14 15 13 12 11 10 8 9 7 6 4 5 2 3 1 L L KEY NOTES: 1 2 K 3 PROVIDE ELECTRIC UTILITY METER PER CU STANDARDS. REFER TO CU METERING STANDARDS FOR ADDITIONAL INFORMATION. REFER TO THE POWER FLOOR PLAN FOR PROPOSED METER LOCATION. THERE SHALL BE NO COST TO THE OWNER FOR LACK OF COORDINATION WITH THE CU UTILITIES DISTRIBUTION DEPARTMENT AND THE REQUIRED METERING STANDARDS. KEY PAD MOUNTED UTILITY TRANSFORMER. COORDINATE WITH THE CU UTILITIES DISTRIBUTION DEPARTMENT. THERE SHALL BE NO COST TO THE OWNER FOR LACK OF COORDINATION WITH CU UTILITIES DISTRIBUTION DEPARTMENT. 3 CONDUCTORS KEY (6) "C LV FLA 6 J 8 PROVIDE FEEDER AS INDICATED, TO JUNCTION BOX LOCATED ABOVE FUTURE LOCATION OF GREENHOUSE DISTRIBUTION EQUIPMENT. COIL WIRE IN JUNCTION BOX FOR FUTURE EXTENSION DOWN TO EQUIPMENT. REFER TO POWER FLOOR PLANS FOR JUNCTION BOX LOCATION. 9 10 H 11 12 CCT BRKR SWITCH LOW VOLTAGE FEEDER (3) GROUNDING (4) DIMENSIONS (5) WEIGHT BTUH OTPT (5) , 1# 10 G 1 1/4 480 V 208 V "C CNDTRS "C HIGH WIDE DEEP (5) , 1# 8 G 1 1/2 T15 18.0 41.6 25 A 3 P 30 A 3 P FRS-R- 25 3# 10 ,1# 10 G 3/4 50 A 3 P 60 A 3 P FRN-R- 50 4# 6 ,1# 10 G 1 1# 8 3/4 27.00 20.13 16.00 310 2806 150.4 G 4# 1/0 , 1# 6 G 2 T30 36.1 83.3 45 A 3 P 60 A 3 P FRS-R- 45 3# 6 ,1# 10 G 1 100 A 3 P 100 A 3 P FRN-R- 100 4# 1 ,1# 8 G 1-1/2 1# 6 3/4 30.00 20.13 16.00 370 5753 200.4 G 4# 3/0 , 1# 6 G 2 1/2 T45 54.1 124.9 70 A 3 P 100 A 3 P FRS-R- 70 3# 4 ,1# 8 G 1-1/4 150 A 3 P 200 A 3 P FRN-R- 150 4# 1/0 ,1# 6 G 1-1/2 1# 6 3/4 39.25 26.13 20.00 480 7425 225.4 G 4# 4/0 , 1# 4 G 2 1/2 T75 90.2 208.2 110 A 3 P 200 A 3 P FRS-R- 110 3# 1 ,1# 6 G 1-1/2 250 A 3 P 400 A 3 P FRN-R- 250 4# 250 ,1# 2 G 2-1/2 1# 2 3/4 39.25 30.00 20.00 675 10549 135.3 600.4 G 2 [ 4# 350 , 1# 1 G 3 ] T112.5 3 [ 4# 300 , 1# 1/0 G 3 ] T500 2500.4 G 7 [ 4# 500 , 1# 350 G 3 1/2 ] NOTES: CONDUCTORS "C FUSE CONDUCTORS 312.3 175 A 3 P 200 A 3 P FRS-R- 175 3# 2/0 ,1# 6 G 2 400 A 3 P 400 A 3 P FRN-R- 400 2[4# 3/0 ,1# 3 G 2] 1# 2 3/4 39.25 30.00 24.00 725 14168 1387.9 750 A 3 P 800 A 3 P KRP-C- 750 2[3# 500 ,1# 1/0 G 3] 1600 A 3 P 1600 A 3 P KRP-C- 1600 5[4# 400 ,1# 4/0 G 3] 1 # 250 1 75.00 48.00 36.00 3770 44638 SECONDARY O.C. PROTECTION PER NEC 450. SEE MECHANICAL EQUIPMENT SCHEDULE 3.) ALL CONDUCTORS ARE COPPER. SEE PLANS FOR INCREASED CONDUCTOR SIZES DUE TO VOLTAGE DROP ETC. SEE TRANSFORMER SCHEDULE 4.) BONDING AND GROUNDING CONDUCTOR PER NEC 250. DIMENSIONS, WEIGHTS & BTUH OUTPUT SHOWN ARE FOR REFERENCE ONLY. ACTUAL DIMENSIONS MAY VARY FROM MANUFACTURER TO MANUFACTURER. 3/0 G 3/4 5.) K 7.) BRANCH CIRCUITS TO HAVE A DEDICATED NEUTRAL FOR EACH CIRCUIT ON K-RATED TRANSFORMERS. FOR K-RATED TRANSFORMERS, PROVIDE PARALLEL NEUTRAL CONDUCTORS LUGS AT TRANSFORMERS, LOW VOLTAGE PANELBOARD, DISCONNECTS AND/OR LOAD . 8.) CONDUIT 40% FILL RATIO BASED ON EMT. Project No.: PR007259 / HSG10910 COLORADO 3 AHU 301 6 11 (TYPICAL) PANEL LM3 AHU 301B M M M M M M M VFD VFD VFD VFD VFD VFD VFD VFD 11 (TYPICAL) H XFMR T 30 XFMR DM XFMR 12 3 12 10 10 ISCA=19,593 ISCA=16,810 3 ROOF/PENTHOUSE ISCA= 1,866 PANEL H2A PANEL KP2A PANEL KP2B PANEL KP2C PANEL KP2D PANEL L2A PANEL SBH2A G ISCA= 6,177 ISCA= 6,177 PANEL SBL2A 60.4G ISCA= 6,177 G ISCA=16,632 XFMR XFMR XFMR 225.4G T 75 LEVEL 2/2ND FLOOR 225.4G 200.4G ISCA= 1,454 ISCA= 3,454 225.4G ISCA= 20,927 ELEV 2 F UPS/MAIL AREA 150.4G 225.4G 6 ISCA= 4,599 PANEL KP1A E 225.4G DM PAD MOUNTED UTILITY TRANSFORMER, 13.2KV-480/277V, 3PH, 1000KVA (ANTICIPATED), BY CONTRACTOR ADD ALTERNATE #02 PANEL KP1B 225.4G XFMR ISCA=21,476 1 3 T 500 SPD M PANEL KH1A XFMR SPD XFMR XFMR XFMR PANEL L1A 1 3 DM M M 60.4G PANEL SBL1B XFMR ISCA=22,683 3 600.4G MEC 400.4G 3 200A4P, LIFE SAFETY AUTOMATIC TRANSFER SWITCH "ATS-LS" ISCA= 5,845 PANEL SBL1C DM 6 500KW/625KVA DIESEL GENERATOR 480/277, 3PH, 4W RATED AT SITE ELEVATION ISCA=22,657 3 6 ISCA= 5,885 ISCA= 12,487 600A4P, STANDBY AUTOMATIC TRANSFER SWITCH "ATS-SB" ISCA= 6,156 XFMR 800A3P D ISCA=43,759 XFMR Cator Ruma & Associates, Co. 896 Tabor Street Lakewood, CO 80401 303.232.6200 office 303.233.3701 fax www.catorruma.com Low Voltage Rimrock 10807 New Allegiance Drive, Suite 400 Colorado Springs, CO 80921-3796 303-405-4895 office 719-533-1113 fax KEY PLAN ISCA= 4,425 600.4G 225.4G XFMR XFMR 225.4G MEC MEC MEC 600.4G 200.4G 600.4G 800.4G 200.4G D ISCA=21,141 7 ~ CAMPUS MEDIUM-VOLTAGE DISTRIBUTION SYSTEM (BY CONTRACTOR) Structural Engineer/ Civil Engineers Martin / Martin Consulting Engineers PC 12499 West Colfax Avenue Lakewood, CO 80215 303.431.6100 office 303.431.4028 fax www.martinmartin.com MEP Engineers 3 ISCA=22,676 100.4G N G ISCA=22,730 The Baker Group 2220 East Paris Ave SE Grand Rapids, MI 49546 800.968.4011 office www.bakergroup.com Landscape Architect Wenk Associates 1335 Elati Street Denver, CO 80204 303.628.0003 office 303..628.0004 fax www.wenkla.com 6 2 200.4G E G T 112.5 DM T 112.5 PANEL SBL1A 5 ISCA= 22,536 3 ELEV XFMR XFMR ISCA= 4,600 F 3 PANEL SBH1A 200.4G 8 J M PANEL LSH1A 5 ELEV ISCA=18,071 T 15 XFMR SPD ISCA=19,402 ISCA= 5,841 PANEL L1B DM 6 XFMR PANEL LSL1A XFMR ISCA= 17,443 PANEL KDP PANEL LM1 DM 400.4G 6 T 45 XFMR 225.4G ISCA= 17,443 PANEL H1A PANEL HM1 ISCA= 5,882 Contractor GE Johnson 5613 DTC Parkway, Suite 450 Greenwood Village, CO 80111 303.221.1249 office 303.221.1989 fax www.gejohnson.com Architect KSQ Architects PC 910 Santa Fe Drive, Suite 302 Denver, CO 80222 720.457.5570 office www.ksqarchitects.com Food Services PANEL SBL2B XFMR MEC ISCA=4,721 ISCA= 6,177 XFMR ISCA= 1,857 DM 6 ISCA=11,524 T 30 XFMR 9 DM WYOMING COLORADO NEW YORK OKLAHOMA TEXAS M ISCA= 1,450 INSTALL VFDs FURNISHED WITH THE EQUIPMENT. COORDINATE WITH THE MECHANICAL CONTRACTOR AND EQUIPMENT SUPPLIER PRIOR TO COMMENCING ANY WORK. 6 OKLAHOMA J INSTALL LOCAL DISCONNECTING MEANS FURNISHED WITH THE EQUIPMENT. COORDINATE WITH THE MECHANICAL CONTRACTOR AND EQUIPMENT SUPPLIER PRIOR TO COMMENCING ANY WORK. PANEL RP1 Village Center Dining & Community Commons NOTE PRIMARY O.C. PROTECTION PER NEC 450. 2.) 1# XFMR 601.4 1.) FUSE PROVIDE (1)2"C. WITH PULL STRINGS FROM THE PENTHOUSE TO THE MAIN ELECTRIC ROOM FOR FUTURE PHOTOVOLTAIC SYSTEM FEEDER. COORDINATE WITH THE MECHANICAL CONTRACTOR AND EQUIPMENT SUPPLIER. PROVIDE FINAL CONNECTION BETWEEN THE DISCONNECTING MEANS AND VFDs AS NECESSARY. LV PROT (2) 4 PROVIDE PANELBOARD WITH SEPARATE SURGE PROTECTIVE DEVICE (SPD), AS REQUIRED BY THE NEC ARTICLE 700. SPD SHALL NOT BE INTEGRAL TO THE PANELBOARD. PROVIDE AN ALTERNATE MAINTENANCE SETTING SWITCH, PER NEC 240.87. WHEN THE SWITCH IS SET IN THE "MAINTENANCE MODE" AN INDICATOR LIGHT SHALL BE ILLUMINATED AND THE SHORT-TIME DELAY SETTING OF THE MAIN CIRCUIT BREAKER SHALL BE TEMPORILY REDUCED. SWITCH LV PROT (2) 1 7 G 7 CCT BRKR HIGH VOLTAGE FEEDER (3) 4# PROVIDE SURGE PROTECTIVE DEVICE PER CU STANDARDS. PROVIDE PANELBOARD WITH SEPARATE CUSTOMER DEMAND METER. PROVIDE CONNECTION FROM THE DEMAND METER TO THE BUILDING AUTOMATION SYSTEM HEAD-END EQUIPMENT FOR DATA REPORTING. THE DEMAND METER SHALL NOT BE INTEGRAL TO THE PANELBOARD. HV PROT (1) 4# 6.) 5 HV PROT (1) 60.4 G 800.4 G PROVIDE CUSTOMER DEMAND METER. PROVIDE CONNECTION TO THE BUILDING AUTOMATION SYSTEM HEAD-END EQUIPMENT FOR DATA REPORTING. HV FLA SCHEDULE 100.4 G MEC 4 TRANSFORMER FEEDER SCHEDULE University of Colorado Boulder GFI 3 3 3 3 3 SPARE SPARE SPARE SPARE SPARE 2500AF 2500AT 200AF 100AF 600AF 225AF 225AF LSI LSI LSI LSI LSI LSI LSI LSI 225AF LSI LSIG 200AT 100AT XFMR 600AT 225AT 225AT XFMR XFMR 225AT ST LSI ST MEC 100AF 400AF 200AF 400AF 600AF LSI LSI LSI LSI LSI LSI LSI MEC MEC 100AT 400AT 200AT 400AT 600AT 200AF 600AF 200AF 200AT 600AT 200AT N G ISCA=20,917 C MAIN DISTRIBUTION CENTER "MDC" 2500A, 480/277V, 3PH, 4W, 35KAIC 7G GENERATOR DISTRIBUTION BOARD "GDB" 800A, 480/277V, 3PH, 4W, 14KAIC C 2500.4G 3 7G 3 TO MDF/IDF ROOM GROUND BARS (TYP.) ~ 7G ~ TO ELECTRICAL ROOM GROUND BARS (TYP.) UFER BLDG GROUND WATER GROUND STEEL RODS PIPE REVISIONS No. 3 LEVEL 1/1ST FLOOR ELECTRICAL ONE-LINE DIAGRAM B Description CD ADDENDUM 1 Date 10/5/15 B ISSUED DATE CD SET SCALE NTS 8/7/15 SHEET NAME 10/9/2015 10:52:12 AM A A ELECTRICAL ONE-LINE DIAGRAM SHEET NUMBER 15 P:\CU\Boulder\2014-272 Village Center Remodel\Cad\Elec\CUVCDCC_ELEC.rvt KSQ Colorado 14 13 12 11 10 9 8 7 6 5 4 3 2 1 COPYRIGHT © 2015 KSQ ARCHITECTS, PC E-500 FOR CONSTRUCTION SCALE: NONE