ELECTRICAL SYMBOLS LEGEND FIRE ALARM SWITCHING LIGHTING RECTANGULAR FIXTURE, CEILING MOUNTED (DIMENSIONS AS SHOWN) A FACP FIRE ALARM (FA) CONTROL PANEL ANN FA ANNUNCIATOR ROUND FIXTURE, CEILING MOUNTED (DIMENSIONS AS SHOWN) A A B C TRACK LIGHTING (LENGTH AS SHOWN, HEADS NOT TO SCALE) A POLE MOUNTED FIXTURE (HEADS NOT TO SCALE) ARM SYMBOL ADDITION INDICATES WALL MOUNTING A A DOT SYMBOL ADDITION INDICATES PENDANT MOUNTING A A A A-E PERFORM ALL ELECTRICAL WORK IN A NEAT AND WORKMANLIKE MANNER IN FULL COMPLIANCE WITH ALL APPLICABLE, ADOPTED, CODES; INCLUDING, BUT NOT LIMITED TO THE NATIONAL ELECTRICAL CODE (NEC), UBC, IBC, NFPA, AND ADA. ALL LOCAL AND STATE REQUIREMENTS WILL BE OBSERVED DURING THE PERFORMANCE OF THIS WORK. 3. NOTIFY THE ENGINEER IN WRITING IF DISCREPANCIES BETWEEN CONTRACT DOCUMENTS AND ANY ASSOCIATED LEGAL OR SAFETY REQUIREMENTS ARE DETECTED. THE ENGINEER WILL MODIFY THE CONTRACT DOCUMENTS ACCORDINGLY. IF THE CONTRACTOR PROCEEDS W/ ANY WORK WHICH IS IN VARIANCE OF KNOWN LEGAL OR SAFETY REQUIREMENTS, THE CONTRACTOR WILL ASSUME RESPONSIBILITY FOR THIS WORK AND WILL PROMPTLY CORRECT THE WORK, WHEN NOTIFIED WITHOUT ADDITIONAL COST TO THE OWNER. 4. FIELD VERIFY EXISTING CONDITIONS PRIOR TO COMMENCING WORK. NOTIFY THE ENGINEER OF ANY DISCREPANCIES BEFORE PROCEEDING. NO CLAIM FOR ADDITIONAL COST OR TIME EXTENSION WILL BE ALLOWED WITHOUT PROPER NOTICE PLUS PRIOR DETERMINATION OF TIME AND COST TO THE OWNER. 5. CLEAN THE ENTIRE ELECTRICAL SYSTEM AFTER COMPLETION OF THE INSTALLATION. REMOVE ALL FOREIGN MATTER, PAINT, OR DIRT, GREASE, UNNEEDED LABELS OR STICKERS FROM FIXTURES AND EQUIPMENT. REMOVE ALL RUBBISH AND DEBRIS ACCUMULATED DURING INSTALLATION FOR THE PREMISES. WALL OCCUPANCY SENSOR (ARROWS INDICATE VIEW) 6. COORDINATE ALL PHASES OF THE ELECTRICAL WORK WITH THE ARCHITECT AND GENERAL CONTRACTOR. PERFORM WORK TO CAUSE AS LITTLE INCONVENIENCE AS POSSIBLE TO THE OWNER. POWER OUTLETS 7. OBTAIN, FROM SYSTEM SUPPLIERS, ALL WIRING DIAGRAMS FOR ALL EQUIPMENT, PRIOR TO ANY ROUGH-IN, TO ASSURE THAT PROPER ELECTRICAL CHARACTERISTICS ARE PROVIDED, ANY INCORRECT WIRING OR DEVICES INSTALLED BY ELECTRICAL CONTRACTOR WITHOUT THE WIRING DIAGRAM SHALL BE CORRECTED AT ELECTRICAL CONTRACTOR'S EXPENSE. 8. VERIFY ELECTRICAL DEVICE LOCATIONS WITH ARCHITECTURAL CASE WORK DETAILS PRIOR TO ANY ROUGH-IN. 9. VERIFY FINAL LOCATIONS OF ALL SINKS WITH THE PLUMBING CONTRACTOR PRIOR TO ROUGH-IN. ANY ELECTRICAL DEVICES LOCATED ABOVE COUNTER AND BEHIND FINAL SINK LOCATIONS WILL BE SHIFTED A MINIMUM OF 8'' TO EITHER SIDE OF SINK. ANY ELECTRICAL DEVICES LEFT BEHIND SINK AT TIME OF FINAL ELECTRICAL WALK THROUGH WILL BE RELOCATED AT ELECTRICAL CONTRACTOR'S EXPENSE. 10. PRIOR TO INSTALLATION, THE OWNER RESERVES THE RIGHT TO RELOCATE ANY ELECTRICAL DEVICE, UP TO A DISTANCE OF 12", WITHOUT ADDITIONAL CHARGE. 11. FIELD VERIFY AND COORDINATE THE EXACT LOCATION OF ALL SYSTEMS AND EQUIPMENT WITH ALL TRADES PRIOR TO INSTALLATION. WHERE EXACT LOCATIONS ARE NECESSARY, THEY ARE DIMENSIONED ON THESE DRAWINGS. WHERE THERE IS A QUESTION OF ADEQUATE CLEARANCE OR COORDINATION BETWEEN TRADES, THIS CONTRACTOR WILL PREPARE AS BUILT DRAWINGS FOR ENGINEERS REVIEW. 12. CONTACT UTILITY COMPANIES (POWER, GAS, WATER, SEWER, TELEPHONE, CABLE TV., ETC.) PRIOR TO TRENCHING IN ORDER TO IDENTIFY UNDERGROUND UTILITIES. CONTRACTOR SHALL LOCATE SECONDARY SERVICE FEEDERS, UNDER- GROUND ELECTRICAL BRANCH CIRCUITS, SPRINKLER LINES, ETC., PRIOR TO TRENCHING. ANY CUT DAMAGED UNDER- GROUND UTILITIES SHALL REPAIRED OR REPLACED AT CONTRACTOR'S EXPENSE. 13. UTILIZE COPPER CONDUCTORS, RATED FOR 600 VOLTS, TYPE THHN/THWN INSULATION, UNLESS OTHERWISE INDICATED. MINIMUM WIRE SIZE #12 AWG AND STRANDED FOR #8 AWG OR LARGER, RUN WIRING IN CONDUIT INCLUDING LOW VOLTAGE AND CONTROL WIRING, UNLESS OTHERWISE NOTED. 14. UTILIZE 1/2 INCH E.M.T. CONDUIT MINIMUM. WHERE REQUIRED TO PROTECT FROM PHYSICAL DAMAGE, USE RIGID OR IMC TYPE CONDUIT. RUN CONDUIT CONCEALED UNLESS OTHERWISE SHOWN ON THE DRAWINGS. USE FLEXIBLE METALLIC CONDUIT WHERE NEEDED. PROVIDE EXPANSION FITTINGS FOR CONDUIT CROSSING EXPANSION JOINTS. 15. SUPPORT ALL CONDUIT INDEPENDENTLY FROM THE BUILDING STRUCTURE. DO NOT SUPPORT FROM VENTILATION DUCTS, MECHANICAL PIPING, SUSPENDED CEILING GRIDS, OR THEIR HANGERS. USE ONLY ACCEPTABLE METHODS OF SUPPORT. 16. TERMINATING & SPLICING: MAKE ALL JOINTS & SPLICES IN BRANCH CIRCUIT WIRING, #10 AWG & SMALLER, W/ AN APPROVED SOLDER LESS TOOL OR TWIST ON CONNECTORS. #8 AWG AND LARGER USE HIGH COMPRESSION BARREL SPLICES WITH SHRINK WRAP AND MANUFACTURER'S COMPATIBLE CONNECTORS IN GUTTERS, AND SIMILAR LOCATIONS; BUT NOT ALLOWED IN RACEWAYS. LEAVE SUFFICIENT SLACK TO PERMIT 2 OR MORE SPLICES OR JOINTS TO BE REMADE IN CASE OF FAULT. 17. EMT CONDUIT FITTINGS: IN DRY LOCATIONS USE STEEL SET SCREW TYPE OR "REGAL" DIE CAST SET SCREW COUPLINGS AND CONNECTORS. DIE CAST FITTINGS WILL NOT BE USED ON THIS PROJECT. DAMP/ WET LOCATIONS: USE STEEL COMPRESSION GLAND TYPE COUPLER AND CONNECTIONS. 18. SURFACE RACEWAY: WHEREVER CONCEALED CONDUIT IN FINISHED AREAS IS NOT POSSIBLE, INSTALL SURFACE MOUNTED RACEWAYS EQUAL TO WIREMOLD. RUN SURFACE RACEWAYS IN CORNER OF WALL AND CEILING. ALL RACEWAYS THAT ARE EXPOSED WILL REQUIRE ARCHITECT'S/ ENGINEER'S APPROVAL PRIOR TO ROUGH-IN. COLOR BY ARCHITECT. 19. TYPE NM (ROMEX CABLE) AND NMC CABLE WILL NOT BE ALLOWED ON THIS PROJECT. F FA CEILING MOUNTED FA HORN/STROBE SN 20A, NETWORKED SWITCH SD DIMMER SWITCH F FA ADA STROBE V F FA CEILING MOUNTED FA STROBE F FA FIRE ALARM PULL STATION F/S FA FIRE/SMOKE DAMPER RI FA REMOTE INDICATOR FS FA FLOW SWITCH TS FA TAMPER SWITCH 20A, 4-WAY TOGGLE SWITCH 20A, 1 POLE KEY OPERATED SWITCH PUSHBUTTON SWITCH TC TIME CLOCK SWITCH PH PHOTOSENSOR RC ROOM CONTROLLER (ABOVE CEILING) CEILING OCCUPANCY SENSOR (ARROWS INDICATE VIEW) FA GAS DETECTOR FA SMOKE DETECTOR EXIT SIGNS (FILL INDICATES NUMBER OF FACES) WITH LIGHTS 2. 20A, 3-WAY TOGGLE SWITCH FA ADA HORN/STROBE. V=VOICE/STROBE S3 S4 SK HALF FILLED SYMBOL INDICATES EMERGENCY VERSION A-E PROVIDE, INSTALL, AND COORDINATE ALL WORK INDICATED BY THESE DRAWINGS. THIS CONSISTS OF FURNISHING ALL LABOR, EQUIPMENT, SUPPLIES AND MATERIALS IN ADDITION TO PERFORMING ALL OPERATIONS INCLUDING CUTTING, CHANNELING & UNDERGROUND TRENCHING, BACK FILL & TAMPING NECESSARY FOR THE INSTALLATION OF COMPLETE POWER, LIGHTING, OR OTHER SYSTEMS AS SHOWN. 20A, 1 POLE TOGGLE SWITCH BOX SYMBOL ADDITION INDICATES FLOOR OR IN-GROUND MOUNTING A 1. S F DS WITH DOUBLE ARROW FACE FA HEAT DETECTOR 20A, 120V, DUPLEX RECEPTACLE FA DUCT SMOKE DETECTOR 20A, 120V, FOURPLEX RECEPTACLE 2P-4W RECEPTACLE (SEE PANEL SCHEDULE FOR DETAILS) NOTES: 1. Lower case letters after a comma in the fixture designation indicate switching. For example, "A3, b" indicates a type A3 fixture controlled by switch b. 2. A fixture designation ending in "-E" indicates an emergency fixture, even where the fixture symbol may too small to show a half fill clearly. 3. Dimensions and mounting heights in the lighting fixture schedule supercede information implied by these symbols. Symbols are for general reference only. POWER DISTRIBUTION G 20A, 120V - GROUND FAULT PROTECTED (AT RECEPT. OR BREAKER, AS REQUIRED FOR ACCESSIBILITY) WP 20A, 120V - WEATHERPROOF IN USE COVER GROUND FAULT PROTECTED (AT RECEPT. OR BREAKER, AS REQUIRED FOR ACCESSIBILITY) SURFACE MOUNTED ELECTRICAL PLUG-IN RACEWAY 20A, 120V, DUPLEX RECEPTACLE, HALF SWITCHED DISCONNECT SWITCH COMMUNICATIONS S T 2P SPECIAL RECEPTACLE 20A FRACTIONAL HORSEPOWER DISCONNECT SWITCH WITH THERMAL OVERLOAD PROTECTION. 2P = 2 POLE DATA OUTLET CEILING MOUNTED DUPLEX RECEPTACLE, 20A, 120V FLOOR MOUNTED DUPLEX RECEPTACLE, 20A, 120V MOTOR OR EXHAUST FAN SIMPLEX TYPE RECEPTACLE CONTROL STATION 20A, 120V, DUPLEX RECEPTACLE, ABOVE COUNTER DATA OUTLET, ABOVE COUNTER ANALOG PHONE OUTLET M METER COMBINATION DATA & ANALOG PHONE OUTLET R RELAY COMBINATION DATA & ANALOG PHONE OUTLET, ABOVE COUNTER G GROUND CONNECTION ANALOG PHONE OUTLET, ABOVE COUNTER BOX INDICATES FLUSH MOUNTING IN FLOOR CIRCLE INDICATES FLUSH MOUNTING IN CEILING 3 SUBSCRIPT INDICATES QUANTITY OF PORTS (IF MORE THAN 1) 4 M M M MICROPHONE: CEILING, WALL AND FLOOR MOUNTED RESPECTIVELY S S S SPEAKER: CEILING, WALL AND FLOOR MOUNTED RESPECTIVELY J DOOR CONTROLS THERMOSTAT OUTLET BOX: SINGLE GANG BACK BOX, PLASTER RING (UNLESS OTHERWISE NOTED) 1/2''CONDUIT AND PULL CORD TO MECH UNIT T 2 J J JUNCTION BOX, CEILING, WALL AND FLOOR MOUNTED RESPECTIVELY BRANCH CIRCUIT PANEL BOARD, SEE SCHEDULE FOR MOUNTING T AO AUTOMATIC DOOR OPENER DH MAGNETIC DOOR HOLDER PS DOOR POSITION SWITCH EL ELECTRIC LOCK/STRIKE KP KEY PAD KC KEY CARD READER PAD MOUNT TRANSFORMER ABBREVIATIONS WALL MOUNTED HORN/SPEAKER T WALL MOUNT TRANSFORMER WIRELESS ACCESS POINT WAP SURGE PROTECTION DEVICE TVSS B BELL GROUND C CLOCK OUTLET, SINGLE RECEPTACLE WITH BRACKET & CLOCK C/S COMBINATION CLOCK & SPEAKER WALL MOUNTED TV TELEVISION OUTLET CONDUIT STUB-OUT LIGHTNING/SURGE ARRESTOR LA S IC INTERCOM CONTROL SWITCH S IV INTERCOM VOLUME CONTROL C1D1 RATED SEALS SECURITY SYSTEM INFRARED MOTION SENSOR SITE PLAN SECURITY SYSTEM CAMERA OR NURSE CALL NP PULL CORD, CEILING MOUNTED NB CALL BUTTON NL INDICATOR LIGHT NC CONTROL STATION UGP UNDERGROUND ELECTRICAL PRIMARY FEEDER UGE UNDERGROUND ELECTRICAL FEEDER UGC UNDERGROUND COMMUNICATIONS OHE OVERHEAD ELECTRICAL FEEDER OHP PULL CORD, WALL MOUNTED NP OVERHEAD ELECTRICAL PRIMARY FEEDER TV UNDERGROUND TELEVISION CABLE T UNDERGROUND TELEPHONE CABLE MOUNTING WALL MOUNTED KEY MOUNTING HEIGHTS A 90'' TO TOP AND NOT LESS THAN 6'' BELOW FINISHED CEILING WHERE REQUIRED 80'' TO BOTTOM AND NOT GREATER THAN 96'' TO BOTTOM F F F B TV PNL C 6'-0'' D 48'' TO TOP AFF E 20'' TO TOP AFF F 3'' CB S C DS 48'' J G F D H C B T TV E GENERAL ELECTRICAL NOTES NOT TO SCALE NOTES: 1. VERIFY ALL MOUNTING HEIGHTS WITH ARCHITECT PRIOR TO ROUGH-IN. 2. DIMENSIONS ARE TO TOP OF DEVICE WITH TRIM. ADJUST BACK BOX LOCATION AS REQUIRED. 6''AC H 5'-0'' TO HANDLE J 6'-6''MAX 3. ALL MOUNTING HEIGHTS SHALL CONFORM TO THE LATEST EDITION OF THE AMERICANS WITH DISABILITIES ACT. (ADA) DASHED VERSION OF SYMBOL INDICATES EXISTING DEVICE. TYPICAL OF ALL SYMBOLS SHOWN ABOVE. F "X" EXISTING DEVICE TO REMAIN. "XO" EXISTING DEVICE REMOVED COMPLETELY. EXISTING DEVICE TO BE RELOCATED TO NEW POSITION. "XRR" "XR" EXISTING RELOCATED DEVICE. "XP" EXISTING DEVICE, COVERPLATE AND CIRCUITING REPLACE WITH NEW. REFER TO NEW POWER PLANS FOR NEW CIRCUITING. ABOVE COUNTER ABOVE FINISHED FLOOR 20. AFG ARCH BC ABOVE FINISHED GRADE ARCHITECTURAL BELOW COUNTER FEEDER RACEWAY: IN ADDITION TO RACEWAY BONDING REQUIRED BY CODE & OUTLET BOX BONDING JUMPERS, A SEPARATE, INSULATED, GREEN EQUIPMENT GROUND CONDUCTOR. TERMINATE EACH END ON SUITABLE LUG, BUS, OR BUSHING. 21. C CONDUIT ELECTRONIC/ COMPUTER EQUIPMENT AND SPECIAL EQUIPMENT BRANCH CIRCUITS: IN ADDITION TO RACEWAY BONDING REQUIRED BY CODE AND OUTLET BOX BONDING JUMPERS, INSTALL A SEPARATE, INSULATED, GREEN EQUIPMENT GROUND CONDUCTOR WITHIN BRANCH CIRCUIT RACEWAY. TERMINATE EACH END ON SUITABLE LUG, BUS, OR BUSHING. EC ELEC EMT ELECTRICAL CONTRACTOR ELECTRICAL ELECTRICAL METALLIC TUBING 22. MAINTAIN A MINIMUM OF 24 INCH SEPARATION BETWEEN POWER CONDUITS AND SIGNAL CONDUITS. ROUTE CONDUITS SO AS NOT CROSS EACH OTHER. GC GEC GRC GENERAL CONTRACTOR GROUND ELECTRODE CONDUCTOR GALVANIZED RIGID CONDUIT 23. PROVIDE WIRING DEVICES RATED FOR THE GIVEN APPLICATION AS REQUIRED BY CODE. 24. INSTALL EXTERIOR WIRING IN CONDUIT. UTILIZE WEATHERPROOF FITTINGS AND WEATHERPROOF BOXES/ COVERS. 25. GRD GROUND SIZE ALL BOXES AND ENCLOSURES PER THE NATIONAL ELECTRICAL CODE. WORKING SPACE FOR ELECTRICAL INSTALLATION SHALL BE IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE ARTICLE 110. GFI GROUND FAULT INTERRUPTER 26. IG ISOLATED GROUND IMC INTERMEDIATE METALLIC CONDUIT LA LIGHTNING ARRESTOR MC MECHANICAL CONTRACTOR PROVIDE A 20 AMP, 120 VOLT, RECEPTACLE OUTLET INSTALLED AT AN ACCESSIBLE LOCATION FOR THE SERVICING OF HEATING, AIR CONDITIONING, AND REFRIGERATION EQUIPMENT OF ROOF TOPS, ATTICS, AND CRAWL SPACES PER NEC 210-63. LOCATE THE RECEPTACLE ON THE SAME LEVEL AND WITHIN 25' OF THE EQUIPMENT. INSTALL A GFCI RECEPTACLE AT ROOF TOP LOCATIONS WITH CAST BOX, WEATHERPROOF COVER PLATE, AND MOUNT ONTO A THREADED IMC CONDUIT SECURELY FASTENED IN PLACE IN ACCORDANCE WITH NEC 314-23. MECH MECHANICAL 27. NIC NOT IN CONTRACT INSTALL AT LEAST ONE WALL SWITCH-CONTROLLED LIGHTING OUTLET AT OR NEAR EQUIPMENT REQUIRING SERVICING SUCH AS HEATING, AIR CONDITIONING, AND REFRIGERATION EQUIPMENT IN ATTIC OR UNDERFLOOR SPACES PER NEC 210-70. LOCATE SWITCH AT POINT OF ENTRY TO THE ATTIC OR UNDERFLOOR SPACE. NTS NOT TO SCALE 28. BRANCH CIRCUITS: UTILIZE #10 AWG CONDUCTORS ON ALL RUNS OVER 100'-0". OHE OVERHEAD ELECTRICAL FEEDER OHP OVERHEAD PRIMARY FEEDER 29. PHASE PROTECTION: INSTALL PHASE PROTECTION ON ALL NEW 3 PHASE MOTORS 1HP AND ABOVE AND ALL 3PH AIR HANDLING UNITS. MANUFACTURED BY CUTLER HAMMER D65 OR SQUARE D MPS. OHS OVERHEAD SECONDARY FEEDER 30. PVC POLYVINYL CHLORIDE PLMBG PLUMBING MULTIPLE PHASE HOME RUNS MAY SHARE A COMMON NEUTRAL EXCEPT WHEN A DIMMER/ DIMMING SYSTEM IS USED, & WHEN ELECTRONIC/ COMPUTER EQUIPMENT CONNECTIONS ARE REQUIRED. VERIFY W/ ENGINEER PRIOR TO ROUGH-IN. PNL PANEL 31. PROVIDE ACCESS PANELS WITHIN THE ELECTRICAL BID. TURN OVER TO THE APPROPRIATE TRADE FOR INSTALLATION. REFER TO ARCHITECTURAL SPECIFICATION SECTIONS. RTU ROOFTOP UNIT TVSS TRANSIENT VOLTAGE SURGE SUPPRESSER 32. UG UNDERGROUND UGE UNDERGROUND ELECTRICAL FEEDER UGP UNDERGROUND PRIMARY FEEDER COORDINATE SHORT CIRCUIT RATING OF PANELBOARDS AND OVER-CURRENT PROTECTION WITH UPSTREAM OVER- CURRENT PROTECTION AND AVAILABLE SCA. PROPERLY IDENTIFY ALL PANELBOARDS W/ LAMINATE LABEL & TYPE ALL PANEL SCHEDULES. INSTALL PANELBOARDS AS INDICATED ON DRAWINGS AND SCHEDULES. PROVIDE CIRCUIT BREAKERS AS REQUIRED. USE "HACR" BREAKERS FOR HEATING /AIR CONDITIONING LOADS, PROVIDE GROUND-FAULT CIRCUIT-INTERRUPTER BREAKERS AS REQUIRED. PROVIDE A GROUND BAR KIT WITHIN EACH DISTRIBUTION PANEL, BRANCH CIRCUIT PANEL, AND LOAD CENTER. UPS UN INTERRUPT ABLE POWER SUPPLY 33. WP WEATHERPROOF INSTALL METERING AND ELECTRICAL SERVICE ENTRANCE EQUIPMENT IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL ELECTRIC UTILITY SYSTEM STANDARDS. XFMR TRANSFORMER 34. EXTEND ALL CONDUIT AND CONDUCTORS, INSTALL ELECTRICAL EQUIPMENT AS NECESSARY, AND MAKE ALL FINAL CONNECTIONS TO MECHANICAL AND OWNER FURNISHED EQUIPMENT. LEAVE ALL EQUIPMENT IN OPERABLE CONDITION WITH APPROPRIATE OVERLOAD AND SERVICE DISCONNECT PROTECTION AS REQUIRED BY THE APPLICABLE CODES. FOLLOW MANUFACTURERS INSTALLATION GUIDELINES WHERE APPLICABLE. 35. COORDINATE WITH THE MECHANICAL /PLUMBING /CONTROLS CONTRACTOR TO INSURE THAT ALL REQUIRED COMPONENTS OF CONTROL WORK ARE INCLUDED AND FULLY UNDERSTOOD. NO ADDITIONAL COST SHALL ACCRUE TO THE OWNER AS A RESULT OF LACK OF SUCH COORDINATION. REFER TO THE ELECTRICAL CONNECTION SCHEDULE FOR MECHANICAL EQUIPMENT AND THE MECHANICAL-ELECTRICAL RESPONSIBILITY TABLE. 36. CEILING PENETRATIONS IN FIRE RATED CEILINGS SHALL CONFORM TO THE REQUIREMENTS OF IBC SECTION 712. IF AGGREGATE PENETRATION AREA (DETERMINE AGGREGATE AREA FOR ALL DISCIPLINES PENETRATING CEILING AREA) EXCEEDS AREA ALLOWED, THE ELECTRICAL CONTRACTOR SHALL INCLUDE, AS REQUIRED, A FIRE RATED ENCLOSURE FOR EACH FIXTURE IN THAT AREA. LIGHTING FIXTURE TYPE MAY REQUIRE ''IC'' RATING. CONSULT ARCH. FOR DETAILS. GENERAL NOTES 26.## G DEMOLITION AC AFF KEYED NOTE - ## MECHANICAL EQUIPMENT IDENTIFICATION K# KITCHEN EQUIPMENT IDENTIFICATION RODAHL & HUMMELL ARCHITECTURE, P.C. GENERAL DEMOLITION NOTES 1. 2. IF CONCEALED OR UNKNOWN CONDITIONS ARE UNCOVERED AND ARE AT A VARIANCE WITH CONDITIONS SHOWN IN THE CONTRACT DOCUMENTS OR OF AN UNUSUAL NATURE NOT ORDINARILY ENCOUNTERED IN WORK OF THIS KIND, NOTICE MUST BE GIVEN TO THE ENGINEER BEFORE PROCEEDING WITH ANY ADDITIONAL WORK. NO CLAIM FOR ADDITIONAL COST OR TIME EXTENSION WILL BE ALLOWED WITHOUT PROPER NOTICE, PRIOR DETERMINATION OF COST OR TIME, AND EXPENSE TO THE OWNER. THE DEMOLITION PLAN SHALL BE USED AS A SCHEMATIC GUIDE TO DEMOLITION ONLY. ADDITIONAL DEMOLITION MAY BE REQUIRED TO COMPLETE THE NEW CONSTRUCTION/ REMODELING AS INDICATED ON THE DRAWINGS. ITEMS OF DEMOLITION WORK NOT SPECIFICALLY INDICATED BUT REQUIRED TO COMPLETE THE PROJECT WORK SHALL BE INCLUDED IN THE CONTRACT SUM. NOTE: SOME OF THE SYMBOLS SHOWN MAY NOT APPEAR ON ALL DOCUMENTS OR PLANS. 3. DAMAGE ON THE CONSTRUCTION SITE CAUSED BY THE CONTRACTOR OR A PARTY TO THE CONTRACTOR DURING THE DEMOLITION OF CONSTRUCTION PHASE SHALL BE REPAIRED PRIOR TO CONTRACT DATE OF SUBSTANTIAL COMPLETION AT NO ADDITIONAL EXPENSE TO THE OWNER. 4. ALL EXISTING REMOVED EQUIPMENT WILL BE STOCKPILED AT THE SITE UNTIL AN INSPECTION BY THE OWNER'S REPRESENTATIVE WILL DETERMINE WHAT WILL BE SALVAGED, ALL EQUIPMENT NOT SALVAGED OR RETAINED BY THE CONTRACTOR FOR REUSE WILL BE HAULED OFF THE SITE BY THIS CONTRACTOR. THE STOCK PILE AREA WILL BE DETERMINED BY THE ARCHITECT AND OWNER. REFER TO ELECTRICAL SPECIFICATIONS SECTION 16060 - ''ELECTRICAL DEMOLITION FOR REMODELING''. 5. VERIFY THAT ALL ELECTRICAL EQUIPMENT TO REMAIN OR BE RELOCATED AND REUSED ARE IN WORKING ORDER PRIOR TO ANY DEMOLITION WORK. IF THE EXISTING MATERIAL IS FOUND TO BE INOPERABLE, CONTRACTOR SHALL INFORM THE OWNER ONCE ANY DEMOLITION WORK HAS BEGUN, ANY INOPERABLE OR DAMAGED MATERIAL SHALL BE REPAIRED OR REPLACED AT THE CONTRACTOR'S EXPENSE. ARCHITECTURE 609 North Dustin Farmington, NM 87401 Phone: (505) 326-6442 VALLEY #1 FIRE STATION KIRTLAND, NM ELECTRICAL LEGEND Checked: Date: Drawn: AW JL 12-09-15 Filename: 1526.rvt Project: 1526 Sheet: E1 Of: 8 KEYED NOTES 26.01 26.17 26.20 EXISTING CORD REEL TO REMAIN. EXISTING TELEPHONE DEMARC AND HANDSET. EQUIPMENT TO REMAIN, LOCATION NOTED FOR REFERENCE. CEILING MOUNTED PROJECTOR, TO BE RELOCATED TO NEW TRAINING ROOM BY OWNER. REMOVE EXISTING OUTLET, AND PROVIDE NEW POWER AND DATA FLUSH WITH NEW CEILING. XO5 EXISTING EQUIPMENT LEGEND XO XRT TYPE XO 26.01 TYP. OF 5 X X X X X XO2 XO2 XO2 XO2 XO2 XO XO XUH XO XO XUH XF XO2 XO XO2 XO2 PANEL C (XO) X GDO1 XEV1 X GDO1 X GDO1 XR GDO2 X GDO1 XEV2 XO2 XO XO XO XO X XO2 XO XO2 XO2 XO2 XO XO XO XO2 XO XO XO XO XBH XCU XEF XEV XEV1 XEV2 XF XHT XRT XUH XWH1 XWH2 CMP DRY GDO1 GDO2 GR HOTSY ICE SCBA WASH BASEBOARD HEATER - TO BE REMOVED CONDENSING UNIT - TO BE REMOVED CEILING EXHAUSTER - TO BE REMOVED EVAPORATOR - TO BE REMOVED EVAP COOLER - TO REMAIN EVAP COOLER - TO BE REMOVED FURNACE - TO BE REMOVED WALL HEATER - TO BE RELOCATED RADIANT TUBE HEATER - TO BE REMOVED UNIT HEATER - TO BE REMOVED WATER HEATER - TO BE REMOVED WATER HEATER - TO BE REMOVED AIR COMPRESSOR - TO REMAIN DRYER - TO BE RELOCATED GARAGE DOOR OPENER, 1/3 HP - TO REMAIN GARAGE DOOR OPENER,1/3 HP - TO BE RELOCATED BENCH GRINDER, 1/2 HP - TO REMAIN PRESSURE WASHER, GAS - TO BE RELOCATED ICE MACHINE - TO BE RELOCATED SCUBA (AIR COMPRESSOR), 10 HP - TO REMAIN WASHER - TO BE RELOCATED EXISTING LIGHTING FIXTURE LEGEND S TYPE XO1 XO2 XO3 XO4 XO5 XO6 SECOND FLOOR ELECTRICAL DEMO PLAN 2 DESCRIPTION DESCRIPTION MOUNTING 1'X4' - TO BE REMOVED 1'X4' - TO BE REMOVED TROFFER - TO BE REMOVED VANITY FIXTURE - TO BE REMOVED WALLPACK - TO BE REPLACED IN SAME LOCATION "CAN" LIGHT - TO BE REMOVED SUSPENDED SURFACE RECESSED WALL WALL RECESSED 1/8" = 1'-0" METER (XO) XO GR WASH XRR XO2 ICE DRY SCBA 26.17 XRR XO1 XO1 XO1 XO1 XO2 XO X S XO6 XO1 XO1 XO XO6 XO3 G XO3 XO1 XO XO XO1 XO3 XO4 G XO XO1 XO3 XBH G XO1 XO1 XO1 XO XEF XHT XO3 XWH2 XO4 XO XO3 HOTSY XRR XO X XO1 XRR XO6 XEF 3 3X XRR XO1 XO3 XO1 XO XO1 XO XO XO1 XO X XCU XO1 XO XBH XO CMP XO XO5 XO XO5 XWH1 MDP (XO) ATS (XO) PANEL G (XO) PANEL B (XO) PANEL A (XO) XO XO XO XEV TO DOOR OPENER XO1 TO DOOR OPENER XO1 TO DOOR OPENER XO1 TO DOOR OPENER XO1 XO5 XO3 XO3 XO3 XO1 XO XO1 26.20 XO3 XO3 XO3 XO3 XO3 XO3 XO XO2 XO1 TO DOOR OPENER XO1 XO6 XO1 XO1 XO1 XO1 XO1 XO1 XO XO1 XO PANEL D (XO) XCU XO XO XO3 XO4 XO2 XO5 XO XO XO5 XO XO XO XO 3 XO XO3 XO5 XO5 RODAHL & HUMMELL ARCHITECTURE, P.C. XO XO5 ARCHITECTURE 1 FIRST FLOOR ELECTRICAL DEMO PLAN 1/8" = 1'-0" 609 North Dustin Farmington, NM 87401 Phone: (505) 326-6442 VALLEY #1 FIRE STATION KIRTLAND, NM ELECTRICAL DEMO PLANS Checked: Date: Drawn: AW JL 12-09-15 Filename: 1526.rvt Project: 1526 Sheet: E2 Of: 8 GENERAL ELECTRICAL PLAN NOTES WX A1 - 11 CX4 G2 - 29 26.02 R.R. 206 G2 - 31 G1 - 9 HALL 205 CX3 X X APPARATUS BAY 211 A1 - 12 G1 - 11 (PART) A1 - 15 X G1 - 15 R.R. 207 A1 - 13 26.16 RP1 G2 - 19 G1 - 16 26.16 26.18 AC4 26.19 G2 - 26 VEST. 208 GDO1 X XEV1 STORAGE 212 GDO1 X 26.18 26.18 GDO1 X G1 - 12 G GDO1 X 26.18 26.18 SLEEPING 202 F2 G1 - 13 G2 - 18 G2 - 21 G1 - 10 UH1 G X 26.04 AC3 SLEEPING 203 G1 - 11 (PART) RP2 26.01 26.02 AC2 X G X KEYED NOTES SLEEPING 204 (PART, WITH LGTS) 26.01 TYP. OF 5 WHERE PHONE/DATA OUTLETS ARE SHOWN, PROVIDE CONDUIT AND BACKBOX ONLY. CABLE IS BY OWNER. G 1 LAUNDRY 209 G1 - 20 26.20 G1 - 17 EXISTING CORD REEL TO REMAIN. PROVIDE EMPTY 1" CONDUIT FROM CO (CO2 SENSOR CONTROLLER) TO CO2 SENSORS, MOTORIZED DAMPERS (M/D), AND WALL EXHAUSTER (WX), FOR CONTROLS CABLE BY OTHERS. PROVIDE ONE RECEPTACLE AT 24" AFF FOR GAS RANGE, ONE RECEPTACLE IN CABINET ABOVE FOR FIRE SUPPRESSION SYSTEM (SEE DETAIL), AND ONE RECEPTACLE IN CABINET ABOVE FOR MICROWAVE. FOR RECEPTACLES MARKED AS GFCI BUT NOT IN READILY ACCESSIBLE LOCATION, PROVIDE GFCI BREAKER AT PANEL. PROVIDE PHONE LINE AND BELL ON BAY CEILING TO NOTIFY OCCUPANTS WHEN PHONE IS RINGING. PROVIDE CONTACTOR AT BACK OF OVERHEAD DOOR TRACK TO INDICATE WHEN DOOR IS FULLY OPEN. PROVIDE LED RED/GREEN SIGNAL LIGHT ADJACENT TO DOOR AT 6' AFF. INDICATOR TO CHANGE TO GREEN ONLY WHEN DOOR IS FULLY OPEN, AND REMAIN RED OTHERWISE. PROVIDE POWER TO WALL MOUNTED CONTROL PANEL SUPPLIED WITH SEWAGE EJECTOR. CONNECT POWER FROM CONTROLLER TO TWO INTEGRAL PUMPS, AND PROVIDE AN ADDITIONAL CONDUIT FOR CONTROLS FROM FLOAT SWITCHES IN TANK TO CONTROLLER. CEILING MOUNTED PROJECTOR, TO BE RELOCATED TO NEW TRAINING ROOM BY OWNER. REMOVE EXISTING OUTLET, AND PROVIDE NEW POWER AND DATA FLUSH WITH NEW CEILING. G2 - 27 AC5 SLEEPING 201 G2 - 20 G2 - 23 OFFICE 200 G2 - 25 26.02 G1 - 18 G2 - 24 M/D G2 - 22 G1 - 14 2 A1 - 14 GDO2 G1 - 19 AC6 XRR 26.18 BAY ADDITION 210 26.02 M/D SECOND FLOOR POWER PLAN 1 1/8" = 1'-0" G XRR HOTSY WP A2 - 1,3 26.02 X STORAGE 109 G1 - 3 WP 26.02 WH1 G1 - 7 WASH A1 - 17,19 CO 26.02 XRR XRR G1 - 25 CO CO DRY WH2 A2 - 2,4 X A2 - 6,8 GEAR ADDITION 108 A1 - 1 CO 26.02 SCBA PANEL A1 PANEL G1 ATS PANEL A2 TRANS. A G2 - 1 G2 - 2 G1 - 8 DAY ROOM 105 26.02 CO GR A2 - 9,11 G2 - 6 G X APPARATUS BAY 107 G2 - 7 G2 - 8 G A1 - 16 XHT G G G2 - 5 A1 - 5 OFFICE 110 G2 - 9 G G GG XRR CMP MDP X A1 - 3 26.04 G KITCHEN 104 G1 - 1 G2 - 3 G2 - 10 G2 - 11 G1 - 4 SE G2 - 4 AC1 PANEL G2 26.18 26.18 CX2 G2 - 28 (PART, WITH LGTS) 26.18 A1 - 6 R.R. 103 G A1 - 21,23 CX1 HALL 102 CU2 R.R. 101 A1 - 24,26 G2 - 12 CU1 A1 - 4 G AC7 26.19 G WP WP 2 WP WP G2 - 15 A1 - 7 A1 - 8 A1 - 9 A1 - 2 G2 - 14 BAY ADDITION 106 G2 - 17 TRAINING 100 F1 M/D G1 - 5 RODAHL & HUMMELL ARCHITECTURE, P.C. M/D 26.20 26.18 2 G1 - 6 2 G1 - 2 26.18 G G CONF. 111 ICE G XRR WP G2 - 16 A1 - 10 ARCHITECTURE 2 609 North Dustin Farmington, NM 87401 Phone: (505) 326-6442 VALLEY #1 FIRE STATION KIRTLAND, NM 2 FIRST FLOOR POWER PLAN 1/8" = 1'-0" Drawn: AW POWER PLANS Checked: Date: JL 12-09-15 Filename: 1526.rvt Project: 1526 Sheet: E3 Of: 8 GENERAL LIGHTING PLAN NOTES 1 2 W2 O-W1 E L R.R. 206 L G2 - 31 S R.R. 207 L O-C c O-W2 KEYED NOTES 26.22 TYPE H FIXTURES INCLUDE AN INTEGRAL OCCUPANCY/DAYLIGHT SENSOR, AND WALL SWITCHES FUNCTION AS A MANUAL OVERRIDE TO OFF. TYPE HE FIXTURES ARE UNSWITCHED, AND HAVE NO SENSOR. SLEEPING T1 203 T1, c A f SLEEPING 204 T1, g T1E, c HALL 205 L APPARATUS BAY 211 A, f g O-W2 S O-C E c A D G1 - 26 D W2 SUPPLY EXIT SIGNS FROM NEAREST CIRCUIT SERVING SAME SPACE (UNSWITCHED). CONTROL DEVICES CONTROL ALL FIXTURES IN ROOM, UNLESS OTHERWISE NOTED WITH A LOWER CASE SWITCH LETTER. A L E T1E 208 STORAGE L 212 SLEEPING T1 202 T1E, c LIGHTING FIXTURE SCHEDULE D O-W1 O-W1 A LAUNDRY L209 O-C TYPE DESCRIPTION A ASSYMETRIC UP/DOWN WALL FIXTURE, DIMMABLE EXIT SIGN, RED ON WHITE HIGH BAY, WIDE DISTRIBUTION, WITH INTEGRAL OCCUPANCY SENSOR HIGH BAY, WIDE DISTRIBUTION, WITH EM BATTERY PACK 4' LINEAR LENSED SQUARE SHOWER LIGHT SQUARE LIGHT, WET LOCATION, WITH EM BATTERY PACK d L OFFICE T1, d 200 SLEEPING T1 201 T1, d E H D O-C d HE A L S SE SIGNAL T1 TROFFER, 2'X2' SURFACE, <5" DEEP T1E TROFFER, 2'X2' SURFACE, <5" DEEP, WITH EM BATTERY PACK T2 TROFFER, 2'X4' T2E TROFFER, 2'X4', WITH EM BATTERY PACK W2 WALLPACK WITH COLD WEATHER EM BATTERY W4 WALLPACK BAY ADDITION 210 MOUNTING HEIGHT LAMP WALL MAKE MODEL ELECT. CCT CRI LUMENS OPTIC 120 V/1-37 VA 40K MIN 80 2,500 ASSYMETRIC LED FINELITE S17-LED-VCF-PF-2-SO-40K-SC-120 N/A 40K N/A MIN 80 N/A 16,000 N/A WIDE 40K MIN 80 16,000 WIDE UNIVERSAL SUSPENDED ABOVE DOOR 18' AFF LED LED COMPASS COLUMBIA SUSPENDED 18' AFF LED COLUMBIA CER 120 V/1-3 VA LLHV4-40M-WST-EU-SFA-WG-OS1360 + 120 V/1-155 VA LHVQM5 LLHV4-40M-WST-EU-SFA-WG-ELL14 + LHVQM5 120 V/1-155 VA SURFACE SURFACE SURFACE CEILING CEILING CEILING LED LED LED COLUMBIA KENALL KENALL LCL4-40LW-EU MS11FL-PP-MW-18L40K-SCC-DV-R80 MS11FL-PP-MW-18L40K-SCC-DV-R80-LEL 120 V/1-25 VA 120 V/1-18 VA 120 V/1-18 VA 40K 40K 40K MIN 80 MIN 80 MIN 80 2,500 1,000 1,000 N/A N/A N/A WALL SURFACE SURFACE CEILING CEILING LED LED LED FINELITE COLUMBIA COLUMBIA S17-LED-VCF-PF-2-SO-40K-SC-120 LCAT22-40ML-SM-EDU LCAT22-40ML-SM-EDU-ELL14 120 V/1-37 VA 120 V/1-30 VA 120 V/1-30 VA 40K 40K MIN 80 MIN 80 3,200 3,200 ASSYMETRIC N/A N/A RECESSED - GRID RECESSED - GRID WALL CEILING CEILING MATCH EXISTING LED LED LED COLUMBIA COLUMBIA HUBBELL LCAT24-40HL-G-EDU LCAT24-40HL-G-EDU-ELL14 LNC2-12LU-4K-2-2-PC(120)-BBU 120 V/1-47 VA 120 V/1-47 VA 120 V/1-29 VA 40K 40K 40K MIN 80 MIN 80 - 5,500 5,500 2,400 N/A N/A TYPE 2 WALL MATCH EXISTING LED HUBBELL LNC2-12LU-4K-4-2-PC(120)-BBU 120 V/1-29 VA 40K - 2,400 TYPE 4 CONTROL DEVICE SCHEDULE TYPE Dimmer O-C O-W1 O-W2 RC 2 DESCRIPTION 0-10V WALL DIMMER WITH ON/OFF TOGGLE CEILING OCCUPANCY SENSOR WALL OCCUPANCY SENSOR WALL OCCUPANCY SENSOR LOCAL ROOM CONTROLLER FOR COORDINATION OF MULTIPLE INPUT DEVICES MOUNTING HEIGHT SENSING TECH RELAYS SWITCH(ES) WALL CEILING WALL WALL ABOVE CEILING SWITCH HEIGHT N/A SWITCH HEIGHT SWITCH HEIGHT N/A N/A DUAL DUAL DUAL N/A PER PLAN 1 1 2 PER PLAN INTEGRAL PROVIDE REMOTE PER PLAN 1 - INTEGRAL 2 - INTEGRAL PER PLAN NOTES SECOND RELAY CONTROLS FAN LOCATE ABOVE NEAREST ACCESSIBLE CEILING SECOND FLOOR LIGHTING PLAN 1/8" = 1'-0" MDP L, e L, e LOW CEILING E G1 - 21 PANEL A1 PANEL G1 TRANS. A ATS L STORAGE 109 L H, c HE H, c O-W1 26.22 TYP. H, d T1 G1 - 23 H, d T1E T1 DAY ROOM 105 c d RC HE 26.22 TYP. APPARATUS BAY 107 E PANEL A2 G1 - 22 3 3 L, e 3 O-W1 e E GEAR ADDITION L, e 108 O-C T1 T1 T1 T1 T1 T1 T1 3 OFFICE O-W1 110 KITCHEN 104 T1 H, c H, c H, c H, d H, d O-C H, d T1 T1E T1 G2 - 28 T1 PANEL G2 CONF. 111 O-W1 R.R. T1 103 T1 c d 3 3 W4 W4 W4 HALL O-W1 T2E R.R. T1 101 O-W1 G1 - 24 W4 D D BAY ADDITION 106 H, d a b T2, a T2, a T2, a RC TRAINING O-C 100 HE T2, a T2, a T2, a RODAHL & HUMMELL ARCHITECTURE, P.C. E T2E, b W4 T2, b T2, b ARCHITECTURE 609 North Dustin Farmington, NM 87401 Phone: (505) 326-6442 E SE VALLEY #1 FIRE STATION KIRTLAND, NM 1 FIRST FLOOR LIGHTING PLAN 1/8" = 1'-0" LIGHTING PLANS Checked: Date: Drawn: AW JL 12-09-15 Filename: 1526.rvt Project: 1526 Sheet: E4 Of: 8 KEYED NOTES 26.03 26.09 26.10 NEW PAD MOUNTED UTILITY TRANSFORMER TO REPLACE EXISTING POLE MOUNTED 26.11 26.12 26.13 26.14 EXISTING OVERHEAD POWER 26.15 26.21 26.23 EXISTING PARKING LOT ISLAND CONTAINING LIGHT POLE, SUBFEED PANEL "P" ON POST, AND FIRE HYDRANT, ALL TO BE DEMOLISHED IN THIS PROJECT. PANEL "F" ON FIRE TOWER IS TO REMAIN, AND IS CURRENTLY FED THROUGH PANEL ON ISLAND. DISCONNECT ALL BRANCH CIRCUITS AND REMOVE PANEL. SPLICE PANEL "F" FEEDER TO PANEL "P" FEEDER, IN HEAVY DUTY TRAFFIC RATED GRADE BOX. PROVIDE 1" CONDUIT FROM GENERATOR TO CABLE ENTRY AT RADIO ROOM, FOR GENERATOR ALARM ANNUNCIATION. PROVIDE #2 CU GROUND RING AROUND NEW RADIO ROOM AT 30" DEPTH. ALL CONNECTIONS TO GROUND RING TO BE #2 CU. PROVIDE 8' COPPER CLAD STEEL GROUND ROD AT EIGHT LOCATIONS ON GROUND RING AS SHOWN. TIE NEW GROUND RING TO EXISTING GROUND RING AROUND EXISTING RADIO TOWER. ICE BRIDGE BY OWNER, SUPPORTED ON SIX 3" STEEL PIPES BY ARCHITECT. TIE BRIDGE SUPPORTS INTO GROUND RING. NEAR ICE BRIDGE CABLE ENTRY INTO RADIO ROOM, PROVIDE #2 CU IN CONDUIT FROM GROUND RING UP 10' ON SIDE OF BUILDING. CAP AND LABEL. EXTERIOR DISCONNECT PREINSTALLED ON RADIO BUILDING. TIE GROUND BUS TO NEW GROUND RING. POWER AND GENERATOR CONTROLS TO ATS, PLUS THREE 120V CIRCUITS FOR GENERATOR ACCESSORIES. SEE PANEL G1 SCHEDULE. LOCATION FOR GENERATOR REMOTE EMERGENCY STOP SWITCH. COORDINATE EXACT LOCATION WITH OWNER. PROVIDE PERMANENT WEATHERPROOF RED LABEL. TO ICE ERV AD S RHE OVE EX. ICE VED SERV EMO UND BE R RGRO UNDE NEW NEW ADDITION NEW ADDITION EXISTING BUILDING EXISTING FIRE TOWER PANEL F IN TO REMA EX. UGE XO EX. UGE TO REMAIN PANEL P 26.03 26.23 NG STI TE I X E CRE N CO ANK T 26.11 26.10 26.09 26.21 26.13 GENERATOR PROPANE RADIO TOWER RODAHL & HUMMELL ARCHITECTURE, P.C. NEW RADIO BUILDING 26.12 26.14 26.15 ARCHITECTURE 609 North Dustin Farmington, NM 87401 Phone: (505) 326-6442 VALLEY #1 FIRE STATION KIRTLAND, NM 1 SITE ELECTRICAL PLAN 1" = 10'-0" ELECTRICAL SITE PLAN Checked: Date: Drawn: AW JL 12-09-15 Filename: 1526.rvt Project: 1526 Sheet: E5 Of: 8 EXISTING ELECTRICAL RISER RISER LEGEND FIRE TOWER MAIN BUILDING NEW OR MODIFIED IN THIS PROJECT 3 A.T.S. EXISTING TO REMAIN EXISTING TO BE DEMOLISHED EMRG NORM PANEL C 1 MLO - 120/240V TO EXISTING POLE MOUNTED UTILITY TRANSFORMER RISER GENERAL NOTES 4 MDP M 1. ALL UNDERGROUND CONDUIT TO BE SCHEDULE 80 PVC. 2. ALL EXPOSED EXTERIOR CONDUIT TO BE RIGID STEEL. 3. THIS DIAGRAM IS SCHEMATIC, AND NOT INTENDED TO SPECIFY CONDUIT ROUTING OR FEED SIDE OF PANELS. 4. WHERE ALUMINUM FEEDERS ARE SPECIFIED, VERIFY THAT ASSOCIATED PANELS ARE RATED FOR ALUMINUM CONDUCTORS. 5. TERMINAL SCREWS ON ALL ALUMINUM FEEDERS SHALL BE TORQUED TO CONDUCTOR MANUFACTURER'S SPECIFICATIONS AT CONSTRUCTION, AND RE-TORQUED 90 DAYS AFTER COMMISSIONING. MCB PANEL P 6 RISER KEYED NOTES MCB - 120/240V MCB - 120/240V NEUT BUS MLO - 120/240V GRND BUS MLO - 120/240V EXISTING GENERATOR MLO - 120/240V 2 MLO - 120/240V 5 PANEL F 1. REMOVE EXISTING MDP, AND PROVIDE NEW MDP IN NEW LOCATION. ADJACENT UTILITY METER MUST BE RELOCATED, COORDINATE WITH UTILITY. 2. REMOVE EXISTING PROPANE GENERATOR, AND REPLACE WITH NEW IN SAME LOCATION. PROPANE TANK TO REMAIN AND BE REUSED. 3. REMOVE AUTOMATIC TRANSFER SWITCH AND RETURN TO OWNER. INSTALL NEW AUTOMATIC TRANSFER SWITCH, PURCHASED BY OWNER. SWITCH SHALL BE 300 AMP, 3 POLE, SOLID NEUTRAL. 4. REMOVE ALL PANELS INSIDE MAIN BUILDING. 5. REMOVE PANEL P, LOCATED ON PARKING ISLAND TO BE REMOVED. SPLICE PANEL P FEEDER TO PANEL F FEEDER IN HEAVY DUTY TRAFFIC RATED GRADE BOX. 6. PANEL ON EXTERIOR OF FIRE TOWER TO REMAIN. 7. PROVIDE NEW PANEL, SEE PANEL SCHEDULE FOR DETAILS. 8. NEW RADIO ROOM BUILDING IS A COMPLETE BUILDING BEING MOVED HERE FROM ANOTHER SITE. EXTERIOR DISCONNECT AND BRANCH PANEL ARE ALREADY INSTALLED, BUT DISCONNECT HAS NO FUSES. PROVIDE 200A FUSES, POWER SUPPLY FROM MAIN BUILDING, AND GROUNDING. NO WORK IN INTERIOR OF BUILDING. 9. NEW GROUNDING RING SURROUNDING RADIO BUILDING. SEE SITE PLAN FOR DETAIL ON SIZE, QUANTITY OF RODS, AND CONNECTIONS TO OTHER ELEMENTS. 10 4 PANEL A 4 PANEL G PANEL B 4 PANEL D 4 #4 CU + #4 CU GROUND #2 CU + #2 CU GROUND NEW ELECTRICAL RISER 10. EXISTING PANEL "D" FEEDS CURRENT RADIO ROOM (INSIDE MAIN BUILDING), WHICH MUST REMAIN OPERATIONAL DURING CONSTRUCTION. WHILE BUILDING SERVICE IS DOWN, FEED PANEL D FROM PORTABLE GENERATOR PROVIDED BY OWNER. COORDINATE DISCONNECTION AND RECONNECTION WITH OWNER IN ADVANCE. NEW RADIO BLDG FIRE TOWER MAIN BUILDING 11. PROVIDE A 45 KVA TRANSFORMER (208 3 PHASE TO 240 CENTER TAP DELTA), TO SERVE EXISTING OWNER EQUIPMENT THAT REQUIRES 240V. PLEASE NOTE THIS TRANSFORMER IS UNCOMMON AND MAY REQUIRE SIGNIFICANT LEAD TIME. 12. PROVIDE PERMANENT ORANGE LABEL ON THIS PANEL INDICATING THAT SOURCE IS CENTER TAPPED DELTA, AND PHASE B IS THE HIGH LEG. 13. EXCLUDE COST OF NEW GENERATOR AND NEW ATS. THESE WILL BE PURCHASED BY OWNER AND INSTALLED BY ELECTRICAL CONTRACTOR. A.T.S. 3W + G EMRG 4W + G 14. INSTALL NEW GENERATOR (PURCHASED BY OWNER). GENERATOR SHALL HAVE A MINIMUM RATING OF THE LOAD SHOWN FOR PANEL G1 PER PANEL SCHEDULES, AFTER THE APPROPRIATE DE-RATING FACTOR IS APPLIED FOR SITE ELEVATION (TYPICALLY AROUND 20%). GENERATOR SHALL INCLUDE THE FOLLOWING OPTIONS: NORM 3 POLE 3 8 14.1. 14.2. 14.3. 14.4. 14.5. 14.6. 14.7. 13 1 MDP TRANS. A 208/3 240/3 45 kVA M MCB 1/0 CU 14 1/0 CU GRND BUS 1/0 CU NEUT BUS NEW GENERATOR PANEL R PANEL A1 100 KVA 120/208V 7 #4 CU 9 PANEL A2 #4 CU 12 7 PANEL F MCB - 208V / 1PH 13 6 MLO - 208V / 3PH MLO - 208V / 1PH NEUT BUS TVSS MCB - 240V / 3PH TO NEW PAD MOUNTED UTILITY TRANSFORMER MLO - 208V / 3PH GRND BUS 11 MLO - 208V / 3PH 200A STANDARD ENCLOSURE REMOTE ANNUNCIATION (LOCATED IN NEW RADIO BUILDING) ENGINE BLOCK HEATER BATTERY WARMER 10A BATTERY CHARGER MAIN LINE CIRCUIT BREAKER NEUTRAL NOT BONDED TO GROUND IN GEN SET PANEL G1 PANEL G2 7 7 5 TO STRUCTURAL STEEL TO UFER GROUND #2 CU 20' LOOP 30" BELOW GRADE 20'-0" 20 '-0 " " '-0 20 #4 CU + #4 CU GROUND #2 CU + #2 CU GROUND (3) 3/4" X 10' COPPER CLAD STEEL GROUND RODS RODAHL & HUMMELL ARCHITECTURE, P.C. FEEDER SCHEDULE TO MDP ATS PANEL A1 TRANS. A PANEL A2 PANEL G1 (VIA ATS) PANEL G2 PANEL F RADIO BUILDING FROM UTILITY GENERATOR MDP A1 TRANS. A MDP G1 G1 G1 REQ. VOLTAGE POLES AMPACITY 208 V 3 500 A 208 V 3 300 A 208 V 3 300 A 208 V 3 150 A 240 V 3 125 A 208 V 3 300 A 208 V 3 100 A 208 V 2 100 A 208 V 2 200 A CONDUCTORS 2 Set(s) of [ (4) 350 MCM AL + NO GRND., 3 IN. CONDUIT ] 1 Set(s) of [ (3) 500 MCM AL + # 2 AL GRND., 3 IN. CONDUIT ] 1 Set(s) of [ (4) 500 MCM AL + # 2 AL GRND., 3 IN. CONDUIT ] 1 Set(s) of [ (4) 250 MCM AL + # 4 AL GRND., 2.5 IN. CONDUIT ] 1 Set(s) of [ (4) # 2/0 AL + # 4 AL GRND., 2 IN. CONDUIT ] 1 Set(s) of [ (4) 500 MCM AL + # 2 AL GRND., 3 IN. CONDUIT ] 1 Set(s) of [ (4) # 1 AL + # 6 AL GRND., 1.5 IN. CONDUIT ] EXISTING, RECONNECT ONLY. SEE RISER. 1 Set(s) of [ (3) 500 MCM CU + # 1 CU GRND., 3 IN. CONDUIT ] - UPSIZED FOR VOLTAGE DROP ARCHITECTURE 609 North Dustin Farmington, NM 87401 Phone: (505) 326-6442 VALLEY #1 FIRE STATION KIRTLAND, NM ELECTRICAL RISER Checked: Date: Drawn: AW JL 12-09-15 Filename: 1526.rvt Project: 1526 Sheet: E6 Of: 8 NEW Location: Supply From: Mounting: Enclosure: PANEL A1 Bay West MDP Surface Type 1 NEW Volts: 120/208 Wye Phases: 3 Wires: 4 A.I.C. Rating: 22,000 Mains Type: MLO Mains Rating: 300 A Location: Supply From: Mounting: Enclosure: Notes: Bay West TRANS. A Surface Type 1 NEW Volts: 120/240 Delta Center Phases: 3 Wires: 4 A.I.C. Rating: 22,000 Mains Type: MCB Mains Rating: 125 A Location: Supply From: Mounting: Enclosure: Notes: PROVIDE PERMANENT ORANGE LABEL INDICATING THAT SOURCE IS 240V DELTA AND PHASE B IS HIGH LEG. A CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 PANEL A2 Circuit Description REC- Bay West REC- Bay South REC- Office 110 REC- Ext East 1 REC- Ext East 3 REC- Upper Bay South REC- Bay Ceiling N XEV1 WASH -CU2 -- Trip 20 20 20 20 20 20 20 25 20 -45 -- Poles 1 1 1 1 1 1 1 1 2 -2 -- 720 B C Poles 1 1 720 1 1 1 720 1 1 1 12840 3 --2760 2 -- 720 900 720 720 180 180 180 180 540 1080 180 1920 936 1080 1080 12240 3240 11640 3240 2760 Total Load: 19140 VA 19716 VA Total Amps: 160 A 165 A Connected Load Demand Factor 13920 VA 100.00% 7740 VA 100.00% 11040 VA 125.00% 28776 VA 100.00% Load Classification HVAC Receptacle Motor - Largest Owner Equip. A 22620 VA 189 A Demand 13920 VA 7740 VA 13800 VA 28776 VA Trip 20 20 20 20 20 20 20 20 150 --40 -- Circuit Description REC- Bay North REC- Bay East REC- Conf 111 REC- Ext East 2 REC- Ext East 4 REC- Bay Ceiling S REC- Bay 106 ceiling GR TRANS. A --CU1 -- CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT 1 3 5 7 9 11 Circuit Description CMP -Space Space SCBA -- Load Classification Motor - Largest Owner Equip. B Trip Poles 2640 4080 40 2 2640 4080 ----0 6120 --5520 0 50 2 --Total Load: 12840 VA 12240 VA Total Amps: 107 A 102 A Connected Load Demand Factor 11040 VA 125.00% 25680 VA 100.00% PANEL MDP EXTERIOR, WEST UTILITY Surface Type 3R Volts: 120/208 Wye Phases: 3 Wires: 4 Notes: C 0 A 6120 5520 0 11640 VA 97 A Demand 13800 VA 25680 VA Poles 2 -2 ---- Trip 40 -60 ---- A.I.C. Rating: 22,000 Mains Type: MCB Mains Rating: 500 A Circuit Description HOTSY -DRY -Space Space CKT 2 4 6 8 10 12 Panel Totals CKT Circuit Description 1 PANEL A1 3 -5 -7 9 11 Load Classification HVAC Commercial Kitchen Equipment Lighting Motor Other Receptacle Motor - Largest Owner Equip. Other - Continuous Refrigeration Total Conn. Load: 36720 VA Total Est. Demand: 39480 VA Total Conn.: 88 A Total Est. Demand: 95 A Trip 300 --- B C Poles Poles 18881 15826 3 3 19537 31978 --22381 31286 --- Total Load: 34707 VA 51516 VA Total Amps: 289 A 451 A Connected Load Demand Factor 28654 VA 100.00% 1400 VA 100.00% 4768 VA 125.00% 2616 VA 100.00% 33404 VA 100.00% 23396 VA 71.37% 11040 VA 125.00% 34368 VA 100.00% 1500 VA 125.00% 1000 VA 100.00% 53667 VA 469 A Demand 28654 VA 1400 VA 5960 VA 2616 VA 33404 VA 16698 VA 13800 VA 34368 VA 1875 VA 1000 VA Trip 300 --- Circuit Description PANEL G1 (VIA ATS) --- CKT 2 4 6 8 10 12 Panel Totals Total Conn. Load: 142146 VA Total Est. Demand: 139775 VA Total Conn.: 395 A Total Est. Demand: 388 A Panel Totals Total Conn. Load: 61476 VA Total Est. Demand: 64236 VA Total Conn.: 171 A Total Est. Demand: 178 A NEW Location: Supply From: Mounting: Enclosure: PANEL G1 Bay West MDP Surface Type 1 PANEL G2 Volts: 120/208 Wye Phases: 3 Wires: 4 A.I.C. Rating: 22,000 Mains Type: MCB Mains Rating: 300 A Location: Supply From: Mounting: Enclosure: Notes: EXISTING Volts: 120/208 Wye Phases: 3 Wires: 4 A.I.C. Rating: 22,000 Mains Type: MLO Mains Rating: 100 A Location: Supply From: Mounting: Enclosure: Notes: * Connect shunt trip breaker serving gas range to ansul system above. See detail. A CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 Training, Hall G1 Recessed Type 1 Circuit Description AC1 XHT F1 WH1 WX RP1, RP2 (2) GDO1 AC2 AC4 AC6 LGT- 109, 110, 111 LGT- Bay, North WH2 PANEL G2 --Spare Spare Spare Spare Spare Spare Load Classification HVAC Commercial Kitchen Equipment Lighting Motor Other Receptacle Owner Equip. Other - Continuous Refrigeration Trip 20 20 20 15 15 20 20 20 20 20 20 20 15 100 --20 20 20 20 20 20 Poles 1 1 1 1 1 1 1 1 1 1 1 1 1 3 --1 1 1 1 1 1 1065 B C 1065 1500 1440 1488 350 120 1656 150 1200 1728 864 1065 1065 1065 1065 1488 170 1030 1240 350 154 7601 15302 7128 6180 1308 0 1038 0 0 500 0 500 Poles 1 1 100 1 1 1 1728 1 1 1 1065 1 1 1 163 1 1 2 15302 -2 -1200 1 1 1 Trip 20 20 15 20 15 20 20 20 20 20 20 20 20 200 -100 -20 20 20 Circuit Description AC7 SE (2) M/D CO UH1, (2) M/D (2) GDO1 GDO2 AC3 AC5 F2 LGT- Bay, South LGT- Exterior East LGT- Bay, South Upper Lev RADIO BUILDING -PANEL F -GEN- Battery Charger GEN- Battery Warmer GEN- Block Heater 0 0 Total Load: 16237 VA 32517 VA Total Amps: 135 A 291 A Connected Load Demand Factor 14734 VA 100.00% 1400 VA 100.00% 4768 VA 125.00% 2616 VA 100.00% 33404 VA 100.00% 15656 VA 81.94% 5592 VA 100.00% 1500 VA 125.00% 1000 VA 100.00% 31779 VA 285 A Demand 14734 VA 1400 VA 5960 VA 2616 VA 33404 VA 12828 VA 5592 VA 1875 VA 1000 VA Panel Totals Total Conn. Load: 80670 VA Total Est. Demand: 79409 VA CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 Circuit Description REC- Dayroom South ICE REC- Kitchen South Garb Disposal Microwave Range, Gas (SHUNT TRIP)* REC- Train Counter REC- Train South REC- 2nd FL, RR, Hall 2nd FL, Dryer REC- 2nd FL, IT 200 REC- 2nd FL, IT 200 REC- 2nd FL, 202 REC- 2nd FL, 204 LGT- UPPER NORTH Spare Spare Spare Spare Spare Load Classification HVAC Commercial Kitchen Equipment Lighting Other Receptacle Owner Equip. Refrigeration A B Trip Poles 540 360 20 1 1272 1000 15 1 20 1 1176 1600 20 1 1400 180 20 1 20 1 0 540 --360 360 20 1 20 1 720 360 20 1 180 900 20 1 20 1 900 540 20 1 540 1038 20 1 20 1 869 15 1 0 20 1 20 1 0 20 1 0 20 1 20 1 Total Load: 7605 VA 7230 VA Total Amps: 65 A 62 A Connected Load Demand Factor 377 VA 100.00% 1400 VA 100.00% 1561 VA 125.00% 500 VA 100.00% 14936 VA 83.48% 1272 VA 100.00% 1000 VA 100.00% PANEL F Fire Tower G1 Surface 3R Volts: 120/208 Single Phases: 1 Wires: 3 A.I.C. Rating: 10,000 Mains Type: MCB Mains Rating: 100 A Notes: THIS PANEL IS EXISTING TO REMAIN, SHOWN FOR REFERENCE ONLY. C A 1600 840 180 540 540 900 500 540 Poles 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Trip 20 20 20 20 20 20 20 20 20 20 20 20 20 15 Circuit Description REC- Dayroom North Refrigerators Dishwasher REC- Kitchen North Kitchen Ansul REC- RR, Ext North REC- Train North REC- Train East 2nd FL, Washer REC- 2nd FL, IT 200 REC- 2nd FL, IT 200 REC- 2nd FL, 201 REC- 2nd FL, 203 LGT- TRAIN, DAYROOM 540 0 0 6180 VA 52 A Demand 377 VA 1400 VA 1951 VA 500 VA 12468 VA 1272 VA 1000 VA CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 CKT 1 3 5 7 9 11 Circuit Description Fan -Controls Load Classification Lighting Motor Other Receptacle Trip 20 -20 Poles 2 -1 588 B 720 588 450 Poles 1 1 Trip 20 20 Circuit Description Receptacles Lighting 0 Total Load: 1308 VA 1038 VA Total Amps: 12 A 10 A Connected Load Demand Factor Demand 450 VA 125.00% 563 VA 1176 VA 100.00% 1176 VA 100 VA 100.00% 100 VA 720 VA 100.00% 720 VA CKT 2 4 6 8 10 12 Panel Totals Total Conn. Load: 2446 VA Total Est. Demand: 2559 VA Total Conn.: 12 A Total Est. Demand: 12 A Panel Totals Total Conn. Load: 21046 VA Total Est. Demand: 18968 VA Total Conn.: 58 A Total Est. Demand: 53 A Total Conn.: 224 A Total Est. Demand: 220 A RODAHL & HUMMELL ARCHITECTURE, P.C. ARCHITECTURE 609 North Dustin Farmington, NM 87401 Phone: (505) 326-6442 VALLEY #1 FIRE STATION KIRTLAND, NM Filename: 1526.rvt Project: 1526 Sheet: ELECTRICAL PANEL SCHEDULES E7 Checked: Date: Drawn: AW JL 12-09-15 Of: 8 MECHANICAL EQUIPMENT CONNECTION SCHEDULE CUMULATIVE VOLTAGE DROP 2 Segment Voltage Drop NM FAULT CURRENT at the secondary of the utility transformer 34800 34800 - - 20686 1.0% 1.0% Motor Contribution M f Conductor Reactance (X) Conductor Resistance (R) Length (L) 1 L-L Volts (E) 3 'C' value 2 MDP Wire/Bus 0 Conduit Type Source (Point) 3 Source Isc Phase 1 SERVICE Point Description SHORT CIRCUIT & VOLTAGE DROP CALCULATIONS Set(s) 350 AL 16812 208 85 of 0.00006 0.00005 0.000048 0.184 0.845 34800 17476 0.3% 1.3% Set(s) 250 AL 12122 208 20 of 0.00009 0.000052 0.240 0.806 20686 14092 0.3% 1.5% 0 0.000000 3.257 0.235 17476 2869 0.0% 1.5% 0.000040 0.733 0.577 150 3 PANEL A1 3 2 20686 M Set(s) 1 500 AL 18755 208 20 of 4 TRANS A -PR 3 3 17476 M 1 5 TRANS A -SC 1 4 14092 TX 0 6 PANEL A2 1 5 2869 M 1 Set(s) 2/0 AL 7186 of 240 10 0.00016 0.000054 0.033 0.968 14092 2777 0.1% 1.7% 7 PANEL G1 3 2 20686 M 1 Set(s) 500 AL 18755 208 20 of 0.00005 0.000048 0.184 0.845 2869 17476 0.3% 1.3% 8 PANEL G2 3 7 17476 M 1 Set(s) of 1 AL 4645 208 70 0.00025 0.000057 2.193 0.313 20686 5473 1.2% 2.5% 9 PANEL F 1 7 17476 M 1 Set(s) of 3 CU 4760 208 310 0.00025 0.000059 10.944 0.084 17476 1463 0.7% 2.0% 10 RADIO ROOM 1 7 17476 M 1 Set(s) 500 CU 22185 208 220 0.00003 of 0.000048 6554 1.7% 2.9% 0 0 0 208 0 NOTES TO THE CONTRACTOR: 1.666 0.375 17476 LEGEND: 1. THE DISTANCES SHOWN ARE FOR CALCULATION PURPOSES ONLY. THEY SHALL NOT BE USED FOR CONTRACTOR TAKEOFFS, NOR FOR BIDDING. 2. CONTRACTOR SHALL NOTIFY ENGINEER OF ANY FIELD CONDITION THAT RESULTS IN A CHANGE OF 10% OR GREATER CIRCUIT DISTANCE TYPE AC1 AC2 AC3 AC4 AC5 AC6 AC7 CO CU1 CU2 CX1 CX2 CX3 CX4 F1 F2 M/D RP1 RP2 SE UH1 WH1 WH2 WX XEV1 XHT TYPE DESCRIPTION CMP DRY GDO1 GDO2 GR HOTSY ICE SCBA WASH AIR COMPRESSOR - TO REMAIN DRYER - TO BE RELOCATED GARAGE DOOR OPENER, 1/3 HP - TO REMAIN GARAGE DOOR OPENER,1/3 HP - TO BE RELOCATED BENCH GRINDER, 1/2 HP - TO REMAIN PRESSURE WASHER, GAS - TO BE RELOCATED ICE MACHINE - TO BE RELOCATED SCUBA (AIR COMPRESSOR), 10 HP - TO REMAIN WASHER - TO BE RELOCATED L= I= Isca (1) = SHORT CIRCUIT CURRENT AT FAULT POINT #1 Isca (2) = SHORT CIRCUIT CURRENT AT FAULT POINT #2 Isca (2) = Isca (1) x M(1) M = 1/(1+f) FEEDER: 'f (3Ø) = 1.732 x L x Isca CxE XFMR: 'f (3Ø) = IP(sca)x Vp x 1.73 x %Z 100,000 x kVA FEEDER: 'f (1Ø) = 2 x L x Isca CxE XFMR: 'f (1Ø) = IP(sca)x Vp x %Z 100,000 x kVA ISsca = Vp x M x IP(sca) Vs AC UNIT, THRU WALL AC UNIT, THRU WALL AC UNIT, THRU WALL AC UNIT, THRU WALL AC UNIT, THRU WALL AC UNIT, THRU WALL AC UNIT, THRU WALL CO/NO2 CONTROLLER CONDENSING UNIT CONDENSING UNIT CEILING EXHAUSTER CEILING EXHAUSTER CEILING EXHAUSTER CEILING EXHAUSTER HORIZ GAS FURNACE HORIZ GAS FURNACE MOTORIZED DAMPER RADIENT HEATER, GAS RADIENT HEATER, GAS SEWAGE EJECTOR, 1HP GAS UNIT HEATER, 1/20 HP TANKLESS GAS WATER HEATER TANKLESS GAS WATER HEATER GARAGE EXHAUSTER EVAP COOLER - TO REMAIN WALL HEATER - TO BE RELOCATED ELECTRICAL 120 V/1-1065 VA 120 V/1-1065 VA 120 V/1-1065 VA 120 V/1-1065 VA 120 V/1-1065 VA 120 V/1-1065 VA 120 V/1-1065 VA 120 V/1-120 VA 208 V/2-5520 VA 208 V/2-6480 VA 120 V/1-50 VA 120 V/1-109 VA 120 V/1-109 VA 120 V/1-109 VA 120 V/1-1488 VA 120 V/1-1488 VA 120 V/1-50 VA 120 V/1-600 VA 120 V/1-600 VA 120 V/1-1440 VA 120 V/1-50 VA 120 V/1-350 VA 120 V/1-350 VA 120 V/1-1656 VA 120 V/1-1920 VA 120 V/1-1500 VA CB AT PANEL DISC. AT UNIT 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 40 A 45 A 15 A 15 A 15 A 15 A 20 A 20 A 15 A 20 A 20 A 20 A 15 A 15 A 15 A 15 A 25 A 20 A CORD/PLUG CORD/PLUG CORD/PLUG CORD/PLUG CORD/PLUG CORD/PLUG CORD/PLUG N/A PROVIDE 60A PROVIDE 60A OS SWITCH OS SWITCH OS SWITCH OS SWITCH CORD/PLUG CORD/PLUG N/A CB IN SIGHT CB IN SIGHT PROVIDE 30A PROVIDE SWITCH CB IN SIGHT CB IN SIGHT CB IN SIGHT PROVIDE 30A PROVIDE SWITCH CONDUCTORS #12 CU + #12 CU GROUND #12 CU + #12 CU GROUND #12 CU + #12 CU GROUND #12 CU + #12 CU GROUND #12 CU + #12 CU GROUND #12 CU + #12 CU GROUND #12 CU + #12 CU GROUND #12 CU + #12 CU GROUND #8 CU + #8 CU GROUND #8 CU + #8 CU GROUND #12 CU + #12 CU GROUND #12 CU + #12 CU GROUND #12 CU + #12 CU GROUND #12 CU + #12 CU GROUND #12 CU + #12 CU GROUND #12 CU + #12 CU GROUND #12 CU + #12 CU GROUND #12 CU + #12 CU GROUND #12 CU + #12 CU GROUND #12 CU + #12 CU GROUND #12 CU + #12 CU GROUND #12 CU + #12 CU GROUND #12 CU + #12 CU GROUND #12 CU + #12 CU GROUND #10 CU + # 10 CU GROUND #12 CU + #12 CU GROUND NOTES PROVIDE RECEPTACLE PROVIDE RECEPTACLE PROVIDE RECEPTACLE PROVIDE RECEPTACLE PROVIDE RECEPTACLE PROVIDE RECEPTACLE PROVIDE RECEPTACLE PROVIDE CONDUIT TO DETECTORS, M/D, WX CONTROL BY SECOND RELAY IN OCC SENSOR CONTROL BY SECOND RELAY IN OCC SENSOR CONTROL BY SECOND RELAY IN OCC SENSOR CONTROL BY SECOND RELAY IN OCC SENSOR PROVIDE RECEPTACLE PROVIDE RECEPTACLE 24V TRANSFORMER PROVIDED BY MECH SEE KEYED NOTE ON PLAN CONTROLLED BY CO2 SENSORS ASSUMED AT 120V-1HP, VERIFY ASSUMMED 1500W, VERIFY OWNER EQUIPMENT CONNECTION SCHEDULE NM = NON-MAGNETIC CONDUIT M = MAGNETIC CONDUIT FB = FEEDER BUSWAY PB = PLUG-IN BUSWAY XFMR = TRANSFORMER CALCULATIONS ARE BASED ON THE "POINT-BY-POINT" METHOD: DESCRIPTION LENGTH OF CIRCUIT TO THE FAULT IN FT (1 WAY). AVAILABLE SHORT-CIRCUIT CURRENT IN AMPS AT THE BEGINNING OF THE CIRCUIT. C = 'C' FACTOR CONSTANT FROM THE TABLE OF 'C' VALUES FOR THE CONDUCTORS. E = LINE-TO-LINE OR LINE-TO NEUTRAL VOLTAGE. IP = PRIMARY SHORT CIRCUIT CURRENT IS = IS = SECONDARY SHORT CIRCUIT CURRENT Vs = SECONDARY VOLTAGE Vp = PRIMARY VOLTAGE ELECTRICAL 240 V/2-5280 VA 240 V/2-12240 VA 120 V/1-864 VA 120 V/1-864 VA 120 V/1-936 VA 240 V/2-8160 VA 120 V/1-1272 VA 240 V/2-11040 VA 208 V/2-2160 VA CB AT PANEL DISC. AT UNIT 40 A 60 A 20 A 20 A 20 A 40 A 15 A 50 A 20 A EXISTING CB IN SIGHT CORD/PLUG CORD/PLUG CORD/PLUG CB IN SIGHT PROVIDE SWITCH EXISTING CB IN SIGHT CONDUCTORS #8 CU + #8 CU GROUND #6 CU + #6 CU GROUND #12 CU + #12 CU GROUND #12 CU + #12 CU GROUND #12 CU + #12 CU GROUND #8 CU + #8 CU GROUND #12 CU + #12 CU GROUND #6 CU + #6 CU GROUND #12 CU + #12 CU GROUND NOTES RECONNECT ONLY RECONNECT ONLY, SWITCH TO REMAIN PROVIDE RECEPTACLE RECONNECT ONLY RECONNECT ONLY GROUNDING ELECTRODE CONDUCTOR MICRO-SWITCH EXOTHERMIC WELD RED (COMMON) BLACK (NORMALLY OPEN) NON-METALLIC PROTECTIVE SLEEVE BROWN (NORMALLY CLOSED) ANSUL SNAP ACTION SWITCHES. CONTACTS SHOWN WITH AUTOMAN IN THE COCKED POSITION (READY) 21 AMP, 125/250 VAC SWITCHES ACTUATING ARM POWER TO COOKING EQUIPMENT SHUNT TRIP BREAKER (BY E.C.) BLACK VOLTAGE FREE N/C CONTACTS FOR INTERCONNECTION TO THE MUA HVAC SYSTEM VOLTAGE FREE N/O CONTACTS FOR INTERCONNECTION TO THE BUILDING ALARM SYSTEM RED BLACK RED BROWN BROWN BLACK BLACK RED BROWN RED RODAHL & HUMMELL ARCHITECTURE, P.C. CONCRETE FOUNDATION IN DIRECT CONTACT WITH EARTH N VOLTAGE FREE N/O CONTACTS FOR INTERCONNECTION TO THE COOKING EQUIPMENT SHUNT TRIP MICRO-SWITCH 2" MIN ARCHITECTURE VOLTAGE FREE EXTRA CONTACTS 609 North Dustin Farmington, NM 87401 Phone: (505) 326-6442 EARTH BROWN FIELD WIRING BY ELECTRICAL CONTRACTOR A3 GROUNDING ELECTRODE : MINIMUM #4 AWG BARE CU, OR REBAR OF MINIMUM 1/2" DIAM. 20' MIN CONTINUOUS (EXOTHERMICALLY WELDED JOINTS ACCEPTABLE) ANSUL MICROSWITCH DETAIL A4 UFER GROUNDING DETAIL VALLEY #1 FIRE STATION KIRTLAND, NM ELECTRICAL DETAILS & SCHED. Checked: Date: Drawn: AW JL 12-09-15 Filename: 1526.rvt Project: 1526 Sheet: E8 Of: 8