED NOTES
26.01
26.17
26.20
EXISTING CORD REEL TO REMAIN.
EXISTING TELEPHONE DEMARC AND HANDSET. EQUIPMENT TO REMAIN, LOCATION NOTED FOR REFERENCE.
CEILING MOUNTED PROJECTOR, TO BE RELOCATED TO NEW TRAINING ROOM BY OWNER. REMOVE EXISTING OUTLET, AND
PROVIDE NEW POWER AND DATA FLUSH WITH NEW CEILING.
XO5
EXISTING EQUIPMENT LEGEND
XO
XRT
TYPE
XO
26.01
TYP. OF 5
X
X
X
X
X
XO2
XO2
XO2
XO2
XO2
XO
XO
XUH
XO
XO
XUH
XF
XO2
XO
XO2
XO2
PANEL C (XO)
X
GDO1
XEV1
X
GDO1
X
GDO1
XR
GDO2
X
GDO1
XEV2
XO2
XO XO
XO
XO
X
XO2
XO
XO2
XO2
XO2
XO
XO
XO
XO2
XO
XO
XO
XO
XBH
XCU
XEF
XEV
XEV1
XEV2
XF
XHT
XRT
XUH
XWH1
XWH2
CMP
DRY
GDO1
GDO2
GR
HOTSY
ICE
SCBA
WASH
BASEBOARD HEATER - TO BE REMOVED
CONDENSING UNIT - TO BE REMOVED
CEILING EXHAUSTER - TO BE REMOVED
EVAPORATOR - TO BE REMOVED
EVAP COOLER - TO REMAIN
EVAP COOLER - TO BE REMOVED
FURNACE - TO BE REMOVED
WALL HEATER - TO BE RELOCATED
RADIANT TUBE HEATER - TO BE REMOVED
UNIT HEATER - TO BE REMOVED
WATER HEATER - TO BE REMOVED
WATER HEATER - TO BE REMOVED
AIR COMPRESSOR - TO REMAIN
DRYER - TO BE RELOCATED
GARAGE DOOR OPENER, 1/3 HP - TO REMAIN
GARAGE DOOR OPENER,1/3 HP - TO BE RELOCATED
BENCH GRINDER, 1/2 HP - TO REMAIN
PRESSURE WASHER, GAS - TO BE RELOCATED
ICE MACHINE - TO BE RELOCATED
SCUBA (AIR COMPRESSOR), 10 HP - TO REMAIN
WASHER - TO BE RELOCATED
EXISTING LIGHTING FIXTURE LEGEND
S
TYPE
XO1
XO2
XO3
XO4
XO5
XO6
SECOND FLOOR ELECTRICAL DEMO PLAN
2
DESCRIPTION
DESCRIPTION
MOUNTING
1'X4' - TO BE REMOVED
1'X4' - TO BE REMOVED
TROFFER - TO BE REMOVED
VANITY FIXTURE - TO BE REMOVED
WALLPACK - TO BE REPLACED IN SAME LOCATION
"CAN" LIGHT - TO BE REMOVED
SUSPENDED
SURFACE
RECESSED
WALL
WALL
RECESSED
1/8" = 1'-0"
METER (XO)
XO
GR
WASH
XRR
XO2
ICE
DRY
SCBA
26.17
XRR
XO1
XO1
XO1
XO1
XO2
XO
X
S
XO6
XO1
XO1
XO
XO6
XO3
G
XO3
XO1
XO
XO
XO1
XO3
XO4
G
XO
XO1
XO3
XBH
G
XO1
XO1
XO1
XO
XEF
XHT
XO3
XWH2
XO4
XO
XO3
HOTSY
XRR
XO
X
XO1
XRR
XO6
XEF
3 3X
XRR
XO1
XO3
XO1
XO
XO1
XO
XO
XO1
XO
X
XCU
XO1
XO
XBH
XO
CMP
XO
XO5
XO
XO5
XWH1
MDP (XO)
ATS (XO)
PANEL G (XO)
PANEL B (XO)
PANEL A (XO)
XO
XO
XO
XEV
TO DOOR OPENER
XO1
TO DOOR OPENER
XO1
TO DOOR OPENER
XO1
TO DOOR OPENER
XO1
XO5
XO3
XO3
XO3
XO1
XO
XO1
26.20
XO3
XO3
XO3
XO3
XO3
XO3
XO
XO2
XO1
TO DOOR OPENER
XO1
XO6
XO1
XO1
XO1
XO1
XO1
XO1
XO
XO1
XO
PANEL D (XO)
XCU
XO
XO
XO3
XO4
XO2
XO5
XO
XO
XO5
XO
XO
XO
XO 3
XO
XO3
XO5
XO5
RODAHL & HUMMELL
ARCHITECTURE, P.C.
XO
XO5
ARCHITECTURE
1
FIRST FLOOR ELECTRICAL DEMO PLAN
1/8" = 1'-0"
609 North Dustin
Farmington, NM 87401
Phone: (505) 326-6442
VALLEY #1
FIRE STATION
KIRTLAND, NM
ELECTRICAL DEMO PLANS
Checked: Date:
Drawn:
AW
JL
12-09-15
Filename:
1526.rvt
Project:
1526
Sheet:
E2
Of: 8
GENERAL ELECTRICAL PLAN NOTES
WX
A1 - 11
CX4
G2 - 29
26.02
R.R.
206
G2 - 31
G1 - 9
HALL
205
CX3
X
X
APPARATUS BAY
211
A1 - 12
G1 - 11
(PART)
A1 - 15
X
G1 - 15
R.R.
207
A1 - 13
26.16
RP1
G2 - 19
G1 - 16
26.16
26.18
AC4
26.19
G2 - 26
VEST.
208
GDO1
X
XEV1
STORAGE
212
GDO1
X
26.18
26.18
GDO1
X
G1 - 12
G
GDO1
X
26.18
26.18
SLEEPING
202
F2
G1 - 13
G2 - 18
G2 - 21
G1 - 10
UH1
G
X
26.04
AC3
SLEEPING
203
G1 - 11
(PART)
RP2
26.01
26.02
AC2
X
G
X
KEYED NOTES
SLEEPING
204
(PART, WITH LGTS)
26.01
TYP. OF 5
WHERE PHONE/DATA OUTLETS ARE SHOWN, PROVIDE CONDUIT AND BACKBOX ONLY. CABLE IS BY OWNER.
G
1
LAUNDRY
209
G1 - 20
26.20
G1 - 17
EXISTING CORD REEL TO REMAIN.
PROVIDE EMPTY 1" CONDUIT FROM CO (CO2 SENSOR CONTROLLER) TO CO2 SENSORS, MOTORIZED DAMPERS (M/D), AND
WALL EXHAUSTER (WX), FOR CONTROLS CABLE BY OTHERS.
PROVIDE ONE RECEPTACLE AT 24" AFF FOR GAS RANGE, ONE RECEPTACLE IN CABINET ABOVE FOR FIRE SUPPRESSION
SYSTEM (SEE DETAIL), AND ONE RECEPTACLE IN CABINET ABOVE FOR MICROWAVE. FOR RECEPTACLES MARKED AS GFCI
BUT NOT IN READILY ACCESSIBLE LOCATION, PROVIDE GFCI BREAKER AT PANEL.
PROVIDE PHONE LINE AND BELL ON BAY CEILING TO NOTIFY OCCUPANTS WHEN PHONE IS RINGING.
PROVIDE CONTACTOR AT BACK OF OVERHEAD DOOR TRACK TO INDICATE WHEN DOOR IS FULLY OPEN. PROVIDE LED
RED/GREEN SIGNAL LIGHT ADJACENT TO DOOR AT 6' AFF. INDICATOR TO CHANGE TO GREEN ONLY WHEN DOOR IS FULLY
OPEN, AND REMAIN RED OTHERWISE.
PROVIDE POWER TO WALL MOUNTED CONTROL PANEL SUPPLIED WITH SEWAGE EJECTOR. CONNECT POWER FROM
CONTROLLER TO TWO INTEGRAL PUMPS, AND PROVIDE AN ADDITIONAL CONDUIT FOR CONTROLS FROM FLOAT SWITCHES
IN TANK TO CONTROLLER.
CEILING MOUNTED PROJECTOR, TO BE RELOCATED TO NEW TRAINING ROOM BY OWNER. REMOVE EXISTING OUTLET, AND
PROVIDE NEW POWER AND DATA FLUSH WITH NEW CEILING.
G2 - 27
AC5
SLEEPING
201
G2 - 20
G2 - 23
OFFICE
200 G2 - 25
26.02
G1 - 18
G2 - 24
M/D
G2 - 22
G1 - 14
2
A1 - 14
GDO2
G1 - 19
AC6
XRR
26.18
BAY ADDITION
210
26.02
M/D
SECOND FLOOR POWER PLAN
1
1/8" = 1'-0"
G
XRR
HOTSY
WP
A2 - 1,3
26.02
X
STORAGE
109
G1 - 3
WP
26.02
WH1
G1 - 7
WASH
A1 - 17,19
CO
26.02
XRR
XRR
G1 - 25
CO
CO
DRY
WH2
A2 - 2,4
X
A2 - 6,8
GEAR ADDITION
108
A1 - 1
CO
26.02
SCBA
PANEL A1
PANEL G1
ATS
PANEL A2
TRANS. A
G2 - 1
G2 - 2
G1 - 8
DAY ROOM
105
26.02
CO
GR
A2 - 9,11
G2 - 6
G
X
APPARATUS BAY
107
G2 - 7
G2 - 8
G
A1 - 16
XHT
G G
G2 - 5
A1 - 5
OFFICE
110
G2 - 9
G G GG
XRR
CMP
MDP
X
A1 - 3
26.04
G
KITCHEN
104
G1 - 1
G2 - 3
G2 - 10
G2 - 11
G1 - 4
SE
G2 - 4
AC1
PANEL G2
26.18
26.18
CX2
G2 - 28
(PART, WITH LGTS)
26.18
A1 - 6
R.R.
103
G
A1 - 21,23
CX1
HALL
102
CU2
R.R.
101
A1 - 24,26
G2 - 12
CU1
A1 - 4
G
AC7
26.19
G
WP
WP
2
WP
WP
G2 - 15
A1 - 7
A1 - 8
A1 - 9
A1 - 2
G2 - 14
BAY ADDITION
106
G2 - 17
TRAINING
100
F1
M/D
G1 - 5
RODAHL & HUMMELL
ARCHITECTURE, P.C.
M/D
26.20
26.18
2
G1 - 6
2
G1 - 2
26.18
G
G
CONF.
111
ICE
G
XRR
WP
G2 - 16
A1 - 10
ARCHITECTURE
2
609 North Dustin
Farmington, NM 87401
Phone: (505) 326-6442
VALLEY #1
FIRE STATION
KIRTLAND, NM
2
FIRST FLOOR POWER PLAN
1/8" = 1'-0"
Drawn:
AW
POWER PLANS
Checked: Date:
JL
12-09-15
Filename:
1526.rvt
Project:
1526
Sheet:
E3
Of: 8
GENERAL LIGHTING PLAN NOTES
1
2
W2
O-W1
E
L
R.R.
206
L
G2 - 31
S
R.R.
207
L
O-C
c
O-W2
KEYED NOTES
26.22
TYPE H FIXTURES INCLUDE AN INTEGRAL OCCUPANCY/DAYLIGHT SENSOR, AND WALL SWITCHES FUNCTION AS A MANUAL
OVERRIDE TO OFF. TYPE HE FIXTURES ARE UNSWITCHED, AND HAVE NO SENSOR.
SLEEPING
T1
203
T1, c
A
f
SLEEPING
204
T1, g
T1E, c
HALL
205
L
APPARATUS BAY
211
A, f
g
O-W2
S
O-C
E
c
A
D
G1 - 26
D
W2
SUPPLY EXIT SIGNS FROM NEAREST CIRCUIT SERVING SAME SPACE (UNSWITCHED).
CONTROL DEVICES CONTROL ALL FIXTURES IN ROOM, UNLESS OTHERWISE NOTED WITH A LOWER CASE SWITCH LETTER.
A
L
E
T1E
208
STORAGE
L
212
SLEEPING
T1
202
T1E, c
LIGHTING FIXTURE SCHEDULE
D
O-W1
O-W1
A
LAUNDRY
L209
O-C
TYPE
DESCRIPTION
A
ASSYMETRIC UP/DOWN WALL FIXTURE,
DIMMABLE
EXIT SIGN, RED ON WHITE
HIGH BAY, WIDE DISTRIBUTION, WITH
INTEGRAL OCCUPANCY SENSOR
HIGH BAY, WIDE DISTRIBUTION, WITH EM
BATTERY PACK
4' LINEAR LENSED
SQUARE SHOWER LIGHT
SQUARE LIGHT, WET LOCATION, WITH EM
BATTERY PACK
d
L
OFFICE
T1,
d
200
SLEEPING
T1
201
T1, d
E
H
D
O-C
d
HE
A
L
S
SE
SIGNAL
T1
TROFFER, 2'X2' SURFACE, <5" DEEP
T1E
TROFFER, 2'X2' SURFACE, <5" DEEP, WITH
EM BATTERY PACK
T2
TROFFER, 2'X4'
T2E
TROFFER, 2'X4', WITH EM BATTERY PACK
W2
WALLPACK WITH COLD WEATHER EM
BATTERY
W4
WALLPACK
BAY ADDITION
210
MOUNTING
HEIGHT
LAMP
WALL
MAKE
MODEL
ELECT.
CCT
CRI LUMENS
OPTIC
120 V/1-37 VA
40K
MIN 80
2,500
ASSYMETRIC
LED
FINELITE
S17-LED-VCF-PF-2-SO-40K-SC-120
N/A
40K
N/A
MIN 80
N/A
16,000
N/A
WIDE
40K
MIN 80
16,000
WIDE
UNIVERSAL
SUSPENDED
ABOVE DOOR
18' AFF
LED
LED
COMPASS
COLUMBIA
SUSPENDED
18' AFF
LED
COLUMBIA
CER
120 V/1-3 VA
LLHV4-40M-WST-EU-SFA-WG-OS1360 +
120 V/1-155 VA
LHVQM5
LLHV4-40M-WST-EU-SFA-WG-ELL14 + LHVQM5 120 V/1-155 VA
SURFACE
SURFACE
SURFACE
CEILING
CEILING
CEILING
LED
LED
LED
COLUMBIA
KENALL
KENALL
LCL4-40LW-EU
MS11FL-PP-MW-18L40K-SCC-DV-R80
MS11FL-PP-MW-18L40K-SCC-DV-R80-LEL
120 V/1-25 VA
120 V/1-18 VA
120 V/1-18 VA
40K
40K
40K
MIN 80
MIN 80
MIN 80
2,500
1,000
1,000
N/A
N/A
N/A
WALL
SURFACE
SURFACE
CEILING
CEILING
LED
LED
LED
FINELITE
COLUMBIA
COLUMBIA
S17-LED-VCF-PF-2-SO-40K-SC-120
LCAT22-40ML-SM-EDU
LCAT22-40ML-SM-EDU-ELL14
120 V/1-37 VA
120 V/1-30 VA
120 V/1-30 VA
40K
40K
MIN 80
MIN 80
3,200
3,200
ASSYMETRIC
N/A
N/A
RECESSED - GRID
RECESSED - GRID
WALL
CEILING
CEILING
MATCH EXISTING
LED
LED
LED
COLUMBIA
COLUMBIA
HUBBELL
LCAT24-40HL-G-EDU
LCAT24-40HL-G-EDU-ELL14
LNC2-12LU-4K-2-2-PC(120)-BBU
120 V/1-47 VA
120 V/1-47 VA
120 V/1-29 VA
40K
40K
40K
MIN 80
MIN 80
-
5,500
5,500
2,400
N/A
N/A
TYPE 2
WALL
MATCH EXISTING
LED
HUBBELL
LNC2-12LU-4K-4-2-PC(120)-BBU
120 V/1-29 VA
40K
-
2,400
TYPE 4
CONTROL DEVICE SCHEDULE
TYPE
Dimmer
O-C
O-W1
O-W2
RC
2
DESCRIPTION
0-10V WALL DIMMER WITH ON/OFF TOGGLE
CEILING OCCUPANCY SENSOR
WALL OCCUPANCY SENSOR
WALL OCCUPANCY SENSOR
LOCAL ROOM CONTROLLER FOR
COORDINATION OF MULTIPLE INPUT DEVICES
MOUNTING
HEIGHT
SENSING TECH
RELAYS
SWITCH(ES)
WALL
CEILING
WALL
WALL
ABOVE CEILING
SWITCH HEIGHT
N/A
SWITCH HEIGHT
SWITCH HEIGHT
N/A
N/A
DUAL
DUAL
DUAL
N/A
PER PLAN
1
1
2
PER PLAN
INTEGRAL
PROVIDE REMOTE PER PLAN
1 - INTEGRAL
2 - INTEGRAL
PER PLAN
NOTES
SECOND RELAY CONTROLS FAN
LOCATE ABOVE NEAREST ACCESSIBLE CEILING
SECOND FLOOR LIGHTING PLAN
1/8" = 1'-0"
MDP
L, e
L, e
LOW CEILING
E
G1 - 21
PANEL A1
PANEL G1
TRANS. A
ATS
L
STORAGE
109
L
H, c
HE
H, c
O-W1
26.22
TYP.
H, d
T1
G1 - 23
H, d
T1E
T1
DAY ROOM
105
c
d
RC
HE
26.22
TYP.
APPARATUS BAY
107
E
PANEL A2
G1 - 22
3 3
L, e
3
O-W1
e
E
GEAR ADDITION
L, e
108
O-C
T1
T1
T1
T1
T1
T1
T1
3
OFFICE O-W1
110
KITCHEN
104
T1
H, c
H, c
H, c
H, d
H, d
O-C
H, d
T1
T1E
T1
G2 - 28
T1
PANEL G2
CONF.
111
O-W1
R.R.
T1
103
T1
c
d
3
3
W4
W4
W4
HALL
O-W1
T2E
R.R.
T1
101
O-W1
G1 - 24
W4
D D
BAY ADDITION
106
H, d
a
b
T2, a
T2, a
T2, a
RC
TRAINING
O-C
100
HE
T2, a
T2, a
T2, a
RODAHL & HUMMELL
ARCHITECTURE, P.C.
E
T2E, b
W4
T2, b
T2, b
ARCHITECTURE
609 North Dustin
Farmington, NM 87401
Phone: (505) 326-6442
E
SE
VALLEY #1
FIRE STATION
KIRTLAND, NM
1
FIRST FLOOR LIGHTING PLAN
1/8" = 1'-0"
LIGHTING PLANS
Checked: Date:
Drawn:
AW
JL
12-09-15
Filename:
1526.rvt
Project:
1526
Sheet:
E4
Of: 8
KEYED NOTES
26.03
26.09
26.10
NEW PAD MOUNTED UTILITY
TRANSFORMER TO REPLACE
EXISTING POLE MOUNTED
26.11
26.12
26.13
26.14
EXISTING OVERHEAD POWER
26.15
26.21
26.23
EXISTING PARKING LOT ISLAND CONTAINING LIGHT POLE, SUBFEED PANEL "P" ON POST, AND FIRE HYDRANT, ALL TO BE
DEMOLISHED IN THIS PROJECT. PANEL "F" ON FIRE TOWER IS TO REMAIN, AND IS CURRENTLY FED THROUGH PANEL ON
ISLAND. DISCONNECT ALL BRANCH CIRCUITS AND REMOVE PANEL. SPLICE PANEL "F" FEEDER TO PANEL "P" FEEDER, IN
HEAVY DUTY TRAFFIC RATED GRADE BOX.
PROVIDE 1" CONDUIT FROM GENERATOR TO CABLE ENTRY AT RADIO ROOM, FOR GENERATOR ALARM ANNUNCIATION.
PROVIDE #2 CU GROUND RING AROUND NEW RADIO ROOM AT 30" DEPTH. ALL CONNECTIONS TO GROUND RING TO BE #2
CU.
PROVIDE 8' COPPER CLAD STEEL GROUND ROD AT EIGHT LOCATIONS ON GROUND RING AS SHOWN.
TIE NEW GROUND RING TO EXISTING GROUND RING AROUND EXISTING RADIO TOWER.
ICE BRIDGE BY OWNER, SUPPORTED ON SIX 3" STEEL PIPES BY ARCHITECT. TIE BRIDGE SUPPORTS INTO GROUND RING.
NEAR ICE BRIDGE CABLE ENTRY INTO RADIO ROOM, PROVIDE #2 CU IN CONDUIT FROM GROUND RING UP 10' ON SIDE OF
BUILDING. CAP AND LABEL.
EXTERIOR DISCONNECT PREINSTALLED ON RADIO BUILDING. TIE GROUND BUS TO NEW GROUND RING.
POWER AND GENERATOR CONTROLS TO ATS, PLUS THREE 120V CIRCUITS FOR GENERATOR ACCESSORIES. SEE PANEL G1
SCHEDULE.
LOCATION FOR GENERATOR REMOTE EMERGENCY STOP SWITCH. COORDINATE EXACT LOCATION WITH OWNER. PROVIDE
PERMANENT WEATHERPROOF RED LABEL.
TO
ICE
ERV
AD S
RHE
OVE
EX.
ICE
VED
SERV
EMO
UND
BE R
RGRO
UNDE
NEW
NEW
ADDITION
NEW ADDITION
EXISTING
BUILDING
EXISTING FIRE TOWER
PANEL F
IN
TO REMA
EX. UGE
XO
EX. UGE TO REMAIN
PANEL P
26.03
26.23
NG
STI TE
I
X
E CRE
N
CO ANK
T
26.11
26.10
26.09
26.21
26.13
GENERATOR
PROPANE
RADIO
TOWER
RODAHL & HUMMELL
ARCHITECTURE, P.C.
NEW RADIO
BUILDING
26.12
26.14
26.15
ARCHITECTURE
609 North Dustin
Farmington, NM 87401
Phone: (505) 326-6442
VALLEY #1
FIRE STATION
KIRTLAND, NM
1
SITE ELECTRICAL PLAN
1" = 10'-0"
ELECTRICAL SITE PLAN
Checked: Date:
Drawn:
AW
JL
12-09-15
Filename:
1526.rvt
Project:
1526
Sheet:
E5
Of: 8
EXISTING ELECTRICAL RISER
RISER LEGEND
FIRE
TOWER
MAIN BUILDING
NEW OR MODIFIED IN THIS PROJECT
3
A.T.S.
EXISTING TO REMAIN
EXISTING TO BE DEMOLISHED
EMRG
NORM
PANEL C
1
MLO - 120/240V
TO EXISTING
POLE MOUNTED
UTILITY TRANSFORMER
RISER GENERAL NOTES
4
MDP
M
1.
ALL UNDERGROUND CONDUIT TO BE SCHEDULE 80 PVC.
2.
ALL EXPOSED EXTERIOR CONDUIT TO BE RIGID STEEL.
3.
THIS DIAGRAM IS SCHEMATIC, AND NOT INTENDED TO SPECIFY CONDUIT ROUTING OR
FEED SIDE OF PANELS.
4.
WHERE ALUMINUM FEEDERS ARE SPECIFIED, VERIFY THAT ASSOCIATED PANELS ARE
RATED FOR ALUMINUM CONDUCTORS.
5.
TERMINAL SCREWS ON ALL ALUMINUM FEEDERS SHALL BE TORQUED TO CONDUCTOR
MANUFACTURER'S SPECIFICATIONS AT CONSTRUCTION, AND RE-TORQUED 90 DAYS
AFTER COMMISSIONING.
MCB
PANEL P
6
RISER KEYED NOTES
MCB - 120/240V
MCB - 120/240V
NEUT BUS
MLO - 120/240V
GRND BUS
MLO - 120/240V
EXISTING
GENERATOR
MLO - 120/240V
2
MLO - 120/240V
5
PANEL F
1.
REMOVE EXISTING MDP, AND PROVIDE NEW MDP IN NEW LOCATION. ADJACENT UTILITY
METER MUST BE RELOCATED, COORDINATE WITH UTILITY.
2.
REMOVE EXISTING PROPANE GENERATOR, AND REPLACE WITH NEW IN SAME
LOCATION. PROPANE TANK TO REMAIN AND BE REUSED.
3.
REMOVE AUTOMATIC TRANSFER SWITCH AND RETURN TO OWNER. INSTALL NEW
AUTOMATIC TRANSFER SWITCH, PURCHASED BY OWNER. SWITCH SHALL BE 300 AMP,
3 POLE, SOLID NEUTRAL.
4.
REMOVE ALL PANELS INSIDE MAIN BUILDING.
5.
REMOVE PANEL P, LOCATED ON PARKING ISLAND TO BE REMOVED. SPLICE PANEL P
FEEDER TO PANEL F FEEDER IN HEAVY DUTY TRAFFIC RATED GRADE BOX.
6.
PANEL ON EXTERIOR OF FIRE TOWER TO REMAIN.
7.
PROVIDE NEW PANEL, SEE PANEL SCHEDULE FOR DETAILS.
8.
NEW RADIO ROOM BUILDING IS A COMPLETE BUILDING BEING MOVED HERE FROM
ANOTHER SITE. EXTERIOR DISCONNECT AND BRANCH PANEL ARE ALREADY
INSTALLED, BUT DISCONNECT HAS NO FUSES. PROVIDE 200A FUSES, POWER SUPPLY
FROM MAIN BUILDING, AND GROUNDING. NO WORK IN INTERIOR OF BUILDING.
9.
NEW GROUNDING RING SURROUNDING RADIO BUILDING. SEE SITE PLAN FOR DETAIL
ON SIZE, QUANTITY OF RODS, AND CONNECTIONS TO OTHER ELEMENTS.
10
4
PANEL A
4
PANEL G
PANEL B
4
PANEL D
4
#4 CU + #4 CU GROUND
#2 CU + #2 CU GROUND
NEW ELECTRICAL RISER
10. EXISTING PANEL "D" FEEDS CURRENT RADIO ROOM (INSIDE MAIN BUILDING), WHICH
MUST REMAIN OPERATIONAL DURING CONSTRUCTION. WHILE BUILDING SERVICE IS
DOWN, FEED PANEL D FROM PORTABLE GENERATOR PROVIDED BY OWNER.
COORDINATE DISCONNECTION AND RECONNECTION WITH OWNER IN ADVANCE.
NEW RADIO BLDG
FIRE
TOWER
MAIN BUILDING
11. PROVIDE A 45 KVA TRANSFORMER (208 3 PHASE TO 240 CENTER TAP DELTA), TO
SERVE EXISTING OWNER EQUIPMENT THAT REQUIRES 240V. PLEASE NOTE THIS
TRANSFORMER IS UNCOMMON AND MAY REQUIRE SIGNIFICANT LEAD TIME.
12. PROVIDE PERMANENT ORANGE LABEL ON THIS PANEL INDICATING THAT SOURCE IS
CENTER TAPPED DELTA, AND PHASE B IS THE HIGH LEG.
13. EXCLUDE COST OF NEW GENERATOR AND NEW ATS. THESE WILL BE PURCHASED BY
OWNER AND INSTALLED BY ELECTRICAL CONTRACTOR.
A.T.S.
3W + G
EMRG
4W + G
14. INSTALL NEW GENERATOR (PURCHASED BY OWNER). GENERATOR SHALL HAVE A
MINIMUM RATING OF THE LOAD SHOWN FOR PANEL G1 PER PANEL SCHEDULES, AFTER
THE APPROPRIATE DE-RATING FACTOR IS APPLIED FOR SITE ELEVATION (TYPICALLY
AROUND 20%). GENERATOR SHALL INCLUDE THE FOLLOWING OPTIONS:
NORM
3 POLE
3
8
14.1.
14.2.
14.3.
14.4.
14.5.
14.6.
14.7.
13
1
MDP
TRANS.
A
208/3 240/3
45 kVA
M
MCB
1/0 CU
14
1/0 CU
GRND BUS
1/0 CU
NEUT BUS
NEW
GENERATOR
PANEL R
PANEL A1
100 KVA
120/208V
7
#4 CU
9
PANEL A2
#4 CU
12
7
PANEL F
MCB - 208V / 1PH
13
6
MLO - 208V / 3PH
MLO - 208V / 1PH
NEUT BUS
TVSS
MCB - 240V / 3PH
TO NEW PAD
MOUNTED UTILITY
TRANSFORMER
MLO - 208V / 3PH
GRND BUS
11
MLO - 208V / 3PH
200A
STANDARD ENCLOSURE
REMOTE ANNUNCIATION (LOCATED IN NEW RADIO BUILDING)
ENGINE BLOCK HEATER
BATTERY WARMER
10A BATTERY CHARGER
MAIN LINE CIRCUIT BREAKER
NEUTRAL NOT BONDED TO GROUND IN GEN SET
PANEL G1
PANEL G2
7
7
5
TO STRUCTURAL STEEL
TO UFER GROUND
#2 CU
20' LOOP 30" BELOW GRADE
20'-0"
20
'-0
"
"
'-0
20
#4 CU + #4 CU GROUND
#2 CU + #2 CU GROUND
(3) 3/4" X 10' COPPER CLAD
STEEL GROUND RODS
RODAHL & HUMMELL
ARCHITECTURE, P.C.
FEEDER SCHEDULE
TO
MDP
ATS
PANEL A1
TRANS. A
PANEL A2
PANEL G1 (VIA ATS)
PANEL G2
PANEL F
RADIO BUILDING
FROM
UTILITY
GENERATOR
MDP
A1
TRANS. A
MDP
G1
G1
G1
REQ.
VOLTAGE POLES AMPACITY
208 V
3
500 A
208 V
3
300 A
208 V
3
300 A
208 V
3
150 A
240 V
3
125 A
208 V
3
300 A
208 V
3
100 A
208 V
2
100 A
208 V
2
200 A
CONDUCTORS
2 Set(s) of [ (4) 350 MCM AL + NO GRND., 3 IN. CONDUIT ]
1 Set(s) of [ (3) 500 MCM AL + # 2 AL GRND., 3 IN. CONDUIT ]
1 Set(s) of [ (4) 500 MCM AL + # 2 AL GRND., 3 IN. CONDUIT ]
1 Set(s) of [ (4) 250 MCM AL + # 4 AL GRND., 2.5 IN. CONDUIT ]
1 Set(s) of [ (4) # 2/0 AL + # 4 AL GRND., 2 IN. CONDUIT ]
1 Set(s) of [ (4) 500 MCM AL + # 2 AL GRND., 3 IN. CONDUIT ]
1 Set(s) of [ (4) # 1 AL + # 6 AL GRND., 1.5 IN. CONDUIT ]
EXISTING, RECONNECT ONLY. SEE RISER.
1 Set(s) of [ (3) 500 MCM CU + # 1 CU GRND., 3 IN. CONDUIT ] - UPSIZED FOR VOLTAGE DROP
ARCHITECTURE
609 North Dustin
Farmington, NM 87401
Phone: (505) 326-6442
VALLEY #1
FIRE STATION
KIRTLAND, NM
ELECTRICAL RISER
Checked: Date:
Drawn:
AW
JL
12-09-15
Filename:
1526.rvt
Project:
1526
Sheet:
E6
Of: 8
NEW
Location:
Supply From:
Mounting:
Enclosure:
PANEL A1
Bay West
MDP
Surface
Type 1
NEW
Volts: 120/208 Wye
Phases: 3
Wires: 4
A.I.C. Rating: 22,000
Mains Type: MLO
Mains Rating: 300 A
Location:
Supply From:
Mounting:
Enclosure:
Notes:
Bay West
TRANS. A
Surface
Type 1
NEW
Volts: 120/240 Delta Center
Phases: 3
Wires: 4
A.I.C. Rating: 22,000
Mains Type: MCB
Mains Rating: 125 A
Location:
Supply From:
Mounting:
Enclosure:
Notes:
PROVIDE PERMANENT ORANGE LABEL INDICATING THAT SOURCE IS 240V DELTA AND PHASE B IS HIGH LEG.
A
CKT
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
PANEL A2
Circuit Description
REC- Bay West
REC- Bay South
REC- Office 110
REC- Ext East 1
REC- Ext East 3
REC- Upper Bay South
REC- Bay Ceiling N
XEV1
WASH
-CU2
--
Trip
20
20
20
20
20
20
20
25
20
-45
--
Poles
1
1
1
1
1
1
1
1
2
-2
--
720
B
C
Poles
1
1
720
1
1
1
720
1
1
1
12840
3
--2760
2
--
720
900
720
720
180
180
180
180
540
1080
180
1920
936
1080
1080
12240
3240
11640
3240
2760
Total Load:
19140 VA
19716 VA
Total Amps:
160 A
165 A
Connected Load Demand Factor
13920 VA
100.00%
7740 VA
100.00%
11040 VA
125.00%
28776 VA
100.00%
Load Classification
HVAC
Receptacle
Motor - Largest
Owner Equip.
A
22620 VA
189 A
Demand
13920 VA
7740 VA
13800 VA
28776 VA
Trip
20
20
20
20
20
20
20
20
150
--40
--
Circuit Description
REC- Bay North
REC- Bay East
REC- Conf 111
REC- Ext East 2
REC- Ext East 4
REC- Bay Ceiling S
REC- Bay 106 ceiling
GR
TRANS. A
--CU1
--
CKT
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
CKT
1
3
5
7
9
11
Circuit Description
CMP
-Space
Space
SCBA
--
Load Classification
Motor - Largest
Owner Equip.
B
Trip Poles
2640 4080
40
2
2640 4080
----0
6120
--5520
0
50
2
--Total Load:
12840 VA
12240 VA
Total Amps:
107 A
102 A
Connected Load Demand Factor
11040 VA
125.00%
25680 VA
100.00%
PANEL MDP
EXTERIOR, WEST
UTILITY
Surface
Type 3R
Volts: 120/208 Wye
Phases: 3
Wires: 4
Notes:
C
0
A
6120
5520
0
11640 VA
97 A
Demand
13800 VA
25680 VA
Poles
2
-2
----
Trip
40
-60
----
A.I.C. Rating: 22,000
Mains Type: MCB
Mains Rating: 500 A
Circuit Description
HOTSY
-DRY
-Space
Space
CKT
2
4
6
8
10
12
Panel Totals
CKT
Circuit Description
1
PANEL A1
3
-5
-7
9
11
Load Classification
HVAC
Commercial Kitchen Equipment
Lighting
Motor
Other
Receptacle
Motor - Largest
Owner Equip.
Other - Continuous
Refrigeration
Total Conn. Load: 36720 VA
Total Est. Demand: 39480 VA
Total Conn.: 88 A
Total Est. Demand: 95 A
Trip
300
---
B
C
Poles
Poles
18881 15826
3
3
19537 31978
--22381 31286
---
Total Load:
34707 VA
51516 VA
Total Amps:
289 A
451 A
Connected Load Demand Factor
28654 VA
100.00%
1400 VA
100.00%
4768 VA
125.00%
2616 VA
100.00%
33404 VA
100.00%
23396 VA
71.37%
11040 VA
125.00%
34368 VA
100.00%
1500 VA
125.00%
1000 VA
100.00%
53667 VA
469 A
Demand
28654 VA
1400 VA
5960 VA
2616 VA
33404 VA
16698 VA
13800 VA
34368 VA
1875 VA
1000 VA
Trip
300
---
Circuit Description
PANEL G1 (VIA ATS)
---
CKT
2
4
6
8
10
12
Panel Totals
Total Conn. Load: 142146 VA
Total Est. Demand: 139775 VA
Total Conn.: 395 A
Total Est. Demand: 388 A
Panel Totals
Total Conn. Load: 61476 VA
Total Est. Demand: 64236 VA
Total Conn.: 171 A
Total Est. Demand: 178 A
NEW
Location:
Supply From:
Mounting:
Enclosure:
PANEL G1
Bay West
MDP
Surface
Type 1
PANEL G2
Volts: 120/208 Wye
Phases: 3
Wires: 4
A.I.C. Rating: 22,000
Mains Type: MCB
Mains Rating: 300 A
Location:
Supply From:
Mounting:
Enclosure:
Notes:
EXISTING
Volts: 120/208 Wye
Phases: 3
Wires: 4
A.I.C. Rating: 22,000
Mains Type: MLO
Mains Rating: 100 A
Location:
Supply From:
Mounting:
Enclosure:
Notes:
* Connect shunt trip breaker serving gas range to ansul system above. See detail.
A
CKT
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
43
45
47
49
51
Training, Hall
G1
Recessed
Type 1
Circuit Description
AC1
XHT
F1
WH1
WX
RP1, RP2
(2) GDO1
AC2
AC4
AC6
LGT- 109, 110, 111
LGT- Bay, North
WH2
PANEL G2
--Spare
Spare
Spare
Spare
Spare
Spare
Load Classification
HVAC
Commercial Kitchen Equipment
Lighting
Motor
Other
Receptacle
Owner Equip.
Other - Continuous
Refrigeration
Trip
20
20
20
15
15
20
20
20
20
20
20
20
15
100
--20
20
20
20
20
20
Poles
1
1
1
1
1
1
1
1
1
1
1
1
1
3
--1
1
1
1
1
1
1065
B
C
1065
1500
1440
1488
350
120
1656
150
1200
1728
864
1065
1065
1065
1065
1488
170
1030
1240
350
154
7601
15302
7128
6180
1308
0
1038
0
0
500
0
500
Poles
1
1
100
1
1
1
1728
1
1
1
1065
1
1
1
163
1
1
2
15302
-2
-1200
1
1
1
Trip
20
20
15
20
15
20
20
20
20
20
20
20
20
200
-100
-20
20
20
Circuit Description
AC7
SE
(2) M/D
CO
UH1, (2) M/D
(2) GDO1
GDO2
AC3
AC5
F2
LGT- Bay, South
LGT- Exterior East
LGT- Bay, South Upper Lev
RADIO BUILDING
-PANEL F
-GEN- Battery Charger
GEN- Battery Warmer
GEN- Block Heater
0
0
Total Load:
16237 VA
32517 VA
Total Amps:
135 A
291 A
Connected Load Demand Factor
14734 VA
100.00%
1400 VA
100.00%
4768 VA
125.00%
2616 VA
100.00%
33404 VA
100.00%
15656 VA
81.94%
5592 VA
100.00%
1500 VA
125.00%
1000 VA
100.00%
31779 VA
285 A
Demand
14734 VA
1400 VA
5960 VA
2616 VA
33404 VA
12828 VA
5592 VA
1875 VA
1000 VA
Panel Totals
Total Conn. Load: 80670 VA
Total Est. Demand: 79409 VA
CKT
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
CKT
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
Circuit Description
REC- Dayroom South
ICE
REC- Kitchen South
Garb Disposal
Microwave
Range, Gas
(SHUNT TRIP)*
REC- Train Counter
REC- Train South
REC- 2nd FL, RR, Hall
2nd FL, Dryer
REC- 2nd FL, IT 200
REC- 2nd FL, IT 200
REC- 2nd FL, 202
REC- 2nd FL, 204
LGT- UPPER NORTH
Spare
Spare
Spare
Spare
Spare
Load Classification
HVAC
Commercial Kitchen Equipment
Lighting
Other
Receptacle
Owner Equip.
Refrigeration
A
B
Trip Poles
540
360
20
1
1272 1000
15
1
20
1
1176 1600
20
1
1400
180
20
1
20
1
0
540
--360
360
20
1
20
1
720
360
20
1
180
900
20
1
20
1
900
540
20
1
540
1038
20
1
20
1
869
15
1
0
20
1
20
1
0
20
1
0
20
1
20
1
Total Load:
7605 VA
7230 VA
Total Amps:
65 A
62 A
Connected Load Demand Factor
377 VA
100.00%
1400 VA
100.00%
1561 VA
125.00%
500 VA
100.00%
14936 VA
83.48%
1272 VA
100.00%
1000 VA
100.00%
PANEL F
Fire Tower
G1
Surface
3R
Volts: 120/208 Single
Phases: 1
Wires: 3
A.I.C. Rating: 10,000
Mains Type: MCB
Mains Rating: 100 A
Notes:
THIS PANEL IS EXISTING TO REMAIN, SHOWN FOR REFERENCE ONLY.
C
A
1600
840
180
540
540
900
500
540
Poles
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Trip
20
20
20
20
20
20
20
20
20
20
20
20
20
15
Circuit Description
REC- Dayroom North
Refrigerators
Dishwasher
REC- Kitchen North
Kitchen Ansul
REC- RR, Ext North
REC- Train North
REC- Train East
2nd FL, Washer
REC- 2nd FL, IT 200
REC- 2nd FL, IT 200
REC- 2nd FL, 201
REC- 2nd FL, 203
LGT- TRAIN, DAYROOM
540
0
0
6180 VA
52 A
Demand
377 VA
1400 VA
1951 VA
500 VA
12468 VA
1272 VA
1000 VA
CKT
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
CKT
1
3
5
7
9
11
Circuit Description
Fan
-Controls
Load Classification
Lighting
Motor
Other
Receptacle
Trip
20
-20
Poles
2
-1
588
B
720
588
450
Poles
1
1
Trip
20
20
Circuit Description
Receptacles
Lighting
0
Total Load:
1308 VA
1038 VA
Total Amps:
12 A
10 A
Connected Load Demand Factor
Demand
450 VA
125.00%
563 VA
1176 VA
100.00%
1176 VA
100 VA
100.00%
100 VA
720 VA
100.00%
720 VA
CKT
2
4
6
8
10
12
Panel Totals
Total Conn. Load: 2446 VA
Total Est. Demand: 2559 VA
Total Conn.: 12 A
Total Est. Demand: 12 A
Panel Totals
Total Conn. Load: 21046 VA
Total Est. Demand: 18968 VA
Total Conn.: 58 A
Total Est. Demand: 53 A
Total Conn.: 224 A
Total Est. Demand: 220 A
RODAHL & HUMMELL
ARCHITECTURE, P.C.
ARCHITECTURE
609 North Dustin
Farmington, NM 87401
Phone: (505) 326-6442
VALLEY #1
FIRE STATION
KIRTLAND, NM
Filename:
1526.rvt
Project:
1526
Sheet:
ELECTRICAL PANEL SCHEDULES
E7
Checked: Date:
Drawn:
AW
JL
12-09-15
Of: 8
MECHANICAL EQUIPMENT CONNECTION SCHEDULE
CUMULATIVE
VOLTAGE DROP
2
Segment
Voltage Drop
NM
FAULT
CURRENT
at the secondary of the utility transformer
34800
34800
-
-
20686
1.0%
1.0%
Motor
Contribution
M
f
Conductor
Reactance
(X)
Conductor
Resistance
(R)
Length (L)
1
L-L Volts (E)
3
'C' value
2 MDP
Wire/Bus
0
Conduit Type
Source (Point)
3
Source Isc
Phase
1 SERVICE
Point
Description
SHORT CIRCUIT & VOLTAGE DROP CALCULATIONS
Set(s)
350 AL 16812 208 85
of
0.00006
0.00005
0.000048
0.184 0.845 34800
17476
0.3%
1.3%
Set(s)
250 AL 12122 208 20
of
0.00009
0.000052
0.240 0.806 20686
14092
0.3%
1.5%
0
0.000000
3.257 0.235 17476
2869
0.0%
1.5%
0.000040
0.733 0.577
150
3 PANEL A1
3
2
20686
M
Set(s)
1
500 AL 18755 208 20
of
4 TRANS A -PR
3
3
17476
M
1
5 TRANS A -SC
1
4
14092
TX
0
6 PANEL A2
1
5
2869
M
1
Set(s)
2/0 AL 7186
of
240 10
0.00016
0.000054
0.033 0.968 14092
2777
0.1%
1.7%
7 PANEL G1
3
2
20686
M
1
Set(s)
500 AL 18755 208 20
of
0.00005
0.000048
0.184 0.845
2869
17476
0.3%
1.3%
8 PANEL G2
3
7
17476
M
1
Set(s)
of
1
AL 4645
208 70
0.00025
0.000057
2.193 0.313 20686
5473
1.2%
2.5%
9 PANEL F
1
7
17476
M
1
Set(s)
of
3
CU 4760
208 310 0.00025
0.000059 10.944 0.084 17476
1463
0.7%
2.0%
10 RADIO ROOM
1
7
17476
M
1
Set(s)
500 CU 22185 208 220 0.00003
of
0.000048
6554
1.7%
2.9%
0
0
0
208
0
NOTES TO THE CONTRACTOR:
1.666 0.375 17476
LEGEND:
1. THE DISTANCES SHOWN ARE FOR CALCULATION PURPOSES ONLY. THEY
SHALL NOT BE USED FOR CONTRACTOR TAKEOFFS, NOR FOR BIDDING.
2. CONTRACTOR SHALL NOTIFY ENGINEER OF ANY FIELD CONDITION THAT
RESULTS IN A CHANGE OF 10% OR GREATER CIRCUIT DISTANCE
TYPE
AC1
AC2
AC3
AC4
AC5
AC6
AC7
CO
CU1
CU2
CX1
CX2
CX3
CX4
F1
F2
M/D
RP1
RP2
SE
UH1
WH1
WH2
WX
XEV1
XHT
TYPE
DESCRIPTION
CMP
DRY
GDO1
GDO2
GR
HOTSY
ICE
SCBA
WASH
AIR COMPRESSOR - TO REMAIN
DRYER - TO BE RELOCATED
GARAGE DOOR OPENER, 1/3 HP - TO REMAIN
GARAGE DOOR OPENER,1/3 HP - TO BE RELOCATED
BENCH GRINDER, 1/2 HP - TO REMAIN
PRESSURE WASHER, GAS - TO BE RELOCATED
ICE MACHINE - TO BE RELOCATED
SCUBA (AIR COMPRESSOR), 10 HP - TO REMAIN
WASHER - TO BE RELOCATED
L=
I=
Isca (1) = SHORT CIRCUIT CURRENT AT FAULT POINT #1
Isca (2) = SHORT CIRCUIT CURRENT AT FAULT POINT #2
Isca (2) = Isca (1) x M(1) M = 1/(1+f)
FEEDER: 'f (3Ø) = 1.732 x L x Isca
CxE
XFMR: 'f (3Ø) = IP(sca)x Vp x 1.73 x %Z
100,000 x kVA
FEEDER: 'f (1Ø) = 2 x L x Isca
CxE
XFMR: 'f (1Ø) = IP(sca)x Vp x %Z
100,000 x kVA
ISsca = Vp x M x IP(sca)
Vs
AC UNIT, THRU WALL
AC UNIT, THRU WALL
AC UNIT, THRU WALL
AC UNIT, THRU WALL
AC UNIT, THRU WALL
AC UNIT, THRU WALL
AC UNIT, THRU WALL
CO/NO2 CONTROLLER
CONDENSING UNIT
CONDENSING UNIT
CEILING EXHAUSTER
CEILING EXHAUSTER
CEILING EXHAUSTER
CEILING EXHAUSTER
HORIZ GAS FURNACE
HORIZ GAS FURNACE
MOTORIZED DAMPER
RADIENT HEATER, GAS
RADIENT HEATER, GAS
SEWAGE EJECTOR, 1HP
GAS UNIT HEATER, 1/20 HP
TANKLESS GAS WATER HEATER
TANKLESS GAS WATER HEATER
GARAGE EXHAUSTER
EVAP COOLER - TO REMAIN
WALL HEATER - TO BE RELOCATED
ELECTRICAL
120 V/1-1065 VA
120 V/1-1065 VA
120 V/1-1065 VA
120 V/1-1065 VA
120 V/1-1065 VA
120 V/1-1065 VA
120 V/1-1065 VA
120 V/1-120 VA
208 V/2-5520 VA
208 V/2-6480 VA
120 V/1-50 VA
120 V/1-109 VA
120 V/1-109 VA
120 V/1-109 VA
120 V/1-1488 VA
120 V/1-1488 VA
120 V/1-50 VA
120 V/1-600 VA
120 V/1-600 VA
120 V/1-1440 VA
120 V/1-50 VA
120 V/1-350 VA
120 V/1-350 VA
120 V/1-1656 VA
120 V/1-1920 VA
120 V/1-1500 VA
CB AT PANEL DISC. AT UNIT
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
40 A
45 A
15 A
15 A
15 A
15 A
20 A
20 A
15 A
20 A
20 A
20 A
15 A
15 A
15 A
15 A
25 A
20 A
CORD/PLUG
CORD/PLUG
CORD/PLUG
CORD/PLUG
CORD/PLUG
CORD/PLUG
CORD/PLUG
N/A
PROVIDE 60A
PROVIDE 60A
OS SWITCH
OS SWITCH
OS SWITCH
OS SWITCH
CORD/PLUG
CORD/PLUG
N/A
CB IN SIGHT
CB IN SIGHT
PROVIDE 30A
PROVIDE SWITCH
CB IN SIGHT
CB IN SIGHT
CB IN SIGHT
PROVIDE 30A
PROVIDE SWITCH
CONDUCTORS
#12 CU + #12 CU GROUND
#12 CU + #12 CU GROUND
#12 CU + #12 CU GROUND
#12 CU + #12 CU GROUND
#12 CU + #12 CU GROUND
#12 CU + #12 CU GROUND
#12 CU + #12 CU GROUND
#12 CU + #12 CU GROUND
#8 CU + #8 CU GROUND
#8 CU + #8 CU GROUND
#12 CU + #12 CU GROUND
#12 CU + #12 CU GROUND
#12 CU + #12 CU GROUND
#12 CU + #12 CU GROUND
#12 CU + #12 CU GROUND
#12 CU + #12 CU GROUND
#12 CU + #12 CU GROUND
#12 CU + #12 CU GROUND
#12 CU + #12 CU GROUND
#12 CU + #12 CU GROUND
#12 CU + #12 CU GROUND
#12 CU + #12 CU GROUND
#12 CU + #12 CU GROUND
#12 CU + #12 CU GROUND
#10 CU + # 10 CU GROUND
#12 CU + #12 CU GROUND
NOTES
PROVIDE RECEPTACLE
PROVIDE RECEPTACLE
PROVIDE RECEPTACLE
PROVIDE RECEPTACLE
PROVIDE RECEPTACLE
PROVIDE RECEPTACLE
PROVIDE RECEPTACLE
PROVIDE CONDUIT TO DETECTORS, M/D, WX
CONTROL BY SECOND RELAY IN OCC SENSOR
CONTROL BY SECOND RELAY IN OCC SENSOR
CONTROL BY SECOND RELAY IN OCC SENSOR
CONTROL BY SECOND RELAY IN OCC SENSOR
PROVIDE RECEPTACLE
PROVIDE RECEPTACLE
24V TRANSFORMER PROVIDED BY MECH
SEE KEYED NOTE ON PLAN
CONTROLLED BY CO2 SENSORS
ASSUMED AT 120V-1HP, VERIFY
ASSUMMED 1500W, VERIFY
OWNER EQUIPMENT CONNECTION SCHEDULE
NM = NON-MAGNETIC CONDUIT
M = MAGNETIC CONDUIT
FB = FEEDER BUSWAY
PB = PLUG-IN BUSWAY
XFMR = TRANSFORMER
CALCULATIONS ARE BASED ON THE "POINT-BY-POINT" METHOD:
DESCRIPTION
LENGTH OF CIRCUIT TO THE FAULT IN FT (1 WAY).
AVAILABLE SHORT-CIRCUIT CURRENT IN AMPS AT
THE BEGINNING OF THE CIRCUIT.
C = 'C' FACTOR CONSTANT FROM THE TABLE OF 'C'
VALUES FOR THE CONDUCTORS.
E = LINE-TO-LINE OR LINE-TO NEUTRAL VOLTAGE.
IP = PRIMARY SHORT CIRCUIT CURRENT IS =
IS = SECONDARY SHORT CIRCUIT CURRENT
Vs = SECONDARY VOLTAGE
Vp = PRIMARY VOLTAGE
ELECTRICAL
240 V/2-5280 VA
240 V/2-12240 VA
120 V/1-864 VA
120 V/1-864 VA
120 V/1-936 VA
240 V/2-8160 VA
120 V/1-1272 VA
240 V/2-11040 VA
208 V/2-2160 VA
CB AT PANEL DISC. AT UNIT
40 A
60 A
20 A
20 A
20 A
40 A
15 A
50 A
20 A
EXISTING
CB IN SIGHT
CORD/PLUG
CORD/PLUG
CORD/PLUG
CB IN SIGHT
PROVIDE SWITCH
EXISTING
CB IN SIGHT
CONDUCTORS
#8 CU + #8 CU GROUND
#6 CU + #6 CU GROUND
#12 CU + #12 CU GROUND
#12 CU + #12 CU GROUND
#12 CU + #12 CU GROUND
#8 CU + #8 CU GROUND
#12 CU + #12 CU GROUND
#6 CU + #6 CU GROUND
#12 CU + #12 CU GROUND
NOTES
RECONNECT ONLY
RECONNECT ONLY, SWITCH TO REMAIN
PROVIDE RECEPTACLE
RECONNECT ONLY
RECONNECT ONLY
GROUNDING ELECTRODE
CONDUCTOR
MICRO-SWITCH
EXOTHERMIC WELD
RED (COMMON)
BLACK (NORMALLY OPEN)
NON-METALLIC
PROTECTIVE SLEEVE
BROWN (NORMALLY CLOSED)
ANSUL SNAP ACTION SWITCHES.
CONTACTS SHOWN WITH AUTOMAN
IN THE COCKED POSITION (READY)
21 AMP, 125/250 VAC SWITCHES
ACTUATING ARM
POWER TO
COOKING EQUIPMENT
SHUNT TRIP BREAKER (BY E.C.)
BLACK
VOLTAGE FREE N/C CONTACTS
FOR INTERCONNECTION TO THE
MUA HVAC SYSTEM
VOLTAGE FREE N/O CONTACTS
FOR INTERCONNECTION TO THE
BUILDING ALARM SYSTEM
RED
BLACK
RED
BROWN
BROWN
BLACK
BLACK
RED
BROWN
RED
RODAHL & HUMMELL
ARCHITECTURE, P.C.
CONCRETE FOUNDATION
IN DIRECT CONTACT WITH EARTH
N
VOLTAGE FREE N/O CONTACTS
FOR INTERCONNECTION TO THE
COOKING EQUIPMENT SHUNT TRIP
MICRO-SWITCH
2" MIN
ARCHITECTURE
VOLTAGE FREE EXTRA CONTACTS
609 North Dustin
Farmington, NM 87401
Phone: (505) 326-6442
EARTH
BROWN
FIELD WIRING BY
ELECTRICAL CONTRACTOR
A3
GROUNDING ELECTRODE :
MINIMUM #4 AWG BARE CU, OR
REBAR OF MINIMUM 1/2" DIAM.
20' MIN CONTINUOUS
(EXOTHERMICALLY WELDED JOINTS ACCEPTABLE)
ANSUL MICROSWITCH DETAIL
A4
UFER GROUNDING DETAIL
VALLEY #1
FIRE STATION
KIRTLAND, NM
ELECTRICAL DETAILS & SCHED.
Checked: Date:
Drawn:
AW
JL
12-09-15
Filename:
1526.rvt
Project:
1526
Sheet:
E8
Of: 8